Zephyr (ZF) & Cuddy dc
❖
INSTALLATION • OPERATION
Zephyr & Cuddy dc Self-Contained
Cooling Only A/C Kits
Revised: 5-11-07
L-2028
Table of Contents
Zephyr and Cuddy dc Units • Installation
Warning .............................................................................. 4
Notice ................................................................................. 4
Introduction ......................................................................... 4
Cuddy dc ............................................................................ 4
Unpacking and Inspection .................................................. 4
Safety Considerations ........................................................ 4
Placement Of System ......................................................... 5
Spacing Allowances & Unit Dimensions ............................. 5
How It Works ...................................................................... 6
Mounting Brackets .............................................................. 6
Condensate Drains ............................................................. 6
Blower Assembly ................................................................ 6
Supply & Return Air Grills and Transition Boxes ........................................................ 6
Ducting ............................................................................... 7
Manual Control Panel Installation ....................................... 7
Electrical Connections, Grounding & Bonding for AC
Powered Zephyr ............................................................... 7
Electrical Connections, Grounding & Bonding for DC
Powered Cuddy dc .......................................................... 7
Electrical System and Wiring for DC Powered Cuddy dc .... 8
Notice and ABYC Standards: ............................................. 8
Seawater Pump and Plumbing ........................................... 8
Installation Checklist
(review prior to and after installation) ............................... 9
Zephyr and Cuddy dc Units • Operation
Operation .......................................................................... 10
Troubleshooting Guidelines .............................................. 10
Zephyr and Cuddy dc Units • Maintenance
Seawater Strainer ............................................................. 12
Condenser Coil Cleaning ................................................. 12
Return Air Filters ............................................................... 12
Winterization ..................................................................... 12
Zephyr and Cuddy dc Kits • Parts List 12
Owner’s Limited Warranty 15
Limited Warranty Periods
Descriptions of Figures
Cruisair Worldwide Service Dealer Locator
17
18
27
L-2028
3 ❖
English
Zephyr and Cuddy dc Units • Installation
Warning
This manual contains essential safety information concerning the safe and proper installation and operation of Zephyr and
Cuddy dc self-contained direct expansion air conditioners. It is very important that you read and understand the contents of this manual thoroughly before attempting to install any
Cruisair equipment. If there are any statements in this manual that you do not understand, contact the Dometic Environmental Applications Department (Dometic) for assistance. Phone
(804) 746-1313, Fax (804) 746-7248 (8:00am - 5:00pm
United States Eastern Time).
Notice
As of July 1, 1992, United States federal law prohibits the intentional release of refrigerant gases into the environment, including the R-22 refrigerant mostly used in Cruisair air conditioning systems. Special care must be taken when installing, charging and servicing Cruisair equipment to prevent any loss of refrigerant.
Cruisair does not recommend the practice of using refrigerant to purge air and moisture from the system at installation. This formerly used practice of purging is in violation of United
States federal law.
Introduction
You have just purchased the first complete built-in marine air conditioning system designed for self installation. We are confident you will find the added comforts experienced in your boat to be well worth the money spent. If, upon opening your new system, you discover any parts are missing, contact your dealer immediately.
Before attempting to install your new Zephyr (AC powered) or
Cuddy dc (DC powered) air conditioning system, you must read this installation manual completely. Failure to perform certain tasks in the proper sequence could result in an inoperative system as well as a voided warranty.
Cuddy dc
The new Cuddy dc marine air conditioner is very similar to the standard Zephyr but is unique in one way–it is designed to be run on 12VDC battery power. Most of the installation, operation and maintenance information in this manual applies to both types of air conditioners, the AC voltage Zephyr and the DC voltage Cuddy dc. Installation of either unit is nearly identical with the exception of the power supply and how that power is connected to the unit, control and pump. With that in mind while reading this manual, please read the Installation,
Operation, and Maintenance sections titled “Zephyr and
Cuddy dc Units”, and especially the sections subtitled “for DC
L-2028 Installation
4
Powered Cuddy dc”. Cuddy dc owners may skip the sections that are subtitled “for AC Powered Zephyr.”
Cuddy dc kits contain the air conditioning unit and these three components: a Dedicated Power Module (DPM), a 2knob mechanical control, and the water pump. Each of these components is connected to the a/c unit with a polarized plug.
These plugs are configured unique to each component. The
DPM is sized to run the Cuddy dc system only and should not be used for any other appliance(s). See Figure 14 in the back of this manual for DPM specifications
! WARNING The DPM is not ignition protected and must not be installed in the engine compartment or in any area with flammable or compressed gasses or liquids (see the Safety
Considerations section of this manual for more information).
Dometic recommends using a separate battery bank dedicated to run the Cuddy dc . For specific instructions, please see the two sections in this manual titled “Electrical System and Wiring for DC Powered Cuddy dc” and “Electrical Connections, Grounding & Bonding for DC Powered Cuddy dc.”
! WARNING The compressor and fan on the Cuddy dc air conditioning unit are AC voltage components, running on
115VAC supplied by the DPM. The pump and 2-knob mechanical control also run on 115VAC supplied by the DPM.
Once the DPM is connected to the dedicated 12VDC battery bank, then all necessary power distribution to each of the components is handled through the polarized plugs—truly a
“plug & play” system.
Unpacking and Inspection
When the equipment is received, all items should be carefully checked against the packing list to ensure all cartons have been received. Move units in the normal “up” orientation as indicated by the arrows on each carton. Examine cartons for shipping damage, removing the units from the cartons if necessary. If the unit is damaged, the carrier should make the proper notation on the delivery receipt acknowledging the damage.
CAUTION: When unpacking and installing the control, care must be taken not to kink or break the copper cap tube when uncoiling the sensing bulb. The cap tube is hollow and kinking or sharp bends will inhibit system operation.
Safety Considerations
Never install your air conditioner in the bilge or engine room areas. Insure that the selected location is sealed from direct access to bilge and/or engine room vapors. Do not terminate condensate drain line within three (3) feet of any outlet of engine or generator exhaust systems, nor in a compartment
❖
English
housing an engine or generator, nor in a bilge, unless the drain is connected properly to a sealed condensate or shower sump pump. Failure to comply may allow bilge or engine room vapors to mix with the air conditioners return air and contaminate living areas which may result in injury or death.
Consideration should be given to installing a trap in the condensate drain line(s) so that normal discharge of condensate can fill the trap and prevent the ingress of carbon monoxide (CO) or other potentially harmful vapors.
Installation and servicing of this system can be hazardous due to system pressure and electrical components. When working on this equipment, always observe precautions described in the literature, tags and labels attached to the unit.
Follow all safety codes. Wear safety glasses and work gloves and place a fire extinguisher close to the work area. The following is a summary of the labels on the unit:
! DANGER Electrical shock hazard. Disconnect voltage at main panel or power source before opening any cover. Failure to comply may result in injury or death.
! WARNING This component does not meet Federal requirements for ignition protection. Do not install in spaces containing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line fittings. Failure to comply may result in injury or death.
NOTICE This component is charged with hydrochlorofluorocarbon (HCFC) refrigerant R22. Effective July 1, 1992 it shall be unlawful for any person to knowingly vent or otherwise knowingly release any class 1 (CFC) or class 2 (HCFC) substance as a refrigerant in a manner which permits such substance to enter the atmosphere per the clean air act of
1990. Public law 101-549 Title IV Section 608-c. Failure to comply may result in severe penalties, including fines and imprisonment. Note: The Cuddy dc unit is charged with
R417A.
! WARNING To minimize the hazard of electrical shock and personal injury, this component must be effectively grounded.
Refer to the installation guidelines for further information.
! WARNING The compressor and fan on the Cuddy dc air conditioning unit are AC voltage components, running on
115VAC supplied by the DPM. The pump and 2-knob mechanical control also run on 115VAC supplied by the DPM.
Disconnect voltage at main panel or power source before opening any cover. Failure to comply may result in injury or death.
Placement Of System
Selecting a good location for your air conditioner is the most important part of your preparations. Be sure to consider the size of the area you are cooling, the air distribution needs, and the size of the unit you have chosen. Keeping in mind that cool air has a tendency to fall, it is highly recommended that
L-2028 Installation
5 you locate the supply air grill as high as possible in the cabin.
Figure 1a at the back of this manual shows the single duct application and Figure 1b shows a dual duct application.
The air conditioning unit should be installed as low as possible, but never in the bilge or engine room areas.
Insure that the selected location is sealed from direct access to bilge and/or engine room vapors . Installing the unit as low as possible (such as under a V-berth, dinette seat or bottom of a locker) and ducting the supply air as high as possible, creates an ideal air flow condition. This type of installation will prevent short or premature cycling.
The unit should be positioned on a firm, level, horizontal surface and the condensate drain line should run downward from the unit to a suitable drain location. Plan all connections which must be made including ducting, condensate drain, seawater in and out, electrical power connections, location of control, and seawater pump placement, to assure easy access for routing and servicing.
Tools Required for Installation
• Screw drivers
• Pliers
• Pipe wrench
• Wire cutters/crimpers
• Drill & 7/8" bit
• Jig saw
• Duct tape
• Electrical tape
• Teflon tape
• Bedding compound to seal thru hull fittings
• Hardware to secure unit, pump, strainer, grills & control panel
Spacing Allowances & Unit Dimensions
The following space allowances should be considered when mounting the unit:
1. Allow a minimum of 6" (152mm) around the perimeter of the unit in the area of the seawater and condensate drain piping.
2. Allow a minimum of 3" (76mm) of air space in front of the evaporator coil for the return air intake if it is adjacent to a bulkhead.
3. Allow a minimum of 3" (76mm) of air space for the electric blower motor ventilation. For Cuddy dc systems, allow at least 1" (25mm) above DPM for adequate ventilation.
4. For flexible ducting connection, allow 2" (51mm) for the duct ring, 1" (25mm) for the duct bend radius and add diameter of the ducting to get the total clearance distance
(2" [51mm] + 1" [25mm] + duct diameter) as measured from the blower outlet (this also applies to clearance needed behind the supply air grill). Note that the blower and duct ring can be positioned either vertically or horizontally. See Figure 2 at the back of this manual.
❖
English
These space allowances are suggested minimums. Enough space should be allocated for installation and serviceability.
See Figure 2 at the back of this manual for space allowances and unit dimensions.
How It Works
The air conditioning unit consists of four main components and a refrigerant gas circulating through the system. The
BLOWER draws warm cabin air across the fins on the
EVAPORATOR where the heat from the air is transferred to the refrigerant in the evaporator coil. As the refrigerant evaporates from a liquid into a gas it absorbs the heat from the cabin air. The COMPRESSOR then compresses the refrigerant gas and pumps it through the outer tube in the
CONDENSER COIL. The seawater pump circulates cool seawater through the inner tube in the condenser coil, this cools the refrigerant in the outer tube and condenses it from a gas into a liquid. The heat from the refrigerant is exchanged to the seawater and discharged overboard. The liquid refrigerant is then passed through the EVAPORATOR COIL and the cycle repeats. Removing heat from the cabin air lowers its temperature. The cooled air is blown through the ducting and out the supply air grill(s). See Figure 3 at the back of this manual for component identification.
Mounting Brackets
The air conditioning unit is supplied with a base pan that also serves as a condensate pan. Mounting clip brackets and screws (4) are provided to secure the base pan onto a flat, horizontal surface. See Figure 4 at the back of this manual.
Condensate Drains
The condensate drain pan is 1¾" high with two drain locations. During conditions of high humidity, condensate may be produced at a rate of approximately ½ gallon (1.9 liters) per hour. With this in mind, it is important to route condensate drains downward to a sump pump. It is not recommended to route condensate drains to the bilge. After the condensate drain installation is complete, test the installation by pouring a quart of water into the pan and checking for good flow.
For installation of the condensate drain (refer to Figure 5 at the back of this manual):
1. Remove the aft facing watertight plug from the base pan of the air conditioning unit.
2. Slip the solid washer and the liquid-seal washer onto the
PVC fitting in that order.
3. Connect the fitting through the exposed hole in the base pan with the locking nut.
4. Securely tighten with two (2) wrenches to provide a proper seal.
5. Attach a 5/8" (16mm) I.D. reinforced hose to the hose barb and secure with stainless steel hose clamps.
L-2028 Installation
6
6. Install the condensate drain hose downhill from the unit and aft to a sump - hose should have a trap.
7. Two drain fittings may be used and the hoses teed together provided there is a minimum 2" (51mm) drop from the bottom of the base pan to the tee connection.
Note:
Do not terminate condensate drain line within 3 feet (91cm) of any outlet of engine or generator exhaust systems, nor in a compartment housing an engine or generator, nor in a bilge, unless the drain is connected properly to a sealed condensate or shower sump pump.
Blower Assembly
Horizontal or vertical supply air discharge may be acheived by rotating the blower. Its design allows the blower to be rotated by removing the screws holding the blower plate to the evaporator coil shroud. Rotate the blower to allow the most direct flow of air to the supply air grill. To rotate the 10-16K blowers, remove the two plastic plugs for access to the mounting screws.
Supply & Return Air Grills and Transition Boxes
As previously indicated, install the supply air grille(s) as high as possible and the return air grille as low and close to the air conditioning unit as possible to insure direct uninterrupted airflow to the evaporator. In no instance should the supply are grille discharge be directed towards the return air grille, as this will cause the system to short cycle.
The cut out for the 3" (76mm) round supply air grille for the
3.5K unit is 3" (76mm) in diameter and the flange is 3 7 /
8
"
(99mm) in diameter. The cut out for the 4" (102mm) round supply air grille for the 5K unit is 4" (102mm) in diameter and the flange is 5½" (140mm) in diameter. The cut out for the rectangular supply air transition box used with the 10 & 12K units is 11 5 /
8 it is 13 5 /
8
" (295mm) by 5 5 /
8
" (346mm) by 5 5 /
8
" (148 mm) and for the 16K unit
" (148 mm). Connect the 6"
(152mm) or 7" (178mm) oblong duct ring to the transition box by first placing the ring on the box and tracing the hole. Cut the oblong hole out of the box. Secure the ring to the box with rivets (trim ¼" [6mm] from ring flanges if necessary). Completely seal the joint between ring and box with silicone. A minimum clearance of 3" (76mm) plus the duct diameter size is required behind the grille for attaching the ducting (see earlier section, “ Spacing Allowance and Unit Dimensions”).
The cut outs for the return air grilles are as follows: 7-5/8"
(194mm) square for the 3.5K & 5K units, 11-5/8" (295mm) square for the 10K & 12K units, and 13-5/8" (346mm) x 11-5/
8" (295mm) (width x height) for the 16K unit. The return air grille should have a minimum of 4" (107mm) of clearance in front of it, free from any furniture or other obstructions. The return air filter, mounted to the front of the evaporator,
❖
English
removes debris from the air prior to the air being drawn across the evaporator coil and fins. Dust and lint can clog and reduce airflow across the evaporator coil resulting in poor performance. See the “ Maintenance” section for filter cleaning instructions.
Ducting
Good airflow is critical for the performance of the entire system. It is highly dependent on the quality of the ducting installation. The ducting should be run as straight, smooth and taut as possible minimizing the number of 90 degree bends
(two tight 90 degree bends can reduce airflow by 25 percent).
The following is a summary of proper ducting connections:
1. Pull back the fiberglass insulation exposing the inner mylar duct hose.
2. Slide the mylar duct hose around the mount ring until it bottoms out.
3. Screw 3 or 4 stainless steel sheet metal screws through the duct hose into the transition ring. Make sure to catch the wire in the duct hose with the heads of the screws. Do not use band clamps, as the hose will slide off.
4. Wrap duct tape around the ducting and ring joint to prevent any air leaks.
5. Pull the insulation back up over the mylar to the ring and tape this joint.
6. Remove excess ducting and use the same connection method at the supply air grill.
Manual Control Panel Installation
The manual control panel should be located within cap tube length of the air conditioning unit. The dimensions for the
2-knob panel is 3¼" (83mm) x 5½" (140mm). The cut out size for the 2-knob panel is 2½" (64mm) wide by 4¾" (121mm) tall.
The 3-knob panel is configured either vertically or horizontally.
Dimensions for the 3-knob is 2 15 /
16
" (75mm) x 7 15 /
16
" (202mm).
The cut out size for the 3-knob panel is 2" (51mm) by
6¾"(171mm). (Refer to Figures 6 and 7 at the back of this manual.) Once the cut out is made, carefully uncoil the copper cap tube with return air sensor (copper bulb) and route the control wires and cap tube through the hole and back to the unit using caution not to kink the cap tube. Mount the return air sensor into the clips provided on the evaporator coil.
If the return air sensor cannot be mounted on the evaporator coil, mount it behind the return air grill. The sensor must be mounted in the return air stream. Make electrical connections according to the wiring diagrams provided. (See wiring diagrams, Figures 8, 9, 10 and 11 at the back of this manual.)
Electrical Connections, Grounding & Bonding for AC Powered Zephyr
All Zephyr units have a five position terminal strip mounted inside the electric box. The terminal strip is labeled for proper connections of the electrical supply, ground wires and pump
L-2028 Installation circuits. Wiring diagrams are provided in the electrical box and in this manual. The correct size circuit breaker should be used to protect the system as specified on the air conditioning unit’s data plate label. A minimum of 12 AWG boat cable should be used to supply power to the air conditioning unit and to the seawater pump (see next paragraph). All connections to the terminal strip shall be made with ring terminals supplied with the Zephyr kit. Turn off AC (alternating current) power supply circuit breaker before opening electrical box and accessing the terminal strip.
Each air conditioning unit installed requires its own dedicated circuit breaker. If there is only one air conditioning unit installed, the seawater pump does not require a circuit breaker; the wiring from the seawater pump is connected to the terminal strip on the unit. (See wiring diagrams, Figures 8,
9 and 10 at the back of this manual.) A minimum of 12 AWG boat cable should be used to extend the wires on the pump, if necessary, using the butt slices included with the kit. If two or more air conditioning units use the same seawater pump, the pump wires will be connected to a pump relay panel (PRP) which in turn has its own dedicated circuit breaker (see the wiring diagram furnished with the PRP). Any electrical connections in the bilge below the waterline should use heat shrink type butt splices.
The air conditioning unit must be connected to the boat’s bonding system to prevent corrosion due to stray electrical current. All pumps, metallic valves and fittings in the seawater circuit that are isolated from the air conditioning unit by PVC or rubber hoses must be individually bonded to the boat’s bonding system also. This will help eliminate any possibility of corrosion due to stray current.
Note: Failure to properly ground and bond the system will void the warranty!
7
Electrical Connections, Grounding & Bonding for DC Powered Cuddy dc
All Cuddy dc units are connected by polarized plugs to the
Dedicated Power Module DPM, pump, and control (available separately or in kit). These plugs are configured unique to each component. Wiring diagrams and schematics are provided in this manual (see Figure 11 at the back of this manual). A 60 amp circuit breaker or fuse should be installed at the positive side of the battery to protect the wires. Any electrical connections in the bilge below the waterline should be heat shrink type.
Turn off DC power supply circuit breaker before making connections.
The air conditioning unit and its components must be connected to the boat’s bonding system to prevent corrosion due to stray electrical current. There is a bonding ground stud on the Dedicated Power Module. This stud must be connected to the vessel’s bonding stud, which is typically on the engine
❖
English
block. This connection must be made per ABYC specifications. All pumps, metallic valves and fittings in the seawater circuit that are isolated from the air conditioning unit by PVC or rubber hoses must be individually bonded to the boat’s bonding system also. This will help eliminate any possibility of corrosion due to stray current.
Note: Failure to properly ground and bond the system will void the warranty!
board, per ABYC E-9. Use a 60 amp breaker for 12 VDC systems. This provides protection from possible short circuits.
When dockside, the Cuddy dc unit can operate against the batteries while using the AC battery charger (50 amp min) as a backup (most marine battery chargers will shut off when the battery is fully charged).
Ensure that all DC electrical connections are made in compliance with American Boat and Yacht Council (ABYC) standards section E-9.
Electrical System and Wiring for DC Powered
Cuddy dc
Dometic recommends a separate set of batteries dedicated for the Cuddy dc air conditioning system. Deep cycle AGM or
Gel Cell batteries are the best for this application. If need be, please contact your Dometic dealer for assistance in sizing batteries.
The Cuddy dc kit contains the Dedicated Power Module
(DPM). The DPM is meant to be used for the Cuddy dc system only and is sized to do so (see Figure 14 at the back of this manual for DPM specifications).
When connecting the DPM to the batteries, maintain correct wire size as shown in the DC Wire Sizing Table (see Figure 15 at the back of this manual), keep wire runs as short as possible, and with as few intermediate connections as possible, to avoid unnecessary resistance or voltage drop.
See wiring diagram Figure 11 for location of customerinstalled 60 amp fuse. Use an ignition protected fuse holder if installed in the engine compartment or in any area with flammable or compressed gasses or liquids (see the Safety
Considerations section of this manual for more information). A standard ABYC approved battery disconnect switch is also recommended and should be used any time the system needs servicing. Do not forget to maintain proper color coding, (red = positive, black = negative) to aid in future electrical troubleshooting. If the wires are incorrectly connected (positive and negative reversed), the air conditioning unit will not start and the DPM will be damaged.
The DPM is wired to the FAN setting on the two-knob switch assembly and is energized only when the Cuddy dc is running (see the Operation section of this manual). For DC wire sizing, see Figure 15 at the back of this manual.
As batteries age, their peak voltage lowers and they discharge quicker. This, of course, can affect the air conditioner performance as well as other DC devices. The battery condition should be maintained and monitored regularly and weak batteries should be replaced. A battery isolator, combiner or selector switch will allow simultaneous charging while preventing the discharge of a fully charged battery into a depleted one.
Over current protection, in addition to fuse provided, must be supplied for the ungrounded conductor at the main switch-
L-2028 Installation
Notice and ABYC Standards:
Field wiring must comply with ABYC electrical standards.
Power to the unit must be within the operating voltage range indicated on the data plate. Properly sized fuses and circuit breakers must be installed for branch circuit protection. See equipment rating plate for maximum size. All air conditioning units must be effectively grounded to minimize the hazard of electric shock and personal injury. The following standards apply:
1. AC (alternating current) grounding (green) wire must be provided with the AC power conductors and connected to the ground terminal (marked “GRND”) at the AC power input terminal block of the unit(s), per ABYC standard E-8.
2. Connections between the vessel’s AC system grounding conductor (green wire) and the vessel’s DC (Direct
Current) negative or bonding system should be made as part of the vessel’s wiring, per ABYC standard E-9.
3. When servicing or replacing existing equipment containing a chassis-mounted “ground” stud, the service person or installer must check the vessel’s wiring for the existence of the connection required in item 2 above.
ABYC standards are available from:
American Boat and Yacht Council
613 Third Street, Suite 10
Annapolis, MD 21403
Phone: (410) 990-4460, Fax: (410) 990-4466
8
Seawater Pump and Plumbing
Several guidelines should be followed during the installation of the seawater system. Since the circulation pump is centrifugal and not self-priming, it must be mounted so that it is always at least one foot below the water line regardless of which tack the vessel is on. Pump may be mounted horizontally or vertically, however the discharge must always be above the inlet. Pump head should be rotated toward the direction of water flow. Install the seawater speed scoop intake as far below the water line and as close to the keel as possible in any application, but especially on a sailboat, to keep the intake in the water when the boat heels over so that air does not get into the system. The speed scoop intake must face forward and not be shared with any other pump. A seawater strainer is mandatory between
❖
English
the shut off valve (seacock) and the pump to protect the pump from any foreign matter. Failure to install a seawater strainer will void the pump warranty . The seawater system should be installed with an upward incline from the speed scoop & seacock, through the strainer, to the inlet of the pump and then up to the inlet of the air conditioning unit’s condenser coil. The discharge from the air conditioning unit should then run to the seawater outlet thru-hull fitting which should be located where it can be visually checked for water flow and as close as practicable to the waterline to reduce noise. All hose connections shall be secured by means of double/reversed stainless steel hose clamps. Use teflon tape on all threaded connections. The following is a summary of the seawater system installation:
1. Install the speed scoop thru-hull inlet as close to the keel and as far below the water line as possible, facing forward.
Bed the scoop with a marine sealant designed for underwater use.
2. Install a bronze, full flow seacock on the speed scoop thru-hull inlet.
3. Install a seawater strainer below the level of the pump with access to filter.
4. Mount the pump above the strainer and at least one foot below the waterline.
5. Connect the seacock and strainer with an uphill run of
5/8" reinforced marine grade hose.
6. Connect the discharge from the pump uphill to the bottom inlet of the air conditioning unit’s condenser coil with 5/8" reinforced marine grade hose. Connect the discharge from the condenser coil to the overboard discharge thruhull fitting with 5/8" reinforced marine grade hose.
7. Avoid loops, high spots or the use of 90° elbows with seawater hose (each 90° elbow is equivalent in pressure drop to 2.5' of hose and a 90° elbow on the pump outlet is equivalent to 20' of hose).
8. Double clamp all hose connections with stainless steel clamps, reversing the clamps.
9. Use teflon tape on all threaded connections.
10.
Connect all metallic parts in contact with seawater to the vessel’s bonding system including the speed scoop inlet, strainer, pump and the air conditioner .
Refer to Figure 12, 13a , and 13b at the back of this manual for seawater kit installation drawings.
Installation Checklist
(review prior to and after installation)
Seawater cooling system
• Speed scoop located as far below the water line and as close to the keel as possible
• Shut off valve and speed scoop properly sealed and tight
• Seawater pump at least one foot below water line and securely mounted
• Strainer mounted below pump with access to filter
• Double/reversed stainless steel hose clamps on all hose connections
• Teflon tape on all threaded connections
• Hose runs uphill from speed scoop to strainer, pump and air conditioning unit
• Water flowing freely from overboard discharge while pump is running
Air Conditioner Unit Mounting
• Not in engine room or bilge areas, must be sealed away from exhaust or fumes
• Proper spacing allowed around unit
• Attached to solid level platform with four hold down clips provided
• Condensate drain routed aft and down hill to a sealed sump
(not bilge), and should have a trap
Grills and Ducting
• Supply air grill mounted as high as possible
• Return air grill mounted as low and as close to the unit as possible
• Return air grill mounted away from exhaust and bilge vapors
• Ducting is pulled taut, straight and properly connected with no excess
Electrical for AC Powered Zephyr
• All butt connections on pump wire tightly crimped and heat shrunk
• AC power source installed and grounded/bonded in accordance with ABYC standards
• Control wires connected to terminal strip with ring terminals
Electrical for DC Powered Cuddy dc
• All polarized plugs connected securely with an audible
“snap”
• DC power source installed and grounded/bonded inaccordance with ABYC standards
• Bonding ground stud on Dedicated Power Module connected to vessel’s bonding system per ABYC
L-2028 Installation
9 ❖
English
Zephyr and Cuddy dc Units • Operation
Operation
Manual Control Panel Operation:
2-knob (2KB), 3.5-5K units; 3-knob (3KB), 10, 12, 16K units, see figures 6 & 7.
1. Ensure seawater intake ball valve (seacock) is open.
2. Turn top (MODE) control knob to OFF.
3. Turn on air conditioning unit circuit breaker. If the seawater pump has its own circuit breaker, turn that on too.
4. Turn top (MODE) control knob to FAN, this energizes the fan (and the DPM in Cuddy dc systems).
5. Turn THERMOSTAT control knob to the coolest position by rotating it fully clockwise.
6. Turn middle (FAN) control knob to highest setting
(for 3KB switch only).
7. Verify that the fan is running and that there is steady airflow out of the supply air grill.
8. Turn top (MODE) control knob to RUN (for 2KB switch) and ON (for 3KB switch). This will start the compressor and seawater pump.
9. Check for a steady solid stream of seawater from the overboard discharge.
10. To set the THERMOSTAT, allow sufficient time for the unit to cool the area to the desired temperature. When the area is sufficiently cooled, turn the thermostat knob slowly toward the center position until it clicks once. The thermostat is now set to maintain a constant temperature.
Important
Do not turn the unit off and immediately turn it back on. Wait at least 30 seconds (2 minutes for the Cuddy dc) for system refrigerant pressures to balance.
Troubleshooting Guidelines
Before you call for service, review this list. It may save you time and expense. This list contains common occurrences that are not a result of defective workmanship or materials. If you need service after trying these procedures, call your nearest Cruisair dealer.
Problem: System will not start.
Possible Reason/Solution
1.
Air conditioner circuit breaker is off.
Turn circuit breaker on at ship’s panel.
2.
Wiring at terminal strip is miswired (VAC unit only).
Check wiring diagram; correct if necessary.
3.
Input line voltage is insufficient (VAC unit only). Check power source for proper voltage. Check wiring and terminals for proper sizes and connections.
L-2028 Operation
10
4.
Cuddy dc plugs are not connected tightly (DC unit only). Check polarized plugs from unit to pump, power module, and control. There should be an audible “snap” when plugs go together.
5.
Batteries are not fully charged (DC unit only).
Turn
Cuddy dc unit off and charge battery bank.
6.
DC power wires are incorrectly sized (DC unit only).
See the “Electrical System and Wiring for DC Powered
Cuddy dc” section of this manual. Ensure that DC power wires are sized and connected correctly.
7.
Dedicated Power Module (DPM) is in lockout mode
(DC unit only).
The DPM has a protective overload lockout feature that will cause it to shutdown in case of a problem. When this occurs, turn Cuddy dc off and wait 2 minutes before turning back on. If that does not solve the problem, then continue reading: a) If DPM has overheated ( ≥ 167°F [75°C]) then ensure that it has at least one inch of air space above unit for, and is in an area that provides, proper ventilation.
b) If compressor has overheated then check water pump, strainer and hoses. When operating properly, there should be a steady stream of water from the overboard discharge. Strainer may need cleaning. Ensure that hoses are not kinked or restricted in some other way. Pump should come on with the compressor when control is set to RUN.
c) If refrigerant pressure is too high, then turning the system off for 2 minutes should correct that by allowing pressure to equalize. Note: Turning the Cuddy dc on and off too quickly may cause a high-pressure shutdown. During normal operation wait at least 2 minutes from the time control is turned off until it is turned back on.
d) If DC voltage is too high (>16-17VDC) or too low
(<10.5VDC), then check battery bank for correct charge.
Charge batteries if need be. Note: Turn Cuddy dc off and charge batteries for 5 minutes. Try turning Cuddy dc on again. If it runs, then that is a good indicator the batteries were low. Fully charge batteries at this time.
e) If there is a dead short in the wiring, then disconnect power supply and repair wiring.
If, after trying all of the above, the fan runs, but the compress and pump do not, then that is a good indicator there is a problem with the compressor and/or pump.
Whereas, if the fan does not come on at this time, then that is a good indicator there is a problem with the fan or the DPM. Either way, call for a service technician – please see listing in back of this manual.
❖
English
Problem: No cooling.
Possible Reason/Solution
1.
Selector knob may not be in “cool” position . Reset selector knob.
2.
Temperature set point is above ambient temperature .
Lower temperature setting.
3.
Obstructed water flow . Clean seawater strainer. Check for good steady flow from overboard discharge.
4.
Pump may be air locked . Remove hose from pump discharge to purge air from line.
5.
Coil iced . See below.
Problem: Coil iced.
Possible Reason/Solution
1.
Thermostat set point is too low . Check setting on temperature knob. If setting is extreme for conditions, raise set point.
2.
Improper air flow . Clean return air filter or remove obstructions from return air stream. Check for crushed or restricted ducting. Ducting run must be as straight as possible; remove any excess ducting.
Problem: Short cycling compressor.
Possible Reason/Solution
1.
Cold supply air returning directly to return air grill .
Redirect supply air so that it is not directed into the return air stream.
Problem: System runs continuously.
Possible Reason/Solution
1.
Port hole or hatch open . Close all port holes and hatches.
2.
Thermostat setting is excessive for conditions . Raise thermostat setting to cycle compressor.
L-2028 Operation
11 ❖
English
Zephyr and Cuddy dc Units • Maintenance
Seawater Strainer
Ensure that the pump receives adequate seawater flow by regularly cleaning the strainer basket. Periodically check the overboard discharge for a steady stream of water. Check seawater intake speed scoop for obstructions. Make sure hoses are not looped, kinked or crushed.
Condenser Coil Cleaning
Coils can become fouled over a period of time due to marine growth or scale build-up. This both obstructs water flow and prohibits proper heat transfer. To clean coils, flush with a 5% muriatic or hydrochloric acid and fresh water solution.
Disconnect system hoses from coil and pump the solution through until clean. Rinse with fresh water and reconnect hoses. Follow manufacturer’s safety guidelines for all cleaning solutions.
Return Air Filters
Check the return air filter about once a month and clean as necessary. To clean the filter, remove it from the unit, rinse with water, air dry and reinstall.
Winterization
There are several methods of winterization, some of which work better than others. The four various methods employed using a 50/50 non-polluting biodegradable anti-freeze/water solution are:
1. Pumping of anti-freeze solution into the overboard thruhull fitting, and discharging through the intake thru-hull fitting.
2. Use of the seawater pump to pump anti-freeze solution through the system and discharging through the overboard thru-hull fitting. Close seacock, remove hose from strainer discharge, raise hose above pump (so pump does not lose its prime) and pour in anti-freeze solution.
Pump solution through system. The strainer and hose to seacock will also need to be drained of water.
3. Use of pressurized air injected at the overboard discharge fitting and the water being discharged through the seawater intake fitting.
4. Use of pressurized air to force water from the intake through the overboard discharge.
Note:
Collect all discharged liquids and recycle or dispose of in a proper manner.
Any method that causes the anti-freeze solution to flow downward is the method of choice. By this means, the antifreeze solution will displace any water trapped and eliminate the possibility of freezing in hidden areas.
In addition, since the seawater pump utilizes a magnetically driven impeller, the impeller should be removed from the wet end assembly, wiped with an alcohol solution, and stored in a warm, dry area until commissioning takes place.
L-2028 Maintenance
12 ❖
English
Zephyr and Cuddy dc Kits • Parts List
Cuddy dc Kits
CD3.5HV 12VDC
Condensate hose barb assembly with 4 mounting brackets included with
P/N
222-110094
222-110110
225-410108
-OR-
225-410112
Qty
1
1
1
1 unit.
Description
DPM Dedicated Power Module 12V with
MX-Plug
MCP 2-KB CDH V BL MYL 12V 150L 2-Knob
Control
Pump PML150 with MX150L-Plug 115V no fittings
-OR- (kit has one pump, PML150 or PML250)
Pump PML250 with MX150L-Plug 115V no fittings
Extension Cables with Plugs for
Cuddy dc Systems
222-120200 1 3m (9.8') Cable with Plugs from Cuddy dc to
DPM
222-120201 1
222-120202 1
6m (19.7') Cable with Plugs from Cuddy dc to
DPM
3m (9.8') Cable with Plugs for Cuddy dc to
Pump
Zephyr ZF3.5 Kits
ZF3.5 115V
Condensate hose barb assembly with 4 mounting brackets included with unit.
P/N Qty Description
222-110087
225-500226
1
1
ZFSA1-XB 2-Knob Control dual voltage
Pump PML250 115V no fittings
Air Distribution Kits
Kits (sold separately) are for use with Cuddy dc or Zephyr 3.5K units only:
226-000301 Kit Air Distribution Kit - Black (includes next 3 items)
333437
217-000773
1
1
226-600045 10'
3" Round Plastic Supply Air Grill, Euro, Black
8x8TRAF Alum Return Air Grill w/Filter, Black
3" Ducting, Insulated Flexible
226-000300 Kit
333439
217-000728
1
1
226-600045 10'
Air Distribution Kit - White (includes next 3 items)
3" Round Plastic Supply Air Grill, Euro, White
8x8 RAF Alum Return Air Grill w/Filter, White
3" Ducting, Insulated Flexible
Zephyr ZF5 Kits
ZF5 115V, or ZF5CK 220V/50Hz
Condensate hose barb assembly with 4 mounting brackets included with unit.
P/N
226-600014
Qty
5'
Description
4" Ducting, Insulated Flexible
330571
332743
222-110087
334220
1
1
1
1
Grill, Circular Off White
Grill, 8x8TRA Anodized
ZFSA1-XB 2-Knob Control dual voltage
Thru Hull, 5/8" Plastic
226-600006 25'
335360 1
335120
335080
3
2
1 225-600021
332822
-OR-
332831
1
369617
330482
369699
338439
336750
17
1
1
3
6
Hose, Seawater 5/8"
Bush, PVC Red 1/2" MPT x 1/4" FPT
Adapt, PVC 1/2" MPT x 1/2" HB
Adapt, PVC 1/2" FPT x 1/2" HB
Strainer (w/ Bracket 1/2" FPT)
PDS-250 115V Seawater Pump
-OR- (kit has one pump, 115V or 220V)
PDS-250C 220V Seawater Pump
Clamp, Hose #06SS Thin
Ball Valve 1/2" SS Hndl (Bronze)
Strainer, Speed Scoop 1/2" Bronze
Terminal Butt Splice 16-14 Blue
Terminal Ring 10-12 Yellow
Zephyr ZF10 Kits
ZF10 115V, or ZF10CK 220V/50Hz
Condensate hose barb assembly with 4 mounting brackets included with unit.
P/N Qty Description
226-600015 10'
229-800025 1
228-700017
217-300131
1
1
1 217-300125
222-110088
-OR-
222-110093
1
334220 1
226-600006 25'
335360
335120
1
3
335080
225-600021
332822
-OR-
2
1
1
332831
369617
330482
369699
338439
336750
17
1
1
3
6
6" Ducting, Insulated Flexible
Transition Box ABS 12x6x4.5
6" ABS Oblong Transition Ring
12x6TV Alum Supply Air Grill
12x12TRA Alum Return Air Grill
ZFSA1-ZB 115V 3-Knob Mech. Control
-OR- (kit has one control, 115V or 220V)
ZFSA1-ZCB 220V 3-Knob Mech. Control
Thru Hull, 5/8" Plastic
Hose, Seawater 5/8"
Bush, PVC Red 1/2" MPT x 1/4" FPT
Adapt, PVC 1/2" MPT x 1/2" HB
Adapt, PVC 1/2" FPT x 1/2" HB
Strainer (w/ Bracket 1/2" FPT)
PDS-250 115V Seawater Pump
-OR- (kit has one pump, 115V or 220V)
PDS-250C 220V Seawater Pump
Clamp, Hose #06SS Thin
Ball Valve 1/2" SS Hndl (Bronze)
Strainer, Speed Scoop 1/2" Bronze
Terminal Butt Splice 16-14 Blue
Terminal Ring 10-12 Yellow
Optional Dual Duct Kit
226-600014 10'
229-000029 1
339284 1
4" Ducting Insulated Flexible
Plenum Tee Box, 6", 6", 4"
4" Plastic Grill, White
L-2028
13 ❖
English
Zephyr ZF12 Kits
ZF12 115V, or ZF12CK 220V/50Hz
Condensate hose barb assembly with 4 mounting brackets included with unit.
P/N Qty
226-600015 10'
Description
6" Ducting, Insulated Flexible
229-800025
228-700017
217-300131
217-300125
1
1
1
1
Transition Box ABS 12x6x4.5
6" ABS Oblong Transition Ring
12x6TV Alum Supply Air Grill
12x12TRA Alum Return Air Grill
222-110088
-OR-
222-110093
334220
335360
335120
335080
225-600021
1
1
226-600006 25'
1
3
2
1
ZFSA1-ZB 115V 3-Knob Mech. Control
-OR- (kit has one control, 115V or 220V)
ZFSA1-ZCB 220V 3-Knob Mech. Control
Thru Hull, 5/8" Plastic
Hose, Seawater 5/8"
Bush, PVC Red 1/2" MPT x 1/4" FPT
Adapt, PVC 1/2" MPT x 1/2" HB
Adapt, PVC 1/2" FPT x 1/2" HB
332822
-OR-
332831
369617
330482
369699
338439
336750
1
17
1
1
3
6
Strainer (w/ Bracket 1/2" FPT)
PDS-250 115V Seawater Pump
-OR- (kit has one pump, 115V or 220V)
PDS-250C 220V Seawater Pump
Clamp, Hose #06SS Thin
Ball Valve 1/2" SS Hndl (Bronze)
Strainer, Speed Scoop 1/2" Bronze
Terminal Butt Splice 16-14 Blue
Terminal Ring 10-12 Yellow
Optional Dual Duct Kit
226-600014 10'
229-000029
339284
1
1
4" Ducting Insulated Flexible
Plenum Tee Box, 6", 6", 4"
4" Plastic Grill, White
Zephyr ZF16 Kits
ZF16 115V, or ZF16CK 220V/50Hz
Condensate hose barb assembly with 4 mounting brackets included with unit.
P/N Qty
226-600000 10'
Description
7" Ducting, Insulated Flexible
229-800026
228-700019
217-300134
217-000221
1
1
1
1
Transition Box ABS14x6x4.5
7" ABS Oblong Transition Ring
14x6TV Alum Supply Air Grill
14x12TRA Alum Return Air Grill
222-110088
-OR-
222-110093
334220
226-600006 25'
335120
335080
225-600021
300823
332724
332823
-OR-
332824
369617
330482
369699
338439
336750
1
1
3
2
1
1
1
1
17
1
1
3
6
ZFSA1-ZB 115V 3-Knob Mech. Control
-OR- (kit has one control, 115V or 220V)
ZFSA1-ZCB 220V 3-Knob Mech. Control
Thru Hull, 5/8" Plastic
Hose, Seawater 5/8"
Adapt, PVC 1/2" MPT x 1/2" HB
Adapt, PVC 1/2" FPT x 1/2" HB
Strainer (w/ Bracket 1/2" FPT)
Adapt, PVC 3/4" MPT x 1/2" HB
Coupling, PVC 3/4" FPT x 3/4" FPT
PDS-500 115V Seawater Pump
-OR- (kit has one pump, 115V or 220V)
PDS-500C 220V Seawater Pump
Clamp, Hose #06SS Thin
Ball Valve 1/2" SS Hndl (Bronze)
Strainer, Speed Scoop 1/2" Bronze
Terminal Butt Splice 16-14 Blue
Terminal Ring 10-12 Yellow
Optional Dual Duct Kit
226-600014 10'
229-800428
339284
1
1
4" Ducting Insulated Flexible
Plenum Tee Box, 7", 7", 4"
4" Plastic Grill, White
L-2028
14 ❖
English
Owner’s Limited Warranty
As hereinafter described, Dometic Environmental Corporation limits the duration of any implied warranty to the duration of the underlying express warranty and also disclaims any liability for consequential or incidental damages arising from any application, installation, use or malfunction of any warranted product.
Section I
What does the Limited Warranty cover?
Products manufactured by Dometic Environmental Corporation (Dometic) are under limited warranty to be free from defects in workmanship or materials under normal use and service with the obligation of Dometic under this limited warranty being limited to replacing or repairing any component(s) which shall disclose defects within the time limits defined in Section III and which, upon examination by
Dometic, shall appear to the satisfaction of Dometic to be defective or not up to specifications.
This Limited Warranty is made in lieu of all other express warranties, obligations, or liabilities on the part of
Dometic. In addition, Dometic shall not be responsible for any incidental or consequential damages. In those instances in which a cash refund is made, such refund shall effect the cancellation of the contract of sale without reservation of rights on the part of the purchaser. Such refund shall constitute full and final satisfaction of all claims which purchaser has or may have against Dometic due to any actual or alleged breach of warranty, either express or implied, including, without limitation, any implied warranty of merchantability or fitness for a particular purpose. Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation may not apply to you. The terms and conditions of this warranty shall be governed by the laws of the Commonwealth of Virginia.
The Dealer is not an agent for Dometic except for the purpose of administering the above warranty to the extent herein provided, and Dometic does not authorize the dealer or any other person to assume for Dometic any liability in connection with such warranty, or any liability or expense incurred in the replacement or repair of its products other than those expressly authorized herein. Dometic shall not be responsible for any liability or expense except as is specifically authorized and provided in this section.
Dometic reserves the right to improve its products through changes in design or material without being obligated to incorporate such changes in products of prior manufacture, and to make changes at any time in design, materials, or part of units of any one year's model, without obligation or liability to owners of units of the same year's model of prior manufacture.
This warranty gives you, the purchaser, specific legal rights, and you may also have other rights which vary from state to state. You also have implied warranty rights, including an implied warranty of merchantability, which means that your product must be fit for the ordinary purposes for which such goods are used. The duration of any implied warranty rights is limited to the duration of the express warranty as found in Section III.
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Section II
What does this Limited Warranty not cover?
This Warranty Shall Not Apply to:
1. Failures resulting from improper installation or use contrary to instructions.
2. Failures resulting from abuse, misuse, accident, fire, or submergence.
3. Any part manufactured by Dometic which shall have been altered so as to impair its original characteristics.
4. Any parts which fail as a result of misuse, improper application or improper installation.
5. Items not manufactured by Dometic, i.e., items which are purchased from another manufacturer and supplied as received by Dometic without alteration or modification except as any part of an Dometic-manufactured unit or component.
6. Components or parts used by or applied by the purchaser as an integral part of products not manufactured by Dometic.
7. Warranty does not cover damage to components that comprise a Custom Wrapped Box Evaporator refrigeration system (aka: catch boxes, fish boxes, etc.) when the box is installed in such a way that the customer can move it. These damages may include, but are not limited to: crimped refrigerant linesets (copper tubing or flexible linesets), refrigerant leaks, moisture ingression into the refrigeration system, subsequent damage to condensing unit from being operated with low refrigerant charge or moisture in the system, broken refrigerant connections, broken thermostat sensors, and/or broken constant pressure valves.
Installation and application of Dometic components is not warranted by Dometic because Dometic has no control or authority over the selection, location, application, or installation of these components.
15
Section III
What is the period of coverage?
See the Limited Warranty Periods, document # L-0694, for the period of coverage.
❖
English
All Dometic components bear a data plate on which there are model and serial numbers. The serial number is date coded. To determine whether or not any Dometic component is in warranty, proceed as follows:
1. Determine the manufacture date of the component from the serial number on the data plate. If you are not familiar with the date code, write or call the Dometic Customer
Service Department at (804)746-1313, to obtain the manufacture date. The hours of the Customer Service
Department are 8:00 am - 5:00 pm (USA, Eastern Time
Zone) Monday through Friday excluding holidays.
2. It is possible that there might exist a considerable time lag between the date a component is manufactured and the date it is put in service. In such instances, the date of manufacture could indicate that the item is out of warranty. However, based on the date the equipment is first put in service, the item may still be covered by the
Dometic warranty described in Section I . For proof of date put in service, Dometic will require a copy of the bill of sale of the Dometic equipment from the installer or new boat dealer to the original owner.
Section IV
How do you get service? Please Read the following Warranty Procedure.
WARRANTY PROCEDURE
If the failure of a Dometic component is determined to be covered under the Dometic warranty and the time in service is determined to be within the warranty time limit, the owner has the following three options:
1. Preferred option: Have a Dometic authorized Servicing
Dealer perform the work needed. The customer should call Dometic's Service Department for a recommendation as to the closest dealer. If the customer already knows an authorized servicing dealer, the dealer should be contacted directly.
2. If the customer contacts Dometic's Service Department for a Servicing Dealer and Dometic has no one in that particular area, Dometic will authorize the use of a local service company and Dometic will work with the local company to assist in any way possible.
3. The customer may send his equipment back to the factory to have the repair work done. Dometic will make every effort to return the equipment to the customer within a three week time period. If the claim represents a legitimate warranty problem, Dometic will pay the freight both ways. Dometic prefers option one and two, if at all possible.
The customer may contact the Dometic Service Department at (804) 746-1313.
L-0123 Revised: 6-5-06
16
WARNING
Dometic Environmental Corporation (Dometic) manufacturers of Cruisair, Dometic
Auxiliary A/C, Dometic Refrigerators and Freezers, Eskimo Ice, Grunert, Marine
Air, and Sentry products, makes the following safety warnings concerning the application, installation, use and care of its products. Although these warnings are extensive, there may be specific hazards which may arise out of circumstances which we have not outlined herein. Use this as a guide for developing an awareness of potential hazards of all kinds. Such an awareness will be a key factor in assuring your SAFETY and comfort.
ELECTRICITY - Many Dometic products operate on 115, 230 or 440 volt AC power. Such voltages can be LETHAL; therefore, the chassis, cabinets, bases, etc., on all components must be grounded together and connected to the vessel's grounding system. Sparks can occur as switches, thermostats and relays open and close in the normal operation of the equipment. Since this is the case, ventilating blowers for the removal of hazardous fumes or vapors should be operated at least 5 minutes before and during operation of any Dometic product or group of Dometic products. All electrical connections must be covered and protected so accidental contact cannot be made by persons using the equipment, as such contact could be LETHAL.
ELECTROLYSIS - Electrical leakage of any component can cause electrolytic deterioration (electrolysis) of thru-hull components which could result in leakage serious enough to sink a vessel which could result in loss of life. All Dometic components must be kept clean and dry and checked periodically for electrical leakage. If any electrical leakage is detected, the component should be replaced or the fault causing the leakage corrected before the component is put back into service.
GAS - Dometic Air Conditioning and Refrigeration components utilize R-22
(Chlorodifluoromethane), R134a refrigerant (Tetrafluoroethane), R-407C (which contains Diflouromethane [HFC-32], Pentafluoroethane [HFC125], and 1.1.1.2 -
Tetrafluoroethane [HFC134a]), R404A (R125/R143a/R134 [44%/52%/4%]), or
R417a, which are non-toxic, non-flammable gases; however, these gases contain no oxygen and will not support life. Refrigerant gas tends to settle in the lowest areas of the compartment. If you experience a leak, evacuate all personnel, and ventilate area. Do not allow open flames in the area of leaks because refrigerant gas, when burned, decomposes into other potentially LETHAL gases. Refrigerant components operate at high pressure and no servicing should be attempted without gloves, long-sleeved clothing and eye protection. Liquid refrigerant gas can cause severe frost burns to the skin and eyes.
VENTILATION - To cool or heat air, Dometic Air Conditioning and Refrigeration components are designed to move air through a heat exchanger by a blower or propeller fan. This design necessarily produces a suction on one side of the air handling component and a pressure on the other side. Air handling components must be installed so that the suction-pressure action does not: (1) pressurize an area to the extent that structural failure occurs which could cause harm to occupants or bystanders, or (2) cause a suction or low pressure in an area where hydrogen gas from batteries, raw fuel vapor from fuel tanks, carbon monoxide from operating propulsion engines, power generators or heaters, methane gas from sewage holding tanks, or any other dangerous gas or vapor could exist. If an air handling unit is installed in such a manner that allows potentially lethal gases or vapors to be discharged by the air handling unit into the living space, this could result in loss of life.
Maximum protection against the introduction of dangerous gases or vapors into living spaces can be obtained by providing living spaces which are sealed from all other spaces by use of airtight bulkheads and decks, etc., and through the introduction of clean air into the living space. Bear in mind that the advent of air conditioning, whether it be for cooling or for heating, naturally leads to the practice of closing a living space tightly. Never close all windows and doors unless auxiliary ventilating systems, which introduce clean outside air into the living space, are used. Always leave enough window and door openings to provide adequate ventilation in the event potentially lethal gases or fumes should escape from any source.
CONDENSATE - All cooling units produce water condensate when operating on the cooling cycle. This water must be drained from the cooling unit overboard. If condensate is allowed to drip on a wooden structure, rotting or decay and structural failure may occur which could result in loss of life. If condensate is allowed to drip on electrical components, deterioration of the electrical components could result in hazardous conditions. When an air conditioning system is in operation, condensate drains may be subjected to negative pressure. Always locate condensate drains as far as possible from points where engine waste and other dangerous gases are exhausted so no such dangerous gases can be drawn into the condensate drains.
Warning
Never sleep in a closed area on a boat when any equipment, which functions as a result of the combustion of a volatile fuel, is in operation (such as engines, generators, power plants, or oil-fired heaters, etc.). At any time, the exhaust system of such devices could fail, resulting in a build-up of LETHAL gases within the closed area.
Warning Revised: 6-5-06
❖
English
Limited Warranty Periods
Please read and keep this document with your important paperwork. Use it as a reference in the future. If you have any questions, please contact the Dometic Environmental Corporation Service Department at (804)746-1313 for clarification.
Note: Any model or replacement part that has been installed due to a warranty failure will carry only the remainder of the original warranty. All warranties begin when the customer takes possession of the equipment. The warranty is extended to all owners of the equipment commencing the date the original owner takes possession of it. Proof of original purchase may be required.
Replacement parts, such as filters , fuses and MOVs, are not covered under our warranty. Fuses and MOVs are used as safety devices to protect Cruisair equipment against over-current conditions caused by lightning or inductive switching environments. We reserve the right to change our warranty policies and procedures as well as our warranty allowances without notice.
Cruisair Direct Expansion (DX) and Modulating Systems
• New, complete system installation using any member of the
SMX family.
The warranty includes the pump.
2 year warranty including Parts and Labor
• New, complete system installation using an electromechanical control (3-knob).
The warranty includes the pump.
1 year warranty including Parts and Labor
• New, complete model sold as a partial system retrofit to an existing system.
Includes SMX family.
1 year warranty including Parts and Labor
Cruisair Tempered Water
• New, complete system installation using any member of the
SMX family.
2 year warranty including Parts and Labor
NOTE: Excludes pump which has a 1 year warranty
• New, complete model sold as a partial system retrofit to an existing system.
Includes SMX family.
1 year warranty including Parts and Labor
Ice Makers, Remote and Self-Contained
• New installation of an entire Self-Contained Ice Maker
1 year warranty including Parts and Labor, including water pump.
• New installation of an entire Remote Ice Maker, including condensing unit, remote display, auger unit, linesets
1 year warranty including Parts and Labor, including water pump.
• New installation of an Remote Ice Maker Auger and
Condensing unit only, with linesets done by others i.e. not
Eskimo pre-charged linesets
1 year warranty including Parts and Labor on mechanical and electrical parts of the auger and condensing unit only.
• New complete component sold as a partial system retro-fit to an existing Eskimo system
1 year warranty including Parts and Labor on new component only.
Note : Use of saltwater as feedwater to make ice will void warranty on the auger section of the unit.
Sentry Battery Chargers
• New SM and FR series installation.
2 year warranty including Parts and Labor
• New G-series installation.
1 year warranty including Parts and Labor
Refrigerators/Freezers/Fish Boxes
The below warranty periods do not apply to systems that are installed as described in Section II, item #7, of the Owner’s
Limited Warranty, document # L-0123.
• New installation of entire system including condensing unit, line sets, evaporator, etc.
1 year warranty including Parts and Labor
• New complete model sold as a partial system retrofit to an existing Cruisair system.
1 year warranty including Parts and Labor
• New installation of condensing unit only, with line sets, evaporators, etc. done by others i.e. not Cruisair precharged line sets and evaporators.
1 year warranty including parts and labor on mechanical and electrical parts of condensing unit only.
Replacement Parts
• Replacement parts and components
Example: A-509, 40401-30.
90 day warranty, Parts only
• Replacement Compressors for other than Tempered Water
Systems - example: R3101-16T, DX equipment - installed in an existing Cruisair system or a competitor’s system.
1 year warranty including Parts and Labor
• Replacement compressors for Tempered Water - example:
30130-36 installed in an existing Cruisair system.
1 year warranty including Parts and Labor
• A Tempered Water compressor - example: 30130-36 installed with competitor’s equipment.
90 day warranty, Parts only
17
Revised: 7-18-06 L-0694
❖
English
Descriptions of Figures
Fig. 1a Single Duct Installation
Fig. 1b Dual Duct Installation
Fig. 2 Spacing Allowances & Unit Dimensions for
Mounting
Fig. 3 Component Identification
Fig. 4 Mounting Bracket Drawing
Fig. 5 Condensate Drain Drawing
Fig. 6 Three-Knob Switch Assembly
Fig. 7 Two-Knob Switch Assembly
Fig. 8 Wiring Diagram of ZF3.5
Fig. 9 Wiring Diagram of ZF5
Fig. 10 Wiring Diagram of ZF10-16
Fig. 11 Wiring Diagram of Cuddy dc CD3.5HV 12VDC
Fig. 12 Seawater Pump and Plumbing Drawings
Fig. 13a Seawater Installation for ZF3.5-12
Fig. 13b Seawater Installation for ZF16
Fig. 14 Dedicated Power Module (DPM) Specs Tables for
Use With Cuddy dc Systems Only
Fig. 15 DC Wire Sizing Table
L-2028
18 ❖
English
Fig. 1a - Typical Single Duct Installation for ZF3.5-5 Fig. 1b- Typical Dual Duct Installation for ZF10-16
Fig. 2 - Spacing Allowances & Unit Dimensions for Mounting
Unit Capacity
A – Duct Size
B – Base Depth
C – Overall Depth
D – Width
E – Height
L-2028
3,500 BTU
(in/mm)
3.0/76
8.0/203
9.0/229
15.0/381
9.3/235
DIMENSIONS
5,000 BTU
(in/mm)
4.0/102
8.0/203
11.6/294
16.0/407
11.6/294
10,000 BTU
(in/mm)
6.0/152
8.4/213
12.2/310
19.0/483
12.9/328
19
12,000 BTU 16,000 BTU
(in/mm) (in/mm)
6.0/152
8.4/213
12.2/310
19.0/483
13.3/337
7.0/178
10.3/261
14.2/361
20.0/508
13.5/343
❖
English
Fig. 3 - Component Identification
Fig. 4 - Mounting Bracket Fig. 5 - Condensate Drain
L-2028
20 ❖
English
Fig. 6 - Three-Knob Switch Assembly Fig. 7 - Two-Knob Switch Assembly
OFF ON
2 Knob Switch
2"
3
Knob
S
witch
L-2028
21 ❖
English
Fig. 8 - Wiring Diagram of ZF3.5
L-2028
22 ❖
English
Fig. 9- ZF5 Wiring Diagram Fig. 10 - ZF10-16 Wiring Diagram
L-2028
ALL WIRES 12 GA
UNLESS OTHERWISE NOTED
23
ALL WIRES 12 GA
UNLESS OTHERWISE NOTED
❖
English
Fig. 11- Wiring Diagram for Cuddy dc CD3.5HV 12VDC
L-2028
24 ❖
English
Fig. 12- Seawater Pump & Plumbing Diagrams
./4%3
4(25(5,,).,%4"!,,6!,6%(/3%!.$342!).%23(/5,$"%3):%$./3-!,,%24(!.05-0).,%4
).34!,,4(25(5,,&)44).'!3&!2"%,/74(%7!4%2,).%!30/33)",%
05-0.%%$3$%$)#!4%$4(25(5,,./43(!2%$7)4(/4(%205-03
!6/)$/2-).)-):% %,"/7&)44).'3!3-5#(!30/33)",%2/4!4%05-0(%!$4/7!2$3$)2%#4)/./&7!4%2&,/7
Fig. 13a - Seawater Kit Installation for ZF3.5-12 Fig. 13b - Seawater Kit Installation for ZF16
L-2028
25 ❖
English
Fig. 14 - Dedicated Power Module (DPM) Specs Tables for Use With Cuddy dc Systems Only
Electrical Specifications
Output Waveform............................................... Modified Sine-Wave
Output Power ..................................................... 600W Continuous
Output Surge Rating ......................................... 1200W for 1 sec
Output Voltage ................................................... 115VAC ± 10%
Output Frequency ............................................. 60Hz (±4Hz)
Input DC Voltage Range ................................... 11 - 15VDC
Input Low Voltage Shutdown ............................ < 10.5VDC ± 0.2VDC
High Temperature Shutdown ............................ Thermistor ≥ 167°F (75°C)
Reverse Polarity Protection .............................. External Fuse
No Load Current Draw ...................................... 0.75A~0.95A
Efficiency ........................................................... ~90%
Over-voltage Shut-down ................................... 16-17VDC, restart below 16VDC
General Specifications
Isolation Voltage ................................................ Non-isolated
Operating Temperature Range ......................... -13 ~ 122°F (-25 ~ +50°C)
Storage Temperature Range ............................ -40 ~ 167°F (-40 ~ +75°C)
External Fuse .................................................... 30A x 2
Safety ................................................................. CE
Dimensions (L x W x H) .................................... 9.5 x 5.1 x 2.7" (241 x 130 x 69mm)
DC Input Connections (IN) ............................... Ring Terminals
Net Weight ......................................................... ~2.9 lbs (1.3kg)
AC Output Connections .................................... Per Dometic Wiring Diagram M8010112 in this manual
Ventilation .......................................................... Allow at least 1" (25mm) above unit for adequate airflow.
LED Lights Scheme for DPM (see note)
Battery Energy Level No Load With Load
Full (Battery Voltage>13V) ................................ Green ................. Green
Intermediate(12-13V) ........................................ Green ................. Orange
Low(<12V) ......................................................... Red .................... Red
Note: LED lights may or may not be readily visible, depending on DPM installation location. This table is included as a convenience, but is not necessary for troubleshooting the system.
Fig. 15 - DC Wire Sizing Table
DC Wire S ize Table*
Di s t a nce from ba ttery (power s o u rce) to C u ddy dc u nit
5 ft a nd u nder (1.5m a nd u nder)
5 ft to 7.5 ft (1.5m to 2.
3 m)
7.5 ft to 10 ft (2.
3 m to 3 .0m)
10 ft to 12.5 ft ( 3 .0m to 3 .
8 m)
12.5 ft to 15 ft ( 3 .
8 m to 4.6m)
15 ft to 20 ft (4.6m to 6.1m)
20 ft to 25 ft (6.1m to 7.6m)
25 ft to 3 0 ft (7.6m to 9 .1m)
Tot a neg l length of a tive wire s b oth po a s itive a nd dded together
10 ft a nd u nder ( 3 .0m a nd u nder)
10 ft to 15 ft ( 3 .0m to 4.6m)
15 ft to 20 ft (4.6m to 6.1m)
20 ft to 25 ft (6.1m to 7.6m)
25 ft to 3 0 ft (7.6m to 9 .1m)
3 0 ft to 40 ft ( 9 .1m to 12.2m)
40 ft to 50 ft (12.2m to 15.2m)
50 ft to 60 ft (15.2m to 1 8 .
3 m)
Wire S ize
AWG
#6
#6
#4
#4
#2
#2
#1
#0
* T ab le derived from ABYC s ection E 9 , t ab le 9 for 12 VDC s y s tem s . The s e s pecific a tion s were c a lc u l a ted us ing 3% volt a ge drop a nd a m a xim u m c u rrent dr a w of 50 a mp s for C u ddy dc a ir conditioner a nd p u mp.
L-2028
26 ❖
English
Cruisair Worldwide Service Dealer Locator
The majority of the service listings displayed for the United States are key members of the national Cruisair distributor or master dealer network. If you need service, please contact the closest company shown. In most cases they will direct you to a local dealer or service port. We have over 500 Cruisair dealers in the national Cruisair network, and one should be convenient to you.
The international companies listed are, in many cases, distributors and are capable of managing the majority of service requests for the countries listed. In some cases they will refer you to a local dealer.
Domestic
USA
AAP Inc.
Location: Milford, VA, USA
Territory: National Coach & Mobile Products Only
Phone:
Fax:
Web:
804-6339 454
804-633-54 99 www.aap.com
Alabama
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Thom Chase Marine
Location: Chattanooga, Tennessee, USA
Territory: Northern Alabama, Northern Mississippi,
Tennessee, Western Kentucky
Phone:
Fax:
E-mail:
423-344-6356
423-344-6356 [email protected]
Alaska
Southern California Marine Enterprises
Location: San Diego, California, USA
Phone:
Fax:
E-mail:
Web:
61 9 -224-286 9
61 9 -226-04 9 6 [email protected]
www.southerncalmarine.com
Arizona
Southern California Marine Enterprises
Location: San Diego, California, USA
Phone:
Fax:
E-mail:
Web:
61 9 -224-286 9
61 9 -226-04 9 6 [email protected]
www.southerncalmarine.com
Arkansas
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
California
Southern California Marine Enterprises
Location: San Diego, California, USA
Phone:
Fax:
E-mail:
Web:
61 9 -224-286 9
61 9 -226-04 9 6 [email protected]
www.southerncalmarine.com
Colorado
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
You may also contact us directly via the web site or call us in the US at (804) 746-1313.
For a complete and up-to-date Dealer locator list, please visit our website at http://www.cruisair.com/cruisair/dealer.html
Connecticut
GDL Services, LLC
Location: Clinton, CT, USA
Territory: Connecticut River Area
Phone:
Fax:
860-66 9 -517 9
860-66 9 -5806
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Delaware
Annapolis Cruisair
Location: Annapolis, Maryland, USA
Territory: In Md: Baltimore & Areas South; In Delaware:
South of the Sassafras River
Phone:
Fax:
E-mail:
Web:
410-224-0 9 70
410-224-0050 [email protected]
www.annapoliscruisair.com
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Florida
Cruisair Southeast, A Division of T.K. Alley, Inc.
Location: Dania Beach, Florida, USA
Territory: Southeast Florida
Phone:
Fax:
E-mail:
Web:
9 549 20-0300
9 549 20-0301 [email protected]
www.cruisair-southeast.com
Ward's Marine Electric, Inc.
Location: Ft. Lauderdale, Florida, USA
Territory: Battery Chargers Only
Phone:
Fax:
E-mail:
9 54-523-2815
9 54-523-1 9 67 [email protected]
Florida, Southwest
Cruisair Suncoast, Inc.
Location: St. Petersburg, Florida, USA
Territory: Tampa, St. Petersburg and surrounding areas
Phone:
Fax:
E-mail:
727-526-7875
727-5289 51 9 [email protected]
Georgia
Beard Marine Savannah - Distributor
Location: Savannah, Georgia, USA
Phone:
Fax:
E-mail:
Web:
( 9 12) 356-5222
( 9 12) 6 9 2-1006 [email protected]
www.beardmarine.com
Hawaii
Southern California Marine Enterprises
Location: San Diego, California, USA
Phone:
Fax:
E-mail:
Web:
61 9 -224-286 9
61 9 -226-04 9 6 [email protected]
www.southerncalmarine.com
Idaho
Sure Marine Services Inc.
Location: Seattle, Washington, USA
Phone:
Fax:
E-mail:
206 -78499 03
206-784-0506 [email protected]
Illinois
J & S Marine Sales & Service
Location: Detroit, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 463-3400
(586) 463-1762 [email protected]
www.jandsmarine.com
Midwest Marine Supply
Location: St. Clair Shores, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 778-8 9 50
(586) 778-6108 [email protected]
www.midwestmarinesupply.com
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Indiana
J & S Marine Sales & Service
Location: Detroit, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 463-3400
(586) 463-1762 [email protected]
www.jandsmarine.com
Midwest Marine Supply
Location: St. Clair Shores, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 778-8 9 50
(586) 778-6108 [email protected]
www.midwestmarinesupply.com
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Iowa
J & S Marine Sales & Service
Location: Detroit, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 463-3400
(586) 463-1762 [email protected]
www.jandsmarine.com
L-0384 Revised: 05-03-07
Iowa
Midwest Marine Supply
Location: St. Clair Shores, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 778-8 9 50
(586) 778-6108 [email protected]
www.midwestmarinesupply.com
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Kansas
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Kentucky
Thom Chase Marine
Location: Chattanooga, Tennessee, USA
Territory: Northern Alabama, Northern Mississippi,
Tennessee, Western Kentucky
Phone:
Fax:
E-mail:
423-344-6356
423-344-6356 [email protected]
Louisiana
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Sea Chest Marine Distributors
Location: New Orleans, Louisiana, USA
Territory: Gulf Coast (LA & MS)
Phone:
Fax:
E-mail:
(504) 288-8431
(504) 288-1758 [email protected]
Maryland
Annapolis Cruisair
Location: Annapolis, Maryland, USA
Territory: In Md: Baltimore & Areas South; In Delaware:
South of the Sassafras River
Phone:
Fax:
E-mail:
Web:
410-224-0 9 70
410-224-0050 [email protected]
www.annapoliscruisair.com
Maryland (N of Baltimore)
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Massachusetts
World Wide Enterprises
Location: East Falmouth, Massachusetts, USA
Phone:
Fax:
E-mail:
Web:
(508) 540-0 9 63
(508) 540-0 9 63 [email protected]
www.worldwideent.net
Michigan
J & S Marine Sales & Service
Location: Detroit, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 463-3400
(586) 463-1762 [email protected]
www.jandsmarine.com
Midwest Cruisair
Minnesota
Location: Red Wing, Minnesota, USA
Territory: Minnesota and Western Wisconsin
Phone:
Fax:
E-mail:
651-388-4881
651-3889 186 [email protected]
Mississippi
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Sea Chest Marine Distributors
Location: New Orleans, Louisiana, USA
Territory: Gulf Coast (LA & MS)
Phone:
Fax:
E-mail:
(504) 288-8431
(504) 288-1758 [email protected]
Thom Chase Marine
Location: Chattanooga, Tennessee, USA
Territory: Northern Alabama, Northern Mississippi,
Tennessee, Western Kentucky
Phone:
Fax:
E-mail:
423-344-6356
423-344-6356 [email protected]
Missouri
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Montana
Sure Marine Services Inc.
Location: Seattle, Washington, USA
Phone:
Fax:
E-mail:
206 -78499 03
206-784-0506 [email protected]
Nebraska
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Nevada
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Southern California Marine Enterprises
Location: San Diego, California, USA
Phone:
Fax:
E-mail:
Web:
61 9 -224-286 9
61 9 -226-04 9 6 [email protected]
www.southerncalmarine.com
New Jersey
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
New Mexico
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
New York
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
North Carolina
Martin's Marine
Location: Wilmington, North Carolina, USA
Territory: North Carolina and Myrtle Beach, SC
Phone:
Fax:
( 9 10) 7 99 9 362
( 9 10) 7 99 9 122
North Dakota
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Ohio
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Oklahoma
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Oregon
Sure Marine Services Inc.
Location: Seattle, Washington, USA
Phone:
Fax:
E-mail:
206 -78499 03
206-784-0506 [email protected]
Pennsylvania
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
Rhode Island
Cay Electronics
Location: Portsmouth, Rhode Island, USA
Territory: Rhode Island
Phone:
Fax:
Web:
401-683-3520
401-683-3633 www.cayelectronics.com
Nautical Air, Inc.
Location: Farmingdale, New York, USA
Territory: CT, DE (N. of Sassafras River), IO, IL, MD (N.of
Baltimore), NJ, NY, PA, OH, RI
Phone:
Fax:
E-mail:
Web:
(516) 586-5244
(516) 586-5241 [email protected]
www.nauticalair.com
South Carolina
Atlantic Boat ACR
Location: Johns Island, South Carolina, USA
Phone:
Fax:
E-mail:
Web:
(843) 557-0788
(843) 557-0786 [email protected]
www.atlanticboatacr.com
L-0384 Revised: 05-03-07
South Carolina
Martin's Marine
Location: Wilmington, North Carolina, USA
Territory: North Carolina and Myrtle Beach, SC
Phone:
Fax:
( 9 10) 7 99 9 362
( 9 10) 7 99 9 122
South Dakota
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Tennessee
Thom Chase Marine
Location: Chattanooga, Tennessee, USA
Territory: Northern Alabama, Northern Mississippi,
Tennessee, Western Kentucky
Phone:
Fax:
E-mail:
423-344-6356
423-344-6356 [email protected]
Texas
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Utah
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
Southern California Marine Enterprises
Location: San Diego, California, USA
Phone:
Fax:
E-mail:
Web:
61 9 -224-286 9
61 9 -226-04 9 6 [email protected]
www.southerncalmarine.com
Virginia
Lamy Marine, Inc.
Location: Chesapeake, Virginia, USA
Phone:
Fax:
E-mail:
757-4 9 4-3747
757-4 9 4-3740 [email protected]
Washington
Sure Marine Services Inc.
Location: Seattle, Washington, USA
Phone:
Fax:
E-mail:
206 -78499 03
206-784-0506 [email protected]
Wisconsin (East)
J & S Marine Sales & Service
Location: Detroit, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 463-3400
(586) 463-1762 [email protected]
www.jandsmarine.com
Midwest Marine Supply
Location: St. Clair Shores, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 778-8 9 50
(586) 778-6108 [email protected]
www.midwestmarinesupply.com
Wisconsin (West)
Midwest Cruisair
Location: Red Wing, Minnesota, USA
Territory: Minnesota and Western Wisconsin
Phone:
Fax:
E-mail:
651-388-4881
651-3889 186 [email protected]
Wyoming
AER Marine Supply
Location: Seabrook, Texas, USA
Phone:
Fax:
E-mail:
Web:
(281) 474-3276
(281) 474-2714 [email protected]
www.aersupply.com
International
Angola
Southern Power Products
Location: Cape Town, South Africa
Phone:
Fax:
E-mail:
27-21-511-0653
27-21-510-304 9 [email protected]
Argentina
Trimer S.A.
Location: Buenos Aires, Argentina
Phone:
Fax:
E-mail:
Web:
5411-4580-0444
5411-4580-0440 [email protected]
www.trimer.com.ar
Australia
Seabreeze Industries
Location: Coomera, Queensland, Australia
Phone:
Fax:
E-mail:
Web:
61-7-55806371
61-7-55806372 [email protected]
www.seabreeze-industries.com.au
Austria
Dometic Marine – Italy, Sales Company
Location: Milano, Italy
Phone:
Fax:
E-mail:
Web:
3 9 0362 44182
3 9 0362 452226 [email protected]
www.dometic.com
Nautica Centis di Nespolo Cinzia & C. Sne
Location: Bevazzana de Latisana (UD), Italy
Territory: Northeast Italy, Austria, Croatia, Slovenia
Phone:
Fax:
E-mail:
Web:
3 9 0-431-53-644
3 9 0-431-53-460 [email protected]
www.nauticacentis.it
Bahamas
Bradford Grand Bahama, Ltd.
Location: Freeport, Grand Bahama, Bahamas
Phone:
Fax:
E-mail:
Web:
+242-352-7711
+242-352-76 9 5 [email protected]
www.bradford-grand-bahama.com
Freezing Point, Ltd.
Location: Nassau, Bahamas
Phone:
Fax:
E-mail:
(242) 325-358 9
(242) 356-5271 [email protected]
Nixon's Refrigeration
Location: Abaco, Bahamas
Territory: Abaco Island only
Phone:
Fax:
E-mail:
242-367-521 9
242-367-521 9 [email protected]
Bahrain
Mantech
Location: Dubai, United Arab Emirates
Phone:
Fax:
E-mail:
+( 9 71) 4-3332-542
+( 9 71) 4-3330-64 9 [email protected]
Belgium
Eberca
Location: , Netherlands
Phone:
Fax:
E-mail:
31 1866 21 9 55
31 1866 21818 [email protected]
Bermuda
Flatt's Marine
Location: St. Georges, Bermuda
Phone:
Fax:
+441-2 9 3-5740
+441-2 9 3-5740
Botswana
Southern Power Products
Location: Cape Town, South Africa
Phone:
Fax:
E-mail:
27-21-511-0653
27-21-510-304 9 [email protected]
Brazil
Sailing Products
Location: Sao Paulo, Brazil
Phone:
Fax:
+55 (0) 11 33546734 Technical
+55 (0) 11 81 1 9 36
Sailing Products
Location: Rio de Janeiro, Brazil
Phone:
Fax:
E-mail:
55 (0) 21 3154999 0
55 (0) 21 24 9 4-7223 [email protected]
British Virgin Islands
Cay Electronics Ltd.
Location: Tortola, British Virgin Islands
Phone:
Fax:
E-mail:
Web:
284-4 9 4-2400
284-4 9 4-538 9 [email protected]
www.cayelectronics.com
Parts And Power
Location: Tortola, British Virgin Islands
Phone:
Fax:
E-mail:
Web:
284-4 9 4-2830
284-4 9 4-1584 [email protected]
www.partsandpower.com
British West Indies
Caribbean Marine & Diesel
Location: Turks and Caicos Islands, British West Indies
Phone:
Fax:
E-mail:
64 9 9 41-5 9 03
64 9 9 41-5 9 02 [email protected]
Canada
British Columbia
Accutemp Refrigeration and Air Conditioning
Location: Victoria, BC, Canada
Territory: Western Canada
Phone:
Fax:
E-mail:
Web:
250-475-2665
250-475-1 9 57 [email protected]
www.accutemp.ca
Airon Heating & Air Conditioning
Location: Richmond, British Columbia, Canada
Phone:
Fax:
E-mail:
Web:
(604) 270-2040
(604) 270-3888 [email protected]
www.aironhvac.com
Ontario
J & S Marine Sales & Service
Location: Detroit, Michigan, USA
Phone:
Fax:
E-mail:
Web:
(586) 463-3400
(586) 463-1762 [email protected]
www.jandsmarine.com
L-0384 Revised: 05-03-07
Ontario
Northland Supply Company
Location: Queensville, Ontario, Canada
Phone:
Fax:
E-mail:
Web:
( 9 05) 478-2244
( 9 05) 478-22 9 5 [email protected]
www.norsupco.com
Caribbean Islands
B & R
Location: Centro Comercial Naco, Santo Domingo,
Dominican Republic
Phone:
Fax:
E-mail:
(80 9 ) 562-1661
(80 9 ) 562-1521 [email protected]
C.S. Services
Location: Martinique, French West Indies
Phone:
Fax:
5 9 6-74 9 113
5 9 6-74 9 174
Caraibe Greemant
Location: Le Marin, Martinique, French West Indies
Phone:
E-mail:
5 9 6 5 9 6 74 80 33 [email protected]
Caribbean Marine & Diesel
Location: Turks and Caicos Islands, British West Indies
Phone:
Fax:
E-mail:
64 9 9 41-5 9 03
64 9 9 41-5 9 02 [email protected]
Cay Electronics Ltd.
Location: Tortola, British Virgin Islands
Phone:
Fax:
E-mail:
Web:
284-4 9 4-2400
284-4 9 4-538 9 [email protected]
www.cayelectronics.com
Centro Cruisair de Puerto Rico
Location: Santurce, Puerto Rico
Phone:
Fax:
E-mail:
787-727-3637
787-727-3637 [email protected]
Cool-Tech Air Condition
Location: Fajardo, Puerto Rico
Phone:
Fax:
Web:
(787) 860-2615
(787) 801-2050 http://www.cooltechac.com/
Coral Bay Marine Service
Location: St. John, U.S. Virgin Islands
Phone:
Fax:
340-776-685 9
340-776-685 9
Dr. Ice
Location: St. Thomas, US Virgin Islands
Territory: St. Thomas
Phone:
Fax:
E-mail:
340-5139 072
340-775-6576 [email protected];
Enertech N.V.
Location: Simpson Bay, St. Maarten/St. Martin, Netherlands
Antilles
Phone:
Fax:
E-mail:
Web:
+5 99 -551-2145
+5 99 -544-4608 [email protected]
www.enertechnv.com
Freezing Point, Ltd.
Location: Nassau, Bahamas
Phone:
Fax:
E-mail:
(242) 325-358 9
(242) 356-5271 [email protected]
Frostline
Location: Cole Bay, St. Maarten/St. Martin, Netherlands
Antilles
Phone:
Fax:
E-mail:
5 99 522 9 610 (Technical)
5 99 544 3263 [email protected] (technical); [email protected]
Hitchcraft Co.
Location: Curacao, Netherlands Antilles
Phone:
Fax:
E-mail:
5 999 667 334 9
501-641-2708 (US Line)
May Day Marine
Location: San Juan, Puerto Rico
Territory: Puerto Rico, Dominican Republic
Phone:
Fax:
787-637-0756
787-7 9 0-2551
Nau-T-Kol Marine Refrigeration
Location: Chaguaramas, Trinidad
Phone:
Fax:
E-mail:
Web:
868-634-2174
868-634-2174 [email protected]
www.nautkol.com
Nixon's Refrigeration
Location: Abaco, Bahamas
Territory: Abaco Island only
Phone:
Fax:
E-mail:
242-367-521 9
242-367-521 9 [email protected]
Outfitters International
Location: St. Georges, Grenada
Phone:
Fax:
E-mail:
473-440-7 9 4 9
473-440-6680 [email protected]
Parts And Power
Location: Tortola, British Virgin Islands
Phone:
Fax:
E-mail:
Web:
284-4 9 4-2830
284-4 9 4-1584 [email protected]
www.partsandpower.com
Reefco, Inc.
Location: , St. Thomas, US Virgin Islands
Phone:
Fax:
E-mail:
Web:
(340) 776-0038
(340) 776-0038 [email protected]
www.reefco.net
Regis Electronics (St Lucia) LTD.
Location: St. Lucia, West Indies
Phone:
Fax:
E-mail:
Web:
758-452-0205
758-452-0206 [email protected]
www.regiselectronics.com
St. Croix Marine Corp.
Location: St. Croix, U.S. Virgin Islands
Phone:
Fax:
E-mail:
340-773-028 9
340-778-8 9 74 [email protected]
Suncool Air Conditioning
Location: Carolina, Puerto Rico, Puerto Rico
Phone:
Fax:
E-mail:
(787) 7 9 1-6 9 71
(787) 7 9 1-3885 [email protected]
Technical House (E.T.S. Inc.)
Location: San Juan, Puerto Rico
Territory: Sentry Battery Chargers Only
Phone:
Fax:
E-mail:
Web:
787-781-1313
787-781-2020 [email protected]
www.technicalhouse.com
The Signal Locker
Location: English Harbour, Antigua, West Indies
Phone:
Fax:
E-mail:
(268) 460-1528
(268) 460-1148 [email protected]
China
Chi-Mo Inc.
Location: Shanghai, China
Phone:
Fax:
E-mail:
Web:
8621-5 9 17-1111
8621-5 9 17-1166 [email protected]
www.springfieldmarine.com.cn
Tripower Beijing
Location: Beijing, China
Phone:
Fax:
E-mail:
Web:
(86) 10 6426 3335
(86) 10 64248862
[email protected]; [email protected]
www.tritex.com.sg
Tripower Guangzhou
Location: Guangzhou, China
Phone:
Fax:
E-mail:
Web:
86-20-8136 0 9 55
86-20 8136 65 9 6
[email protected]; www.tritex.com.sg
Tripower Hangzhou
Location: Hangzhou, China
Phone:
Fax:
E-mail:
Web:
86 571 86414317
86-571-86414317
[email protected]; HZwww.tritex.com.sg
Tripower Shanghai
Location: Shanghai, China
Phone:
Fax:
E-mail:
Web:
86 21 5240 2638
86 21 5240 2153 [email protected]
www.tritex.com.sg
Tripower Xiamen
Location: Xiamen, China
Phone:
Fax:
E-mail:
Web:
(86) 5 9 2 5376000
(86) 5 9 2 5376013 [email protected], xmwww.tritex.com.sg
Tripower Zhuhai
Location: C.Zhuhai, China
Phone:
Fax:
E-mail:
Web:
86-756 3222470
86-756 3222471 [email protected]; [email protected]
www.tritex.com.sg
Columbia
Todomar CHL Marina S.A.
Location: Cartagena, Colombia
Phone:
Fax:
E-mail:
+57-5-6654177
+57-5-6655118 [email protected]
Costa Rica
CR Marine Supply S.A.
Location: Garrabito, Costa Rica
Territory: Costa Rica
Phone:
Fax:
E-mail:
506-637-741 9
506-637-7180 [email protected]
Metro Marine
Location: Herradura Bay, Costa Rica
Phone:
Fax:
Web:
506-643-240 9
506-643-240 9 [email protected]
Croatia
Dometic Marine – Italy, Sales Company
Location: Milano, Italy
Phone:
Fax:
E-mail:
Web:
3 9 0362 44182
3 9 0362 452226 [email protected]
www.dometic.com
Nautica Centis di Nespolo Cinzia & C. Sne
Location: Bevazzana de Latisana (UD), Italy
Territory: Northeast Italy, Austria, Croatia, Slovenia
Phone:
Fax:
E-mail:
Web:
3 9 0-431-53-644
3 9 0-431-53-460 [email protected]
www.nauticacentis.it
L-0384 Revised: 05-03-07
Cyprus
Dometic Marine - United Kingdom, Sales
Company
Location: Poole, Dorset, England
Phone:
Fax:
E-mail:
Web:
44 870 3306101
44 870 3306102 [email protected]
www.dometic.com
Tuti Mare Trading
Location: Limassol, Cyprus
Phone:
Fax:
E-mail:
(35) 725.43.1313
(35) 725.43.1300
Dominican Republic
May Day Marine
Location: San Juan, Puerto Rico
Territory: Puerto Rico, Dominican Republic
Phone:
Fax:
787-637-0756
787-7 9 0-2551
Santo Domingo
B & R
Location: Centro Comercial Naco, Santo Domingo,
Dominican Republic
Phone:
Fax:
E-mail:
(80 9 ) 562-1661
(80 9 ) 562-1521 [email protected]
Ecuador
Navas-Bustos Representaciones
Location: Guayaquil, Equador
Phone:
Fax:
5 9 3-2-252542
5 9 3-2-251-421
Egypt
Climate Company
Location: Cairo, Egypt
Phone:
Fax:
E-mail:
20-2-25 9 80 9 2
20-2-4523028 [email protected]
Eritrea
DM Electrical Engineering
Location: Asmara, Eritrea
Phone:
Fax:
2 9 1-1-126737
2 9 1-1-127650
France
Dometic Marine – France, Sales Company
Location: Plailly, France
Phone:
Fax:
E-mail:
Web:
Cell: 0033 (0)680 415 543
0033 (0)344 633 518 [email protected]
www.dometic.com
PolyMarine Distribution (C/O Occas Marine)
Location: Le Cannet, Rocheville, France
Phone:
Fax:
E-mail:
0033 4 9 3463634
0033 4 9 3463634 [email protected]
French West Indies
C.S. Services
Location: Martinique, French West Indies
Phone:
Fax:
5 9 6-74 9 113
5 9 6-74 9 174
Caraibe Greemant
Location: Le Marin, Martinique, French West Indies
Phone:
E-mail:
5 9 6 5 9 6 74 80 33 [email protected]
Germany
GEMO Service Gmbh
Location: Lubeck – Travemunde, Germany
Phone:
Fax:
E-mail:
Web:
(4 9 ) 4502 2466
(4 9 ) 4502 2425 [email protected]
www.gemo_online.de
Greece
Dometic Marine - United Kingdom, Sales
Company
Location: Poole, Dorset, England
Phone:
Fax:
E-mail:
Web:
44 870 3306101
44 870 3306102 [email protected]
www.dometic.com
Polfrost Technical Ltd.
Location: Piraeus, Greece
Phone:
Fax:
30-210-461-3370
30-210-461-4376
Athens
Aegean Diesel Electric Ltd.
Location: Athens, Piraeus, Greece
Phone:
Fax:
E-mail:
+30 210 42 22 484
+30 210 41 75 201 [email protected]
Grenada
Outfitters International
Location: St. Georges, Grenada
Phone:
Fax:
E-mail:
473-440-7 9 4 9
473-440-6680 [email protected]
Guam
Fentress Refrigeration Service Co.
Location: Tamuning, Guam
Phone:
Fax:
E-mail:
671-565-4038
671-565-3315 [email protected]
Guatemala
Automotores y Marina, S.A.
Location: Villa Nueva, Guatemala
Phone:
Fax:
E-mail:
(502) 6628-6400
(502) 6628-6401 [email protected]
Hong Kong
Alan Reid
Location: Sai Kung, NT, Hong Kong
Phone:
Fax:
E-mail:
852-271 9 5 9 82
852-21 9 444 63 [email protected]
Tripower Hong Kong
Location: Kowloon, Hong Kong
Phone:
Fax:
E-mail:
Web:
(852) 2341-332 9
(852) 2343-1830 [email protected]; [email protected]
www.tritex.com.sg
Indonesia
PT.TriMarine Indonesia
Location: Lippo Karawachi, Tangerang, Jakarta, Indonesia
Phone:
Fax:
E-mail:
Web:
+6221-5512635
+6221-5513382 [email protected]; [email protected]
www.tritex.com.sg
Israel
Yamit Mil Ltd.
Location: Ramat-Gan, Israel
Phone:
Fax:
E-mail:
Web:
9 72 3 61231 9 2
9 72 3 61231 9 7 [email protected]
www.yamit-mil.com
Italy
Cummins Diesel Italia S.P.A
Location: Milan, Italy
Territory: Central & Southern Italy
Phone:
Fax:
E-mail:
3 9 02 51 655 856
3 9 02 51 65 58 55 [email protected]
Dometic Marine – Italy, Sales Company
Location: Milano, Italy
Phone:
Fax:
E-mail:
Web:
3 9 0362 44182
3 9 0362 452226 [email protected]
www.dometic.com
Nautica Centis di Nespolo Cinzia & C. Sne
Location: Bevazzana de Latisana (UD), Italy
Territory: Northeast Italy, Austria, Croatia, Slovenia
Phone:
Fax:
E-mail:
Web:
3 9 0-431-53-644
3 9 0-431-53-460 [email protected]
www.nauticacentis.it
Japan
Gunji Corporation
Location: Osaka, Japan
Phone:
Fax:
E-mail:
Web:
81-6-6451-5615
81-6-6454-0056 [email protected]
www.gunji.com
Kuwait
Mantech
Location: Dubai, United Arab Emirates
Phone:
Fax:
E-mail:
+( 9 71) 4-3332-542
+( 9 71) 4-3330-64 9 [email protected]
Seas & Deserts Group
Location: Al-shawikh, Kuwait
Phone:
Fax:
9 65-484 9 212
9 65-4820 9 13
Luxembourg
Eberca
Location: , Netherlands
Phone:
Fax:
E-mail:
31 1866 21 9 55
31 1866 21818 [email protected]
Malaysia
Gypsie Marine Sdn Bhd
Location: Langkawi, Malaysia
Phone:
Fax:
E-mail:
604 9 553006
604 9 553006 [email protected]
Pen-Marine Sdn Bhd
Location: Kuala Lumpur, Malaysia
Phone:
Fax:
E-mail:
+6 06 64627 9 2
+6 06 64627 9 3 [email protected]
Pen-Marine Sdn Bhd
Location: Penang, Malaysia
Phone:
Fax:
E-mail:
604-6262628
604-6262688 [email protected]
Maldives
TriMarine Maldives Pvt. Ltd.
Location: Male', Maldives
Phone:
E-mail:
Web:
( 9 60) 778-1818 [email protected]
www.tritex.com.sg
Wheel Engineering Services
Location: Malé, Maldives
Territory: Maldives
Phone:
Fax:
E-mail:
9 60-3327806
9 60-3324145 [email protected]
Malta
Dometic Marine - United Kingdom, Sales
Company
Location: Poole, Dorset, England
Phone:
Fax:
E-mail:
Web:
44 870 3306101
44 870 3306102 [email protected]
www.dometic.com
L-0384 Revised: 05-03-07
Inmartech Ltd.
Location: Swieqi, STJ 04, Malta
Territory: Malta
Phone:
Fax:
E-mail:
00356 21376476
00356 21376476 [email protected]
Mexico
Southern California Marine Enterprises
Location: San Diego, California, USA
Phone:
Fax:
E-mail:
Web:
61 9 -224-286 9
61 9 -226-04 9 6 [email protected]
www.southerncalmarine.com
Monaco
PolyMarine Distribution (C/O Occas Marine)
Location: Le Cannet, Rocheville, France
Phone:
Fax:
E-mail:
0033 4 9 3463634
0033 4 9 3463634 [email protected]
Mozambique
Southern Power Products
Location: Cape Town, South Africa
Phone:
Fax:
E-mail:
27-21-511-0653
27-21-510-304 9 [email protected]
Myanmar
TriMarine Myanmar
Location: Mayangon Township, Yangon Union of Myanmar
Phone:
Fax:
E-mail:
Web:
9 5-1-681753
9 5-1-681813
[email protected]; [email protected]
www.tritex.com.sg
Namibia
Southern Power Products
Location: Cape Town, South Africa
Phone:
Fax:
E-mail:
27-21-511-0653
27-21-510-304 9 [email protected]
Netherlands
Eberca
Location: , Netherlands
Phone:
Fax:
E-mail:
31 1866 21 9 55
31 1866 21818 [email protected]
Netherlands Antilles
Enertech N.V.
Location: Simpson Bay, St. Maarten/St. Martin, Netherlands
Antilles
Phone:
Fax:
E-mail:
Web:
+5 99 -551-2145
+5 99 -544-4608 [email protected]
www.enertechnv.com
Frostline
Location: Cole Bay, St. Maarten/St. Martin, Netherlands
Antilles
Phone:
Fax:
E-mail:
5 99 522 9 610 (Technical)
5 99 544 3263 [email protected] (technical); [email protected]
Hitchcraft Co.
Location: Curacao, Netherlands Antilles
Phone:
Fax:
E-mail:
5 999 667 334 9
501-641-2708 (US Line)
New Caledonia
Altomarine
Location: Noumea, New Caledonia
Phone:
Fax:
687 25 9 6 12
687 25 43 30
New Zealand
Whiting Power Systems
Location: 1 9 2 Herne Bay, Auckland, New Zealand
Phone:
Fax:
E-mail:
Web:
64 9 .358.2050
64 9 .358.0285
www.whiting.co.nz
Norway
Refnor A.S.
Location: Østerås, Norway
Phone:
Fax:
E-mail:
47-67 14 07 50
47-67 14 70 88 [email protected]
Oman
Mantech
Location: Dubai, United Arab Emirates
Phone:
Fax:
E-mail:
+( 9 71) 4-3332-542
+( 9 71) 4-3330-64 9 [email protected]
OHI Marine LLC
Location: Muscat, Oman
Phone:
Fax:
9 68-712240
9 68-712085
Pakistan
Breeze Marketing
Location: Karachi, Pakistan
Phone:
Fax:
E-mail:
+( 9 2-21) 5883662, 5380735 & 5883824
+( 9 2-21) 5883813 [email protected]
Mantech
Location: Dubai, United Arab Emirates
Phone:
Fax:
E-mail:
+( 9 71) 4-3332-542
+( 9 71) 4-3330-64 9 [email protected]
Panama
Evans International Services SA
Location: Panama City, Panama
Territory: Panama
Phone:
Fax:
E-mail:
Web:
507-232-5406
507-232-7648 [email protected]
www.evansint.com
Panama Yacht Sales and Service
Location: Panama City, Panama
Territory: Panama
Phone:
Fax:
E-mail:
507-314-3345
507-314-3346 [email protected]
Papua New Guinea
Lohberger Engineering Pty
Location: Port Moresby, NCD, Papua New Guinea
Phone:
Fax:
E-mail:
Web:
675-321-2122
675-321-2704 [email protected]
www.lohberger.com.pg
Peru
Corporación Frío Novo SAC
Location: Lima (La Molina), Peru
Phone:
E-mail:
(511) 451-5052 [email protected]
Philippines
Harbour Yacht Trading & Services Corp.
Location: Subic Bay, Philippines
Phone:
Fax:
E-mail:
+63 9 178 426166
+63 47 2525523 [email protected]
Portugal
PowerCool LDA
Location: Portimao, Portugal
Phone:
Fax:
E-mail:
Web:
351 9 1 786 63 73
351 282 461 818 [email protected]
www.powercool.org
Puerto Rico
Centro Cruisair de Puerto Rico
Location: Santurce, Puerto Rico
Phone:
Fax:
E-mail:
787-727-3637
787-727-3637 [email protected]
Cool-Tech Air Condition
Location: Fajardo, Puerto Rico
Phone:
Fax:
Web:
(787) 860-2615
(787) 801-2050 http://www.cooltechac.com/
May Day Marine
Location: San Juan, Puerto Rico
Territory: Puerto Rico, Dominican Republic
Phone:
Fax:
787-637-0756
787-7 9 0-2551
Suncool Air Conditioning
Location: Carolina, Puerto Rico, Puerto Rico
Phone:
Fax:
E-mail:
(787) 7 9 1-6 9 71
(787) 7 9 1-3885 [email protected]
Technical House (E.T.S. Inc.)
Location: San Juan, Puerto Rico
Territory: Sentry Battery Chargers Only
Phone:
Fax:
E-mail:
Web:
787-781-1313
787-781-2020 [email protected]
www.technicalhouse.com
Qatar
Al-Badi Trading Co.
Location: Doha, Qatar
Phone:
Fax:
E-mail:
9 74-4320715
9 74-4442888 [email protected]
Mantech
Location: Dubai, United Arab Emirates
Phone:
Fax:
E-mail:
+( 9 71) 4-3332-542
+( 9 71) 4-3330-64 9 [email protected]
Russia
Standarte
Location: Starbeevo, Moscow region, Russia
Phone:
Fax:
E-mail:
Web:
7 0 9 5 575 67 23
7 0 9 5 575 3 9 77 [email protected]
www.standarte.ru
Saudi Arabia
Mantech
Location: Dubai, United Arab Emirates
Phone:
Fax:
E-mail:
+( 9 71) 4-3332-542
+( 9 71) 4-3330-64 9 [email protected]
Samaco Marine Division
Location: Alnahdah dis Jeddah, Saudi Arabia
Phone:
Fax:
( 9 66) 2-6 99 -2300
( 9 66) 2-6 99 -1024
Scandinavia
Dometic Marine – Nordic Sales, Sales Company
Location: Halmstad, Sweden
Phone:
Fax:
E-mail:
Web:
46 35165700
46 35165710 [email protected]
www.dometic.com
L-0384 Revised: 05-03-07
Refnor A.S.
Location: Østerås, Norway
Phone:
Fax:
E-mail:
47-67 14 07 50
47-67 14 70 88 [email protected]
Singapore
Tripower Corporation Pte Ltd
Location: , Singapore
Phone:
Fax:
E-mail:
Web:
(65) 6861 1188
(65) 6861 4263 [email protected]; [email protected]
www.tritex.com.sg
Slovenia
Dometic Marine – Italy, Sales Company
Location: Milano, Italy
Phone:
Fax:
E-mail:
Web:
3 9 0362 44182
3 9 0362 452226 [email protected]
www.dometic.com
Nautica Centis di Nespolo Cinzia & C. Sne
Location: Bevazzana de Latisana (UD), Italy
Territory: Northeast Italy, Austria, Croatia, Slovenia
Phone:
Fax:
E-mail:
Web:
3 9 0-431-53-644
3 9 0-431-53-460 [email protected]
www.nauticacentis.it
South Africa
Southern Power Products
Location: Cape Town, South Africa
Phone:
Fax:
E-mail:
27-21-511-0653
27-21-510-304 9 [email protected]
Spain
Acastimar
Location: Tarragona, Spain
Phone:
Fax:
E-mail:
34 9 -77-362118
34 9 -77-362687 [email protected]
Sri Lanka
G&M Enterprises
Location: Borella-Colombo 8, Sri Lanka
Phone:
Fax:
E-mail:
9 4 11 26 9 1 9 66
9 4 11 26 9 1751 [email protected]
Sweden
Dometic Marine – Nordic Sales, Sales Company
Location: Halmstad, Sweden
Phone:
Fax:
E-mail:
Web:
46 35165700
46 35165710 [email protected]
www.dometic.com
Switzerland
Marine Parts Heimgartner
Location: Volketswil, Switzerland
Phone:
Fax:
E-mail:
Web:
41-199 7 40 9 0
41-199 7 40 9 4 [email protected]
www.marineparts.ch
Taiwan
Ing Hai Company, Ltd.
Location: Kaohsiung, Taiwan
Phone:
Fax:
E-mail:
886-7-802-180 9
886-7-802-180 9 [email protected]
Ing Hai Company, Ltd.
Location: Taipei, Taiwan
Phone:
Fax:
886-2-2531-2088
886-2-2523-6531
Thailand
Thai Kolon Co. Ltd.
Location: Bangkok, Thailand
Phone:
Fax:
E-mail:
Web:
66-2-745-6468-77 (10 lines)
66-2-745-6152 [email protected]
www.thaikolon.com
Trinidad
Nau-T-Kol Marine Refrigeration
Location: Chaguaramas, Trinidad
Phone:
Fax:
E-mail:
Web:
868-634-2174
868-634-2174 [email protected]
www.nautkol.com
Turkey
Dometic Marine - United Kingdom, Sales
Company
Location: Poole, Dorset, England
Phone:
Fax:
E-mail:
Web:
44 870 3306101
44 870 3306102 [email protected]
www.dometic.com
Egemar Muhendiscik Ltd.
Location: Tuzla, Istanbul, Turkey
Phone:
Fax:
E-mail:
Web:
9 0 216 4 9 4 2168
9 0 216 4 9 4 2218 [email protected]
www.egemar.com.tr
U.S. Virgin Islands
Coral Bay Marine Service
Location: St. John, U.S. Virgin Islands
Phone:
Fax:
340-776-685 9
340-776-685 9
Dr. Ice
Location: St. Thomas, US Virgin Islands
Territory: St. Thomas
Phone:
Fax:
E-mail:
340-5139 072
340-775-6576 [email protected];
Reefco, Inc.
Location: , St. Thomas, US Virgin Islands
Phone:
Fax:
E-mail:
Web:
(340) 776-0038
(340) 776-0038 [email protected]
www.reefco.net
St. Croix Marine Corp.
Location: St. Croix, U.S. Virgin Islands
Phone:
Fax:
E-mail:
340-773-028 9
340-778-8 9 74 [email protected]
Ukraine
Standarte
Location: Starbeevo, Moscow region, Russia
Phone:
Fax:
E-mail:
Web:
7 0 9 5 575 67 23
7 0 9 5 575 3 9 77 [email protected]
www.standarte.ru
United Arab Emirates
Mantech
Location: Dubai, United Arab Emirates
Phone:
Fax:
E-mail:
+( 9 71) 4-3332-542
+( 9 71) 4-3330-64 9 [email protected]
United Kingdom
Dometic Marine - United Kingdom, Sales
Company
Location: Poole, Dorset, England
Phone:
Fax:
E-mail:
Web:
44 870 3306101
44 870 3306102 [email protected]
www.dometic.com
Uruguay
Trimer S.A.
Location: Buenos Aires, Argentina
Phone:
Fax:
E-mail:
Web:
5411-4580-0444
5411-4580-0440 [email protected]
www.trimer.com.ar
Venezuela
Rich Marine Center
Location: Complejo Turistico El Morro, Venezuela, South
America
Phone:
Fax:
E-mail:
(58) 281 2181630
(58) 281-2811630 [email protected]
West Indies
Regis Electronics (St Lucia) LTD.
Location: St. Lucia, West Indies
Phone:
Fax:
E-mail:
Web:
758-452-0205
758-452-0206 [email protected]
www.regiselectronics.com
The Signal Locker
Antigua
Location: English Harbour, Antigua, West Indies
Phone:
Fax:
E-mail:
(268) 460-1528
(268) 460-1148 [email protected]
Zambia
Southern Power Products
Location: Cape Town, South Africa
Phone:
Fax:
E-mail:
27-21-511-0653
27-21-510-304 9 [email protected]
Zimbabwe
Southern Power Products
Location: Cape Town, South Africa
Phone:
Fax:
E-mail:
27-21-511-0653
27-21-510-304 9 [email protected]
L-0384 Revised: 05-03-07
Dometic Environmental Corporation
P.O. Box 15299 • Richmond, VA 23227 USA
Phone: 804-746-1313 • Facsimile: 804-746-7248 • www.cruisair.com • [email protected]
United States & Canada Service Only:
8:00 AM to 5:00 PM Eastern Time: 804-746-1313
24/7 A/C SERVICE HOTLINE: 5:00PM to 8:00 AM: 888-440-4494
International Sales & Service:
Europe & the Middle East: Call +44(0)870-330-6101
For all other areas visit our website to find your nearest distributor
L-2028
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 Warning
- 4 Notice
- 4 Introduction
- 4 Cuddy dc
- 4 Unpacking and Inspection
- 4 Safety Considerations
- 5 Placement Of System
- 5 Spacing Allowances & Unit Dimensions
- 6 How It Works
- 6 Mounting Brackets
- 6 Condensate Drains
- 6 Blower Assembly
- 6 and Transition Boxes
- 7 Ducting
- 7 Manual Control Panel Installation
- 7 Powered Zephyr
- 7 Powered Cuddy dc
- 8 Electrical System and Wiring for DC Powered Cuddy dc
- 8 Notice and ABYC Standards
- 8 Seawater Pump and Plumbing
- 9 (review prior to and after installation)
- 10 Operation
- 10 Troubleshooting Guidelines
- 12 Seawater Strainer
- 12 Condenser Coil Cleaning
- 12 Return Air Filters
- 12 Winterization