Technical Data Manual
Model Nos. and pricing: see Price List
V I I T O C E L L
1 0 0 V
Indirect-fired domestic hot water storage tank
42 to 119 USG / 160 to 450 ltr
Vitocell-V 100
42 to 79 USG / 160 to 300 ltr
Product may not be exactly as shown
Vitocell 100-V
CVA Series
Indirect-fired domestic hot water storage tank steel construction, with Ceraprotect two-coat enamel finish
Vitocell-V 100
119 USG / 450 ltr
5167 518 - 01 03/2014
Product Information
V I T O C E L L 1 0 0 -
The vertical tank solution for cost-efficient domestic hot water supply. The
Vitocell 100-V DHW tank offers storage capacities of up to 119 USG / 450 ltrs.
The benefits at a glance:
H Corrosion-protected steel tank shell with
Ceraprotect two-coat enamel finish.
Magnesium anode provides additional cathodic tank protection.
H Universally suitable - for applications requiring larger quantities of hot water, multiple Vitocell 100-V tanks may be connected to a header to form a tank battery.
H Heat exchanger coil extends to the bottom of the tank , thereby heating the entire water content.
H Increased energy savings thanks to highly effective, foamed-in-place HCFC-free insulation keeping standby losses at a minimum.
H Extremely convenient domestic hot water supply assured by fast, uniform heating via generously sized heat exchanger surfaces.
H The vitocell-V 100 119 USG / 450 L capacity tank is supplied with removable soft PET insulation for easier handling.
H Certified to CSA Low Lead Content
Certification Program; including US Safe Drinking Water Act,
NSF/ANSI 372 as well as other applicable
US State requirements .
VITOCELL 100-V
Product Information
Cross-Section
Magnesium anode
Steel domestic hot water storage tank, with Ceraprotect two-coat enamel finish
Recirculation tapping
Boiler water supply
2¼”/58 mm PUR Foam or 4”/100 mm wrap-around PET insulation (HCFC-free)
Boiler water return
Non-finned tubular steel heat exchanger coil with
Ceraprotect finish extends to tank bottom the entire water volume is heated, preventing cold spots where bacteria growth could occur
Product may not be exactly as illustrated.
VITOCELL 100-V 3
Technical Data
Technical Data
For domestic hot water heating applications in conjunction with hot water heating boilers
Storage Capacity
Recovery rate with a temperature rise
50 to 113
10 to 45
°
°
F /
C and boiler water supply temperature of.... at the supply flow rate stated
Recovery rate
*1
*1 with a temperature rise
194 °F
90 °C
USG ltr
MBH
GPM ltr/h
176 °F
80 °C
MBH
GPM ltr/h
158 °F
70 °C
MBH
GPM ltr/h
140 °F
60 °C
122 °F
50 °C
194 °F
90 °C
MBH
GPM ltr/h
MBH
GPM ltr/h
MBH
GPM ltr/h
Suitable for heating systems with
H max. working pressure on the heat exchanger side of up to 150 psig / 10 bar
H max. working pressure on DHW side of up to 150 psig / 10 bar
H max. supply temperature on the heat exchanger side of up to 230 °F / 110 °C
H max. DHW supply temperature of up to 150 °F / 65.6 °C
42
160
53
200
79
300
119
450
136
4.3
982
109
3.5
786
136
4.3
982
109
3.5
786
180
5.7
1302
150
4.8
1081
238
7.6
1720
198
6.3
1425
85
2.7
614
58
1.8
417
31
1
221
123
2.7
619
85
2.7
614
58
1.8
417
31
1
221
123
2.7
619
113
3.6
811
78
0.3
565
61
1.9
442
153
3.4
774
153
4.9
1106
109
3.5
786
82
2.6
589
181
4
911
50 to 140 ° F /
10 to 60 ° C and boiler water supply temperature of.... at the supply flow rate stated below
Supply flow rate for the recovery rates stated
Standby losses *2
176 °F
80 °C
158 °F
70 °C
Overall dimensions with insulation
Width ( ∅ )
Depth
Height
Tilt height
Weight
Tank with insulation
MBH
GPM ltr/h
MBH
GPM ltr/h
GPM m 3 /h
MBH/24 h inches mm inches mm inches mm inches mm lbs kg
Heating water content
Heat exchanger surface area
USG ltr ft.
2 m 2
Connections
Heating water supply/return
Recirculation
∅ ” (male thread)
∅ ” (male thread)
∅ ” (female thread)
∅ ” (male thread)
95
2
482
65
1.4
327
13.2
3.0
5.1
23
581
24
608
47
1189
50
1260
190
86
1.45
5.5
10.8
1
1
95
2
482
65
1.4
327
13.2
3.0
5.8
23
581
24
608
55½
1409
57½
1460
214
97
1.45
5.5
10.8
1
1
116
2.6
584
78
1.7
395
13.2
3.0
7.5
25
633
27¾
705
68¾
1746
70½
1792
333
151
2.6
10
16.1
1.5
1
150
3.3
756
113
¾ ¾ 1
*1 When planning for the recovery rate as stated or calculated, allow for the corresponding circulation pump. The stated recovery rate is only achieved when the rated output of the boiler is equal to or greater than that stated under “Recovery rate”.
Please also refer to the corresponding sizing chart at the end of this manual.
*2 Measured values are based on a room temp. of 68°F / 20 ºC and a domestic hot water temp. of 149°F / 65 ºC and can vary by 5%.
2.5
567
13.2
3.0
9.6
1
1
33½
850
35¼
898
77
1955
73¼
1860
399
181
3.3
12.5
20.5
1.9
VITOCELL 100-V
Technical Data
Vitocel 100l-V (42 and 53 USG / 160 and 200 ltr )
IO
MA
TPV
DHW
RT
BWS
AQ
BWR
Overall depth h
DCW/D
Vitocell 100-V (79 USG / 300 ltr)
IO
TPV
MA
DHW
RT
BWS
IO
AQ
BWR g
Overall depth h
DCW/D
Vitocell 100-V (119 USG / 450 ltr)
IO
MA
RT
DHW
Ø 25½” / 650 mm
AQ
IO BWS f
Dimensions
Storage capacity
USG ltr a b c d e g h j Ø inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm inches mm
53
200
884
41
1270
––
––
12½
317
––
––
––
––
2¾
72
9¾
249
25
634
35
42
160
884
41
1050
––
––
12½
317
––
––
––
––
2¾
72
9¾
249
25
634
35
79
300
1115
63
1600
26
660
13½
343
4½
114
13
336
3
76
10
260
34½
875
44
119
450
1230
70¼
1784
33
837
18
455
4½
114
16½
422
4
107
13¾
349
36¼
924
48½
Legend
IO Inspection and clean-out opening
D Drain
BWR Boiler water return
BWS Boiler water supply
DCW Domestic cold water
AQ Aquastat well
(at same height as boiler water supply connection)
MA Magnesium anode
DHW Domestic hot water
RT Recirculation tapping
TPV Temperature and pressure relief valve
BWR g
Overall depth h
DCW/D
VITOCELL 100-V 5
Technical Data
Domestic hot water draw rate
Storage tank contents heated to 140 °F / 60 °C, boiler not reheating
Storage capacity USG ltr
42
160
DHW draw rate
Domestic hot water draw
Water with t = 140 °F /
60 °C (constant)
Percentage tank volume
GPM ltr/min
USG ltr
2.6
10
32
120
75%
53
200
2.6
10
38
145
73%
79
300
4.0
15
63
240
80%
Heat-up time
The stated heating times are achieved when the maximum recovery rate of the domestic hot water tank is made available at the respective supply temperature and with a domestic hot water rise from 50 to 140 °F / 10 to 60 °C.
Storage capacity USG ltr
42
160
53
200
79
300
119
450
Heating water supply temperature
194 °F / 90 °C
176 °F / 80 °C
158 °F / 70 °C
19
24
34
Heat-up time (minutes)
19
24
37
23
31
45
28
36
50
Pressure drop on heating water side (primary circuit) Pressure drop on domestic hot water side
(secondary circuit)
119
450
4.0
15
111
420
93%
200
160
120
500
400
300
80 200
40 100
32 80
24 60
20 50
16 40
12 30
8 20
40
32
24
20
16
100
80
60
50
40
12 30
8 20
4 10
3.2
8
2.4
6
2 5
1.6
4
1.2
3
0.8
2 4
3.2
2.4
2
1.6
10
8
6
5
4
Flow rate ltr/h
GPM
0.4
1
8 10 13 17
2.2
2.6
3.5
4.4
Flow rate
33
8.8
50 67 83 100 ltr/min
13 18 22 26 GPM
42 USG / 160 ltr and 53 USG / 200 ltr storage capacities
79 USG / 300 ltr storage capacity
119 USG / 450 ltr storage capacity
VITOCELL 100-V
Multiple Tank Installation (79 and 119 USG / 300 and 450 ltr only)
Technical Data
The 79 and 119 USG / 300 and 450 ltr tank sizes may be combined into a battery consisting of between 2 and 4 tanks.
Tank batteries consisting of more than 4 tanks can be installed by creating up to 4 batteries, each consisting of 4 tanks. The heating contractor is responsible to ensure proper piping on both the primary and secondary circuits.
Tank storage capacity USG ltr
79
300
119
450
Total capacity of tank battery
Number of storage tanks
USG ltr
159
600
2
FF
238
900
2
FF
357
1350
3
FFF
476
1800
4
FFFF
Recovery rate *1 with a temperature rise
194 °F
90 °C
50 to 113 ° F /
10 to 45 ° C and boiler water supply temperature of .....
at the supply flow rate
Recovery rate *1 with a temperature rise
176 °F
80 °C
158 °F
70 °C
140 °F
60 °C
122 °F
50 °C
194 °F
90 °C
MBH
GPM ltr/h
MBH
GPM ltr/h
MBH
GPM ltr/h
MBH
GPM ltr/h
MBH
GPM ltr/h
MBH
GPM ltr/h
361
11.5
2604
300
9.5
2162
225
7.1
1622
157
5
1130
123
3.9
884
307
6.8
1548
477
15.1
3440
396
12.5
2850
307
9.7
2212
218
6.9
1572
164
5.2
1178
361
8.0
1822
716
22.7
5160
593
18.8
4275
460
14.6
3318
327
10.4
2358
246
7.8
1767
542
12.0
2733
955
30.3
6880
791
25.1
5700
614
19.5
4424
436
13.8
3144
327
10.4
2356
723
16.0
3644
50 to 140 ° F /
10 to 60 ° C and boiler water supply temperature of .....
at the supply flow rate stated below
Supply flow rate for the recovery rates stated
Standby losses *2
Overall dimensions with insulation
Overall width
Overall depth
Overall height
176 °F
80 °C
158 °F
70 °C
MBH
GPM ltr/h
MBH
GPM ltr/h
GPM m 3 /h
MBH/24 h inches mm inches mm inches mm
232
5.1
1168
157
3.5
790
26.4
6
15
300
6.7
1512
225
5.0
1134
26.4
6
19.2
450
10.0
2268
338
7.5
1701
39.6
9
28.8
600
13.3
3024
450
10.0
2268
50.8
12
38.4
57½
1461
43½
1109
69
1752
736¼
334
72½
1838
48
1218
77
1955
932
423
111¼
2826
48
1218
77
1955
1409
639
Weight
Tank with insulation lbs kg
Heating water content
(heat exchanger pipe coil)
USG ltr
6½
25
8½
32
13¾
50
20¾
79
Heat exchanger surface area ft.
2 m 2
32¼
3.0
42
3.9
62½
5.8
*1 When planning for the recovery rate as stated or calculated, allow for the corresponding circulation pump. The stated recovery rate is only achieved when the rated output of the boiler is equal to or greater than that stated under “Recovery rate”.
Please also refer to the corresponding sizing chart at the end of this manual.
*2 Measured values are based on a room temperature of 68°F / 20 ºC and a domestic hot water temperature of 149°F / 65 ºC and can vary by 5%.
84
7.8
150
3814
48¾
1237
77
1955
1913
868
VITOCELL 100-V 7
Multiple Tank Installation (79 and 119 USG / 300 and 450 ltr only)
For domestic hot water applications which utilize modulating and low temperature hot water heating boilers or remote heating plants
Qty 2 Qty 3 Qty 4
IO
DHW
TPV
BWR
RT
A
BWS
BWR
IO
BWR
DHW/
D e
Side view
Legend
IO Inspection and clean-out opening
D Drain
A Air vent
Dimensions
Storage capacity
Total capacity of battery
USG ltr
USG ltr
Number of storage tanks a b c d e h inches mm inches mm inches mm inches mm inches mm inches mm
Depth
Top view
BWR Boiler water return
BWS Boiler water supply
DCW Domestic cold water
79
300
159
600
2
3
76
10¼
260
34½
875
63
1600
16½
343
8
206
BWR
A
BWS
Depth
A
BWS
Depth
238
900
2
4¼
107
13¾
349
36¼
924
70¼
1784
18
455
12½
315
DHW Domestic hot water
RT Recirculation tapping
TPV T&P valve
119
450
357
1350
3
4¼
107
13¾
349
36¼
924
70¼
1784
18
455
12½
315
A
BWS
476
1800
4
4¼
107
13¾
349
36¼
924
70¼
1784
18
455
12½
315
VITOCELL 100-V
Multilple Tank Installation (79 and 119 USG / 300 and 450 ltr only)
Domestic hot water draw rate
Storage tank content heated to 140 °F / 60 °C
Storage capacity USG ltr
Battery storage capacity USG ltr
Number of tanks
DHW draw rate
Domestic hot water draw
Water with t = 140 °F /
60 °C (constant)
Percentage of battery volume
GPM ltr/min
USG ltr
79
300
159
600
2
7.9
30
127
480
80%
238
900
2
7.9
30
222
840
84%
Quick recovery (over 10-minute period)
Domestic hot water rise from 50 to 113 °F / 10 to 45 °C
Storage capacity USG ltr
Battery storage capacity USG ltr
Number of tanks
Heating water supply temperature
194 °F / 90 °C
176 °F / 80 °C
158 °F / 70 °C
USG/10 min ltr/10 min
USG/10 min ltr/10 min
USG/10 min ltr/10 min
79
300
159
600
2
238
900
2
119
450
357
1350
3
201
759
197
745
192
728
Quick DHW recovery (over 10-minute period)
317
1200
310
1175
284
1075
441
1670
431
1630
396
1498
Max. domestic hot water draw rate (over 10-minute period)
Domestic hot water rise from 50 to 113 °F / 10 to 45 °C
Storage capacity USG ltr
Battery storage capacity
Number of tanks
Heating water supply temperature
USG ltr
194 °F / 90 °C
176 °F / 80 °C
158 °F / 70 °C
GPM ltr/min
GPM ltr/min
GPM ltr/min
79
300
159
600
2
20.1
76
20
74
19.3
73
119
450
238
900
2
357
1350
3
Max. DHW draw rate (over 10-minute period)
32
120
31.3
118
28.4
107
44.1
167
43.2
163
40
150
119
450
357
1350
3
7.9
30
333
1260
84%
476
1800
4
11.9
45
444
1680
84%
476
1800
4
54
204
50.4
190
48
181
476
1800
4
540
2045
502
1900
478
1810
VITOCELL 100-V 9
Standard Equipment
Product Installation
Standard Equipment
Vitocell 100-V
42 to 79 USG / 160 to 300 ltr capacity
Domestic hot water storage tank of high-grade steel with PUR Foam insulation
(HCFC-free) and Ceraprotect two-coat enamel finish with:
H thermometer
H adjustable leveling feet
H built-in aquastat well
H Magnesium anode
Vitocell 100-V
119 USG / 450 ltr capacity
Domestic hot water storage tank of high-grade steel with wrap-around soft PET insulation (HCFC-free) and Ceraprotect two-coat enamel finish with:
H thermometer
H adjustable leveling feet
H
H built-in aquastat well
Magnesium anode
The following is packed separately and attached to the crate:
H installation fittings package: with the necessary brass adaptors, other necessary hardware, and hemp
H temperature and pressure relief valve.
The following is packed separately and attached to the crate:
H installation fittings package: with the necessary brass adaptors, other necessary hardware, and hemp
H temperature and pressure relief valve.
Electrostatically powder-coated sheet metal enclosure panel in a Vitosilver finish.
Synthetic wrap-around enclosure panel in a
Vitosilver finish.
Domestic hot water connections
IMPORTANT
This is a simplified conceptual drawing only! Piping and necessary componentry must be field verified. Proper installation and functionality in the field is the responsibility of the heating contractor.
Domestic hot water supply
DHW recirculation line
DHW recirculation pump
Spring-loaded flow check valve
Discharge pipe
Temperature and pressure relief valve
(TPV)
Shut-off valve
Drain
Domestic cold water supply lines
Backflow preventer
Domestic cold water inlet
Precharged expansion tank
(required where backflow preventer is installed; check local plumbing codes and requirements)
Thermostatic mixing valve/anti-scald valve for solar applications (field supplied)
VITOCELL 100-V
Product Installation
Backflow preventers
Where backflow preventers are required, a domestic water expansion tank installation is recommended in the cold water inlet piping before the cold water enters the
Vitocell. For the backflow device, observe local plumbing codes and regulations.
Warranty
Our warranty for domestic hot water tanks states that the water heated must be of drinking (potable) water quality and that any water treatment equipment in use must function correctly.
Temperature and pressure relief valve
A temperature and pressure relief valve
(T&P relief valve) is supplied with the tank.
The heating contractor must install the valve on each tank in a method meeting code requirements. If local codes require a different relief valve, substitute the manufacturer’s supplied valve. The tank is approved for 150 psig. Maximum operating pressure is 150 psig.
The T&P relief valve supplied with the tank is tested under ANSI Z21.22 Code for Relief
Valves and Automatic Gas Shut-off Devices for Hot Water Supply Systems.
Viessmann accepts no responsibility for damage howsoever caused and reserves the right to withdraw the product warranty if the product has been improperly installed or misapplied by the installer, contractor or final user. In order to qualify for product warranty, strict adherence to the installation and service manuals must be assured. In the event that Viessmann non-approved components are utilized, Viessmann reserves the right to withdraw all expressed or implied warranties without written notice.
The water to be heated with the Vitocell must be drinking (potable) water quality. If the tank is used to heat other media, the warranty will be null and void. Damage resulting from excessive pressure or temperature is clearly not the responsibility of Viessmann.
IMPORTANT
Since the heat exchanger coil allows for high MBH input (see Vitocell flow charts), confirmation that the appropriate and correct size pressure and temperature relief valve is used and installed, is necessary.
The amount of chloride and sulfate acceptable to the tank is limited. In areas where high concentrations of chloride and sulfate are present in drinking water, please consult Viessmann for directions.
Sensor Well
Vitocell 100-V
42 to 119 USG / 160 to 450 ltr capacity
The sensor well is welded into the domestic hot water storage tank.
8” / 200 mm
Ø ½”/
14.9 mm
Watts Model
40XL-8
ASME pressure steam rating
CSA temperature steam rating
Relief temperature
Inlet thread
Outlet thread
150 psig
(US and Canada)
1438 MBH
205 MBH
210ºF (99ºC)
¾” male
¾” female
VITOCELL 100-V 11
Vitocell 100-V Sizing
Continuous Flow Capacity Chart
Vitocell 100-V,
42 and 53 USG / 160 and 200 ltr capacities
Curve
Domestic hot water 40 to 113°F / 4 to 45°C
Curve
Domestic hot water 40 to 140°F / 4 to 60°C
VITOCELL 100-V
Vitocell 100-V,
79 USG / 300 ltr capacity
Curve
Domestic hot water 40 to 113°F / 4 to 45°C
Curve
Domestic hot water 40 to 140°F / 4 to 60°C
Vitocell 100-V Sizing
Continuous Flow Capacity Chart
VITOCELL 100-V 13
Vitocell 100-V Sizing
Continuous Flow Capacity Chart
Vitocell 100-V,
119 USG / 450 ltr capacity
Curve
Domestic hot water 40 to 113°F / 4 to 45°C
Curve
Domestic hot water 40 to 140°F / 4 to 60°C
VITOCELL 100-V
Vitocell 100-V Sizing
Continuous Flow Capacity Chart
Example: Vitocell 100-V, 119 USG / 450 ltr capacity
Assume boiler output to tank is 170 MBH. Enter chart at left and draw horizontal line across to recovery rate of 203 GPH / 3.4 GPM for
140°F / 60°C domestic hot water under column B. Where the horizontal line intersects the 194°F / 90°C curve is the point of intersection for the diagonal line used to size the pump. The diagonal line begins at the origin and goes through the point of intersection extending up to the top of the chart. Read between the reference diagonal lines to get a pump specification of 11.9 GPM at 5 ft. To summarize: For a
Vitocell-V 100 with 119 USG / 450 ltr capacity and 170 MBH input, the boiler water temperature is 194°F / 90°C, difference between boiler return and supply water temperature is 31°F / 17°C, recovery rate is 3.4 GPM of 140°F / 60°C DHW, and the pump required is
11.9 GPM, 5.0 ft. plus pressure drop in piping and boiler.
VITOCELL 100-V 15
VITOCELL 100-V