Company Owning or
Operating Facility
Building/unit
Site Address
Contact person
Telephone email
1. System Configuration
Single channel stand-alone system
Single channel with remote repeater
Single TTDM with TTSIM network
Multiple TTDM network system
Other:
2. TTDM Installation Inspection
Visual Inspection
Seating of circuit boards
Wiring (check all that are applicable)
Ground/earth
Power supply wiring
Sensing cable
Zener barrier
Fault relay
Leak relay
Service relay
4-20 mA
Host port (RS-232 / RS-485)
RS-485 SIM network port
TT-NRM
Internal SIM
(Quantity: )
External TTSIM (Quantity: )
3. TTDM Initial Power up Test
Close enclosure and supply power to the unit.
Green LED illuminated at first
Passes self-tests
Finds all connected SIM, TTSIM, and TT-NRM modules
Commissioning Record
TraceTek Leak Detection System
TTDM-128 Alarm & Locating Module
Authorized TraceTek service company
Address
Contact person
Telephone email
4. General settings
Language selected:
Affix front panel label in chosen language
Change time/date to local time
5. Self Tests with UI Software
UI Test
Memory Tests
SI Test
Audio Tests
Display Test
Keypad
Alert response personnel before testing relays or other
interfaces (if connected):
Relay Test
4-20 mA Test (if installed and connected)
Host port comm. Loop back test (requires transmit/receive jumper)
6. Leak and Port Settings
Leak Default Other
Re-alarm interval Never __________
Auto-Reset
Audible Alarm
Alarm re-flash
Off
On
Off
Single
On
Off
On
All Alarm Reset
Host port
Baud 9600
485 Address
Mode switch
TTDM
1
RS 232
Master
__________
__________
RS 485
Slave
1
R
Commissioning Record
TraceTek Leak Detection System
TTDM-128 Alarm & Locating Module
Complete a copy of this page for each SIM or TTSIM installed in the system.
7. Application
Beneath raised floor
Double contained piping
Double contained tanks
Buried pipeline
Sumps
Trench
AST
Overhead piping
10. Relay configuration
Complete this section for TTSIM-1A or TTSIM-2 modules, or when TT-NRMs are installed.
TT-NRM Regions and Relays:
Trouble relay
Other:
Service relay
TraceTek Sensors connected:
Type Approx. length
# Start End ID
1
TT1000 water sensing
TT3000 conductive liquids
TT5000 fuel sensing
TT5001 solvent sensing
Other:
Other:
8. Setup
Visual Inspection
2
3
4
5
6
7
8
9
10
Wiring (check all that are applicable)
Ground/earth
Power supply wiring
Sensing cable
Zener barrier
Internal SIM
External TTSIM (Quantity: )
RS-485 connection
9. Sensor and System Settings
At the TTDM, select this channel then press the down arrow and record:
SIM Address
ID
Status
Test length
RG Resistance
YB Resistance
SI Version
SI Comm
Sense Current
Service alert >=
Sense Resistance
Leak alarm <=
ft / m / z
µA
µA
K
Ω
K
Ω
Ω
Ω
%
SIM relay:
Alarm mode
Alarm state
Alarm reset
Leak
On
Auto
Leak/Break
Off
Manual Safe
11. Sensor Mapping
Record TTDM-128 Leak location reading for simulated leaks created at key points on the system:
Location TTDM leak location
Ft / m
Ft / m
Ft / m
Ft / m
Ft / m
Ft / m
Ft / m
Ft / m
12. Acceptance Test
When sensor is subjected to a simulated leak
Ft / m
System detects and locates simulated leak
Acceptance test was performed in presence of owner’s representative:
Yes No
2
R
13. Operation and Maintenance Training
This documentation was provided and reviewed with the end user:
Project specific documents:
General installation instructions:
General instructions for commercial buildings
General instructions for environmental applications
Sensor installation instructions:
TT1000 modular sensing cables
TT3000 and TT5000 series modular sensing cables
TT3000 and TT5000 series bulk sensing cables
TTDM-128 Documentation:
TTDM-128 Installation Instructions
TTDM-128 User Manual
Commissioning Record
TraceTek Leak Detection System
TTDM-128 Alarm & Locating Module
Tyco, TraceTek and the TraceTek logo are trademarks or registered trademarks of Tyco Thermal Controls LLC or its affiliates.
Signatures
Test performed by:
Client acceptance:
Name
Name
Signature
Signature
Date
Date
Copies to: 1) Client 2) TraceTek service representative