advertisement
CAS-2700-24
SMA Gateway
Modbus / BACnet / HTML Gateway
CAS-2700-24
SMA
Modbus (RTU and TCP) / BACnet / HTML Gateway
©2014 Chipkin Automation Systems , 3381 Cambie St- Box 211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
Email : [email protected] Website: www.chipkin.com
Blank Page
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 3 of 62
TABLE OF CONTENTS
TABLE OF CONTENTS ..........................................................................................................................3
1.
SMA Gateway Description ...........................................................................................................6
2.
Connections ................................................................................................................................7
2.1. Block Diagram ................................................................................................................................. 7
2.2. Wiring / Connections ...................................................................................................................... 8
2.2.1.
Modbus RTU Connections ....................................................................................................... 8
2.3. Limitations and Best Practices ........................................................................................................ 9
3.
Configuration and Settings ........................................................................................................ 10
3.1. SMA Sunny Webbox Connection Settings .................................................................................... 10
3.2. SMA Sunny Webbox Configuration Options ................................................................................ 10
3.3. ModbusTCP Settings ..................................................................................................................... 11
3.4. ModbusRTU Settings .................................................................................................................... 11
3.5. BACnet IP Settings ........................................................................................................................ 12
3.6. Change Configuration Settings ..................................................................................................... 12
3.7. Adding SMA Devices ..................................................................................................................... 14
3.8. Configuration Tools ...................................................................................................................... 15
4.
Reading Data using HTML / Web Browser .................................................................................. 16
5.
Reading Modbus Data ............................................................................................................... 17
5.1. Modbus Function Supported (RTU and TCP) ................................................................................ 17
5.2. SMA Modbus Data Map ............................................................................................................... 17
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 4 of 62
5.3. Interpreting Modbus Data ............................................................................................................ 25
5.4. Test Procedure – Use CAS Modbus Scanner ................................................................................ 26
6.
Reading BACnet Data ................................................................................................................ 29
6.1. Most Common BACnet Problem .................................................................................................. 29
6.2. Interpreting BACnet Data ............................................................................................................. 29
6.3. BACnet Objects ............................................................................................................................. 29
6.4. BACnet Test Procedure................................................................................................................. 38
7.
Commissioning, Diagnostics and Trouble Shooting ..................................................................... 44
7.1. What to Take to Site for Commissioning ...................................................................................... 44
7.2. Gateway Status ............................................................................................................................. 48
7.3. Gateway Diagnostics .................................................................................................................... 48
7.4. Debug log. ..................................................................................................................................... 49
7.5. Veeder Device Connection ........................................................................................................... 51
7.6. Another Method for Changing the IP Address - DHCP ................................................................. 53
7.7. Discovering the Gateway .............................................................................................................. 54
7.8. Downloading New Firmware ........................................................................................................ 54
8.
Specifications ............................................................................................................................ 56
9.
SMA Enumerations .................................................................................................................... 57
9.1. SMA Invertor Data Enumerations ................................................................................................ 57
9.1.1.
Mode ..................................................................................................................................... 57
9.1.2.
Grid Type ............................................................................................................................... 57
9.1.3.
Balancer................................................................................................................................. 57
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 5 of 62
9.1.4.
Backup State .......................................................................................................................... 57
9.1.5.
Error ....................................................................................................................................... 58
9.2. SMA Sunny Island Data Enumerations ......................................................................................... 59
9.2.1.
Mode ..................................................................................................................................... 59
9.2.2.
Invertor Operating State (InvOpStt) ...................................................................................... 59
9.2.3.
Relay State (Rly1Stt, Rly2Stt) ................................................................................................. 59
9.2.4.
Battery Charging Process (BatChrgOp) ................................................................................. 59
9.2.5.
Absorption Phase (AptPhs) .................................................................................................... 59
9.2.6.
GnDmdSrc .............................................................................................................................. 59
9.2.7.
GnStatus ................................................................................................................................ 60
9.2.8.
GnRnStatus ............................................................................................................................ 60
9.2.9.
CHPStatus .............................................................................................................................. 60
9.2.10.
Address (Adr) ..................................................................................................................... 60
9.2.11.
Operating Status (OpStt) ................................................................................................... 60
9.2.12.
Card Status (CardStt) ......................................................................................................... 61
9.2.13.
Error ................................................................................................................................... 61
10.
Revision History ..................................................................................................................... 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
1.
SMA Gateway Description
Page 6 of 62
The SMA Gateway connects to a SMA Sunny Webbox via an Ethernet (TCP/IP) connection. The SMA
Gateway can then be configured to poll for data values from a number of devices that are connected to the Webbox. These devices can be Sunny Invertors, SensorBox, or Sunny Islands.
After configuration, the Gateway will poll and read the data from the SMA devices and stores it internally. When a remote system requests data, this data is served in a form that is appropriate to the requesting protocol (Modbus TCP/RTU or BACnet). In the event that the connection to the SMA
Webbox is lost, or data cannot be read, the gateway can signal this to the remote data clients by changing all the values currently stored to a predefined default value.
The Gateway requires configuration that will be described later in this document.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
2.
Connections
2.1.
Block Diagram
Page 7 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
2.2.
Wiring / Connections
Page 8 of 62
2.2.1.
Modbus RTU Connections
Port 0 – RS485 Mode Terminals
All 4 jumpers required for 2 wire operation.
CAS recommends the use of 3 conductors for so called 2-Wire RS485.
The signal common is there for purpose.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
2.3.
Limitations and Best Practices
Page 9 of 62
Maximum Number of SMA Sunny Webboxes per Gateway
Only 1 SMA Sunny Webbox can be connected to a single gateway.
RS232 Best Practices
We recommend a maximum of 30ft for the RS232 cable. A well-made cable in a clean environment can easily run to 100ft and provide satisfactory performance.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
3.
Configuration and Settings
Page 10 of 62
3.1.
SMA Sunny Webbox Connection Settings
To poll for data from a Sunny Invertor, Sunny Island, or SensorBox all that is needed is the IP address of the Sunny Webbox that these devices are connected to.
3.2.
SMA Sunny Webbox Configuration Options
The following options are set to determine how the data from the SMA devices is handled.
- Night Data – SMA Invertors turn off at night. By enabling this option and selecting one of the Night data methods, empty values will be replaced with either a zero value or the last successfully polled value.
- Night Data Method o Use Default Value – Uses the supplied default value to represent Invertor data at night.
o Use Last Polled Values – Uses the last successfully polled Invertor data to represent
Invertor data at night. If no such data is available, the supplied default value is used.
- Default Value – The value that all points are set to initially and when the device is disconnected or offline.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 11 of 62
3.3.
ModbusTCP Settings
To connect using ModbusTCP you need to know the IP address of the gateway and the Modbus
‘Station’ number (also known as ‘Device Address’ or ‘Node ID’) and the TCP Port for the connection.
The following are the configurable parameters for this connection:
Modbus Station Number (Default value is 1)
Modbus TCP Port (Default value is 502)
Review section 7.6 Another Method for Changing the IP Address - DHCP to see the default IP
Address settings and how to change them.
3.4.
ModbusRTU Settings
To connect using ModbusRTU you need to set the connection parameters correctly and the
Modbus ‘Station’ number (also known as ‘Device Address’ or ‘Node ID’)
- Modbus Station Number (Defaut value is 1)
- Connection Parameters : o Baud Rate – 1200, 2400, 4800, 9600 (Default), 19200, 38400, 76800,
115200 o Data Bits – 8 (Default), 7 o Parity – None (Default), Odd, Even o Stop Bits – 1 (Default), 2
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
3.5.
BACnet IP Settings
Page 12 of 62
BACnet supports discovery. Thus any BACnet tool will discover the gateway and report its properties. Each gateway must be allocated a unique device instance number and thus this is a configurable setting.
The configurable BACnet IP connection settings are:
Device Instance Number (Default value is 389001)
Port
Network
(Default value is 47808)
(Default value is 0)
It is important to note that BACnet messages cannot pass from one subnet to another without a
BACnet technology called BBMD installed. The easiest installation and the best way to avoid this complication is to set the gateway’s IP address so that it is on the same subnet as the BACnet data client (usually the BAS / Scada system).
Review section 7.6 Another Method for Changing the IP Address - DHCP to see the default IP
Address settings and how to change them.
3.6.
Change Configuration Settings
Use a Web Browser and type the following into the address bar: http://192.168.1.113/ bin/sma/config/
IP Address of your unit.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 13 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 14 of 62
Change the Settings and click Submit to save them. To cancel changes simply close the page without submitting.
Note on IP Addresses: Another method is provided to change the Netmask and Gateway address.
Changes do not take effect until the device restarts. Use the Reset button the web page or recycle the power.
3.7.
Adding SMA Devices
Parameters:
Device Name – Name of the device, usually contains serial number, get this value by running the RPC Client application, see 3.8 Configuration Tools.
IP Address – IP address of the Sunny Webbox that the device is connected to
Device Type – Select one of Invertor, SensorBox, or Sunny Island
Scan – The polling interval, defaulted to 30 seconds.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 15 of 62
3.8.
Configuration Tools
In order to complete the configuration process, the names and serial numbers of the SMA devices are needed.
There is a tool that is required to get this information called the RPC Client.
Please contact Chipkin Automation Systems to get access to this tool and for help with configuration.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
4.
Reading Data using HTML / Web Browser
Page 16 of 62
Use a Web Browser to browse to this page. http://192.168.1.113/bin/sma/report
This is the IP address of your gateway
You are presented with a screen similar to this one.
This screen is useful for seeing the current BACnet and Modbus mappings as well as the current value of the data point, which is useful for quickly checking that the connections are good and data is being read.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
5.
Reading Modbus Data
Need to know more about Modbus? Read this guide. http://www.chipkin.com/september-2010-newsletter
Page 17 of 62
5.1.
Modbus Function Supported (RTU and TCP)
The Gateway supports functions 1, 2, 3, and 4. Most masters should be configured to use function 3 (Read Holding Registers). However it will respond to polls that use the other functions with offset equal to zero. You can read this data as 3xxxx, 1xxxx, 0xxxx or 4xxxx data.
5.2.
SMA Modbus Data Map
For the following registers, each set of data (Invertor, SensorBox, and Sunny Island) will be described as if it was the first device configured. Each additional device added will be offset by
100. So the first device will have data starting at 40001, the second device will have data starting at 40101, the third device will have data starting at 40201, etc.
Typical Invertor Data
Modbus Address Value Stored
40001 BackUp State
40002
40003
40004
Balancer
CO2 Saved
Error
40005
40006
40007
E-Total
Event-Cnt
Fac
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 18 of 62
40008
40009
40010
40011
40012
40013
40014
40015
Grid Type h-On h-Total
Iac
Ipv
Mode
Pac
Power On
40016
40017
40018
40019
Temperature
Vac
Vpv
Serial Number
40020
40021
40022
40023
40024
40025
VacL1
VacL2
Vpv-PE
Max Temperature
Max Vpv
Vfan
Note 1: Balancer, Error, Mode, Grid Type are enumerated values. See section 9: SMA
Enumerations for more information
Note 2: All of these values will be sent a 16 bit values, therefore any real (decimal) values will be sent as their whole number part (i.e. 24.3 will be sent as 24). If you require the entire decimal value, please contact Chipkin Automation Systems.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
40005
40006
40007
40008
40009
Typical SensorBox Data
Modbus Address Value Stored
40001
40002
40003
40004
ExlSollrr
IntSollrr
OpTm
TmpAmb F
TmpMdul F
TmpAmb C
TmpMdul C
WindVel m/s
WindVel mph
Page 19 of 62
Note 1: All of these values will be sent a 16 bit values, therefore any real (decimal) values will be sent as their whole number part (i.e. 24.3 will be sent as 24). If you require the entire decimal value, please contact Chipkin Automation Systems.
Typical Sunny Island Data
Modbus Address Value Stored
40001 Adr
40002 AptPhs
40003 AptTmRmg
40004 BatChrgOp
40005 BatChrgVtg
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
40006 BatSoc
40007 BatSocErr
40008 BatTmp
40009 BatVtg
40010 CardStt
40011 ChpPwrAt
40012 ChpRmgTm
40013 ChpStrRmgTm
40014 ChpStt
40015 EgyCntIn
40016 EgyCntOut
40017 EgyCntTm
40018 Error
40019 E-Total
40020 E-Total-In
40021 ExtCur
40022 ExtCurSlv1
40023 ExtCurSlv2
40024 ExtCurSlv3
40025 ExtFrq
40026 ExtPwrAt
40027 ExtPwrAtSlv1
Page 20 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
40028 ExtPwrAtSlv2
40029 ExtPwrAtSlv3
40030 ExtPwrRt
40031 ExtPwrRtSlv1
40032 ExtPwrRtSlv2
40033 ExtPwrRtSlv3
40034 ExtVtg
40035 ExtVtgSlv1
40036 ExtVtgSlv2
40037 ExtVtgSlv3
40038 Fac
40039 Firmware
40040 FwVer
40041 FwVer2
40042 GdCtcCnt
40043 GdEgyCntIn
40044 GdEgyCntOut
40045 GdEgyTmh
40046 GdOpTmh
40047 GdRmgTm
40048 GnDmdSrc
40049 GnEgyCnt
Page 21 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
40050 GnEgyTm
40051 GnOpTmh
40052 GnRmgTm
40053 GnRnStt
40054 GnStrCnt
40055 GnStt
40056 h-On
40057 Iac
40058 InvCur
40059 InvCurSlv1
40060 InvCurSlv2
40061 InvCurSlv3
40062 InvFrq
40063 InvOpStt
40064 InvOpSttSlv1
40065 InvOpSttSlv2
40066 InvOpSttSlv3
40067 InvPwrAt
40068 InvPwrAtSlv1
40069 InvPwrAtSlv2
40070 InvPwrAtSlv3
40071 InvPwrRt
Page 22 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
40072 InvPwrRtSlv1
40073 InvPwrRtSlv2
40074 InvPwrRtSlv3
40075 InvVtg
40076 InvVtgSlv1
40077 InvVtgSlv2
40078 InvVtgSlv3
40079 Mode
40080 Msg
40081 OnTmh
40082 OpStt
40083 OpSttSlv1
40084 OpSttSlv2
40085 OpSttSlv3
40086 Pac
40087 Prio
40088 Rly1Stt
40089 Rly2Stt
40090 RmgTmEqu
40091 RmgTmFul
40092 Serial Number
40093 Sic1EgyCntIn
Page 23 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
40094 Sic1PvPwr
40095 Sic1TdyEgyCntIn
40096 Sic2EgyCntIn
40097 Sic2PvPwr
40098 Sic2TdyEgyCntIn
40099 Sic3EgyCntIn
40100 Sic3PvPwr
40101 Sic3TdyEgyCntIn
40102 Sic4EgyCntIn
40103 Sic4PvPwr
40104 Sic4TdyEgyCntIn
40105 Soh
40106 TotBatCur
40107 TotExtCur
40108 TotExtPwrAt
40109 TotExtPwrRt
40110 TotInvCur
40111 TotInvPwrAt
40112 TotInvPwrRt
40113 TotLodPwr
40114 TotMccLodPwr
40115 TotSicBatCur
Page 24 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
40116 TotSicDyEgyCntI
40117 TotSicEgyCntIn
40118 TotSicPvPwr
40119 TotTmh
40120 Vac
5.3.
Interpreting Modbus Data
Page 25 of 62
Modbus does not have a mechanism for reporting the validity of data. What happens if the gateway loses its connection to the SMA Webbox? After a timeout period has elapsed the gateway will regard the data it had read previously, as unreliable.
The remote data client will see the value 65535 (-1, configurable) in the registers that contain unreliable data. In other words, rather than serve the old (possibly obsolete) data, the gateway serves a value that clearly identifies that the data is invalid.
If you require the data as floats, please contact Chipkin Automation Systems to update the configuration and Modbus map. These values will be encoded as IEEE754 format floating point numbers. These values use 2x 16bit registers. They are clearly identified in the Modbus Map.
Since Modbus does not support floating point numbers so all other values are served as whole numbers.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
5.4.
Test Procedure – Use CAS Modbus Scanner
Page 26 of 62
You can test the ModbusTCP data using free test software provided by Chipkin
Automation Software.
This is a link to the download page. http://www.chipkin.com/cas-modbus-scanner
Configure the scanner as follows
1.
Add a connection – specify the IP address of the gateway
2.
Add a device to the connection. Set the device=1
3.
Add a Request to the device: Read Holding register offset=1 Length=68
The result should be like this.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 27 of 62
4.
Click the Poll Button
5.
Use the values found in the ‘int16 column and the data map table to review the data.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 28 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
6.
Reading BACnet Data
Page 29 of 62
BACnet supports discovery. When you discover the gateway, objects and properties you will find appropriately named objects that report data from the SMA Devices. Because BACnet supports discovery, usually knowledge of the BACnet Device Instance Number does not need to be known in advance.
Each BACnet device (like the gateway) needs to have a unique instance number. Therefore it may be necessary for you to change the instance number.
Need to learn some BACnet basics? Read this guide. http://www.chipkin.com/bacnet-solutions
6.1.
Most Common BACnet Problem
If the device or application that is reading the BACnet data is on another subnet then it will not discover or be able to talk to the gateway. This can be resolved two ways. 1. Change the IP address of the gateway to be on the same subnet – a simple task. 2. Install BBMD – a non trivial task – but a task you can often pass the buck on – it is the responsibility of the company installing the BAS system to provide BBMD. You can read more about it at this link. http://www.chipkin.com/articles/bacnet-bbmd
6.2.
Interpreting BACnet Data
If the gateway loses communications with the Veeder Root device or if a data point cannot be read from the controller, the ‘Out of Service’ property of the data object is set true once the timeout has expired. The value of the ‘Present Value’ property is not changed, thus the last good value will be shown.
6.3.
BACnet Objects
The following is a list of possible BACnet Objects. Note : This list only contains what is configured with the default configuration (four tanks and system alarms).
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 30 of 62
For the following BACnet objects, each set of data (Invertor, SensorBox, and Sunny Island) will be described as if it was the first device configured. Each additional device added will be offset by 100. So the first device will have data starting with analog-input 1, the second device will have data starting at analog-input 101, the third device will have data starting at analog-input 201, etc.
Typical Invertor Data
BACnet IP Object analog_input (1) analog_input (2) analog_input (3) analog_input (4) analog_input (5) analog_input (6) analog_input (7) analog_input (8) analog_input (9)
Description
Backup State
Balancer
CO2 saved
Error
E-Total
Event-Cnt
Fac analog_input (10) analog_input (11) analog_input (12) analog_input (13)
Grid Type h-On h-Total
Iac
Ipv
Mode analog_input (14) analog_input (15) analog_input (16) analog_input (17)
Pac
Power On
Temperature
Vac
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 31 of 62 analog_input (18) analog_input (19) analog_input (20) analog_input (21) analog_input (22) analog_input (23)
Vpv
Serial Number
VacL1
VacL2
Vpv-_PE
Max Temperature analog_input (24) analog_input (25)
Typical SensorBox Data
Max Vpv
Vfan analog_input (1) analog_input (2) analog_input (3) analog_input (4) analog_input (5) analog_input (6) analog_input (7) analog_input (8)
ExlSolIrr
IntSolIrr
OpTm
TmpAmb F
TmpMdul F
TmpAmb C
TmpMdul C
WindVel m/s analog_input (9) WindVel mph
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Typical Sunny Island Data analog_input (1) analog_input (2)
Adr
AptPhs analog_input (3) analog_input (4) analog_input (5)
AptTmRmg
BatChrgOp
BatChrgVtg analog_input (6) analog_input (7) analog_input (8) analog_input (9) analog_input (10) analog_input (11) analog_input (12) analog_input (13)
BatSoc
BatSocErr
BatTmp
BatVtg
CardStt
ChpPwrAt
ChpRmgTm
ChpStrRmgTm analog_input (14) analog_input (15) analog_input (16) analog_input (17) analog_input (18) analog_input (19) analog_input (20) analog_input (21)
ChpStt
EgyCntIn
EgyCntOut
EgyCntTm
Error
E-Total
E-Total-In
ExtCur
Page 32 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual analog_input (22) analog_input (23) analog_input (24) analog_input (25) analog_input (26) analog_input (27) analog_input (28) analog_input (29) analog_input (30) analog_input (31) analog_input (32) analog_input (33) analog_input (34) analog_input (35) analog_input (36) analog_input (37) analog_input (38) analog_input (39) analog_input (40) analog_input (41) analog_input (42) analog_input (43)
ExtPwrRtSlv2
ExtPwrRtSlv3
ExtVtg
ExtVtgSlv1
ExtVtgSlv2
ExtVtgSlv3
Fac
Firmware
FwVer
FwVer2
GdCtcCnt
GdEgyCntIn
ExtCurSlv1
ExtCurSlv2
ExtCurSlv3
ExtFrq
ExtPwrAt
ExtPwrAtSlv1
ExtPwrAtSlv2
ExtPwrAtSlv3
ExtPwrRt
ExtPwrRtSlv1
Page 33 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual analog_input (44) analog_input (45) analog_input (46) analog_input (47) analog_input (48) analog_input (49) analog_input (50) analog_input (51) analog_input (52) analog_input (53) analog_input (54) analog_input (55) analog_input (56) analog_input (57) analog_input (58) analog_input (59) analog_input (60) analog_input (61) analog_input (62) analog_input (63) analog_input (64) analog_input (65)
GnStrCnt
GnStt h-On
Iac
InvCur
InvCurSlv1
InvCurSlv2
InvCurSlv3
InvFrq
InvOpStt
InvOpSttSlv1
InvOpSttSlv2
GdEgyCntOut
GdEgyTmh
GdOpTmh
GdRmgTm
GnDmdSrc
GnEgyCnt
GnEgyTm
GnOpTmh
GnRmgTm
GnRnStt
Page 34 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual analog_input (66) analog_input (67) analog_input (68) analog_input (69) analog_input (70) analog_input (71) analog_input (72) analog_input (73) analog_input (74) analog_input (75) analog_input (76) analog_input (77) analog_input (78) analog_input (79) analog_input (80) analog_input (81) analog_input (82) analog_input (83) analog_input (84) analog_input (85) analog_input (86) analog_input (87)
InvVtgSlv1
InvVtgSlv2
InvVtgSlv3
Mode
Msg
OnTmh
OpStt
OpSttSlv1
OpSttSlv2
OpSttSlv3
Pac
Prio
InvOpSttSlv3
InvPwrAt
InvPwrAtSlv1
InvPwrAtSlv2
InvPwrAtSlv3
InvPwrRt
InvPwrRtSlv1
InvPwrRtSlv2
InvPwrRtSlv3
InvVtg
Page 35 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual analog_input (88) analog_input (89) analog_input (90) analog_input (91) analog_input (92) analog_input (93) analog_input (94) analog_input (95) analog_input (96) analog_input (97) analog_input (98) analog_input (99) analog_input (100) analog_input (101) analog_input (102) analog_input (103) analog_input (104) analog_input (105) analog_input (106) analog_input (107) analog_input (108) analog_input (109)
Rly1Stt
Rly2Stt
RmgTmEqu
RmgTmFul
Serial Number
Sic1EgyCntIn
Sic1PvPwr
Sic1TdyEgyCntIn
Sic2EgyCntIn
Sic2PvPwr
Sic2TdyEgyCntIn
Sic3EgyCntIn
Sic3PvPwr
Sic3TdyEgyCntIn
Sic4EgyCntIn
Sic4PvPwr
Sic4TdyEgyCntIn
Soh
TotBatCur
TotExtCur
TotExtPwrAt
TotExtPwrRt
Page 36 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual analog_input (110) analog_input (111) analog_input (112) analog_input (113) analog_input (114) analog_input (115) analog_input (116) analog_input (117) analog_input (118) analog_input (119) analog_input (120)
TotInvCur
TotInvPwrAt
TotInvPwrRt
TotLodPwr
TotMccLodPwr
TotSicBatCur
TotSicDyEgyCntI
TotSicEgyCntIn
TotSicPvPwr
TotTmh
Vac
Page 37 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 38 of 62
6.4.
BACnet Test Procedure
You have been provided with a USB key to the CAS BACnet Explorer. This key activates the software. It cannot run without it. If you don’t have your USB key, you can still activate the application – it requires an internet connection. A video provides help. http://www.chipkin.com/articles/cas-bacnet-explorer-software-activation-video
You might also want to refer to these articles. http://www.chipkin.com/articles/cas-bacnet-explorer-usbsoftware-activation-problems http://www.chipkin.com/cas-bacnet-explorer-licenses-faq
Install and activate the application. Download from here. http://www.chipkin.com/cas-bacnet-explorer/
Procedure
1.
Start the application
2.
Click Settings
3.
Check IP – uncheck MSTP and Ethernet
4.
Click on the network card you will use.
5.
Click Ok.
6.
Now click discover
7.
Click Send
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 39 of 62
Device(s) were discovered.
Click the + to open up.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 40 of 62
Select the device and click discover again.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 41 of 62
Check the ‘Discover properties’ box.
Click the Send button.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 42 of 62
You get a list of objects with properties.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 43 of 62
Present value is the value found in the
Veeder Device.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
7.
Commissioning, Diagnostics and Trouble Shooting
Page 44 of 62
7.1.
What to Take to Site for Commissioning
1.
The gateway and other supplied components.
2.
USB->485 Converter
Any will do. This will allow you run tests using the 485 serial connection for Modbus RTU.
Connect to the device and find out which COM port is now available, use CAS Modbus
Scanner to retrieve data.
3.
Serial Cables
A Null Modem cable is used to connect to the gateway diagnostic port. Take one with you.
4.
Laptop
5.
Gateway IP Address Allocation Tool
Download from http://www.chipkin.com/articles/cas-gateway-ip-address-tool
6.
Wireshark packet sniffer software – free download http://www.wireshark.org/download.html
7.
CAS Modbus Scanner – free download
CAS Modbus Scanner is a utility to retrieve coils, inputs, holding registers, and input registers from a Modbus enabled device. Values retrieved from the device can be viewed in many different formats including Binary, HEX, Uint16, Int16, Uint32, Int32, and Float32. http://www.chipkin.com/cas-modbus-scanner
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
8.
Serial Mini Tester
Page 45 of 62
9.
DB9 and DB25 male and female connector make-up kits (Solder free)
Always useful but not required if you have tested your cable prior to attending the site.
10.
Rx / TX cross over.
Always useful but not required if you have tested your cable prior to attending the site.
It is useful to be able to swap the conductors connected to pins 2 and 3. Take a module with you. It is easier than changing the wires.
For example, the Ziotek Null Modem Adapter DB25 http://www.cyberguys.com/productdetails/?productid=751&rtn=750&core_cross=SEARCH_DETAIL_SIMILAR#page=page-1
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 46 of 62
11.
Gender Benders
Always useful but not required if you have tested your cable prior to attending the site.
12.
Ethernet Patch cables
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 47 of 62
13.
Hub
Used as a last resort if there are problems on Modbus or BACnet
A hub is not a switch. A hub can be used for trouble-shooting whereas only a ‘supervised’ switch can. Most switches are not supervised. http://www.chipkin.com/articles/hubs-vs-switches-using-wireshark-to-sniff-networkpackets
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
7.2.
Gateway Status
Page 48 of 62
Browse to http://192.168.1.113/bin/sma/report and you will the present values of the data points
If all of the data values are displayed as “-1” (or whatever the configured default value is) then it could mean one of two things.
1) The Gateway has just been configured and has begun to poll for values.
Wait for a little while for the first couple of scan intervals to finish, and then refresh the page. Current correct values should be displayed.
2) The Gateway is not connected to the Veeder Device. Either the Gateway was never connected, or the Gateway got disconnected from the device.
After an amount of time has passed (as configured in the Disconnect Time parameter of the configuration), the Gateway will set all values to the default value.
You must manually refresh this page to get the updated values.
7.3.
Gateway Diagnostics
Power Led: Green Solid = Normal Condition.
RJ45 LED: Green to show link.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
7.4.
Debug log.
Page 49 of 62
The debug messages are sent on UDP port 514 to the broadcast IP address:
{255.255.255.255} as plain ASCII text. You can use "logview4net" tool to view and recorded the debug messages as they are sent from the device.
Logview4net
Free and open source tool built to viewing and monitoring logs. It works with many different file formats and protocols including UDP. This tool can be download for "free" from the publishers website http://logview4net.com/
Click Done
Port=65534 and
Encoding=US-ascii
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 50 of 62
Timeout
Abnormal operation. No communication with device. Perform Veeder Device
Connection Diagnostics.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 51 of 62
Operating Normally
Occasional timeout messages should be tolerated.
Normal Operation.
7.5.
Veeder Device Connection
Use a mini tester to check the serial ports.
Connect the cable to the Veeder device only – RD should be green. If it isn’t this means the cable to the Veeder device is wrong or the port isn’t working.
Connect the cable to the gateway only – TD should be green. If it isn’t this means the cable to the gateway is wrong or the port isn’t working.
During normal operation RD will flicker green/red
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 52 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
7.6.
Another Method for Changing the IP Address - DHCP
This device supports DHCP and DHCP is disabled.
When shipped the device
IP = 192.168.1.113
Mask = 255.255.255.0
Gateway = 192.168.1.1
Page 53 of 62
If you simply want to change the IP address then use the simpler method provided in section 3.6
Change Configuration Settings.
A tool is provided to change the IP address of the gateway. The tool can be downloaded from: http://www.chipkin.com/articles/cas-gateway-ip-address-tool
When you start this tool it discovers gateways and list them in the right had side ‘Select a Unit’ area. If the area is blank then click the ‘Search Again’ button. If it remains blank check that the
Ethernet connection is made – is there a green link LED on the RJ45 and on the hub/switch you are connected to.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Page 54 of 62
To change the IP address complete the Fields and click the ‘Set’ button.
Please set the IP, Network Mask, and Gateway fields.
To set it to DHCP, simply put all fields to 0.0.0.0 and click the ‘Set’ button.
7.7.
Discovering the Gateway
Use the tool provided to change the IP address to discover the gateway and learn what its preallocated IP address is. See section 7.6 Another Method for Changing the IP Address
7.8.
Downloading New Firmware
If you are sent new firmware you will be provided with specific instructions. These are generic – i.e. folder and file names may be different.
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
A tool is provided. It can be downloaded from
http://www.chipkin.com/articles/cas-gateway-firmware-download-tool
Screen Shot from the Firmware update tool.
Page 55 of 62
File name and path may change. You will be provided with specific instructions.
Click to find a gateway
(discover)
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
8.
Specifications
UL and ULc approved
10/100BaseT with RJ-45 connector
1x RS232 Port
1x RS485 Port (Different Models have additional ports)
2MBytes flash memory, 8MBytes of SDRAM
Power: 5-24VDC
Operating Temperature: 0 to 70 C
Dimensions: 4.2" x 3.25" x 1"
LEDs: Link, Speed/Data, Power
Page 56 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
9.
SMA Enumerations
The following lists are the enumerated values for various SMA Data points
Page 57 of 62
9.1.
9.1.1.
9.1.2.
0
1
2
3
4
5
6
0
1
2
3
4
5
SMA Invertor Data Enumerations
Mode
Offset
Stop
Grid Monitoring
Waiting
V Const
Turbine
MPP Search
Grid Type
No Grid
277V
208V
240V
208V without N
240V without N
9.1.3.
0
1
2
3
Balancer
Off
Phase Guard
Power Guard
Fault Guard
9.1.4.
0
1
2
Backup State
No State
Grid
Off Grid
7
8
9
10
11
12
MPP
Disturbance
Error
Mpp Peak
Derating
Balanced
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
Error
No Error
MSD VAC
MSD FAC
B1
K1 Open
K2 Open
EEPROM p
ROM
Power Balance
MSD Idif
EarthCurMax Bfr
Derating
XFMR TEMP W
EeRestore
Grid Timeout
VacL1 Bfr
VacL2 Bfr
B2
B3
EEPROM
Bfr Srr
K1 Close
Watchdog
SRR Timeout
VpvMax
GFDI Fuse Open
B4
B5
Vac Bfr
Fac Bfr
XFMR TEMP F
B6
9.1.5.
15
16
17
18
19
20
9
10
11
12
13
14
3
4
5
6
7
8
0
1
2
21
22
23
24
25
26
27
28
29
30
31
Page 58 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
47
48
49
50
51
52
41
42
43
44
45
46
32
33
34
35
36
37
38
39
40
53
54
55
56
57
58
59
60
61
62
63
VacL1 Srr
VacL2 Srr
OFFSET
Imax
ShutDown
I Sense
Vac Srr
Fac Srr
S21
S22
S23
EarthCurMax Srr
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
S11
S12
S13
S14
S15
S16
S17
S18
XFMR
Grid Fault S
CAS-2700-24 SMA Gateway Manual
9.2.
SMA Sunny Island Data Enumerations
9.2.1.
Mode
Same as 9.1.1 SMA Invertor Data Enumerations – Mode
Page 59 of 62
9.2.2.
9.2.3.
9.2.4.
9.2.5.
9.2.6.
1
2
0
1
2
3
4
5
1
2
3
4
5
1
4
5
2
3
6
7
0
1
Invertor Operating State (InvOpStt)
None
Startup
Standby
Run
EmCharge
Error
Relay State (Rly1Stt, Rly2Stt)
Off
On
Battery Charging Process (BatChrgOp)
Boost
Full
Float
Equalize
Silent
Absorption Phase (AptPhs)
Off
On
GnDmdSrc
None
Bat
Lod
Tim
Run1h
Start
ExtSrcReq
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
9.2.7.
9.2.8.
9.2.9.
9.2.10.
2
0
1
1
2
9.2.11.
0
3
1
2
1
4
2
3
6
4
5
1
2
3
GnStatus
Off
Init
Ready
Warm
Connect
Run
GnRnStatus
Off
On
CHPStatus
Idle
Run
Lock
Address (Adr)
Master
Slave1
Slave2
Slave4
Operating Status (OpStt)
None
Operating
Warning
Failure
Page 60 of 62
7
8
9
10
11
12
Retry
Disconnect
Cool
Lock
Fail
FailLock
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
9.2.12.
9.2.13.
6
7
4
5
8
9
1
2
3
10
5
6
3
4
7
8
0
1
2
Error
None
1xx_INV
2xx_BAT
3xx_EXT
4xx_GEN
5xx_GRD
6xx_RLY
7xx_SYS
8xx_AUX
Card Status (CardStt)
Off
Operational
Mount
OutOfSpace
BadFileSys
Incomp
Parameter
ParamFailed
WriteLogData
WriteLogFailed
Page 61 of 62
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
CAS-2700-24 SMA Gateway Manual
10.
Revision History
Date
12 Feb 2014
Resp Format
ACF
Driver Ver.
0.11
Page 62 of 62
0
Doc.
Rev.
Comment
Document Created
2014
© Chipkin Automation Systems , 3495 Cambie St. Unit211, Vancouver, BC, Canada, V5Z 4R3
Tel: (866) 383-1657, Fax: (416) 915-4024
advertisement
Related manuals
advertisement
Table of contents
- 3 TABLE OF CONTENTS
- 6 SMA Gateway Description
- 7 Connections
- 8 Modbus RTU Connections
- 10 Configuration and Settings
- 16 Reading Data using HTML / Web Browser
- 17 Reading Modbus Data
- 29 Reading BACnet Data
- 44 Commissioning, Diagnostics and Trouble Shooting
- 56 Specifications
- 57 SMA Enumerations
- 57 Grid Type
- 57 Balancer
- 57 Backup State
- 58 Error
- 59 Invertor Operating State (InvOpStt)
- 59 Relay State (Rly1Stt, Rly2Stt)
- 59 Battery Charging Process (BatChrgOp)
- 59 Absorption Phase (AptPhs)
- 59 GnDmdSrc
- 60 GnStatus
- 60 GnRnStatus
- 60 CHPStatus
- 60 Address (Adr)
- 60 Operating Status (OpStt)
- 61 Card Status (CardStt)
- 61 Error
- 62 Revision History