C&K systems S802 Installation manual


Add to my manuals
16 Pages

advertisement

C&K systems S802 Installation manual | Manualzz

INSTALLATION

MANUAL

SECURIT 802 CONTROL PANEL S802

CONTENTS

Warnings

Standards

Warranty Statement

Product Description

Available Parts

Intended use

Specifications

Processor Version

Power Supply

Keypads

General

Factory Defaults

Installation

Mounting

Wiring

Battery

Detector Circuits

L as Latch Line

L as ID-

Internal Sounders

External Devices

Strobe

Keyswitch Connections

Aux DC power

Mounting Keypads

Wiring Keypads

Powering Up

Programming

Exit Time

Entry Time

Bell Duration

Night Set Exit Time

Home Set Exit Time

Circuit Programming

Zone Selections

Extended Programming

Home Set Zone Selection

Engineer Access Code

Engineer Log Review

Engineer Test Options

Restoring Default Codes

Restoring Default Programming

11

Glossary Of Terms

Information Table

Sounder Wiring Chart

Fault Finding

8

8

7

7

6

6

6/7

7

5

5

5

5

5

5

4

4

9

9

8

9

9/10

10

10

10

4

4

4

4

3

3

3

3

3

3

2

2

2

2

2

2

11

11/12

13

13

14

1

WARNINGS

Prolonged short circuit of any supply can cause damage to the unit.

Take the necessary precautions in not allowing liquids to spill on or into the unit.

STANDARDS

This unit conforms to ECD 89/336/EEC & LVD 73/23/EEC. This unit has been tested and has proven to meet all current emission and immunity regulations as set out by the EEC. This unit complies with

BS4737 part 1 1988 which relates to security control equipment.

WARRANTY STATEMENT

For this product, C&K Systems offers a two and a half year warranty from the date of manufacture.

If for some reason the unit fails in the first six months C&K will replace the unit free of charge. If the unit fails in the remaining two years, return the pcb (unless other parts have failed) to C&K systems and we will test the unit. If the unit is found “customer damaged” a charge will incur otherwise the unit will be repaired and returned free of charge.

PRODUCT DESCRIPTION

The Securit 800L ( hereafter known as “the Control Panel” ) is an 8 zone programmable microprocessor control panel using state of the art technology and manufacturing techniques. The panel has many advanced features that can only be found in more expensive control panels such as two user codes, Chime, Fire, and Keypad PA. There are many options in the programming functions to allow the control panel to be versatile and user friendly this allows the panel to be the ideal choice for residential or light commercial installations.

AVAILABLE PARTS

A selection of spares and extras are available. These are:-

Remote Keypad - giving full control over the control panel.

Spare PCB - for replacement in the event of failure.

Keyswitch - giving simple set / unset operation.

These can be obtained from your original place of purchase.

INTENDED USE

This panel is designed to be used in residential and light commercial applications such as homes, small shops etc.

2

PROCESSOR

VERSION

POWER

SUPPLY

KEYPADS

GENERAL

FACTORY

DEFAULTS

SPECIFICATIONS

There now follows the specifications of the panel. These include power consumption, panel dimensions etc.

SPECIFICATION FOR SOFTWARE REVISION NUMBER V1.0

The software revision number is located on the top of the main processor

SPECIFICATION

Power Supply

Mains Supply Voltage

PSU output voltage

Maximum output current

Aux. current

Battery Fuse

Panel Quiescent

Keypads

Supply Voltage

Quiescent Current

Active

Maximum number allowed

230 V AC Nominal

13.6 V Nominal

1 A (total)

500 mA Max.

1 A (20 mm)

40 mA

12 V

20 mA

45 mA

6

General

Normal operating temperature 0

°

C to 40

°

C

Humidity 10 to 90% R.H. non condensing

Dimensions

Control Panel Weight

Stand by Battery

263 mm (W) 223 mm (H) 82 mm (D)

2.7 kg Excluding Battery

1.2 Ah 12 V Rechargeable Lead Acid

2.1 Ah max.

Maximum Cable Run

Use

100 Metres per run.

For internal use only

Factory Defaults

User/customer Code 1

User/customer Code 2

Engineer Code

Circuit 1

Circuit 2

Circuit 3

Circuit 4

Circuit 5

Circuit 6

Circuit 7

Circuit 8

Full Set Exit Time

Night set Exit Time

Entry time

Sounder Ring Time

Chimes

1234

Disabled (0000)

7890

Entry Circuit. (Fixed)

Alarm Circuit isolated in Night set.

Alarm Circuit.

Alarm Circuit.

Alarm Circuit.

Alarm Circuit.

Alarm Circuit.

P.A (Personal Attack)

30 Seconds

15 Seconds

30 Seconds

15 Minutes

Disabled

3

INSTALLATION

1)

2)

3)

4)

5)

When fitting the panel, make sure to site it somewhere that is not visible from an outside location ( Window or Door ) and also make sure that the panel is going to be accessible. An ideal location would be a cupboard in a hall or under stairs located close to the main entrance. Ensure there is adequate light so the user can operate the keypad/s.

Mounting

Remove the lid screws and remove lid.

Remove the PCB or keypad packaging.

Place the panel in the selected position and mark the three fixing holes.

Mount the Panel securely using all three mounting hole positions.

Attach the tamper spring and mount the PCB onto the support pillars.

WIRING THE CONTROL PANEL

WARNING - MAINS CONNECTION

The panel must be permanently connected to the mains supply in accordance with current IEE wiring regulation. An unswitched fused spur, fitted with a fuse no greater than the rating of the cable connected from the spur to the panel, should be used.

Any fault which could be mains related must be diagnosed and corrected by a qualified electrician to ensure continued safe operation.

CAUTION: Under certain circumstances the transformer metalwork can reach 70°C. this is normal and well within prescribed limits.

INSTALLATION

PROCEDURES

MOUNTING

PROCEDURE

MAINS POWER

WARNING

BATTERY

SPECIFICATION

Battery connection.

Maximum battery size 12V 2.1Ah max.

This panel requires a standby battery to be fitted to provide power in the event of mains failure. A valve regulated lead acid battery must be used.

Detector circuits

Connections are provided for up to eight detector circuits of which normally closed detection devices must be used. A common tamper loop is provided for all detection devices marked as 24 HR Tamper. One or more devices may be connected to each alarm circuit. These should be connected in a series configuration. These circuit connections are located to the bottom right of the PCB

(see diagram B).

PIR Latch Line (L+)

In the event of two or more detectors (motion sensors or glassbreak detectors) being fitted to any single zone, latching detectors should be used. The 'L+' connection provides this function. It is low (0 V) when unset and high (12 V) when set. It should be connected to the appropriate SET or LATCH terminal in your detector. See glossary for explanation.

DETECTOR

CIRCUITS

LATCH LINE

DESCRIPTION

4

DETECTOR

RESET

INTERNAL

DEVICES

EXTERNAL

DEVICES

AUXILIARY

POWER

BASIC BOARD

LAYOUT

Detector reset (L+ when programmed for ID)

Some detectors require the removal of power to reset (e.g. Viper Plus

®

or Smoke detectors). The L+ terminal can be programmed to be used as an 'ID' output using option 7-4. The L+ terminal should then be used as the negative supply for these devices. The positive supply should be taken from the AUX +.

Internal Sounders, Speakers, Strobe and Keyswitch Wiring.

** DIAGRAM A **

Keyswitch Connections

Open = ON

Closed = OFF

Z8 only

OFF

ON

A maximum of two 16 ohm speakers may be fitted in parallel.

External Sounder & Strobe.

Connection for external sounder and strobe are shown in diagram A. Please note sounder trigger is applied negative. (Negative ring).

-

+

ST- Strobe switched negative trigger.

S Sounder switched negative trigger

-R

Sounder hold off/strobe positive supply.

Sounder hold off supply & sounder tamper feed (negative)

Sounder tamper return. (negative)

AUX DC - Detector power.

The auxiliary power is provided from connections marked 'AUX'. This is to provide the 12 V supply for detectors e.g. movement or glassbreak detectors. The auxiliary power output is rated at 500 mA max. (12 VCD nominal). See diagram B

5

** DIAGRAM B **

MOUNTING A REMOTE KEYPAD

1)

2)

3)

Locate the position for your keypad then mark the holes for mounting.

Make sure the cable is run through the backbox.

Screw the backbox in the agreed position making sure it is not twisted.

WIRING A REMOTE KEYPAD

1)

2)

All remote keypads require 6 core cable for their connection.

Connect the cable into the terminals shown below in diagram C making sure each wire goes to a like named terminal in the panel. C goes to C, D goes to D, + goes to + and - goes to -. The tamper wires are wired in series with your existing tamper loop. Refer to series & parallel examples in glossary for details.

Individual keypads do not need to be identified to the system. If more than one remote keypad is in use it can be either wired back to the control panel or daisychained from another keypad. All connections are in parallel with the exception of the tamper circuit which MUST be wired in series.(see glossary of terms for series and parallel examples).

** DIAGRAM C **

MOUNTING

REMOTE

KEYPADS

WIRING

REMOTE

KEYPADS

KEYPAD

DIAGRAM

INITIAL

POWER UP

POWERING UP

INITIAL POWER UP

NOTE The lid should remain off the main control panel so that engineer mode may be used. Alternatively, entering 7890 # can also be used to enter engineer mode. If the engineers code is entered and the panel is then left, it will set.

1) Switch the mains supply on, the internal sounder will start.

This denotes a tamper alarm.

2)

Enter 1 2 3 4 followed by the # (hash) button - this will silence the sounder and the TAMPER LED will flash. Fit the link onto LINK 1

This has now acknowledged and cancelled the alarm. By inserting LINK 1, you have disabled the onboard tamper.

3)

4)

5)

Connect your battery and walk test the control panel.

This will make sure all the zones are clear.

Power Down and complete the wiring of the control panel. Remove LINK 1

NEVER wire the control panel live. You have also re-enabled the onboard tamper loop.

Power back up, cancel the alarm and enter engineering mode by entering

7, 8, 9, 0. Close Lid when all the wiring is completed

The panel is now ready for programming.

6

NO

PROGRAMMING

NEEDED?

EXIT

ENGINEERING

MODE

RE-ENTER

ENGINEERING

MODE

STAY IN

ENGINEERING

MODE

TIMERS

EXIT TIME

ENTRY TIME

If programming is not required simply close any lids that are open and press the # key. This will exit engineering mode. Now refer to the users manual for customer options.

If at any time you wish to exit engineering mode, confirm any options you have selected with the * (STAR) key, then close ALL tamper circuits and wait for approximately 60 seconds after which the panel will automatically exit engineering mode or pressing the # (HASH) key will manually exit engineering

If at any time you wish to re-enter engineering mode, enter the engineering code and then press the # (HASH) key. This will now force the panel into engineering mode Note: If left unattended for approximately 60 seconds it will revert to day mode.

If you need to stay in engineering for longer unattended periods, once in engineering mode open a tamper circuit. The easiest way to do this is to remove the lid of the panel or keypad.

PROGRAMMING

Once in engineering mode, the day LED will flash. You now have the following options available.

EXIT TIME 3 0 (Range 10-90 Seconds.)

Enter 3-0. This has been preset to a factory default of 30 seconds. A new time may be programmed by entering one key from the following table.

Once the desired option is chosen press * to confirm. The accept tone will sound.

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

10 Seconds. Led 1 on.

15 Seconds. Led 2 on.

30 Seconds. Led 3 on. (default)

45 Seconds. Led 4 on.

60 Seconds. Led 5 on.

90 Seconds. Led 6 on.

ENTRY TIME 3-1 (Range 10-90 seconds)

Enter 3-1. Again this has been preset to a factory default of 30 seconds. To reprogram the entry time follow exactly the same directions as for the EXIT time

(3-0). Again press * to confirm option. The accept tone will sound.

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

10 Seconds. Led 1 on.

15 Seconds. Led 2 on.

30 Seconds. Led 3 on. (default)

45 Seconds. Led 4 on.

60 Seconds. Led 5 on.

90 Seconds. Led 6 on.

7

SOUNDER DURATION (sounder ring time) 3-2 (Range 3-20 minutes)

Enter 3-2. This has been preset to a factory default of 15 minutes. A new time may be programmed by entering one key from the following table. Press * to confirm the selection. The accept tone will sound.

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

3 minutes. Led 1 on.

4 minutes. Led 2 on.

5 minutes. Led 3 on.

10 minutes. Led 4 on.

15 minutes. Led 5 on. (default)

20 minutes. Led 6 on.

NIGHT SET / HOME SET EXIT TIME 3-3 (Range 0-90 seconds)

Enter 3-3. This has been preset to a factory default of 15 seconds. A new time may be programmed by entering one key from the following table. Press * to confirm the selection. The accept tone will sound.

Enter 0

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Enter 6

0 Seconds. All LED's off ( Instant ).

10 Seconds. Led 1 on.

15 Seconds. Led 2 on. (default)

30 Seconds. Led 3 on.

45 Seconds. Led 4 on.

60 Seconds. Led 5 on.

90 Seconds. Led 6 on.

NOTE: The exit sounder volume can be altered by the control on the PCB marked

VOLUME or RV1. Please note, this will not apply to keypad bleepers.

Option Option

Code Description

3-0

3-1

Exit Time (secs)

Entry Time (secs)

3-2

3-3

Sounder Duration (mins)

Night / Home Exit (secs)

0

0

Results from choosing option no.

1 2 3 4 5 6

10 15 30 45 60 90

10 15 30 45 60 90

3 4 5 10 15 20

10 15 30 45 60 90

Examples

Change the FULL set exit time to 60 seconds

ENTER THIS

Description

3-0 5 *

Choose full set Select 60 seconds Confirm selection

Change the Sounder duration to 3 minutes

ENTER THIS 3-2 1

Description Choose sounder

Select 3 minutes

*

Confirm selection

Change the ENTRY time to 45 seconds

ENTER THIS

Description

3-1

Choose entry

4 *

Select 45 seconds Confirm selection

SOUNDER

DURATION

NIGHT / HOME

SET EXIT TIMER

SUMMARY

8

CIRCUIT

PROGRAMMING

ZONE

SELECTIONS

EXTENDED

PROGRAMMING

HOME SET

ZONE

SELECTION

CIRCUIT PROGRAMMING 4 (Range 2-7)

Circuits 2 - 7 can be reprogrammed to suit your requirements. Circuit 1 is fixed as a Final exit circuit. Circuit 8 has limited options.

ENTER PROGRAM ZONE

4 - 2 2

4 - 3

4 - 4

4 - 5

3

4

5

ENTER

4 - 6

4 - 7

4 - 8

PROGRAM ZONE

6

7

8

Select the circuit you wish to alter. That circuit may then be programmed by entering one key from the following table. Once the option is selected press * to confirm. The accept tone will sound.

N/S = Night Set

Option no.

Zones 2-7 Zone 8

3

4

1

2

Alarm

Alarm with walk through

Alarm & Isolate in Night Set

Alarm, Walk through & Isolate in N/S

Alarm

Fire

PA

Full set keyswitch

5

6

Alarm, Walk through & N/S Entry

Fire

7 Entry Route

8 P.A

SEE GLOSSARY OF TERMS (p.11) FOR DESCRIPTIONS OF ZONE TYPES etc.

To program zone 3 as an “Entry Route” enter - 4 3 7 *

To program zone 8 as a “Keyswitch” enter - 4 8 4 *

EXTENDED PROGRAMMING OPTIONS 7 (Range 1-8)

Further options are available to increase the versatility of the control panel.

Enter 7 - 1 Disables sounder & strobe in night set.

Enter 7 - 2 Chime Enable ( See user manual for zone allocation).

Enter 7 - 3 Full set door sense setting.

Enter 7 - 4 Convert L+ to ID- output.

Enter 7 - 5 Allow Manual Isolation of Zone 1 (Entry/Exit) In night set.

Enter 7 - 6 Remote Keypad PA Enable ( Operated by * & # ).

Enter 7 - 7 L+ will latch only the first detector to alarm.

Enter 7 - 8 Inhibit strobe testing. ( For speech dialler connection)

Press * to confirm. The accept tone will sound

HOME SET ZONE SELECTION 8 (Range 1-8 N/A if Fire or PA)

This Control Panel can enable parts of the premises to be alarm protected while other parts are occupied and in use .. This can be achieved by using the Home

Set feature. This is similar to Night Set except that an Exit/Entry route is not required as part of the Setting or Unsetting procedure.

In programming mode press 8 to select Home Set zone selection mode.

9

By pressing the keys 1-8 on the keypad you will select which zones you want

ISOLATED during home set.

As a key is pressed, its relevant LED on the display will toggle on or off. Any LED’s that are ON will be ISOLATED during home set and any that are off will remain

ACTIVE.

ENGINEER ACCESS CODE 1-1

The engineer access code is programmed to 7890 by default. To change this code

(while in engineering mode):

Enter 1-1. LEDs 1, 2, 3 and 4 will illuminate.

Enter the new 4 digit code. After each keypress one LED will go out.

The speaker will emit an accept tone if the new code is accepted.

If the speaker emits an error tone, then your new chosen code is invalid. This could be due to a conflict with another code. At this time your old access code is still valid. Repeat the procedure using a different code.

ENGINEER

ACCESS CODE

ENGINEER

LOG REVIEW

ENGINEER EVENT LOG REVIEW 5 (Choices of set & unset)

The Panel stores the last alarm condition in both set and unset conditions

TOGGLE

SET & UNSET

Select Engineering Mode and press 5 to gain log access.

You will hear a continual tone which denotes you are viewing the last set condition.

There may be no lights illuminated as there may not have been an alarm during that time. Pressing the # key will turn off the sounder and show the last unset period. By pressing 0 you will show the last ALARM condition that was caused in an UNSET period (no matter how long ago that alarm was). Pressing # will bring the sounder back on and will show the last ALARM condition in a SET state. Press

* to finish.

ENGINEER

TEST OPTIONS

Pressing * will exit the log displays and return you to main engineering mode.

ENGINEER TEST OPTIONS 6 (Range 0-5)

The engineer has some test facilities available to him so he can test sounders etc.

without having to come out of engineering. These new options are accessed by pressing 6 from within engineering mode and then selecting another option below.

Enter 0

Enter 1

Enter 2

Enter 3

Enter 4

Enter 5

Internal buzzer ( entry exit sound etc. )

Internal Sounder ( Alarm sounds from speaker / keypad )

External Sounder

External Strobe

L+ Terminal( even if programmed as ID- )

FULL LOAD ( Everything enabled )

Press * to finish and return to main engineering mode.

10

FACTORY

DEFAULTS

RESTORE

DEFAULT

PROGRAMMING

RESTORE

DEFAULT

CODES

GLOSSARY OF

TERMS

FACTORY PROGRAMMING DEFAULTS 9-9

Factory defaults have been split into two sections, programming and codes.

To return to factory programming defaults first enter Engineering Mode then proceed as follows:-

1) Enter 9-9

Any extension sounders will give a rapid pipping sound. The internal keypad sounder will emit a steady tone.

2) Enter the engineer code.

If entered correctly an accept tone will sound and the factory programming defaults will be restored. If any error is made an error tone will sound and the programming will not be altered. The user and engineer codes have not changed.

If at any stage you want to default the customer codes, follow this procedure while in engineering mode.

1) Place the small link supplied with the spare fuses, on the memory link.

Then remove the mains and battery power.

The link is positioned left of the LEDS near the top of the pcb and is labelled

“Memory Default”.(at which point zone 1 light will illuminate)

2) Wait a few seconds then re-connect the battery and then the mains and then refer to page 6 regarding initial power up.

The speaker will omit the accept tone and the factory user code defaults will be restored.

3) Remove the link. ( at which point zone 1 light will go out ).

GLOSSARY OF TERMS

FULL SET

This is a setting method normally used when leaving the premises. Full system armed.

NIGHT SET

This is a setting method normally used when going to bed

HOME SET

This is a setting method normally used for high security protection whilst still inside the premises. For example an antiques cabinet etc.

ALARM

This is a zone that will trigger the panel when activated, providing the panel is set.

WALK THROUGH

This zone will be disabled during an entry period.

ISOLATE IN NIGHT SET

This simply means the zone will be disabled when the panel is NIGHT SET. For example downstairs may be armed but upstairs may be disabled.

11

NIGHT SET ENTRY

This means when the panel is NIGHT SET the zone, when activated, will start the entry timer but if the panel is FULL SET then this zone will simply act as an ALARM zone

ENTRY CIRCUIT

This will start the entry timer when activated providing the panel is set.

FIRE (for use with smoke detectors etc.)

This is a zone that when activated will emit an ascending sound from any internal speakers. If the panel is set, external sirens and strobes will also sound but in an unset state the external sounders will pulse every two seconds.

TAMPER

This is a loop that should run through every device on your system. If broken, it will trigger the internal speakers. If the panel is set, external sounders and strobes will also trigger.

The tamper LED is shown on the keypad as TPR

CHIME

Chime is similar to a doorbell. This can be used to alert a user to a certain zone being triggered during the day.

DOOR SENSE SETTING

This allows you to have a variable FULL SET EXIT TIME. You can program the EXIT time to maximum and when you full set the system, the exit time will drop to 8 seconds as soon as the EXIT door has closed thus avoiding the preset exit time.

FULL SET KEYSWITCH

This allows the panel to be set, unset and reset via zone 8. This is performed by using a 2 position keyswitch (make / break) across the zone. To set, open the zone. To unset, close the zone. To Reset you must open and close the zone after an alarm condition.

THE * KEY (STAR)

This is commonly used as an ACCEPT or STORE button

THE # KEY (HASH)

This is commonly used as RESET, CANCEL or EXIT

GLOSSARY

OF TERMS

THE ACCEPT TONE

This is heard when an action is accepted. The sound made is “diddly dee”

THE ERROR TONE

This is heard when an action is not accepted. The sound made is “dee dah”

SERIES AND PARALLEL

Series Parallel

LATCHING DETECTORS

These detectors, when triggered during a set period, latch on to aid the process of alarm event origin checking. These detectors are only normally used if many detectors are to be used on a single zone but are to cover a large area of space.

12

KEYS ENTERED

ZONE ZONE USE /

LOCATION

3

4

1

2

7

8

5

6

TIMER

FULL

NIGHT

EXT SOUNDER

TICK BOX

EXTENDED OPTIONS

BATTERY VOLTAGE

AUX. VOLTAGE

INSTALLED BY

VALUE

RESISTANCE

SECONDS

SECONDS

MINUTES

1 2 3 4 5 6 7 8

V

V

KEYS ENTERED

CHECKED

THIS INFORMATION SHOULD BE KEPT EITHER INSIDE THE CONTROL PANEL OR WITH THE

INSTALLER. IT CAN BE USED TO REFER TO PROGRAMMING DETAILS WHEN NEEDED.

CONTROL

PANEL

SONADE 2000

FLASHGUARD XL+

STARLIGHT 2000

ACTIVEGUARD

ACTIVE GUARD 3

SECURIGUARD

NOVA GUARD 2+T

SPIRIT AU1000

GENERAL TERMINALS

AG6 / AG8

ST-

STROBE-

STROBE-

ST

STB-

ST-

STROBE-

STROBE-

STB-

STROBE TRIG

-

ST-

S-

B

SIREN-

-R

-S

-SW

S-

S-

TRG-

SIREN TRIG

-

-SW

+

D

SUPPLY+

+H

+12V

V+

SUPPLY+

12V+

HOLD OFF +

SUPPLY+

V+

AUX -

A

SUPPLY-

-H

-12V

V-

SUPPLY-

12V-

HOLD OFF -

SUPPLY-

V-

-R

T

TAMPER OUT

RTN

RIGHT HAND

TAMPER

RET

LEFT HAND

TAMPER

R

RTN-

TAMPER RETURN

RET

13

FAULT FINDING

A selection of common known problems and solutions are listed below.

Problem

Programmed 7-5 but zone 1 wont isolate in night set.

Zone 1 is permanently lit

Tamper wont clear with lid on.

Cause

Have not MANUALLY isolated zone when setting panel.

Memory default link is on.

Tamper loop open

PA will not work on the keypad Not holding * & # long enough or option not enabled

Mains light not on.

Battery not taking over after mains fail

Zone activates during entry

Zone activates even in day mode

No mains

Battery fuse blown or battery not connected or flat battery.

Remote keypad not responding Incorrect wiring

Zones failing to activate.

Incorrect wiring

Seeing an alarm zone on entry or deviating from entry route.

Programmed to PA or FIRE.

Answer

When night setting enter code * 0 * 1.

Remove link.

Check 24hr tamper, sounder tamper and all devices for an open tamper loop.

Be sure to HOLD * & # until the alarm activates. Enable option

7-2.

Check fuse & mains supply

Connect battery and check 1A battery fuse. Fit new battery.

Check wiring. C to C & D to D.

Make sure the devices are wired in series NOT parallel.

Make sure all zones on entry route are programmed with walkthrough. Don’t deviate.

Reprogram the zone to be an alarm zone or similar.

If you are still experiencing problems then contact our technical helpline with information at hand regarding your situation. If your problem stems from wiring, you may be required to write down wiring instructions so have a pen and paper at hand.

General questions & Answers

Question

Can two bellboxes be used on the system

Can a “sound bomb” be installed

Can the engineer set the panel without the need of the user code.

How many PIRS can be connected to a zone

Answer

Yes, make sure tampers are in series and dont break current limit

Yes, connect between AUX+ and S-. Be sure not to exceed maximum current rating.

Yes, if the engineering code is entered, the panel with start the set.

As many as current supply will allow. Zone resistance should not exceed 50 ohms.

14

C&K Systems Ltd.

Unit 23-24 Walkers Road

North Moons Moat Industrial Estate

Redditch

Worcs.

B98 9HE

Tel: 01527 68111

Fax: 01527 68222

Tech Support:0345 660533 9am-5pm Weekdays (UK ONLY) email to: [email protected]

website: http://users.powernet.co.uk/cksys

5-051-519-01

15

Approved

BS EN ISO No.9002:1994

Certificate No. 0944