Power Over the NET™

PN5212 / PN5320

Power Distribution Unit

User Manual

www.aten.com

ii

PN5212 / PN5320 User Manual

FCC Information

This is an FCC Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

This equipment has been tested and found to comply with the limits for a Class

A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

RoHS

This product is RoHS compliant.

SJ/T 11364-2006

The following contains information that relates to China.

PN5212 / PN5320 User Manual

User Information

Online Registration

Be sure to register your product at our online support center:

International

North America http://support.aten.com

http://www.aten-usa.com/product_registration

Telephone Support

For telephone support, call this number:

International

China

Japan

Korea

North America

United Kingdom

886-2-8692-6959

86-10-5255-0110

81-3-5615-5811

82-2-467-6789

1-888-999-ATEN ext 4988

44-8-4481-58923

User Notice

All information, documentation, and specifications contained in this manual are subject to change without prior notification by the manufacturer. The manufacturer makes no representations or warranties, either expressed or implied, with respect to the contents hereof and specifically disclaims any warranties as to merchantability or fitness for any particular purpose. Any of the manufacturer's software described in this manual is sold or licensed as is. Should the programs prove defective following their purchase, the buyer

(and not the manufacturer, its distributor, or its dealer), assumes the entire cost of all necessary servicing, repair and any incidental or consequential damages resulting from any defect in the software.

The manufacturer of this system is not responsible for any radio and/or TV interference caused by unauthorized modifications to this device. It is the responsibility of the user to correct such interference.

The manufacturer is not responsible for any damage incurred in the operation of this system if the correct operational voltage setting was not selected prior to operation. PLEASE VERIFY THAT THE

VOLTAGE SETTING IS CORRECT BEFORE USE.

PN Device Safety Notice

Š

Set the maximum permissible breaker protection in the building circuitry to the current rating specified on the rating plate. Observe all national regulations and safety codes as well as deviations for breakers.

Š

Only connect the PN Device to a grounded power outlet or a grounded system!

Š

Make sure that the total current input of the connected systems does not exceed the current rating specified on the rating plate of the PN Device.

Š

There is a risk of explosion if the battery is replaced with an incorrect type. Dispose of used batteries according to the relevant instructions.

Š

If the power source is unstable, the PN Device’s measurements will not be accurate.

iii

PN5212 / PN5320 User Manual

Package Contents

The PN5212 / PN5320 package consists of:

1 PN5212 or PN5320 Power Distribution Unit

3 Serial Adapters:

1 SA0149 (RJ45F to DB9F)

1 SA0150 (RJ45F to DB9M)

1 SA0151 (RJ45F to DB9F)

2 Rack Mount Kit

1 Grounding Wire

1 User Manual*

1 Quick Start Guide

1 Software CD

Check to make sure that all of the components are present and in good order.

If anything is missing, or was damaged in shipping, contact your dealer.

Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the PN5212 / PN5320 installation.

* Features may have been added to the PN5212 / PN5320 since this manual was printed. Please visit our website to download the most up-to-date version of the manual.

Copyright © 2010–2011 ATEN® International Co., Ltd.

Manual Part No. PAPE-0321-AX1G

Printing Date: 2011-06-17

Altusen and the Altusen logo are registered trademarks of ATEN International Co., Ltd. All rights reserved. All other brand names and trademarks are the registered property of their respective owners.

iv

PN5212 / PN5320 User Manual

Contents

FCC Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii

RoHS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii

SJ/T 11364-2006. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii

User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii

Online Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii

Telephone Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii

User Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii

PN Device Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii

Package Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v

About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . x

Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi

Product Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii

Chapter 1.

Introduction

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Remote Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Port and Led Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Chapter 2.

Hardware Setup

Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Single Stage Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Daisy Chaining . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Chapter 3.

Super Administrator Setup

First Time Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Changing the Administrator Login . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Moving On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 v

PN5212 / PN5320 User Manual

Chapter 4.

Browser Login

Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

The PN5212 / PN5320 Main Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Page Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Chapter 5.

Outlet Access

Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

The Outlet Selection Sidebar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Manual Power Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Station Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Outlet Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Outlet Group Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

User Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Sessions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Station Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Outlet Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Station Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Outlet Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Chapter 6.

User Management

Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Adding Users. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Modifying User Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Deleting User Accounts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Moving On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Creating Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Modifying Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Deleting Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Users and Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Assigning Users to a Group From the Accounts Page . . . . . . . . . . . . 55

Removing Users From a Group From the Accounts Page . . . . . . . . . 56

Assigning Users to a Group From the Groups Page. . . . . . . . . . . . . . 57

Removing Users From a Group From the Groups Page. . . . . . . . . . . 58

Device Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Assigning Device Permissions From the Accounts Menu. . . . . . . . . . 59

Assigning Device Permissions From the Groups Page . . . . . . . . . . . 60 vi

PN5212 / PN5320 User Manual

Chapter 7.

Device Management

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Device Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Service Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

IP Installer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

IPv4 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

IPv6 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

ANMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Event Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Authentication & Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

CC Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

OOBC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Console Port Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

Login String . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

IP and MAC Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Account Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

Private Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

Customization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Login Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Working Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

Time Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

Manual Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

Network Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

Finishing Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

Chapter 8.

Log

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

System Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

The Log Event List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

Save . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Notification Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

Chapter 9.

Maintenance and Download

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Firmware Upgrade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Backup/Restore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 vii

PN5212 / PN5320 User Manual

Chapter 10.

The Log Server

Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

Starting Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

The Menu Bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

Configure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

Help. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

The Log Server Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

The List Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

The Event Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Chapter 11.

Out of Band Operation

Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Console Terminal Session . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Chapter 12.

Remote Terminal Operation

Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Telnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

SSH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

Terminal Session (Linux) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

Third Party Utility (Windows). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112

Chapter 13.

LDAP Server Configuration

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

Install the Windows 2003 Support Tools . . . . . . . . . . . . . . . . . . . . . . . . 113

Install the Active Directory Schema Snap-in. . . . . . . . . . . . . . . . . . . . . . 114

Create a Start Menu Shortcut Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

Extend and Update the Active Directory Schema. . . . . . . . . . . . . . . . . . 115

Creating a New Attribute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

Extending the Object Class With the New Attribute . . . . . . . . . . . . . 117

Editing Active Directory Users. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

OpenLDAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

OpenLDAP Server Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

OpenLDAP Server Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

Starting the OpenLDAP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

Customizing the OpenLDAP Schema . . . . . . . . . . . . . . . . . . . . . . . . 125

LDAP DIT Design and LDIF File . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126

Using the New Schema. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 viii

PN5212 / PN5320 User Manual

Appendix

Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

International. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

IP Address Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

Trusted Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135

Installing the Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136

Certificate Trusted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137

Mismatch Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138

Self-Signed Private Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

Importing the Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

Administrator Login Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145

Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 ix

x

PN5212 / PN5320 User Manual

About This Manual

This User Manual is provided to help you get the most from your PN5212 /

PN5320 system. It covers all aspects of installation, configuration and operation. An overview of the information found in the manual is provided below. Chapters 1, 4, and 5 are for all users. The remaining chapters are for administrators and users with administrator privileges.

Overview

Chapter 1, Introduction, introduces you to the PN5212 / PN5320 system. Its

purpose, features and benefits are presented, and its front and back panel components are described.

Chapter 2, Hardware Setup, provides step-by-step instructions for setting

up your installation.

Chapter 3, Super Administrator Setup, explains the procedures that the

super administrator employs to set up the PN5212 / PN5320 network environment, and change the default username and password.

Chapter 4, Browser Login, describes how to log in to the PN5212 / PN5320

with an internet browser, and explains the layout and components of the

PN5212 / PN5320’s user interface.

Chapter 5, Outlet Access, describes the Outlet Access page; how to

configure the options it provides regarding outlet operation; and how to access and operate the PN5212 / PN5320’s outlets.

Chapter 6, User Management, shows administrators how to create,

modify, and delete users and groups, and authorize outlet access for them.

Chapter 7, Device Management, shows administrators, and users with

device management permission how to configure and control overall Power

Over the NET™ device operations.

Chapter 8, Log, explains how to use the PN5212 / PN5320’s log feature to

view the events that take place on the Power Over the NET™ installation.

Chapter 9, Maintenance and Download, describes the procedures for

upgrading the PN5212 / PN5320’s firmware; backing up and restoring the device’s configuration settings; and downloading a stand-alone Java Client AP program to access the PN5212 / PN5320.

Chapter 10, The Log Server, explains how to install and configure the Log

Server.

PN5212 / PN5320 User Manual

Chapter 11, Out of Band Operation, explains an alternative method to

access the PN5212 / PN5320 in case the LAN that it resides on goes down, or it cannot be accessed with the usual browser based method for some reason.

Chapter 12, Remote Terminal Operation, describes how the PN5212 /

PN5320 can be accessed via remote terminal sessions such as Telnet, SSH, and

PuTTY.

Chapter 13, LDAP Server Configuration, explains how to configure the

PN5212 / PN5320 for LDAP / LDAPS authentication and authorization with

Active Directory or OpenLDAP.

An Appendix, provides specifications and other technical information regarding the PN5212 / PN5320.

Conventions

This manual uses the following conventions:

Monospaced

[ ]

1.

Indicates text that you should key in.

Indicates keys you should press. For example, [Enter] means to press the Enter key. If keys need to be chorded, they appear together in the same bracket with a plus sign between them: [Ctrl+Alt].

Numbered lists represent procedures with sequential steps.

Bullet lists provide information, but do not involve sequential steps.

Indicates selecting the option (on a menu or dialog box, for example), that comes next. For example, Start

Run means to open the Start menu, and then select Run.

Indicates critical information.

xi

PN5212 / PN5320 User Manual

Product Information

For information about all ALTUSEN products and how they can help you connect without limits, visit ALTUSEN on the Web or contact an ALTUSEN

Authorized Reseller. Visit ALTUSEN on the Web for a list of locations and telephone numbers

Š International – http://www.aten.com

Š North America – http://www.aten-usa.com xii

Chapter 1

Introduction

Overview

The PN5212 and PN5320 are power distribution units (PDUs) that contain 12 and 20 AC outlets, respectively, and are available in IEC or NEMA socket configurations. They provide secure, centralized, intelligent, power management (power on, off, cycle) of remote data center equipment (servers,

KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center's health environment. By daisy chaining up to 15 additional PN5212 or PN5320 units, as many as 320 outlets can be managed from a single interface.

The characteristics of each model are shown in the following table:

Model

PN5212

PN5320

Amps

16/20

32/30

Outlets

12

20

The power status of each outlet can be set individually, allowing users to establish on/off schedules for each device. Outlets can also be aggregated into groups, allowing groups of devices to be power managed at the same time, while On/Off sequencing enables users to set the power on sequence and delay time for each port to allow equipment to be turned on in the proper order.

Installation and operation is fast and easy: plugging cables into their appropriate ports and user-friendly browser-based configuration and management is all that is entailed. Serial access via modem, Telnet and SSH is also supported to ensure system availability.

Since the PN5212 / PN5320 firmware is upgradeable over the Net, you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available.

With its advanced security features and ease of operation, the PN5212 /

PN5320 is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations.

1

PN5212 / PN5320 User Manual

Features

Power Distribution

Š Maximum Amps/Outlet: 20A / 12 outlets (PN5212); 30A / 20 outlets

PN5320)

Š Space saving 0U rack mount design

Š IEC or NEMA outlet models

Š Daisy chain up to 15 additional stations for up to 192 (PN5212) or 320

(PN5320) outlets

Š 2 x 7 segment front panel LED shows Station ID and Current / Voltage /

Active Power

Š Overcurrent protection and recovery (PN5320 only)

Š Remote users can monitor outlet status via web pages on their browsers

Š Safe shutdown support

Š Separate power for the unit's own power and its power outlets. The user interface is still accessible even when an overload condition trips the devices' circuit breaker (PN5320 only)

Remote Access

Š Remote power control via TCP/IP and a built in 10/100 Ethernet port

Š Network Interfaces: TCP/IP, PPP, UDP, HTTP, HTTPS, SSL, SMTP,

DHCP, ARP, NTP, DNS, Telnet, 10Base-T/100Base-TX, auto sense, Ping

Š IPv6 support

Operation

Š Local and Remote power outlet control (On, Off, Power Cycle) by individual outlets and outlet groups

Š Outlet group support at the PDU and Daisy-chain levels – the same action can be performed on a specified group of outlets at the same time

Š Supports redundant power management via daisy chaining and outlet groups

Š On/Off scheduling for individual outlets and outlet groups. Power management tasks can be scheduled to perform everything on a daily, weekly, monthly, or user-specified times basis

Š Supports multiple power on/off control methods – Wake on LAN, System

After AC Back, Kill the Power

2

Chapter 1. Introduction

Š Power-on sequencing - users can set the power on sequence and delay time for each port to allow equipment to be turned on in the proper order

Š Easy setup and operation via a browser-based user interface

Š Multibrowser support (IE, Mozilla, Firefox, Chrome, Safari, Opera,

Netscape)

Š Telnet and SSH access for text menu configuration and outlet level switching / monitoring

Š Local console access support

Š Java GUI AP program provided for non-browser connectivity

Š RTC support to keep the timer running during times of no power.

Š Up to 64 user accounts - up to 32 concurrent logins

Management

Š Power status measurement at the PDU level

Š LED indicators for current, voltage and active power at the PDU level

Š Real-time current, voltage, active power, and power dissipation displayed in a browsed-based UI for monitoring at the PDU and daisy-chained PDU levels

Š Current, voltage, active power, and power dissipation threshold setting

Š Alert notification for selected events (On, Off, Recycle, Failure, exceeding threshold settings, etc.), via audio alarm and blinking LEDs (locally),

SMTP, SNMP trap notification, and digital output

Š Naming support for outlets and outlet groups

Š User outlet access assignment on an outlet-by-outlet basis.

Š Windows-based Log Server; event logging, KVM logging, and syslog support

Š Integration with ALTUSEN CC2000 Management software

Š API for 3rd party software centralized control integration

Š Upgradeable firmware – daisy chained stations receive the upgrade via the daisy chain bus

Š Multilanguage support: English, German, Traditional Chinese, Simplified

Chinese, Japanese, Korean, Russian

3

PN5212 / PN5320 User Manual

Security

Š Three-level password security

Š IP/MAC filtering

Š Strong security features include strong password protection and advanced encryption technologies – 128 bit SSL

Š Remote authentication support: RADIUS, TACACS+, LDAP, LDAPS and

Active Directory

Requirements

Š Browsers accessing the PN5212 / PN5320 must support SSL 128 bit encryption.

Š For cold booting of attached computers, the computer's BIOS must support Wake on LAN or System after AC Back.

Š For Safe Shutdown:

Š The computer must be running Windows (Windows 2000 or higher) or

Linux.

Š The Safe Shutdown program (available by download from our website or on the software CD included), must be installed and running on the computer.

4

Components

Front View

1

2

3

2

1

PN5320 - NEMA

4

5

6

PN5320 - IEC

Chapter 1. Introduction

5

PN5212 / PN5320 User Manual

No.

1

5 Grounding

Terminal

6

Item

Power Sockets

Power Cord

NEMA 5-15R

– or –

IEC320 C13

Description

2 Power Sockets NEMA 5-20R

– or –

IEC320 C19

Details of this section are provided on the following page.

3 Port and LED

Panel

4 Circuit Breakers PN5320 only. As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.

Note: Circuit breakers are not provided on the PN5212.

Therefore, it is not recommended to plug the unit directly into any unprotected power source, such as a wall outlet.

The wire used to ground the unit connects here.

Note: The grounding terminal does not appear in the diagram. It is hidden by the power cord.

Plug the cord into your AC source.

Note: The Front View diagram depicts a PN5320. The PN5212 is basically the same, except there are only 12 AC power sockets (6 on each side of the

Port and LED panel), and all the sockets are NEMA 5-15R or IEC320

C13. There are no NEMA 5-20R or IEC320 C19 sockets. The PN5212 does not feature circuit breakers.

6

Port and Led Panel

1 2

Chapter 1. Introduction

3 4 5 6

No.

1

Item

Station

Selection

2

3

4

Readout

Section

Status

LEDs and

Reset

Switch

LAN Port

Description

Š

Press the Left or Right button to move to the previous or next

Station.

Š

The Station number appears in the display window.

Š

The readouts for Current, Voltage, and Active Power appear in the display window.

Š

The LEDs above the items indicate which one the readout relates to.

Š

Press the button above the display window to cycle the selection among the items.

Power: Lights when the PN5212 / PN5320 is powered up and ready to operate.

Link: Lights GREEN to indicate that a connection via the

PN5212 / PN5320's RJ-45 Ethernet port has been established.

Flashes to indicate data is being transmitted.

10/100 Mbps: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100

Mbps data transmission speed.

On Line: Lights to indicate that a connection to a KVM switch or a parent PDU has been established. Flashes to indicate that data is being transmitted.

Reset Switch:

Š

This switch is recessed and must be pushed with a thin object, such as the end of a paper clip.

Š

Press and release to reboot the device.

Š

Press and hold for more that three seconds to reset the

PN5212 / PN5320 to its factory default settings (except for user account settings – they are not removed).

The cable that connects the PN5212 / PN5320 to the Internet,

LAN, or WAN plugs in here.

7

PN5212 / PN5320 User Manual

No.

5

Item

PON Out

Port

6

7

RS-232/

RS-485

Switch

PON In /

Console

Port

Description

When daisy chaining PDUs, the cable that connects to the child device plugs in here.

If the child device is a PN0108, you must use an SA0150 adapter

to plug into the PN0108’s PON In port (see PN5212 / PN5320 to

PN0108, page 14, for details).

Selects which protocol the PON In / Console port uses.

Š

For PON In use, select RS-232 (for PN0108) or RS-485

Š

For Console use, select RS-232

Š

For KVM switches, select either RS-232 (can be used for shorter distances), or RS-485 (for longer distances).

Š

When daisy chaining PN5212 / PN5320 devices, set the switch to RS-232 on all child devices.

This is a multifunction port:

PON In:

When used as a PON In port, it can: 1) Daisy chain the device to a parent PDU; or 2) Connect the device to a KVM switch.

If the parent PDU is a PN0108, you must use an SA0149

adapter to plug into the PN0108’s PON Out port (see PN0108

to PN5212 / PN5320, page 15, for details).

Console:

When used as a Console port, it can establish a serial terminal connection to a computer. An SA0151 (DTE) adapter

is required for this connection (see Single Stage Installation, page 11, for details).

8

Chapter 2

Hardware Setup

Before You Begin

1. Important safety information regarding the placement of this device is

provided on page 129. Please review it before proceeding.

2. The PN5212 requires a dedicated circuit. See Package Contents, page iv, for important information about this matter.

3. Make sure that power to all the devices you will be connecting have been turned off. You must unplug the power cords of any computers that have the Keyboard Power On function.

Rack Mounting

The PN5212 / PN5320 can be installed in a 0U configuration on the side of a rack. To rack mount the device, use the rack mounting brackets that came with your device. The brackets can be mounted either near the top and bottom of the back panel, or the top and bottom ends of the device (see page 10), as shown in the diagrams below:

(Continues on next page.)

9

PN5212 / PN5320 User Manual

(Continued from previous page.)

The PN5212 / PN5320 comes supplied with top and bottom screws already inserted, as shown below:

If you want to mount to brackets at the top and bottom ends of the device, you must first remove the screws from each end of the unit before attaching the mounting brackets:

10

Chapter 2. Hardware Setup

Single Stage Installation

In a single stage installation, there are no additional PN5212 / PN5320 stations daisy chained down from the first unit. To set up a single stage installation, refer to the installation diagram on the next page (the numbers in the diagram correspond to the numbered steps), and do the following:

1. Use a grounding wire to ground the PN5212 / PN5320 by connecting one end of the wire to its grounding terminal, and the other end of the wire to a suitable grounded object.

Note: Do not omit this step. Proper grounding helps to prevent damage to the unit from surges or static electricity.

2. For each device you want to connect, use its power cable to connect from the device's AC socket to any available outlet on the PN5212 / PN5320.

3. Plug the cable that connects the PN5212 / PN5320 to the LAN into the

PN5212 / PN5320's LAN port.

4. (Optional) If you wish to use a console terminal connection, use Cat 5e cable to connect the PN5212 / PN5320’s PON IN/Console port to the

SA0151 (DTE) adapter supplied with your package. Connect the adapter’s serial connector to the COM port of the computer you will use for the console terminal.

5. Connect the PN5212 / PN5320's power cord to an AC power source.

Note: 1. We strongly advise that you do not plug the PN5212 / PN5320 into a multi socket extension cord, since it may not receive enough amperage to operate correctly.

2. Circuit breakers are not provided on the PN5212. Therefore, it is not recommended to plug the unit directly into any unprotected

power source, such as a wall outlet. See Package Contents, page iv.

Once you have finished these installation steps, you can turn on the PN5212 /

PN5320 and the connected devices.

Note: We strongly recommend using cable ties and cable bars to safely and securely route the cables attached to the back of the unit.

11

PN5212 / PN5320 User Manual

1

5

3

SA0151

(DTE)

4

2

12

Chapter 2. Hardware Setup

Daisy Chaining

To manage even more outlets from the same single session as a standalone

PN5212 / PN5320, additional Power Over the NET™ devices can be daisy chained, as described in the following three configurations.

Note: The maximum distance between any two Power Over the NET™ devices must not exceed 15 m; the total distance from the first station to the last must not exceed 100 m.

PN5212 / PN5320 to PN5212 / PN5320

Up to 15 additional PN5212 / PN5320 stations can be daisy chained down from the top level (master) device – allowing up to 320 outlets to be managed on a complete installation. To daisy chain a PN5212 / PN5320, do the following:

1. Set the RS-232/RS-485 switch (see page 8), of the child device to the RS-

232 setting.

2. Use Cat 5e cable to connect the PON OUT port of the parent device to the

PON IN port of the child device.

3. Repeat the procedure for any additional devices you wish to connect.

13

PN5212 / PN5320 User Manual

PN5212 / PN5320 to PN0108

To daisy chain a child PN0108 from a parent PN5212 / PN5320, do the following:

1. Use Cat 5e cable to connect the PN5212 / PN5320’s PON OUT port to the

SA0150 Adapter supplied with your package.

2. Connect the SA0150 to the PN0108’s PON IN port.

SA0150

2

1

14

Chapter 2. Hardware Setup

PN0108 to PN5212 / PN5320

To daisy chain a PN5212 / PN5320 from a parent PN0108, do the following:

1. Set the RS-232/RS-485 switch (see page 8), of the child PN5212 / PN5320

to the RS-232 setting.

2. Connect the SA0149 Adapter supplied with your package to the PN0108’s

PON OUT port.

3. Use Cat 5e cable to connect the SA0149 to the PN5212 / PN5320’s PON

IN port.

SA0149

1

2

Note: In this configuration, the PN0108 would be connected to a KVM switch that supports Power Over the NET™ devices (such as the KN4140v), through its PON IN port, and the PON devices would be managed through the KVM switch’s interface.

15

PN5212 / PN5320 User Manual

This Page Intentionally Left Blank

16

Chapter 3

Super Administrator Setup

First Time Setup

Once the PN5212 / PN5320 installation has been cabled up, the next tasks the

Administrator needs to perform involve configuring the network parameters, changing the default Super Administrator login settings, and adding users.

The easiest way to accomplish this is to log in over the Net with a browser (see

Logging In, page 21).

Note: 1. Since this is the first time you are logging in, use the default

Username: administrator; and the default Password: password. For security purposes we recommend changing them to something unique

(see Changing the Administrator Login, page 19).

2. For remote methods of getting logged in to the network, see IP

Address Determination, page 133.

After you successfully log in the PN5212 / PN5320 Main Page appears:

17

PN5212 / PN5320 User Manual

Network Configuration

To set up the network, do the following:

1. Click the Device Management tab.

2. Select Network on the menu bar. A screen similar to the one below appears:

3. Fill in the fields according to the information provided under Network, page 63.

18

Chapter 3. Super Administrator Setup

Changing the Administrator Login

To change the default Super Administrator username and password, do the following:

1. Click the User Management tab.

The User Management page has a list of Users and Groups in the Sidebar at the left, and a more detailed list of users – with more information about them – in the large central panel. Since this is the first time the page is being accessed, only the Super Administrator appears:

2. Click administrator in the Sidebar

– or –

Select administrator in the central panel, then click Modify (at the bottom of the page.)

(Continues on next page.)

19

PN5212 / PN5320 User Manual

(Continued from previous page.)

The User General page appears:

3. Change the Username and Password to something unique.

4. Re-enter the password to confirm it is correct.

5. Click Save.

6. When the dialog box informing you that the change completed successfully appears, Click OK.

Moving On

After setting up the network and changing the default Administrator username and password, you can proceed to other administration activities – including

adding users. Administration is discussed in detail in Chapter 4.

20

Chapter 4

Browser Login

Logging In

The PN5212 / PN5320 can be accessed via a supported Internet browser from any platform.

Note: Browsers must support SSL 128 bit encryption.

To access the PN5212 / PN5320 do the following:

1. Open your browser and specify the IP address of the PN5212 / PN5320 you want to access in the browser's URL location bar.

Note: 1. Get the IP address from the PN5212 / PN5320 administrator

2. If you are the administrator, and are logging in for the first time,

see First Time Setup, page 17.

2. If a Security Alert dialog box appears, accept the certificate – it can be

trusted. (See Trusted Certificates, page 135, for details.) The Login page

appears:

3. Provide a valid Username and Password (set by the PN5212 / PN5320 administrator), then Click Login to bring up the browser Main Page.

21

PN5212 / PN5320 User Manual

The PN5212 / PN5320 Main Page

After you have successfully logged in, the PN5212 / PN5320 Main Page comes up with the Outlet Access Connections page displayed:

Note: 1. The screen depicts a Super Administrator’s page. Depending on a user’s type and permissions, not all of these elements appear.

2. Clicking the Altusen logo (at the top-right of the page), takes you to the ATEN website.

22

Chapter 4. Browser Login

Page Components

The web page screen components are described in the table, below:

No.

1

2

3

Tab Bar

Menu Bar

Sidebar

Item Description

The tab bar contains the Power Over the NET™’s main operation categories. The items that appear in the tab bar are determined by the user’s type, and the authorization options that were selected when the user’s account was created.

The menu bar contains operational sub-categories that pertain to the item selected in the tab bar. The items that appear in the menu bar are determined by the user’s type, and the authorization options that were selected when the user’s account was created.

The Sidebar provides a tree view listing of stations and outlets that relate to the various tab bar and menu bar selections. Clicking a node in the Sidebar brings up a page with the details that are relevant to it.

4

5

6

About/Help

Logout

Welcome Message

About provides information regarding the switch’s current firmware version. Help provides on-line help for the device’s configuration and operation.

Click this button to log out of your Power Over the

NET™ session.

If this function is enabled (see User Preferences, page 34), a welcome message displays here.

7 Interactive Display Panel This is your main work area. The screens that appear reflect your menu choices and Sidebar node selection.

23

PN5212 / PN5320 User Manual

This Page Intentionally Left Blank

24

Chapter 5

Outlet Access

Overview

When you log in to the PN5212 / PN5320, the UI opens with its default selection of the Outlet Access tab; the Connections menu; and the Outlets submenu. The contents of the Outlets submenu are displayed in the main panel.

The main panel Outlets display provides a listing of each outlet a user is permitted to access, as well as a means of accessing the outlets. All the outlets that a user is permitted to access are also listed in the Sidebar at the left of the page.

25

PN5212 / PN5320 User Manual

The Outlet Selection Sidebar

All stations and their outlets – including cascaded stations and their outlets – are listed in a tree structure in the Sidebar at the left of the screen. Outlet groups are listed at the bottom of the tree:

Š Users are only allowed to see the stations and outlets that they have access permission for.

Š Outlets and child stations may be nested under their parent stations. Click the + in front of a station to expand the tree and see the nested outlets.

Click the - to collapse the tree and hide the nested outlets.

Š An outlet’s ID number is displayed in brackets next to the outlet icon. For

convenience the outlets can be named (See Configuration, page 37 for details). If an outlet has been named, its name appears next to the outlet

ID.

Š Outlet groups are identified by a double socket icon.

26

Chapter 5. Outlet Access

Š The outlet’s icon color indicates its status as explained in the table, below:

Icon

Steady Amber

Flashing Amber

Steady Gray

Flashing Gray

Flashing Lightbulb

Status

Power to the outlet is On.

A change in the outlet's power status is pending.

(See Shutdown Method, page 43)

Power to the outlet is Off.

Power to the outlet is Off, but Wake On LAN has been

specified as the remote power option. (See Shutdown

Method, page 43.)

Indicates an outlet status error. A firmware upgrade may resolve the problem.

Š Clicking a Station icon opens its General, and Groups pages.

Š Clicking an Outlet icon opens its Configuration and Schedule pages.

Š Clicking a Group icon opens its General and Schedule pages.

Manual Power Management

In addition to automated power management (see To configure the schedule,

select Configuration at the far right of the menu bar. See Schedule, page 44 for

details, page 32), an Outlet or a Group’s power can be managed manually.

Clicking the outlet or group’s icon in the Sidebar brings up its General page:

Outlet General Page

27

PN5212 / PN5320 User Manual

Group General Page

With the exception of the power outlet icon, the pages are view only and provide power status and usage information. To configure the settings, select

Configuration at the far right of the menu bar. See Configuration, page 37 for details.

The color of the power outlet icon indicates its status (as explained in the table

on page 27). The power status of the outlet can be changed by clicking the icon.

Note: 1. The Outlet page’s Reboot checkbox is only enabled when the shutdown method is either Wake on Lan or System after AC Back, and the outlet status is On. If the box is enabled and checked, clicking the power outlet icon causes the connected device to reboot, rather than

shut down. See Shutdown Method, page 43, for further information.

2. When you click the icon to change the outlet’s power status, the icon flashes to indicate the change, but the icon doesn’t change to the new color at this time. You must leave the page and come back to it in order to see the changed color.

3. When you click the icon to change the outlet’s power status, the color of the outlet’s icon in the Sidebar doesn’t immediately change to the

new color. You must leave the Connections page and come back to it

in order to see the changed color.

4. For Outlet Groups, all of the outlets in the group turn On or Off together.

28

Chapter 5. Outlet Access

Connections

The Connections pages provide status and settings information for stations, outlets, and outlet groups. The pages that come up in the main panel differ depending on which item is selected in the Sidebar.

Station Level

When a station is selected in the Sidebar, the main panel page has three tabs:

Outlets, General, and Groups:

Outlets

The station’s Outlets page displays status information for that device and each of its power outlets:

Note: You can manually manage the outlet’s power status by clicking the

power outlet icon. See Manual Power Management, page 27 for details.

29

PN5212 / PN5320 User Manual

General

The station’s General page shows the station’s settings configuration:

This page only displays information. Settings changes cannot be made here. To

configure the settings, select Configuration at the far right of the menu bar. See

Configuration, page 37 for details.

Groups

The station’s Groups page lists the names of the outlet groups that have been created with its outlets in the left column. The outlets that make up the group are in the right column:

The outlets are displayed as [Station ID-Outlet Number]. For example, [C01-

05] refers to outlet number 5 belonging to station number 1.

This page only displays information. Settings changes cannot be made here. To configure Outlet Groups, select Configuration at the far right of the menu bar.

See Groups, page 39 for outlet group management details.

:

30

Chapter 5. Outlet Access

Outlet Level

When an outlet is selected in the Sidebar, the main panel tabs change to:

General, Configuration, and Scheduling:

Each of the tabs is described below.

General

The outlet’s General page provides information regarding the outlet’s name and power status:

You can manually turn the outlet On and Off from this page by clicking the

power outlet icon (see Manual Power Management, page 27 for details).

Configuration

The outlet’s Configuration page summarizes the various configuration settings that have been made for the outlet:

This page only displays information. Setting changes cannot be made here. To configure the settings, select Configuration at the far right of the menu bar. See

Configuration, page 37 for details.

31

PN5212 / PN5320 User Manual

Scheduling

The outlet’s Scheduling page shows the date and time schedule settings for automatic power control of the outlet:

To configure the schedule, select Configuration at the far right of the menu bar.

See Schedule, page 44 for details

32

Chapter 5. Outlet Access

Outlet Group Level

When an outlet group is selected in the Sidebar, the main panel tabs change to

General, and Schedule.

Each of the tabs is described below.

General

The outlet group’s General page provides information regarding the group’s name, the outlets that belong to the group, and the power status of the outlets:

You can manually turn the outlets On and Off from this page by clicking the

power outlet icon (see Manual Power Management, page 27 for details).

Note: All of the outlets in the group turn On or Off together.

Schedule

The outlet group’s Schedule page shows the date and time schedule settings for automatic power control of the outlet group. This page is similar to the Outlet

Schedule page discussed in the previous section.

33

PN5212 / PN5320 User Manual

User Preferences

The User Preferences page allows users to set up their own, individual, working environments. The PN5212 / PN5320 stores a separate configuration record for each user profile, and sets up the working configuration according to the Username that was keyed into the Login dialog box.

Make your settings changes according to the information given in the following table:

Setting

Language

Function

Selects the language that the interface displays in. Drop down the list of available languages to choose the one you want.

Logout Timeout If there is no user input for the amount of time set with this function, the user is automatically logged out. A login is necessary before the

PN5212 / PN5320 can be accessed again. Key in a value from 0–180 minutes.

Note: A setting of 0 (zero) disables this function, in which case users are never automatically logged out, no matter how much time passes.

Beeper If this is enabled (there is a check in the checkbox), the beeper sounds whenever any of the following conditions occur: the PN5212 /

PN5320 is powered On; whenever an environment alarm is triggered; whenever a device level alarm is triggered; whenever an outlet level alarm is triggered.

Note: This is the master alarm setting. If it is not enabled, no alarms will sound – even if they are enabled on the Station Level

configuration pages. (See page 41.)

Welcome

Message

Password

Fields

If this is enabled, a welcome message appears at the right side of the menu bar.

To change the user password, first key the old password into the Old

Password input box, then key the new password into the New

Password and Confirm Password input boxes.

34

Chapter 5. Outlet Access

Sessions

The Session page shows all of the users currently logged into the PN5212 /

PN5320, and provides information about each of their sessions.

Š The information under the IP heading indicates the IP address that the user is logged in from.

Š The information under the Client heading indicates whether the user has logged in via a browser connection (HTTPS), or from a local console.

Š Administrator have the option of forcing user logouts by selecting the user and clicking End Session.

Access

The Access page provides a way to assign permissions to users and groups at both the station level and individual power outlet levels. The items available differ depending on whether a station or an outlet is selected in the Sidebar.

Station Level

When a station is selected in the Sidebar, a page similar to the one below, displays in the main panel, with users and user groups listed in the left column.:

Š A check mark indicates the user or user group is authorized to perform the task indicated in the column head.

Š The permissions are the same ones assigned under user accounts. See

Permissions, page 49 for details.

When you have made your settings on this page, click Save.

35

PN5212 / PN5320 User Manual

Outlet Level

When an outlet is selected in the Sidebar, a page similar to the one below, comes up in the main panel:

Users and groups are listed alphabetically in the left column.

Š A check mark under the Access column, indicates the user or group is authorized to access and power control the selected outlet.

Š A check mark under the Outlet Configuration column, indicates the user or

group is authorized to configure the selected outlet’s settings (see

Configuration, page 37).

When you have made your settings on this page, click Save.

36

Chapter 5. Outlet Access

Configuration

The Configuration page is used to configure the operation of the PN5212 /

PN5320 at both the station level and the individual power outlet level. The items available differ depending on whether a station or an outlet is selected in the Sidebar.

Station Level Configuration

When a station is selected in the Sidebar, a page similar to the one below, displays in the main panel.

The station level Configuration page has two tabs: General, and Groups, as described in the sections that follow.

37

PN5212 / PN5320 User Manual

General

When the Configuration page opens, the station’s General page is selected.

This page allows you to set up a power management configuration for the device as a whole. The meanings of the field headings are given in the following table:

Heading

Device Name

Load Alarm

Meaning

To make things more convenient on a multi-station installation, each station can be given a distinctive name.

To name a station key in the name of your choice - up to

32 letters and numbers.

A checkmark in the check box disables an alarm from being triggered when the device’s current load falls outside of its specified range.

Device Threshold Settings These fields are used to set the maximum, minimum, and fluctuation threshold settings. If a range falls below the minimum setting, or exceeds the maximum setting an alarm is triggered.

In order to keep alarms from being constantly triggered due to slight fluctuations at the threshold points, you can set a fluctuation range that must be exceeded when a threshold is crossed in order for the alarm to be triggered.

For example, if there is a temperature threshold of 32 o and you set a fluctuation range of 2 o

, there won’t be an alarm triggered if the temperature fluctuates back and forth between 31 and 32 o

.

Temperature Unit Click a radio button to choose the temperature unit for the temperature sensor.

38

Chapter 5. Outlet Access

Groups

Outlet groups enable power configuration and control actions to be carried out on a selected group of outlets at the same time, rather than repeatedly performing the same action on each individual one. The Groups page lists the outlet groups that have already been configured, and shows which outlets are included in the group.

Note: In the Outlet column the outlets are displayed as [Station ID-Outlet

Number]. For example, [C01-05] refers to outlet number 5 belonging to

PN5212 / PN5320 station number 01.

This page is also used to create new outlet groups, as well as to modify or delete existing ones.

Š To Create an outlet group, do the following:

1. Click Add.

2. In the page that comes up, first key in a name that will help you identify the group, then click the plus sign (+) in front of the device name to show the list of outlets.

39

PN5212 / PN5320 User Manual

3. Click to put a checkmark in the checkbox of the outlets you want to add to the group, then click Save.

When you return to the Group page, your new group is included in the list:

Note: The group also shows up as a device in the Sidebar, and this page can be accessed by clicking on its icon in the Sidebar.

Š To Modify an outlet group, select it in the list, then click Modify. The screen that comes up is the same one that appears when you click Add.

You can rename the group as well as add and remove outlets. When you are done modifying the group click Save.

Š To Delete an outlet group, select it in the list, then click Delete.

40

Chapter 5. Outlet Access

Outlet Level Configuration

The configuration settings for a PN5212 / PN5320 can be specified on an outlet by outlet basis. When an outlet is selected in the Configuration page Sidebar, the main panel displays a page with two tabs: Configuration, and Schedule, as described in the sections that follow.

Configuration

The Configuration tab page, similar to the one below, is the default that appears in the main panel.

41

PN5212 / PN5320 User Manual

This page lets you set up the power management configuration for the selected outlet. The meanings of the field headings are given in the following table:

Heading

Outlet Name

Confirmation Required

Power On Delay

Power Off Delay

Meaning

Each outlet can be given a distinctive name. The maximum number of characters is 15.

If this option is enabled (there is a check in the checkbox), a dialog box comes up asking you to confirm a power operation before it is performed. If it is disabled (there is no check in the checkbox), the operation is performed without confirmation.

Sets the amount of time the PN5212 / PN5320 waits after

the Power Button is clicked (see Manual Power

Management, page 27), before it turns on the computer

attached to the corresponding outlet.

Note: The default delay time is 0 seconds; the maximum is 999 seconds. When a series of outlets are scheduled to be powered up, they turn on in sequence with a default delay of 10 milliseconds between each outlet.

Sets the amount of time the PN5212 / PN5320 waits after

the Power Button is clicked (see Manual Power

Management, page 27), before it turns off the computer

attached to the corresponding outlet.

For the System after AC Back option (see below), after the delay time expires, the PN5212 / PN5320 waits another fifteen seconds, then shuts the computer down.

The default delay time is 15 seconds. The maximum delay time is 999 seconds.

42

Chapter 5. Outlet Access

Heading

Shutdown Method

MAC Address

Meaning

There are three choices for the Shutdown method. Drop down the list to select a choice. The meaning of each choice is described, below:

Wake on LAN: This is a Safe Shutdown and Restart option. If this is selected, when an Outlet is turned Off, the PN5212 / PN5320 first sends a message to the computer telling it to prepare for a shutdown; it then waits for the amount time set in the Power Off Delay

field to give the OS time to close down before the computer is powered down to standby mode.

Likewise, when the Outlet is turned On, the PN5212 /

PN5320 waits for the amount time set in the Power On

Delay field, then sends an Ethernet message to the computer connected to the Outlet telling the computer to turn itself On.

Note: For Safe Shutdown and Restart, the computer must be running Windows (Windows 98 or higher), and the Safe Shutdown program (available by download from our website), must be installed and running on the computer.

System after AC Back: This is a Safe Shutdown and

Restart option. If this is selected, when an Outlet is turned Off, the PN5212 / PN5320 first sends a message to the computer telling it to prepare for a shutdown; it then waits for the amount time set in the Power Off

Delay field to give the OS time to close down before the computer is powered down.

When the Outlet is turned On, the PN5212 / PN5320 waits for the amount time set in the Power On Delay field, then sends power to the server. When the server receives the power, it turns itself on.

Note: For Safe Shutdown and Reboot, the computer must be running Windows (Windows 98 or higher), and the Safe Shutdown program (available by download from our website), must be installed and running on the computer.

Kill the Power: If this option is selected, the PN5212 /

PN5320 waits for the amount time set in the Power Off

Delay field, and then turns the Outlet's power Off.

Turning the power off performs a cold (non-safe) shutdown.

In order to use either of the Safe Shutdown and Restart methods the MAC address of the computer connected to the outlet must be filled in here.

When you have finished making your configuration settings, click Save.

43

PN5212 / PN5320 User Manual

Schedule

Clicking the Schedule tab brings up a page that lets you set up a scheduled power On/Off configuration for the selected outlet:

The meanings of the field headings are given in the table, below:

Heading

Routine Type

Week Day

Date

Start Date

End Date

Shutdown Time

Meaning

Drop down the list to select whether the scheduled power configuration should take place just Once, or on a Daily,

Weekly, or Monthly basis.

This field only becomes active if you choose Weekly as the routine type. If you choose Weekly, drop down the list to choose which day of the week you want the power management routine to take place on.

This field only becomes active if you choose Monthly as the routine type. If you choose Monthly, drop down the list to choose which day of the month you want the power management routine to take place on.

If you want to limit the power management routine to a particular time period, either click the calendar icon to select the date that the routine will start at, or key in a start date using the

YYYY-MM-DD format

If you want to limit the power management routine to a particular time period, either click the calendar icon to select the date that the routine will end at, or key in an end date using the

YYYY-MM-DD format

Key in the time of day you want the shutdown to take place using the HH:MM format.

If you want to temporarily suspend this function without deleting the entry, click to put a check in the Disable checkbox at the right of this field. You can reinstate the function by unchecking the checkbox.

44

Chapter 5. Outlet Access

Heading

Restart Time

Every

Meaning

Key in the time of day you want the restart to take place using the HH:MM format.

If you want to temporarily suspend this function without deleting the entry, click to put a check in the Disable checkbox at the right of this field. You can reinstate the function by unchecking the checkbox.

For added flexibility, you can use this field to refine the Daily,

Weekly, and Monthly routines. For example, if you chose Daily as your routine type, you could have the routine take place every 3 days (instead of every day), by keying a 3 in this field.

After you have made your schedule settings, click Add. The schedule is summarized in the list at the bottom of the panel.

To remove the outlet’s schedule, select it in the list and click Delete.

45

PN5212 / PN5320 User Manual

This Page Intentionally Left Blank

46

Chapter 6

User Management

Overview

When you select the User Management tab the screen comes up with Accounts selected in the Menu bar, and the User List displayed in the main panel:

47

PN5212 / PN5320 User Manual

The Accounts page has two menu items: Accounts, for managing individual users; and Groups, for managing user groups.

Note: There is a pre-installed super administrator account. It can be used to set up the device and to begin creating users and groups. The Username for this account is administrator; the password is password. For security purposes, we strongly recommend changing these to something unique.

See Modifying User Accounts, page 51 for details.

Users

Adding Users

To add a user, do the following:

1. Select Users in the Sidebar.

2. Click Add at the bottom of the User List in the main panel. The page opens with three tabs at the top: User, Groups, and Devices. The User tab is selected by default:

48

Chapter 6. User Management

3. Enter the required information in the appropriate fields. A description of each of the fields is given in the table below:

Field

Username

Description

From 1 to16 characters are allowed depending on the

Account Policy settings. See Account Policy, page 80.

Password

Confirm Password To be sure there is no mistake in the password, you are asked to enter it again. The two entries must match.

User Type

From 1 to16 characters are allowed depending on the

Account Policy settings. See Account Policy, page 80.

Permissions

There are three categories: Super Administrator,

Administrator and User. There is no limitation on the number of accounts that can be created in each category.

Š

The super administrator is responsible for the overall installation configuration and maintenance; user management; and device and outlet assignments.

Š

Administrators have User Management, Device

Management, and Maintenance privileges, as well as being able to access specified devices and outlets.

Š

Users can access the devices and outlets assigned to them by the super administrator or administrator.

Additional privileges can be assigned to them by the super administrator or administrator (see Permissions, below).

Š

Super administrators automatically have all permissions.

Š

Administrators automatically have User Management,

Device Management, Java Client, and Maintenance permissions. They can be given additional permissions by checking the appropriate boxes.

Š

Ordinary users Java Client automatic privileges only. Their permissions are set individually by checking the appropriate boxes.

Š

Checking User Management, Device Management,

Log, and/or Maintenance gives the user access to the respective tabs (on the tab bar), allowing the user to set and change the configuration parameters for the checked items.

Š

Java Client allows a user to access the Power Over the NET™ device with Java Client software in addition to (or instead of) the browser access method.

Š

Modem allows a user to access the Power Over the

NET™ device using a modem connection.

49

PN5212 / PN5320 User Manual

Status

Field Description

Status allows you to control the user’s account and access to the installation, as follows:

Š

Disable Account lets you suspend a user’s account without actually deleting it, so that it can be easily reinstated in the future.

Š

If you don’t want to limit the time scope of the account, select Account never expires; if you want to limit the amount of time that the account remains in effect, select

Account expires on, and key in the expiration date.

Š

To require a user to change his password at the next logon, select User must change password at next logon.

This can be used by the administrator to give the user a temporary password to log in for the first time, and then let the user set the password of his choice for future logins.

Š

To make a password permanent, so that the user cannot change it to something else, select User cannot change

password.

Š

For security purposes, administrators may want users to change their passwords from time to time.

Š

If not, select Password never expires. This allows users to keep their current passwords for as long as they like.

Š

If so, select Password expires after, and key in the number of days allowed before the password expires.

Once the time is up, a new password must be set.

4. When your selections have been made click Save.

5. When the Operation Succeeded message appears, click OK.

You return to the main screen. The new user appears in the Sidebar Users tree and in the User List of the main panel.

The large main panel shows the user’s name; the description that was given when the account was created; and whether the account is currently active or has been disabled.

50

Chapter 6. User Management

Modifying User Accounts

To modify a user account, do the following:

1. In the Sidebar User tree, click the user’s name

– or –

In the main panel, select the user’s name, then click Modify.

2. In the User page that comes up is the same as the one for adding users (see page 48). Make your changes, then click Save.

Deleting User Accounts

To delete a user account do the following:

1. In the main panel, select the user’s name, then click Delete.

2. Click OK.

Moving On

From here, we move on to the Groups menu entry. The Groups tab page that is

part of the Accounts menu is discussed under Users and Groups, page 55. The

Devices tab page is discussed under Device Assignment, page 59.

51

PN5212 / PN5320 User Manual

Groups

Groups allow administrators to easily and efficiently manage users and devices. Since device access rights apply to anyone who is a member of the group, administrators need only set them once for the group, instead of having to set them for each user individually. Multiple groups can be defined to allow some users access to specific devices, while restricting other users from accessing them.

Note: This section refers to the Groups menu. The Groups tab that appears

when the Accounts menu item is selected, is discussed on page 55.

Creating Groups

To create a group, do the following:

1. Select Groups on the menu bar.

2. Select User Groups in the Sidebar.

3. Click Add at the bottom of the Group List in the main panel. The page opens with three tabs at the top: Groups, Members, and Devices. The

Groups tab is selected by default:

52

Chapter 6. User Management

4. Enter the required information in the appropriate fields. A description of each of the fields is given in the table below:

Field

Group Name

Permissions

Status

Description

A maximum of 16 characters is allowed.

Group permissions are set by checking the appropriate boxes, as follows:

Š

Checking User Management, Device Management,

Log, and/or Maintenance gives all group members access to the respective tabs (on the tab bar), allowing the user to set and change the configuration parameters for the checked items.

Š

Java Client allows a user to access the Power Over the NET™ device with Java Client software in addition to (or instead of) the browser access method.

Š

Modem allows a user to access the Power Over the

NET™ device using a modem connection.

Š

Checking Disable Group allows the administrator to suspend a group’s authorization without having to delete the group. This way, the group can be easily reinstated without having to create it all over again

– simply by unchecking the box.

Š

If administrators only want the group to exist for a certain period of time, they can click the Group

expires on radio button and then specify and expiration date (YYYY-MM-DD). The default setting is Group never expires.

5. When your selections have been made click Save.

6. When the Operation Succeeded message appears, click OK.

You return to the main screen. The new group appears in the Sidebar User

Groups list and in the Group List of the main panel.

53

PN5212 / PN5320 User Manual

Modifying Groups

To modify a group, do the following:

1. In the Sidebar Group tree, click the group’s name

– or –

In the main panel, select the group’s name, then click Modify.

2. The Groups page that comes up is the same as the one for adding groups

(see page 52). Make your changes, then click Save.

Deleting Groups

To delete a group do the following:

1. In the main panel, select the group’s name, then click Delete.

2. Click OK.

54

Chapter 6. User Management

Users and Groups

There are two ways to assign users to – and remove users from – groups: from the Accounts menu; and from the Groups menu.

Note: 1. Before you can assign users to groups, you must first create them.

See Adding Users, page 48 for details.

2. If a user has permissions in addition to the ones assigned to the group, the user keeps those permissions in addition to the group ones.

Assigning Users to a Group From the Accounts Page

To assign a user to a group from the Accounts page, do the following:

1. In the Sidebar Users tree, click the user’s name

– or –

In the main panel, select the user’s name, then click Modify.

2. In the page that comes up, select the Groups tab. A page similar to the one below appears:

3. In the Available column, select the group that you want the user to be in.

4. Click the Right Arrow to put the group’s name into the Selected column.

5. Repeat the above for any other groups that you want the user to be in.

6. Click Save when you are done.

55

PN5212 / PN5320 User Manual

Removing Users From a Group From the Accounts Page

To remove a user from a group from the Accounts page, do the following:

1. In the Sidebar Users tree, click the user’s name

– or –

In the main panel, select the user’s name, then click Modify.

2. In the page that comes up, select the Groups tab. A screen, similar to the one below, appears:

3. In the Selected column, select the group that you want to remove the user from.

4. Click the Left Arrow to remove the group’s name from the Selected column. (It goes back into the Available column.)

5. Repeat the above for any other groups that you want to remove the user from.

6. Click Save when you are done.

56

Chapter 6. User Management

Assigning Users to a Group From the Groups Page

To assign a user to a group from the Groups page, do the following:

1. In the Sidebar User Groups tree, click the group’s name

– or –

In the main panel, select the group’s name, then click Modify.

2. In the page that comes up, select the Members tab. A screen, similar to the one below, appears:

3. In the Available column, select the user that you want to be a member of the group.

4. Click the Right Arrow to put the user’s name into the Selected column.

5. Repeat the above for any other users that you want to be members of the group.

6. Click Save when you are done.

57

PN5212 / PN5320 User Manual

Removing Users From a Group From the Groups Page

To remove a user from a group from the Groups page, do the following:

1. In the Sidebar User Groups tree, click the group’s name

– or –

In the main panel, select the group’s name, then click Modify.

2. In the page that comes up, select the Members tab. A screen, similar to the one below, appears:

3. In the Selected column, select the user that you want to remove from the group.

4. Click the Left Arrow to remove the user’s name from the Selected column. (It goes back into the Available column.)

5. Repeat the above for any other users that you want to remove from the group.

6. Click Save when you are done.

58

Chapter 6. User Management

Device Assignment

When a user logs in to the Power Over the NET™ device, the interface comes up with the Outlet Access page displayed. All the outlets that the user is permitted to access are listed in the Sidebar at the left of the page. Access permissions for those outlets can be assigned on an outlet-by-outlet basis from the Accounts menu for individual users, or the Groups menu for user groups.

Assigning Device Permissions From the Accounts Menu

To assign device permissions to a user from the Accounts menu, do the following:

1. In the Sidebar Users tree, click the user’s name

– or –

In the main panel, select the user’s name, then click Modify.

2. In the that comes up, select the Devices tab. A screen, similar to the one below, appears:

Note: The page comes up with the outlets nested under the devices. Click the plus sign in front of a device’s name to show the outlets.

Š Outlets are listed in the left hand column. Permissions can be set on an outlet-by-outlet basis.

Š The Access column is where device access rights are set.

Š The Configuration column enables/disables a user from making configuration changes to the outlet settings.

59

PN5212 / PN5320 User Manual

3. Under the Access column, click to permit or restrict the user’s access to an outlet. A check mark (

) indicates that the user has permission to access the outlet; a blank checkbox means that the user is denied permission to access the outlet.

4. Under the Configuration column, click to permit or restrict the user’s ability to change the outlet’s configuration settings. A check mark (

) indicates that the user has permission to make changes to the outlet’s

configuration settings (see Chapter 7, Device Management); a blank

checkbox means that the user is denied permission to make changes to the outlet’s configuration settings.

5. In the confirmation popup that appears, click OK.

Assigning Device Permissions From the Groups Page

To assign device permissions to a Group of users, do the following:

1. In the Sidebar User Groups tree, click the group’s name

– or –

In the main panel, select the group’s name, then click Modify.

2. In the page that comes up, select the Devices tab.

3. The screen that comes up is the same one that appears when assigning permissions from the Accounts page. Make your device assignments

according to the information described under Assigning Device

Permissions From the Accounts Menu, page 59.

The only difference is that whatever settings you make apply to all members of the group instead of just one individual member.

60

Chapter 7

Device Management

Overview

The Device Management page allows super administrators, administrators, and users with device management permission to configure and control overall

Power Over the NET™ device operations.

Device Information

When you click the Device Management tab, the display opens with the

Device Information menu page displayed:

61

PN5212 / PN5320 User Manual

The page presents information about the selected device, as described in the following table.

Item

Device Name

MAC Address

Meaning

This field lets you give the device a unique name. This can be convenient when you need to differentiate among several devices in multi station installations. Simply delete whatever is in the text box and key in the name of your choice. Click Save to save the new name.

This item displays the Power Over the NET™ device’s MAC address.

Firmware Version This item displays the current firmware version number. You can reference it to see if there are newer versions available on the

ALTUSEN website.

IPv4 Address

IPv6 Address

This item displays the IP address of the device’s network interface in the traditional format.

This item displays the IP address of the device’s network interface in the new format.

62

Chapter 7. Device Management

Network

The Network page is used to specify the Power Over the NET™ device’s network environment. The main section is divided into 5 panels. Select the device you want to configure in the Sidebar, then fill in the information in the panels according to the information given in the sections that follow.

When you have finished making all of your configuration settings, click Save

(at the bottom of the page).

Service Ports

As a security measure, if a firewall is being used, the Administrator can specify the port numbers that the firewall will allow. If a port other than the default is used, users must specify the port number as part of the IP address when they log in. If an invalid port number (or no port number) is specified, the Power

Over the NET™ device will not be found.

An explanation of the fields is given in the table below:

HTTP

HTTPS

Field Explanation

The port number for a browser login. The default is 80.

The port number for a secure browser login. The default is 443.

Note: 1. Valid entries for all of the Service Ports are from 1–65535.

2. The service ports cannot have the same value. You must set a different value for each one.

3. If there is no firewall (on an Intranet, for example), it doesn’t matter what these numbers are set to, since they have no effect.

63

PN5212 / PN5320 User Manual

Settings

This field specifies the time interval for the browser page to automatically refresh and display the latest power information.

IP Installer

The IP Installer is an external Windows-based utility for assigning IP addresses to the Power Over the NET™ device.

Click one of the radio buttons to select Enable, View Only, or Disable for the

IP Installer utility. See Method 1:, page 133, for IP Installer details.

Note: 1. If you select View Only, you will be able to see the Power Over the

NET™ device in the IP Installer’s Device List, but you will not be able to change the IP address.

2. For security, we strongly recommend that you set this to View Only or Disable after use.

64

Chapter 7. Device Management

IPv4 Configuration

The device’s IPv4 IP and DNS addresses (the traditional method of specifying

IP addresses) can either be assigned dynamically (DHCP), or a fixed IP address can be specified.

Š For dynamic IP address assignment, select the Obtain IP address

automatically radio button. (This is the default setting.)

Š To specify a fixed IP address, select the Set IP address manually radio button and fill in the IP address with values appropriate for your network.

Š For automatic DNS Server address assignment, select the Obtain DNS

Server address automatically radio button.

Š To specify the DNS Server address manually, select the Set DNS server

address manually radio button, and fill in the addresses for the Preferred and Alternate DNS servers with values appropriate for your network.

Note: 1. If you choose Obtain IP address automatically, when the device starts up it waits to get its IP address from the DHCP server. If it hasn’t obtained the address after one minute, it automatically reverts to its factory default IP address (192.168.0.60.)

2. If the device is on a network that uses DHCP to assign network

addresses, and you need to ascertain its IP address, see IP Address

Determination, page 133, for information.

3. Specifying the Alternate DNS Server address is optional.

65

PN5212 / PN5320 User Manual

IPv6 Configuration

The device’s IPv6 IP and DNS addresses (the new method of specifying IP addresses) can either be assigned dynamically, or a fixed IP address can be specified.

Š For dynamic IP address assignment, select the Enable Autoconfiguration radio button. (This is the default setting.)

Š To specify a fixed IP address, select the Set configuration manually radio button and fill in the IP address, Static Prefix Length, and Default

Gateway fields with values appropriate for your network.

Š For automatic DNS Server address assignment, select the Use DHCPv6 to

obtain DNS Server Addresses radio button.

Š To specify the DNS Server address manually, select the Set DNS server

address manually radio button, and fill in the addresses for the Preferred and Alternate DNS servers with values appropriate for your network.

Note: Specifying the Alternate DNS Server address is optional.

66

Chapter 7. Device Management

ANMS

The ANMS (Advanced Network Management Settings) page is used to set up event notifications, login authentication and authorization management from external sources, and CC Management. It is organized in three tabbed pages:

Event Notification; Authentication & Authorization; and CC Management.

These pages are explained in the sections that follow

Event Notification

When you select ANMS on the menu bar, the GUI displays the Event

Notification tab’s page. The page is divided into 4 sections: SMTP Settings;

Log Server; SNMP Trap Receivers; and Syslog Server. Each section is described below.

SMTP Settings

To have the Power Over the NET™ device email reports from the SMTP server to you, do the following:

1. Enable the Enable report from the following SMTP server, and key in the

IP address of your SMTP server.

2. If your server requires authentication, put a check in the My server

requires authentication checkbox.

3. Key in the appropriate account information in the Account Name,

Password, and From field.

Note: Only one email address is allowed in the From field, and it cannot exceed 64 Bytes. (1 Byte = 1 English alphanumeric character.)

67

PN5212 / PN5320 User Manual

4. Key in the email address (addresses) of where you want the event reports sent to in the To field.

Note: If you are sending the report to more than one email address, separate the addresses with a semicolon. The total cannot exceed

256 Bytes.

Log Server

Important transactions that occur on the Power Over the NET™ device, such as logins and internal status messages, are automatically generated and kept by an ATEN Log Server program. Specify the MAC address of the computer that the Log Server resides on, and the service port number used. The valid port range is 1-65535. The default port number is 9001.

Note: 1. Make sure that the port number you specify here matches the one you

specify in the Log Server’s configuration settings (see Configure, page 99).

2. The port number must different than the one used for the Program

port (see Service Ports, page 63).

Installation and operation of the Log Server is discussed in Chapter 10. The

Log File is discussed on page 85.

68

SNMP Trap Receivers

Chapter 7. Device Management

Up to four SNMP management stations can be specified. If you want to use

SNMP trap notifications, do the following:

1. Check Enable SNMP Trap.

2. Key in the IP address(es) and the service port number(s) of the computer(s) to be notified of SNMP trap events. The valid port range is

1–65535. The default port number is 192.

Note: Make sure that the port number you specify here matches the port number used by the SNMP receiver computer.

3. Key in the Community name(s) that correspond to each of the stations.

69

PN5212 / PN5320 User Manual

Syslog Server

To record all the events that take place on Power Over the NET

TM

devicees and write them to the PN5212 / PN5320 Syslog server, do the following:

1. Check Enable.

2. Key in the IP address and the port number of the Syslog server. The valid port range is 1-65535. The default port number is 514.

Finishing Up

When you have finished making your settings on this page, click Save.

70

Chapter 7. Device Management

Authentication & Authorization

The Authentication & Authorization page is used to set up login authentication and authorization management from external sources.

Disable Local Authentication

Selecting this option will disable login authentication locally on the Power

Over the NET™ device. The device can only be accessed using LDAP,

LDAPS, MS Active Directory, RADIUS, TACACS+, or CC Management authentication.

RADIUS Settings

To allow authentication and authorization for the Power Over the NET™ device through a RADIUS server, do the following:

1. Check Enable.

2. Fill in the IP addresses and service port numbers for the Preferred and

Alternate RADIUS servers. The default port number for the Preferred server is 1812; the default port number for the Alternate server is 1645.

Note: Make sure that the port numbers you specify here match the port numbers used by the RADIUS servers.

3. In the Timeout field, set the time in seconds that the Power Over the

NET™ device waits for a RADIUS server reply before it times out.

71

PN5212 / PN5320 User Manual

4. In the Retries field, set the number of allowed retries for attempting to connect to the RADIUS server.

5. In the Shared Secret field, key in the character string that you want to use for authentication between the Power Over the NET™ device and the

RADIUS Server.

6. On the RADIUS server, set the entry for each user as follows: su/xxxx

Where xxxx represents the Username given to the user when the account was created on the Power Over the NET™ device. The user’s access rights are the ones assigned for the Power Over the NET™ device, as well.

(See Adding Users, page 48.)

LDAP/AD Settings

72

Chapter 7. Device Management

To allow authentication and authorization for the Power Over the NET™ device through an LDAP/AD server, refer to the information in the table, below:

Enable

Item

Enable SSL

Preferred/Alternate

LDAP Server IP

Action

Put a check in the Enable checkbox to allow LDAP authentication and authorization.

Put a check in the Enable SSL checkbox to specify an SSL connection.

Fill in the IP address for the preferred/alternate LDAP server.

The default port number is 389; for LDAPS, the default port number is 636.

Preferred/Alternate

LDAP Service Port

Preferred/Alternate

LDAP SSL Service Port

Fill in the SSL port number for the preferred/alternate LDAP server. The default port number is 636.

Timeout

Fill in the port number for the preferred/alternate LDAP server. The default port number is 389.

Admin DN

Set the time in seconds that the Power Over the NET™ device waits for an LDAP server reply before it times out.

Consult the LDAP / LDAPS administrator to ascertain the appropriate entry for this field. For example, the entry might look like this: ou=kn4132,dc=aten,dc=com

Admin Name

Password

Search DN

Key in the LDAP administrator’s username.

Key in the LDAP administrator’s password.

Set the distinguished name of the search base. This is the domain name where the search starts for user names.

Note: If LDAP is enabled, the LDAP schema for MS Active Directory must

be extended. See LDAP Server Configuration, page 113 for details.

73

PN5212 / PN5320 User Manual

TACACS+

To allow authentication and authorization for the Power Over the NET™ device through a TACACS+ server, do the following:

1. Check Enable.

2. Fill in the IP addresses and port numbers for the Preferred and Alternate

TACACS+ servers. The default port number is 49.

Note: Make sure that the port numbers you specify here match the port numbers used by the TACACS+ servers.

3. In the Shared Secret field, key in the character string that you want to use for authentication between the Power Over the NET™ device and the

TACACS+ Server.

Finishing Up

When you have finished making your settings on this page, click Save.

74

Chapter 7. Device Management

CC Management

This page allows you to manage authentication and authorization for the Power

Over the NET™ device through a CC (Control Center) server. If this is enabled, users will be able to access the device via their CC session.

To allow authentication and authorization for the Power Over the NET™ device through a CC (Control Center) server, check Enable and fill in the CC

Server’s IP address and the port that it listens on in the appropriate fields.

When you have finished making your settings on this page, click Save.

75

PN5212 / PN5320 User Manual

OOBC

In case the LAN that the Power Over the NET™ device resides on goes down, or the it cannot be accessed with the usual browser based method for some other reason, the device can be accessed via an Out of Band method utilizing its Console.

The OOBC page is used to set up the serial configuration parameters for serial terminal Out of Band access to the Power Over the NET™ device, as described in the section that follows.

Š To operate the PN5212 / PN5320 from a local computer's console terminal

(HyperTerminal, GTKTerminal, etc.), connect the PN5212 / PN5320’s

Console port to the COM port of a local computer (see Single Stage

Installation, page 11, and Console Terminal Session, page 105).

Console Port Settings

For serial terminal operation, this section sets the serial parameters of the

Power Over the NET™ device’s Console port.

Note: The Console port’s serial parameters and the parameters of the device it connects to must both be the same.

76

Chapter 7. Device Management

Security

The Security page controls access to the Power Over the NET™ device.

77

PN5212 / PN5320 User Manual

Login String

The Login String entry field is used to specify a login string (in addition to the

IP address) that users must include when accessing the Power Over the NET™ device with a browser. For example:

192.168.0.126/abcdefg

Š The following characters are allowed:

0–9 a–z A–Z ~ ! @ $ ^ & * ( ) _ + ‘ - = [ ] { } ; ’ < > , . |

Š The following characters are not allowed:

Š % ” : / ? # \ [Space]

Š Compound characters (É Ç ñ ... etc.)

Note: 1. There must be a forward slash between the IP address and the string.

2. If no login string is specified here, anyone will be able to access the

Power Over the NET

TM

device login page using the IP address alone.

This makes your installation less secure.

For security purposes, we recommend that you change this string occasionally.

IP and MAC Filtering

If any filters have been configured, they appear in the IP Filter and/or MAC

Filter list boxes.

IP and MAC Filters control access to the Power Over the NET™ device based on the IP and/or MAC addresses of the client computers attempting to connect.

A maximum of 100 IP filters and 100 MAC filters are allowed.

To enable IP and/or MAC filtering, click to put a check mark in the IP Filter

Enable and/or MAC Filter Enable checkbox.

Š If the include button is checked, all the addresses within the filter range are allowed access; all other addresses are denied access.

Š If the exclude button is checked, all the addresses within the filter range are denied access; all other addresses are allowed access.

78

Chapter 7. Device Management

Adding Filters

To add an IP filter, do the following:

1. Click Add. A dialog box similar to the one below appears:

2. Specify the filter address in the dialog box (for example, 192.168.0.200), then click OK.

A second dialog box, similar to the one below, appears:

3. To filter a single IP address, key in the same address as the start IP. To filter a continuous range of addresses, key in the end number of the range

(for example, 192.168.0.225).

4. After filling in the address, click OK.

Repeat these steps for any additional IP addresses you want to filter.

To add a MAC filter, do the following:

1. Click Add. A dialog box similar to the one below appears:

79

PN5212 / PN5320 User Manual

2. Specify the MAC address in the dialog box (for example, 001074670000), then click OK.

Repeat these steps for any additional MAC addresses you want to filter.

IP Filter / MAC Filter Conflict

If there is a conflict between an IP filter and a MAC filter – for example, where a computer’s IP address is allowed by the IP filter but it’s MAC address is excluded by the MAC filter – then that computer’s access is blocked.

In other words, if either filter blocks a computer, then the computer is blocked, no matter what the other filter is set to.

Modifying Filters

To modify a filter, select it in the IP Filter or MAC Filter list box and click

Modify. The Modify dialog box is similar to the Add dialog box. When it comes up, simply delete the old address(es) and replace it with the new one(s).

Deleting Filters

To delete a filter, select it in the IP Filter or MAC Filter list box and click

Delete.

Account Policy

The Account Policy section governs policies in regard to usernames and passwords. Check a policy and enter the required information in the appropriate fields.

Item

Minimum Username Length

Description

Sets the minimum number of characters required for a username. Acceptable values are from 1–16.

Minimum Password Length

Password Must Contain At Least Checking any of these items requires users to include at least one of the specified items in their password.

Note: This policy does not affect existing user accounts. Only new user accounts created after this policy has been enabled, and users required to change their passwords are affected.

Disable Duplicate Login

Sets the minimum number of characters required for a password. Acceptable values are from 1–16.

Check this to prevent users from logging in with the same account at the same time.

80

Chapter 7. Device Management

Private Certificate

When logging in over a secure (SSL) connection, a signed certificate is used to verify that the user is logging in to the intended site. For enhanced security, the

Private Certificate section allows you to use your own private encryption key and signed certificate, rather than the default ATEN certificate.

There are two methods for establishing your private certificate: generating a self-signed certificate; and importing a third-party certificate authority (CA) signed certificate.

Generating a Self-Signed Certificate

If you wish to create your own self-signed certificate, a free utility –

openssl.exe – is available for download over the web. See Self-Signed Private

Certificates, page 139 for details about using OpenSSL to generate your own

private key and SSL certificate.

Obtaining a CA Signed SSL Server Certificate

For the greatest security, we recommend using a third party certificate authority (CA) signed certificate. To obtain a third party signed certificate, go to a CA (Certificate Authority) website to apply for an SSL certificate. After the CA sends you the certificate and private encryption key, save them to a convenient location on your computer.

Importing the Private Certificate

To import the private certificate, do the following:

1. Click Browse to the right of Private Key; browse to where your private encryption key file is located; and select it.

2. Click Browse to the right of Certificate; browse to where your certificate file is located; and select it.

3. Click Upload to complete the procedure.

Note: 1. Clicking Restore Default returns the device to using the default

ATEN certificate.

2. Both the private encryption key and the signed certificate must be imported at the same time.

When you have finished making your settings on this page, click Save.

81

PN5212 / PN5320 User Manual

Customization

The Customization page is used to set Login Failure and Working Mode parameters.

Login Failures

Š Allowed sets the number of consecutive failed login attempts that are permitted from a remote user.

Š Timeout sets the amount of time a remote user must wait before attempting to login again after exceeding the number of allowed failures.

Working Mode

Š If ICMP is enabled, the Power Over the NET

TM

device can be pinged. If it is not enabled, the device cannot be pinged. The default is Enabled.

Š To permit browser access to the Power Over the NET

TM

device, click to put a check mark in the Enable Browser checkbox. If browser access is not enabled, users must use the Java Client AP program to access the switch.

The default is Enabled.

Š Enabling Multiuser operation permits up to 32 users to log in at the same time to share the remote bus. If not enabled, only one user can log in at a time. The default is Enabled.

When you have finished making your settings on this page, click Save.

82

Chapter 7. Device Management

Date/Time

The Date/Time dialog page sets the Power Over the NET

TM

device time parameters:

Set the parameters according to the information below.

Time Zone

Š To establish the time zone that the Power Over the NET

TM

device is located in, drop down the Time Zone list and choose the city that most closely corresponds to where it is at.

Š If your country or region employs Daylight Saving Time (Summer Time), check the corresponding checkbox.

83

PN5212 / PN5320 User Manual

Manual Input

Use this section to specify the Power Over the NET

TM

device’s date and time manually.

Š Click the calendar icon and click the calendar entry for the date.

Š Key the time into the Time field, using the HH:MM:SS (hours, minutes, seconds) format.

Note: This section is only enabled when auto adjustment (in the Network Time section) is disabled (the checkbox is unchecked).

As an alternative to specifying the date and time by entering them into the date and time fields, you can click to put a check in the Sync with PC checkbox, in which case the Power Over the NET™ device will take its date and time settings from the locally connected PC.

Network Time

To have the time automatically synchronized to a network time server, do the following:

1. Check the Enable auto adjustment checkbox.

2. Drop down the time server list to select your preferred time server

– or –

Check the Preferred custom server IP checkbox, and key in the IP address of the time server of your choice.

3. If you want to configure an alternate time server, check the Alternate time

server checkbox, and repeat step 2 for the alternate time server entries.

4. Key in your choice for the number of days between synchronization procedures.

Finishing Up

When you have finished making your settings on this page, click Save.

After you have saved your changes, if you want to synchronize immediately, click Adjust Time Now.

84

Chapter 8

Log

Overview

The PN5212 / PN5320 keeps an extensive record of all the transactions that take place on its installation. The Log page provides a powerful array of filters and functions that allow you to view and export the log file data, as well as be informed by email of specified events as they occur.

System Log

When you click the Log tab, the display opens with the System Log menu page, which looks similar to the one below:

85

PN5212 / PN5320 User Manual

The Log Event List

Š Clicking on a device in the Sidebar displays its log events in the main panel’s log event list.

Š Clicking the Refresh button brings the log list up to date with the latest events.

Š The entry box to the right of the Refresh button lets you set the number of events to display per page. Simply key in the number of your choice.

Š The top right of the main panel shows the total number of pages in the log file, and what page you are currently viewing.

Š The icons in the row just below the log event list are explained in the table, below:

Icon Function

Clear: Click to erase the contents of the log event list.

Search: Click to bring up a dialog box with search parameters that let you refine the display to items that fall within the parameters

you choose. See Search, page 87 for details.

Click to go to the first page of the log event list.

Click to move to the previous page of the log event list.

Click to move to the next page of the log event list.

Click to move to the last page of the log event list.

Click to save the contents of the log event list to file. See Save, page 88 for details.

Click to print the contents of the log event list.

86

Chapter 8. Log

Search

Search allows you to search for events according to selected criteria, such as: specific words, users, date, time, severity, and category. You can also search on any combination of criteria to refine the search even further.

When you click the Search icon, a Search panel, similar to the one below, appears:

Š To search on a keyword, key it into the Keyword text box.

Š To search for a user, click the arrow at the right of the User entry box and make your selection from the drop down list.

Š To search by date, click on the calendar icons to the right of the From and

To fields and click on the appropriate dates. To search on a single day, pick the same day for both fields.

Š To search by time drop down the lists for hours and seconds in the From and To fields and click on the appropriate figures.

Š By default, all the Severity and Category items are checked and will be included in the search criteria. To deselect an item, click on its checkbox.

Š To return the panel to its default settings (all entry fields blank or zero; all

Server and Category items checked) click Reset.

Š To begin the search, click Submit.

Š To dismiss this panel, click the Search icon again.

87

PN5212 / PN5320 User Manual

Save

Save allows you to save the contents of the event log list (or the results of a Search), to a file. When you click the Save icon, similar to the one below appears:

To save specified logged events to a file, do the following:

1. Click one of the radio buttons to specify the file format you want to save the file in (csv files can be read by a spreadsheet program).

2. Click Save.

After a moment, a dialog box similar to the one below, comes up:

3. Select Save File, then click OK.

88

Chapter 8. Log

Notification Settings

The Notification Settings page is used to specify which of the PN5212 /

PN5320’s components will receive notification of a log event. When you click the Notification Settings menu item, a page similar to the one below appears:

Š The event categories are listed in the left column.

Š When you first open the page, only the main category items appear.

(Main category item rows have a gray background.)

Š Sub-category items are nested under the main category headings. Click the arrow in front of the main category headings to display the subcategory items. (Sub-category item rows have a white background.)

Š Click the checkboxes under the column headings to select which component(s) will receive notification of the log events.

Š Clicking on a main category heading’s row automatically selects all the sub-category items nested below it.

Š If you only want to set notification for some of the sub-category events, don’t put a check in the main category row. Instead, drop down the sub-category list, and only check the sub-category events you want.

Š When you have finished making your setting choices, click Save. When a specified log event occurs, notification of that event will be sent to the selected component.

Š Reset Digital Output: If an event has been triggered that changes the digital output sensor from Low to High, click this button to return the sensor to the Low state.

89

PN5212 / PN5320 User Manual

This Page Intentionally Left Blank

90

Chapter 9

Maintenance and Download

Overview

The Maintenance function is used to upgrade the PN5212 / PN5320’s firmware, and to backup and restore the device’s configuration settings.

Download is used to download a stand-alone Java Client AP program to access the PN5212 / PN5320.

Maintenance

Firmware Upgrade

When you click the Maintenance tab, the display opens with the Firmware

Upgrade menu page, which looks similar to the one below:

91

PN5212 / PN5320 User Manual

The Main Panel

A description of the items shown in this panel are given in the table, below:

Item

Check Main

Firmware Version

Name

F/W Version

Filename

Upgrade

Description

If you enable Check Main Firmware Version, the PN5212 /

PN5320’s current firmware level is compared with that of the upgrade file. If the current version is equal to or higher than the upgrade version, a popup message appears, to inform you of the situation and stops the upgrade procedure.

Lists all of the PN5212 / PN5320 devices. Click to put a check in the checkbox of the device’s whose firmware you want to upgrade.

Displays the PN5212 / PN5320’s current firmware version.

As new versions of the firmware become available, they are posted on our website and can be downloaded to a convenient location on your computer. Click the Browse button to select the downloaded upgrade file.

Click this button to upgrade the firmware of the selected devices.

Upgrading the Firmware

To upgrade the firmware refer to the screenshot on the preceding page, and do the following:

1. Go to our website and download the new firmware file to a convenient location on your computer.

2. Click the Browse button; navigate to where the firmware file is located and select it.

3. Click Upgrade to start the upgrade procedure.

Š If you enabled Check Main Firmware Version the current firmware level is compared with that of the upgrade file. If the current version is equal to or higher than the upgrade version, a popup message appears, to inform you of the situation and stops the upgrade procedure.

Š If you didn't enable Check Main Firmware Version, the upgrade file is installed without checking what its level is.

Š Once the upgrade completes successfully, the switch resets itself.

4. Log in again, and check the firmware version to be sure it is the new one.

92

Chapter 9. Maintenance and Download

Firmware Upgrade Recovery

Should the PN5212 / PN5320’s firmware upgrade procedure fail, and the device becomes unusable, the following firmware upgrade recovery procedure will resolve the problem:

1. Power off the device.

2. Press and hold the Reset Switch in (see page 7).

3. While holding the Reset Switch in, power the switch back on.

This causes the switch to use the original factory installed main firmware version. Once the switch is operational, you can try upgrading the main firmware again.

Backup/Restore

Selecting Backup/Restore on the menu bar gives you the ability to back up the switch’s configuration and user profile information:

93

PN5212 / PN5320 User Manual

Backup

To backup the device’s settings do the following:

1. In the Password field, key in a password for the file.

Note: Entering a password is optional. If you do enter a password, make a note of it, since you will need it to be able to restore the file.

2. Click Save.

3. When the browser asks what you want to do with the file, select Save to

disk; then save it in a convenient location.

Restore

To restore a previous backup, do the following:

1. Click Browse; navigate to the file and select it.

Note: If you renamed the file, you can leave the new name. There is no need to return it to its original name.

2. In the Password field, key in the same password that you used to save the file.

Note: If you did not set a password when you created the backup file, you can omit this step.

3. Select as many of the options that are presented as you wish to restore.

4. Click Restore.

After the file is restored, a message appears to inform you that the procedure succeeded.

94

Chapter 9. Maintenance and Download

Download

Download is used to download a stand-alone Java Client AP version of the

PN5212 / PN5320 software. When you click the Download tab, the browser brings up a dialog box asking what you want to do with the program file:

The Java Client AP can be run via a console terminal connection from your computer’s COM port to the PN5212 / PN5320’s Console Port.

95

PN5212 / PN5320 User Manual

This Page Intentionally Left Blank

96

Chapter 10

The Log Server

The Windows-based Log Server is an administrative utility that records all the events that take place on selected Power Over the NET™ devices and writes them to a searchable database. This chapter describes how to install and configure the Log Server.

Installation

The Log Server AP Installer is provided on the CD that came with your Power

Over the NET

TM

device. To install the Log Server, do the following:

1. On the computer you want to use as the Log Server, put the CD into its CD

(DVD) drive.

2. Navigate to the Log Server AP Installer folder on the CD.

3. Click the Log Server icon to start the installation. A screen, similar to the one below, appears:

4. Click Next. Then follow the on-screen instructions to complete the installation and have the Log Server program icon placed on your desktop.

97

PN5212 / PN5320 User Manual

Starting Up

To start the Log Server, either double click the program icon, or key in the full path to the program on the command line. The first time your run it, a screen similar to the one below appears:

Note: 1. The MAC address of the Log Server computer must be specified

under the ANMS settings – see Log Server, page 68 for details.

2. The Log Server requires the Microsoft Jet OLEDB 4.0 driver.

See The Log Server program does not run., page 143 if the program

doesn’t start.

The screen is divided into three components:

Š A Menu Bar at the top

Š A panel that will contain a list of Power Over the NET™ units in the

middle (see The Log Server Main Screen, page 103).

Š A panel that will contain an Events List at the bottom

Each of the components is explained in the sections that follow.

98

Chapter 10. The Log Server

The Menu Bar

The Menu bar consists of four items:

Š Configure

Š Events

Š Options

Š Help

These are discussed in the sections that follow.

Note: If the Menu Bar appears to be disabled, click in the List window to enable it.

Configure

The Configure menu contains three items: Add; Edit; and Delete. They are used to add new units to the List; edit the information for units already on the list; or delete units from the list.

Š To add a unit to the list, click Add.

Š To edit or delete a listed unit, first select the target in the List window, then open this menu and click Edit or Delete.

When you choose Add or Edit, a dialog box, similar to the one below, appears:

99

PN5212 / PN5320 User Manual

A description of the fields is given in the table, below:

Field

Address

Port

Description

Limit

Explanation

This can either be the IP address of the unit or its DNS name

(if the network administrator has assigned it a DNS name).

The port number that was assigned to the Log Server

(see Log Server, page 68).

This field is provided so that you can put in a descriptive reference for the unit to help identify it.

This specifies the number of days that an event should be kept in the

Log Server's database. Events that exceed the amount of time

specified here can be removed with the Maintenance function (see

Maintenance:, page 101).

Fill in or modify the fields, then click OK to finish.

Events

The Events Menu has two items: Search and Maintenance.

Search:

Search allows you to search for events containing specific words or strings.

When you access this function, a screen, similar to the one below, appears:

100

Chapter 10. The Log Server

A description of the items is given in the table, below:

Item

New search

Search last results

Search excluding last results

This is a secondary search performed on the events that resulted from the previous search.

This is a secondary search performed on all the events in the database for the selected unit excluding the events that resulted from the previous search.

Server List

Priority

Start Date

Start Time

End Date

Power Over the NET™ units are listed according to their IP address. Select the unit that you want to perform the search on from this list. You can select more than one unit for the search.

If no units are selected, the search is performed on all of them.

Sets the level for how detailed the search results display should be. Least is the most general; Most is the most specific.

Least results appear in black; Less results appear in blue;

Most results appear in red.

Select the date that you want the search to start from. The format follows the YYYY/MM/DD convention, as follows:

2009/11/04

Select the time that you want the search to start from. The format follows the HH:MM:SS convention.

Select the date that you want the search to end at.

End Time

Pattern

Description

This is one of three radio buttons that define the scope of the search. If it is selected, the search is performed on all the events in the database for the selected unit.

Select the time that you want the search to end at.

Key in the pattern that you are searching for here. The multiple character wildcard (%) is supported. E.g., h%ds would match hands and hoods.

Results

Search

Print

Export

Exit

Lists the events that contained matches for the search.

Click this button to start the search.

Click this button to print the search results.

Click this button to save the search results to file.

Click this button to exit the Log Server.

Maintenance:

This function allows the administrator to perform manual maintenance of the database, such as erasing specified records before their expiration time is up.

101

PN5212 / PN5320 User Manual

Options

Network Retry allows you to set the number of seconds that the Log Server should wait before attempting to connect if its previous attempt to connect failed. When you click this item, a dialog box, similar to the one below, appears:

Key in the number of seconds, then click OK to finish.

Help

From the Help menu, click Contents to access the online Windows Help file.

The help file contains instructions about how to setup, operation and troubleshoot the Log Server.

102

Chapter 10. The Log Server

The Log Server Main Screen

Overview

The Log Server Main Screen is divided into two main panels.

Š The upper (List) panel lists all of the units that have been selected for the

Log Server to track (see Configure, page 99).

Š The lower (Event) panel displays the tick information for the currently selected unit. (If there are more than one unit, the selected unit is the one that is highlighted).

Š To select a unit in the list, simply click on it.

103

PN5212 / PN5320 User Manual

The List Panel

The List panel contains six fields:

Field

Recording

Address

Port

Connection

Days

Description

Explanation

Determines whether the Log Server records the ticks for this unit, or not. If the Recording checkbox is checked, the field displays Recording, and the ticks are recorded. If the

Recording checkbox is not checked, the field displays Paused, and the ticks are not recorded.

Note: Even though a unit is not the currently selected one, if its Recording checkbox is checked, the Log Server will still record its ticks.

This is the IP Address or DNS name that was given to the unit

when it was added to the Log Server (see Configure, page 99).

This is the Access Port number assigned to the unit (see

Configure, page 99).

Š

If the Log Server is connected to the unit, this field displays

Connected.

Š

If the Log Server is not connected, this field displays

Waiting. This means that the Log Server's MAC address

has not been set properly. It needs to be set on the Device

Management Date/Time page (see page 83).

This field displays the number of days that the unit's log events are to be kept in the Log Server's database before expiration

(see Configure, page 99).

This field displays the descriptive information given for the unit

when it was added to the Log Server (see Configure, page 99).

The Event Panel

The lower panel displays log events for the currently selected unit. Note that if the installation contains more than one unit, even though a unit isn’t currently selected, if its Recording checkbox is checked, the Log Server records its log events and keeps them in its database.

104

Chapter 11

Out of Band Operation

Overview

In case the LAN that the PN5212 / PN5320 resides on goes down, or the

PN5212 / PN5320 cannot be accessed with the usual browser based method for some other reason, the PN5212 / PN5320 can be accessed via an Out of Band method utilizing the PN5212 / PN5320's Console port in the following way:

Š For a console terminal session, connect the PN5212 / PN5320’s Console

port (see PON In / Console Port, page 8), to the COM port of a local

computer. You can then operate the PN5212 / PN5320 from the local computer's console terminal (HyperTerminal, GTKTerminal, etc.).

Console Terminal Session

This section describes how to establish a console terminal session using

HyperTerminal as an example, as follows:

1. Use Cat 5e cable to connect the PN5212 / PN5320’s PON IN/Console port to the SA0151 (DTE) adapter supplied with your package. Connect the adapter to the COM port of the computer you will use for the console terminal.

Cat 5e Cable

SA0151

(DTE)

2. On your local computer, run the HyperTerminal program:

3. When a dialog box, similar to the one below appears, key in a name to describe the connection in the Name field, select an icon to represent the connection; then click OK.

105

PN5212 / PN5320 User Manual

Note: In the examples we used Com1Test for the Name, and COM1 for the computer’s COM port. If you use a different COM port, change the settings accordingly.

The following dialog box comes up:

106

Chapter 11. Out of Band Operation

4. For the Connect using: field, select Direct to COM1 (assuming you are using COM1 on your computer), then click OK. A Port Setting dialog box similar to the one below comes up:

5. Fill in the settings so that the match the ones you specified for the PN5212

/ PN5320's console port settings on the OOBC page (see Console Port

Settings, page 76), then click OK.

6. When the HyperTerminal screen appears, open its File menu and select:

Properties

→ Settings. A dialog box, similar to the one below, displays:

107

PN5212 / PN5320 User Manual

7. Change your settings (if necessary), so that they match the settings shown in the diagram, then click ASCII Setup...

8. In the ASCII Setup dialog box that comes up, change the settings (if necessary), so that they match the settings shown in the diagram below, then click OK.

9. Close the HyperTerminal window. When Windows asks if you want to disconnect, click Yes. When Windows asks if you want to save the session, click Yes.

This completes the HyperTerminal setup. For Windows NT, 2000, XP and

Windows Server 2003 systems, a HyperTerminal icon that connects you to the

PN5212 / PN5320 is created on the desktop. For Windows 98 and ME, you must access HyperTerminal from the Windows Start Menu.

Logging In

1. Double click the HyperTerminal icon on your desktop.

2. In the VT100 terminal window, key in:

???

A login prompt appears.

3. Key in your Username and Password to bring up the PN5212 / PN5320's text-based configuration menu. The text-based configuration menu is

discussed on page 110.

108

Chapter 12

Remote Terminal Operation

Overview

The PN5212 / PN5320 can be accessed via a remote terminal session using several methods, including Telnet, SSH, or PuTTY, as described in the sections that follow.

Telnet

Logging In

To log in to the PN5212 / PN5320 by means of a Telnet session, do the following:

1. On your computer, open a terminal (command line) session.

2. At the prompt, key in the PN5212 / PN5320's IP Address in the following way: telnet [IP Address]

3. Press Enter.

The login screen appears:

4. At the login prompt, provide your Username and Password.

109

PN5212 / PN5320 User Manual

Once a Telnet connection to the device is established, the PN5212 /

PN5320’s text-based Configuration Menu comes up:

The text-based Configuration Menu provides text-based equivalents for the functions found under the web-based tabs and menus. You can reference the information provided for the browser version as you work your way through the submenus.

Note: As with the browser version, access to many of these submenus are restricted to the administrator or users with administration permission.

If you select a submenu that you are not authorized for, nothing will happen.

When you have finished with your session, bring up the Main Menu and press

X to log out. After you are offline, you can simply close the terminal (command line) window.

110

Chapter 12. Remote Terminal Operation

SSH

Terminal Session (Linux):

To log in to the PN5212 / PN5320 by means of a secure SSH session, do the following:

1. Open a terminal (command line) on your computer.

2. At the prompt, key in your PN5212 / PN5320 Username and the PN5212 /

PN5320's IP Address in the following way: ssh [username@IP Address]

3. Press Enter

4. When you are prompted for a password, use your PN5212 / PN5320 password.

Once an SSH connection to the device is established, the PN5212 /

PN5320’s text-based Configuration Menu comes up:

This menu is the same as the configuration menu that appears with Telnet

sessions (see page 110). It provides text-based equivalents for the functions

found under the web-based tabs and menus. You can reference the information provided for the browser version as you work your way through the submenus.

111

PN5212 / PN5320 User Manual

Third Party Utility (Windows):

SSH sessions can be implemented under Windows with the use of third party utility software, such as PuTTY, a free implementation of Telnet and SSH for the Win32 and Unix platforms. To make an SSH connection with PuTTY, do the following:

1. In the Host Name box, enter the Internet host name or IP Address of the server you want to connect to.

2. Select SSH from the Protocol buttons.

3. Click Open (at the bottom of the dialog box)

4. After you have connected, provide your PN5212 / PN5320 username and password at the login prompts.

Note: If you make a mistake keying in the username, the SSH protocol doesn't allow you to try again. You must close PuTTY and start over.

Once an SSH connection to the device is established, the PN5212 / PN5320’s text-based Configuration Menu comes up. This menu is the same as the

configuration menu that appears with Telnet sessions (see page 110).

112

Chapter 13

LDAP Server Configuration

Introduction

The PN5212 / PN5320 allows log in authentication and authorization through external programs. This chapter describes how to configure Active Directory for PN5212 / PN5320 authentication and authorization.

To allow authentication and authorization via LDAP or LDAPS, the Active

Directory’s LDAP Schema must be extended so that an extended attribute name for the PN5212 / PN5320 – PNxxxx-userProfile – is added as an optional attribute to the person class.

Note: Authentication refers to determining the authenticity of the person logging in; authorization refers to assigning permission to use the device’s various functions.

In order to configure the LDAP server, you will have to complete the following procedures: 1) Install the Windows Server Support Tools; 2) Install the Active

Directory Schema Snap-in; and 3) Extend and Update the Active Directory

Schema.

The following section provides an example of configuring LDAP under

Windows 2003 Server.

Install the Windows 2003 Support Tools

To install the Windows 2003 Support Tools, do the following:

1. On your Windows Server CD, open the Support

Tools folder.

2. In the right panel of the dialog box that comes up, double click

SupTools.msi.

3. Follow along with the Installation Wizard to complete the procedure.

113

PN5212 / PN5320 User Manual

Install the Active Directory Schema Snap-in

To install the Active Directory Schema Snap-in, do the following:

1. Open a Command Prompt.

2. Key in: regsvr32 schmmgmt.dll to register schmmgmt.dll on your

Active Directory computer.

3. Open the Start menu; click Run; key in: mmc /a; click OK.

4. On the File menu of the screen that appears, click Add/Remove Snap-in; then click Add.

5. Under Available Standalone Snap-ins, double click Active Directory

Schema; click Close; click OK.

6. On the screen you are in, open the File menu and click Save.

7. For Save in, specify the C:\Windows\system32 directory.

8. For File name, key in schmmgmt.msc.

9. Click Save to complete the procedure.

Create a Start Menu Shortcut Entry

To create a shortcut entry on the Start Menu for the Active Directory Schema, do the following:

1. Right click Start; select: Open all Users

Programs

Administrative

Tools.

2. On the File menu, select New

Shortcut

3. In the dialog box that comes up, browse to, or key in the path to schmmgmt.msc (C:\Windows\system32\schmmgmt.msc), then click Next.

4. In the dialog box that comes up, key in Active Directory Schema as the name for the shortcut, then click Finish.

114

Chapter 13. LDAP Server Configuration

Extend and Update the Active Directory Schema

To extend and update the Active Directory Schema, you must do the following

3 procedures: 1) create a new attribute; 2) extend the object class with the new attribute; and 3) edit the active directory users with the extended schema.

Creating a New Attribute

To create a new attribute do the following:

1. From the Start menu, open Administrative Tools

Active Directory

Schema.

2. In the left panel of the screen that comes up, right-click Attributes:

3. Select New

Attribute.

4. In the warning message that appears, click Continue to bring up the

Create New Attribute dialog box.

(Continues on next page.)

115

PN5212 / PN5320 User Manual

(Continued from previous page.)

5. Fill in the dialog box to match the entries for Description and Common

Name shown below, then click OK to complete the procedure.

Note: The Unique X500 Object ID uses periods, not commas.

116

Chapter 13. LDAP Server Configuration

Extending the Object Class With the New Attribute

To extend the object class with the new attribute, do the following:

1. Open the Control Panel

Administrative Tools

Active Directory

Schema.

2. In the left panel of the screen that comes up, select Classes.

3. In the right panel, right-click person:

4. Select Properties; the person Properties dialog box comes up with the

General page displayed. Click the Attributes tab.

117

PN5212 / PN5320 User Manual

5. On the Attributes page, click Add:

6. In the list that comes up, select PNxxxx-userProfile, then click OK to complete the procedure.

118

Chapter 13. LDAP Server Configuration

Editing Active Directory Users

To edit Active Directory Users With the Extended Schema, do the following:

1. Run ADSI Edit. (Installed as part of the Support Tools.)

2. In the left panel, open Domain, and navigate to the DC=aten,DC=com

CN=Users node.

3. In the right panel, locate the user you wish to edit. (Our example uses

jason.)

4. Right-click on the user’s name and select properties.

(Continues on next page.)

119

PN5212 / PN5320 User Manual

(Continued from previous page.)

5. On the Attribute Editor page of the dialog box that appears, select

PNxxxx-userProfile from the list.

6. Click Edit to bring up the String Attribute Editor:

(Continues on next page.)

120

Chapter 13. LDAP Server Configuration

(Continued from previous page.)

7. Key in the PN5212 / PN5320 permission attribute values. For example:

Note: Where user represents the Username of a PN5212 / PN5320 user whose permissions reflect the permissions you want Jason to have

(see Users, page 48).

8. Click OK. When you return to the Attribute Editor page, the

PNxxxx-userProfile entry now reflects the new permissions: a) Click Apply to save the change and complete the procedure. Jason now has the same permissions as user.

b) Repeat the Editing Active Directory Users procedure for any other users

you wish to add.

121

PN5212 / PN5320 User Manual

OpenLDAP

OpenLDAP is an Open source LDAP server designed for Unix platforms. A

Windows version can be downloaded from: http://download.bergmans.us/openldap/openldap-2.2.29/ openldap-2.2.29-db-4.3.29-openssl-0.9.8awin32_Setup.exe.

OpenLDAP Server Installation

After downloading the program, launch the installer, select your language, accept the license and choose the target installation directory. The default directory is: c:\Program Files\OpenLDAP.

When the Select Components dialog box appears, select install BDB-tools and

install OpenLDAP-slapd as NT service, as shown in the diagram, below:

122

Chapter 13. LDAP Server Configuration

OpenLDAP Server Configuration

The main OpenLDAP configuration file, slapd.conf, is found in the /OpenLdap directory. It has to be customized before launching the server. This section provides a quick summary of the modifications to the configuration file in order for it to be used with the PN5212 / PN5320, for a complete explanation of OpenLDAP, refer to the official OpenLDAP documentation.

The modifications to the configuration file will do the following:

Š Specify the Unicode data directory. The default is ./ucdata.

Š Choose the required LDAP schemas. The core schema is mandatory.

Š Configure the path for the OpenLDAP pid and args start up files. The first contains the server pid, the second includes command line arguments.

Š Choose the database type. The default is bdb (Berkeley DB).

Š Specify the server suffix. All entries in the directory will have this suffix, which represents the root of the directory tree. For example, with suffix

dc=aten,dc=com, the fully qualified name of all entries in the database will end with dc=aten,dc=com.

Š Define the name of the administrator entry for the server (rootdn), along with its password (rootpw). This is the server's super user. The rootdn name must match the suffix defined above. (Since all entry names must end with the defined suffix, and the rootdn is an entry.)

An example configuration file is provided in the figure, below:

123

PN5212 / PN5320 User Manual

Starting the OpenLDAP Server

To start the OpenLDAP Server, run slapd (the OpenLDAP Server executable file) from the command line. slapd supports a number of command line options, the most important option is the d switch that triggers debug information. For example, a command of: slapd -d 256 would start OpenLDAP with a debug level of 256, as shown in the following screenshot:

Note: For details about slapd options and their meanings, refer to the

OpenLDAP documentation.

124

Chapter 13. LDAP Server Configuration

Customizing the OpenLDAP Schema

The schema that slapd uses may be extended to support additional syntaxes, matching rules, attribute types, and object classes.

In the case of the PN5212 / PN5320, the User class and the permission attribute are extended to define a new schema. The extended schema file used to authenticate and authorize users logging in to the PN5212 / PN5320 is shown in the figure, below:

125

PN5212 / PN5320 User Manual

LDAP DIT Design and LDIF File

LDAP Data Structure

An LDAP Directory stores information in a tree structure known as the

Directory Information Tree (DIT). The nodes in the tree are directory entries, and each entry contains information in attribute-value form. An example of the

LDAP directory tree for the PN5212 / PN5320 is shown in the figure, below:

(Continues on next page.)

126

Chapter 13. LDAP Server Configuration

(Continued from previous page.)

DIT Creation

The LDAP Data Interchange Format (LDIF) is used to represent LDAP entries in a simple text format (please refer to RFC 2849). The figure below illustrates an LDIF file that creates the DIT for the KN4140 directory tree. The name of the file is init.ldif and you create it in the /OpenLDAP directory, as follows:

127

PN5212 / PN5320 User Manual

Using the New Schema

To use the new schema, do the following:

1. Save the new schema file (e.g., kn4140.schema) in the

/OpenLDAP/schema/ directory.

2. Add the new schema to the slapd.conf file (in the /OpenLDAP directory), as shown in the figure, below:

3. Restart the LDAP server.

4. Write the LDIF file and create the database entries in init.ldif with the

ldapadd command, as shown in the following example: ldapadd -f init.ldif -x -D "cn=ldapadmin,dc=aten,dc=com"

-w password

128

Appendix

Safety Instructions

General

Š Read all of these instructions. Save them for future reference.

Š Follow all warnings and instructions marked on the device.

Š Do not place the device on any unstable surface (cart, stand, table, etc.). If the device falls, serious damage will result.

Š Do not use the device near water.

Š Do not place the device near, or over, radiators or heat registers.

Š The device cabinet is provided with slots and openings to allow for adequate ventilation. To ensure reliable operation, and to protect against overheating, these openings must never be blocked or covered.

Š The device should never be placed on a soft surface (bed, sofa, rug, etc.) as this will block its ventilation openings. Likewise, the device should not be placed in a built in enclosure unless adequate ventilation has been provided.

Š Never spill liquid of any kind on the device.

Š Unplug the device from the wall outlet before cleaning. Do not use liquid or aerosol cleaners. Use a damp cloth for cleaning.

Š The device should be operated from the type of power source indicated on the marking label. If you are not sure of the type of power available, consult your dealer or local power company.

Š To prevent damage to your installation it is important that all devices are properly grounded.

Š The device is equipped with a 3-wire grounding type plug. This is a safety feature. If you are unable to insert the plug into the outlet, contact your electrician to replace your obsolete outlet. Do not attempt to defeat the purpose of the grounding-type plug. Always follow your local/national wiring codes.

Š The socket-outlet should be installed near the equipment and should be easily accessible.

Š Do not allow anything to rest on the power cord or cables. Route the power cord and cables so that they cannot be stepped on or tripped over.

129

PN5212 / PN5320 User Manual

Š To help protect your system from sudden, transient increases and decreases in electrical power, use a surge suppressor, line conditioner, or uninterruptible power supply (UPS).

Š Position system cables and power cables carefully; Be sure that nothing rests on any cables.

Š When connecting or disconnecting power to hot pluggable power supplies, observe the following guidelines:

Š Install the power supply before connecting the power cable to the power supply.

Š Unplug the power cable before removing the power supply.

Š If the system has multiple sources of power, disconnect power from the system by unplugging all power cables from the power supplies.

Š Never push objects of any kind into or through cabinet slots. They may touch dangerous voltage points or short out parts resulting in a risk of fire or electrical shock.

Š Do not attempt to service the device yourself. Refer all servicing to qualified service personnel.

Š If the following conditions occur, unplug the device from the wall outlet and bring it to qualified service personnel for repair.

Š The power cord or plug has become damaged or frayed.

Š Liquid has been spilled into the device.

Š The device has been exposed to rain or water.

Š The device has been dropped, or the cabinet has been damaged.

Š The device exhibits a distinct change in performance, indicating a need for service.

Š The device does not operate normally when the operating instructions are followed.

Š Only adjust those controls that are covered in the operating instructions.

Improper adjustment of other controls may result in damage that will require extensive work by a qualified technician to repair.

130

Appendix

Rack Mounting

Š Before working on the rack, make sure that the stabilizers are secured to the rack, extended to the floor, and that the full weight of the rack rests on the floor. Install front and side stabilizers on a single rack or front stabilizers for joined multiple racks before working on the rack.

Š Always load the rack from the bottom up, and load the heaviest item in the rack first.

Š Make sure that the rack is level and stable before extending a device from the rack.

Š Use caution when pressing the device rail release latches and sliding a device into or out of a rack; the slide rails can pinch your fingers.

Š After a device is inserted into the rack, carefully extend the rail into a locking position, and then slide the device into the rack.

Š Do not overload the AC supply branch circuit that provides power to the rack. The total rack load should not exceed 80 percent of the branch circuit rating.

Š Make sure that all equipment used on the rack – including power strips and other electrical connectors – is properly grounded.

Š Ensure that proper airflow is provided to devices in the rack.

Š Ensure that the operating ambient temperature of the rack environment does not exceed the maximum ambient temperature specified for the equipment by the manufacturer

Š Do not step on or stand on any device when servicing other devices in a rack.

131

PN5212 / PN5320 User Manual

Technical Support

International

Š For online technical support – including troubleshooting, documentation, and software updates: http://support.aten.com

Š For telephone support, see Telephone Support, page iii

North America

Email Support

Online

Technical

Support

Troubleshooting

Documentation

Software Updates

Telephone Support [email protected]

http://www.aten-usa.com/support

1-888-999-ATEN ext 4988

When you contact us, please have the following information ready beforehand:

Š Product model number, serial number, and date of purchase.

Š Your computer configuration, including operating system, revision level, expansion cards, and software.

Š Any error messages displayed at the time the error occurred.

Š The sequence of operations that led up to the error.

Š Any other information you feel may be of help.

132

Appendix

IP Address Determination

If you are an administrator logging in for the first time, you need to access the

PN5212 / PN5320 in order to give it an IP address that users can connect to.

There are two methods to choose from. In each case, your client computer must be on the same network segment as the PN5212 / PN5320. After you have connected and logged in you can give the device its fixed network address.

(See Network, page 63.)

Method 1:

For computers running Windows, an IP address can be determined and/or assigned with the IP Installer utility. The utility can be obtained from the

Download area of our web site. Look under Driver/SW, and the model of your device. After downloading the utility to your computer, do the following:

1. Unzip the contents of IPInstaller.zip to a directory on your hard drive.

2. Go to the directory that you unzipped the IPInstaller program to and run

IPInstaller.exe. A dialog box similar to the one below appears:

3. Select the device in the Device List.

Note: 1. If the list is empty, or your device doesn't appear, click

Enumerate to refresh the Device List.

2. If there is more than one device in the list, use the MAC address to pick the one you want. The PN5212 / PN5320's MAC address is located on its bottom panel.

133

PN5212 / PN5320 User Manual

4. Select either Obtain an IP address automatically (DHCP), or Specify an

IP address. If you chose the latter, fill the IP Address, Subnet Mask, and

Gateway fields with the information appropriate to your network.

5. Click Set IP.

6. After the IP address shows up in the Device List, click Exit to end the program.

Method 2:

1. Set your computer's IP address to 192.168.0.XXX

Where XXX represents any number or numbers except 60. (192.168.0.60) is the default address of the PN5212 / PN5320.)

2. Specify the device’s default IP address (192.168.0.60) in your browser, and you will be able to connect.

3. Assign a fixed IP address for the device (see Network, page 63), that is

suitable for the network segment that it resides on.

4. After you log out, reset your computer's IP address to its original value.

5. Once you have logged in, go to Network Settings to set up the permanent

IP environment (see page 63).

134

Appendix

Trusted Certificates

Overview

When you try to log in to the device from your browser, a Security Alert message appears to inform you that the device’s certificate is not trusted, and asks if you want to proceed.

The certificate can be trusted, but the alert is triggered because the certificate’s name is not found on Microsoft list of Trusted Authorities. You have two options: 1) you can ignore the warning and click Yes to go on; or 2) you can install the certificate and have it be recognized as trusted.

Š If you are working on a computer at another location, accept the certificate for just this session by clicking Yes.

Š If you are working at your own computer, install the certificate on your computer (see below for details). After the certificate is installed, it will be recognized as trusted.

Note: The security alert message will appear even after installing the certificate, but now the icon related to the first paragraph will be a check mark (indicating no alert) instead of the exclamation mark icon.

135

PN5212 / PN5320 User Manual

Installing the Certificate

To install the certificate, do the following:

1. In the Security Alert dialog box, click View Certificate. The Certificate

Information dialog box appears:

Note: There is a red and white X logo over the certificate to indicate that it is not trusted.

2. Click Install Certificate.

3. Follow the Installation Wizard to complete the installation. Unless you have a specific reason to choose otherwise, accept the default options.

4. When the Wizard presents a caution screen:

136

Click Yes.

Appendix

5. Next, click Finish to complete the installation; then click OK to close the dialog box.

Certificate Trusted

The certificate is now trusted:

When you click View Certificate, you can see that the red and white X logo is no longer present – further indication that the certificate is trusted:

137

PN5212 / PN5320 User Manual

Mismatch Considerations

If the site name or IP address used for generating the certificate no longer matches the current address of the switch a mismatch warning occurs:

You can click Yes to go on, or you can disable mismatch checking.

To disable mismatch checking, do the following:

1. After the page you are logging in to comes up open the browser’s Tools menu; Select Internet Options

Advanced.

2. Scroll to the bottom of the list and uncheck Warn about trusted

certificates:

3. Click OK. The next time you run the browser the change will be in effect.

138

Appendix

Self-Signed Private Certificates

If you wish to create your own self-signed encryption key and certificate, a free utility – openssl.exe – is available for download over the web at

www.openssl.org. To create your private key and certificate do the following:

1. Go to the directory where you downloaded and extracted openssl.exe to.

2. Run openssl.exe with the following parameters: openssl req -new -newkey rsa:1024 -days 3653 -nodes -x509

-keyout CA.key -out CA.cer -config openssl.cnf

Note: 1. The command should be entered all on one line (i.e., do not press

[Enter] until all the parameters have been keyed in).

2. If there are spaces in the input, surround the entry in quotes (e.g.,

“ATEN International”).

To avoid having to input information during key generation the following additional parameters can be used:

/C /ST /L /O /OU /CN /emailAddress.

Examples

openssl req -new -newkey rsa:1024 -days 3653 -nodes -x509

-keyout CA.key -out CA.cer -config openssl.cnf -subj

/C=yourcountry/ST=yourstateorprovince/L=yourlocationor city/O=yourorganiztion/OU=yourorganizationalunit/

CN=yourcommonname/[email protected]

openssl req -new -newkey rsa:1024 -days 3653 -nodes -x509

-keyout CA.key -out CA.cer -config openssl.cnf -subj

/C=CA/ST=BC/L=Richmond/O="ATEN International"/OU=ATEN

/CN=ATEN/[email protected]

Importing the Files

After the openssl.exe program completes, two files – CA.key (the private key) and CA.cer (the self-signed SSL certificate) – are created in the directory that you ran the program from. These are the files that you upload in the Private

Certificate panel of the Security page (see page 81).

139

PN5212 / PN5320 User Manual

Troubleshooting

Overview

Operation problems can be due to a variety of causes. The first step in solving them is to make sure that all cables are securely attached and seated completely in their sockets.

In addition, updating the product’s firmware may solve problems that have been discovered and resolved since the prior version was released. If your product is not running the latest firmware version, we strongly recommend that

you upgrade. See Firmware Upgrade, page 91, for upgrade details.

Problem 1:

On a safe shutdown and reboot operation, when rebooting, the computer stops at the logon screen and waits for a Username and Password instead of automatically logging on.

Solution:

The Autologon function hasn't been configured. Set it up as follows:

1. For Win NT, run regedit.exe; for Win 2000 or XP, run regedt32

2. Select the following:

HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows

NT\Current Version\Winlogon

3. Under the Edit menu, select Add Value.

4. Add the variables and values as shown in the table below:

Name

DefaultDomainName

DefaultUserName

DefaultPassword

AutoAdminLogon

Value

[domain name for this computer]

[user name for this computer]

[user password for this computer]

1

Note: Remove the brackets and replace the text inside the brackets with suitable values for yourself on this computer.

5. Close the Registry Editor.

Note: Make sure you have a real password (not blank) configured for logging on to your system.

140

Appendix

Problem 2:

The computer has an older mainboard that doesn't support APM in the BIOS.

What can I do to get Safe Shutdown and Reboot working?

Solution:

If you are running Windows 2000, XP, or Server 2003, you can do the following:

1. Open Control Panel

→ Power Options.

2. Open Properties

→ APM.

3. Enable Advanced Power Management support.

Problem 3:

I have enabled Synchronize with NTP Server in the Date / Time dialog box, but

I am unable to obtain the date and time from an NTP server on the internet.

Solution:

Contact your MIS department and have them enable a port for the NTP server.

141

PN5212 / PN5320 User Manual

Problem 4:

Although my computers have been configured for a Safe Shutdown, some of them don't shut down.

Solution:

This may be due to the applications running on them putting up a dialog box asking if you want to save the information running on them before they close.

Since you haven't provided an answer, the shutdown procedure doesn't continue to completion.

You can either change their shutdown behavior to Kill the Power - which is not a Safe Shutdown option, or use a product such as KVM over the NET™ to access them remotely and answer the dialog box questions.

Problem 5:

When I log in, the browser generates a CA Root certificate is not trusted, or a

Certificate Error response.

Solution:

The certificate’s name is not found on Microsoft’s list of Trusted Authorities.

The certificate can be trusted, however. See Trusted Certificates, page 135, for

details.

Problem 6:

System after AC Back doesn’t work.

Solution:

Make sure System after AC Back is set to On (not Last State) in your computer’s BIOS.

Problem 7:

After I rack mount my PN5212 / PN5320, the cables often come unplugged from the back of the unit.

Solution:

The connectors used on this device all conform to industry standard specifications. Nevertheless, if this problem occurs, we recommend using cable ties and cable bars to safely and securely route the cables. Contact your rack dealer for the cable routing hardware appropriate for your rack.

142

Appendix

Problem 8:

The Log Server program does not run.

Solution:

The Log Server requires the Microsoft Jet OLEDB 4.0 driver in order to access the database.

This driver is automatically installed with Windows ME, 2000, and XP.

For Windows 98 and NT you will have to go to the Microsoft download site: http://www.microsoft.com/data/download.htm

to retrieve the driver file:

MDAC 2.7 RTM Refresh (2.70.9001.0)

Since this driver is used in Windows Office Suite, an alternate method of obtaining it is to install Windows Office Suite. Once the driver file or Suite has been installed, the Log Server will run.

143

PN5212 / PN5320 User Manual

Administrator Login Failure

If you are unable to perform an Administrator login (because the Username and

Password information has become corrupted, or you have forgotten it, for example), you can clear the login information with the following procedure:

1. Power off the PN5212 / PN5320 and remove its housing.

2. Short the jumper labeled J5.

3. Power on the switch.

4. When the Link and 10/100Mbps LEDs flash, power off the switch.

5. Remove the jumper cap from J6.

6. Close the housing and start the PN5212 / PN5320 back up.

After you start back up, you can use the default Username and Password

(see First Time Setup, page 17) to log in.

144

Appendix

Specifications

Power

Outlets

Connectors

Function

Direct

Max

Power

Inlets

Power

Outlets

NEMA

IEC

NEMA

IEC

LEDs

PON In / Console

PON Out

LAN

ID

Station

Readout

Current

Voltage

Power

I/P Rating (Total Input)

Load Capacity

O/P Rating

Physical

Properties

NEMA (UL)

NEMA (PSE)

IEC

NEMA (UL)

NEMA (PSE)

IEC

Per Port NEMA (UL)

NEMA (PSE)

IEC

Total NEMA (UL)

NEMA (PSE)

IEC

NEMA (UL / PSE) Power Consumption

IEC

Environment Operating Temperature

Storage Temperature

Humidity

Housing

Weight

Dimensions (L x W x H)

PN5212

12

192 (via Daisy Chain)

1 x NEMA L5-20P

1 x IEC 60309

12 x NEMA 5-15R

PN5320

20

320 (via Daisy Chain)

1 x NEMA L5-30P

1 x IEC 60309

3 x NEMA 5-20R

17 x NEMA 5-15R

12 x IEC320 C13 3 x IEC320 C19

17 x IEC320 C13

1 x RJ-45 (F)

1 x RJ-45 (F)

1 x RJ-45 (F)

1 x 2-digit 7-segment

1 x Green

1 x 3-digit 7-segment

1 x Green

1 x Green

1 x Green

100-120V; 50/60Hz; 16A 100-120V; 50/60Hz; 24A

100-120V; 50/60Hz; 16A 100-120V; 50/60Hz; 24A

200-240V; 50/60Hz; 16A 200-240V; 50/60Hz; 32A

120V; 50/60Hz; 1920W 120V; 50/60Hz; 2880W

120V; 50/60Hz; 1920W 120V; 50/60Hz; 2880W

230V; 50/60Hz; 3680W 230V; 50/60Hz; 7360W

100-120V; 50/60Hz; 12A 100-120V; 50/60Hz;

16A (x3) / 12A (x17)

100-120V; 50/60Hz; 12A 100-120V; 50/60Hz;

16A (x3) / 12A (x17)

200-240V; 50/60Hz; 10A 200-240V; 50/60Hz;

16A (x3) / 10A (x17)

100-120V; 50/60Hz; 15A 100-120V; 50/60Hz; 23A

100-120V; 50/60Hz; 15A 100-120V; 50/60Hz; 23A

200-240V; 50/60Hz; 15A 200-240V; 50/60Hz; 31A

120V; 50/60Hz; 16W 120V; 50/60Hz; 22W

230V; 50/60Hz; 18W 230V; 50/60Hz; 26W

0–50 o

C

-20–60 o

C

0 ~ 80% RH Non-condensing

Metal

4.49 kg

6.42 x 5.46 x 134 cm

5.68 kg

6.42 x 5.46 x 167.64 cm

145

PN5212 / PN5320 User Manual

Limited Warranty

ATEN warrants this product against defects in material or workmanship for a period of one (1) year from the date of purchase. If this product proves to be defective, contact ATEN's support department for repair or replacement of your unit. ATEN will not issue a refund. Return requests can not be processed without the original proof of purchase.

When returning the product, you must ship the product in its original packaging or packaging that gives an equal degree of protection. Include your proof of purchase in the packaging and the RMA number clearly marked on the outside of the package.

This warranty becomes invalid if the factory-supplied serial number has been removed or altered on the product.

This warranty does not cover cosmetic damage or damage due to acts of God, accident, misuse, abuse, negligence or modification of any part of the product. This warranty does not cover damage due to improper operation or maintenance, connection to improper equipment, or attempted repair by anyone other than ATEN. This warranty does not cover products sold AS IS or WITH FAULTS.

IN NO EVENT SHALL ATEN'S LIABILITY EXCEED THE PRICE PAID FOR THE

PRODUCT. FURTHER, ATEN SHALL NOT BE RESPONSIBLE FOR DIRECT, INDIRECT,

SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE USE

OF THE PRODUCT, ITS ACCOMPANYING SOFTWARE, OR ITS DOCUMENTATION.

ATEN SHALL NOT IN ANY WAY BE RESPONSIBLE FOR, WITHOUT LIMITATION, LOSS

OF DATA, LOSS OF PROFITS, DOWNTIME, GOODWILL, DAMAGE OR REPLACEMENT

OF EQUIPMENT OR PROPERTY, AND ANY EXPENSES FROM RECOVERY,

PROGRAMMING, AND REPRODUCTION OF ANY PROGRAM OR DATA.

ATEN makes no warranty or representation, expressed, implied, or statutory with respect to its products, contents or use of this documentation and all accompanying software, and specifically disclaims its quality, performance, merchantability, or fitness for any particular purpose.

ATEN reserves the right to revise or update its product, software or documentation without obligation to notify any individual or entity of such revisions, or update.

For details about extended warranties, please contact one of our dedicated value added resellers.

146

A

Access

Outlet Level, 36

Station Level, 35

Access Ports, 63

Adding Users, 48

Administrator Login Failure, 144

ANMS, 67

B

Backup, 94

Browser login, 21

C

Configuration, 37

Outlet Level, 41

Station Level, 37

Console Terminal Session, 105

Corrupt Password, 144

Creating Groups, 52

Customization, 82

D

Daisy Chaining, 13

Date/Time, 83

Date/Time Settings, 83

Deleting groups, 54

Deleting user accounts, 51

Device Assignment, 59

Device Information, 61

Device Management, 61

Network, 63

Device Permissions

assigning, 59, 60

Download, 95

Index

E

End Session, 35

Event Panel, 104

F

Features, 2

Filtering

IP, 78

MAC, 78

Firmware Upgrade, 91

Firmware upgrade recovery, 93

Forgotten Password, 144

G

Groups, 30, 31

assigning users, 55, 57

creating, 52

Deleting, 54

Managing, 52

Modifying, 54

removing users, 56, 58

H

Hardware Setup, 9

HyperTerminal, 105

I

Installation

Daisy Chaining, 13

Single stage, 11

IP address determination, 133

IP Filtering, 78

IP Installer, 64

IPv4 Configuration, 65

IPv6 Configuration, 66

147

PN5212 / PN5320 User Manual

L

LDAP Server Configuration, 113

List Panel, 104

Log, 85

Log Event List, 86

Notification Settings, 89

Save, 88

Search, 87

System Log, 85

Log Server

Configure, 99

Event Panel, 104

Events, 100

Installation, 97

List Panel, 104

Main Screen, 103

Menu Bar, 99

Options, 102

Starting Up, 98

Log server, 97

Logging in

Browser, 21

Login Failures, 82

Login String, 78

M

MAC Filtering, 78

Main Page, 22

Managing Groups, 52

Managing Users, 48

Manual Power Management, 27

Modifying groups, 54

Modifying user accounts, 51

Mounting, 9

N

Network, 63

Network Configuration, 18

Network Time, 84

148

O

Online Registration, iii

OOB

Console Terminal Session, 105

OOBC, 76

OpenLDAP

Server Configuration, 123

Server Installation, 122

Operation, 21

Out of Band, 76

Out Of Band Operation, 105, 109

Outlet groups, 30, 31, 39

Outlets, 29

P

Port Selection

Sidebar, 26

Power management

manual, 27

scheduled, 44

Private Certificate, 81

Private Certificates, 139

PuTTY, 112

R

Rack Mounting, 9

Remote Terminal Operation, 109

Requirements, 4

Restore, 94

RoHS, ii

S

Safety Instructions

General, 129

Rack Mounting, 131

Schedule, 44

Scheduled Power Management, 44

Security, 77

Login string, 78

Self-signed certificates, 139

Sessions, 35

Settings

Web refresh rate, 64

Setup

network configuration, 18

Sidebar, 26

Single stage installation, 11

SJ/T 11364-2006, ii

Specifications, 145

SSH

terminal session (Linux), 111

third party utility (Windows), 112

System after AC Back, 142

System Log, 85

T

Technical Support, 132

Telephone support, iii

Telnet, 109

Time settings, 83

Troubleshooting, 140

Trusted Certificates, 135

U

User interface

Page components, 23

User Management, 47

User Notice, iii

Users

Adding, 48

assigning to groups, 55, 57

Deleting, 51

Managing, 48

Modifying, 51

removing from groups, 56, 58

Users and Groups, 55

W

Web refresh rate, 64

Working Mode, 82

.

149