VUT 2000 PW EC

VUT 3000 PW EC

USER’S MANUAL

Heat recovery air handling unit

2

CONTENTS

Safety requirements

Introduction

Purpose

Delivery set

Designation key

Technical data

Unit design and operating logic

Mounting and set-up

Connection to power mains

Functional diagram

Technical maintenance

Fault handling

Storage and transportation rules

Manufacturer's warranty

Acceptance certificate

Seller information

Mounting certificate

Warranty card

www.ventilation-system.com

17

18

19

19

14

15

17

19

20

8

9

5

6

13

3

5

5

5

3

SAFETY REQUIREMENTS

• Read the user’s manual carefully prior to the operation and installation of the heat recovery air handling unit.

• Fulfil the user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical and technical norms and standards.

• The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.

• Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.

• After a careful reading of the manual, keep it for the entire service life of the unit.

• While transferring the unit control the User’s manual must be turned over to the receiving operator.

Symbol legend:

WARNING!

DO NOT!

UNIT MOUNTING SAFETY PRECAUTIONS

Disconnect the unit from power mains prior to any installation or repair operations.

The unit must be grounded!

The unit must not be operated outside the temperature range stated in the user's manual and in aggressive or explosive environments.

Do not use damaged equipment or cables when connecting the unit to power mains.

While installing the unit follow the safety regulations specific to the use of electric tools.

Do not change the power cable length at your own discretion.

Do not bend the power cord.

Avoid damaging the power cord.

Unpack the unit with care.

Do not position any heating devices or other equipment in close proximity to the unit power cable.

4

www.ventilation-system.com

UNIT OPERATION SAFETY PRECAUTIONS

Do not touch the unit controls with wet hands.

Do not carry out the unit maintenance with wet hands.

Do not wash the unit with water.

Protect the unit electric parts from water ingress.

Use the unit only as intended by the manufacturer.

Do not connect a clothes dryer or other similar equipment to the unit or the ventilation system.

Do not put any water containers on the unit, i.e. flower vases.

Do not sit on the unit and avoid placing foreign objects on it.

ON

OFF

Disconnect the unit from power mains prior to maintenance.

Do not let children operate the unit.

Do not damage the power cable while operating the unit.

Do not put foreign objects on the power cable.

Keep combustible gases and inflammable products away of the unit.

When the unit generates unusual sounds, odour or emits smoke disconnect it from power supply and contact the Seller.

Do not open the operating unit.

In case of continuous operation of the unit periodically check the security of mounting.

Do not block the air duct when the unit is on.

Do not let air flow from the unit be directed to the open flame devices or candles.

5

INTRODUCTION

The user’s manual consisting of the technical details, operating instructions and technical specification applies to the installation and mounting of the heat recovery air handling unit VENTS VUT 2000-3000 PW EC, hereinafter referred to as «the unit».

PURPOSE

The unit with a heat exchanger and a water heater is designed to save heat energy by means of heat recovery and is one of the energy saving components used in the buildings and premises. The unit is a component part and is not designed for independent operation.

The unit is designed to provide permanent controlled air exchange by means of mechanical ventilation in houses, offices, hotels, cafés, meeting halls and other mechanically ventilated premises as well as utilization of extract air heat energy to warm up supply purified air.

The unit is designed for suspended mounting.

The unit is rated for continuous operation.

Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

THE UNIT MAY NOT bE OPERATED bY CHILDREN OR PERSONS WITH REDUCED PHYSICAL, MENTAL

OR SENSORY CAPACITIES, OR LACkING THE APPROPRIATE TRAINING.

THE UNIT MUST bE INSTALLED AND CONNECTED ONLY bY PROPERLY QUALIFIED PERSONNEL

AFTER THE APPROPRIATE bRIEFING.

THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIzED ACCESS bY

UNATTENDED CHILDREN.

Unit

User's manual

Control panel

Packing box

Name

DELIVERY SET

Number

1 item

1 item

1 item

1 item

DESIGNATION kEY

VUT ХХХ PB ЕС - Х - X

Control panel

__ — PU SENS 01 with a sensor display

А7 — PU JK 01 with an LCD display

Modification

L - left-handed modification

R - right-handed modification

Motor type

EC - electronically commutated motors

Heater type

W - water heater

Mounting method

P — suspended mounting

Air capacity [m3/h]

Unit type

VUT - ventilation with heat recovery

www.ventilation-system.com

6

TECHNICAL DATA

The unit is designed for indoor application with the ambient temperature ranging from +1°C up to +40°C and relative humidity up to 80%.

Hazardous parts access and water ingress protection rating:

IP 44 for the unit motors;

IP 22 for the assembled unit connected to the air ducts.

The unit design is constantly being improved, so some models can slightly differ from those ones described in this manual.

OVERALL DIMENSIONS OF THE UNIT, MM

Model VUT 2000 PW EC VUT 3000 PW EC

Ø D

B

B2

B3

B4

H

H1

H2

L

L1

314

950

405

225

500

761

367

501

1400

1453

399

1265

563

347

570

881

427

300

1835

1888

Model

Unit voltage [V /50-60 Hz]

Max. fan power [W]

Max. fan current [A]

Number of water heating coils

Total unit power [kW]

Total unit current [A]

Max. air capacity [m

3

/h]

RPM

Sound pressure level at 3 m distance [dB(A)]

Max. transported air temperature [°C]

Casing material

Insulation

Filter:

Extract filter

Supply filter

Connected air duct diameter [mm]

Weight [kg]

Heat recovery efficiency, %

Heat exchanger type

Heat exchanger material

UNIT TECHNICAL DATA

VUT 2000 PW EC

1 ~ 230

2 items х 420

2 items х 2,5

2

0,84

5,0

1950

2920

58 from -25 up to +40

Ø315

194

VUT 3000 PW EC

3 ~ 400

2 items х 990

2 items х 1,7

2

1,99

3,4

3800

2580

59 from -25 up to +50

Aluzinc

25 mm mineral wool

G4

G4 up to 75

Cross flow

Aluminium

Ø400

295

7

PERFORMANCE CHARTS FOR THE WATER HEATER PARAMETERS OF THE UNIT

In order to attain maximum power the water heater should be counterflow connected. In case of the direct-flow connection the water heater has lower power but higher frost-resistant properties.

How to use water heater diagrams

System Parameters: Air flow = 1450 m

3

/h. Outside air temperature =-25 °C. Water temperature (in/out) = 70/50 °C.

Air Speed. Starting from 1450 m 3 /h on the air flow scale draw a vertical line till the air speed axis which makes about 3.2 m/s.

Supply air temperature. prolong the line up to the point where it crosses the outside air temperature ( blue curve, e.g. -25 °C); then draw a horizontal line f r o m t h i s p o i n t t o t h e t it ll c r o s s i n g water in/out temperature curve (e.g. 70/50 °C). From this point draw a vertical line to the supply air temperature axis on top of the graphic (+28 °C).

Heating coil capacity. Prolong the line up to the point where it crosses the outside air temperature (e.g. -25 °C, red curve ) and draw a horizontal line from this point to the right until it crosses water in/out temperature curve (e.g., 70/50 °C), from here draw a vertical line up to the scale representing the heating coil capacity (31.0 kW).

l e f

Water flow. Prolong the line down to water flow axis at the bottom of the graphic (0.38 l/s).

Water pressure drop. Draw the line from the point where the line crosses the black curve to the pressure drop axis. (9.8 kPa).

How to use water heater diagrams

System Parameters: Air flow = 3500 m

3

/h. Outside air temperature =-10°C. Water temperature (in/out) = 90/70 °C.

Air Speed. Starting from 3500 m

3

/h on the air flow scale draw a vertical line till the air speed axis which makes about 4.65 m/s.

Supply air temperature. prolong the line up to the point where it crosses the outside air temperature ( blue curve, e.g. -10 °C); then draw a horizontal line from this point to the left till crossing water in/out temperature curve (e.g. 90/70 °C). From this point draw a vertical line to the supply air temperature axis on top of the graphic (+22,5 °C).

Heating coil capacity. Prolong the line up to the point where it crosses the outside air temperature (e.g. -10 °C, red curve ) and draw a horizontal line from this point to the right until it crosses water in/out temperature curve (e.g., 90/70 °C), from here draw a vertical line up to the scale representing the heating coil capacity (42.0 kW).

Water flow. Prolong the line down to water flow axis at the bottom of the graphic (0.5 l/s).

Water pressure drop. Draw the line from the point where the line crosses the black curve to the pressure drop axis. (6.5 kPa).

www.ventilation-system.com

8

UNIT DESIGN AND OPERATING LOGIC

The unit has the following operating logic:

Warm stale extract air from the room flows to the unit, where it is filtered, then air flows through the heat exchanger and is exhausted outside by the extract fan. Clean cold air from outside is moved to the supply filter. Then filtered air flows through the heat exchanger and is moved to the room with the supply fan.

Heat energy of warm extract air is transferred to clean intake fresh air from outside and warms it up. Heat recovery minimizes thermal energy losses and space heating expenses in cold seasons.

The unit is equipped with a detachable service panel for repair and maintenance operations and a cover enabling access to the control system components.

UNIT OPERATING LOGIC (TOP VIEW) bASED ON VUT 2000 PW EC UNIT ExAMPLE

Bypass damper electric actuator

Heat exchanger

Supply filter

INTAKE AIR

Drain pan

Condensate drain pipe

Extract fan

EXHAUST AIR

EXTRACT AIR SUPPLY AIR

Control unit

Extract filter

Bypass

Supply fan

Water heater

Condensate drain pipe

The basic unit delivery set includes a control panel for connection to the control system inside the unit casing using a data cable.

The unit is equipped with a supply and an extract centrifugal single-inlet fans with backward curved blades; maintenance-free EC motors with an external rotor and a built-in overheating protection; a plate counterflow heat exchanger and a water heater.

The supply G4 filter cleans supply air flow and prevents contamination of the unit parts. The extract G4 filter prevents contamination of the unit components.

Some condensate may form during heat recovery. The condensate is collected in the drain pan and is removed from the unit through the drain pipes.

The unit is equipped with a heat exchanger freeze protection. If the air temperature in the intake air duct is below +3°C, the bypass damper opens and automatically controls the air temperature.

9

MOUNTING AND SET-UP

MINIMUM DISTANCE FOR ACCESSING THE UNIT

While mounting the unit provide enough space for its maintenance or repair work.

min 20 mm

А — minimum distance for condensate disposal arrangement. The distance is selected depending on the installation conditions at the discretion of the installer.

b — minimum distance for water heater connection and condensate disposal arrangement. The distance is selected depending on the installation conditions at the discretion of the installer.

С — minimum distance from the service panel to the floor.

VUT 2000 PW EC VUT 3000 PW EC

1000 mm 1300 mm

min C

B

A

UNIT MOUNTING

The unit must be suspended to the ceiling on the threaded rod that is fixed inside a dowel.

Example

Nut

Washer

Vibration damping rubber

Nut and lock-nut

To attain the best performance of the unit and to minimise turbulence-induced air pressure losses connect a straight air duct section on both sides of the unit while mounting.

Minimum straight air duct length:

• equal to 1 air duct diameter on intake side.

• equal to 3 air duct diameters on outlet side.

If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects, e.g. by covering the spigots with a protecting grille or other protecting device with mesh width not more than 12.5 mm to prevent uncontrollable access to the fans.

www.ventilation-system.com

10

Safety precautions:

The unit must be mounted to a rigid and stable structure.

The unit must be suspended using threaded rods. Before starting mounting check that the mounting structure has sufficient loading capacity for the unit weight. Otherwise reinforce the mounting location with beams or similar elements.

If the threaded rods used for the unit mounting are too short, the unit can generate abnormal noise resulting from resonance with the ceiling.

Use threaded rods of sufficient length to prevent resonance.

If the abnormal noise is generated at the spiral air duct joint replace the spiral air duct with a flexible one to prevent resonance. Flexible antivibration connectors are another alternative for dealing with resonance.

WATER HEATER CONNECTION

Mixing unit diagram (not included in the delivery set) of the water heater is shown in the following figure.

Direct flow connection Counterflow connection

water inlet Water outlet

1

2

2

3

Water outlet

4

MIxING UNIT DIAGRAM

5 water inlet

6

M

7 9 8

HEAT MEDIUM REGULATING VALVE ACTUATOR

1. Water heater.

2. Shutoff valves.

3. Circulation pump.

4. Bypass damper.

5. Boiler.

6. Heat medium regulating valve with an electric actuator.

7. Non-return valve.

8. Coarse filter.

9. Water pressure sensor (nc).

WARNING!

The unit operates either in Winter or Summer mode. If the outside air temperature is below +10 °C the Winter mode is activated. If the outside temperature accedes +10 °C the unit operates in Summer mode.

In Summer mode the unit operates regardless of the return heat medium temperature in the mixing unit.

In Winter mode the unit has following temperature limits:

• The unit may not be started when the return heat medium temperature is below +40 °C. If the return heat medium temperature is +40 °C and higher the unit will be turned on with a 90 seconds delay.

• The unit turns off when the return heat medium temperature falls below +20 °C.

11

CONDENSATE DRAINAGE ARRANGEMENT

The drain pan is equipped with two drain pipes for condensate removal outside the unit.

Connect the drain pipe, the U-trap (not included in the standard delivery set) and the sewage system with metal, plastic or rubber pipes.

While laying the hoses provide the slope downwards min. 3%. Fill the system with water prior to connecting it to power supply! During operation the U-trap must always be filled with water. Provide free drainage for the condensed water, otherwise it is accumulated inside the unit that may cause the equipment damage and condensate outflow to the room.

The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C! If the expected ambient air temperatures are below 0 °C the condensate drainage system must be equipped with heat insulation and pre-heating facilities.

DO NOT CONNECT SEVERAL DRAIN PIPES FROM SEVERAL AIR HANDLING UNITS TO ONE U-TRAP!

DIRECT CONDENSATE DRAINAGE OUTSIDE WITHOUT CONNECTION TO SEWAGE SYSTEM IS NOT

ALLOWED.

Sewage system

Pipe

U-trap Pipe

Pipe U-trap Pipe Sewage system

Condensate drain pipe

OUTDOOR TEMPERATURE SENSOR MOUNTING AND CONNECTION

The unit is supplied with the TE1 outdoor temperature sensor.

The outdoor temperature sensor mounting is as follows:

1. Remove two screws that retain the sensor cover.

2. Take off the sensor cover.

3. Install the sensor on the outer wall. The installation place must not be subjected to direct solar light.

4. Install the sensor cover back.

5. Connect the sensor to the X1 terminal block in compliance with the electric wiring diagram.

1 2 3 4

www.ventilation-system.com

12

DUCT HUMIDITY SENSOR MOUNTING AND CONNECTION

The HV1 duct humidity sensor is a special accessory and is purchased separately. Connect the contact socket of the humidity sensor to the contact socket located inside of the heat recovery unit. After that fix the sensor using the clamp and the holder in the air duct upstream of the heat exchanger.

Humidity sensor mounting location

1.

DUCT HUMIDITY SENSOR CONNECTION

2.

3.

13

CONNECTION TO POWER MAINS

DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY ELECTRIC INSTALLATION

OPERATIONS. CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED bY A QUALIFIED

ELECTRICIAN WITH A WORk PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL

READING OF THE PRESENT USER’S MANUAL. THE RATED ELECTRICAL PARAMETERS OF THE UNIT

ARE SHOWN ON THE RATING PLATE. ANY INTERNAL CONNECTION MODIFICATIONS ARE NOT

ALLOWED AND RESULT IN WARRANTY LOSS.

The VUT 2000-3000 PW EC airhandling unit is rated for connection to single-phase AC 230 V / 50 Hz power mains. The unit must be connected to power mains using durable, insulated and heat-resistant conductors (cables and wires) with minimum cross section not less than 2.5 mm

2

.

ExTERNAL WIRING DIAGRAM FOR THE UNIT VUT 2000 PW EC

X1

L N PE 1

L

2

N

3

PE

4

1

5

2

6

3

7 c

8 nc

9

N

10 11 12 13 14 15 16 17 18 19 20 21 22 23

L N L c nc c no +12V Gnd B A E+ Gnd Out

L N PE 1

SM4

2 3

+ Y

M4

— ELECTRIC SHOCK HAZARD!

1 2 1

N

SM1

2 1

L N

SM2

2

L

DD1

1

PK1

2 +12V Gnd B A E+ Gnd Out

P1 TE1

The VUT 2000-3000 PW EC airhandling unit is rated for connection to three-phase AC 400 V / 50 Hz power mains. The unit must be connected to power mains using durable, insulated and heat-resistant conductors (cables and wires) with minimum cross section not less than 2.5 mm

2

.

ExTERNAL WIRING DIAGRAM FOR THE UNIT VUT 3000 PW EC

X1

L1 L2 L3 N PE 1

L

2

N

3

PE

4

1

5

2

6

3

7 c

8 nc

9

N

10 11 12 13 14 15 16 17 18 19 20 21 22 23

L N L c nc c no +12V Gnd B A E+ Gnd Out

L N PE 1

SM4

2 3

+ Y

M4

— ELECTRIC SHOCK HAZARD!

1 2 1

N

SM1

2 1

L N

SM2

2

L

DD1

1

PK1

2 +12V Gnd B A

P1

E+ Gnd Out

TE1

Design.

Cooler DX cooler

Name

DD1 Pump dry run protection relay

M4 Circulation pump of the heater

SM1 Supply air damper actuator

SM2 Extract air damper actuator

SM4 3-way valve actuator

PK1 Contact from fire alarm panel

P1** Control panel

TE1 Outdoor air temperature sensor

1. The unit delivery set includes P1 and TE1 only.

2. ** - Max. connecting cable length is 20 m.

Model

NO

NC max. 0,3 kW

LF230

LF230

LR24 SR

NO

Wire

2 х 0,75 mm

2

2 х 0,75 mm 2

3 х 0,75 mm

2

2 х 0,75 mm 2

2 х 0,75 mm

2

3 х 0,75 mm

2

2 х 0,75 mm

2

4 х 0,75 mm

2

3 х 0,75 mm

2

The above cross section is for reference only. The applicable cable cross section must be selected depending on the wire type, its maximum temperature and insulation, the maximum current, the wire length and its installation method.

Use copper wires only.

Connect the unit to power mains through the terminal block located in the terminal box on the side panel of the unit in compliance with the wiring diagram and terminal marking. Connect all the control and supply cables in compliance with the terminal marking and polarity!

Connect the unit to power mains through the external automatic circuit breaker with a magnetic trip integrated into the fixed wiring system.

The trip current must be in compliance with current consumption.

www.ventilation-system.com

14

FUNCTIONAL DIAGRAM

Outside

TE1

D1 F1

D2

M2

SM2 SM1 SM3

TE2

RK1

400 V AC

Power supply 12 V AC

230 V AC

Digital input (DI)

24 V AC

Digital output (DO)

Analogue input (AI)

Analogue output (AO)

RS485

M1

HV1

Q1

TE4 TE5

TE3

М4

SM4

DD1

F2

Indoor

TE6 HV2

P1

Q1

HV1*

HV2

RK1

SM1*

SM2*

SM3

SM4*

Designation

D1*

D2*

F1

F2

M1

M2

P1

TE5

TE6

DD1*

M4*

TE1

TE2

TE3

TE4

Name

Supply air damper.

Extract air damper.

Supply filter.

Extract filter.

Supply fan.

Extract fan.

Control panel.

Water heater.

Duct humidity sensor.

Indoor humidity sensor.

Plate heat exchanger.

Supply air damper actuator.

Extract air damper actuator.

Bypass damper electric actuator.

3-way valve actuator.

Intake air temperature sensor.

Temperature sensor downstream of the heat exchanger.

Return heat medium temperature sensor.

Water heater freeze protection sensor.

Air temperature duct sensor.

Room air temperature sensor.

Pump dry run protection relay.

Circulation pump of the water heater.

* - The appliances are not supplied with the unit, are available separately.

15

MAINTENANCE

Maintenance operations of the unit are required 3-4 times per year. Maintenance includes general cleaning of the unit and the following operations:

1. Filter maintenance (3-4 times per year).

Dirty filters increase air resistance in the system and reduce supply air volume. The filters require cleaning not less than 3-4 times per year.

Vacuum cleaning is allowed. After two consecutive cleanings filters must be replaced. For new filters contact your Seller.

Sequence of filter removal:

1. Unlatch and open the service panel. Open the panel with care.

2. Set the retaining plate aside. Pull the filters until they slide off the guides.

Install the filters in the reverse order.

2. Heat exchanger cleaning (once per year).

Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the filters. To maintain the high heat recovery efficiency, regular cleaning is required. To clean the heat exchanger remove the drain pan and the filters from the unit and clean the heat exchanger by using compressed air or a vacuum cleaner.

Sequence of the drain pan removal:

1. Unlatch and open both service panels. Open the panels with care.

2. Release the drain pipe from the side of the water heater connection and pull it down.

3. Release the second drain pipe by pulling the drain pan aside.

Install the drain pan in the reverse order.

If a more thorough cleaning of the heat exchanger is required, call your service technician.

www.ventilation-system.com

16

3. Fan inspection (once per year).

Even in case of regular maintenance of the filters, some dust may accumulate inside the fans and reduce the fan performance and supply air flow.

Clean the filters with a vacuum cleaner, a soft cloth or brush. Do not use water, aggressive solvents or sharp objects as they may damage the impeller.

Access to the fans is from the side of air ducts connections.

4. Condensate drainage inspection (once per year).

The condensate drainage (drain line) may get clogged by dirt and dust particles contained in the exhaust air. Check the drain line operation by filling the drain pan under the unit with water, clean the U-trap and the drain line, if necessary.

5. Exhaust louvre shutters and intake diffusers cleaning (as required).

Wash the diffusers and the louvre shutters with warm detergent solution.

6. Supply air flow control (twice per year).

The supply duct grille may get clogged with leaves and other objects reducing the unit performance and supply air delivery. Check the supply grille twice per year and clean it as required.

7. Ductwork system inspection (once in 5 years).

Even regular fulfilling of all the prescribed above maintenance operations may not completely prevent dirt accumulation in the air ducts which reduces the unit capacity. Duct maintenance means regular cleaning or replacement.

17

FAULT HANDLING

Problem

The fan(s) do(es) no start.

No power supply.

The motor is jammed, the impeller blades are soiled.

Alarm in the system.

FAULTS AND FAULT HANDLING

Possible reasons Fault handling

Make sure the power supply line is connected correctly, otherwise troubleshoot a connection error.

Turn the unit off. Troubleshoot the motor jam and the impeller clogging. Clean the blades. Restart the unit.

For troubleshooting of the control system errors refer to the control panel manual.

Automatic circuit breaker tripping following the unit turning on.

Overcurrent resulted from short circuit in the electric circuit.

Turn the unit off. Contact the Seller.

Low air flow.

Cold supply air.

Noise, vibration.

Water leakage.

Low set fan speed.

The filters and the fans are soiled, the heat exchanger is soiled.

The ventilation system components (air ducts, diffusers, louvre shutters, grilles) are soiled or damaged.

The air dampers, diffusers or the louvre shutters are closed.

The extract filter is soiled.

The heat exchanger is frozen.

Malfunction of the water heater.

The impeller(s) is soiled.

The fan or casing screw connections are too loose.

No anti-vibration connectors.

The drainage system is soiled, damaged or arranged not correctly.

Set higher speed.

Clean or replace the filters. Clean the fans and the heat exchanger.

Clean or replace the ventilation system components (air ducts, diffusers, louvre shutters, grilles).

Make sure that the air dampers, diffusers or louvre shutters are fully opened.

Clean or replace the extract filter.

Check the heat exchanger for freezing. Turn the unit off if required and restart it after the freezing danger is no longer imminent.

Contact the Seller.

Clean the impeller(s).

Tighten the screw connection of the fans or the casing against stop.

Install anti-vibration connectors.

Clean the drain line. Check the drain line slope angle. Make sure that the U-trap is filled with water and the drain pipes are frost protected.

STORAGE AND TRANSPORTATION RULES

Store the unit in the manufacturer’s original packing box in a dry closed ventilated premise with temperature range from +5 °C to + 40°C.

Vapours or particles which can cause corrosion or damage the insulation or connection tightness are not allowed in the storage environment.

Use hoist machinery for handling and transportation to prevent possible mechanical damages of the unit.

Fulfil the requirements for transportation of the specified cargo type.

Use any vehicle types for the unit transportation provided that it is protected against mechanical or weather damage.

Avoid any mechanical shocks and strokes during handling operations.

www.ventilation-system.com

18

MANUFACTURER’S WARRANTY

The manufacturer hereby warrants normal operation of the unit over the period of 24 months from the retail sale date provided the user’s observance of the transportation, storage, installation and operation regulations.

Should any malfunctions occur during the unit operation due to manufacturer’s fault during the warranty period the user is entitled to elimination of faults by means of warranty repair performed by the manufacturer.

The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the warranty period. The faults are eliminated by means of replacement or repair of the complete unit or the faulty part thereof.

The warranty repair does not include:

• routine maintenance

• unit installation / dismantling

• unit setup

To benefit from warranty repair the user must provide the unit, the user’s manual with stamped sale date and the payment document certifying the purchase.

The unit model must comply with the one stated in the user’s manual.

Contact the Seller for warranty service.

The manufacturer’s warranty does not apply to the following cases:

• user’s failure to provide the unit with the entire delivery package as stated in the user’s manual or with missing component parts previously dismounted by the user

• mismatch of the unit model and mark with the respective details stated on the unit packing and in the user’s manual

• user’s failure to ensure timely technical maintenance of the unit

• external damage to the casing (excluding external modifications of the unit as required for its installation) and the internal components of the unit

• alteration of the unit design or engineering changes of the unit

• replacement and use of the unit assemblies, parts and components not approved by the manufacturer

• unit misuse

• user’s violation of the unit installation regulations

• user’s violation of the unit management regulations

• unit connection to power mains with a voltage different from the one stated in the user’s manual

• unit breakdown due to voltage surges in the power mains

• user’s discretionary repair of the unit

• unit repair performed by any persons not authorized by the manufacturer

• expiry of the unit warranty period

• user’s violation of the established regulations specific to the unit transportation

• user’s violation of the unit storage regulations

• wrongful acts against the unit committed by third persons

• unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, or blockade)

• missing seals if provided by the user’s manual

• failure to provide the user’s manual with the sale date stamp

• missing payment document certifying the unit purchase

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUbLE-FREE

OPERATION OF THE UNIT.

USER’S CLAIMS SHALL bE A SUbJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE

PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE SALE DATE STAMP.

19

ACCEPTANCE CERTIFICATE

Product type

Model

Serial number

Heat recovery air handling unit

VUT __________ PW EC

Manufacturing date

We hereby declare that the product complies with the essential protection requirements of Electromagnetic Council Directive2004/108/EC,

89/336/EEC and Low Voltage Directive 2006/95/EC, 73/23/EEC and CE-marking Directive 93/68/EEC on the approximation of the laws of the

Member States relating to electromagnetic compatibility.

This certificate is issued following test carried out on samples of the product referred to above.

Quality inspector’s stamp

SELLER INFORMATION

Shop name

Address

Phone number

E-mail

Sales date

This is to certify delivery of the complete unit with the user's manual.

Customer's signature

Seller’s seal

MOUNTING CERTIFICATE

VUT ___ PW EC heat recovery air handling unit has been connected to power mains pursuant to the requirements stated in the present user’s manual.

Company name

Address

Phone number

Installation technician's full name

Installation date: Signature:

Installation technician’s company seal

This is to certify that the works specific to the unit installation has been performed in accordance with all the applicable provisions of local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.

Signature:

www.ventilation-system.com

20

WARRANTY CARD

Product type

Model

Serial number

Manufacturing date

Sales date

Warranty period

Sales company

Heat recovery air handling unit

VUT __________ PW EC

Seller’s seal

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________

___________________________________________________________________________________________________________