Mitsubishi Electric GOT-A900 Series Owner's Manual


Add to my manuals
84 Pages

advertisement

Mitsubishi Electric GOT-A900 Series Owner's Manual | Manualzz

GOT-A900 Series Operating Manual

(GT Works2 Version1/GT Designer2 Version1 compatible

Gateway Functions Manual)

O

GOT-A900 Series Operating Manual

(GT Works2 Version1/GT Designer2 Version1 compatible

Gateway Functions Manual)

MODEL

SW1-GTD2-O(G)-E

MODEL

CODE

1D0J00

SH(NA)-080398E-A(0304)MEE

HEAD OFFICE : 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212,JAPAN

NAGOYA WORKS : 1-14 , YADA-MINAMI 5 , HIGASHI-KU, NAGOYA , JAPAN

When exported from Japan, this manual does not require application to the

Ministry of Economy, Trade and Industry for service transaction permission.

Specifications subject to change without notice.

MITSUBISHI Graphic Operation Terminal

MONO

SAFETY PRECAUTIONS

(Always read these instructions before using this equipment.)

Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly.

The instructions given in this manual are concerned with this product. For the safety instructions of the programmable controller system, please read the CPU module user's manual.

In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".

!

DANGER

!

CAUTION

Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.

Note that the

!

CAUTION level may lead to a serious consequence according to the circumstances.

Always follow the instructions of both levels because they are important to personal safety.

Please save this manual to make it accessible when required and always forward it to the end user.

[Precautions for test operation]

!

CAUTION

Before starting test operation for system monitor, special function module monitor or ladder monitor (bit device ON/OFF, word device present value changing, timer/counter set value/present value changing, buffer memory present value changing), please read the manual carefully to fully understand the operation methods.

For the devices that perform significant operations for the system, never perform test operation to change data.

Doing so can cause accidents due to false outputs or malfunctions.

A - 1 A - 1

REVISIONS

* The manual number is given on the bottom left of the back cover.

Print Date * Manual Number

Apr., 2003 SH (NA)-080398E-A First printing

Jan., 2004 SH (NA)-080398E-B Partial corrections

Revision

Chapter 4, Section 5.4

Jul., 2004 SH (NA)-080398E-C Partial corrections

Section 5.5

MODEL CODE change

Changed from 1D0J00 to 1DM208.

Japanese Manual Version SH-080352-C

This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

2003 MITSUBISHI ELECTRIC CORPORATION

A - 2 A - 2

Structure of This Manual

This manual is made up of the following chapters.

Chapter 1

Overview

Describes the features of the gateway functions.

1

Chapter 2

System Configuration

Describes the system configuration of the gateway functions.

2

Chapter 3

Operation Sequence

Provides the general procedure for using the gateway functions.

3

Chapter 4

Settings Common to

Functions

Chapter 5

Server and Client

Functions

Describes the settings common to the gateway functions.

4

Describes the specifications, setting methods, precautions and others of the server and client functions.

5

Chapter 6

FTP Server Function

Describes the specifications, setting methods, precautions and others of the FTP server function.

6

Chapter 7

Mail Send Function

Describes the specifications, setting methods, precautions and others of the mail send function.

7

Chapter 8

Troubleshooting

Describes the error messages and troubleshooting for the functions.

8

A - 3 A - 3

INTRODUCTION

Thank you for choosing the Mitsubishi Graphic Operation Terminal.

Before using the equipment, please read this manual carefully to use the equipment to its optimum.

CONTENTS

SAFETY PRECAUTIONS

REVISIONS

Structure of This Manual

A- 1

A- 2

A- 3

About Manuals

About the Generic Terms and Abbreviations

About the Symbols

1. OVERVIEW

1.1 Features of Server and Client Functions

1.2 Features of FTP Server Function

1.3 Featuers of Mail Send Function

2. SYSTEM CONFIGURATION

2.1 System Configuration of Gateway Functions

2.2 Connection Form

2.3 Required Devices

2.4 Precautions for Mounting the Communication Board

2.5 About the System Programs

2.6 Precautions for System Configuration

3. OPERATION SEQUENCE

4. FUNCTION SETTING

4.1 GOT Setting

4.2 GT Designer2 Setting

A- 7

A- 8

A- 11

1- 1 to 1- 3

1- 1

1- 3

1- 3

2- 1 to 2- 4

2- 1

2- 1

2- 2

2- 2

2- 4

2- 4

3- 1 to 3- 2

4- 1 to 4- 4

4- 3

4- 4

A - 4 A - 4

5. SERVER AND CLIENT FUNCTIONS 5- 1 to 5-22

5.1 Gateway Devices 5- 1

5.1.1 What are the gateway devices?.................................................................................... 5- 1

5.1.2 Usable gateway devices ............................................................................................... 5- 2

5.1.3 How to monitor the gateway devices............................................................................ 5- 3

5.1.4 PLC devices that can be assigned ............................................................................... 5- 6

5.2 Specifications 5- 8

5.2.1 Specifications................................................................................................................. 5- 8

5.2.2 Access range that can be monitored ............................................................................ 5- 9

5.3 Setting Method 5-10

5.4 Examples of Use

5.5 Precautions

5-13

5-18

5-20 5.6 For Efficient Use

6. FTP SERVER FUNCTION 6- 1 to 6-13

6.1 Specifications 6- 1

6.1.1 Specifications................................................................................................................. 6- 1

6.1.2 File accessible range..................................................................................................... 6- 2

6.2 Setting Method 6- 3

6.3 Operation on the FTP Client Side 6- 4

6.3.1 Input command at FTP client ........................................................................................ 6- 4

6.3.2 File specifying method................................................................................................... 6- 5

6.3.3 Checking the line connection condition ........................................................................ 6- 6

6.3.4 Line cutoff ...................................................................................................................... 6- 7

6.4 Example of Use 6- 8

6-12 6.5 Precautions

7. MAIL SEND FUNCTION 7- 1 to 7- 8

7.1 Specifications 7- 1

7.1.1 Specifications................................................................................................................. 7- 1

7.1.2 Mail send enabled range.............................................................................................. 7- 2

7.2 Setting Method 7- 3

7.3 Send Examples

7.4 Examples of Use

7.5 Precautions

7- 4

7- 6

7- 8

A - 5 A - 5

8. TROUBLESHOOTING 8- 1 to 8-9

8.1 Troubleshooting Common to Gateway Functions

8.2 Gateway Information

8- 1

8- 2

8.3 Server and Client Functions 8- 4

8.3.1 Error codes and error messages .................................................................................. 8- 4

8.3.2 Troubleshooting............................................................................................................. 8- 6

8.4 FTP Server Function 8- 7

8.4.1 Error codes and error messages .................................................................................. 8- 7

8.4.2 Troubleshooting............................................................................................................. 8- 8

8.5 Mail Send Function 8- 9

8.5.1 Error codes and error messages .................................................................................. 8- 9

8.5.2 Troubleshooting............................................................................................................. 8- 9

INDEX Index- 1 to Index - 2

A - 6 A - 6

About Manuals

The following manuals are also related to this product.

In necessary, order them by quoting the details in the tables below.

Related Manuals

Manual Name

GT Designer2 Version1 Operating Manual

Describes methods of operating GT Designer2 and transmitting data to GOT

(Option)

GT Designer2 Version1 Reference Manual

Describes the specifications and settings of each object function used in GT Designer2

(Option)

GOT-A900 Series Operating Manual

(GT Works2 Version1/GT Designer2 Version1 compatible Extended • Option Functions Manual)

Describes the following extended functions and optional functions applicable to GOT

• Utility • Ladder monitor

• Special module monitor • Network monitor

• Module monitor

• Font change

• Servo amplifier monitor

• System monitor

• List editing

• CNC monitor

(Option)

GOT-A900 Series User’s Manual

(GT Works2 Version1/GT Designer2 Version1 compatible Connection System Manual)

Describes the system configuration of which connection method is compatible with GOT-A900 series as well as processing cables.

(Option)

A985GOT/A975GOT/A970GOT/A960GOT User's Manual

Explains the performance specifications, installation methods, communication board/communication unit mounting methods and others of the GOTs.

(Option)

A950GOT/A951GOT/A953GOT/A956GOT User's Manual

Explains the performance specifications, installation methods, communication board/communication unit mounting methods and others of the GOTs.

(Option)

MX Component Version3 Operating Manual

Explains the setting and operating methods of the utilities on MX Component.

(Option)

MX Component Version3 Programming Manual

Explains the programming procedures, detailed descriptions and error codes of the ACT controls.

(Option)

Manual Number

(Model Code)

SH-080278E

(1DM205)

SH-080251

(1DM204)

SH-080253

(1DM206)

SH-080255

(1DM207)

SH-4005

(1DM099)

SH-080018

(1DM103)

SH-080271

(13JU32)

SH-080272

(13JF66)

A - 7 A - 7

About the Generic Terms and Abbreviations

The following abbreviations and generic terms are used in this manual.

GOT

Generic Term/Abbreviation Description

A975GOT

A975GOT-TBA-B, A975GOT-TBD-B, A975GOT-TBA, A975GOT-TBD,

A975GOT-TBA-EU

A970GOT

A970GOT-TBA-B, A970GOT-TBD-B, A970GOT-TBA, A970GOT-TBD,

A970GOT-SBA, A970GOT-SBD, A970GOT-LBA, A970GOT-LBD,

A970GOT-TBA-EU, A970GOT-SBA-EU, A970GOT-LBA-EU

A97 GOT A975GOT, A970GOT

GOT-A900

Series

A956WGOT A956WGOT-TBD

A956GOT

A956GOT-TBD, A956GOT-SBD, A956GOT-LBD,

A956GOT-TBD-M3, A956GOT-SBD-M3, A956GOT-LBD-M3

A953GOT

A951GOT

A951GOT-Q

A953GOT-TBD, A953GOT-SBD, A953GOT-LBD,

A953GOT-TBD-M3, A953GOT-SBD-M3, A953GOT-LBD-M3

A951GOT-TBD, A951GOT-SBD, A951GOT-LBD,

A951GOT-TBD-M3, A951GOT-SBD-M3, A951GOT-LBD-M3

A951GOT-QTBD, A951GOT-QSBD, A951GOT-QLBD,

A951GOT-QTBD-M3, A951GOT-QSBD-M3, A951GOT-QLBD-M3

A950GOT

A95

A95

handy GOT

GOT

A950GOT-TBD, A950GOT-SBD, A950GOT-LBD,

A950GOT-TBD-M3, A950GOT-SBD-M3, A950GOT-LBD-M3

A950GOT-SBD-M3-H, A950GOT-LBD-M3-H, A953GOT-SBD-M3-H,

A953GOT-LBD-M3-H

A956GOT, A953GOT, A951GOT, A951GOT-Q,

A950GOT, A950 handy GOT

Communication board/Communication module

A9GT-QBUS2S,

Description

A9GT-BUSS, A9GT-BUS2S,

Generic Term/Abbreviation

Communication board

Communication module

Bus connection board A9GT-QBUSS,

Serial communication board A9GT-50WRS4

Ethernet communication module

A9GT-J71E71-T

Option unit

Generic Term/Abbreviation

Option module

Memory card interface module

A1SD59J-MIF

Description

A - 8 A - 8

Option

Generic Term/Abbreviation Description

A9GT-FNB, A9GT-FNB1M, A9GT-FNB2M, A9GT-FNB4M,

Memory board

Option

PC card

(memory card)

Flash PC card/Commercially available flash PC card/SRAM type PC card

Flash PC card A9GTMEM-10MF, A9GTMEM-20MF, A9GTMEM-40MF

Compact flash PC

Commercially available flash PC card card

Software

Generic Term/Abbreviation

GT Works2 Version1 SW1D5C-GTWK2-E

GT Designer2

Version1

SW1D5C-GTD2-E

Software

GT Designer2

GT Simulator2

GT SoftGOT2

Description

GT Designer2 screen creation software for GOT900

GT Simulator2 screen simulator for GOT900

GT SoftGOT2 monitoring software

MX Component MX Component ActiveX communication support tool

CPU

Generic Term/Abbreviation

QCPU

QCPU (Q Mode)

Q00JCPU,

Q02HCPU,

Q12PHCPU,

QCPU (A Mode) Q02CPU-A,

Remote I/O station

QnACPU

QnACPU type

QnASCPU type

AnUCPU

Q00CPU,

Q06HCPU,

Q25PHCPU,

Q02HCPU-A,

Description

Q01CPU,

Q12HCPU,

Q12PRHCPU,

Q06HCPU-A

Network module for MELSECNET/H network system remote I/O station

(QJ71LP25-25, QJ72LP25, QJ72BR15)

Q2ACPU,

Q3ACPU,

Q2ACPU-S1,

Q4ACPU,

Q2AHCPU,

Q4ARCPU

Q2ASCPU,

A2UCPU,

Q2ASCPU-S1,

A2UCPU-S1,

Q2ASHCPU,

A3UCPU,

A3ACPU

A2NCPU-S1,

AnNCPU

A2USHCPU-S1

ACPU

FXCPU

AnACPU

AnNCPU

AnCPU type

AnUS(H)CPU

AnS(H)CPU

A2ACPU,

A1NCPU,

AnUCPU,

A2USCPU,

A1SCPU,

A1SHCPU,

A1SJCPU,

A2ACPU-S1,

A2NCPU,

AnACPU,

A2USCPU-S1,

A1SCPUC24-R2,

A2SHCPU,

A1SJCPU-S3, A1SJ(H)CPU

AnSCPU type AnUS(H)CPU,

A1FXCPU A1FXCPU

A0J2HCPU,

FX

0

series,

AnS(H)CPU,

A2CCPU,

FX

0N

series,

FX

1N

series,

FX

2C

series,

FX

FX

FX

(2N)

-10GM/20GM series,

1NC

2N

series,

series,

A2SCPU,

A2SHCPU-S1

A1SJHCPU

A1SJ(H)CPU

A2CCPUC24,

FX

0S

series,

FX

1S

series,

FX

2NC

series,

FX

3UC

series

Q02CPU,

Q25HCPU,

Q25PRHCPU

Q2AHCPU-S1,

Q2ASHCPU-S1

A4UCPU

A3NCPU

A2SCPU-S1,

A2CJCPU

FX

1

series,

FX

2

series,

Motion controller

CPU (Q series)

Q172CPU, Q173CPU

Motion controller

CPU

Motion controller

CPU (A series)

FA controller

MELDAS C6/C64

A172SHCPUN, A173UHCPU, A173UHCPU-S1

LM610, LM7600, LM8000

FCA C6, FCA C64

A - 9 A - 9

Other PLC

Generic Term/Abbreviation

Omron PLC

Yaskawa PLC

Allen-

Bradley

PLC

Sharp PLC

SLC500 series

MicroLogix1000 series

MicroLogix1500 series

C200HS, C200H,

C200HE),

CV500,

CVM1-CPU11,

CJ1M,

CPM2C,

GL60S,

GL130,

MP-930,

SLC500-20,

SLC5/02,

CQM1,

CV1000,

CVM1-CPU21,

CPM1,

CPM1H

GL60H,

CP-9200SH,

MP-940,

SLC500-30,

SLC5/03,

1761-L10BWA,

1761-L16BWB,

1761-L10BWB,

1761-L16BBB,

1761-L32BWB, 1761-L32BBB,

1761-L20BWA-5A, 1761-L20BWB-5A

Description

C200H series (C200HX, C200HG,

C1000H,

CV2000,

CS1,

CPM1A,

C2000H,

CVM1-CPU01,

CS1D,

CPM2A,

GL70H,

CP-9300MS,

MP-9200(H),

SLC500-40,

SLC5/04,

1761-L16AWA,

1761-L32AWA,

1761-L32AAA,

GL120,

MP-920,

PROGIC-8

SLC5/01,

SLC5/05

1761-L16BWA,

1761-L32BWA,

1761-L20AWA-5A,

1764-LSP

JW-21CU, JW-22CU, JW-31CUH, JW-32CUH,

JW-33CUH, JW-50CUH, JW-70CUH, JW-100CUH,

JM-100CU, Z-512J

T3, T3H, T2E, T2N

Toshiba

PLC

SIEMENS PLC

HITACHI

PLC

(HIDEC H series)

PROSEC T series

PROSEC V series

Large-sized H series

H-200 to 252 series

H series board type

EH-150 series

Matsushita Electric Works PLC

Model3000, S2T

SIMATIC S7-200 series,

SIMATIC S7-400 series

SIMATIC S7-300series,

H-302(CPU2-03H), H-702(CPU2-07H), H-1002(CPU2-10H), H-2002(CPU2-20H),

H-4010(CPU3-40H), H-300(CPU-03Ha), H-700(CPU-07Ha), H-2000(CPU-20Ha)

H-200(CPU-02H,CPE-02H),

H-252(CPU22-02H),

H-252C(CPU22-02HC, CPE22-02HC)

H-250(CPU21-02H),

H-252B(CPU22-02HB),

H-20DR,

H-20DT,

HL-40DR,

EH-CPU104,

H-28DR,

H-28DT,

HL-64DR

EH-CPU208,

H-40DR,

H-40DT,

H-64DR,

H-64DT,

FP0-C16CT,

FP2,

FP5,

FP-M(C32TC)

FP0-C32CT,

FP2SH,

FP10(S),

EH-CPU308,

FP1-C24C,

FP2-CCU,

FP10SH,

EH-CPU316

FP1-C40C,

FP3,

FP-M(C20TC),

A - 10 A - 10

About the Symbols

In this manual, the following symbols are used to represent menus and buttons.

Symbols Description

Represents the menu item to be selected from the menu bar.

[ ]

Represents the item in the setting dialog box or the utility menu item of the GOT.

Point

Remark

Represents the operation sequence, to to .

Represents the item that provides detailed explanation (manual or the chapter, section or item of that manual).

Represents the information that you should know.

Represents the information that will be useful.

Represents the supplementary explanation that will be helpful.

A - 11 A - 11

1. OVERVIEW

1

This manual explains the gateway functions that can be performed on the GOT-A900 series.

There are the following gateway functions to support remote watching and remote maintenance of production sites from an office.

• Server function • Client function

• FTP server function • Mail send function

1.1 Features of Server and Client Functions

Collection of data by personal computer (server function)

Monitoring the GOTs (servers) from the personal computer (MX Component) allows data to be read/written indirectly from/to the PLC CPU devices being monitored by the GOTs.

If the PLC CPU of a different maker is monitored, use of the server function enables data to be read/written with only MX Component and the communication method to be standardized by

Ethernet.

Previously ...

When server function is used ...

Install peripheral software programs of various companies.

Necessary software is MX Component only.

Mitsubishi Company

A

Micro computer board

Communications are made with personal computer in respective communication methods

of companies.

MX Component

Communication method is standardized by Ethernet.

Ethernet

Bus communication

RS-232C communication

RS-422 communication

RS-232C communication

RS-422 communication

RS-232C communication

RS-422 communication

Server

Bus communication

RS-232C communication

RS-422 communication

Server

RS-232C communication

RS-422 communication

Server

RS-232C communication

RS-422 communication

Mitsubishi PLC Company A PLC Micro computer board

Mitsubishi PLC Company A PLC Micro computer board

1 - 1 1 - 1

Monitoring of other GOTs from client GOT (server function, client function)

Monitoring of the GOTs (servers) from the GOT (client) allows data to be read/written indirectly from/to the PLC CPU devices being monitored by the GOTs (servers).

Use of the client function enables data to be read/written indirectly from/to the PLC CPUs of different makers that are different from the maker of the PLC CPU connected to the GOT (client).

1

Ethernet

Client

Bus communication

RS-232C communication

RS-422 communication

Server

RS-232C communication

RS-422 communication

Server

RS-232C communication

RS-422 communication

Mitsubishi PLC Company A PLC Micro computer board

1 - 2 1 - 2

1.2 Features of FTP Server Function

Using the FTP server function, you can read/write data (recipe, alarm history, screen image data) saved in the PC cards of the GOTs from the personal computer.

General-purpose FTP client tool

R

Windows MS-DOS prompt or command prompt

Recipe data (CSV file), alarm history data (CSV file) or screen image data (BMP/JPG file) are read to personal computer.

Recipe data (CSV file) are written to PC cards.

Ethernet

PC card PC card

FTP server function

Bus communication

RS-232C communication

RS-422 communication

FTP server function

PC card

RS-232C communication

RS-422 communication

FTP server function

RS-232C communication

RS-422 communication

Mitsubishi PLC Company A PLC

1.3 Features of Mail Send Function

Micro computer board

Using the alarm history display function, you can send the occurrence or restoration information of an error to the personal computer or cellular phone by mail at occurrence of or restoration from the error.

Alarm history display function

Sends alarm occurrence or restoration information

Intranet mail server

Internet

Personal computer

Ethernet

Cellular phone

Mail send function

Bus communication

RS-232C communication

RS-422 communication

Mail send function

RS-232C communication

RS-422 communication

Mail send function

RS-232C communication

RS-422 communication

Mitsubishi PLC Company A PLC Micro computer board

1 - 3 1 - 3

This chapter describes the system configuration of the gateway functions.

2.1 System Configuration of Gateway Functions

When the gateway functions are used, one GOT connects to Ethernet and PLCs and therefore both the

Ethernet communication module and communication board must be mounted to the GOT.

Hence, the gateway functions cannot be used for the GOT that cannot be mounted with the Ethernet communication module and for the connection form that uses the communication module.

(Example 1) For A951GOT (Example 2) For CC-Link connection

Since the Ethernet communication module cannot be mounted, the gateway functions cannot be used.

Since two different communication modules cannot be mounted to one GOT, the gateway functions cannot be used.

2

CC-Link communication module

A951GOT

Ethernet communication module

GOT

Ethernet communication module

The GOTs that can use the gateway functions are indicated on a connection form basis.

Refer to the following manual for details of the connection forms.

Connection Form

Bus connection

CPU direct connection

Computer link connection

MELSECNET connection

CC-Link connection

Ethernet connection

Third party PLC connection

Microcomputer connection

GOT-A900 Series User's Manual (GT Works2 Version1/GT Designer2 Version1 compatible Connection System Manual)

A985

GOT(-V)

A97

GOT

A960GOT

A956W

GOT

A956GOT

-M3

*1*2

: Usable : Unusable : Not connectable

A953GOT

A951GOT

(-Q)

A950GOT

A95 handy

GOT

GT

SoftGOT

1 When using the A956GOT, use the memory extension type (A956GOT-TBD-M3, A956GOT-SBD-M3,

A956GOT-LBD-M3) GOT.

2

Unable to make RS-232C/RS-422 communication, the A956GOT cannot be connected with the FXCPU or third-party PLC.

2 - 1 2 - 1

2

The following devices of the GOTs are required to use the gateway functions.

Application Required Device

A985GOT

(-V)

A97 GOT A960GOT A956WGOT

Connects GOT to

Ethernet communication module A9GT-J71E71-T (Hardware version E (June, 2002) or later) 1

Ethernet system.

Bus connection

(QCPU (Q mode))

A9GT-QBUSS or A9GT-QBUS2S 2, 3

PLC. board

Bus connection

Connects GOT to Communication

(QnA/ACPU)

RS-232C communication

RS-422 communication

Executes gateway functions with

GOT.

Memory board

PC card

A9GT-BUSS or A9GT-BUS2S 2, 3

A9GT-RS2 or A9GT-RS2T A9GT-50WRS2

Cannot be connected.

A9GT-RS4 A9GT-50WRS4

A9GT-QFNB (4/8M) or A9GT-FNB (1/2/4/8M) Not required

JEIDA Ver. 4.2 compliant (PCMCIA 2.1 compliant) PC card 4

Required to use

FTP server function.

Flash PC card

A9GTMEM-10MF, A9GTMEM-20MF,

A9GTMEM-40MF

Cannot be used.

Compact flash PC card Compact FlashTM compliant compact flash PC card 5

Cannot be used.

1 The gateway functions cannot be used with the hardware version D or earlier.

2 The bus connection module (A9GT-BUSSU, A9GT-BUS2SU, A9GT-QBUS2SU) cannot be used for the gateway functions.

Use the above bus connection board when making bus connection.

3 The bus connection board (A9GT-50WQBUSS, A9GT-50WBUSS) dedicated to the A956WGOT cannot be used for the gateway functions.

Use the above bus connection board when making bus connection with the A956WGOT.

4 The memory card interface module is required to use the PC card with the A956WGOT or

A956GOT.

5 The A985GOT cannot use the compact flash PC card. (It can be used with the A985GOT-V only.)

2.4 Precautions for Mounting the Communication

Board

A956GOT

-M3

How to mount the communication board to the GOT changes depending on the communication board used. The precautions for mounting the communication board are described below.

Point

About the mounting of the communication board

Do not mount both the bus connection board and serial communication board to the GOT.

When using the serial communication board

When mounting the serial communication board, mount it to the GOT as previously.

Refer to the following manual for the way to mount the communication board.

• A985GOT/A975GOT/A970GOT/A960GOT User's Manual

• A950GOT/A951GOT/A953GOT/A956GOT User's Manual

2 - 2 2 - 2

When using the bus connection board

Mount the bus connection board to the back of the A9GT-J71E71-T.

How to mount the bus connection board is shown below.

1) Loosen the mounting screws (2 pcs.) that fix the slot cover on the back of the A9GT-J71E71-T.

Slot cover

Bus connection board

2) Remove the slot cover.

Save the removed slot cover carefully.

(If the A9GT-J71E71-T is used alone without the slot cover, foreign matter will enter the unit, causing a failure or malfunction.)

3) Fit the bus connection board to the A9GT-J71E71-T.

4) Tighten the mounting screws (2 pcs.) of the bus connection board to the specified torque (36 to 48N • cm) to fix the bus connection board.

5) After fitting the bus connection board, mount the

A9GT-J71E71-T to the GOT.

2 - 3 2 - 3

2.5 About the System Programs

The system programs compatible with the GOT must have been installed to use the gateway functions.

Refer to the following manual for the system programs necessary for the gateway functions, their installation methods and precautions.

GT Designer2 Version1 Operating Manual

2.6 Precautions for System Configuration

Connection to the intranet must be fully safeguarded.

Consult the network access provider or network manager (person who does network planning, IP address management, etc.).

We have no liability for any system problems that occur at the time of connection to the intranet.

If a delay occurs due to network congestion, take preventive measures, e.g. install a bridge.

2 - 4 2 - 4

A general procedure for using the gateway functions is given below.

Examine the system configuration.

Install the OSs into the GOTs.

Connect the GOTs to Ethernet.

Start

Examine the configuration of the whole system.

• Connection structure of the whole system such as the PLCs and

GOTs

• PLC setting (device assignment, etc.)

• GOT setting (IP address, network number, station number, etc.)

Connect the GOTs and the personal computer, where GT Designer2 has started, by the RS-232C cable.

.....GT Designer2 Version1

Operating Manual

Fit the memory boards to the GOTs.

(Not required when the A956GOT is used)

.....User's manual of the used

GOT

Check the ROM_BIOS versions of the GOTs.

If the ROM_BIOS version does not support the gateway functions, install

ROM_BIOS again.

.....GT Designer2 Version1

Operating Manual

Install the system programs into the GOTs.

• Basic function OS

• PLC communication driver

• Extended function OS ("gateway functions" and other necessary

OS)

.....GT Designer2 Version1

Operating Manual

When the GOT is restarted, the utility menu appears. Select "Memory information" to check whether the installed OSs are correct or not.

.....Extended • Option

Functions Manual

Set the following items in the utility setup of the GOT.

• IP address of the GOT

• Set the NET No. (network number) and PLC No. (station number) of the GOT.

• When making bus connection with the QCPU, set the extension number and I/O slots.

• When making other connection, make communication settings, such as the transmission speed to the PLC, as required.

Section 4.1 in this manual

Connection System Manual

Fit the communication board to the GOT or Ethernet communication module and connect it with the PLC by the cable.

(For QnA/ACPU bus connection, make setting with the extension number and I/O slot switches on the communication board.)

Fit the Ethernet communication module to the GOT and connect the

Ethernet cable.

Section 2.4 in this manual

Connection System Manual

.....User's manual of the used

GOT

To next page

3 - 1 3 - 1

3

Create monitor screen data.

3

Download the monitor screen data.

Debug.

From previous page

Set the gateway functions to be used.

• When using the server and client functions

Make server and client settings on GT Designer2.

• When using the FTP server function

Make FTP server setting on GT Designer2.

• When using the mail send function

Set the mail of each object on GT Designer2 .

Set the send destination and SMTP server in the mail send setting.

Create monitor screen data.

.....Sections 5.3, 6.2, 7.2 in this manual

.....GT Designer2 Version1

Reference Manual

.....GT Designer2 Version1

Operating Manual

Transfer the monitor screen data to the GOTs.

(Transfer by RS-232C communication or transfer using the PC cards)

Check the operations of the GOTs.

End

3 - 2 3 - 2

To use the gateway functions, settings related to the gateway functions must be made on both the GOT and GT Designer2.

Settings to be made on the GOT and GT Designer2 will be described below.

Server and client functions

<System configuration example>

MX Component

• Utility menu of the GOT (Refer to Section 4.1.)

Set the network No., station number, IP address, etc. of the GOT itself on each GOT.

IP address: 10.97.14.20

4

GOT NW No

GOT PC No

: 1

: 1

GOT IP address : 10.97.14.10

Router address : 10.97.14.254

Ethernet

IP:

10.97.14.254

GOT NW No

GOT PC No

: 1

: 2

Router

GOT IP address : 10.97.14.11

Router address : 10.97.14.254

IP:

10.97.15.254

• GT Designer2 (Refer to Section 5.3.)

<Server setting>

Setting of the server function to the GOT.

Assign the PLC CPU devices to the gateway devices to be accessed by MX Component and the GOT of the client function.

GOT NW No

GOT PC No

: 2

: 1

GOT IP address : 10.97.15.10

Router address : 10.97.15.254

<Client setting>

Setting of the client function to the GOT.

Register its the network No., PLC No. and IP addresses of the GOTs of the server function to be accessed.

4 - 1 4 - 1

FTP server function

<System configuration example>

General-purpose FTP client tool

R

Windows MS-DOS prompt or command prompt

IP address: 10.97.14.20

Ethernet

GOT IP address : 10.97.14.10

Router address : 10.97.14.254

• Utility menu of the GOT (Refer to Section 4.1.)

Set the IP address of the GOT itself on each GOT.

GOT IP address : 10.97.14.11

Router address : 10.97.14.254

IP:10.97.14.254

Router

IP:10.97.15.254

• GT Designer2 (Refer to Section 6.2.)

<FTP server setting>

Set the login name and password used for connection of the line of the personal computer and GOT.

4

GOT IP address : 10.97.15.10

Router address : 10.97.15.254

Mail send function

<System configuration example>

Intranet mail server

Internet

IP address: 10.97.14.20

Personal computer

Ethernet

Cellular phone

• Utility menu of the GOT (Refer to Section 4.1.)

Set the IP address and mail sending of the GOT itself on each GOT.

GOT IP address : 10.97.14.10

Router address : 10.97.14.254

GOT IP address : 10.97.14.11

Router address : 10.97.14.254

IP:

10.97.14.254

Router

IP:

10.97.15.254

• GT Designer2 (Refer to Section 7.2.)

<Mail send setting>

Specify the mail server and set the mail address and others of the send destination.

GOT IP address : 10.97.15.10

Router address : 10.97.15.254

4 - 2 4 - 2

Perform the GOT setting in the setup of the utility menu.

Installing the gateway option driver into the GOT or fitting the A9GT-J71E71-T to the GOT displays the following menu. Make the necessary settings.

The settings to be made change depending on the gateway functions used.

Refer to the following manual for the way to operate the utility menu.

GOT-A900 Series Operating Manual (GT Works2 Version1/GT Designer2 Version1 compatible Extended • Option Functions Manual)

: Setting required : Setting required depending on condition : Setting not required (no problem will arise if setting is made)

Setting Item Description Factory Setting

Server

Function

Client

Function

FTP

Server

Function

Mail Send

Function

GOT NET NO.

GOT PC NO.

GOT IP ADDRESS

GOT PORT NO.

ROUTER

ADDRESS

2

SUBNET MASK

SEND MESSAGE

WAIT

SEND MESSAGE

TIME

2

Set the network No. of the GOT.

Set the station number of the GOT.

1

Set the IP address of the GOT.

Set the port No. of the GOT.

1

1

000.000.000.000

5001

When the system is connected to the other network by a router, set the router address of 000.000.000.000 the network where the GOT is connected.

When the GOT is connected to the Ethernet network under control of the subnet, set the subnet mask set commonly to the networks.

When the subnet is not used, the default value

255.255.255.000 is used for operation.

Set the send message wait to reduce the loads of the network and target PLC.

0

Set the message time. 3

START UP TIME

Set when to start communication (in seconds) after power-on of the GOT.

3

3

4

1 Set the IP address after consulting the network manager (person who does network planning, IP address management, etc.).

2 Before setting the values, have them checked by the network manager.

3 When sending multiple mails, set the time interval from when one mail is sent until the next mail is sent.

4 The send message time for connection with the SMTP server at the start of mail sending has been set to 1 minute (fixed).

Set the send message time after connection of the SMTP server.

4 - 3 4 - 3

4.2 GT Designer2 Setting

Set the gateway functions in the gateway setting of GT Designer2.

For the settings, refer to the setting methods of the corresponding functions.

• When using the server and client functions

Section 5.3 Setting Method

• When using the FTP server function

Section 6.2 Setting Method

• When using the mail send function

Section 7.2 Setting Method

4 - 4 4 - 4

5. SERVER AND CLIENT FUNCTIONS

This chapter explains the server and client functions.

5.1.1 What are the gateway devices?

The gateway devices are virtual devices designed exclusively to perform the server and client functions on the GOT, and the PLC CPU devices and GOT's internal devices are assigned to the gateway devices for use.

When accessing the PLC from the personal computer via the GOT

Accessing the gateway devices of the GOTs (server function) from the personal computer enables indirect access to the PLC CPU devices.

5

Personal computer

Use MX Component

Version 3 or later.

Mitsubishi PLC

D100

250

Omron PLC

TIM50

330

Access to gateway devices

Ethernet

Gateway device

EG0

Assignment definition

EG0=D100

GOT (server function)

Gateway device

EG0

Assignment definition

EG0=TIM50

GOT (server function)

D100 : 250 TIM50 : 330

Omron PLC Mitsubishi PLC

Refer to the following for the devices required for the GOT.

Section 2.3 Required Devices

5 - 1 5 - 1

When monitoring the PLC of different maker from one GOT

Accessing the gateway device of the GOT (server function) from the GOT (client function) enables indirect access to the PLC CPU device.

Access to gateway device

Mitsubishi PLC

D100

Omron PLC

250

TIM50

330

D100 : 250

GOT (client function)

Access to PLC

Gateway device

EG0

Assignment definition

EG0=TIM50

TIM50 : 330

GOT (server function)

5

Mitsubishi PLC

5.1.2 Usable gateway devices

The usable gateway devices are indicated below.

Device Name Device Range

Word device

Bit device

EG

EG

EG0 to EG32767

Specified bits of above word devices

Omron PLC

Device Number

Representation

Decimal

Decimal

Max. Number of Points

32k points

5 - 2 5 - 2

5.1.3 How to monitor the gateway devices

When accessing the gateway devices from the personal computer

Using the functions of MX Component (e.g. Microsoft

R

Excel), access the gateway devices of the

GOTs.

Refer to the following manuals for the operation method and programming procedure of MX

Component.

• MX Component Operating Manual

• MX Component Programming Manual

The following functions of MX Component are compatible with the GOT.

Item

Open

Close

ReadDeviceBlock

ReadDeviceBlock2

WriteDeviceBlock

WriteDeviceBlock2

ReadDeviceRandom

ReadDeviceRandom2

WriteDeviceRandom

WriteDeviceRandom2

EntryDeviceStatus

FreeDeviceStatus

Description

Opens the communication line (starts communication with the GOT).

Closes the communication line (ends communication with the GOT).

Batch-reads data from devices.

Batch-writes data to devices.

Randomly reads data from devices.

Randomly writes data to devices.

Registers device status watching.

Cancels registering device status watching.

SetDevice

SetDevice2

GetDevice

GetDevice2

GetCpuType

Changes the device data values.

Gets the device data values.

Gets the GOT model.

5 - 3 5 - 3

When accessing the gateway device from the GOT

The gateway devices cannot be assigned to the object functions.

Hence, the script function is used to monitor them.

The following explains the setting example for access to the gateway device from the GOT.

(1) When reading the gateway device value

Using the script function, read the gateway device value of the GOT (server function) to the internal device of the GOT (client function).

By monitoring the value read to the internal device using the numerical display function or like, the GOT (client function) can monitor the same value as the gateway device value of the GOT

(server function).

EG0 value is read to GD100 by script function.

Ethernet

Mitsubishi PLC

D100 250

Omron PLC

TIM50 330

D100 : 250

GOT internal device

GD100 : 330

GOT (client function)

Script function

Client setting

Numerical display 1 (for Mitsubishi)

Numerical display 2

(for GOT internal device)

Gateway device

EG0

Assignment definition

EG0=TIM50

TIM50 : 330

GOT (server function)

Server setting

Mitsubishi PLC Omron PLC

*The read destination of the script function can be set to the device of the Mitsubishi Electric PLC.

(a) Setting items of the GOT (client function)

• Script function ..........................Make setting to read the gateway device value of the

GOT (server function) to the internal device of the GOT

(client function).

• Client setting ............................Register the GOT of the server function whose device value will be read.

Mitsubishi Electric PLC.

• Numerical display 2 function ....Make setting to display the internal device value of the

GOT (client function).

(b) Setting item of the GOT (server function)

• Server setting ...........................Make setting to assign the device of the Omron PLC to the gateway device.

5 - 4 5 - 4

(2) When writing a value to the gateway device

Using the numerical input function or like, write a value to the gateway device of the GOT

(client function).

Using the script function, write the internal device value of the GOT (client function) the gateway device of the GOT (server function).

GD100 value is written to EG0 by script function.

Ethernet

Mitsubishi PLC

D100

Omron PLC

250

TIM50 520

D100 : 250

GOT internal device

GD100 : 520

GOT (client function)

Script function

Client setting

Numerical display 1 (for Mitsubishi)

Numerical display 2

(for GOT internal device)

Gateway device

EG0

Assignment definition

EG0=TIM50

TIM50 : 520

GOT (server function)

Server setting

Mitsubishi PLC Omron PLC

*The write destination of the script function can be set to the GOT internal device of the sever function.

(a) Setting items of the GOT (client function)

• Script function ..........................Make setting to write the internal device value of the

GOT (client function) to the gateway device of the GOT

(server function).

• Client setting ............................Register the GOT of the server function where the value will be written.

• Numerical input 1 function .......Make setting to input a value to the device of the

Mitsubishi Electric PLC.

• Numerical input 2 function .......Make setting to input a value to the internal device of the GOT (client function).

(b) Setting item of the GOT (server function)

• Server setting ...........................Make setting to assign the device of the Omron PLC to the gateway device.

Point

About details of the script function

Refer to the following manual for details of the script function.

GT Designer2 Version1 Reference Manual

For the examples using the script function, refer to Section 5.4 of this manual.

5 - 5 5 - 5

5.1.4 PLC devices that can be assigned

PLC devices that can be assigned

The PLC PCU devices that can be monitored by the GOT and the GOT internal devices can be assigned to the gateway devices.

Refer to the following manual for the devices that can be monitored by the GOT.

GT Designer2 Version1 Reference Manual

Precautions for monitoring the gateway devices

When the following PLC CPU devices are assigned to the gateway devices, they cannot be monitored depending on the used script function commands or MX Component functions.

The restricted commands/functions are indicated on a PLC CPU basis.

Maker Name

: No restrictions : Some devices cannot be used (unusable device names are indicated in parentheses)

Restricted Script Function Commands bmov, fmov instruction

Word device- specified

Bit device- specified

Restricted MX Component Functions

ReadDevice

Block

ReadDeviceRandom

WriteDeviceRandom

Word device- specified

Bit device- specified

Q/QnA/A/FX

CPU, motion

Mitsubishi controller A series

Electric

Motion controller Q series

(TT, TC, CT, CC) (Z, BM) (TT, TC, CT, CC) (Z, BM)

Allen-Bradley PLC

Omron PLC

Sharp PLC

Yaskawa PLC

Toshiba PLC

(TT, TN, CU, CD,

CN, TP, TA, CP,

CN)

(TT, TN, CU, CD,

CA)

(T, C) (T, C)

(Z, T, C)

(TT, TN, CU, CD,

CN, TP, TA, CP,

CN)

(TT, TN, CU, CD,

CA)

(T, C) (T, C)

(Z, T, C)

Hitachi PLC

(TD, SS, WDT,

MS, TMR, CU,

RCU, CT, R, DIF,

DFN)

Matsushita Electric

Works PLC (T, C)

SIEMENS PLC

(Example) When the bmov instruction is used with the script function

The gateway device to which TT (Allen-Bradley PLC device) has been assigned cannot be monitored.

1 The devices not indicated in the above table can be monitored.

2 Can be monitored if the bit device-specified command is used.

Script function bmov instruction

GOT

(client function)

(TD, SS, WDT,

MS, TMR, CU,

RCU, CT, R, DIF,

DFN)

(T, C)

Device TT is assigned to gateway device.

EG0=T4:0/14(TT)

GOT

(server function)

Mitsubishi Electric PLC Allen-Bradley PLC

5 - 6 5 - 6

Remark

Restricted script function commands

There are restrictions on the following script function commands.

Refer to the following manual for details of the commands.

GT Designer2 Version1 Reference Manual

• Word device-specified command names

Item

Function

Applied arithmetic operation

Description sin, cos, tan, asin, acos, atan, abs, log, log10, exp, ldexp, sqrt

• Bit device-specified command names

Item

Operator

Description

Bit device &, |, ~, ^, <<, >>

Substitution =

Device operation set, rst, alt

5 - 7 5 - 7

5.2 Specifications

5.2.1 Specifications

The specifications of the server and client functions are given below.

Port number

Item

Server function

Client function

Max. number of nodes

Specifications

5011

5012, 5013

Recommended: Max. 64 units

(GOT (server function) + GOT (client function) + personal computer that communicates with GOTs = 64 units)

Setting Method

Fixed

Number of clients (GOT, personal computer) that can access servers

(GOTs) simultaneously

Other node designation

Gateway device

Compatible MX Component

Memory space used by GOT

(bytes)

Server function

Client function

Max. 5 units

IP address designation, max. 128 units

32k points of word devices: EG0 to 32767

MX Component Version 3 (SW3D5C-ACT(-A)) or later

20 + 20

16 + 20

1 number of assigned gateway device points preset number of GOTs of server function

GT Designer2

GT Designer2

1 If six or more clients (GOT, personal computer) make simultaneous access to the servers (GOTs), the scripts of the clients may stop.

5 - 8 5 - 8

5.2.2 Access range that can be monitored

The access range of the server and client functions is shown below.

When the PLC CPU is monitored via the GOT, only the PLC CPU device set to the gateway device of the GOT can be accessed.

• The device of the PLC CPU as the network destination can be monitored when it is assigned to the gateway device of the GOT connected.

• The GOT cannot monitor the PLC CPU of Ethernet connection.

Ethernet

Personal computer

(MX Component)

PLC 2)

GOT 1)

Bus connection

RS-232C/RS-422 communication

GOT 2) PLC 1)

Bus connection

RS-232C/RS-422 communication

PLC 6)

PLC 3)

MELSECNET or like

PLC 5)

PLC 4)

Monitor

Destination

Monitor Source

Personal computer

GOT 1) (client)

GOT 2) (client)

Personal computer

GOT 1)

(Server)

GOT 2)

(Server)

PLC 1) PLC 2) PLC 3) PLC 4) PLC 5) PLC 6)

1) 1) 1) 1) 2)

1) 1) 1) 1)

2)

: Can monitor the gateway device

: Can monitor the PLC CPU device.

1) : Can monitor the PLC CPU device assigned to the gateway device of the GOT 1).

2) : Can monitor the PLC CPU device assigned to the gateway device of the GOT 2).

: Cannot monitor.

5 - 9 5 - 9

Server setting

In the server setting, set the gateway device to be used by the GOT of the server function and the

PLC CPU device to be assigned to that gateway device.

(1) Server function setting method

When either of the following operations is performed, the Gateway server dialog box is displayed.

• Choose the [Common] [Gateway] [Server] menu.

• Double-click (Gateway Server) in the workspace.

(b) Gateway server dialog box

Item

Assignment setting list

EG Device

Type

PLC Device

OK

Cancel

Add

Delete

Delete All

Check

Points

Description

Set the gateway devices used for the GOT of the server function and the PLC CPU devices to be assigned to those gateway devices.

Set the gateway device to which the PLC CPU device will be assigned.

Select the type of the device to be assigned.

Set the N/W number, PLC station number, CPU number and device of the PLC CPU to be assigned to the gateway device.

Refer to the following for the device setting method.

GT Designer2 Version1 Reference Manual

Register the consecutive device points in "Points" for the device type already set.

Used to confirm the settings and close the dialog box.

Used to cancel the settings and close the dialog box.

Used to add new assignment settings.

Click this switch to display the EG Device setting dialog box, and make settings.

After selecting the setting, click this switch to delete the setting.

Used to delete all settings.

Used to check whether the settings are correct or not.

If any setting is incorrect, the error message is displayed.

5 - 10 5 - 10

(2) Precautions for device assignment

A gateway device is set on a two point basis.

Hence, the number of assigned points changes depending on the set device type.

(a) Assignment of bit device (1-bit device)

It is assigned on a 32 point basis.

(Example) When M0 is assigned to EG0

EG0 M15 to M0

(b) Assignment of word device (16-bit device)

It is assigned on a 2 point basis.

(Example) When D0 (16 bits) is assigned to EG0

EG0 D0

EG1 M32 to M16

(c) Assignment of word device (32-bit device)

It is assigned on a 1 point basis.

(Example) When CN200 (32 bits) is assigned to EG0

EG0 CN200 (lower bits)

EG1 CN200 (upper bits)

EG1 D1

(d) Assignment of 8-bit device

It is assigned on a 4 point basis.

(Example) When E0000 is assigned to EG0

EG0

EG1

E0001 E0000

E0003 E0002

5 - 11 5 - 11

Client setting

In the client setting, register the N/W No., PLC No. and IP address of the GOT of the server function to be monitored by the GOT of the client function.

(1) Client function setting method

When either of the following operations is performed, the Gateway client dialog box is displayed.

• Choose the [Common] [Gateway] [Client] menu.

• Double-click (Gateway Client) in the workspace.

(b) Gateway client dialog box

Item Description

Server function GOT list

OK

N/W No.

PLC No.

Type

IP address

Set the N/W numbers, PLC numbers, types, etc. of the GOTs of the server function to be monitored by the

GOT of the client function.

Register the network No. of the corresponding GOT.

Register the PLC No. (station number) of the corresponding GOT.

Fixed to GOT.

Register the IP address of the corresponding GOT.

Port No. Fixed to 5011.

Communication Fixed to UDP.

Used to confirm the settings and close the dialog box.

Cancel

Add

Delete

Delete All

Copy

Used to cancel the settings and close the dialog box.

Used to add a new GOT of the server function.

Click this switch to add the GOT of the server function, and make settings.

After selecting the settings, click this switch to delete the settings.

Used to delete all settings.

After selecting the settings, click this switch to copy the settings.

5 - 12 5 - 12

5.4 Examples of Use

The following gives the examples of using the sever and client functions.

Making access to the PLC from the personal computer via the GOT

The device values of EG0 to EG5 of the GOT 1) (server function) are displayed on MX Component.

MX Component

EG devices (EG0 to EG5) of GOT 1) are monitored.

EG0:150 EG1:480

EG2:230 EG3:370

EG4: 80 EG5: 25

Device batch-read function is issued to GOT to monitor EG0 to EG5 devices of GOT.

Ethernet

GOT utility menu

GOT NET No.

GOT PC No.

GOT IP address

: 1

: 2

: 10.97.14.2

GOT 1)

PLC devices (D10 to D15) are monitored.

D10:150 D11:480

D12:230 D13:370

D14: 80 D15: 25

GT Designer2 Gateway server setting

EG device

EG0

Device

0-FF D10

Points

6

Bus connection

RS-422 communication

RS-232C communication

PLC device values

D10:150 D11:480

D12:230 D13:370

D14: 80 D15: 25

PLC

(1) GOT 1) setting example

(a) Server setting

EG Device Device Type

(b) Numerical display function

Item

Device D10 to D15

Network Host

Description

(2) Personal computer setting

Set the personal computer in the environment where Ethernet can be used.

Points

5 - 13 5 - 13

Displaying on the client GOT the alarms that occurred on multiple PLCs

The device values of the PLC 2) and PLC 3) are transferred to the internal devices (GD100 to

GD147) of the GOT 1)

The GOT 1) monitors its own internal devices, and if an alarm occurs on the PLC 2) or PLC 3), displays the occurrence information.

PLC 1)

GOT utility menu

GOT NET No.

:1

GOT PC No.

IP address

:1

: 10.97.14.1

GOT 1)

GT Designer2 client setting

NET No. PLC No. IP Address

1

1

2

3

10.97.14.2

10.97.14.3

Transferred by script 1)

(5 second sampling)

GOT internal devices

Transferred by script 2)

GD100 to 131

(5 second sampling)

GD132 to 147

Ethernet

GOT utility menu

GOT NET No.

: 1

GOT PC No.

IP address

: 2

: 10.97.14.2

GOT 2)

GOT utility menu

GOT NET No.

: 1

GOT PC No.

IP address

: 3

: 10.97.14.3

GT Designer2 server setting

EG device Device Points

EG0 0-FF IB200 512

GOT 3)

GT Designer2 server setting

EG device Device Points

EG0 0-FF ..300

256

5 - 14

PLC 2)

PLC 3)

(1) GOT 1) setting example

(a) Client setting

NET No PLC No IP Address

1 2 10.97.14.2

1 3 10.97.14.3

(b) Alarm list display function (for GOT 2) alarm display)

Item Description

Number of device points 512 points (consecutive)

Device GD100.b0

(c) Alarm list display function (for GOT 3) alarm display)

Item Description

Number of device points 256 points (consecutive)

Device GD132.b0

Preset the comments that will be displayed by the alarm list display functions.

5 - 14

(d) Script function (for GOT 2) alarm display)

Item

Script 1)

Description

Trigger type

Data format

Script description

Sampling, 5 sec

Unsigned BIN 16-bit bmov([1-2:w:EG0],[w:GD100],32);

//Transfers the data of 32 points, starting from EG0, of GOT 2) to GD100 and later of GOT 1).

(e) Script function (for GOT 3) alarm display)

Item

Script 2)

Description

Trigger type

Data format

Script description

Sampling, 5 sec

Unsigned BIN 16-bit bmov([1-3:w:EG0],[w:GD132],16);

//Transfers the data of 16 points, starting from EG0, of GOT 3) to GD132 and later of GOT 1).

(2) GOT 2) setting example

(a) Server setting

EG Device

EG0

Device

0-FF IB200 Bit

Type

512

Points

(3) GOT 3) setting example

(a) Server setting

EG Device

Point

EG0

Device

0-FF ..300 Bit

Type

256

Points

About the trigger type

When using the script function, do not set the trigger type as [Ordinary] or

[Sampling, within 2 seconds].

Doing so may affect the other monitor operations.

5 - 15 5 - 15

Monitoring and controlling the production conditions of multiple PLCs with the server

GOT

The device values of the PLC 2) and PLC 3) are transferred to the EG devices of the GOT 1)

(devices of the PLC 1)).

When values are written to the PLC 1), the EG devices of the GOT 1) (internal devices (GB100,

GB101) of the GOT 1)) turn ON. (Check completion of write using the lamp display function or like.)

The GOT 1) monitors the devices of the PLC 1) to check the production conditions of the PLC 2) and

PLC 3).

GOT 2)

When the bit device that indicates production completion turns ON, HR200 value (233)

is transferred to EG2 by script 1).

GOT utility menu

GOT NET No.

: 1

GOT PC No.

IP address

: 2

: 10.97.14.2

GT Designer2 client setting

N/W No. PLC No. IP Address

1 1 10.97.14.1

PLC 1) devices

D100

D101

233

523

PLC 1)

EG0.b0/EG1.b1 turn ON at completion of write.

EG0.b0

EG0.b1

EG2

EG3

OFF ON

OFF ON

233

523

GOT 1)

GOT internal devices

GB128 OFF ON

GB129 OFF ON

GOT utility menu

GOT NET No.

GOT PC No.

IP address

EG2

: 1

: 1

: 10.97.14.1

GT Designer2 server setting

EG device Device

Points

EG0

0-FF GB128

32

0-FF D100 2

GOT 3)

Ethernet

When the bit device that indicates production completion turns ON, W200 value (523) is transferred to EG3 by script 2).

GOT utility menu

GOT NET No.

: 1

GOT PC No.

IP address

: 3

: 10.97.14.3

GT Designer2 client setting

N/W No. PLC No. IP Address

1 1 10.97.14.1

PLC 2)

Bit device that indicates

Production completion:

OFF ON

PLC 2) device

HR200 233

PLC 3)

Bit device that indicates

Production completion:

OFF ON

PLC 3) device

W200 523

5 - 16 5 - 16

(1) GOT 1) setting example

(a) Server setting

EG0

EG2

EG Device Device

0-FF GB128

0-FF D100

(b) Numerical display function

Item

Device D100 to D101

Network Host

Bit

Word

Type

Description

(c) Lamp display function (set two)

Item

Device GB100 to GB101

Network Host

Description

32

2

Points

(2) GOT 2) setting example

(a) Client setting

NET No PLC No

1 1

(b) Script function

Item

Script 1)

IP Address

10.97.14.1

Description

Trigger type

Data format

Script description

While ON, bit device that indicates production completion

Unsigned BIN 16-bit

[1-1:w:EG2]=[w:HR200]; //Writes the production count to the PLC 1). set ([1-1:b:EG0.00]); //Turns ON the write completion signal.

(3) GOT 3) setting example

(a) Client setting

NET No PLC No

1 1

(b) Script function

Item

Script 2)

IP Address

10.97.14.1

Description

Trigger type

Data format

Script description

While ON, bit device that indicates production completion

Unsigned BIN 16-bit

[1-1:w:EG3]=[w:W200]; //Writes the production count to the

PLC 1. set ([1-1:b:EG0.01]); //Turns ON the write completion signal.

5 - 17 5 - 17

5.5 Precautions

This section provides the precautions for using the server and client functions.

Precautions for assigning the devices in the gateway setting

(1) The gateway devices are set as at least two points, and set on a two point basis thereafter.

(2) When a bit device is assigned, 32 points are set, starting from the set device.

(3) When a device was not assigned, the unassigned area (empty area) is on a word basis.

(4) The network number and PLC station number must be set to assign the MELSEC-A/QnA/Q series PLC CPU devices.

(5) The CPU number must be set to assign the CPU of the multiple PLC system.

(6) If station No. is changed while monitoring the gateway device to which PLC CPU device has been assigned,the monitored device is irrelevant to the station No. change.

Example) When station No. is changed on the GOT (server)

Use the script function to read EGO to the GOT internal device.

GD100(D100)

250

GOT internal devices

GD100:250

GOT(Client function)

Gateway device

EG0

Assignment definition

EG0=D100

Ethernet

Station No. is changed

Station number switching device

D50 00FF 0101

D100

200

Monitoring D100 in the numeric display

GOT(Server function)

D100:250

Station No.0

(00FF)

Monitoring

Station No.1

D100:100

D100:200

Station

No.3

Station No.1

(0101)

D100:150

Station

No.2

If station No. is changed on the GOT (server), the station No. change is irrelevant to the

GOT (client) that monitors D100 assigned to the gateway device.

As D100 has not been assigned to the gateway device on the GOT (server), station No. change is executed.

5 - 18 5 - 18

Precautions for setting the script function

(1) When setting the script function, do not set the trigger type to [Ordinary] or [Sampling, within 2 seconds].

Doing so may affect the other monitor operations.

(2) The script function cannot be used to monitor the gateway devices of the GOT itself.

When monitoring the PLC devices assigned to the gateway devices, monitor the PLC devices directly.

Precautions for using GT Simulator for debugging

(1) GT Simulator cannot debug the gateway functions.

An error will occur if the gateway device is monitored or data is written to the gateway device.

Precautions for monitoring

(1) If the GOT monitors devices by transient communication via the network, the monitor speed will decrease.

To increase the monitor speed, use link devices.

(2) If the gateway device of the GOT of the server function is monitored in a status where the server and client functions cannot be used , an error occurs and the script stops.

While power is off, when the ROM_BIOS version of the GOT is incompatible, or when the memory board is not fitted, for example.

(3) The gateway device, to which the PLC device has not been assigned, is monitored as 0 (OFF for bit).

When write is executed, the written value is invalid.

(4) If the screen save of the GOT is canceled (by a screen touch or the human sensor) during execution of the script that uses the gateway devices, it may take some time to cancel.

When the execution of automatic screen save has been specified, it may take more time than the specified.

(For example, when the script processing time is 2 seconds, the screen save is canceled in a maximum of 2 seconds after the screen is touched.)

5 - 19 5 - 19

5.6 For Efficient Use

This section explains the points for efficient use of the server and client functions.

Script function setting

When the gateway devices are used directly to execute a program, the number of times to access the other GOT increases, slowing the processing.

By performing batch read from the GOT internal devices and performing batch write after execution of the processing as shown in the following (1), the number of access times can be decreased, improving the processing speed.

(1) When performing batch read from GOT internal devices (GD) and performing batch write after processing

Access to the other station GOT occurs twice (1), 3)).

When one time of access requires 50ms, the necessary processing time is about 100ms.

Script description example

1) bmov([1-2:w:EG0], [w:GD100],10);

1)

Server

EG0 to EG9

3)

Client

GD100 to GD109

2) Processing 2)

[w:D200]=[w:GD100];

[w:D201]=[w:GD101];

[w:D202]=[w:GD102];

[w:D203]=[w:GD103];

[w:D204]=[w:GD104];

[w:GD105]=128;

[w:GD106]=[w:D106];

[w:D205]=[w:GD107];

[w:D206]=[w:GD108];

[w:GD109]=5433;

3) bmov([w:GD100], [1-2:w:EG0],10);

(2) When using gateway devices directly

Access to the other station GOT occurs 10 times (1) to 10)).

When one time of access requires 50ms, the necessary processing time is about 500ms.

Script description example

1),2),3) 8),9),10)

1) [w:D200]=[1-2:w:EG0];

Server

EG0 to EG9

Client

D106

D200 to D206

2) [w:D201]=[1-2:w:EG1];

3) [w:D202]=[1-2:w:EG2];

4) [w:D203]=[1-2:w:EG3];

5) [w:D204]=[1-2:w:EG4];

6) [1-2:w:EG5]=128;

7) [1-2:w:EG6]=[w:D106];

8) [w:D205]=[1-2:w:EG7];

9) [w:D206]=[1-2:w:EG8];

10) [1-2:w:EG9]=5433;

Point

About the written values

In the above (1), the gateway devices are batch-accessed when the script execution condition is established. Therefore, the gateway device values available when the condition is established can be processed as the written values.

In the above (2), the gateway devices are accessed one by one after the script execution condition is established. Therefore, the written values may differ from the gateway device values available when the condition is established.

5 - 20 5 - 20

Gateway device setting

When assigning the PLC devices to the gateway devices, set the same type of devices of the same

PLC together where possible.

By setting the same devices of the same PLC together as in the following (1), the number of access times can be reduced, improving the processing speed.

(1) Devices of host, other station and other PLC are set together

When the GOT of the client function accesses the host devices of the GOT of the server function, access can be made with the program that reads 50 points starting from EG0 (1)).

1) bmov([W:GD100], [1-2:w:EG0],50);

(2) Devices of host, other station and other PLC are set not together

When the GOT of the client function accesses the host devices of the GOT of the server function, access requires the program that reads 40 points starting from EG0 (1)) and the program that reads 10 points starting from EG130 (2)).

1) bmov([W:GD100], [1-2:w:EG0], 40);

2) bmov([w:GD140], [1-2:w:EG130], 10);

To further increase efficiency

By reserving together in advance the PLC devices to be used for the server and client functions in the system design stage as shown in the following (a), the number of times for the GOT of the server function to access the PLC can be decreased, improving the processing speed.

(a) When PLC devices are assigned together

When 100 points of devices are accessed, access to the PLC occurs only once.

(b) When PLC devices are not assigned together

When 100 points of devices are accessed, access to the PLC must be made five times.

5 - 21 5 - 21

Performance of server and client functions (reference values)

The following table indicates the performance of the server and client functions (reference values) when and on the previous pages are used.

The reference values of the performance assume the following conditions.

• System consists of one GOT of server function and one GOT of client function

• GOT of server function : Numerical input setting of 64 points

• GOT of client function : Numerical input setting of 64 points

• Number of assigned device points : Word devices of 10 points

Item

1

2

3

4 bmov is used

(Batch access)

Device are assigned together

Response speed for bus connection

Approx. 140ms

Approx. 700ms

Approx. 700ms

Approx. 700ms

Response speed for

CPU direct connection

Approx. 260ms

Approx. 1300ms

Approx. 1300ms

Approx. 1300ms

When there are multiple clients, the response speed is the "above response speed number of clients".

(When there are five clients in above "1", the response speed for bus connection is approximately

700ms.)

5 - 22 5 - 22

6. FTP SERVER FUNCTION

This chapter descries the FTP server function.

6.1 Specifications

6.1.1 Specifications

The specifications of the FTP server function are indicated below.

Item Specifications

FTP server function setting

User name

Password

Port number

Whether the function will be used or not can be set (default: Not used)

1 to 12 alphanumeric characters (case sensitivity, anonymous must not be used) (default: GOT900)

1 to 8 alphanumeric characters (case sensitivity) (default: GOT900)

20, 21

Number of clients that can connect simultaneously

Time set to watching timer of command input

Before login

After login

2

1

1 unit minute

1 to 60 minutes (default: 15 minutes)

File size that can be read

File name

Access mode

FTP client

Memory space used by GOT (bytes)

Setting Method

GT Designer2

GT Designer2

GT Designer2

Fixed

Fixed

Fixed

GT Designer2

Unlimited (max. read size depends on PC card capacity.)

Within 8 characters of only alphanumeric characters

(longer file name not acceptable)

Normal: Reference mode (write to PC card disabled)

Write is enabled after issue of dedicated command

• General-purpose FTP client tool can be used.

3

• Access can be made by FTP command from Windows R prompt or command prompt.

MS-DOS

12 + 2 total number of login name and password characters GT Designer2

1 The line is cut off if a correct password and login name are not entered within 1 minute after line connection with the GOT.

2 The GOT cuts off the line if a command is not input from the FTP client within the time set to the watching timer of command input.

3 Microsoft

R

Internet Explorer and Netscape Communicator are unusable.

The following table indicates the FTP client tools that have been confirmed to operate properly by

Mitsubishi Electric.

FFFTP (freeware)

NextFTP Ver. 2 (shareware)

Name Compatible OS

Microsoft R

Microsoft R

Microsoft R

Microsoft R

Windows R

Windows R

98 operating system,

Millennium Edition operating system,

WindowsNT

Windows R

R Workstation4.0 operating system,

2000 Professional operating system

6

6 - 1 6 - 1

6

6.1.2 File accessible range

The FTP server function can access on the PC card of the GOT within the network to which the FTP client is connected. (Multiple clients cannot access the PC card of the GOT simultaneously.)

When using a relay device such as a router, consult the network manager.

Personal computer

(FTP client)

Ethernet

GOT

(FTP server function)

Router

PLC

GOT

(FTP server function)

PLC

Simple judgment of whether file access is possible or not

Simple judgment of whether file access is possible or not can be made by issuing the ping command to the GOT.

Example of issuing the ping command (Windows R

IP address of GOT: 10.97.14.10

MS-DOS prompt)

• When file can be read

C:\ping 10.97.14.10

pinging 10.97.14.10 with 32 byte of data:

reply from 10.97.14.10: bytes=32 time<10ms ttl=128

reply from 10.97.14.10: bytes=32 time<10ms ttl=128

reply from 10.97.14.10: bytes=32 time<10ms ttl=128

C:\

• When file cannot be read

C:\ping 10.97.14.10

pinging 10.97.14.10 with 32 byte of data:

request timed out.

request timed out.

request timed out.

C:\

6 - 2 6 - 2

Operation procedure

When either of the following operations is performed, the FTP dialog box is displayed.

• Choose the [Common] [Gateway] [FTP] menu.

• Double-click (FTP) in the workspace.

FTP dialog box

Item

Use FTP Server

Login Name

Password

Watching timer of command input

Description

Check here when using the FTP server function.

Set the login name used when the FTP client connects to the GOT.

You can set only one login name up to 12 characters.

Only alphanumeric characters (a to z, A to Z, 0 to 9) can be used.

Set the password used when the FTP client connects to the GOT.

You can set only one password up to 8 characters.

Only alphanumeric characters (a to z, A to Z, 0 to 9) can be used.

Set when the line with the GOT will be cut off if no command is entered from the FTP client.

You can set this time between 1 and 60 minutes in 1 minute increments.

Normally use it as default (15 minutes).

6 - 3 6 - 3

6.3 Operation on the FTP Client Side

6.3.1 Input command at FTP client

Command

Name append ascii binary bye cd mkdir mls mput open put pwd quit quote close delete dir get ls mdelete mdir mget user

General commands

The following table indicates the correspondences between the commands that can be used with a general FTP client tool and the FTP server function of the GOT.

The usable commands change depending on the FTP client tool used.

For details, refer to the manual of the used FTP client tool.

: Usable : Unusable : Setting invalid (command does not result in error)

Function

Additionally writes a file to the GOT (PC card).

Changes the file transfer mode to the ascii mode.

Changes the file transfer mode to the binary mode.

Exits the FTP client tool.

Changes the current directory of the GOT (PC card).

Reference

Mode

1

Write

Mode

1

Cuts off the line with the GOT.

Deletes a file in the GOT (PC card).

Reads the file information in the GOT (PC card).

Reads a file from the GOT (PC card).

Displays file names in the GOT (PC card).

Deletes multiple files specified using a wild card.

Reads the file information in the GOT (PC card) to the specified file.

Reads multiple files.

Creates a directory in the GOT (PC card).

Reads the file names in the GOT (PC card) to the specified file.

Writes the specified multiple files using a wild card to the GOT.

Connects the line with the GOT.

Write a file to the GOT (PC card).

Creates the current directory of the GOT.

Cuts off the line with the GOT to exit the FTP client tool.

Used when the GOT-dedicated command is used. (Example: quote gtwr)

Enters the user name and password used to log in to the GOT.

1 Since this command is fixed to "No file conversion (binary)" in the FTP server function, it is invalid if set.

2 The rename and rmdir commands are unusable.

GOT-dedicated commands

When the line with the GOT is connected, the FTP client is in the "reference mode" in which only file read is enabled.

Before executing file write, delete or directory creation, change it to the "write mode".

To select the reference mode or write mode, issue a mode change command.

Command

Name quote gtwr quote gtrd quote help

Function

: Usable : Setting invalid (command does not result in error)

Reference

Mode

Write

Mode

Changes the FTP server function mode of the GOT to the write mode.

Changes the FTP server function mode of the GOT to the reference mode.

Displays the general-purpose actual commands of the FTP protocol supported by the

FTP server function of the GOT.

6 - 4 6 - 4

6.3.2 File specifying method

There are two file specifying methods: one is to specify one file directly and the other is to specify multiple files that meet the condition.

Specifying the file name to read

Specify the file name, period and extension of the file to be specified.

File name + . + Extension

Represents the file type.

Separates the file name and extension.

The file name to be read.

The FTP server function mainly uses files having the following extensions. csv bmp jpg

Extension Application on GOT

Recipe file (recipe function), alarm history file (alarm history display function)

Monitor screen image (hardcopy function)

Specifying the files that meet the condition (wild card)

When specifying multiple files, you can use " " or "?" as a wild card.

(Example)

When specifying only JPEG files.......................................................

.jpg

When specifying the CSV files that begin with Main ......................... Main .csv

When specifying the files whose extensions begin with b.................

.b??

Point

(1) Precautions for specifying the file name

For the FTP server function, do not put a space into a file name or extension.

The file that has a space cannot be read or written as a correct file name.

(2) About data in PC card

The PC card of the GOT contains the files that can cause the operation fault of the GOT if they are deleted.

To prevent the operation fault of the GOT, do not access the folders, which store the above files, from the FTP client.

<Folder structure in the PC card>

Can be used with the FTP server function.

Cannot be used with the FTP server function.

Do not delete files.

ALARMHST

RECIPE

REPORT

For alarm history file storage

For recipe file storage

For report file storage

SNAPSHOT For screen image file storage

SNAPHDCP.BMP Work file for printer printout

USERDATA For monitor screen data storage (for screen copy)

OS For OS storage (for OS copy)

SYSTEMD

SPCDATA

For OS system screen storage (for OS copy)

For special function module monitor data storage

(for screen copy)

For motion monitor data storage (for screen copy)

For servo amplifier monitor data storage

(for screen copy)

* In addition to the above, do not delete the file whose extension is "ini"

(GOT information file).

6 - 5 6 - 5

6.3.3 Checking the line connection condition

The connection condition of the line between the GOT and FTP client is stored into the GOT special register GS200.b2 (bit position: 2).

By referring to this bit on the GOT, you can check whether the line is connecting or not.

Device Name ON OFF

Refer to the following manual for details of the GOT special registers.

GT Designer2 Version1 Reference Manual

Example of using GS200.b2

(1) Using the above device with the lamp display function, you can create a line condition confirmation lamp.

GS200.b2 : OFF GS200.b2 : ON

Line Connecting

(2) By setting the above device to the operation condition as a trigger using the touch key function or numerical input function, you can restrict operation (input) while the line is connecting.

GS200.b2 : OFF GS200.b2 : ON

Manufacturing line

A

B

C

Manufacturing line

Operation is

A is connecting.

C

Using the touch key function or numerical input function, make setting to enable input only when the device (GS200.b2) is OFF.

6 - 6 6 - 6

6.3.4 Line cutoff

There are two line cutoff methods: automatic cutoff and manual cutoff.

Automatic cutoff

The GOT cuts off the line automatically if no command is entered from the FTP client within the time set to the watching timer of command input in the FTP server setting.

The watching timer of command input is always set.

Refer to the following for the setting of the watching timer of command input.

Section 6.2 Setting Method

Manual cutoff (Forcibly cutting off the line)

Using the GOT special register GS400.b2 (bit position: 2), you can cut off the line forcibly.

When you want to cut off the line, turn "ON" GS400.b2 (bit position: 2).

Refer to the following manual for details of the GOT special registers.

GT Designer2 Version1 Reference Manual

Point

Precautions for use of GS400.b2

After confirming that the line has been cut off, always turn "OFF" GS400.b2.

Remark

About line cutoff

Since the GOT cannot detect the fault status of the FTP client, it does not cut off the line immediately if the FTP client could not exited properly (e.g. the personal computer was powered off while the line is connecting).

However, as the watching timer of command input has been set, the line is cut off automatically in the predetermined period of time.

6 - 7 6 - 7

6.4 Example of Use

The example of using the FTP server function is described below.

In this example of use, the Windows

R

MS-DOS prompt is used to access the GOT and FTP client.

When performing operation using the commercially available FTP client tool or like, refer to the manual of the FTP client tool used.

General procedure

Start

Connect the line of the GOT and FTP client.

Refer to

Read the file of the GOT (PC card).

Write a file to the GOT (PC card).

Refer to

Refer to

Refer to Operate the directory of the GOT (PC card).

Cut off the line of the GOT and FTP client.

Refer to

End

Point

Precautions for file write

When writing a file to the GOT (PC card) or operating the directory, turn ON the memory card access switch of the GOT to make the PC card write-enabled.

System configuration

FTP client

File read File write

Directory operation

FTP server

(IP address:

10.97.14.200)

PC card

6 - 8 6 - 8

Connecting the line of the GOT and FTP client.

Connect the GOT and FTP client in the following procedure.

Start of the FTP client .............................................................. ftp

Connection with the GOT ........................................................ open IP address of GOT

Input of the login name ............................................................ login name

Input of the password .............................................................. password

Login image (when the line was connected properly)

C:\>ftp ftp>open 10.97.14.200 connected to 10.97.14.200

220 GOT900 FTP server ready. user:GOT900

331 Password required.

Password:****

230 User logged in. ftp>

Login image (when the other personal computer has already connected to the GOT)

C:\>ftp ftp>open 10.97.14.200 connected to 10.97.14.200

220 GOT900 FTP server ready. user:GOT900

530 Not logged in. ftp>

Login image (when the password is incorrect)

C:\>ftp ftp>open 10.97.14.200 connected to 10.97.14.200

220 GOT900 FTP server ready. user:GOT900

331 Password required.

Password:****

530 Not logged in. ftp>

6 - 9 6 - 9

Reading the file of the GOT (PC card).

Read the file in the following procedure.

Notification of no file conversion .............................................. binary

Read of file............................................................................... get file name

Read image ftp>binary

200 Command Okey. ftp>get SNAP0001.BMP

200 PORT command successful

150 Opening connection.

226 Closing data connection.

250 bytes received in 0.02 seconds ftp>

Writing a file to the GOT (PC card).

Write a file in the following procedure.

Notification of no file conversion .............................................. binary

Selection of the write mode ..................................................... quote gtwr

Display of the file name to check for the same file name ........ ls or dir

Deletion made if the same file exists ....................................... delete file name

File write................................................................................... put file name

Write image ftp>binary

200 Command Okey. ftp>quote gtwr

200 command successful. ftp>ls

200 PORT command successful

SNAP0001.BMP

SNAP0002.BMP

226 Closing data connection. ftp>delete SNAP.0001.BMP

200 Command Okey. ftp>put SNAP0001.BMP

200 PORT command successful

150 Opening connection.

226 Closing data connection.

250 bytes sent in 0.01 seconds. ftp>

6 - 10 6 - 10

Operating the directory of the GOT (PC card).

Create and change the directory in the following procedure.

Current directory display .......................................................... pwd

Selection of the write mode ..................................................... quote gtwr

Directory creation..................................................................... mkdir directory name

Current directory change ......................................................... cd directory name

Directory operation image ftp>pwd

257 “A:\snapshot” is current directory. ftp> quote gtwr

200 command successful. ftp>mkdir bmpdata

275 MKD command successful. ftp>cd bmpdata

250 CWD command successful. ftp>pwd

257 “A:\snapshot\bmpdata” is current directory ftp>cd ..

250 CWD command successful. ftp>pwd

257 “A:\snapshot” is current directory. ftp>

Cutting off the line of the GOT and FTP client.

Cut off the GOT and FTP client in the following procedure.

Quit command ......................................................................... quit

Logout (line cutoff) image ftp>quit

221 User logged out. Good-Bye.

C:\>

Error display

An error that occurred in the FTP server function is displayed on the FTP client.

Refer to the following for the displayed error messages.

Section 8.2 Error Messages

If an attempt was made to read an non-existing file snap0010.bmp ftp>get snap0010.bmp

200 PORT command successful.

550 snap0010.bmp

No such file or directory.

C:\>

6 - 11 6 - 11

6.5 Precautions

The following are the precautions for using the FTP server function.

Precautions for system design using the FTP server function

(1) When writing a recipe file from the FTP client to the GOT, set the format of the recipe file as set for the recipe function of the GOT.

When writing a recipe file from a remote location, confirm the operation with the field site personnel before executing write.

(2) Before using the FTP client tool, refer to the manual of the FTP client tool, confirm its functions and operation methods, and make tests before starting operation.

Depending on the FTP client tool used, the GOT (FTP server) may not support some operations.

Also, depending on the FTP client tool used, the FTP server function may not be usable since the GOT cannot support the extended command (quote) and issue the GOT-dedicated command.

(3) If a number of files are read at once under one command (e.g. get or put is executed by specifying a wild card), processing may be delayed by network congestion. If processing is slow, issue commands separately to perform the processing separately.

Precautions for file read

(1) The GOT cuts off the line if no command is input from the FTP client for longer than the time set to the watching timer of command input.

(2) The line is cut off if any of the GOT IP address, router address and subnet mask is changed while the line of the GOT and FTP client is connecting.

(3) The line is kept connected if the GOT is put offline (e.g. the monitor screen data is downloaded) while the line of the GOT and FTP client is connecting.

(4) When you want to change (rewrite) the contents of the recipe file, make the recipe inactive.

If the recipe file in the PC card is deleted during recipe processing, the function will not operate properly.

If the recipe file is deleted other than during recipe processing, an error (system alarm: recipe file error) will occur in the next recipe operation.

(

Section 6.3.3 Checking the line connection condition)

(5) Do not delete the printer printout temporary file.

If the printer printout temporary file is deleted, the function will not operate properly.

(6) If the FTP client has become faulty (personal computer), wait until the time set to the watching timer of command input elapses or turn ON the forced logout signal "GS400.b2" to cut off the line, and log in again.

The line connecting condition can be checked using GS200.b2 (bit position: 2).

(7) Do not power off the GOT while access is being made from the FTP client to the file in the PC card of the GOT.

Doing so may damage the data in the PC card.

6 - 12 6 - 12

(8) If you reset the GOT or switch power off while the line of the GOT and FTP client is connecting, the operation of the FTP client depends on the specifications of the FTP client tool used.

Use the FTP client tool that supports the detection of an FTP server fault or that can be exited properly.

(9) Access to a file cannot be made if the memory card access switch of the GOT is OFF.

(10) Write processing (put) cannot be performed if the write protect switch of the GOT is ON.

(11) The GOT does not use any file whose file name is 8 or more characters long.

Hence, if the PC card contains a file whose file name is 9 or more characters long, it cannot be accessed from the FTP client.

Set the file name of a file to be accessed to within 8 characters (except a period and extension).

(12) Depending on the used FTP client tool, the time stamp may differ from that of the file in the PC card of the GOT.

If the time stamp differs, check the setting of the FTP client tool.

Precautions for FTP login

(1) If you have forgotten the password for FTP login, connection to the GOT cannot be made. You can confirm the set password on GT Designer2.

(2) You cannot log in to the GOT from multiple FTP clients simultaneously.

6 - 13 6 - 13

7. MAIL SEND FUNCTION

This chapter describes the mail send function.

Point

(1) About the mail software

The GOT (send source) does not require mail software.

(2) About the system when using the mail send function

The SMTP (mail) server must be installed in the intranet to use the mail send function.

7.1 Specifications

7.1.1 Specifications

7

The specifications of the mail send function are given below.

Item Specifications Setting Method

SMTP server

IP address setting (1 server only)

Port 25

Server certification Disabled

To

1 to 32 (max. 64 characters for 1 address: Alphanumeric characters only)

Fixed

Fixed

Send destination address

0 to 32 (max. 64 characters for 1 address: Alphanumeric characters only)

GT Designer2

Cc

Bcc

Subject

Text data size

Max. 128 characters (alphanumeric characters only)

Either of the following two different comments can be sent.

Alarm comment: Max. 512 characters (alphanumeric characters)

Detailed comment: Max. 512 characters

(alphanumeric characters)

GT Designer2

Attached file Disabled

Encoding No

Compression No

Memory space used by GOT (bytes)

20 + 4 (number of destinations + 2) + 2 (total number of destination, subject and sender characters)

GT Designer2

The following table indicates the mail software programs that have been confirmed to operate properly by Mitsubishi Electric.

Name

Netscape Communicator 4.7 or later

AL-Mail32 Version1.12 (shareware)

Netscape

Maker Compatible OS

Microsoft

R

Microsoft

R

Microsoft

R

R

Windows

R

Windows

R

95 operating system,

98 operating system,

Windows

R

Millennium Edition operating system,

WindowsNT

R

Workstation4.0 operating system,

2000 Professional operating system

7 - 1 7 - 1

7.1.2 Mail send enabled range

Since the IP address is used to specify the SMTP server in the mail send function of the GOT, a dial-up router cannot be utilized to send mail. (The SMTP server in the Internet service provider cannot be used.)

Install the SMTP (mail) sever in the intranet.

SMTP (mail) server

Internet

Personal computer Cellular phone

Ethernet

Mail is sent

Dial up router

Internet

GOT

Personal computer Cellular phone

PLC

7

7 - 2 7 - 2

Only one mail send setting can be made for one GOT.

Operation procedure

When either of the following operations is performed, the Mail dialog box is displayed.

• Choose the [Common] [Gateway] [Mail] menu.

• Double-click (Mail) in the workspace.

Mail dialog box

Item

Available E-Mail

SMTP Server

FROM

1

SUBJECT

2

TO

3

CC

BCC

Description

Check here when using the mail send function.

Set the IP address of the SMTP server used.

Enter the address of the mail send source. (Alphanumeric characters only)

Enter the title of the mail. (Alphanumeric characters only)

Enter the address of the mail send destination. (Alphanumeric characters only)

Enter the address of the mail send destination (copy). (Alphanumeric characters only, mail can be sent if this address is not entered.)

Enter the address of the mail send destination (hidden copy). (Alphanumeric characters only, mail can be sent if this address is not entered.)

1 Since the GOT does not have the mail receive function, set the reply destination in "FROM" when the mail receiver from the GOT will make a reply.

When there is no specific reply destination, set the address as set in "TO".

2 When mail is to be received from multiple GOTs, the GOTs that have sent mail can be identified if you enter different subjects into the GOTs.

3 When setting multiple send destination addresses, separate them with a space or comma.

7 - 3 7 - 3

When e-mail is sent from GOT to the target device, the reception header part shown at the destination displays a message that shows that the e-mail is from GOT.

Example of display in the reception header part at the destination

From:**********************

To:************************

Cc:************************

Subject:GOT 01

:

X-Mailer:GOT

Point

About mail send

(1) The format and contents of the display of e-mail sent vary depending on the mailer specifications used at the destination.

(2) When e-mail is sent to a mobile phone, the display may vary depending on the specifications (screen size) of the mobile phone.

(3) GOT can send up to 16 e-mail at one time. If alarms occur 17 times or more, the 17th e-mail and subsequent are not sent.

When sending e-mail using the alarm history display function

If an alarm occurs in GOT, the time and information of the alarm are sent to the destination by e-mail.

Moreover, if the alarm recovers, the time and information of the alarm recovery are sent to the destination by e-mail.

Refer to the following manual for the way to set the alarm history display function.

GT Designer2 Version1 Reference Manual

(1) Example of display at the destination (when an alarm occurred)

(a)

(b)

[Alarm history occurred information]

[Occur Time]

2002/11/28 09:48:15

[Occur Information]

Line A supply conveyor stopped.

[detailed Information]

Alarm history: A-line supply converter stopped.

Check the power source.

(a) The comment entered in the alarm history display function is displayed.

(b) The content of detailed display entered in the alarm history display function is displayed.

"Detail Information" is not displayed if the detail display setting of the alarm history display function has not been made or has been made for the base or window screen.

("Alarm history: detail comment nothing" appears under "Detail Information ".)

To display "Detail Information ", make the detail display setting in the comment window.

7 - 4 7 - 4

(2) Example of display at destination (when an alarm recovered)

[Alarm history repaired information]

[repair Time]

2002/11/28 10:38:23

[repair Information]

Alarm "Line A supply conveyor stopped." recovered.

Alarmhistory:detail comment nothing

7 - 5 7 - 5

7.4 Examples of Use

Sending the definition of the alarm that occurred in the GOT to the production site and office by mail

If an alarm has occurred in the GOT, mail is sent to the personal computer 1) (production site

(operator)), cellular phone and personal computer 2) (office (manager)).

On the production site where the alarm was received, the system is repaired/recovered.

At the office, the manager can send mail to prompt the operator on the production site to report the current restoration condition.

Mail is sent

SMTP (mail) server

(10.97.14.12)

Internet

Mail is sent

Personal computer 2)

(Office (manager))

Internet

Mail is sent

Ethernet

Cellular phone

Mail is sent

Mail is returned*

Operator is asked to check restoration condition.

GOT

(10.97.14.1)

Personal computer 1)

(Production site (operator))

PLC

Since the GOT cannot receive mail, set FROM as the mail address of the personal computer or like on the production site.

This allows the mail to be returned from the office (manager) to the production site and the mail requesting confirmation of the restoration condition to be sent to the production site.

(1) GOT setting example

(a) Utility menu of GOT

Item

IP address

Send message wait

Send message time

Startup time

10.97.14.1

000 10ms

03 seconds

003 seconds

Description

7 - 6

Item Description

SMTP (mail) server

FROM

10.97.14.12

Mail address of personal computer 1)

TO

CC

Mail address of personal computer 1)

Mail address of personal computer 2)

Mail address of Cellular phone subject GOT01

7 - 6

(c) Alarm history display function (alarm history common setting)

Item

Monitor device

Send mail

Description

Mail send

Occurred/restored

Preset the comment to be displayed for the alarm history display function.

7 - 7 7 - 7

7.5 Precautions

The precautions for using the mail send function are described below.

(1) The languages that can be sent by mail is only English.

The other languages are sent as "?" by mail.

(2) The GOT refers to the PLC CPU clock every 60 minutes.

Note that if the time is changed on the PLC side, an error of up to 60 minutes will be produced.

(3) The mail send date/time is the time of the SMTP server at the time of send.

7 - 8 7 - 8

8. TROUBLESHOOTING

This chapter describes the troubleshooting of the gateway functions.

8.1 Troubleshooting Common to Gateway Functions

8

The following troubleshooting is common to the gateway functions.

Phenomenon

The GOT displays the "Check

Communication" message.

The gateway functions are not executed.

The ERR. LED is lit on the PLC.

1

Definition and Cause

The mounting position of the serial communication board is incorrect.

The version of the ROM_BIOS. OS installed in the GOT is incorrect.

The used A9GT-J71E71-T is not compatible with the gateway functions.

The used A9GT-J71E71-T is not compatible with the gateway functions.

Corrective Action

Mount the serial communication board on the

GOT.

( User's Manual of used GOT)

Match the versions of the OSs to be installed.

(All versions of the basic function OS, PLC communication driver and extended function OS should be Ver. 9.*.* or later.)

( GT Designer2 Version1 Reference

Manual)

Use the A9GT-J71E71-T (hardware version E

(June, 2002) or later) that is compatible with the gateway functions.

( Section 2.3)

Use the A9GT-J71E71-T (hardware version E

(June, 2002) or later) that is compatible with the gateway functions.

( Section 2.3)

The extended function OS of the gateway functions has not been installed in the GOT.

Install the extended function OS of the gateway functions into the GOT.

( GT Designer2 Version1 Reference

When all bits of

GS200 are OFF and no response is made to Ping

2, 3

The memory board has not been mounted.

(When A985GOT, A97

A956WGOT is used)

GOT, A960GOT or

The memory extension type (-M3 type) GOT is not used. (When A956GOT is used)

Manual)

Mount the memory board to the GOT.

Use the memory extension type (-M3 type) GOT.

The IP address has not been set to the GOT.

The mounting position of the bus connection board is incorrect.

Using the utility function of the GOT, check whether the IP address has not been set to the

GOT.

Mount the bus connection board on the

A9GT-J71E71-T.

(

Section 2.4)

When any of the

GS200 bits is

ON and response is made to Ping

2, 3

Refer to the troubleshooting of the function corresponding to the ON bit and take a corrective action.

(

Section 8.2)

1 "1401 : SP. UNIT DOWN" is displayed in the PLC diagnostics of GX Developer.

2 Refer to the following for details of the gateway common information (GS200).

Section 8.2 Gateway Information

3 Check whether response is made to Ping or not by issuing the Ping command to the GOT from the personal computer.

Example: ping "IP address of GOT" in Command Prompt

8 - 1 8 - 1

The error information of the gateway functions is stored into the GOT special registers (GS).

By monitoring the following GOT special registers, you can confirm the error information of the gateway functions.

Refer to the following manual for details of the GOT special registers.

GT Designer2 Version1 Reference Manual

Error information list of gateway functions

(1) GOT write information

Device Function Description

GS200

GS201

GS202

GS203

GS204

GS205

GS206 to 209

GS210

GS211

GS212

GS213

GS214

GS215

GS216

GS217 to GS219

GS220

GS221

GS222

GS223

GS224

GS225

GS226

Gateway common information Refer to (a) on the next page.

Error counter Stores the number of error occurrences.

Mail send function

Error code Stores the error code (refer to Section 8.4.1).

Stores the year (upper byte, 2 lower digits of year) and month (lower byte) of the error occurrence date and time in BCD code.

Occurrence date and time

Stores the day (upper byte) and hour (lower byte) of the error occurrence date and time in BCD code.

Stores the minute (upper byte) and second (lower byte) of the error occurrence date and time in BCD code.

Reserved

Error counter

Error code

Stores the number of error occurrences.

Stores the error code (refer to Section 8.2.1).

Stores the year (upper byte, 2 lower digits of year) and month (lower byte) of the error occurrence date and time in BCD code.

Occurrence date and time

Stores the day (upper byte) and hour (lower byte) of the error occurrence date and time in BCD code.

Server function

Request source

Stores the minute (upper byte) and second (lower byte) of the error occurrence date and time in BCD code.

Stores the lower part of the IP address of the GOT (client function) where the error occurred in BIN code.

Stores the upper part of the IP address of the GOT (client function) where the error occurred in BIN code.

Reserved

Error counter Stores the number of error occurrences.

Error code Stores the error code (refer to Section 8.2.1).

Stores the year (upper byte, 2 lower digits of year) and month (lower byte) of the error occurrence date and time in BCD code.

Occurrence date Stores the day (upper byte) and hour (lower byte) of the error occurrence date and time and time in BCD code.

Client function

Request source

Stores the minute (upper byte) and second (lower byte) of the error occurrence date and time in BCD code.

Stores the lower part of the IP address of the GOT (server function) where the error occurred in BIN code.

Stores the upper part of the IP address of the GOT (server function) where the error occurred in BIN code.

GS227 to GS229 Reserved

8

8 - 2 8 - 2

(2) GOT read information

Device

GS400

Function

Gateway common control Refer to (b) given below.

(a) Gateway common information (GS200) b15 b14 b13 to b12 b11 b10 to b5

Description b4 b3 b2 b1 b0 b0 b1 b2 b3

: ON while the mail send function is ready.

: ON while the FTP server function is ready.

: Turns ON when the FTP client logs in.

: ON while the server function is ready. b4 : ON while the client function is ready. b5 to b10 : Reserved b11 : Turns ON when an error occurs in the mail send function. b12 to b13 : Reserved b14 b15

: Turns ON when an error occurs in the server function.

: Turns ON when an error occurs in the client function.

(b) Gateway common control (GS400) b15 b14 b13 to b12 b11 b10 to b3 b2 b0 to b1 : Fixed at OFF. b2 : Turns ON to cause forced logout in the FTP server function. b3 to b10 : Fixed at OFF. b11 : Turns ON to clear the error of the mail send function

(GS200.b11, GS201 to GS206). b12 to b13 : Fixed at OFF. b14 : Turns ON to clear the error of the server function

(GS200.b14, GS210, GS211). b15 : Turns ON to clear the error of the client function

(GS200.b15, GS220, GS221). b1 to b0

8 - 3 8 - 3

8.3 Server and Client Functions

8.3.1 Error codes and error messages

GOT error code list

The following table lists the error codes that are stored into the GOT special registers GS211 (server function error code) and GS221 (client function error code).

Error Code

490

491

492

493

Point

Definition and Cause Corrective Action

An attempt was made to monitor the gateway device of the GOT itself using the script function.

1.Set the other GOT as the monitor destination in the script.

2. Do not use the script but directly monitor the PLC devices.

An attempt was made to access a non-existing Check the network number, PLC station number and Ethernet station. settings of the monitor destination.

A communication time error occurred.

A communication error occurred.

1. Increase the "send time-out" period in the utility menu of the

GOT.

2. Check the network. (Check firewall presence/absence, execute Ping, for example.)

1.Check for cable disconnection and check the module mounting status.

2. Check the network. (Check firewall presence/absence, execute Ping, for example.)

The error that will occur in the GOT of the server function is the error code 493 only.

(1) If error code 493 occurs in GOT of server function

This error may occur when networks coexist.

If no error has occurred on the target client side, it poses no specific problem since communication is restored to normal by the retry processing on the client side.

(2) System that uses a router

If the error code 493 occurred in the GOT of the server function, note that the IP address of the target client is the address of the router.

Ethernet

At 493 error, not the IP address of the client but the IP address of the router

(10.97.14.254) is stored into the GOT internal device.

IP : 10.97.15.254

Server

GOT IP address: 10.97.14.10

Router

IP : 10.97.15.254

8 - 4

Client

GOT IP address: 10.97.15.10

(3) If an error occurs in the GOT with client function.

If an error occurs in the GOT with client function, the script will stop.

Take the corrective action and then re-execute the script.

Refer to the following manual for details of “Script function”.

GT Designer2 Version1 Reference Manual

(4) If error code 492 occurs in GOT of client function

This error may occur when there are many clients that access the server.

To increase the "send time-out period", set the value of "already set send time-out period number of clients".

8 - 4

(5) If error code 15 (script was not terminated after elapse of script watching time) was stored into the script error data (GS16 to GS47) when script that used gateway devices was used

This error may occur when there are many clients that access the server.

To increase the script watching time (GS385), set the value of "already set script watching time number of clients".

Refer to the following manual for details of the script function.

GT Designer2 Version1 Reference Manual

MX Component error code list

The following table lists the error codes that may occur when access is made from MX Component to the GOT.

Error Code

0 0180840B

Definition and Cause

Time-out error

Time-out period elapsed but data could not be received.

The used A9GT-J71E71-T is not compatible with the gateway functions.

Corrective Action

1. Corrective action for MX Component

• Reexamine the time-out value in Properties.

• Make the communication setting again in the communication setting utility.

• Reexamine the PLC CPU, module setting, cable status and others.

• Exit from MX Component once and execute it again.

• Exit from the program and restart the DOS/V personal computer. ( MX Component Programming Manual)

2. Corrective action for GOT

• Check whether the server setting of GT Designer2 has been made or not. (

Section 5.3)

Use the A9GT-J71E71-T that is compatible with the gateway

( functions.

Section 2.3)

0 010F4030

0 010F4031

0 010F4B00

An unusable device or non-existing device has been assigned to the accessed gateway device.

In the server setting of GT Designer2, check whether device assignment is correct or the set device exists.

The PLC device outside the monitor range has In the server setting of GT Designer2, check whether the device been assigned to the accessed gateway device. within the monitor range has been assigned.

Communication time-out occurred.

Module or cable is not loaded properly.

1. Check for cable disconnection and check the communication board/communication module mounting status and PLC status.

2. This error may occur if the PLC load increases at other station access. At that time, move the other station data to the host

PLC and monitor them on the host.

3. If the sequence scan is long, insert the COM instruction.

4. Check the GOT error codes of the alarm list display function

(system alarm) and system information.

If an error has occurred, take the corresponding corrective action.

1

1 About the GOT error codes

Refer to the following manuals for details of the GOT error codes.

• A985GOT/A975GOT/A970GOT/A960GOT User's Manual

• A950GOT/A951GOT/A953GOT/A956GOT User's Manual

8 - 5 8 - 5

8.3.2 Troubleshooting

The following table indicates the troubleshooting for use of the server and client functions.

Phenomenon

Gateway device cannot be monitored.

Definition and Cause

A non-existing device is monitored in the server setting.

The IP address of the GOT to be monitored is wrong in the client setting.

Corrective Action

Check the PLC CPU device assigned to the gateway device.

Check the IP address of the GOT to be monitored.

An error occurs in the GOT with server function or client function.

The script function error occurs.

Confirm the GOT special register GS211 and GS221, and then

( take the corrective action.

Section 8.2.1 Error code/Error message)

Confirm the script function error and then take the corrective action. ( GT Designer2 Version1 Reference Manual)

8 - 6 8 - 6

8.4 FTP Server Function

8.4.1 Error codes and error messages

The error codes and error messages related to the FTP server function are displayed on the FTP client side.

The error displaying method changes depending on the used FTP client tool.

The following tables indicate the errors that the GOT sends to the FTP client.

125

150

200

214

220

221

226

230

250

Normal codes and messages

code message

Data Connection already open; transfer starting

Opening connection

Command okay.

Command successful.

PORT command successful.

The following commands are recognized.

Help end.

Syntax: <command name>

GOT900 FTP server ready.

User logged out. Good-Bye.

Closing data connection.

User logged in.

CWD command successful.

Description

Transfer is started.

Connection for transfer is established.

Command is normal.

PORT command succeeded.

Supported command list

HELP display ends.

HELP display of corresponding command

Connection is established.

Connection ends.

Connection for transfer ends.

Login succeeded.

CWD (current directory change) command succeeded.

257

275

"A:\ directory.

/ /

MKD command successful.

.

" is current

Current directory display

MKD (directory creation) command succeeded.

Password is required. 331 Password required.

Abnormal codes and messages

426

500

510

530

550

Error code Error message

Connection closed; transfer aborted.

Syntax error, command unrecognized.

Command not supported.

Port open fails.

File open fails.

Not logged in.

Requested action not taken.

Description

Transfer error

Syntax error, command cannot be recognized.

Unsupported command

Port open failed.

File open failed.

Login failed.

Command execution failed.

8 - 7 8 - 7

8.4.2 Troubleshooting

The following table indicates the troubleshooting for use of the FTP server function.

Phenomenon Corrective Action Definition and Cause

[Use FTP server function] is not checked in the

FTP server setting of GT Designer2.

Check [Use FTP server function].

Line cannot be connected.

Login cannot be made.

The other device has logged in to the GOT.

The login name or password is wrong.

The file name is 9 or more characters long.

After the other device has logged in, connect to the line again.

Issue the Ping command to the GOT and check for a reply.

Ask the manager for confirmation.

Enter the correct login name or password.

(Case sensitive)

Reduce the file name to "8 characters" + "." +

"extension".

Change to the write mode. The reference mode is selected.

Overwrite disable or similar setting has been made in the FTP client setting.

Reexamine the FTP client setting.

File cannot be written.

The file of the same name exists.

Delete the file or change the file name so that the file of the same name does not exist.

Cancel the write protection of the PC card.

Turn ON the memory card access switch of the GOT.

File cannot be read.

File cannot be deleted.

GOT was powered off during login.

FTP client software was forcibly exited during login.

The PC card is write-protected.

The memory card access switch of the GOT is

OFF.

An attempt was made to read the file that does not exist.

The memory card access switch of the GOT is

OFF.

The PC card is write-protected.

The memory card access switch of the GOT is

OFF.

Check for the file using the dir or ls command.

Turn ON the memory card access switch of the GOT.

Cancel the write protection of the PC card.

Turn ON the memory card access switch of the GOT.

Since the file being transferred may have been corrupted, do not use but delete it.

(The operation of the FTP client changes depending on the specifications of the FTP client.)

Log in to the GOT again after the time set to the watching timer of command input in the

FTP server setting has elapsed.

(The GOT logs out after the time set to the command has elapsed.)

8 - 8 8 - 8

8.5 Mail Send Function

8.5.1 Error codes and error messages

The following table indicates the error codes stored into the GOT special register GS202 (mail send function error code).

Error Code Definition and Cause

2

3

4

5

6

10

11

12

The FROM address has not been set.

The SMTP server has not been set.

The send destination address has not been set.

The mail address is incorrect.

The number of alarms that occurred may be greater than the number of alarms that can be sent by mail.

The SMTP server could not be connected.

Time-out occurred at the time of connection with the

SMTP server.

Error notification is given from the SMTP server.

Corrective Action

Set FROM.

(Mail send setting on GT Designer2)

Set the SMTP server.

(Mail send setting on GT Designer2)

Set the send destination (TO).

(Mail send setting on GT Designer2)

Check whether the mail address settings of FROM,

TO, CC and BCC are correct.

(Mail send setting on GT Designer2)

Check the number of alarms that occurred. (Max. number of queuing alarms: 16)

1. Check whether the SMTP server is normal or not.

2. Check whether the IP address setting of the

SMTP server is correct or not. (Mail send setting on GT Designer2)

3. Ask the network manager about the router address and sub-net mask and set the returned data in the setup of the GOT.

4. When a firewall has been built on the network, ask the network manager if it has been set to pass through the port 25.

1. Check whether the SMTP server is normal or not.

2. Increase the send message time value.

(Setup screen of GOT)

1. Check whether the SMTP server is normal or not.

2. Ask the network manager if mail can be sent without certification. (e.g. POP3 certification)

8.5.2 Troubleshooting

The following table indicates the troubleshooting for use of the mail send function.

Phenomenon

Mail is not sent.

Time of sent mail is incorrect.

Sentence of mail sent

(received) by cellular phone is broken midway.

Definition and Cause

The SMTP server does not operate properly.

FROM of the send source is not set correctly.

An attempt was made to send 17 or more mails at one time.

The time of the SMTP server is wrong. (The GOT sends mail at the time of the SMTP server.)

The number of characters that can be sent (received) by the cellular phone was exceeded.

Corrective Action

Ask the network manager if the SMTP server is operating properly.

Check whether FROM of the send source is set correctly.

Reduce the number of mails to be sent simultaneously to 16 or less.

Check whether the time of the SMTP server is precise or not.

Reduce the number of characters in the sentence sent by mail to within the number of characters that can be sent (received) by the corresponding cellular phone.

8 - 9 8 - 9

INDEX

[A]

About system programs ................................. 2- 4

Access range

FTP server function .................................... 6- 2

Mail send function....................................... 7- 2

Server and client functions......................... 5- 9

[C]

Checking the line connection condition ......... 6- 6

[E]

Client setting.................................................. 5-12

Connection form ............................................. 2- 1

Error codes and error messages

FTP server function .................................... 8- 7

Mail send function....................................... 8- 9

Server and client functions......................... 8- 4

Example of use

FTP server function .................................... 6- 8

Mail send function....................................... 7- 6

Server and client functions........................ 5-13

[F]

Features of FTP server function .................... 1- 3

Features of mail send function....................... 1- 3

Features of server and client functions ......... 1- 1

File specifying method ................................... 6- 5

FTP server setting .......................................... 6- 3

Function setting .............................................. 4- 1

[G]

Gateway information ...................................... 8- 2

GOT setting .................................................... 4- 3

GT Designer2 setting ..................................... 4- 4

[H]

[I]

How to monitor the gateway devices............. 5- 3

Input command on FTP client side ................ 6- 4

[L]

Line cutoff ....................................................... 6- 7

Index - 1

[M]

Mail send enabled range ................................7- 2

Mail send setting .............................................7- 3

[O]

Operation on FTP client side..........................6- 4

Operation sequence .......................................3- 1

[P]

PLC devices that can be assigned.................5- 6

Precautions

FTP server function....................................6-12

Mail send function .......................................7- 8

Server and client functions ........................5-18

Precautions for mounting the

Communication board ....................................2- 2

[R]

Required devices ............................................2- 2

[S]

Server setting .................................................5-10

Setting method

FTP server function.....................................6- 3

Mail send function .......................................7- 3

Server and client functions ........................5-10

Specifications

FTP server function.....................................6- 1

Mail send function .......................................7- 1

Server and client functions .........................5- 8

[T]

System configuration ......................................2- 1

System configuration of gateway functions ...2- 1

Troubleshooting

FTP server function.....................................8- 8

[W]

Mail send function .......................................8- 9

Server and client functions .........................8- 6

What is gateway device..................................5- 1

When using the bus connection board...........2- 3

When using the serial communication board.2- 2

Ind

Index - 1

Ind

MEMO

Index - 2 Index - 2

WARRANTY

Please confirm the following product warranty details before using this product.

1. Gratis Warranty Term and Gratis Warranty Range

If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service

Company.

However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer’s discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing onsite that involves replacement of the failed module.

[Gratis Warranty Term]

The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place.

Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs.

[Gratis Warranty Range]

(1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product.

(2) Even within the gratis warranty term, repairs shall be charged for in the following cases.

1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design.

2. Failure caused by unapproved modifications, etc., to the product by the user.

3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided.

4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced.

5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage.

6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi.

7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.

2. Onerous repair term after discontinuation of production

(1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued.

Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc.

(2) Product supply (including repair parts) is not available after production is discontinued.

3. Overseas service

Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA

Center may differ.

4. Exclusion of loss in opportunity and secondary loss from warranty liability

Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation of damages caused by any cause found not to be the responsibility of Mitsubishi, loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products, special damages and secondary damages whether foreseeable or not , compensation for accidents, and compensation for damages to products other than Mitsubishi products, replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.

5. Changes in product specifications

The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.

6. Product application

(1) In using the Mitsubishi MELSEC programmable logic controller, the usage conditions shall be that the application will not lead to a major accident even if any problem or fault should occur in the programmable logic controller device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault.

(2) The Mitsubishi programmable logic controller has been designed and manufactured for applications in general industries, etc. Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for Railway companies or Public service purposes shall be excluded from the programmable logic controller applications.

In addition, applications in which human life or property that could be greatly affected, such as in aircraft, medical applications, incineration and fuel devices, manned transportation, equipment for recreation and amusement, and safety devices, shall also be excluded from the programmable logic controller range of applications.

However, in certain cases, some applications may be possible, providing the user consults their local Mitsubishi representative outlining the special requirements of the project, and providing that all parties concerned agree to the special circumstances, solely at the users discretion.

Microsoft Windows, Microsoft Windows NT are registered trademarks of Microsoft Corporation in the United

States and other countries.

Pentium is a registered trademark of Intel Corporation in the United States and other countries.

Other company and product names herein are either trademarks or registered trademarks of their respective owners.

SPREAD

Copyright (C) 1998 Farpoint Technologies, Inc.

GOT-A900 Series Operating Manual

(GT Works2 Version1/GT Designer2 Version1 compatible

Gateway Functions Manual)

O

GOT-A900 Series Operating Manual

(GT Works2 Version1/GT Designer2 Version1 compatible

Gateway Functions Manual)

MODEL

SW1-GTD2-O(G)-E

MODEL

CODE

1DM208

SH(NA)-080398E-C(0407)MEE

HEAD OFFICE : 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212,JAPAN

NAGOYA WORKS : 1-14 , YADA-MINAMI 5-CHOME , HIGASHI-KU, NAGOYA , JAPAN

When exported from Japan, this manual does not require application to the

Ministry of Economy, Trade and Industry for service transaction permission.

Specifications subject to change without notice.

MITSUBISHI Graphic Operation Terminal

MONO