Installation Instructions

MicroLogix 1400 Programmable Controllers

Catalog Number(s) 1766-L32BWA, 1766-L32AWA,

1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA,

1766-L32BXBA http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1

766-in001_-mu-p.pdf

FR

Cette publication est disponible en français sous forme électronique (fichier PDF). Pour la télécharger, rendez-vous sur la page Internet indiquée ci-dessus.

IT

DE

ES

PT

Questa pubblicazione è disponibile in Italiano in formato PDF. Per scaricarla collegarsi al sito

Web indicato sopra.

Diese Publikation ist als PDF auf Deutsch verfügbar. Gehen Sie auf die oben genannte

Web-Adresse, um nach der Publikation zu suchen und sie herunterzuladen.

Esta publicación está disponible en español como PDF. Diríjase a la dirección web indicada arriba para buscar y descarga esta publicación.

Esta publicação está disponível em portugués como PDF. Vá ao endereço web que aparece acima para encontrar e fazer download da publicação.

Installation Instructions

MicroLogix 1400 Programmable Controllers

Catalog Number(s) 1766-L32AWA, 1766-L32AWAA,

1766-L32BWA, 1766-L32BWAA, 1766-L32BXB,

1766-L32BXBA

Topic

Important User Information

Additional Resources

Overview

Controller Description

Hazardous Location Considerations

Mount the Controller

Connect 1762 I/O Expansion Modules

Wire the Controller

Specifications

9

11

13

18

7

8

Page

4

20

27

4 MicroLogix 1400 Programmable Controllers

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment.

Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication

SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com

) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell

Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT

Identifies information that is critical for successful application and understanding of the product.

ATTENTION

Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

SHOCK HAZARD

Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 5

Environment and Enclosure

ATTENTION

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to

IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

Preventing Electrostatic Discharge

ATTENTION

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

• Touch a grounded object to discharge potential static.

• Wear an approved grounding wriststrap.

• Do not touch connectors or pins on component boards.

• Do not touch circuit components inside the equipment.

• Use a static-safe workstation, if available.

• Store the equipment in appropriate static-safe packaging when not in use.

Publication 1766-IN001A-EN-P - July 2008

6 MicroLogix 1400 Programmable Controllers

North American Hazardous Location Approval

The following modules are North American Hazardous Location approved: 1766-L32AWA,

1766-L32AWAA, 1766-L32BWA, 1766-L32BWAA, 1766-L32BXB, 1766-L32BXBA

The following information applies when operating this equipment in hazardous locations:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C,

D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code

(lowest "T" number) may be used to help determine the overall temperature code of the system.

Combinations of equipment in your system are subject to investigation by the local Authority Having

Jurisdiction at the time of installation.

WARNING

EXPLOSION HAZARD

• Do not disconnect while the circuit is live or unless the area is known to be free of ignitible concentations.

Informations sur l’utilisation de cet

équipement en environnements dangereux:

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation.

AVERTISSEMENT

RISQUE D’EXPLOSION

• Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.

• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous.

Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

• Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

• Substitution of components may impair suitability for Class I,

Division 2.

• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I,

Division 2.

• Do not remove or replace lamps, fuses or plug-in modules (as applicable) unless power has been disconnected or the area is known to be free of ignitible concentrations of flammable gases or vapors.

• S’assurer que l’environnement est classé non dangereux avant de changer les piles.

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 7

Additional Resources

Resource

MicroLogix 1400 Programmable Controllers User

Manual 1766-UM001

MicroLogix 1400 Instruction Set Reference

Manual1766-RM001

Installation Instructions 1762-INxxx

Description

A more detailed description of how to install and use your MicroLogix 1400 programmable controller and expansion I/O system.

A reference manual that contains data and function files, instruction set, and troubleshooting information for MicroLogix 1400.

Information on installing and using 1762 expansion I/O modules.

More information on proper wiring and grounding techniques.

Industrial Automation Wiring and Grounding

Guidelines 1770-4.1

If you would like a manual, you can:

• download a free electronic version from the internet: http://literature.rockwellautomation.com

• purchase a printed manual by contacting your local Allen-Bradley distributor or

Rockwell Automation representative

Publication 1766-IN001A-EN-P - July 2008

8 MicroLogix 1400 Programmable Controllers

Overview

MicroLogix 1400 controllers are suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2

(1)

) and with circuits not exceeding Over Voltage

Category II

(2)

(IEC 60664-1)

(3)

.

Install your controller using these installation instructions.

Debris strip

44513

ATTENTION

Do not remove the protective debris strip until after the controller and all other equipment in the panel near the controller are mounted and wiring is complete.

Once wiring is complete, remove protective debris strip. Failure to remove strip before operating can cause overheating.

ATTENTION

Electrostatic discharge can damage semiconductor devices inside the controller.

Do not touch the connector pins or other sensitive areas.

(1)

(2)

(3)

Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.

Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impule voltage capability of the product's insulation.

Pollution Degree 2 and Over Voltage Category II are International Electrotechnical commissions (IEC) designations.

Publication 1766-IN001A-EN-P - July 2008

Controller Description

MicroLogix 1400 Programmable Controllers 9

1 2 3 4 5 6 7

1

ESC

OK

44514

Left side view

13 12 11 10

Top view

9 8

1

2

Description

Comm port 2 - 9-pin D-Shell RS-232C connector

Memory module (refer to MicroLogix 1400 Memory Module Installation Instructions, publication

1766-IN010A for instructions on installing the memory module).

User 24V (for 1766-L32BWA and 1766-L32BWAA only) 3

4

5

8

9

6

7

Input terminal block

LCD Display Keypad (ESC, OK, Up, Down, Left, Right)

Battery compartment

1762 expansion bus connector

Battery connector

Output terminal block

10 LCD Display

11 Indicator LED panel

12 Comm port 1 - RJ45 connector

13 Comm port 0 - 8-pin mini DIN RS-232C/RS-485 connector

44515

Publication 1766-IN001A-EN-P - July 2008

10 MicroLogix 1400 Programmable Controllers

Controller Input and Output Description

Catalog

Number

1766-L32BWA

1766-L32AWA

1766-L32BXB

1766-L32BWA

A

1766-L32AWA

A

1766-L32BXBA

Description

Input

Power

100/240V AC

24 V DC

100/240V AC

24V DC

User

Power

Embedded

Discrete I/O

24V DC

12 Fast 24V DC Inputs

8 Normal 24V DC Inputs

12 Relay Outputs

20 120V AC Inputs

12 Relay Outputs

None

24V DC

12 Fast 24V DC Inputs

8 Normal 24V DC Inputs

6 Relay Outputs

3 Fast DC Outputs

3 Normal DC Outputs

12 Fast 24V DC Inputs

8 Normal 24V DC Inputs

12 Relay Outputs

None

20 120V AC Inputs

12 Relay Outputs

12 Fast 24V DC Inputs

8 Normal 24V DC Inputs

6 Relay Outputs

3 Fast DC Outputs

3 Normal DC Outputs

Embedded

Analog I/O

None

4 Voltage Inputs

2 Voltage

Outputs

(1)

(2)

Isolated RS-232/RS-485 combo port. Same as ML1100 Comm 0

Non-isolated RS-232. Standard D-sub connector

Comm.

Ports

1 RS232/RS485

(1)

1 Ethernet/IP

1 RS232

(2)

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 11

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.

WARNING

EXPLOSION HAZARD

• Substitution of components may impair suitability for Class I, Division 2.

• Do not replace components or disconnect equipment unless power has been switched off.

• Do not connect or disconnect components unless power has been switched off.

• This product must be installed in an enclosure. All cables connected to the product must remain in the enclosure or be protected by conduit or other means.

• All wiring must comply with N.E.C. article 501-10(b) and/or in accordance with

Section 18-1J2 of the Canadian Electrical Code, and in accordance with the authority having jurisdiction.

Use only the following communication cables in Class I, Division 2 hazardous locations.

Environment Classification

Class I, Division 2 Hazardous Environment

Communication Cables

1761-CBL-AC00 Series C or later

1761-CBL-AM00 Series C or later

1761-CBL-AP00 Series C or later

1761-CBL-PM02 Series C or later

1761-CBL-HM02 Series C or later

2707-NC9 Series C or later

1763-NC01 Series A or later

1747-CP3 Series

Publication 1766-IN001A-EN-P - July 2008

12 MicroLogix 1400 Programmable Controllers

Environnements dangereux

Cet équipement est conçu pour une utilisation en environnements dangereux de Classe I,

Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à utilisation en environnements dangereux.

WARNING

DANGER D’EXPLOSION

• La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe I, Division 2.

• Ne pas remplacer de composants ou déconnecter l’équipement sans s’être assuré que l’alimentation est coupée.

• Ne pas connecter ou déconnecter des composants sans s’être assuré que l’alimentation est coupée.

• Ce produit doit être installé dans une armoire. Tous les câbles connectés à l’appareil doivent rester dans l’armoire ou être protégés par une goulotte ou tout autre moyen.

• L’ensemble du câblage doit être conforme à la réglementation en vigueur dans les pays où l’appareil est installé.

Utilisez uniquement les câbles de communication suivants dans les environnements dangereux de Classe I, Division 2.

Classification des environnements Câbles de communication

Environnement dangereux de Classe I, Division 2 1761-CBL-AC00 série C ou ultérieure

1761-CBL-AM00 série C ou ultérieure

1761-CBL-AP00 série C ou ultérieure

1761-CBL-PM02 série C ou ultérieure

1761-CBL-HM02 série C ou ultérieure

2707-NC9 série C ou ultérieure

1763-NC01 série A ou ultérieure série 1747-CP3

ATTENTION

UNSUPPORTED CONNECTION

Do not connect the Comm0 port on the MicroLogix 1400 controller to another MicroLogix family controller such as MicroLogix 1000, MicroLogix 1200, or MicroLogix 1500 using a

1761-CBL-AM00 (8-pin mini-DIN to 8-pin mini-DIN) cable or equivalent.

This type of connection will cause damage to the RS-232/485 communication port

(Channel 0) of the MicroLogix 1400 and/or the controller itself. Communication pins used for RS-485 communications are alternately used for 24V power on the other MicroLogix controllers.

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 13

Mount the Controller

General Considerations

Most applications require installation in an industrial enclosure to reduce the effects of electrical interference and environmental exposure. Locate your controller as far as possible from power lines, load lines, and other sources of electrical noise such as hard-contact switches, relays, and ac motor drives. For more information on proper grounding guidelines, see the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

.

ATTENTION

Mount the controller horizontally only. Vertical mounting is not supported due to thermal considerations.

ATTENTION

Be careful of metal chips when drilling mounting holes for your controller or other equipment within the enclosure or panel. Drilled fragments that fall into the controller could cause damage. Do not drill holes above a mounted controller if the protective debris strips have been removed.

WARNING

Do not place the MLX1400 Programmable Controller in direct sunlight.

Prolonged exposure to direct sunlight could degrade the LCD display.

WARNING

The local programming terminal port is intended for temporary use only and must not be connected or disconnected unless the area is assured to be nonhazardous.

Publication 1766-IN001A-EN-P - July 2008

14 MicroLogix 1400 Programmable Controllers

Mounting Dimensions

C

Dimension

A

B

C

A

B

1766-L32BWA, 1766-L32AWA, 1766-L32BXB,

1766-L32BWAA, 1766-L32AWAA, 1766-L32BXBA

44516

Height

90 mm (3.5 in.)

180 mm (7.087 in.)

87 mm (3.43 in.)

Controller Spacing

The controller mounts horizontally, with the expansion I/O extending to the right of the controller. Allow 50 mm (2 in.) of space on all but the right side for adequate ventilation, as shown below.

Top

Side

ESC

OK

Bottom

44517

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 15

DIN Rail Mounting

The maximum extension of the latch is 14 mm (0.55 in.) in the open position. A flat-blade screwdriver is required for removal of the controller. The controller can be mounted to

EN50022-35x7.5 or EN50022-35x15 DIN rails. DIN rail mounting dimensions are shown below..

B

A

C

44518

Dimension

A

B

C

Height

90 mm (3.5 in.)

27.5 mm (1.08 in.)

27.5 mm (1.08 in.)

Follow these steps to install your controller on the DIN rail.

1. Mount your DIN rail. Make sure that the placement of the controller on the DIN rail

meets the recommended spacing requirements (see Controller Spacing on page 14

for more information). Refer to the mounting template inside the back cover of this document.

2. If it is open, close the DIN latch.

3. Hook the top slot over the DIN rail.

4. While pressing the controller down against the top of the rail, snap the bottom of the controller into position.

5. Leave the protective debris strip attached until you are finished wiring the controller and any other devices.

Follow these steps to remove your controller from the DIN rail.

1. Place a flat-blade screwdriver in the DIN rail latch at the bottom of the controller.

Publication 1766-IN001A-EN-P - July 2008

16 MicroLogix 1400 Programmable Controllers

2. Holding the controller, pry downward on the latch until the latch locks in the open position.

3. Repeat steps 1 and 2 for the second DIN rail latch.

4. Unhook the top of the DIN rail slot from the rail.

Open

ESC

OK

Closed

44519

44520

Panel Mounting

Mount to panel using #8 or M4 screws. Follow these steps to install your controller using mounting screws.

1. Remove the mounting template from inside the back cover of this document.

2. Secure the template to the mounting surface. Make sure your controller is spaced

properly (see Controller Spacing on page 14 for more information).

3. Drill holes through the template.

4. Remove the mounting template.

Mounting Template

5. Mount the controller.

6. Leave the protective debris strip in place until you are finished wiring the controller and any other devices

ESC

OK

44521

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 17

Using the Battery

The MicroLogix 1400 controller is equipped with a replaceable battery (catalog number

1747-BA). The Battery Low indicator on the LCD display of the controller shows the status of the replaceable battery. When the battery is low, the indicator is set (displayed as a solid rectangle). This means that either the battery wire connector is disconnected, or the battery may fail within 2 days if it is connected.

IMPORTANT

The MicroLogix 1400 controller ships with the battery wire connector connected.

Ensure that the battery wire connector is inserted into the connector port if your application needs battery power. For example, when using a real-time clock

(RTC).

Replacing the battery when the controller is powered down will lose all user application memory. Replace the battery when the controller is powered on.

Refer to the SLC 500 Lithium Battery Installation Instructions, publication

1747-IN515 , for more information on installation, handling, usage, storage, and disposal of the battery.

WARNING

When you connect or disconnect the battery an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that the area is nonhazardous before proceeding.

For Safety information on the handling of lithium batteries, including handling and disposal of leaking batteries, see Guidelines for Handling Lithium Batteries, publication AG 5-4 .

Follow these steps to connect the replaceable battery.

1. Insert the replaceable battery wire connector into the controller’s battery connector.

Publication 1766-IN001A-EN-P - July 2008

18 MicroLogix 1400 Programmable Controllers

2. Secure the battery connector wires so that it does not block the 1762 expansion bus connector as shown below.

Battery compartment

1762 I/O expansion bus connector

Battery wire connector

Battery connector

Battery wires twisted pair

44522

Connect 1762 I/O Expansion Modules

ATTENTION

Remove power from the system before installing or removing expansion I/O or damage to the controller may result.

Connect 1762 I/O after mounting the controller.

1. Remove the expansion port cover to install expansion I/O modules.

2. Plug the ribbon cable connector into the bus connector.

Publication 1766-IN001A-EN-P - July 2008

3. Replace the cover as shown below.

MicroLogix 1400 Programmable Controllers 19

44523

The MicroLogix 1400 controller is designed to support up to any seven 1762 expansion I/O modules.

For detailed information on using expansion I/O, refer to the installation instructions for your expansion module.

Publication 1766-IN001A-EN-P - July 2008

20 MicroLogix 1400 Programmable Controllers

Wire the Controller

Terminal Block Layouts

WARNING

When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING

When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure. All wiring must be in accordance with Class I,

Division 2 wiring methods of Article 501 of the National Electrical Code and/or in accordance with Section 18-1J2 of the Canadian Electrical Code, and in accordance with the authority having jurisdiction.

TIP

The shading in the following terminal block illustrations indicates which terminals are tied to which commons.

1766-L32BWA/L32BWAA

Input Terminal Block

+24 V COM +24 V DC

IN0 IN2 COM 1 IN5 IN7 IN8 IN10 COM 3 IN13 IN15 IN17 IN19 IV0(+) IV2(+)

COM 0

IN1 IN3 IN4 IN6

COM 2

IN9 IN11 IN12 IN14 IN16 IN18 COM

ANA

IV1(+) IV3(+)

VAC

L1

VAC

L2/N OUT0 OUT1 OUT2 OUT3 OUT4

VAC

DC5 OUT7 OUT8 OUT10

COM

ANA

OV1

DC0

VAC

DC1

VAC

DC2

VAC

DC3

VAC

DC4

VAC

OUT5 OUT6 DC6

VAC

OUT9 OUT11

OV0

Output Terminal Block

44524

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 21

1766-L32AWA/L32AWAA

Input Terminal Block

IN0 IN2 COM 1 IN5 IN7 IN8 IN10 COM 3 IN13 IN15 IN17 IN19 IV0(+) IV2(+)

COM 0 IN1 IN3 IN4 IN6 COM 2 IN9 IN11 IN12 IN14 IN16 IN18 COM

ANA

IV1(+) IV3(+)

VAC

L1

VAC

L2/N OUT0 OUT1 OUT2 OUT3 OUT4

VAC

DC5 OUT7 OUT8 OUT10

COM

ANA

OV1

DC0

VAC

DC1

VAC

DC2

VAC

DC3

VAC

DC4

VAC

OUT5 OUT6 DC6

VAC

OUT9 OUT11 OV0

Output Terminal Block

1766-L32BXB/L32BXBA

Input Terminal Block

IN0 IN2 COM 1 IN5 IN7 IN8 IN10 COM 3 IN13 IN15 IN17 IN19 IV0(+) IV2(+)

44525

COM 0 IN1 IN3 IN4 IN6 COM 2 IN9 IN11 IN12 IN14 IN16 IN18 COM

ANA

IV1(+) IV3(+)

VDC

+24

VDC

NEUT OUT0 OUT1 OUT2 OUT4 OUT6 COM 2 OUT8 OUT9 OUT10

COM

ANA OV1

DC0

VAC

DC1

VAC

DC1

VDC2

OUT3 OUT5 OUT7 DC3

VAC

DC4

VAC

Output Terminal Block

DC5

VAC

OUT11 OV0

Wire Type

Solid wire

Stranded wire

Cu-90

°C (194°F)

Cu-90

°C (194°F)

Wiring torque = 0.791Nm (7 in-lb) rated.

Wire Size

14...22 AWG

16...22 AWG

44526

Publication 1766-IN001A-EN-P - July 2008

22 MicroLogix 1400 Programmable Controllers

WARNING

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding

WARNING

The local programming terminal port is intended for temporary use only and must not be connected or disconnected unless the area is assured to be nonhazardous.

Wiring Recommendation

When wiring without spade lugs, keep the finger-safe covers in place. Loosen the terminal screw and route the wires through the opening in the finger-safe cover. Tighten the terminal screw, making sure the pressure plate secures the wire.

Finger-safe cover

44527

ATTENTION

Be careful when stripping wires. Wire fragments that fall into the controller could cause damage. Once wiring is complete, be sure the controller is free of all metal fragments before removing the protective debris strip. Failure to remove the strip before operating can cause overheating.

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 23

Spade Lug Recommendation

The diameter of the terminal screw head is 5.5 mm (0.220 in.). The input and output terminals of the MicroLogix 1400 controller are designed for the following spade lugs. The terminals will accept a 6.35mm (0.25 in.) wide spade (standard for #6 screw for up to 14

AWG) or a 4 mm (metric #4) fork terminal.

When using spade lugs, use a small, flat-blade screwdriver to pry the finger-safe cover from the terminal blocks, then loosen the terminal screw.

Finger-safe cover

TIP

44528

If you wire the terminal block with the finger-safe cover removed, you may not be able to put it back on the terminal block if the wires are in the way.

Surge Suppression

ATTENTION

Inductive load devices such as motor starters and solenoids require the use of some type of surge suppression to protect the controller output. Switching inductive loads without surge suppression can significantly reduce the life of relay contacts or damage transistor outputs. By using suppression, you also reduce the effects of voltage transients caused by interrupting the current to that inductive device, and prevent electrical noise from radiating into system wiring. Refer to the MicroLogix 1400 Programmable Controller User Manual, publication 1766-UM001 , for more information on surge suppression.

Publication 1766-IN001A-EN-P - July 2008

24 MicroLogix 1400 Programmable Controllers

Grounding the Controller

In solid-state control systems, grounding and wire routing helps limit the effects of noise due to electromagnetic interference (EMI). Run the ground connection from the ground screw of the controller to the ground bus prior to connecting any devices. Use AWG #14 wire. For

AC-powered controllers, this connection must be made for safety purposes.

You must also provide an acceptable grounding path for each device in your application. For more information on proper grounding guidelines, refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

.

Wiring Your Analog Channels

Analog input circuits can monitor voltage signals and convert them to serial digital data as shown in the following illustration.

Analog Input

Sensor 2

(V) Voltage

Sensor 0

(V) Voltage

Input Terminal Block

/7 I/8 I/10 COM 3 I/13 I/15 I/17 I/19 IV0(+) IV2(+)

COM 2 I/9 I/11 I/12 I/14 I/16 I/18 COM

ANA

IV1(+) IV3(+)

Sensor 1

(V) Voltage

Sensor 3

(V) Voltage

44529

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 25

The controller does not provide loop power for analog inputs. Use a power supply that matches the transmitter specifications as shown.

The analog output can support a voltage function as shown in the following illustration.

Analog Output

Voltage Load

O/3 O/4

VAC

DC5 O/7 O/8 O/10

COM

ANA OV1

3

C

DC4

VAC

O/5 O/6 DC6

VAC

O/9 O/11 OV0

Output Terminal Block

Voltage Load

Analog Input Transmitter Specifications

2-Wire Transmitter

-

+

Transmitter

+ -

3-Wire Transmitter

Power

Supply

-

+

Transmitter

Supply

GND

Signal

4-Wire Transmitter

Power

Supply

-

+

Transmitter

Supply

+

Signal

+

-

-

44680

Controller

IV0(+), IV1(+), IV2(+) or IV3(+)

COM ANA

Controller

IV0(+), IV1(+), IV2(+) or IV3(+)

COM ANA

Controller

IV0(+), IV1(+), IV2(+) or IV3(+)

COM ANA

44530

Publication 1766-IN001A-EN-P - July 2008

26 MicroLogix 1400 Programmable Controllers

Minimizing Electrical Noise on Analog Channels

Inputs on analog channels employ digital high-frequency filters that significantly reduce the effects of electrical noise on input signals. However, because of the variety of applications and environments where analog controllers are installed and operated, it is impossible to ensure that all environmental noise will be removed by the input filters.

Several specific steps can be taken to help reduce the effects of environmental noise on analog signals:

• Install the MicroLogix 1400 system in a properly rated (NEMA) enclosure. Make sure that the MicroLogix 1400 system is properly grounded.

• Use Belden cable #8761 for wiring the analog channels, making sure that the drain

wire and foil shield are properly earth grounded, (see Grounding Your Analog Cable on page 26 for more information).

• Route the Belden cable separately from any AC wiring. Additional noise immunity can be obtained by routing the cables in grounded conduit.

Grounding Your Analog Cable

Use shielded communication cable

(Belden #8761). The Belden cable has two signal wires (black and clear), one drain wire, and a foil shield. The drain wire and foil shield must be grounded at one end of the cable.

Insulation

Foil Shield

Black Wire

Drain Wire

Clear Wire

44531

IMPORTANT

Do not ground the drain wire and foil shield at both ends of the cable.

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 27

Specifications

General Specifications

Description

Dimensions

HxWxD

Shipping weight

Number of I/O

Power supply voltage

Heat dissipation

Power supply inrush current

Power consumption

24V DC sensor power

Input circuit type

Output circuit type

Enclosure type rating

Wire size

Wiring category

Terminal screw torque

Pilot duty rating

Expansion bus

(1)

1766-L32AWAA

90 x 180 x 87 mm

3.5 x 7.087 x 3.43 in.

1766-L32BWAA 1766-L32BXBA

0.9 kg (2.0 lbs)

24 inputs (20 digital and 4 analog) and 14 outputs (12 digital and 2 analog)

100...240V AC (-15%, +10%) at 47...63 Hz 24V DC (-15%, +10%)

Class 2 SELV

Refer to the MicroLogix 1400 Programmable Controllers User Manual,

Publication 1766-UM001 .

120V AC: 25 A for 8 ms

240V AC: 40A for 4 ms

100 VA 120 VA

24V DC:

15 A for 20 ms

50W none

Digital: 120V AC

Analog: 0...10V DC

Relay

None (open-style)

24V DC at 250 mA

400 µF max.

Digital: 24V DC sink/source

(standard and high-speed)

Analog: 0...10V DC none

Digital: 24V DC sink/source

(standard and high-speed)

Analog: 0...10V DC

Relay/FET

0.25... 2.5 mm

2

(22...14 AWG) solid or stranded copper wire rated at 90 °C

(194 °F ) or greater.

2 - on signal ports

2 - on power ports

3 - on communications ports

0.79 Nm (7.0 in-lb) rated

R300, C300

Supports up to seven 1762 modules, up to a maximum of 5V, 1500 mA and 24 V,

1500 mA.

T3C North American temp code

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and

Grounding Guidelines, publication 1770-4.1

.

Publication 1766-IN001A-EN-P - July 2008

28 MicroLogix 1400 Programmable Controllers

Specifications for Inputs

Digital Inputs

Description 1766-L32AWA/A 1766-L32BWA/A, 1766-L32BXB/A

Inputs 0 through 11

(12 high-speed DC inputs)

4.5...24V DC, Class 2

Inputs 12 and higher

(8 standard DC inputs)

10...24V DC, Class 2 On-state voltage range

79 ...132 V AC

Off-state voltage range

Operating frequency

0...20 V AC

47...63 Hz

On-state current

Mininum

Nominal

Maximum

Off-State

Leakage Current

5.0 mA @ 79 V AC

12 mA @ 120 V AC

16.0 mA @ 132 V AC

2.5 mA max.

Nominal

Impedance

12 k

Ω at 50 Hz

Inrush Current

(max.) at 120V AC

10 k

Ω at 60 Hz

250mA

(4.5...26.4V DC @ 65°C/149°F)

(4.5...30V DC @ 30°C/86°F)

0...1.5V DC

0 Hz...100 kHz

7.1 mA @ 4.5V DC

9.9 mA @ 24V DC

10.5 mA @ 30V DC

0.2 mA max.

2.4 k

Ω

(10...26.4V DC @ 65°C/149°F)

(10...30V DC @ 30°C/86°F)

0...5V DC

0 Hz...1 kHz

(scan time dependent)

3.2 mA @ 10V DC

5.3 mA @ 24V DC

5.5 mA @ 30V DC

1.5 mA max.

4.5 k

Ω

Analog Inputs

Description

Voltage Input Range

Type of Data

Input Coding (0 to 10.0V DC - 1 LSB)

Voltage Input Impedance

Input Resolution

Non-linearity

Overall accurarcy

-20...+65 °C (-4...+149 °F)

Voltage input overvoltage protection

Field wiring to logic isolation

1766-L32AWAA, -L32BWAA, -L32BXBA

0 ...10.0V DC - 1 LSB

12-bit unsigned integer

0 ...4,095

>199 k

Ω

12 bit

±

1.0% of full scale

±

1.0% of full scale

10.5 V DC

Non-isolated with internal logic

Publication 1766-IN001A-EN-P - July 2008

Analog Outputs

Description

Number of inputs

Voltage output range

Type of data

Step response

Load range

Voltage output

Output resolution

Analog output setting time

Overall Accurarcy

-20...65 °C (-4...149 °F)

Electrical isolation

Cable length

MicroLogix 1400 Programmable Controllers 29

1766-L32AWAA, -L32BWAA, -L32BXBA

2 single-ended

0...10 V DC - 1 LSB

12 bit unsigned integer

2.5 ms @ 95%

1 K

Ω

12 bit

3 ms (max.)

±

1.0% of full scale

Non-isolated with internal logic

30 m (98 ft) shielded cable

Publication 1766-IN001A-EN-P - July 2008

30 MicroLogix 1400 Programmable Controllers

Specifications for Outputs in Hazardous Locations

(Class 1, Division 2, Groups A, B, C, D)

Relay and FET Outputs

Description 1766-L32AWA/A,

1766-L32BWA/A

1440 VA

1766-L32BXB/A

Maximum Controlled Load

Maximum Continuous Current:

1080 VA

Current per Channel and Group Common 2.5 A per channel

8A max channel 8...11 common

Current per Controller at 150V max 28 A or total of per-point loads, whichever is less

2.5 A per channel at 240V max 20 A or total of per-point loads, whichever is less

Relay Outputs

Description

Turn On Time/Turn Off Time

Load Current

(1)

Scan time dependent

1766-L32AWA/A, 1766-L32BWA/A, 1766-L32BXB/A

10 msec (maximum)

(1)

10 mA (minimum)

Maximum Volts

240V AC

120V AC

250V DC

125V DC

Amperes

Make

7.5 A

15.0 A

Break

0.75 A

1.5 A

0.11 A

0.22 A

Amperes

Continuous

3.0 A

3.0 A

1.0 A

1.0 A

Volt-Amperes

Make

1800 VA

1800 VA

Break

180 VA

180 VA

28 VA

28 VA

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 31

Specifications for Outputs in (Non-Hazardous) Locations only

1766-L32BXB, 1766-L32BXBA FET Output

Maximum Output Current (temperature dependent):

FET Current per Point FET Total Current

2.0

1.75

1.5

1.25

1.0

0.75

0.5

0.25

1.5A, 30°C (86°F)

0.75A, 60°C (140°F)

10°C

(50°F)

Valid

Range

30°C

(86°F)

50°C

(122°F)

Temperature

70°C

(158°F)

80°C

(176°F)

44532

5.0

4.0

3.0

2.0

1.0

8.0

7.0

6.0

6.0A , 30°C (86°F)

Valid

Range

3.0A , 60°C (140°F)

10°C

(50°F)

30°C

(86°F)

50°C

(122°F)

Temperature

70°C

(158°F)

80°C

(176°F)

44533

Description General Operation

High Speed Operation

(1)

(Output 2, 3 and 4 Only)

24V DC (-15%, 10%) Class 2 Power Supply Voltage

On-State Voltage Drop: at maximum load current at maximum surge current

Current Rating per Point maximum load minimum load maximum leakage

Surge Current per Point: peak current maximum surge duration maximum rate of repetition at 30 °C (86 °F) maximum rate of repetition at 65 °C (149 °F)

Turn-On Time (maximum)

Turn-Off Time (maximum)

1V DC

2.5V DC

See graphs below

1.0 mA

1.0 mA

4.0 A

10 ms once every second once every 2 seconds

11

μs

89

μs

Not Applicable

Not Applicable

100 mA

20 mA

1.0 mA

Not Applicable

Not Applicable

Not Applicable

Not Applicable

28 ns

2.3

μs

(1)

Output 2, 3 and 4 are designed to provide increased functionality over the other FET outputs. Output 2, 3 and 4 may be used like the other FET transistor outputs, but in addition, within a limited current range, they may be operated at a higher speed.

Output 2, 3 and 4 also provide a pulse train output (PTO) or pulse width modulation output (PWM) function.

Publication 1766-IN001A-EN-P - July 2008

32 MicroLogix 1400 Programmable Controllers

Working Voltage

Working Voltage for 1766-L32AWA/A

Description

Power Supply Input to

Backplane Isolation

Input Group to Backplane

Isolation

Input Group to Input Group

Isolation

Output Group to Backplane

Isolation

Output Group to Output

Group Isolation

Recommendation

Verified by one of the following dielectric tests: 1836V AC for 1 second or

2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests:1517V AC for 1 second or

2145V DC for 1 second

132V AC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests:1517V AC for 1 second or

2145V DC for 1 second

132V AC Working Voltage (basic insulation)

Verified by one of the following dielectric tests: 1836V AC for 1 second or

2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests: 1836V AC for 1 second or

2596V DC for 1second

265V AC Working Voltage (basic insulation), 150V AC Working Voltage (IEC

Class 2 reinforced insulation)

Working Voltage for 1766-L32BWA/A

Description

Power Supply Input to

Backplane Isolation

Input Group to Backplane

Isolation and Input Group to

Input Group Isolation

Recommendation

Verified by one of the following dielectric tests:1836V AC for 1 second or

2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests: 1100V AC for 1 second or

1697V DC for 1 second

Output Group to Backplane

Isolation

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests: 1836V AC for 1 second or

2596V DC for 1 second

Output Group to Output

Group Isolation

265V AC Working Voltage (IEC Class 2 reinforced insulation).

Verified by one of the following dielectric tests: 1836V AC for 1 second or

2596V DC for 1 second

265V AC Working Voltage (basic insulation) 150V Working Voltage (IEC Class 2 reinforced insulation)

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 33

Working Voltage for 1766-L16BXB/A

Description

Input Group to Backplane

Isolation and Input Group to

Input Group Isolation

FET Output Group to

Backplane Isolation

Recommendation

Verified by one of the following dielectric tests: 1100V AC for 1 second or

1697V DC for 1 second

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests: 1100V AC for 1 second or

1697V DC for 1 second

Relay Output Group to

Backplane Isolation

75V DC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests: 1836V AC for 1 second or

2596V DC for 1 second

Relay Output Group to Relay

Output Group and FET

Output Group Isolation

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Verified by one of the following dielectric tests: 1836V AC for 1 second or

2596V DC for 1 second

265V AC Working Voltage (basic insulation), 150V Working Voltage

(IEC Class 2 reinforced insulation)

Environmental Specifications

Description

Vibration

1766-L32AWA/A 1766-L32BWA/A 1766-L32BXB/A

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20... 60 °C (-4 ...140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)-40...85 °C (-40... 185 °F)

Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5...95% non-condensing

IEC 60068-2-6 (Test Fc, Operating):

5g @ 10... 500 Hz

Shock, operating

Shock, nonoperating

Emissions

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

Panel mount - 50 g

DIN mount - 40 g

CISPR 11

Group 1, Class A

Publication 1766-IN001A-EN-P - July 2008

34 MicroLogix 1400 Programmable Controllers

Description

ESD immunity

1766-L32AWA/A

IEC 61000-4-2:

4 kV contact discharges

8 kV air discharges

1766-L32BWA/A 1766-L32BXB/A

Radiated RF immunity IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz

3 V/m with 1 kHz sine-wave 80% AM from 1.4...2.0 GHz

1 V/m with 1 kHz sine-wave 80% AM from 2.0...2.7 GHz

EFT/B immunity IEC 61000-4-4:

±2 kV at 5 kHz on power ports

±2 kV at 5 kHz on signal ports

±1 kV at 5 kHz on communications ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on AC power ports

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

±1 kV line-earth(CM) on communications ports

Conducted RF immunity IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Voltage Variation IEC 6100-4-11:

60% dip for 10 periods on AC supply ports

30% dips for 25 periods at 0

° and 180° on AC supply ports

100% dip for 250 periods at 0

° and 180° on AC supply ports

100% dip for 0.5 periods, arbitrary angle, on AC supply ports

Publication 1766-IN001A-EN-P - July 2008

MicroLogix 1400 Programmable Controllers 35

Certifications for 1766-32AWA/A, 1766-L32BWA/A,

1766-L32BXB/A

Certification (when product is marked)

(1)

UL

Value

CE

C-Tick

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations.

See UL File E10314.

European Union 2004/108/EC EMC Directive, compliant with:

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

EN 61131-2; Programmable Controllers (Clause 11)

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

(1)

See the Product Certification link at http://www.ab.com

for Declaration of Conformity, Certificates, and other certification details.

Publication 1766-IN001A-EN-P - July 2008

36 MicroLogix 1400 Programmable Controllers

Publication 1766-IN001A-EN-P - July 2008

100.06 mm

(3.939 in.)

0.164

180.0 mm

(7.087 in.)

165.8 mm

(6.528 in.)

DIN rail center line.

Ligne médiane du rail DIN.

Mittellinie der DIN-Schiene.

Línea central del riel DIN.

Linea centrale della guida DIN.

linha de centro do trilho DIN.

1766-L32AWA, 1766-L32AWAA

1766-L32BWA, 1766-L32BWAA

1766-L32BXB, 1766-L32BXBA

25.81 mm

(1.016 in.)

Expansion I/O

Extension d'E/S

E/A -

Erweiterungsmodule

Espansione dei moduli I/O

Expansión de E/S

Expansão de E/S

L32AWA L32AWAA

L32AWAA L32AWA

953203-16

L32BWA L32BWAA

L32BWAA L32BWA

953203-16

L32BXBA L32BXB

L32BXB L32BXBA

953203-16

Publication 1766-IN001A-EN-P - June 2008

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell

Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:

United States 1.440.646.3434 Monday – Friday, 8am – 5pm EST

Outside United States Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States Please contact your local Rockwell Automation representative for return procedure.

Allen-Bradley, Rockwell Automation, MicroLogix, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1766-IN001A-EN-P - June 2008 PN 953203-13

Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.