advertisement
Electricity Meters IEC
HIGH PRECISION METERING
Landis+Gyr Qualigrid
ZMQ202 / ZFQ202
USER MANUAL
H 71 0200 0215 h en
c d e f g h
Revision History
Index Date a 20.12.2002
Comments
First release, for approbation.
07.03.2003
19.03.2003
30.06.2003
19.12.2003
31.03.2004
31.01.2005
Chapter 2 updated, various changes: hazard symbols, sealing, LP memory, starting load
Minor changes to paragraph 6.3 Errors
Updates according to the safety review (preliminary edition) and to final review
Updates according to product risk analysis and firmware H00
Updates for firmware H01
Amendments for firmware version H02/H90 (registration of delta values, demand and power factor, stored billing value profile, IEC870 subset, transmitting contact test mode) subject to technical changes
Landis+Gyr AG
Feldstrasse 1
CH - 6301 Zug
Switzerland
Phone: +41 41 935 60 00 www.landisgyr.com
© Landis+Gyr AG
2/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
About this Document
Range of validity
Purpose
Target group
Conditions
Reference documentation
The present user manual applies to the meters specified on the title page with firmware H01.
The user manual contains all the information required for application of the meters for the intended purpose. This includes:
• Provision of knowledge concerning characteristics, construction and function of the meters
• Information about possible dangers, their consequences and measures to prevent any danger
• Details concerning the performance of all work throughout the service life of the meters (parameterisation, installation, commissioning, operation, maintenance, shutting down and disposal)
The contents of this user manual are intended for technically qualified personnel of energy supply companies responsible for the system planning, installation and commissioning, operation, maintenance, decommissioning and disposal of the meters.
Users of this manual are familiar from their training with the basic principles of electrical engineering, in particular with the principles of energy measurement, including circuitry types, connection technology, etc.
The following documents complement this user manual:
Type designation
Functional description: Explains the functionality of the ZxQ meter and the parameterisation using the MAP tool.
Technical data: States all technical data of the ZxQ meter.
The following conventions are employed in this user manual for representing type designations:
• The lower case letter "x" can be used as an unknown to indicate different versions (e.g. ZxQ202 for the ZMQ202 and ZFQ202 meters).
• The digit pair "00" can be used to indicate accuracy data (e.g. ZxQ200 for the ZxQ202 and ZxQ205 meters).
• The abbreviated type designation ZMQ or ZFQ meters can be used when all three-phase four-wire meters or three-phase three-wire meters are meant.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual © Landis+Gyr AG
3/108
Table of Contents
Safety _____________________________________________ 9
Safety Information ____________________________________________ 9
Responsibilities _______________________________________________ 9
Safety Regulations ___________________________________________ 10
Description of Unit___________________________________ 13
Application _________________________________________________ 13
Features ___________________________________________________ 13
Type Designation ____________________________________________ 14
Block Schematic Diagram ______________________________________ 15
Measuring System ___________________________________________ 17
Input Signals________________________________________________ 17
Input Circuits _______________________________________________ 17
Signal Converter _____________________________________________ 17
Signal Processor _____________________________________________ 17
Microprocessor ______________________________________________ 18
Measured Values ____________________________________________ 19
Calculation of Measured Quantities ______________________________ 20
Demand ___________________________________________________ 21
Power Factor________________________________________________ 22
Instantaneous Values _________________________________________ 22
Diagnostic Values ____________________________________________ 22
Tariff Control _______________________________________________ 23
Calendar Clock ______________________________________________ 24
Synchronisation and Time-Setting _______________________________ 25
Synchronising the Calendar Clock via the Synchronisation Input _______ 25
Synchronising the Calendar Clock via Communication _______________ 27
Setting the Time _____________________________________________ 27
Handling the Deviations _______________________________________ 28
Registers ___________________________________________________ 29
Memory____________________________________________________ 30
Load Profile_________________________________________________ 30
Snapshot___________________________________________________ 30
Stored Billing Value Profile _____________________________________ 30
Event Log __________________________________________________ 31
Power Supply _______________________________________________ 31
Additional Power Supply_______________________________________ 31
© Landis+Gyr AG
4/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Transmitting Contacts Module___________________________________31
Communication Unit (Option) ___________________________________32
Software Tools _______________________________________________32
Mechanical Description _______________________________ 33
Manufacturer's Seal ___________________________________________34
Verification Seal ______________________________________________34
Utility's Seals ________________________________________________35
Face Plate f6 ________________________________________________37
Information Plate f6___________________________________________37
Terminal Connection Diagram f6_________________________________38
Face Plate and Information Plate f9 ______________________________38
Connection Diagram f9 ________________________________________38
Dimension Diagrams f6 ________________________________________39
Dimension Diagrams f9 ________________________________________40
Rack Mounting _______________________________________________40
Racks ______________________________________________________41
Flush Mounting ______________________________________________43
Mounting f6 _________________________________________________44
Installation / De-installation___________________________ 45
Prerequisites ________________________________________________45
Connect the f6 Meter__________________________________________46
Connection Diagram __________________________________________46
Terminal Layout ______________________________________________46
Procedure___________________________________________________47
Connect the f9 Meter__________________________________________50
Connection Diagram __________________________________________50
Terminal Layout ______________________________________________50
Procedure___________________________________________________51
Installation Check ____________________________________________52
Check Procedure _____________________________________________52
Testing the Transmitting Contacts _______________________________54
Set Date and Time____________________________________________55
Set Battery Low Indicator ______________________________________56
Sealing _____________________________________________________56
Disconnect the f6 Meter _______________________________________57
Procedure___________________________________________________57
Disconnect the f9 Meter _______________________________________59
Procedure___________________________________________________59
© Landis+Gyr AG
5/108
© Landis+Gyr AG
6/108
Operation _________________________________________ 61
Operating Elements __________________________________________ 61
Display ____________________________________________________ 62
Arrows in Display ____________________________________________ 63
Display Buttons______________________________________________ 64
Optical Interface_____________________________________________ 64
Optical Test Outputs__________________________________________ 64
Alarm LED__________________________________________________ 65
Display Menu _______________________________________________ 66
Select Display Menu __________________________________________ 67
Display List _________________________________________________ 68
Load Profile_________________________________________________ 69
Event Log __________________________________________________ 70
Daily Snapshot ______________________________________________ 71
Stored Billing Value Profile _____________________________________ 72
Losses _____________________________________________________ 72
Grid Diagnostic ______________________________________________ 73
Meter Operation in Systems ____________________________________ 74
Remote Meter Reading in Energy Production Applications ____________ 74
Types of Communication ______________________________________ 74
Communication Units _________________________________________ 75
MAP 120 Service Tool_________________________________________ 75
Service____________________________________________ 77
Alarm Reset Button __________________________________________ 77
Service Menu _______________________________________________ 78
Select Service Menu __________________________________________ 79
Service List _________________________________________________ 79
Installation Diagnostic List _____________________________________ 80
Test Mode__________________________________________________ 80
Set Battery Low Indicator______________________________________ 81
Billing Period Reset___________________________________________ 82
Errors _____________________________________________________ 83
Fatal Errors _________________________________________________ 83
Alarms_____________________________________________________ 84
Operational Indications _______________________________________ 85
Repair _____________________________________________________ 86
Maintenance _______________________________________ 87
Meter Tests_________________________________________________ 87
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Measuring Times _____________________________________________87
Optical Test Outputs __________________________________________87
Test via Transmitting Contacts __________________________________87
Test Mode __________________________________________________88
No Load Test ________________________________________________89
Starting Load for Active Energy__________________________________89
Starting Load for Reactive Energy________________________________89
Set Time & Date, ID Numbers, Battery Time _______________________90
Change Battery ______________________________________________91
When to Change Battery _______________________________________91
How to Change Battery ________________________________________91
Change Communication Unit ____________________________________94
When to Change Communication Unit ____________________________94
How to Change Communication Unit _____________________________94
ZxQ200C.2_________________________________________ 97
Communication According to the IEC870 Subset ____________________97
Measured Quantities __________________________________________98
Service Menu ________________________________________________99
Installation Check ___________________________________________100
Check Meter Address _________________________________________100
Reset Communication Counter _________________________________101
Check Communication ________________________________________102
Error Messages _____________________________________________103
Disposal__________________________________________ 105
Components________________________________________________105
Meters ____________________________________________________105
Index____________________________________________ 107
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual © Landis+Gyr AG
7/108
© Landis+Gyr AG
8/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
1 Safety
This chapter explains the safety information used in this user manual, describes the responsibilities and lists the safety regulations to be obeyed.
Danger
Warning
Note
Attention is drawn as follows in the individual chapters of this user manual with classified word symbols and pictographs to the relevant danger level, i.e. the severity and probability of any danger:
Definition of Danger
For a possibly dangerous situation, which could result in severe physical injury or fatality.
Definition of Warning
For a possibly dangerous situation, which could result in minor physical injury or material damage.
Definition of Note
For general details and other useful information to simplify the work.
In addition to the danger level, all safety information also describes the type and source of the danger, its possible consequences and measures to counteract the danger.
1.2 Responsibilities
The owner of the meters – usually the utility – is responsible that all persons engaged on work with meters:
1. have read and understood the relevant sections of the user manual.
2. are sufficiently qualified for the work to be performed.
3. strictly observe the safety regulations (according to section
f
Regulations
) and the operating information in the individual chapters.
In particular, the owner of the meters bears responsibility for
• the protection of persons,
• the prevention of material damage
• and the training of personnel.
Landis+Gyr AG provides training courses for this purpose on specific equipment; please contact the relevant agent if interested.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Safety
© Landis+Gyr AG
9/108
Danger
Danger
Danger
Danger
Danger
The following safety regulations must be observed at all times.
Do not open the meter when energised
When the meter is connected and energised, there are live parts inside the meter. Do not open the meter when energised.
Disconnect the measuring voltage and all auxiliary circuits before opening the meter housing.
Dangerous voltage on conductors
Dangerous voltage is present on the conductors that the meter is to be connected to.
Contact with the conductors when under voltage will result in severe personal injury or death.
The conductors must not be under voltage when connecting or disconnecting the meter. The relevant preliminary fuses must therefore be removed and kept in a safe place until the work is completed, so that other persons cannot replace them unnoticed.
Dangerous voltage on transformers
Dangerous voltage is produced by the current transformers when the secondary circuit is broken while current is flowing in the primary.
Contact with the transformers when under voltage will result in severe personal injury or death. The high voltage produced will also destroy the transformers.
The current transformer secondary circuit must be short-circuited before de-installing the meter.
Missing transformer earthing
Voltage transformers that are not earthed on the secondary may reach dangerously high voltage values on the secondary.
Voltage transformers are usually earthed on the secondary. As an exception for special connections, the earthing can be omitted unless possible otherwise.
If the voltage transformer is not earthed, severe personal injury or death can result if contact is made with the meter and the meter will be damaged beyond repair.
If the voltage transformers are not earthed, special precautions must be taken when working at the meter.
Galvanic isolation
The measuring circuits and auxiliary circuits (additional power supply, tariff control input, synchronisation input, transmitting contacts, communication interfaces) must be galvanically isolated.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
10/108 Safety
Danger
Warning
Voltage paths must be fused
When installing the meter, all auxiliary circuits such as the additional power supply and the tariff control voltage must be fused by max. 6A delay fuses.
It is recommended to fuse the measurement voltage, too.
Damage of dust, water, incorrect cleaning and handling
Damage to the meter could occur if the meter is subjected to running water or even high-pressure devices, e.g. for cleaning purposes. The meter may be cleaned with a damp cloth.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Safety
© Landis+Gyr AG
11/108
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
12/108 Safety
2.1 Application
The ZxQ is a high precision combimeter of class 0.2S designed for energy measurement in the following applications.
• energy production applications
• energy transmission applications
• industrial consumer applications
• in special, high-precision metering applications
2.2 Features
The ZxQ is the answer to customer needs, providing
• More measurement quantities (e.g. single phase, U, I, VA)
• Installation diagnostics for easy commissioning
• Quick network diagnostics on site
• Standard protocols for the communication of the meter with the billing station.
Excellent measurement features for Cl.0.2S
• Landis+Gyr-proven long-term stability and reliability
(75,000 Cl.0.2S meters in operation)
• All requirements guaranteed according to IEC 62053-22
• Excellence in measurement from starting load to Pmax in both energy directions
• Negligible influence if power factor is less than 1
• Reactive energy Cl.0.5 possible (IEC definitions only for Cl.2).
Special grid functions
• Measurement system five times faster than for industrial meters, giving sufficient resolution for capture periods less than 15 minutes (1 to 5 minutes) and accurate measurement when at energy direction changes
• Measurement or losses if the billing point and the metering point are not he same
• Easy customer calibration for all-phase corrections
• Transmitting meter with concentrator (extension for existing equipment)
• An additional power supply secures communication even if the measuring voltage fails. In addition, the additional power supply prevents the line between transformer and meter from improper voltage drops.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
13/108
Communication
• Standard dlms communication protocol with the possibility of other standard protocols for network management
• Use of modular communication units separated from measurement
(same solution as ZMD400).
Transmitting contacts
None, or 4 to 8 transmitting contacts, constant impulse frequency up to
40 imps/s, possibility for two contacts with the same value or quadrant splitting.
Broad range of applications
Wall / projection-mounting and rack / flush-mounting with the same printed circuit boards give more flexibility at the place of installation and saves money on spare parts. Plug-in compatible version with ESSAILEC connectors for replacement or extension of system.
ZMQ 2 02 C.4 r4 f6
Network Type
ZFQ
ZMQ
3-phase 3 wire network (F-circuit)
3-phase 4 wire network (M-circuit)
Accuracy Class
02 class 0.2 S according to IEC
Functional Range
C.2
C.4
C.6
C.8 active and reactive measurement, dlms or IEC870 subset active und reactive measurement, dlms protocol additionally losses and CT/VT correction, dlms protocol all functions incl. demand measurement, dlms protocol
Transmitting Contacts
r3 r4 r4a r4aa
4 changeover contacts with symmetric mark/space ratio (4 x u)
4 changeover contacts with fixed pulse width (4 x u)
8 normally open contacts with fixed pulse width (4 x 2a)
4 twin normally open contacts with fixed pulse width (2 x 4a)
Housing
f6: wall mounted housing f9: rack
For more information concerning the meter with the functional range C.2 for the connection to the Landis+Gyr FAG and the communication according to the IEC870 subset please refer to
Chapter 8 on page 97
In this user manual, the communication according to the IEC870 subset will be referred to as IEC870 communication hereafter.
© Landis+Gyr AG
14/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
2.4
Inputs
Block Schematic Diagram
I1
I2
I3
U1
U2
U3
N
E1
E2
E3
Syn
A/D
Filter
Signal processing
A/D
Filter
Calibration
Measuring system
Power supply
Supply monitor
Additional power supply
Flash memory
Microprocessor
Billing data
Load profil data
Display buttons
U
S
U
S
Alarm reset
Calendar clock
Time switch
Control inputs
Tariff control
Measured quantities
Standard functions
Optional functions
Control signals
The main inputs to the meter are:
• Phase voltages U1, U2, U3 and neutral conductor N
-
- to be processed in the measuring system to be monitored by the voltage monitor
- for the three-phase power supply of the meter
• Phase currents I1, I2, I3
-
- to be processed in the measuring system to be monitored by the current monitor
• Control inputs used for:
- selecting of energy tariffs (3 control inputs: E1, E2, E3)
- synchronising the internal calendar clock (1 control input: Syn)
Opto-couplers provide the galvanic isolation and protect the electronic circuits of the meter from interference, which could otherwise enter via the control inputs.
• Additional power supply U
S
to ensure the operation of the meter during interruptions of the measurement voltage
• Push buttons
-
- for display control (2 buttons) for service functions and alarm reset (1 button)
LCD display
Optical interface
Local
RS485 interface
Communication unit with interfaces
Transmitting contacts board
4 changeover or
8 normally open contacts
Optical test output
Alarm output
Digital data
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
15/108
Outputs
The meter has following outputs:
• Single line, 8-digit liquid crystal display (LCD) with back light for local reading of billing data and load profile data and additional information, such as energy flow, type of energy, presence of phase voltages and identification numbers
• Optical test outputs (green LEDs) for either active and reactive energy or I
2
and U
2
• Alarm output (relay and red LED)
• Up to 8 transmitting contacts with selectable signal assignment on the transmitting contacts board (static relays)
• Optical interface for the download of parameterisation data and for local data acquisition by a suitable data acquisition unit (e.g. lap-top computer)
• Local serial interface RS485 for the daisy-chain connection between the individual meters
• Various communication interfaces (e.g. RS485, RS232, modem) for the transfer of billing data and load profile data to the central station.
© Landis+Gyr AG
16/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
Voltage input
Current input
analogue input signals
I1, I2, I3
U1, U2, U3
Input circuits
U
I
, U
U
Signal converter digital input values i, u
Signal processor
Calibration digital output values measured quantities
I, U,
P, Q,
S, fn etc
Microprocessor
±A, ±R, etc.
The measuring system of the meter has the analogue current values I1, I2,
I3 and the analogue voltage values U1, U2, U3 available as input signals.
High resistance voltage dividers reduce the voltages U1, U2, U3 applied to the meter (57.7 V to 132.8 V) to a proportional value of a few mV (U
U further processing.
) for
Compensated current transformers similarly reduce the input currents I1,
I2, I3 applied to the meter (0 A to 2 A or 0 A to 7.5 A). The secondary currents of these current transformers develop voltages over burden resistors. These voltage values are proportional to the input currents, also of a few mV (U
I
).
The meter can be adapted to the required current range (1 A or 5 A) by changing the burden resistors of the current transformers.
The analogue input signals U
U signal converter.
and U
I
are converted to digital values by
Digital instantaneous values of voltage (U) and current (I) for all three phases are then available at the output of the signal converter.
Over an integration interval of 0.2 seconds, the signal processor calculates active, reactive and apparent energy. As a general rule, the measuring system of the ZMQ produces single-phase data while the ZFQ provides data corresponding to its two measuring elements.
The signal processor also provides various instantaneous values such as phase voltages and phase currents as well as diagnostic values (total harmonic distortion, voltage failures etc.).
The values will be available as digital data. They are stored in the output buffer of the signal processor from where they are transferred to the microprocessor by an SPI interface.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
17/108
2.5.5 Microprocessor
Based on the data of the signal processor the microprocessor calculates the measured quantities.
Single phase energy calculation
The calculation of the energy per phase is a two-step procedure:
Active energy
Reactive energy
1. The instantaneous, single-phase values of power are produced by multiplying the instantaneous, single phase values of voltage U and current I.
2. The single-phase values of power are then integrated over the integration period.
The active power is the product of the voltage multiplied by the current component parallel to the voltage I
P
.
I
Q
I ϕ
Calculation per phase of
.
. .
P = U I
P ϕ
I
P
U
The instantaneous value of active power P is then integrated over the integration period of 0.2 seconds to form a digital value of active energy.
For the instantaneous value of reactive power Q the instantaneous values of voltage U and current I must be rotated by +45° and -45° respectively prior to the multiplication.
The reactive power is the product of the voltage multiplied by the current component vertical to the voltage I
Q
.
I
Q ϕ
I
Calculation per phase of
.
.
Q = U I
Q
.
ϕ
I
P
U
The instantaneous value of reactive power Q is then integrated over the integration period of 0.2 seconds to form a digital value of reactive energy.
© Landis+Gyr AG
18/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
C.4
C.6
Depending on the functional range of the meter (C.4, C.6 or C.8), different sets of measured quantities are available.
Meters with the functional range C.4 provide the following measured quantities:
Measured quantity
Active energy import
Active energy export
Reactive energy import
Reactive energy export
Reactive energy in quadrant I
Reactive energy in quadrant II
Reactive energy in quadrant III
Reactive energy in quadrant IV
Energy direction of active energy
ZMQ
+A Sum
–A Sum
+R Sum
–R Sum
+Ri Sum
+Rc Sum
–Ri Sum
–Rc Sum
EFA Sum
ZFQ
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Energy direction of reactive energy EFR Sum Sum
Meters with the functional range C.6 provide the following measured quantities in addition to the C.4:
Measured quantity
Active iron losses (transformer)
Active copper losses (line)
Reactive iron losses (transformer) *
Reactive copper losses (line) *
Total active losses in positive direction
Total active losses in negative direction
Total reactive losses in positive direction *
Total reactive losses in negative direction *
NLA
OLA
NLR
OLR
ZMQ
Sum
Sum
Sum
Sum
+TLA Sum
-TLA Sum
+TLR Sum
-TLR Sum
Net/gross active energy in positive direction
Net/gross active energy in negative direction
+CA Sum
-CA Sum
Net/gross reactive energy in positive direction * +CR Sum
Net/gross reactive energy in negative direction * -CR Sum
Total losses of active energy TLA Sum
Total losses of reactive energy TLR Sum Sum
THD of active energy THD
A
Sum / Phases Sum
* Values for reactive losses are available for compatibility reasons with third-party products. However, Landis+Gyr recommend not to measure reactive losses.
ZFQ
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
19/108
C.8
Meters with the functional range C.8 provide the following measured quantities in addition to the C.6 and the C.4:
Measured quantity
Active energy import
Active energy export
Reactive energy import
Reactive energy export
Reactive energy in quadrant I
Reactive energy in quadrant II
Reactive energy in quadrant III
Reactive energy in quadrant IV
Apparent energy import
Apparent energy export
Apparent energy in quadrant I
Apparent energy in quadrant II
Apparent energy in quadrant III
ZMQ
+A single-phase
–A single-phase
+R single-phase
–R single-phase
+Ri single-phase
+Rc single-phase
–Ri single-phase
–Rc single-phase
+S Sum / Phases
-S Sum / Phases
+Si Sum / Phases
+Sc Sum / Phases
–Si Sum / Phases
Apparent energy in quadrant IV
Current square hours
–Sc Sum / Phases
I
2 h Sum
Sum *
Sum
Voltage square hours U
2 h Sum Sum
* Due to the different type of measurement of the Aron circuit, data for the individual phases are not provided by the ZFQ.
Sum *
Sum *
Sum *
ZFQ
Sum *
Sum *
2.6.1 Calculation of Measured Quantities
Active energy
By scanning the digital output values of active energy A and reactive energy R every 0.2 seconds, energy components (Ws or vars) with varying energy magnitudes are produced at fixed intervals.
The microprocessor calculates the total active energy import +A and the total active energy export -A by summating the raw data of active energy
A1, A2 and A3.
Raw data of active energy
Measured quantities
A1
+A (Import)
A2
Σ
-A (Export)
A3
© Landis+Gyr AG
20/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
Reactive energy
Allocation to the four quadrants
The microprocessor calculates the total reactive energy import +R and the total reactive energy export -R by summating the raw data of reactive energy R1, R2 and R3.
Raw data of reactive energy
Measured quantities
R1
R2
Σ
+R (Import)
-R (Export)
R3
These energy components are scaled by the microprocessor corresponding to the meter constant (primary data) and are then available as measured quantities. The measured quantities can be selected by parameter setting and their measured values are fed directly to the registers to record the energy.
Based on the signs of A and R the microprocessor can allocate the reactive energy to the four quadrants.
• Reactive energy in quadrant I: +Ri
• Reactive energy in quadrant II: +Rc
• Reactive energy in quadrant III: –Ri
• Reactive energy in quadrant IV: –Rc
Export active power
_
Import active power
+ sin ϕ =1 (90°) cos ϕ = 0,5 (60°)
Import reactive power sin ϕ = 0,5 (150°)
+
II
+Rc +Ri
Leading
Q
I
Lagging
S sin ϕ = 0,5 (30°)
U
_
-Ac
-Ai
+Ai
+Ac ϕ cos ϕ
=
1(0°
)
P
I
Lagging Leading
Export reactive power
III
-Ri -Rc
IV cos ϕ = 0,5 (- 60°)
-90°
2.6.2 Demand
The ZxQ meters with the functional range C.8 register the demand of the measured values +a, -A, +S and -S. The meters may register the average demand of the current and the last integration period as well as maximum demand and cumulated maximum demand.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
21/108
The ZxQ meters with the functional range C.8 register the power factor.
The meters may register the instantaneous power factor as well as the average power factor of the current and the last integration period for both energy directions (import and export).
The ZxQ may register the following instantaneous values:
Instantaneous values ZMQ
Active power (instantaneous value)
Reactive power (instantaneous value)
Phase voltages (RMS)
Primary and secondary values
Phase currents (RMS)
Network frequency
Phase angle between voltages
Sum
Sum
U1, U2, U3
ZFQ
Sum
Sum
U12, U32
I1, I2, I3 I1, I3 fn yes yes ϕ U U1-U2 / U1-U3* U12-U32 **
Phase angle between voltage and current ϕ U-I U1-I1, U1-I2,
U1-I3 *
Direction of rotating field yes
Power factor PF C.8 only
* Phase angles will only be displayed if voltage L1 is present.
** Phase angles will only be displayed if all voltages are present.
U12-I1,
U12-I3 ** yes
C.8 only
The ZxQ may register the following diagnostic values:
Diagnostic values ZMQ
Phase failures
Voltage dip table
THD of RMS phase voltages
THD of RMS phase currents
ZFQ
yes
Sum yes
Sum
THD
U
Sum / Phases Sum
THD
I
Sum / Phases Sum
© Landis+Gyr AG
22/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
Various signal sources can be used to select the required tariff. Tariff control may be performed:
• Externally by the three input control signals E1, E2, E3 (with selectable control voltage ranges: 24 V up to 230 V; the control voltage must be specified by the customer). The control input E1 may also be used to enable the bypass feeder operation mode.
• Internally by the calendar clock and the time switch
• By event signals based on threshold values of the monitoring functions, e.g. frequency, voltage
Signals from the various signal sources can be combined to realise a sophisticated tariff structure.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
23/108
Time base
Accuracy
Synchronisation
Time-setting
Power reserve
The internal calendar clock of the ZxQ generates the date and time information, which is used:
• for the date and time information to be displayed
• to control the time switch TOU
• for the time stamps in the load profile, snapshot, stored billing value profile and event log
• for the controlling of the capture period of the load profile
Calendar clock
Crystal
Capture period synchronous capture period
Internal capture period
Network frequency
50/60 Hz
Date and time
Synchronising
The calendar clock either uses the internal crystal or the network frequency as time base (depending on parameterisation).
The network frequency (50 Hz or 60 Hz) may be used as time base, provided it is sufficiently accurate. Tuning is then performed after each full wave, i.e. after 20 ms at 50 Hz. If the network frequency happens to vary by more then 5% the calendar clock automatically switches to the crystal time base.
The crystal features a maximum deviation of 0.5 s per day (<6ppm).
The calendar clock can be synchronised in regular intervals:
• by an external master clock via synchronisation input Syn
• via communication (e.g. by the central station).
The time and date of the calendar clock can be set:
• manually in the set mode in the service menu of the meter
• via communication
A supercap (capacitor of a very large capacity) provides the power reserve for the calendar clock. The power reserve may be extended by the use of a battery.
• Power reserve without battery: 20 days (only after the meter has been connected to the network for at least 300 hours)
• Power reserve with battery: 10 years
© Landis+Gyr AG
24/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
2.8.1 Synchronisation and Time-Setting
Synchronisation
Time-setting
We talk about synchronisation when the clock is adjusted to an external reference in regular intervals. The synchronisation signal is sent to the meter within a predefined time window. Synchronisation is performed in order to make sure that all meters within the network show the same time.
Synchronisation of the meter may take place via the control inputs or via communication.
We talk about time-setting when the time is adjusted outside the synchronisation window. This is the case when, for instance, during meter installation the calendar clock is set to the local time.
The time may be set manually in the set mode or via communication.
2.8.2 Synchronising the Calendar Clock via the Synchronisation Input
The calendar clock can be synchronised by an external master clock (e.g. central station), which sends synchronisation pulses at regular intervals.
Note
There are three possibilities of synchronising the calendar clock using the external synchronisation signal:
• The synchronisation takes place several times per day
-
To the minute or
-
To the capture period
• The synchronisation takes place once per day.
Use only one type of synchronisation
Only one type of synchronisation can be used at a time, either several times per day or once per day.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
25/108
several times per day The "several times per day" synchronisation takes place at regular intervals. The interval is defined by parameter setting.
> 2 s
Synchronisation interval e.g. 15 min
Note
Once per day
< 100 ms bounce-free
Since the synchronisation signal is transmitted at regular intervals (e.g.
00:00h, 00:15h, 00:30h etc) it carries a time information. When, for instance, the meter receives the third synchronisation signal of the day
(00:30h) the calendar clock is synchronised to 00:30h. The reaction of the meter to the synchronisation signal depends on the detected deviation (see
2.8.5 Handling the Deviations
The meter will accept the synchronisation pulse any time but only once within one synchronisation interval.
Ignoring second synchronisation pulse
A second synchronisation pulse within the same synchronisation interval will be ignored.
With the daily synchronisation, the meter allows one time window per day within which the synchronisation pulse must be sent to the meter. The time of the day (e.g. 22:00h) and the width (e.g. one minute) of the window can be defined by parameter setting.
Daily synchronisation time window
00:00h
24:00h
Daily synchronisation pulse
If the "time of the day" parameter is set to 22:00h and the meter receives a synchronisation signal within the defined window, the calendar clock is synchronised to 22:00h. The reaction of the meter to the synchronisation signal depends on the deviation (see
2.8.5 Handling the Deviations
The meter will not accept any synchronisation pulses outside the time window and the signal will therefore have no effect.
© Landis+Gyr AG
26/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
2.8.3 Synchronising the Calendar Clock via Communication
Note
Note
The calendar clock can be synchronised by the central station, which sends the time information to the meter via the selected communication interface.
The time information received is compared with the local time of the meter.
The reaction of the meter to the time information depends on the deviation
(see
2.8.5 Handling the Deviations
Via communication, the time may be synchronised only once per synchronisation interval.
Time synchronisation twice within synchronisation interval
If the time is synchronised a second time within the same synchronisation interval, the capture period is reset no matter how small the deviation.
This is to prevent multiple synchronisation with a small time shift resulting in a large time shift that, if made in one single approach, would have reset the capture period.
Disabling the synchronisation via communication
The synchronisation of the calendar clock via communication may be disabled by setting the parameters of the security system accordingly.
Note
Date and time of the calendar clock can be set manually in the set mode or via communication (e.g. with a laptop computer).
The time information received is compared with the local time of the meter.
The reaction of the meter to the time information depends on the deviation
(see
2.8.5 Handling the Deviations
Setting the time twice within capture period
If the time is set a second time within the same capture period, the capture period is reset no matter how small the deviation.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
27/108
Depending on the time deviation of the internal clock from the external master clock, the adjustment has different effects on the calendar clock.
The following two cases are possible:
• the time deviation is smaller than 2 to 9 seconds (depending on parameter setting) => time shift
• the time deviation is longer than 2 to 9 seconds (depending on parameter setting) => capture period reset time shift capture period reset
0 s 2...9 s
Time deviation
Time shift
Threshold can be parameterised
If the difference between the internal clock and the master clock is between one second and the parameterised threshold, the time is adjusted to the synchronisation time. Advancing or setting back the clock is only allowed once per synchronisation interval. The affected capture period is shortened or elongated by the number of seconds of the time shift.
This time shift is allowed only once per synchronisation interval. Thus further time shifts within the same synchronisation interval will restart the capture period.
Capture period reset If the difference between the internal clock and the master clock is greater than the parameterised threshold, the time for the calendar clock is set to the synchronisation time. Setting the time always causes the termination of the present capture period and the start of a new period. An entry in the event log will also be made.
Setting the time to either the begin or the end of the capture period results in one shortened capture period.
Setting the time to a time within the capture period results in at least one shortened capture period. Load profile entries for shortened capture periods are identified by a corresponding status entry and are declared invalid.
© Landis+Gyr AG
28/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
2.9 Registers
The following registers are available for the analysis of the individual measured values:
• 36 total energy registers (no tariffs)
• 24 rated energy registers
• 1 register for the instantaneous power factor (C.8 only)
• 2 registers for the average power factor of the last integration period for energy import and export (C.8 only)
• 4 registers for average demand of the current integration period (C.8 only)
• 4 registers for average demand of the last integration period (C.8 only)
• 8 registers for maximum demand (C.8 only)
• 8 registers for cumulated maximum demand (C.8 only)
• other registers for values of voltage and current, network frequency, phase angles etc.
max. 36 total energy registers
display local communication tariff control
max. 24 rated energy registers
communication
instantanteous power factor
test output
average power factor
(last IP)
stored billing value profile
4 registers for average demand
(current IP)
4 registers for average demand
(last IP)
daily snapshot load profile
8 registers for maximum demand
8 registers for cumulated maximum demand
tariff control
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
29/108
2.10 Memory
A non-volatile memory (FLASH memory) contains the configuration and parameterisation data of the meter. It also contains the load profile, the snapshot, the stored billing value profile and the event log data.
All data stored in the flash memory is prevented from loss caused by voltage failures. No battery is required to do so.
Load profile memory size
The current statuses of various registers are saved to the load profile at regular intervals.
Each load profile entry consists of the measured value itself (energy registers = 8 bytes, diagnostic values = 4 bytes), a time stamp of 8 bytes and a status code of 4 bytes.
The ZxQ meters feature a load profile memory of 1.8 MB. The memory depth of the load profile is calculated with the formula below. memory depth
[ days
]
= used
1'810'000 memory byte per
× capture entry
[ byte
] period
× 24 h × 60 min
A minimum of 100 days is guaranteed with 36 captured registers and a capture period of 15 minutes.
The load profile is organised as a circular buffer, i.e. the oldest entry will be overwritten by the most recent entry.
2.10.2 Snapshot
The meter stores the current value of the energy registers to the snapshot profile every day. Which registers are stored to the snapshot profile and at what time of the day the storage takes place can be selected by parameterisation.
The snapshot profile may register a maximum of 36 registers with a maximum of 40 entries each.
2.10.3 Stored Billing Value Profile
At the end of the billing period, the meter stores the current value of the registers to the stored billing value profile. The billing period always corresponds with the capture period of the load profile. Which energy registers and/or demand registers are stored to the stored billing value profile can be selected by parameterisation.
The stored billing value profile is available with meters with the functional range C.8 only. The stored billing value profile may register a maximum of
36 registers with a maximum of 40 entries each.
© Landis+Gyr AG
30/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
Event log memory size
Events that occur sporadically are stored in the event log. The user may select what events trigger an entry in the event log. The event log is used to analyse the behaviour of the network as well as to supervise the correct application of the meter.
In the event log, a minimum of 256 event entries can be stored, all of which consist of the time stamp and the event number.
The event log is organised as a circular buffer, i.e. the oldest entry will be overwritten by the most recent entry.
The supply voltages for the meter are obtained from the three-phase network, whereby the phase voltage may vary over the entire voltage range without the power supply having to be adjusted. As the power supply even works with only one phase voltage available, single-phase voltage dips do not affect the operation of the meter.
A voltage monitor ensures correct operation and reliable data recovery in the event of a all-phase voltage interruption and correct restarting when the voltage is restored.
Because the three-phase network can be switched off in grid metering applications, the meter is equipped with an additional power supply in order to prevent the meter from being switched off.
The additional power supply supplies its voltage in parallel to the normal network supply and it ensures an uninterrupted operation of the meter, so that the meter can be read at any time. In a special mode, the meter may also be powered by the additional power supply only (optional, depending on parameter settings). As a result, there is no load on the line between transformer and meter which prevents the line from voltage drops.
The transmitting contacts module is fitted inside the meter and is therefore secured by verification seals. It features up to four changeover contacts or up to eight normally open contacts (solid-state relays). The contacts are used to transmit energy pulses and/or energy direction information or status information.
The transmitting contacts either transmit pulses with a defined pulse length
(20 ms, 40 ms or 80 ms) or pulses with a mark-to-space-ratio of 1.
There are transmitting contact modules with a pre-defined terminal allocation while the terminal allocation of other modules can be parameterised according to the customer’s specification.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
© Landis+Gyr AG
31/108
2.14 Communication Unit (Option)
The optional communication unit is a complete unit housed in its own case.
If mounted, it is situated under the front cover. Therefore, it is secured by a utility seal and can be mounted and replaced in the field if necessary. It contains communication interfaces (e.g. RS232, RS485, modem) as required for remote reading of the meter data. Two different communication units are available.
MAP190
MAP120
There are two software tools available with the meter, which enable easy parameter setting and communication with the meter.
The software Landis+Gyr MAP190 is used for setting up complete parameter sets off-line (parameter editor). The prepared parameter sets can then be downloaded to the meter via the optical interface. The software MAP190 is used for the order processing by regional companies.
The software Landis+Gyr MAP120 is used:
• to communicate with the meter according to dlms
• to perform service tasks
• to set certain parameter ranges such as primary data, the time switch etc.
• to reparameterise the meter and the communication unit
© Landis+Gyr AG
32/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Description of Unit
3
4
Wall-mounting f6
1
9
8
5
6
7
2
2 Manufacturer's or verification seal
3 Front window with face plate
4 Front door with information plate and terminal connection diagram on rear side
5 Cover
6 Base
9 Utility's seal after installation
Wall-mounting f6
Rack-mounting f9
3
1
1 Manufacturer's or verification seal
2 Utility's seal after installation
3 Front cover with face plate and additional information
5 Housing
4
2
6
Usage of Seals
at manufacturer's site
5
Sealing at utility's site - no verification necessary
7 none utility's seal utility's seal
Sealing at utility's site verification necessary manufacturer's seal verification seal verification or utility's seal utility's seal 9 none
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
© Landis+Gyr AG
33/108
Rack-mounting f9
at manufacturer's site
1 (left) manufacturer's seal manufacturer's seal
1 (right) manufacturer's seal manufacturer's seal
2 none
Sealing at utility's site - no verification necessary
6 binder
Sealing at utility's site verification necessary manufacturer's seal verification seal
Wall-mounting f6
Rack-mounting f9
The manufacturer's seal is secured after the meter has been assembled, tested, and calibrated.
For the f6, the manufacturer's seal secures the meter cover so that the front window can not be opened without removing the seal. The ZxQ is delivered with two manufacturer's seal; one at the upper left side of the front window and one on the upper right side. Once certified, the manufacturer's seal on the upper right side of the front window is replaced with the verification seal.
For the f9, the manufacturer's seal secures the meter base so that it can not be opened without removing the seal. The ZxQ is delivered with two manufacturer's seals at the back of the base; one at the upper right side and one at the lower left side. Once certified, one or both of the manufacturer's seals is replaced with the verification seal.
Note
Wall-mounting f6
Rack-mounting f9
Note
The verification seal is secured after the meter's measuring capability has been verified.
Damaging the verification seal
In countries with an obligatory verification, the verification seal is awarded by the verification body and guarantees the correct measurement performance of the meter according to the local regulations.
Breaking a verification seal renders the official verification invalid. Breaking a verification seal also renders the guarantee invalid, as defined in the general delivery conditions.
Once certified, the manufacturer’s seal on the upper right side of the front window is replaced with the verification seal.
Once certified, one or both of the manufacturer's seal at the back of the meter case is replaced with the verification seal.
Removal of communication unit on rack mounted version f9
For f9, the communication unit can only be removed or exchanged for another communication unit or dummy by opening the meter case and breaking the verification seal.
© Landis+Gyr AG
34/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
Wall-mounting f6
Rack-mounting f9
The utility's seals are secured after the meter is prepared for use and commissioning.
For the f6, the utility's seal secures the hinged front door, which allows access to the battery compartment, the alarm reset button and the communication unit. The information plate with the connection diagram on the rear side is also located in the front door.
For the f9, the utility's seal secures the hinged front cover, which allows access to the battery compartment and the alarm reset button.
2
3
4
1
Alarm reset button
Communication unit or dummy
Information plate with connection diagram
2
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
© Landis+Gyr AG
35/108
A 6 V lithium battery can be inserted in the battery compartment to provide power to the calendar clock and display.
The alarm reset button has three functions:
1. Reset an alarm.
2. Select the service menu from the display check.
3. Perform the cursor function in the set mode.
A communication unit is installed when the meter is used in a system where remote meter reading is employed. Remote meter reading requires communication between the meter and the central station, which the communication unit provides via a serial interface or modem.
Remote meter reading, time synchronisation with the central station time, meter check to ensure the meter is functioning correctly, and parameter setting can be performed using the communication unit.
If a communication unit is not required, a dummy is inserted.
For f6, the terminal cover protects the meter terminal connecters. The terminal cover is secured with two utility’s seals to prevent unauthorised access, both for safety and anti-tampering reasons.
© Landis+Gyr AG
36/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
The face plate is located behind the front window, which is secured by a manufacturer's or verification seal. The face plate is designed to customer specifications. It contains all relevant data about the meter.
3.5
Recesses in the front window permit operation of the display buttons "up" and "down" for control of the liquid crystal display.
Information Plate f6
The information plate is located in the hinged front door. It contains all relevant data about the meter. The front door is secured by the utility's seal after the meter has been connected according to the terminal connection diagram which is located on the back of the face plate. The terminal connection diagram is only visible with the door open.
On the information plate you will find:
• explanations to the display
• the pulse values of the transmitting contacts
• the hint "U
S
< 0.1 VA" if the meter is supplied via additional power supply only (max. load of 0.1 VA on the measurement voltage, optional)
• the meter constant R2 for testing meters with primary data on the testing station (this is to avoid roundoff errors when calculating the secondary meter constant).
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
© Landis+Gyr AG
37/108
3.6 Terminal Connection Diagram f6
The terminal connection diagram is located on the back of the face plate and specifies how the meter is to be connected. It is only visible with the front door open. After the connections have been made, the front door is secured by the utility's seal.
3.7
3.8
Face Plate and Information Plate f9
The f9 face plate and information plate is located in the front cover, which is secured by the utility's seal. When the utility's seal is broken, the front cover can be opened. The face plate and information plate is designed to customer specifications. It contains all relevant data about the meter.
Recesses in the front cover permit operation of the display buttons "up" and "down" for control of the liquid crystal display.
Connection Diagram f9
The connection diagram is located on the top of the case and specifies how the meter is to be connected. The connection diagram is visible when the meter is drawn out of the rack.
© Landis+Gyr AG
38/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
3.9 Dimension Diagrams f6
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
© Landis+Gyr AG
39/108
3.10 Dimension Diagrams f9
© Landis+Gyr AG
40/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
3.10.2 Racks f9.10 for meters with cable connection f9.11 for one meter with direct connection
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
© Landis+Gyr AG
41/108
f9.12 for two meters with direct connection
Front view
8,5
482 (19")
465 8,5
© Landis+Gyr AG
42/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
201
Cut-out for panel-flush mounting
7
465
451
7
Cut-out for 19" Chassis
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
© Landis+Gyr AG
43/108
1. Select the position for mounting the meter.
2. Mark the three fixing points (suspension triangle) on the mounting surface: horizontal base of suspension triangle = 150 mm height of suspension triangle for open mounting = 206 mm
Warning
75 mm
150 mm
3. Drill the three holes for the fixing screws.
4. Unscrew the meter terminal cover.
5. Fix the meter with the three fixing screws on the mounting surface.
Dropping meters
The meters can cause injuries if dropped.
They must be held securely during installation.
Meters which have dropped must not be installed, even if no damage is apparent. They must be returned for testing to the service and repair department responsible (or the manufacturer). Internal damage can result in functional disorders or short-circuits.
© Landis+Gyr AG
44/108
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Mechanical Description
4.1 Prerequisites
Danger
Danger
Warning
Galvanic isolation
The measuring circuits and auxiliary circuits (additional power supply, tariff control input, synchronisation input, transmitting contacts, communication interfaces) must be galvanically isolated.
Voltage paths must be fused
When installing the meter, all voltage paths (measurement voltage and all auxiliary circuits such as the auxiliary power supply and the tariff control voltage) must be fused by max. 6 A delay fuses.
Separation of voltage connections and communication lines
The voltage connections must be physically separated from the communication lines in accordance with local laws and regulations.
Note
Recommendation
We recommend that twisted and shielded cables are used for the communication lines. One end of the cable shield should be connected to the ground.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
45/108
4.2
Note
Connect the f6 Meter
Assumption of mounted meter
It is assumed that the meter is already mounted. How to mount the meter
3.11 Mounting f6
The f6 is connected according to the terminal connection diagram located in the front door. The following is an example.
Transmitting contacts
© Landis+Gyr AG
Pulse transmitting contacts
Energy direction contacts
Static output contact
Communication unit
Additional power supply
Tariff control inputs
Alarm contact
Synchronisation input
I1
U1
I1 I2
U2
I2 I3
U3
I3
N
RS485 interface
The 12 spring clamp connectors are located on the transmitting module and transmit measured values as pulses to telemetering instruments. They are passive output contacts, i.e. energised by the receiver.
The function of each output depends on the connected PCB. Assigning the functions to the corresponding connector is determined in the software.
The connector numbers remain the same, whichever PCB is connected.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Communication interface
Depending on the communication unit type, the number of RJ-12 connectors can vary. When spring clamp connectors are available (e.g. at
B4 and M4) they are not used. The RJ-12 connectors are located on the communication unit. Communication between the meter and the central station can be achieved via a PSTN modem, RS485 interface, or RS232 interface.
The four spring clamp connectors on the left provide connection for the
Additional power supply additional power supply
.
Inputs and outputs
The five spring clamp connectors on the right of the additional power supply provide connection for tariff control inputs. If the meter is shipped without external tariff control, these terminals will not be labelled.
Serial interface
The three spring clamp connectors on the right of the tariff control inputs is the synchronisation input.
The two spring clamp connectors on the right of the synchronisation input is the alarm contact.
The two RJ-12 connectors are located on the power supply board, and provide local serial RS485 connection of other meters (daisy chain). They are connected in parallel so that the use of a T-piece is not necessary.
4.2.3 Procedure
Danger
Danger
Dangerous voltage on conductors
Dangerous voltage is present on the conductors that the meter is to be connected to.
Contact with the conductors when under voltage will result in severe personal injury or death.
The conductors must not be under voltage when connecting or disconnecting the meter.
Installation and de-installation of the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
Dangerous voltage on current transformers
Dangerous voltage is produced by the current transformers when the secondary circuit is broken while current is flowing in the primary.
Contact with the transformers when under voltage will result in severe personal injury or death. The high voltage produced will destroy the transformers.
The current transformer secondary circuit must be short-circuited before de-installing the meter. Installation and de-installation of the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
47/108
Danger
Missing transformer earthing
Voltage transformers in medium and high voltage systems that are not earthed on the secondary may reach dangerously high voltage values on the secondary.
Voltage transformers are usually earthed on the secondary. If the voltage transformer is not earthed, severe personal injury or death can result if contact is made with the meter and the meter will be damaged beyond repair.
If the voltage transformers are not earthed, special precautions must be taken when working at the meter. Installation and de-installation of the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
Connect Current and Voltage Connectors
1. Shorten the current and voltage connecting wires to the required length and then strip them to fit the connectors.
2. Insert the current and voltage connecting wires to the terminal numbers as shown in the connection diagram.
3. Tighten (torque up to 1.7 Nm) the terminal screws using the torque screwdriver size 2.
Connect Control Inputs and Outputs and Transmitting Contacts
4. Shorten the connecting wires of the control inputs and outputs to the required length and strip them for approx. 4 mm (wires and strands up to 2.5 mm
2
can be connected).
5. If stranded wire is used, it is recommended to fit it with ferrules for connection.
6. Connect the connecting wires of the control inputs and outputs as shown on the terminal connection diagram to the spring clamp connectors as follows:
Insert a size 1 screwdriver, turning it slightly upwards, in the upper opening.
© Landis+Gyr AG ap pr ox
. 4
m m
Place the stripped connecting wire in the lower opening and hold it there securely.
Withdraw the screwdriver. The connecting wire is now firmly fixed.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Avoid bare parts of wire
When voltage is applied, any bare part of the wire will become live. Ensure no bare wire is visible above the terminal edge.
Danger
If this is not the case, the stripped part of the wire must be shortened as necessary.
Connect Communication and Serial Interfaces
7. Plug in the ready-made telephone cables as shown on the terminal connection diagram.
Power on
Warning
Incorrect connections could damage the meter or result in the meter measuring incorrectly.
We recommend all connections be checked before applying power.
8. Open circuit the current transformer secondary circuit using the provided assembly.
9. Switch on the voltage and current.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
49/108
4.3 Connect the f9 Meter
The f9 is connected according to the connection diagram located on the top of the case. The following is an example.
© Landis+Gyr AG
Communication unit
Synchronisation input
RS485 interface
Alarm contact
Pulse output contacts
Energy direction contacts
Static output contact
Tariff control inputs or bypass feeder operation on/off
Additional power supply
Voltage inputs Current inputs
The f9 is equipped with Essailec connectors for direct plug-in into a prewired rack. The rack is pre-wired according to the plug connection diagram.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
4.3.3 Procedure
Danger
Warning
Warning
High voltage on transformer
High voltage is produced by the current transformers when the secondary circuit is broken while current is flowing in the primary.
Contact with the transformers when under voltage will result in severe personal injury or death. In addition, the high voltage produced will destroy the transformers.
The current transformer secondary circuit must be short-circuited before de-installing the meter. Connecting and disconnecting the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
Power on
Incorrect connections could damage the meter or result in the meter measuring incorrectly.
We recommend all connections be checked before applying power.
Dropping meters
The meters can cause injuries if dropped.
They must be held securely during installation.
Meters which have dropped must not be installed, even if no damage is apparent. They must be returned for testing to the service and repair department responsible (or the manufacturer). Internal damage can result in functional disorders or short-circuits.
1. Open-circuit the current transformer secondary circuit using the provided assembly. (The detailed procedure depends on the transformers being used.)
2. Plug the f9 into the pre-wired rack.
3. Tighten both meter fixing screws.
4. Switch on the voltage and current.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
51/108
Key:
© Landis+Gyr AG
The power must be connected and all 3 phases under load. If the phase voltages are present only, the optical test outputs are continuously lit.
R
Short press down display button (<2s)
Long press down display button (>2s)
Short press up display button (<2s)
Long press up display button (>2s)
Short press down display button until "End" is displayed then long press down display button
Alarm reset button (under utility's seal)
1.
2.
Check whether the operating display is shown. An 'FF' indicates fatal errors or alarms.
Operating display
Check phases L1,
L2, and L3 are present and in the correct phase sequence, i.e. L1-
L2-L3.
Phase check
If one phase is not present or the voltage is < 45% Un, the relevant symbol is absent.
With the normal phase sequence the symbols are displayed continuously. If the meter is connected with reversed phase sequence (e.g. L2-L1-L3) the symbols flash. energy direction arrows indicate whether energy is being imported (+) or exported (-).
P = active energy,
Q = reactive energy.
Energy direction indicator
4.
5.
R
All segments of the display are illuminated
Enter service menu
Display check
Set mode
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
6.
7.
8.
Select menu item
Enter installation diagnostic list
Check the phase voltages:
Voltage L1: Code 32.7
Voltage L2: Code 52.7
Voltage L3: Code 72.7
Check the phase currents:
Current L1: Code 31.7
Current L2: Code 51.7
Current L3: Code 71.7
Check the phase angles:
9.
10.
11.
12.
Phase angle U(L1)
Phase angle U(L2)
Phase angle U(L3)
Phase angle I (L1)
Phase angle I (L2)
Phase angle I (L3)
Advance display until End.
Back to the service menu.
Advance display until End.
Exit service menu.
Code 81.7.0
Code 81.7.1
Code 81.7.2
Code 81.7.4
Code 81.7.5
Code 81.7.6
Installation diagnostic
Note: Current must be flowing to show the phase angles
End of installation diagnostic
Service menu
End of service menu
Operating display
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
53/108
4.4.2 Testing the Transmitting Contacts
In order to check the wiring of the transmitting contact the meter is switched to transmitting contact test mode. While in the test mode the meter send pulses with a frequency of 1 Hz to the pulse receiver.
The transmitting contact test mode is only available with meters with the functional range C.4, C.6 and C.8.
Operating display
Note
1.
All segments of the display are illuminated
Enter service menu
Display check
2.
R
Set mode
3.
Select required setting
Transmitting contact test mode display
4.
5.
6.
Switch on transmitting contact test mode
1 = transmitting contact test mode switched on
0 = transmitting contact test mode switched off
Check whether the 1 Hz pulses of the transmitting contacts are received by the transcoder and whether they are allocated to the correct registers.
Switch off transmitting contact test mode
Advance display until End
7.
End of transmitting contact test mode display
8.
Exit service menu Operating display
Availability
The transmitting contact test mode is not available in some countries. In these countries it cannot be activated.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
4.4.3 Set Date and Time
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
R
R
R
R
Operating display
All segments of the display are illuminated
Enter service menu
Display check
Set mode
Enter set mode Identification number
Select required setting
Date, old value
Select next digit to be changed
Digit flashes
Change digit value Digit flashes
Select digit to be changed
Next digit flashes
Repeat steps 5 - 7 for all digits to be changed All digits flash
Confirm new setting
Repeat steps 4 - 9 for all settings to be changed
Date, new value
Advance display until End
End of set mode
Service menu
12.
13.
Back to service menu
Advance display until End
Exit service menu
14.
End of service menu
Operating display
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
55/108
4.4.4 Set Battery Low Indicator
1.
2.
3.
4.
R
All segments of the display are illuminated
Enter service menu
Select menu item
Change setting:
Operating display
Display check
Set mode
Battery on / off display
5.
6.
1 = battery low indicator on
0 = battery low indicator off
Advance display until End
Exit service menu
End of battery on / off display
Operating display
4.5 Sealing
When the installation check is complete, the utility's seals may be applied.
1. Screw on the terminal cover (f6 only).
2. Apply utility seals using the sealing pliers.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
4.6 Disconnect the f6 Meter
4.6.1 Procedure
Danger
Danger
Dangerous voltage on conductors
Dangerous voltage is present on the conductors that the meter is connected to.
Contact with the conductors when under voltage will result in severe personal injury or death.
The conductors must not be under voltage when connecting or disconnecting the meter.
Installation and de-installation of the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
Dangerous voltage produced by current transformers
Dangerous voltage is produced by the current transformers when the secondary circuit is broken while current is flowing in the primary.
Contact with the transformers when under voltage will result in severe personal injury or death. The high voltage produced will destroy the transformers.
The current transformer secondary circuit must be short-circuited before de-installing the meter. Installation and de-installation of the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
Power off
1. Short-circuit the current transformers using the provided assembly.
2. Switch off the voltage. The phase voltage display (L1 L2 L3) disappears.
3. Switch off tariff inputs and synchronisation input. Check if the corresponding indicators disappear from the display.
4. Switch off the voltage for the additional power supply.
5. Check that all connections are free from voltage.
6. Remove the two utility's seals on the terminal cover, release the two screws and remove the terminal cover.
Disconnect Voltage and Current
7. Loosen the terminal screws and remove the wires of the measuring voltage and current.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
57/108
Disconnect Control Inputs and Outputs
8. Disconnect the connecting wires of the supply inputs and outputs from the spring clamp connectors as follows:
Withdrawing the wire
Note
Withdrawing the wire with the terminal closed can damage the terminal.
Insert a size 1 screwdriver, turning it slightly upwards, into the upper opening
Withdraw the wire from the connector.
Precautions on disconnected wires
Withdraw the screwdriver.
Note
The disconnected wires should be isolated and may also be numbered for convenience when reconnecting.
Disconnect Communication Interfaces
9. Unplug the ready-made telephone cables from modems and serial interfaces.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
4.7 Disconnect the f9 Meter
4.7.1 Procedure
The f9 can be directly connected or cable connected.
Direct connection
1. Loosen both meter fixing screws.
Cable connection
Danger
2. Carefully withdraw the meter from the rack.
Dangerous voltage on current transformers
Dangerous voltage is produced by the current transformers when the secondary circuit is broken while current is flowing in the primary.
Contact with the transformers when under voltage will result in severe personal injury or death. The high voltage produced will also destroy the transformers.
The current transformer secondary circuit must be short-circuited before de-installing the meter. Installation and de-installation of the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
1. Short-circuit the current transformers using the provided assembly.
(the detailed procedure depends on the transformers being used.)
2. Switch off the voltage. The phase voltage display (L1 L2 L3) disappears.
3. Switch off the voltage for the tariff inputs and the synchronisation input. Check if the corresponding indicators disappear from the display.
4. Switch off the voltage for the additional power supply.
5. Loosen both meter fixing screws.
6. Carefully withdraw the meter from the rack.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Installation / De-installation
© Landis+Gyr AG
59/108
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
5 Operation
1 Display
2a Display button up
2b Display button down
4 Optical test outputs
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
61/108
5.1.1 Display
The LCD (liquid crystal display) is provided with background lighting for easier reading.
When a display check is made, all segments of the display are illuminated.
1
2 3 4
Object Identification
System
1
5
Energy direction indicator
6
P = Active energy (A) Q = Reactive energy (R)
7
4
5
2
3
D
E
+ = import - = export
Phase voltage display (flashes if phase sequence is reversed)
Battery low indicator
Unit field (W, var, VA, k…, M…, …h, V, A, h, Hz)
Display code (8 digits). A code identifying the values in the value field.
The code is according to the Object Identification System, described below
Arrow symbols for status information according to face plate 6
7 Value field (8 digits)
The B:C.D.E.F structure applies to Object Identification System (OBIS)
B Defines the channel number, i.e. the number of the input of a metering equipment having several inputs for the measurement of energy of the same or different types (e.g. in data concentrators, registration units). This enables data from different sources to be identified.
C Defines the abstract or physical data items related to the information source concerned, e.g. active power, reactive power, apparent power, cosφ, current or voltage.
Defines types, or the result of the processing of physical quantities according to various specific algorithms. The algorithms can deliver energy and demand quantities as well as other physical quantities.
Defines the further processing of measurement results to tariff registers, according to the tariffs in use. For abstract data or for measurement results for which tariffs are not relevant, this value group can be used for further classification.
F Defines the storage of data according to different billing periods.
Where this is not relevant, this value group can be used for further classification.
To simplify the reading of the display code, individual parts of the OBIS code can be omitted. The abstract or physical data C and type of data D must be shown.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
62/108 Operation
Examples
Note
1.8.0
1 = all-phase active power in positive direction
8 = cumulative value (meter reading)
0 = total energy (no tariffs)
0.9.1
Local time
Display code
The display codes are parameterisable for all measured quantities.
Therefore, they may differ from the OBIS code.
The most important display codes are annotated on the face plate.
5.1.2 Arrows in Display
Example
The arrow symbols in the display are used to give status information according to the face plate.
The twelve arrows my be used to indicate the following statuses:
Currently active tariff for active energy
Currently active tariff for reactive energy
Time/date is invalid
The meter is in the set mode
The meter is in the test mode
The meter communicates locally
The meter communicates with the master station
A customer calibration has been made
T1A, T2A, T3A
T1R, T2R
RTC
SET
TEST
LC
MC
Cal
The additional power supply U
S is present U
S
T1A T2A T3A T1R T2R RTC SET TEST LC MC Cal U s
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
63/108
Up display button
Down display button
The display is controlled using the up and down display buttons.
A short press of either button (< 2 seconds):
• Changes the operating display to display check
• Opens the display menu from the display check
• Runs sequentially through menus from item to item, and in lists from value to value (either forwards or backwards).
A long press of either button (> 2 seconds):
• Opens a selected sub-menu
• Returns to the next higher level when End is displayed
• Browses through lists from main value to main value (either forwards or backwards).
Simultaneously
pressing both buttons cancels the function in use and returns to the operating display.
The optical interface enables:
• Read out of meter data
• Parameter setting using MAP 120 service tool.
These functions are performed via a magnetically attached optical reading head.
The optical interface also functions as an optical switch. A light beam, e.g. from a torch, has the same function as the down display button. This enables reading to be made from a distance, e.g. through a protective glass screen in front of the meter.
The two green optical test outputs, one for active energy and one for
reactive energy
are used to test the meter. They transmit pulses corresponding to the power applied.
In a no load state, when no current is flowing, the optical test outputs are continuously illuminated.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
64/108 Operation
The red alarm LED indicates that the meter is not functioning correctly.
• A constantly lit alarm LED indicates that an alarm has been issued. An alarm indicates an internal meter error that prevents the meter from measuring correctly.
For more details about alarms please refer to
r
• A blinking alarm LED indicates that an operational indication has been issued. An operational indication can indicate an internal condition such as a low battery voltage or an external condition such as a missing phase voltage.
For more details about operational indications please refer to
Operational Indications on page 85
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
65/108
Operating display
Display check
Display menu
Display list
Laod profile
Event log
R
Service menu
Daily snapshot
Stored billing value profile
Losses
Grid diagnostic
End of display menu
Short press down display button (<2s)
Long press down display button (>2s)
Short press up display button (<2s)
Long press down display button (>2s)
Short press down display button until "End" is displayed then long press down display button
R
Alarm reset button (under utility's seal)
The operating display is shown when the display buttons have not been operated. It can be fixed, showing only one value or rolling, showing several values alternately.
The display menu is accessed using the display buttons.
The above allocation of displays to the display menu is an example.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
66/108 Operation
2.
3.
4.
1.
All segments of the display are illuminated
Display first menu item
Select menu item
Back to operating display
Operating display
Display check
Display list
Load profile
Event log
Daily snapshot
Stored billing value profile
Losses
Grid diagnostic
End of display menu
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
67/108
Note
For Germany
In Germany, this list may only contain certified values.
1.
Select display list
2.
3.
4.
5.
6.
Enter display list
Select main value
Select required value (main value or stored value)
Repeat steps 3 and 4 for all required readouts
Long press: display main values only
Short press: display main values or stored values
Advance display until End
Display list
First main value
Other main values
Main value or stored value
End of display list
Exit display list
7.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
68/108 Operation
1.
Select load profile
Enter load profile
2.
3.
4.
5.
Select required entry
Enter related load profile value list
Select entry display of all entries (max.
36)
AutoScroll changes every 2 seconds
7.
8.
Repeat steps 5 and
6 for all entries to be checked
Back to date selection
9.
Select the next date, open list as step 4
10. Advance until End (at the end of date list)
11.
Exit load profile
Load profile
Date of last entry
Date x
Time of first entry
Time of next entry
Status code
Active energy import
End of value list
Next date
End of load profile
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
69/108
1.
Select event log Event log
2.
Enter event log Date of last entry
3.
Select required entry
Time
Event number
+A energy register
-A energy register
+R energy register
-R energy register
Date of next entry
4. Repeat step 3 for all entries to be checked
5.
Jump to end of event log
End of event log
6.
Exit event log
Which events are recorded in the event log is determined by the parameter settings. The time and date of the event is recorded together with a code determining the cause of the event. The most important events are:
Number Event
1 Parameters influencing the measurement data changed
7
9
10
11
2
3
4
5
13
17 - 22
All rated energy registers cleared
Load profile and/or energy profile cleared
Event log cleared
Battery voltage low
Battery voltage OK
Summer time changeover
Clock adjusted (old date/time)
Clock adjusted (new date/time)
Status of control inputs changed
Measuring voltage (undervoltage, overvoltage L1, L2, L3)
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
70/108 Operation
25 - 27
47
55 - 57
58
59
61
62
66 - 96
Measuring current (overcurrent L1, L2, L3)
Bypass feeder operation mode active
Current without phase voltage L1, L2, L3
Missing additional power supply
All registers cleared
Active power too high (depending on parameter setting)
Reactive power too high (depending on parameter setting)
Event log entries resulting from error messages
121-123 Phase voltage without current L1, L2, L3
125-127 Phase failures L1, L2, L3
Further information on events is given in the Functional Description, H71 0200 0216.
1.
2.
3.
4.
5.
6.
Select daily snapshot
Enter daily snapshot
Select required entry
Repeat step 3 for all required snapshots
Jump to end of daily snapshot
Exit daily snapshot
Daily snapshot
Most recent snapshot of the first register
Most recent snapshot of the second register
After displaying the most recent snapshots of all registers, the meter displays the penultimate snapshots of all registers and so on.
End of daily snapshot
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
71/108
5.2.6 Stored Billing Value Profile
1.
2.
3.
4.
5.
Select stored billing value profile
Open stored billing value profile
Select required value
Repeat step 3 all required readings
Advance display until End
Stored billing value profile
Most recent stored value of the first register
Most recent stored value of the second register
After displaying the most recent stored value of all registers, the meter displays the penultimate stored value of all registers and so on.
End of energy profile
6.
Exit stored billing value profile
5.2.7 Losses
1.
2.
3.
4.
5.
6.
Select losses
Open losses
Select required value
Repeat step 3 all required readings
Advance display until End
Exit losses
Losses
First losses value
Selected value
End of losses
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
72/108 Operation
1.
2.
3.
4.
5.
6.
Select grid diagnostics
Open grid diagnostics
Select required value
Repeat steps 3 all required readings
Advance display until End
Exit grid diagnostics
Grid diagnostics
First grid diagnostic value
Selected value
End of grid diagnostic values
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
73/108
5.3 Meter Operation in Systems
5.3.1 Remote Meter Reading in Energy Production Applications dlms Protocol
IEC870 Protocol
The ZxQ is most suitably employed in production and transmission networks and by large industrial consumers. Such networks and consumers seldom read their meters manually on-site but employ automatic remote
meter reading
.
The communication with meter takes place using the dlms protocol according to the IEC62056 series.
Remote meter reading requires communication between the meter and the
central station
. This is achieved using a communication unit via a serial interface or modem. Normally the central station is scheduled to call each meter in the system and to acquire the required data. The following functions can be performed:
• Meter reading; acquisition of meter reading and status information of the meter
• Time synchronisation; with the central station time
Communication with the meter can be established using the standard dlms protocol according to IEC62056 series.
Meters with the functional range C.2 can communicate using the protocol according to the IEC870 subset.
The meter is connected to a transcoder (e.g. Landis+Gyr FAG) via the local RS485 interface. The transcoder requests the meter every minute to send the current data. Every measured value that is transmitted to the transcoder carries a unique identification number.
For more detailed information please refer to
Chap er 8 on page 97
5.3.2 Types Communication
Communication between the central station and the meter can be performed using any of the following types of communication:
• Dedicated (leased) lines
• Permanently installed connections, bus systems, etc.
• Public telephone network using PSTN modems
• Public mobile telephone network using GSM modems
• Others such as ISDN and TCP/IP.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
74/108 Operation
The following types of communication units (CU) are specially designed for use with the ZxQ:
Communication units B4
with RS485 and RS232 interfaces (dlms)
Communication units M22/V34b
with PSTN modem and RS485 interfaces (dlms)
Communication units G22 (for f6 only)
with GSM modem and RS485 interfaces (dlms)
Communication units E22
for TCP/IP and RS485 interfaces (dlms)
Communication units Q22
for RS485 interfaces (IEC870-5-102 and/or dlms)
For further information about communication units refer to document
H71 0200 0144, Survey of Communication Applications.
5.3.4 MAP 120 Service Tool
The MAP 120 Service Tool supports both the meter and communication unit during all phases of their life cycle. It is used to:
• Initial setting of application-specific parameters
• Testing and verification on site
• Register read-out on site
• Change parameters on site; functions, switching tables, tariffs, etc. can be altered by changing parameters.
• Installation and service on site.
Meter reading
Set & reset parameters
Test and certification
Installation
Meter reading
Service
MAP 120
Service Tool
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Operation
© Landis+Gyr AG
75/108
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
76/108 Operation
6 Service
6.1 Alarm Reset Button
R
Access to the alarm reset button is protected by the verification seal or by the utility's seal. The button is located behind the front door of the wall-mounted f6 and behind the front cover of the rack-mounted f9.
The alarm reset button has three functions:
1. Reset an alarm. Meter failure alarms are cleared by pressing the alarm reset button.
2. Select the service menu from the display check.
3. Perform the cursor function in the set mode.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Service
© Landis+Gyr AG
77/108
Operating display
Display check
Display menu
R
Service menu
Set mode
Service list
Installation diagnostic
Test mode
Short press down display button (<2s)
Long press down display button (>2s)
Short press up display button (<2s)
Long press down display button (>2s)
Short press down display button until "End" is displayed then long press down display button
R
Alarm reset button (under utility's seal)
Battery on/off
Transmitting contact test mode on/off
Billing period reset
End of service menu
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
78/108 Service
6.2.1 Select Service Menu
1.
2.
3.
4.
R
All segments of the display are illuminated
Display first menu item
Select menu item
Back to operating display
Operating display
Display check
Set mode
Service list
Installation diagnostic list
Test mode
Battery on/off display
Transmitting contact test mode on/off
Billing period reset
End of service menu
6.
7.
3.
4.
5.
1.
2.
Select service list Service list
Enter service list Error code
Select the required main value
Main values
Select required value (main value or stored value)
Repeat steps 3 and 4 for all values to be checked.
Long press: display main values only
Short press: display main values and stored value
Advance display until End
Main value or stored value
End of service list
Exit service menu
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Service
© Landis+Gyr AG
79/108
6.2.3 Installation Diagnostic List
1.
Select installation diagnostic list
2.
3.
4.
5.
6.
Enter installation diagnostic list
Select required value
Repeat step 3 for all values to be checked
Advance display until End
Exit installation diagnostic list
Installation diagnostic list
First value
Value x
End of diagnostic list
Note
Test mode enables you to select which measuring quantity (active, reactive, I
2
, U
2
) is output to the optical test output. Depending on parameter setting, the resolution of the display register can be increased for faster testing, using the time-power-method.
Operating display
1.
All segments of the display are illuminated
Enter service menu
Display check
2.
R
Set mode
3.
Select test mode Test mode
4.
Enter test mode First value
5.
Select required value
Value x
6. Repeat step 5 for all values to be tested.
Exit test mode Operating display
7.
Example
The first value and value x are examples. The real values are defined in the parameter settings and are the same as the operating display.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
80/108 Service
The measured values are displayed at the optical test outputs as shown in the following table:
Mode Register on Display
Test output reactive
Test output active
Normal mode Some sort of register
Test mode NLA register
(Transformer losses per phase
NLA1,NLA2,NLA3; Total
Transformer Losses NLA)
|R|
I
2 with R
CU
=1 Ω
|A|
U
R
2
FE with
=1M Ω
U
2 with R
FE
=1M Ω
I
2 with R
CU
=1 Ω
(Line losses per phase OLA1,
OLA2, OLA3; Total line losses
OLA)
Reactive energy register |A| |R|
Active energy register or one of not mentioned registers in this table.
6.2.5 Set Battery Low Indicator
|R| |A|
Operating display
Display check
1.
2.
3.
4.
R
All segments of the display are illuminated
Enter service menu
Select menu item
Change setting:
Set mode
Battery on / off display
5.
6.
1 = battery low indicator on
0 = battery low indicator off
Advance display until End
Exit service menu
End of battery on / off display
Operating display
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Service
© Landis+Gyr AG
81/108
6.2.6 Billing Period Reset
At the end of the billing period the reset signal triggers the entry of the current values into the stored billing value profile (C.8 only). Control of the billing period is usually automatic and synchronous to the capture period of the load profile.
Using the following the procedure you can trigger a billing period reset manually.
Operating display
1.
Display check
2.
3.
R
All segments of the display are illuminated
Enter service menu
Select required entry
Set mode
Billing period reset
4.
5.
Perform a billing period reset
Change from 0 to 1 = billing period reset
Change from 1 to 0 = billing period reset
Advance display until End.
Exit service menu
6.
End of service menu
Operating display
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
82/108 Service
6.3 Errors
Errors are graded according to their severity and are classified as fatal errors, alarms and operational indications. The type of error that has occurred can be established from the error information on the meter as follows:
Error type Term according to IEC870-5
Fatal error ----
Alarm
Operational indication
Display
Error indication
FF and error code
(display locked)
FF and error code
(More registers can be displayed by pressing the display buttons.)
Entry in event log
(if activated by parameter setting)
Warning message FF and error code in rolling display (with some operational indications)
Alarm LED Alarm contact
Off
On
Blinking
(if activated by parameter setting)
Closed
(OK = contact open)
Closed
(for 1..9 seconds or until the alarm is cleared, depending on parameter setting)
Closed, while the event is present
(if activated by parameter setting)
Entry in event log
(if activated by parameter setting)
When two or more errors occur simultaneously, the hexadecimal code values will be added.
Errors that prevent the meter from performing the measuring function are classified as fatal errors.
When a fatal error occurs, the meter must be changed. Refer to chapter 4 for how to install / de-install a meter,
page 45
Fatal errors are shown on the display as follows:
Display
FF 00010000
FF 00020000
FF 00000100
FF 00000200
FF 00000400
FF 00000040
Description
Main memory error (RAM)
FLASH memory error
ROM checksum error
Back-up data checksum error (FLASH)
Parameter data checksum error (FLASH)
FLASH ID does not match
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Service
© Landis+Gyr AG
83/108
6.3.2 Alarms
Internal meter errors that can prevent the meter from measuring correctly and can cause the measured data to be incorrect are classified as alarms.
An FF and error code on the display, constantly lit alarm LED, and possibly a closed alarm contact (depending on parameter settings) signifies an alarm. Normally the alarm contact remains closed until the alarm is cleared but it may also be cancelled after a defined period depending on the parameter settings.
When an alarm occurs, contact the service engineer. Depending on parameter settings, it may be possible to clear the alarm by pressing the alarm reset button.
Alarms are shown on the display and in the event log (depending on parameter settings) as follows:
Read/Write Access Errors:
Display Description Event number
FF 00040000 Measuring system access error
FF 00080000 Time base error (CTS)
FF 00100000 Data profile memory error (FLASH)
75
76
77
79 FF 00400000 Communication unit error
Checksum Errors:
Display Description
FF 00000400 Parameter data checksum error (FLASH)
FF 00000010 General system error
Event number
83
FF 00000800 Load profile data checksum error (FLASH) 84
Other Errors:
Display Description Event number
FF 00000001 Start-up sequence invalid 89
93
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
84/108 Service
There are two types of operational indications:
Internal conditions
Internal conditions that remain until the condition is rectified, e.g. battery voltage low. An FF and error code on the display, blinking alarm LED, a closed alarm contact, and possibly an entry in the event log (depending on parameter settings) signifies an internally generated operational indication.
These operational indications are shown on the display and in the event log as follows (examples, depending on parameter settings):
External operating conditions
Display Description
FF 01000000 Battery voltage low
FF 02000000 Invalid time or date
Event number
65
66
FF 00000080 Transmitting contact ID not valid (If this error occurs no pulses will be transmitted.)
96
Operational indications due to internal conditions are cancelled when the appropriate steps have been taken to remedy the condition, e.g. the battery is replaced.
External operating conditions that clear automatically when the condition no longer exists, e.g. missing phase voltage L1. A blinking alarm LED, a closed alarm contact, and possibly an entry in the event log (depending on parameter settings) signifies an externally generated operational indication.
Because no error code is apparent on the display the cause for these operational indications must be viewed in the event log.
Operational indications due to external operating conditions are cancelled when the warning condition no longer exists, e.g. additional power supply has returned.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Service
© Landis+Gyr AG
85/108
6.4 Repair
When a fatal error or an alarm occurs that cannot be cleared (see previous paragraph Errors), the meter must be repaired by the authorised service and repair centre.
chapter
4
2. Describe the error clearly and state the name and telephone number of the person responsible in case of inquiries.
Whenever possible, fill out the supplied form and attach to the meter.
3. Pack the meter using the original packing. Do not enclose any loose components.
4. Send the meter to the responsible service and repair centre.
5. Quote the meter serial number from the face plate in all communication!
Shipment of the meter
The meter may only be shipped in its original packing.
Warning
Warning
Do not repair f9 meters with fire damage
Meters with an f9 housing contain isolation material made of polyvinyl chloride (PVC).
In the unlikely event of a fire, this isolation material may be burned and deposited on the PCBs.
No attempts must be made to repair f9 meters with fire damage. The meters must be disposed of in accordance with local laws and / or regulations. For details please refer to
chapter 9
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
86/108 Service
7 Maintenance
Note
Based on our experience as long-term meter manufacturers, electronic meters require no maintenance.
Meter modification
No conversion, modification or retrofitting of the meter is allowed unless stated in this chapter!
A meter accuracy check should be performed periodically according to national regulations, usually every 8 years.
When testing the meter, the measuring conditions and the measuring points must follow the IEC meter standards.
Use test equipment according to regulations for Cl.0.2S. all-phase single phase
Metering Point
1%In cos ϕ = 1
2%In cos ϕ = 0.5
100%In cos ϕ = 1
100%In cos ϕ = 0.5
Measuring Time
90 s
90 s
10 s
40 s
The green optical test outputs supply pulses at a frequency dependent on the load applied and the meter constant R. The pulse’s rising edge is always decisive for the test.
After switch on of voltage and current, wait 1 second for measurement to be started.
The impulse frequency at nominal load Pn is between 4 and 6 Hz.
For the accuracy test of the transmitting contacts the same test is performed as for the optical test outputs.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Maintenance
© Landis+Gyr AG
87/108
Note
The test mode enables you to select which measuring value (active, reactive, I
2
, U
2
) is output to the optical test output.
In the display, values for active, reactive and apparent energy are available. Depending on parameter setting, the resolution of the display register can be increased for faster testing. In the test mode, the resolution is increased by one decimal point compared with the normal mode. A maximum of 5 decimal points are possible.
1.
Select test mode Test mode
2.
Enter test mode First value
3.
Select required value
Value x
4. Repeat step 3 for all values to be tested
Exit test mode Operating display
5.
Examples
First value and value x are examples. The real values are defined in the parameter settings and are the same as the operating display.
The measured values are displayed at the optical test outputs as shown in the following table:
Mode Register on Display
Test output reactive
Test output active
Normal mode Some sort of register
Test mode NLA register
(Transformer losses per phase
NLA1,NLA2,NLA3; Total
Transformer Losses NLA)
|R|
I
2 with R
CU
=1 Ω
|A|
U
R
2
FE with
=1M Ω
U
2 with R
FE
=1M Ω
I
2 with R
CU
=1 Ω
(Line losses per phase OLA1,
OLA2, OLA3; Total line losses
OLA)
Reactive energy register |A| |R|
Active energy register or one of not mentioned registers in this table.
|R| |A|
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
88/108 Maintenance
7.1.5 No Load Test
Test voltage Up =
Test current Ip =
1.15 x nominal voltage Un
0.3 x starting load
1. Switch off the current for at least 10 seconds.
2. Switch on the test voltage Up and current Ip (0.3 x starting load).
The green optical test outputs must be permanently lit.
Note
3. Run the test for 5 minutes. The meter must not deliver more than one pulse during the test. Check the energy reading for changes in test mode. The last digit of the display must not increase by more than 1.
Local regulations
In some countries, the observation time must be longer than 5 minutes.
Follow the local the local regulations.
7.1.6 Starting Load for Active Energy
Apply a load current of 0.05% of the nominal current ln (other values may be selected in the parameter setting) and the voltage Un (three-phase in each case) at cos ϕ= 1. The meter must start registering. The green optical test output must start blinking.
7.1.7 Starting Load for Reactive Energy
Apply a load current of 0.1% of the nominal current ln (other values may be selected in the parameter setting) and the voltage Un (three-phase in each case) at sin ϕ = 1. The meter must start registering. The green optical test output must start blinking.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Maintenance
© Landis+Gyr AG
89/108
7.2 Set Time & Date, ID Numbers, Battery Time
The following values can be changed at any time from the service menu
(set mode):
• Date and time
• Identification numbers
• Operating time of battery
Below is an example of how to set the date and time.
Operating display
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
R
R
R
R
All segments of the display are illuminated
Enter service menu
Display check
Set mode
Enter set mode Identification number
Select required setting
Date, old value
Select digit to be changed
Digit flashes
Change digit value Digit flashes
Select digit to be changed
Next digit flashes
Repeat steps 5 - 7 for all digits to be changed. All digits flash
Confirm new setting
Repeat steps 4 - 9 for all settings to be changed.
Date, new value
Advance display until End
End of set mode
Service menu
12.
13.
14.
Back to service menu
Advance display until End
Back to operating display
End of service menu
Operating display
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
90/108 Maintenance
7.3.1 When to Change Battery
If the meter is provided with a battery, this must be changed if one of the following events occurs:
Note
• The symbol appears in the liquid crystal display.
• During the normal calibration cycle of the meter.
• The battery charge indicates less than 4.8 V (can be read under code
C.6.1 in service list).
Indication of symbol “BAT LOW”
Only meters with the parameter set to allow the battery symbol will display it at a low battery condition.
The meter functions perfectly well without a battery.
7.3.2 How to Change Battery
Presence of dangerous voltage
Danger
Warning
Warning
Dangerous voltage may be present on the battery and battery contacts in the battery compartment.
Touching the battery or battery contacts could result in severe personal injury or death.
Only remove and replace the battery with the existing battery holder without touching the contacts.
Wrong battery type
Replacing the battery with the wrong type or voltage rating could result in damage to the meter.
Only use a lithium battery with a rated voltage of 6 V and the same construction as the original battery (type CR-P2) as a replacement.
Battery replacement after a long period of non-use
If the meter has been disconnected from the supply for a long time, the power reserve is exhausted. Replacing the battery when the power reserve is exhausted may lead to an invalid time/date information without the corresponding error message.
Reconnect the meter to the measurement voltage or additional power supply before replacing the battery.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Maintenance
© Landis+Gyr AG
91/108
Replacing the Battery in f6 Meters
1. Remove the front door seal and open the front door.
Danger
Presence of dangerous voltage
Only remove the battery with the existing battery holder without touching the contacts.
2. Lightly press down the latch of the plastic battery holder until it releases and then withdraw the battery holder with the old battery.
Danger
3. Mark the current date on the new battery.
4. Draw the old battery from the holder and insert the new 6 Volt rated lithium battery.
Presence of dangerous voltage
Only replace the battery with the existing battery holder without touching the contacts.
5. Push the battery holder with battery in the battery compartment until the latch engages.
6. In the set mode, reset the operating time of the battery to zero and change the time and date if necessary as described earlier in this chapter.
7. Close and re-seal the front door.
8. Dispose of old battery as hazardous waste in accordance with local regulations.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
92/108 Maintenance
Replacing the Battery in f9 Meters
1. Remove the front cover seal and open the front cover.
Danger
Presence of dangerous voltage
Only remove the battery with the existing battery holder without touching the contacts.
2. Loosen and remove the two battery holder fixing screws. Withdraw the battery holder from the meter.
3. Mark the current date on the new battery.
4. At the rear of the battery holder loosen the clamp fixing screws and take off the battery.
Danger
5. Insert the new battery into the battery holder. Tighten the screws so that the clamp holds the battery.
Presence of dangerous voltage
Only replace the battery with the existing battery holder without touching the contacts.
6. Insert the battery holder into the meter. Tighten the two fixing screws.
7. In the set mode, reset the operating time of the battery to zero and change the time and date if necessary as described in earlier in this chapter.
8. Close and re-seal the front cover.
9. Dispose of old battery as hazardous waste in accordance with local regulations.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Maintenance
© Landis+Gyr AG
93/108
7.4.1 When to Change Communication Unit
The communication unit can be changed, if for example, different communication requirements are needed.
7.4.2 How to Change Communication Unit
Danger
Danger
Warning
Dangerous voltage on conductors
Dangerous voltage is present on the conductors that the meter is to be connected to.
Contact with the conductors when under voltage will result in severe personal injury or death.
The conductors must not be under voltage when connecting or disconnecting the meter.
Installation and de-installation of the meter must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
Dangerous voltage when connecting communication unit
Dangerous voltage is present on the meter connections to the communication unit.
Contact with the connections will result in severe personal injury or death.
Voltage must not be present on the meter connections when changing / installing the communication unit.
Changing / installing the communication unit must only be performed by qualified meter installers, with strict adherence to the utility's safety regulations.
Do not use communication unit CU-M./V22B
Do not connect any of the communication units of the type CU-M./V22B to the ZxQ meter. Using a communication unit of the type CU-M./V22B may lead to an instable communication.
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
94/108 Maintenance
Changing the Communication Unit in f6 Meters
1. Switch off the voltage. The phase voltage indicator ( L1 L2 L3) disappears.
2. Switch off tariff inputs and synchronisation input. Check if the corresponding indicators disappear from the display.
3. Switch off the voltage for the additional power supply.
4. Check that all connections are free from voltage.
5. Remove the two utility's seals on the terminal cover, release the two screws and remove the terminal cover.
6. Remove the communication unit (or dummy).
7. Carefully insert the new communication unit ensuring that plug and socket are properly engaged.
8. Connect the connecting wires to the terminals of the communication unit.
9. Carry out functional tests as described in the relevant communication unit manual to ensure it is functioning correctly.
10. Replace the terminal cover, close the front door, and re-seal.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Maintenance
© Landis+Gyr AG
95/108
Changing the Communication Unit in f9 Meters
1. De-install the meter (
see page 59
2. Switch off the voltage. The phase voltage indicator ( L1 L2 L3) disappears.
3. Switch off tariff inputs and synchronisation input. Check if the corresponding indicators disappear from the display.
4. Switch off the voltage for the additional power supply.
5. Withdraw the meter from the rack.
6. Remove the seals at the back of the housing and remove the housing.
7. Remove the communication unit (or dummy).
8. Carefully insert the new communication unit ensuring that plug and socket are properly engaged.
9. Connect the connecting wires to the terminals of the communication unit.
10. Carry out functional tests as described in the relevant communication unit manual to ensure it is functioning correctly.
11. Replace the housing and re-seal.
12. Install the meter (
see page 50
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
96/108 Maintenance
8 ZxQ200C.2
Functional range
This chapter describes the characteristics of the ZxQ200C.2.
Unlike the dlms meters ZxQ200C.4, ZxQ200C.6 and ZxQ200C.8 the
ZxQ200C.2 can communicate via the protocol according to the IEC870 subset.
The C.2 meter has been designed for the communication according to the
IEC870 subset and therefore, it features:
• no tariff control
- no tariff control inputs
-
- no energy tariff registers no time switch (time of use)
• no synchronisation input
Meter Address
Measured Value
Number
The ZxQ meters with the functional range C.2 are capable of communicating according to the IEC870 subset. These meters are particularly suited for the replacement of previous IEC870 meters such as the Landis+Gyr ZMU. As a result, the ZxQ C.2 is predestined to be used in existing telemetering systems with transcoders such as the Landis+Gyr
FAG.
The meter is connected to a transcoder via the local RS485 interface. The transcoder requests the meter every minute to send the current data.
Every meter has got its own meter address (Com No)with which it is clearly identified by the transcoder. All meters that are connected to the same transcoder must have a unique meter address. The meter address may be a number between 1 and 127.
In addition to the display code the measured values (energy/loss) also feature a number (MV No) between 1 and 255 with which the value is clearly identified by the transcoder. All measured values of the various meters that are connected to the same transcoder must have a unique measured value number.
Measured value
Display code
Measured value number
When setting the parameters a meter address must be defined for every meter and a measured value number must be defined for every measured value.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
ZxQ200C.2
© Landis+Gyr AG
97/108
Meters with the functional range C.2 provide the following measured quantities.
Meters with quadrant splitting provide the measured quantities +Ri, +Rc, -
Ri and -Rc instead of +R and -R.
Measured Quantities ZMQ ZFQ
Active energy import
Active energy export
Reactive energy import
Reactive energy export
Reactive energy in quadrant I
Reactive energy in quadrant III
Reactive energy in quadrant II
Reactive energy in quadrant IV
Active iron losses (transformer)
Active copper losses, (line)
Total active losses in positive direction
Total active losses in negative direction
Energy flow of active energy
Energy flow of reactive energy
+A Sum
–A Sum
+R Sum
–R Sum
+Ri Sum
–Ri Sum
+Rc Sum
–Rc Sum
NLA Sum
OLA Sum
+TLA Sum
-TLA Sum
EFA Sum
EFR Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
Sum
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
98/108 ZxQ200C.2
The service menu of the ZxQ200C.2 is expanded by the functions for the communication according to the IEC870 subset.
Operating display
Display check
Display menu
R
Service menu
Set mode
Service list
Installation diagnostic
Test mode
Short press down display button (<2s)
Long press down display button (>2s)
Short press up display button (<2s)
Long press down display button (>2s)
Short press down display button until "End" is displayed then long press down display button
R
Alarm reset button (under utility's seal)
Battery on/off
Reset communication counter
End of service menu
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
ZxQ200C.2
© Landis+Gyr AG
99/108
If the C.2 meter communicates according to the IEC870 subset the following steps must be carried out during the installation check in addition
to the steps described in section
4.4 Installation Check on page 52.
8.4.1 Check Meter Address
Check whether all meters that are connected to the same transcoder have a unique meter address.
1. Operating display
2.
Display check
3.
4.
5.
6.
R
All segments of the display are illuminated
Enter service menu
Select required menu item
Enter installation diagnostic
Advance display until End
Set mode
Installation diagnostic
Check meter address
End of installation diagnostic
Service menu
7.
8.
Return to service menu
Advance display until End
Exit service menu
9.
End of service menu
Operating display
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
100/108 ZxQ200C.2
8.4.2 Reset Communication Counter
Set the counter of the three communication commands freeze, send and respond to "0".
Operating display
1.
2.
3.
4.
5.
6.
R
All segments of the display are illuminated
Enter service menu
Advance display until End
Exit service menu
Display check
Set mode
Select required menu item
Reset communication counter
Change from 0 to 1 = reset communication counter
Change from 1 to 0 = reset communication counter
Communication counter reset
End of display communication counter reset
Operating display
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
ZxQ200C.2
© Landis+Gyr AG
101/108
Checking the communication counters
The communication according to the IEC870 subset has got the sequence of commands:
1) Freeze
2) Send
3) Respond
The communication between the meter and the transcoder is only completed successfully if all three commands have been carried out. In order to be able to check the communication the meter features a counter for every command. These counters are always incremented by 1 after the command has been carried out.
Varying counter readings indicate communication problems.
Check whether the counters for the communication commands freeze, send and respond show identical readings.
1.
2.
Operating display
Display check
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
R
All segments of the display are illuminated
Enter service menu
Select required menu item
Enter installation diagnostic
Select freeze counter
Select send counter
Select respond counter
Advance display until End
Return to the service menu
Advance display until End
Exit service menu
Set mode
Installation diagnostic
Meter address
Check freeze counter
Check send counter
Check respond counter
End of installations diagnostic
Service menu
End of service menu
Operating display
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
102/108 ZxQ200C.2
If the protocol according to the IEC870 subset is used to communicate between meter and transcoder all meter types that can communicate using this protocol can be utilized (e.g. ZxU, ZxV, ZxQ200C.2).
These different meter types generate different operational indications and alarms.
The table below provides a cross-reference of the error messages of the
ZxU/ZxV and the ZxQ.
Message ZxU/ZxV
System restart
Coldstart
Program error
Parameter error
Parameter error M, D
Message ZxQ
Energy register cleared
General system error
ROM checksum error
Event No ZxQ
128
93
(81, fatal error)
Parameter data checksum error (FLASH)
Measuring system access error
83
75
Main memory error (RAM) (73, fatal error) Data error
Current without voltage phase
Lx
Outage Phase Lx
Parameter change
1)
Bypass feeder operation
1)
Power outage
1)
Set register value
1)
Current without voltage Lx 55-57
Single-phase failure Lx
Bypass feeder operation
125-127
47
2) 2)
Register overflow
1) 2) 2)
1) These messages do not appear in the display of the ZxU/ZxV. However, they will be transmitted to the transcoder using the protocol according to the IEC870 subset.
2) These events do not trigger an event log entry at the ZxQ. However, the events will be transmitted to the transcoder using the protocol according to the IEC870 subset.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
ZxQ200C.2
© Landis+Gyr AG
103/108
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
104/108 ZxQ200C.2
9 Disposal
9.1 Components
Warning
Based on the data specified in environmental certificate ISO 14001, the components used in meters are largely separable and can therefore be taken to the relevant disposal or recycling point.
Hazardous waste in case of disposal
The ZxQ contains opto-electronic components and possibly a lithium battery, which are regarded as hazardous waste.
Incorrect disposal of these parts could cause ground pollution or emission of poisonous gases, which could lead to environmental damage and personal injury.
Disposal of these parts must be performed by a qualified person in accordance with local laws and/or regulations.
The separable components are graded as follows:
Component
Disposal
LEDs and LCD
Lithium battery
Hazardous waste: disposal according to local regulations.
Hazardous waste: disposal according to local regulations.
PVC isolation material Hazardous waste: sorted and taken to recycling
(regranulation) plant or disposal according to local regulations.
Printed circuit boards Electronic waste: disposal according to local regulations.
Metal parts Sorted and taken to collective materials disposal point.
Plastic components Sorted and taken to recycling (regranulation) plant or if no other possibility to refuse incineration.
9.2 Meters
Warning
For the disposal of meters as a complete unit, observe the local disposal and environmental protection regulations in effect.
Hazardous waste in case of disposal
The ZxQ contains LCD, LEDs, and lithium battery, which are regarded as hazardous waste.
Incorrect disposal of the meter could cause ground pollution or emission of poisonous gases, which could lead to environmental damage and personal injury.
Disposal of the meter must be performed by a qualified person in accordance with local laws and/or regulations.
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Disposal
© Landis+Gyr AG
105/108
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
106/108 Disposal
10 Index
Additional power supply _____________ 31, 47
Alarm ___________________________ 65, 84
Alarm LED________________________ 61, 65
Alarm reset button ______________ 35, 36, 77
Application of ZxQ ____________________ 13
Arrows in display _____________________ 63
Base _______________________________ 33
Battery _____________________________ 36
Change ___________________________ 91
Battery compartment __________________ 35
Battery low indicator
Set____________________________ 56, 81
Block schematic diagram _______________ 15
Calendar clock _______________________ 24
Central station _______________________ 36
Change battery_______________________ 91
Change communication unit_____________ 94
Check installation _____________________ 52
Communication_______________________ 74 dlms protocol ______________________ 74
IEC870 Subset __________________ 74, 97
Communication counter
Check the ________________________ 102
Reset ____________________________ 101
Communication interface _______________ 47
Communication unit __________ 32, 35, 36, 75
Change ___________________________ 94
Conditions for the use of this user manual __ 3
Connect f6 meter _____________________ 46
Connect f9 meter _____________________ 50
Connection diagram ________________ 33, 38
Connection diagram f6 _________________ 46
Connection diagram f9 _________________ 50
Cover ______________________________ 33
Daily snapshot _______________________ 71
Date and time
Set____________________________ 55, 90
Description of unit ____________________ 13
Deviations of the calendar clock _________ 28
Diagnostic list ________________________ 80
Dimension diagrams f6 meter __________________________ 39 f9 meter __________________________ 40
Disconnect f6 meter __________________________ 57 f9 meter __________________________ 59
Display __________________________ 61, 62
Arrows____________________________ 63
Display buttons____________________ 61, 64
Display list __________________________ 68
Display menu ________________________ 66
Disposal
Components _______________________105
Meters ___________________________105
Energy registers_______________________29
Error indication ___________________ 65, 84
Errors _______________________________83
Checksum__________________________84
Others_____________________________84
Read/write access ___________________84
Several simultaneously _______________83
Event log ________________________ 31, 70
Face plate f6 meter _______________________ 33, 37 f9 meter ___________________________38
Fatal errors __________________________83
Front cover___________________________33
Functional description __________________13
Grid diagnostics _______________________73
Housing _____________________________33
Identification numbers
Set _______________________________90
IEC870 Subset ________________________97
Information plate______________________33 f6 meter ___________________________37 f9 meter ___________________________38
Inputs and outputs ____________________47
Installation ___________________________45
Installation check______________________52
Load profile ______________________ 30, 69
Losses ______________________________72
Maintenance__________________________87
Manufacturer's seal ________________ 33, 34
MAP 120 service tool ___________________75
MAP tool_____________________________32
Measured quantities ___________________19
Measuring system _____________________17
Measuring times_______________________87
Mechanical description _________________33
Meter address ________________________97
Check the _________________________100
Meter operation in systems ______________74
Meter tests___________________________87
Mounting the f6 meter__________________44
No load test __________________________89
Object identification system _____________62
Operating elements ____________________61
Operating time of battery
Set _______________________________90
Operation ____________________________61
Operational indication ______________ 65, 85
Optical interface___________________ 61, 64
H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
Index
© Landis+Gyr AG
107/108
Optical test outputs______________61, 64, 87
Power supply_________________________ 31
Purpose of this user manual ______________ 3
Reference documentation________________ 3
Remote meter reading _________________ 74
Repair ______________________________ 86
Representation of type designations _______ 3
Responsibilities for the safety _____________ 9
Safety pictographs _____________________ 9
Safety regulations _____________________ 10
Seal
Manufacturer's______________________ 34
Utility's ____________________________ 35
Verification_________________________ 34
Sealing______________________________ 56
Serial interface _______________________ 47
Service and repair _____________________ 77
Service list ___________________________ 79
Service menu
IEC870 Subset ______________________ 99
Set
Overview __________________________ 78
Select _____________________________ 79
Date and time ______________________ 90
Identification numbers _______________ 90
Operating time of battery_____________ 90
Setting the time of the calendar clock _____ 27
Starting load _________________________ 89
Stored billing value profile ______________ 72
Synchronising the calendar clock______ 25, 27
Target group of this user manual _________ 3
Tariff control_________________________ 23
Terminal connection diagram_________ 33, 38
Terminal cover _______________________ 33
Terminal layout f6 meter __________________________ 46 f9 meter __________________________ 50
Test mode________________________ 80, 88
Transmitting contacts_______________ 31, 46
Transmitting Contacts
Test (test mode)____________________ 54
Type designation _____________________ 14
Utility's seals_________________________ 35
Verification seal ___________________ 33, 34
Warning message__________________ 65, 85
© Landis+Gyr AG H 71 0200 0215 h en - ZMQ202 / ZFQ202 - User Manual
108/108 Index
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 9 Safety
- 9 Safety Information
- 9 Responsibilities
- 10 Safety Regulations
- 13 Description of Unit
- 13 Application
- 13 Features
- 14 Type Designation
- 15 Block Schematic Diagram
- 17 Measuring System
- 17 Input Signals
- 17 Input Circuits
- 17 Signal Converter
- 17 Signal Processor
- 18 Microprocessor
- 19 Measured Values
- 20 Calculation of Measured Quantities
- 21 Demand
- 22 Power Factor
- 22 Instantaneous Values
- 22 Diagnostic Values
- 23 Tariff Control
- 24 Calendar Clock
- 25 Synchronisation and Time-Setting
- 25 Synchronising the Calendar Clock via the Synchronisation Inp
- 27 Synchronising the Calendar Clock via Communication
- 27 Setting the Time
- 28 Handling the Deviations
- 29 Registers
- 30 Memory
- 30 Load Profile
- 30 Snapshot
- 30 Stored Billing Value Profile
- 31 Event Log
- 31 Power Supply
- 31 Additional Power Supply
- 31 Transmitting Contacts Module
- 32 Communication Unit (Option)
- 32 Software Tools
- 33 Mechanical Description
- 34 Manufacturer's Seal
- 34 Verification Seal
- 35 Utility's Seals
- 37 Face Plate f6
- 37 Information Plate f6
- 38 Terminal Connection Diagram f6
- 38 Face Plate and Information Plate f9
- 38 Connection Diagram f9
- 39 Dimension Diagrams f6
- 40 Dimension Diagrams f9
- 40 Rack Mounting
- 41 Racks
- 43 Flush Mounting
- 44 Mounting f6
- 45 Installation / De-installation
- 45 Prerequisites
- 46 Connect the f6 Meter
- 46 Connection Diagram
- 46 Terminal Layout
- 47 Procedure
- 50 Connect the f9 Meter
- 50 Connection Diagram
- 50 Terminal Layout
- 51 Procedure
- 52 Installation Check
- 52 Check Procedure
- 54 Testing the Transmitting Contacts
- 55 Set Date and Time
- 56 Set Battery Low Indicator
- 56 Sealing
- 57 Disconnect the f6 Meter
- 57 Procedure
- 59 Disconnect the f9 Meter
- 59 Procedure
- 61 Operation
- 61 Operating Elements
- 62 Display
- 63 Arrows in Display
- 64 Display Buttons
- 64 Optical Interface
- 64 Optical Test Outputs
- 65 Alarm LED
- 66 Display Menu
- 67 Select Display Menu
- 68 Display List
- 69 Load Profile
- 70 Event Log
- 71 Daily Snapshot
- 72 Stored Billing Value Profile
- 72 Losses
- 73 Grid Diagnostic
- 74 Meter Operation in Systems
- 74 Remote Meter Reading in Energy Production Applications
- 74 Types of Communication
- 75 Communication Units
- 75 MAP 120 Service Tool
- 77 Service
- 77 Alarm Reset Button
- 78 Service Menu
- 79 Select Service Menu
- 79 Service List
- 80 Installation Diagnostic List
- 80 Test Mode
- 81 Set Battery Low Indicator
- 82 Billing Period Reset
- 83 Errors
- 83 Fatal Errors
- 84 Alarms
- 85 Operational Indications
- 86 Repair
- 87 Maintenance
- 87 Meter Tests
- 87 Measuring Times
- 87 Optical Test Outputs
- 87 Test via Transmitting Contacts
- 88 Test Mode
- 89 No Load Test
- 89 Starting Load for Active Energy
- 89 Starting Load for Reactive Energy
- 90 Set Time & Date, ID Numbers, Battery Time
- 91 Change Battery
- 91 When to Change Battery
- 91 How to Change Battery
- 94 Change Communication Unit
- 94 When to Change Communication Unit
- 94 How to Change Communication Unit
- 97 ZxQ200C.2
- 97 Communication According to the IEC870 Subset
- 98 Measured Quantities
- 99 Service Menu
- 100 Installation Check
- 100 Check Meter Address
- 101 Reset Communication Counter
- 102 Check Communication
- 103 Error Messages
- 105 Disposal
- 105 Components
- 105 Meters
- 107 Index