MRCOOL H4TXV01 Signature Series 1.5 - 2.5 Ton Thermal Expansion Valve Instructions
Add to My manuals1 Pages
advertisement
SPLIT SYSTEM AIR CONDITIONER
ACCESSORIES
Description
TXV Kit
Where Used
18, 24, 30
36, 42, 48
60
Kit Number
H4TXV01
H4TXV02
H4TXV03
H4TXV0*
REFRIGERATION DATA
Model
Refrig. Charge
(oz.) *
MAC16018A
MAC16024A
MAC16030A
MAC16036A
MAC16042A
MAC16048A
MAC16060A
*Factory charged for 15 feet of line set
** Adapter shipped with unit
73
73
88
113
140
156
192
TXV
H4TXV01
H4TXV01
H4TXV01
H4TXV02
H4TXV02
H4TXV02
H4TXV03
Refrigerant Line Size
Suction
3/4
3/4
3/4
7/8
7/8
7/8
1 1/8
Liquid
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Outdoor Unit
Connection
Suction Liquid
3/4 3/8
3/4
3/4
3/8
3/8
7/8
7/8
7/8
7/8 **
3/8
3/8
3/8
3/8
Indoor Unit Connection
Suction
3/4
3/4
3/4
7/8
7/8
7/8
7/8
Liquid
3/8
3/8
3/8
3/8
3/8
3/8
3/8
1.
Separate the distributor assembly and remove the piston orifice and used teflon seal. Insert nozzle end of the expansion valve along with a new teflon seal into the distributor and tighten to 20 – 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening will crush the teflon seal and may cause a leak.
2.
Attach liquid line portion of distributor assembly along with new teflon seal to the inlet of the expansion valve.
Tighten to 20 – 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening will crush the teflon seal and may cause a leak.
3.
Connect the external equalizer line to the equalizer port on the suction line and tighten to 8 ft. lbs.
4.
Strap the superheat sensing bulb to the suction header.
If installing an expansion valve on an indoor coil that previously used a fixed orifice, be sure to remove the existing fixed orifice. Failure to remove a fixed orifice when installing an expansion valve to the indoor coil will result in improper operation and damage to the system.
www.mrcool.com