1949–2011
YEARS OF INNOVATION
Smart Metering
Smart metering with Eltako Wireless Building
Wirless energy consumption indicator FEA55LED with LED and FEA55D with display
Wireless Visualisation and Control Software FVS-Energy and
wireless energy meter transmitter module FSS12
Energy consumption indicator EVA12 and
wireless single-phase energy meter transmitter module FWZ12 and FWZ61
Wireless actuator Impulse switch with integr. relay function with
active power measurement FSR70W-16A and with current measurement FSR61VA-10A
Selection table single-phase and three-phase energy meters
Single-phase energy meter WSZ12D-32A and
single-phase energy meter WSZ12D-65A, with MID approval
Single-phase energy meter WSZ12DE-32A, without approval
Single-phase energy meter WSZ12DE-65A, without approval
Single-phase energy meter WZR12 with reset, without approval
Three-phase energy meter DSZ12D with display and MID approval
Three-phase energy meter DSZ12WD with display and MID approval
Three-phase energy meter DSZ12DE with display, without approval
Three-phase energy meter DSZ12WDE with display, without approval
2
3
5
6
8
9
10
11
11
12
13
13
14
14
Electronic two-way three-phase energy meter DSZ12DZ-3x65A with display and MID approval
Two-way three-phase energy meter DSZ12WDZ-3x5A with display and MID approval
15
16
Electronical single-phase energy meters and
three-phase energy meters for meter mounting installation WSZ60, DSZ60 and DSZ60D
Technical data single-phase and three-phase energy meters and energy consumption indicator
Measuring Instruments Directive MID
17
18
20
Switching on the future
06/2012
Smart metering with the Eltako Wireless Building
2
Observing power consumption is a recognised way to sharpen awareness about energy consumption and to realise
how consumers are driving up costs at what time of the day. If automatic countermeasures are taken – e.g. appliances
with high consumption are only switched on at low tariff periods – this knowledge and the corresponding efforts take
on a practical ecological and economic purpose.
Eltako Wireless Building offers Smart Metering in several stages. From a low-cost solution in the home up to a
professional solution in large buildings for genuine energy management.
Stage 1 in a home
A FWZ single-phase energy meter transmitter module in a circuit measures power consumption and sends wireless
telegrams to the Eltako wireless network. We manufacture transmitter modules such as FWZ12 rail mounted devices
for central installation up to 16 A and 65 A, or the FWZ61 build-in device for decentralised installation up to 16 A.
An FEA55LED energy consumption indicator receives these wireless telegrams and displays realtime consumption and
normal rate / off-peak by LEDs.
+
+
Stage 2 in a home
Consumption measurement as for Stage 1. A FEA55D digital energy consumption indicator with display and a memory
for consumption parameters receives the wireless telegrams. Realtime consumption and accumulated consumption are
displayed constantly. The consumption over the past hours, days, months and years is also retrievable.
+
+
Stage 3 in a home or a building
Power consumption is queried directly from the energy meters via their S0 interfaces and sent over the Eltako wireless
network by an FSS12 energy meter transmitter module. An integrated load shedding relay can switch off consumers if a
preset consumption is exceeded.
Energy consumption in Stages 1 and 2 can be indicated by a FEA55 or by means of the FVS-Energy FVS Wireless
Visualisation and Control Software or the FVS of the FVS-Safe. FVS-Energy is downloadable free of charge from the
Eltako website.
+
+
Zeitraum
Von
09.11.2009
Stage 4 in all residential, office and commercial buildings
Up to 30 energy meters in a group can be connected by their S0 interfaces to the FPZ12 wireless Powernet meter
connector. Up to 3 meters per FPZ12. These FPZ12s transmit meter information over the power mains (Powernet).
This information can be read out with other FPZ12s at any point in the internal building power mains and either
transmitted over the Eltako wireless network or directly sent via an USB connection to FVS-Safe.
The data is displayed, evaluated and stored using the FVS Wireless Visualisation and Control Software of the FVS-Safe
server. This can also be performed by FEA55 energy consumption displays in individual homes, departments or machine
locations.
+
+
+
Einstellungen
Informations about MID see page 20
Direct display with the Wireless Energy
Consumption Indicator FEA55LED
Smart Metering is so cost-effective and incurs no follow-on costs:
The energy consumption indicator EVA12 (page 6) displays the current active current consumption in the control cabinet or distributor.
They save the consumption figures in non-volatile memories that are viewable at any time. The wireless energy consumption Indicators
FEA55LED and FEA55D (page 4) show directly the wireless readings of an energy meter transmitter module FSS12 (page 5), FWZ12
(page 7), FWZ61 (page 7) or of a wireless impulse switch with integrated relay function with active current meter FSR70W-16A
respectively with power measurement FSR61VA-10A. The energy consumption indicator with display FEA55D saves the values in the
same way as the EVA12.
Only the Wireless Visualisation and Control Software FVS on your PC can evaluate several meters. FVS Energy and FVS Home can
evaluate up to 100 meters and FVS Professional up to 250 meters.
FEA55LEDWirless energy consumption indicator with 10 red LEDs for individual fitting
and integration in the 55x55mm and 63x63mm switch system. Standby
loss 0.8 watt only.
The scope of supply includes a frame R, an intermediate frame ZR in the same colour, a
mounting plate and an adhesive film. In addition, an intermediate frame ZRF in the same
colour is supplied for installation in an existing frame R1F, R2F or R3F for flat pushbuttons.
Power supply 230 V.
A 20cm long black/blue connecting wire is routed to the rear.
Before screwing on, remove the frame and intermediate frame from the mounting plate.
To do this, press out the catches on the mounting plate. Then screw on the mounting plate with the catches at the top and bottom -, snap on the frame and the intermediate frame, and
connect and snap on the energy consumption indicator.
We recommend sheet metal countersink screws 2.9x25mm, DIN 7982 C, for screw connections
on 55mm switch boxes.
The energy consumption indicator evaluates the information received from the wireless
energy meter transmitter module FSS12 or the wireless single-phase energy meters
FWZ12- or FWZ61-16A or from a wireless impulse switch with integrated relay function with
active current meter FSR70W-16 A respectively with power measurement FSR61VA-10 A and
indicates the current energy consumption by a row of LEDs.
The normal rate and off-peak status are also displayed by the FSS12.
The 15W to 30kW reading is adaptable to maximum expected consumption using a rotary
switch to visualise even minor changes. There are 5 ranges to choose from, starting on
the left with 1, 3, 7, 15 and 30 kW. On the energy consumption indicator, a maximum of 5
out of 10 LEDs light up simultaneously, and the last clockwise LED lights up the brightest. If
one range setting is exceeded, the last LED flashes.
A light sensor controls LED brightness depending on the ambient brightness.
* The bottom of the housing is matt.
FEA55LED-ws
FEA55LED-rw
FEA55LED-sz
FEA55LED-an
FEA55LED-wg*
FEA55LED-si*
FEA55LED-al
FEA55LED-sg*
Energy consumption indicator with LED white
Energy consumption indicator with LED pure white
Energy consumption indicator with LED black
Energy consumption indicator with LED anthracite
Energy consumption indicator with LED pure white glossy
Energy consumption indicator with LED silver grey glossy
Energy consumption indicator with LED coated/aluminium paint
Energy consumption indicator with LED black glossy
Recommended retail prices excluding VAT.
EAN
EAN
EAN
EAN
EAN
EAN
EAN
EAN
4010312302750
4010312302774
4010312302798
4010312302828
4010312302804
4010312304631
4010312310779
4010312310786
74,90 € /pc.
74,90 € /pc.
74,90 € /pc.
74,90 € /pc.
74,90 € /pc.
74,90 € /pc.
83,70 € /pc.
83,70 € /pc.
3
Direct display with the Wireless Energy
Consumption Indicator FEA55D
4
FEA55DWirless energy consumption indicator with display for individual fitting and
integration in the 55x55mm and 63x63mm switch system. Standby loss
0.8 watt only.
The scope of supply includes a frame R, an intermediate frame ZR in the same colour, a
mounting plate and an adhesive film. In addition, an intermediate frame ZRF in the same
colour is supplied for installation in an existing frame R1F, R2F or R3F for flat pushbuttons.
Power supply 230 V.
A 20cm long black/blue connecting wire is routed to the rear.
Before screwing on, remove the frame and intermediate frame from the mounting plate. To do
this, press out the catches on the mounting plate. Then screw on the mounting plate - with the
catches at the top and bottom -, snap on the frame and the intermediate frame, and connect
and snap on the energy consumption indicator.
We recommend sheet metal countersink screws 2.9x25mm, DIN 7982 C, for screw connections
on 55mm switch boxes.
The energy consumption indicator evaluates the information received from the wireless energy
meter transmitter module FSS12 or the wireless single-phase energy meters FWZ12 or FWZ61
and indicates alternately at a rate of 4 seconds the aggregate power consumption and the
momentary power consumption (P at the end of the display) from 15W to 65kW. In addition,
press the MOD and SEL buttons to call up consumption values in the last hours, days, months
and years.
The normal rate and off-peak status are also displayed on the FSS12 by an LED.
Display readings
The standard display appears after power is applied.
The power consumption is displayed alternating for a duration of 4 seconds. The reading,
comprising 7 digits of which there is one decimal place, ranges from 0.1 to 999999.9 kWh or
the actual value of the power consumption from 15P to 65000P (active power) in watts (W).
Press the top button MOD to page through the display options. They are indicated by a bar:
h (hours), d (days), m (months), y (years), LRN.
Press the bottom button SEL within the display options. Each press of the button increments
the number displayed by 1 and the actual value is indicated in the display. The last full hour
then becomes the last hour but one, etc.
h01 = shows the consumption for the last hour up to h24 = 24 hours ago.
d01 = shows the consumption for the last day up to d31 = 31 days ago.
m01 = shows the consumption for the last month up to m12 = 12 months ago.
y01 = shows the consumption for the last year up to y24 = 24 years ago.
The program returns to the standard display mode automatically if MOD or SEL are not operated
for 20 seconds or if you press both buttons briefly simultaneously.
* The bottom of the housing is matt.
FEA55D-ws
FEA55D-rw
FEA55D-sz
FEA55D-an
FEA55D-wg*
FEA55D-si *
FEA55D-al
FEA55D-sg *
Energy consumption indicator with display white
Energy consumption indicator with display pure white
Energy consumption indicator with display black
Energy consumption indicator with display anthracite
Energy consumption indicator with display pure white glossy
Energy consumption indicator with display silver grey glossy
Energy consumption indicator with display coated/aluminium paint
Energy consumption indicator with display black glossy
Recommended retail prices excluding VAT.
EAN
EAN
EAN
EAN
EAN
EAN
EAN
EAN
4010312302675
4010312302699
4010312302712
4010312302743
4010312302729
4010312304648
4010312310809
4010312310793
60,90 € /pc.
60,90 € /pc.
60,90 € /pc.
60,90 € /pc.
60,90 € /pc.
60,90 € /pc.
69,70 € /pc.
69,70 € /pc.
Wireless Visualisation and
Control Software FVS-Energy
Radio telegrams from the wireless energy meter transmitter module FSS12 and the self-learning wireless
single-phase energy meter transmitter modules FWZ12 and FWZ61 can be received and displayed on a PC
using the Wireless Visualisation and Control Software FVS-Energy and the USB receiver FAM-USB.
! Caution! The FVS-Energy software is contained in the Wireless Visualisation Software FVS-Home and
FVS-Professional and need not be installed separately.
FVS-Energy
Free-of-charge wireless visualisation and control software for up to
100 energy meters with energy meter transmitter module FSS12.
The software is ready for downloading at "eltako-wireless.com".
Updates will also be available there free of charge.
The wireless receiver FAM-USB with USB port is also required for PC reception and
if required for transmitting wireless telegrams from a PC to load shedding relays in addition.
A web license is necessary.
Zeitraum
Von
09.11.2009
FAM-USB
FSS12-12 V DC
Wireless Energy meter transmitter module for connection to S0 interface
of the Eltako single-phase energy meter and three-phase energy meter.
Only 0.5 watt standby loss. With load shedding relay 1 NO contact potential free 4 A/250 V and with exchangeable antenna. If required, a wireless
antenna FA250 can be connected.
Field 1
Field 2
Field 3
The enclosed small antenna
can be replaced with a wireless
antenna FA250 or FA200 with
magnetic base and cable.
L
N
L
N
FSNT12FSNT1212V/12W
12V/12W
oder
24W
or 24W
S0+ S0S0+ S0-
FSS12
energy
Stromzähler
meter
2 -12V +12V
E2
1
E1
–
power
Schaltsupply
Netzteil
unit
+
Typical connection
Modular device for DIN-EN 60715 TH35 rail mounting. 2 modules = 36mm wide, 58mm deep.
The energy meter transmitter module FSS12 evaluates the signals from the energy meter
S0 interface and transmits wireless telegrams containing consumption and meter reading
to the Eltako wireless network for evaluation on a PC using the Visualisation and Control
Software FVS Home and FVS Energy. On three-phase energy meters, the data sent includes
normal rate (HT) or off-peak (NT) energy tariff data, provided the E1/E2 terminals on the
three-phase energy meter are connected to E1/E2 on the FSS12.
FVS-Energy and FVS-Home support up to 100 transmitter modules and FVS-Professional up to
250 transmitter modules.
The 12V DC supply voltage of the complete RS485 bus is mainly powered at 12W or 24W by
a switch mode power supply unit FSNT12-12V DC that is only 1 or 2 pitch units wide. When the
relay of the FSS12 is switched on, a power of 0.6 watts is required.
The setting and display screen is subdivided into 3 fields:
Field 1: The normal display is the unit of the meter reading currently displayed in Field 3. This
alternates every 4 seconds with either kilowatt hours kWh (KWH in display) or megawatt
hours MWh (MWH in display). The display in Field 1 is supplemented by a + sign after the
reading to indicate that the off-peak tariff rate is applied to E1/E2.
Field 2: Instantaneous values of energy consumption (active power) in watt (W) or kilowatt
(kW). The left-pointing arrow in Field 1 indicates an automatic switchover from 0 to 99W to
0.1 to 65kW.
Field 3: The meter reading is the normal display. Every 4 seconds the display alternates between 3 whole numbers and 1 decimal point (from 0.1 to 999.9kWh) and 1 or max 3 whole
numbers (from 0 to 999 MWh).
Wireless telegrams: A power telegram is transmitted every 130 seconds and the display
is updated. Otherwise a telegram is transmitted within 20 seconds if the power changes by
minimum 10 percent. A switchover from HT to NT is transmitted immediately in the same way as
a meter reading change. A full telegram comprising meter reading HT, meter reading NT and
power is transmitted 20 seconds after the power supply is switched on and then every
10 minutes. The LED lights up briefly when a telegram is transmitted.
See page 2-3 of the 'The Eltako Wireless Building' Catalogue for a detailed description.
FAM-USB with license FVS-Energy USB wireless receiver
FSS12-12V DC
Wireless energy meter transmitter module
Recommended retail prices excluding VAT.
EAN 4010312305003
149,60 €/pc.
EAN 4010312301944
79,80 €/pc.
5
Direct display with the
Energy Consumption Indicator EVA12
6
EVA12-32 A
Maximum current 32A, standby loss 0.5 watt only.
Field 1
Field 2
Field 3
Typical connection
Field 1
Field 2
Field 3
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18mm wide, 58mm deep.
The energy consumption indicator EVA12 uses the current between input and output to
measure active energy in the same way as a single-phase energy meter. It saves the
consumption parameter in a non-volatile memory.
Accuracy conforms to Class B MID (1%) like all Eltako single-phase energy meters.
The inrush current is 20mA.
In this way the energy consumption indicator reproduces exactly the reading on the
billing energy meter installed at a different location in the building.
The display is subdivided into 3 fields.
Field 1:
This display refers to the cumulative value in field 3.
IIII moving slowly to the right = Field 3 shows the cumulative consumption since last
reset. This is the display standard mode.
H01 = Field 3 shows the consumption for the last hour up to H24 = 24 hours ago.
D01 = Field 3 shows the consumption for the last day up to D31 = 31 days ago.
M01 = Field 3 shows the consumption for the last month up to M12 = 12 months ago.
Y01 = Field 3 shows the consumption for the last year up to Y24 = 24 years ago.
Field 2:
Instantaneous values of energy consumption (active power) in watt (W) or kilowatt (kW).
The display arrows on the left and right show the automatic change W and kW.
Field 3:
Cumulative value in kWh. Display up to 9.999kWh with 3 decimal digits, from 10kWh
with 1 deciaml digit and from 1000 kWh without decimal digit.
Press the left button MODE to scroll down the display options which are shown in field 1:
H01, D01, M01 and Y01 as described above. Finally, press MODE to show the abbreviation of
the set language, e.g. GB for English, D for German and F for French.
Press the right button SELECT once within the display options to increment the indicated
figure by 1. The corresponding value is indicated in field 3. The last clock hour then becomes
the hour before last, etc.
If the active language was selected with MODE, press SELECT to switch to a different
language. Exit the new language setting by pressing MODE to activate the setting.
The program returns to the standard display mode automatically if MODE or SELECT are not
operated for 20 seconds or if you press both buttons briefly simultaneously.
Reset
To start saving the values to the nearest hour, we recommend performing a reset at
an opportune moment after installation. Hold down the buttons MODE and SELECT
simultaneously for a further 3 seconds until RES appears in field 1. Then press SELECT briefly
to reset all memories. Afterwards the program returns automatically to standard display
mode.
Technical data page 18.
EVA12-32A
Maximum current 32 A
Recommended retail prices excluding VAT.
EAN 4010312500828
59,90 €/pc.
Wireless Single-phase Energy Meter
Transmitter Modules FWZ12 and FWZ61
FWZ12-16 A
7
Wireless single-phase energy meter transmitter module,
maximum current 16A. Only 0.5 watt standby loss.
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18mm wide, 58mm deep.
This single-phase energy meter measures active energy by means of the current between input
and output and transmits the consumption and meter reading over the Eltako wireless network.
Accuracy class B (1%).
Evaluation on PC using the Visualisation and Control Software FVS or the energy
consumption indicators FEA55LED or FEA55D. FVS-Energy and FVS-Home support up to
100 transmitter modules, FVS-Professional up to 250 transmitter modules.
The internal power consumption of max. 0.5 watt active power is neither metered nor indicated.
Like all meters without PTB or MID approval in Germany, not approved to levy electricity charges.
1 phase conductor with a max. current up to 16A can be connected. The inrush current is
20mA. The consumption is saved to a non-volatile memory and is immediately available
again after a power failure.
Wireless telegrams: A telegram is transmitted within 20 seconds if the power status changes
by min. 10 percent. A change in meter reading is transmitted immediately. A full telegram comprising meter reading and power status is transmitted every 10 minutes.
When the power supply is switched on, a teach-in telegram is sent to teach in the associated
energy consumption indicator.
If the L input and the L output were interchanged when hooked up, a normal rate (HT)/off-peak
(NT) switchover telegram is transmitted to indicate the hook-up error.
FWZ12-16A
Wireless single-phase energy meter
transmitter module 16A
EAN 4010312303184
74,80 €/pc.
FWZ12-65 A
Wireless single-phase energy meter transmitter module, maximum current
65A. Only 0.5 watt standby loss.
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18 mm wide, 58 mm deep.
Internal power consumption max. 0.5 watt active power.
1 phase conductor with a max. current up to 65A can be connected.
The inrush current is 40mA.
Functions same as FWZ12-16A.
FWZ12-65A
Wireless single-phase energy meter
transmitter module 65A
EAN 4010312311059
80,80 €/pc.
FWZ61-16 A
Wireless single-phase energy meter transmitter module,
maximum current 16A. Only 0.5 watt standby loss.
For installation. 45 mm long, 55 mm wide, 35 mm deep.
Internal power consumption max. 0.5 watt active power.
1 phase conductor with a max. current up to 16A can be connected. The inrush current is 20mA.
Functions same as FWZ12-16A.
FWZ61-16A
Wireless single-phase energy meter
transmitter module
Recommended retail prices excluding VAT.
EAN 4010312302354
71,80 €/pc.
Wireless Actuator – Impulse Switch with integr. relay function
FSR70W and FSR61VA
8
FSR70W-16 A
1 NO contact not potential free 16A/250V AC, incandescent lamps up to
2000 watts. With integrated active power measurement up to 3680 watts.
Bidirectional wireless and with repeater function. Only 0.9 watt standby loss.
Mounting in the 230 V power supply cord, e.g. in false ceilings.
100mm long, 50mm wide and 31mm deep.
The integrated active power measurement measures power upwards of approx. 10W when the
contact is closed and transmits it to the Eltako wireless network. Signal evaluated by the FVS
Wireless Visualisation and Control Software or the power consumption displays FEA55.
With bidirectional wireless; in addition, a repeater function can be switched in. Every change
in state and incoming central command telegrams are confirmed by a wireless telegram.
This wireless telegram can be taught-in in other actuators, in the FVS software and in FUA55
universal displays.
Function rotary switches
on the side
FSR70W-16A
Wireless actuator – Impulse switch with integr.
relay function with active power measurement
EAN 4010312312179
95,90 €/pc.
FSR61VA-10 A
1 NO contact not potential free 10A/250V AC, incandescent lamps up to
2000 watts, off delay with switch-off early warning and switchable pushbutton permanent light. With integrated current measurement up to 10 A.
Bidirectional wireless and with repeater function.
Only 0.7 watt standby loss.
Typical connection
FSR61VA-10 A
For installation. 45 mm long, 55 mm wide, 33 mm deep.
Supply voltage 230 V.
The apparent power from approx. 10VA up to 2300VA will be measured at closed contacts
with the integrated power measurement and transmitted into the Eltako wireless system. Signal
evaluated by the FVS Wireless Visualisation and Control Software or the power consumption
displays FEA55.
With bidirectional wireless; in addition, a repeater function can be switched in. Every change
in state and incoming central command telegrams are confirmed by a wireless telegram.
This wireless telegram can be taught-in in other actuators, in the FVS software and in FUA55
universal displays.
Scene control: several FSR61s can be switched on or off in a scene by one of the four control
signals of a double-rocker pushbutton taught-in as scene pushbutton.
Wireless actuator – Impulse switch with integr.
relay function with current measurement
Recommended retail prices excluding VAT.
EAN 4010312311462
73,70 €/pc.
Selection Table
Single-phase and Three-phase Energy Meters
The smart counting champions
9
Eltako offers a complete range of energy meters for DIN-EN 60715 TH35 rail mounting from 32A up to 65A. Special attention
should be paid to the power consumption of only 0.3W active power of the 32A and 65A single-phase devices.
If energy meters for DIN-EN 60715 TH35 rail mounting are not used for billing we recommend the "Economy Line" without
approval. Our marking is an "E" in the type designation: WSZ12DE-32A, WSZ12E-65A, DSZ12DE-3x65A and DSZ12WDE-3x5A.
All meters have an S0 interface according to DIN 43 864.
1
1
4
4
4
4
4
4
-
-
-
–
–
–
–
–
5 (32) 10(65) 5(32) 10(65) 5 (32) 10(65) 5 (6)1) 10(65) 5 (6)1) 10(65) 5 (6)1) 5 (60) 5 (60) 5(60)
Display drum type register digits
Display LC display digits
bottom
1
Two-way three-phase energy meter
Reference current I ref (Limiting current
I max) A
17
center
1
Three-phase energy meter
With MID approval
17
top
1
Meter mounting installation
Single-phase energy meter
17
DSZ60D
Economy
Line
16
DSZ60
Economy
Line
15
WSZ60
bottom
DSZ12WDZ-3x5A
14
top
DSZ12DZ-3x65A
14
bottom
DSZ12WDE-3x5 A
13
top
DSZ12DE-3x65 A
Economy
Line
13
DSZ12WD-3x5 A
Economy
Line
12
DSZ12D-3x65 A
bottom
WZR12-32 A
11
top
WSZ12DE-65 A
11
bottom
WSZ12DE-32 A
10
top
WSZ12D-65 A
Modular device for mounting on DIN rail
EN 60715 TH35, number of modules
18 mm each
10
WSZ12D-32 A
Page
6+1
5+2 2) 5+2 2) 5+2 2) 5+2 2)
6 +1 6 +1 6 +1 6 +1
2 /4
6+1
5+2 2) 5+2 2) 5+2 2) 5+2 2) 5+2 2) 5+2 2)
6 +1 6 +1 6 +1 6 +1 6 +1 6 +1
6 +1
Accuracy class MID, inaccuracy ±1%
B
B
B
B
B
B
B
B
B
B
B
B
B
B
With return stop
Display instantaneous values
Indication of misconnection
Low standby loss
S0 interface potential free
1)
CT operated energy meter
2)
Switches over automatically from 5+2 to 6+1.
Informations about MID see page 20.
Single-phase Energy Meters WSZ12D
with MID approval
10
WSZ12D-32A
Maximum current 32A. Standby loss 0.7 watt only.
Typical connection
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
This single-phase energy meter measures active energy by means of the current between input
and output. The internal power consumption of 0.7 watt active power is neither metered nor
indicated.
1 phase conductor with a max. current of up to 32A can be connected.
The start current is 2OmA.
Zwei N-Klemmen für die sichere Querverdrahtung mehrerer Zähler.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply. Press the button.
Below the displays is a button which you can use to browse through the menu as described in
the User Manual. First the backlighting switches on. Then you can display the total active energy,
active energy of the resettable memory and the instantaneous values for active power, voltage
and current.
Power consumption is shown by a bar flashing at a rate of 1000 times per kWh.
Error message
In the event of a connection error the bar flashes at a high rate (2 times per second).
Technical data page 18.
WSZ12D-32A
MID approval
EAN 4010312501269
129,00 €/pc.
WSZ12D-65 A
Maximum current 65A. Standby loss 0.7 watt only.
Typical connection
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
This single-phase energy meter measures active energy by means of the current between input
and output. The internal power consumption of 0.7 watt active power is neither metered nor
indicated.
1 phase conductor with a max. current up to 65A can be connected.
The start current is 4OmA.
Two N terminals for secure cross wiring of several counters.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply. Press the button.
Below the displays is a button which you can use to browse through the menu as described in
the User Manual. First the backlighting switches on. Then you can display the total active energy,
active energy of the resettable memory and the instantaneous values for active power, voltage
and current.
Power consumption is shown by a bar flashing at a rate of 1000 times per kWh.
Error message
In the event of a connection error the bar flashes at a high rate (2 times per second).
Technical data page 18.
WSZ12D-65A
MID approval
Recommended retail prices excluding VAT.
EAN 4010312501283
140,00 €/pc.
Single-phase Energy Meters WSZ12
without approval
WSZ12DE-32 A
11
Maximum current 32A. Standby loss 0.5 watt only.
Typical connection
Modular device for DIN-EN 60715 TH35 rail mounting. 1 module = 18mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
It measures active energy by means of the current between input and output. The internal
power consumption of 0.5 watt active power is neither metered nor indicated. Like all meters
without approval (e.g. MID), this meter is not permitted for billing.
Every 30 seconds, the display switches for 5 seconds from the accumulated active energy
in kWh to the momentary consumption in watts.
1 phase conductor with a max. current up to 32A can be connected. The inrush current is
20mA. The display can only be read when the power supply is on. However, the consumption
is saved to a non-volatile memory and is displayed immediately after power restoration.
Two N terminals for secure cross wiring of several counters.
The flashing decimal point is dependent on power consumption and indicates that power is
being consumed. If the connection is incorrectly wired, the display shows the message 'false'.
The digital display has 7 digits. Two decimal places are indicated up to 99999.99kWh.
Above 100000.0kWh there is only one decimal place. Assuming the maximum theoretical
power consumption, the display would have a service life of more than 15 years.
The power consumption is displayed with a decimal point.
Energy meter connected,
no power consumption
Energy meter correctly
connected, with power
consumption
T = depends on power consumption
2000 Imp./kWh
time
time
T = 50 ms
Technical data page 16.
WSZ12DE-32A
without approval
EAN 4010312501245
56,00 €/pc.
WSZ12DE-65 A
Maximum current 65A. Standby loss 0.5 watt only.
Typical connection
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
This single-phase energy meter measures active energy by means of the current between input
and output. The internal power consumption of 0.5 watt active power is neither metered nor
indicated. Like all meters without approval (e.g. MID), this meter is not permitted for billing.
Every 30 seconds, the display switches for 5 seconds from the accumulated active energy
in kWh to the momentary consumption in watts.
1 phase conductor with a max. current up to 65A can be connected. The inrush current is
40mA. The display can only be read when the power supply is on. However, the consumption
is saved to a non-volatile memory and is displayed immediately after power restoration.
Two N terminals for secure cross wiring of several counters.
The flashing decimal point is dependent on power consumption and indicates that power is
being consumed. If the connection is incorrectly wired, the display shows the message 'false'.
The digital display has 7 digits. Two decimal places are indicated up to 99999.99 kWh.
Above 100000.0 kWh there is only one decimal place.
The power consumption is displayed with a decimal point.
Energy meter
connected, no power
consumption
T = depends on power consumption
1000 Imp./ kWh
time
Energy meter correctly
connected, with power consumption
time
T = 50 ms
WSZ12DE-65A
without approval
Unverbindliche Preisempfehlung
zuzüglich
Recommended
retail prices excluding
VAT. gesetzl. MwSt.
EAN 4010312501276
76,20 €/pc.
Single-phase Energy Meter WZR12 with reset,
without approval
12
WZR12-32 A
Maximum current 32A, standby loss 0.5 watt only.
Modular device for DIN-EN 60715 TH35 rail mounting.
1 module = 18mm wide, 58mm deep.
Field 1
Field 2
Field 3
Typical connection
Field 1
Field 2
Field 3
This single-phase energy meter with reset function uses the current between input and
output to measure active energy and saves the consumption parameter in a non-volatile
memory.
Accuracy conforms to Class B MID (1%) like all Eltako single-phase energy meters,
the inrush current is 20mA.
The display is subdivided into 3 fields.
Field 1:
This display refers to the cumulative value in field 3.
|||| moving slowly to the right = Field 3 shows the cumulative consumption since last
reset. This is the display standard mode.
H01 = Field 3 shows the consumption for the last hour up to H24 = 24 hours ago.
D01 = Field 3 shows the consumption for the last day up to D95 = 95 days ago.
Field 2:
Instantaneous values of energy consumption (active power) in watt (W) or kilowatt (kW).
The display arrows on the left and right show the automatic change W and kW.
Field 3:
Cumulative value in kWh. Display up to 9.999kWh with 3 decimal digits, from 10kWh
with 1 decimal digit and from 1000kWh without decimal digit.
Press the left button MODE to scroll down the display options which are shown in field 1:
H01 and D01 as described above. Finally, press MODE to show the abbreviation of the set
language, e.g. GB for English, D for German, F for French and ES for Spanish.
Press the right button SELECT once within the display options to increment the indicated
figure by 1. The corresponding value is indicated in field 3. The last clock hour then becomes
the hour before last, etc.
If the active language was selected with MODE, press SELECT to switch to a different
language. Exit the new language setting by pressing MODE to activate the setting.
The program returns to the standard display mode automatically if MODE or SELECT are not
operated for 20 seconds or if you press both buttons briefly simultaneously.
Reset
Hold down the buttons MODE and SELECT simultaneously for 3 seconds until RES appears
in segment 1. Then press SELECT briefly to reset all memories. Afterwards the program
returns automatically to standard display mode.
Technical data page 18.
WZR12-32A
Maximum current 32 A
Recommended retail prices excluding VAT.
EAN 4010312501252
48,60 €/pc.
Three-phase Energy
Elektronische
Wechselstromzähler
Meters DSZ12 WSZ
mit Zulassung
with
display and
und
MID
geeicht
approval
DSZ12D-3x65 A
13
Maximum current 3x65A. Standby loss 0.4 watt per path only.
Typical connection
4-wire-connection 3x230/400V
S0 output
Modular device for DIN-EN 60715 TH35 rail mounting.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
It measures active energy by means of the current between input and output. The internal
power consumption of 0.4 watt active power per path is neither metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 65A can be connected.
The inrush current is 40mA.
The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply.
Power consumption is shown by a bar flashing at a rate of 100 times per kWh.
Designed as standard for using as double-tariff meter: Switch over to a second tariff by
applying 230V to terminals E1/E2.
On the right next to the display are the keys MODE and SELECT. Press them to scroll through
the menu according to the operation manual. First the background lighting switches on. The
display then shows the total active energy per tariff, the active energy per resettable memory
RS1 or RS2, and the instantaneous values of consumption, voltage and current per phase.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false' and the
corresponding phase conductor are indicated on the display.
Technical data page 18.
MID approval
DSZ12D-3x65A
EAN 4010312501207
239,00 €/pc.
WSZ12B-65 A A
DSZ12WD-3x5
CT operated energy meter with settable CT ratio and MID.
Maximum current 3x5A. Standby loss 0.4 watt per path only.
Typical connection
4-wire-connection 3x230/400V
S0 output
Modular device for DIN-EN 60715 TH35 rail mounting.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
This three-phase energy meter measures active energy by means of the current between input
and output. The internal power consumption of 0.4 watt active power per path is neither metered
nor indicated.
1, 2 or 3 phase conductors with max. currents up to 5A can be connected.
The inrush current is 10mA.
The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply.
Power consumption is shown by a bar flashing at a rate of 10 times per kWh.
On the right next to the display are the keys MODE and SELECT. Press them to scroll through
the menu according to the operation manual. First the background lighting switches on. The
display then shows the total active energy, the active energy per resettable memory, and the
instantaneous values of consumption, voltage and current per phase.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a bridge over the
terminals which are marked with 'JUMPER'. To adjust the CT ratio to the installed transformer
remove the bridge and reset the energy meter according to the operation manual. Then block it
again with the bridge. Adjustable current transformer ratios: 5:5, 50:5, 100:5, 150:5, 200:5,
250:5, 300:5, 400:5, 500:5, 600:5, 750:5, 1000:5, 1250:5 and 1500:5.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false' and the
corresponding phase conductor are indicated on the display.
Important! Before working on the current transformers disconnect the voltage paths of the
energy meters.
Technical data page 18.
DSZ12WD-3x5A
MID approval
Unverbindliche Preisempfehlung
zuzüglich
Recommended
retail prices excluding
VAT. gesetzl. MwSt.
EAN 4010312501214
259,00 €/pc.
Three-phase Energy Meters DSZ12
with display, without approval
14
DSZ12DE-3x65 A
Maximum current 3x65A. Standby loss 0.4 watt per path only.
Typical connection
4-wire-connection 3x230/400V
S0 output
Modular device for DIN-EN 60715 TH35 rail mounting.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
It measures active energy by means of the current between input and output. The internal
power consumption of 0.4 watt active power per path is neither metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 65A can be connected.
The inrush current is 40mA.
The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply.
Power consumption is shown by a bar flashing at a rate of 100 times per kWh.
Designed as standard for using as double-tariff meter: Switch over to a second tariff by
applying 230 V to terminals E1/E2.
On the right next to the display are the keys MODE and SELECT. Press them to scroll through
the menu according to the operation manual. First the background lighting switches on. The
display then shows the total active energy per tariff, the active energy per resettable memory
RS1 or RS2, and the instantaneous values of consumption, voltage and current per phase.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false' and the
corresponding phase conductor are indicated on the display.
Technical data page 18.
without approval
DSZ12DE-3x65A
EAN 4010312501221
198,20 €/pc.
WSZ12B-65 A A
DSZ12WDE-3x5
CT operated energy meter with settable CT ratio.
Maximum current 3x5A. Standby loss 0.4 watt per path only.
Typical connection
4-wire-connection 3x230/400V
S0 output
Modular device for DIN-EN 60715 TH35 rail mounting.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
This three-phase energy meter measures active energy by means of the current between input
and output. The internal power consumption of 0.4 watt active power per path is neither metered
nor indicated.
1, 2 or 3 phase conductors with max. currents up to 5A can be connected.
The inrush current is 10mA.
The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply.
Power consumption is shown by a bar flashing at a rate of 10 times per kWh.
On the right next to the display are the keys MODE and SELECT. Press them to scroll through
the menu according to the operation manual. First the background lighting switches on. The
display then shows the total active energy, the active energy per resettable memory, and the
instantaneous values of consumption, voltage and current per phase.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a bridge over the
terminals which are marked with 'JUMPER'. To adjust the CT ratio to the installed transformer
remove the bridge and reset the energy meter according to the operation manual. Then block it
again with the bridge. Adjustable current transformer ratios: 5:5, 50:5, 100:5, 150:5, 200:5,
250:5, 300:5, 400:5, 500:5, 600:5, 750:5, 1000:5, 1250:5 and 1500:5.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false' and the
corresponding phase conductor are indicated on the display.
Important! Before working on the current transformers disconnect the voltage paths of the
energy meters.
Technical data page 18.
DSZ12WDE-3x5A
without approval
Unverbindliche Preisempfehlung
zuzüglich
Recommended
retail prices excluding
VAT. gesetzl. MwSt.
EAN 4010312501238
238,00 €/pc.
Electronic Two-way
Elektronische
Wechselstromzähler
Three-phase Energy
WSZ Meter
mit Zulassung und
DSZ12DZ-3x65A
with
geeicht
display, MID approval
DSZ12DZ-3x65 A
15
Maximum current 3x65A. Standby loss 0.4 watt per path only.
Typical connection
4-wire-connection 3x230/400V
Modular device for DIN-EN 60715 TH35 rail mounting.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
The directly measuring two-way three-phase energy meter measures active energy by means of
the currents flowing between inputs and outputs. The internal power consumption of 0.4 watt
active power per path is neither metered nor indicated.
The active energy will be added dependently on the sign.
and power supply with a left Arrow
Energy consumption is displayed with a right arrow
each over the active bar in the display.
3 phase conductors with max. currents up to 65A must be connected.
The inrush current is 40mA.
The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply.
Power consumption is shown by a bar flashing at a rate of 100 times per kWh.
On the right next to the display are the keys MODE and SELECT. Press them to scroll through the
menu according to the operation manual. First the background lighting switches on. After that,
the total active energy per reference and supply, the active energy of the resettable memory per
reference and supply as well as the instantaneous values of power, voltage and current per phase
can be displayed.
Error message (false)
When phase conductor is missing the bar 'false' appears and the corresponding phase conductor
is also shown in the display.
July 2012.
Technical data page 18.
DSZ12DZ-3x65A
MID approval
Unverbindliche Preisempfehlung
zuzüglich
Recommended
retail prices excluding
VAT. gesetzl. MwSt.
EAN 4010312501429
239,00 €/pc.
Two-way Three-phase
Elektronische
Wechselstromzähler
Energy Meter
WSZ
mit Zulassung und
DSZ12WDZ-3x5
A with
geeicht
display, MID approval
16
DSZ12WDZ-3x5 A
CT operated energy meter with settable CT ratio and MID.
Maximum current 3x5A. Standby loss 0.4 watt per path only.
Typical connection
4-wire-connection 3x230/400V
Modular device for DIN-EN 60715 TH35 rail mounting.
4 modules = 70mm wide and 58mm deep.
Accuracy class B (1%). With S0 interface.
The directly measuring two-way three-phase energy meter measures active energy by means of
the currents flowing between inputs and outputs. The internal power consumption of 0.4 watt
active power per path is neither metered nor indicated.
The active energy will be added dependently on the sign.
and power supply with a left arrow
Energy consumption is displayed with a right arrow
each over the active bar in the display.
3 phase conductors with max. currents up to 5A must be connected.
The inrush current is 10mA.
The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks without power
supply.
Power consumption is shown by a bar flashing at a rate of 10 times per kWh. On the right next
to the display are the keys MODE and SELECT. Press them to scroll through the menu. First the
background lighting switches on. After that, the total active energy per reference and supply, the
active energy of the resettable memory per reference and supply as well as the instantaneous
values of power, voltage and current per phase can be displayed.
The CT ratio can also be set. It is set to 5:5 at the factory and blocked with a bridge over the
terminals which are marked with 'JUMPER'. To adjust the CT ratio to the installed transformer
remove the bridge and reset the energy meter according to the operation manual. Then block
it again with the bridge. Adjustable current transformer ratios: 5:5, 50:5, 100:5, 150:5, 200:5,
250:5, 300:5, 400:5, 500:5, 600:5, 750:5, 1000:5, 1250:5 and 1500:5.
Error message (false)
When phase conductor is missing the bar 'false' appears and the corresponding phase conductor is also shown in the display.
Important! Before working on the current transformers disconnect the voltage paths of the
energy meters.
July 2012.
Technical data page 18.
DSZ12WDZ-3x5A
MID approval
Unverbindliche Preisempfehlung
zuzüglich
Recommended
retail prices excluding
VAT. gesetzl. MwSt.
EAN 4010312501436
259,00 €/pc.
Single-phase Energy Meter WSZ60, Three-phase
Energy Meters DSZ60 and DSZ60D, MID approval
WSZ60
17
Maximum current 60A, standby loss 1.2 watt.
Single-phase energy meter for 3-point energy meter mounting.
Accuracy class B.
This single-phase energy meter measures active energy by means of the current between input
and output. The internal power consumption of 1.2 watt active power is neither metered nor
indicated.
1 phase conductor with a max. current up to 60A can be connected. The inrush current is
10mA. The meter can be read anytime without power supply.
Power consumption is shown by a red LED flashing at a rate of 1000 times per kWh.
Permanent light: halt; light off: free of tension.
Technical data page 19.
MID approval
WSZ60
EAN 4010312501368
50,30 €/pc.
DSZ60
Maximum current 3x60A, standby loss 1 watt per path.
Three-phase energy meter for 3-point energy meter mounting.
Accuracy class B.
This directly measuring three-phase energy meter measures active energy by means of the
current between input and output. The internal power consumption of 1 watt active power per
path is neither metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 60 A can be connected.
The inrush current is 10 mA. The meter can be read anytime without power supply.
The N terminal must always be connected.
Power consumption is shown by a red LED flashing at a rate of 500 times per kWh.
Permanent light: halt; light off: free of tension.
Technical data page 19.
MID approval
DSZ60
EAN 4010312501351
97,40 €/pc.
DSZ60D
Maximum current 3x60A, standby loss 1 watt per path.
Three-phase energy meter for 3-point energy meter mounting.
Accuracy class B.
With additional terminals to switch over to a second tariff.
This directly measuring three-phase energy meter measures active energy by means of the
current between input and output. The internal power consumption of 1 watt active power per
path is neither metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 60 A can be connected.
The inrush current is 10mA.
The N terminal must always be connected.
The 7 segment LC display is also legible without external power supply.
Power consumption is shown by a red LED flashing at a rate of 500 times per kWh.
Permanent light: halt; light off: free of tension.
Technical data page 19.
DSZ60D
MID approval
Unverbindliche Preisempfehlung
zuzüglich
Recommended
retail prices excluding
VAT. gesetzl. MwSt.
EAN 4010312501344
119,30 €/pc.
Technical Data Single-phase and Three-phase
Energy Meters and Energy Consumption Indicator
18
EVA12-32 A
WSZ12D-65 A
DSZ12D-3x65 A
DSZ12WD-3x5A
WSZ12D-32A
WSZ12DE-65 A
DSZ12DE-3x65 A
DSZ12WDE-3x5 A
DSZ12DZ-3x65 A
DSZ12WDZ-3x5A
WSZ12DE-32 A
WZR12-32 A
Rated voltage
Extended range
230 V, 50 Hz
-2O % /+15%
230 V, 50 Hz
-2O % /+15%
3 x230 / 400 V, 50 Hz
-2O % /+15%
3 x230 / 400 V, 50 Hz
-2O % /+15%
Reference current I ref
(Limiting current I max )
5 (32) A
10 (65) A
3x10 (65) A
3x5(6) A
Internal consumption
Active power
0.5 W
WSZ12D: 0.7 W
0.5 W
WSZ12D: 0.7 W
0.4 W per path
0.4 W per path
Display
LC display 7 digits,
LC display 7 digits,
LC display 7 digits,
therefrom 1 or 2 digits after the therefrom 1 or 2 digits after the therefrom 1 or 2 digits after
decimal point
decimal point
the decimal point
Display instantaneous
values
WSZ12D: With a key you
can select active power,
voltage and current
WSZ12D: With a key you
can select active power,
voltage and current
With a key you can select
total active energy and
active energy resettable,
power, voltage and current
per phase.
EVA12, WSZ12DE, WZR12:
active power
WSZ12DE:
active power
DSZ12D, DSZ12DE:
tariff 1 and tariff 2
LC display 7 digits,
therefrom 1 digit after the
decimal point
With a key you can select
total active energy and
active energy resettable,
power, voltage and current
per phase
DSZ12DZ:
consumption and supply
Accuracy class ±1%
B
B
B
B
Inrush current according to
accuracy class B
20 mA
40 mA
40 mA
10 mA
Operating temperature
-10 /+55°C
-10 /+55°C
-10 /+55°C
-10 /+55°C
Pulse interface S0 according to DIN EN 62053-31, potential free by opto-coupler, max. 30 V DC / 2O mA and min. 5 V DC.
Impedance 100 ohms
Interface
(not EVA12, WZR12)
WSZ12D:
pulse length 30 ms
WSZ12D:
pulse length 30 ms
WSZ12DE:
pulse length 50 ms
WSZ12DE:
pulse length 50 ms
pulse length 30 ms
pulse length 30 ms
1000 Imp./kWh
10 Imp./kWh
Terminal
cover claps
Terminal
cover claps
2000 Imp./kWh
Terminal cover sealable
2000 Imp./kWh
WSZ12DE-65 A:
1000 Imp./kWh
With sealing cap PK18.
For the current path 1 sealing
cap is required
With sealing cap PK18.
For the current path 1 sealing
cap is required
Protection degree
Maximum conductor
cross section
lP50 for mounting in distribution cabines with protection class IP51
6 mm 2
WSZ12D:
L terminals 16 mm 2
L terminals 16 mm 2 ,
N and S0 terminals 6 mm 2
N and L terminals 16 mm 2 ,
S0 terminals 6 mm 2
The N terminal of three-phase energy meters must be connected, if not the electronics might be destroyed.
Compliance with: EN 50470
29.05.2012
Technical Data Single-phase and Three-phase
Energy Meters for meter mounting installation
WSZ60
DSZ60
DSZ60D
Rated voltage
Extended range
230 V, 50 Hz
-1O % /+10 %
3 x230 /400 V, 50 Hz
-1O % /+10 %
3 x230 /400 V, 50 Hz
-1O % /+10 %
Reference current I ref
(Limiting current I max )
5 (60) A
Internal consumption
Active power
1.2W
Display
drum type register with 7 digits and
1 decimal digit
LC display 7 digits,
therefrom 1 decimal digit
Accuracy class ± 1%
B
B
B
Backstop
yes
yes
yes
Inrush current
10 mA
10 mA
10 mA
Number of tariffs
1
1
2
Operating temperature
3x5 (60) A
1W per path
-40/+70°C
1 W per path
-25/+70°C
Protection degree
IP51
IP51
IP51
Maximum conductor cross section
35 mm2
35 mm2
35 mm2
weight
1.3 kg
1.7 kg
1.6 kg
dimensions
176x121x63 mm
EG model test certificate
DE-07-MI003-PTB 015
Compliance with: EN 50470
270x178x60 mm
DE-08-MI003-PTB 013
19
Measuring Instruments Directive MID
20
The Measuring Instruments Directive (MID) is a new European Union (EU) directive aimed at creating a single
market for measuring instruments across the EU. It came into force on 30th October 2006. This regulation means
that meters which receive a MID approval can be used in any other EU country irrespective of where in the EU that
approval was granted. The meters can be used for billing purposes, industrial and commercial purposes.
Therefore, the MID replaces the present regulations consisting of national approval and subsequent
calibration.
The MID covers a range of measuring instruments which include gas, water and active electrical energy meters.
According to the directive all new types of meters must comply with the requirements of the directive as from
30 October 2006. However, all instruments approved before this date may continue to be marketed for up to
10 years.
For new types of measuring instruments the MID directive includes the following requirements:
■ Compliance with standard DIN EN 50470-1-3
■ Completion of conformity assessment
■ Placing the product on the market
■ Marking the devices in accordance with the directive
■ Market surveillance
Validity of calibration, subsequent calibration and any charges will still be regulated by the national law.
When a MID device is put into circulation, we declare the conformity with MID in the operation instructions.
The number of the type examination certificate is also indicated there. It begins with the country code of the
accredited laboratory, such as DE for Germany and CH for Switzerland.
The MID marking signifies the following:
CE – M12 – 1259
Notation of the Authorities which have carried out the inspection
Metrology marking and year of assessment of conformity
CE approval
The year after the year of assessment of conformity is important for the follow-up calibration.
It will be renewed every year.
The duration of validity of the calibration is liable to national law.
Which accuracy classes exist?
The MID refers to new accuracy classes which are A, B, and C. These are in accordance with the familiar ones
like 2, 1, and 0,5. The ELTAKO meters have accuracy class B ( = former 1 with PTB).
Germany
International contact addresses
Offices and Sales representatives
and sales representatives
Mecklenburg-Vorpommern/
Brandenburg (North)/
Saxony-Anhalt (North)
Fellbach
Eltako Headquarter
Hofener Straße 54
70736 Fellbach
0711 94350000
0711 5183740
info@eltako.de
kundenservice@eltako.de
Klaus-Peter Schmitz
18276 Sarmstorf
03843 215884
03843 215884
0176 13582501
schmitz@eltako.de
Baden-Württemberg
Carsten Krampe
75172 Pforzheim
0173 3180392
krampe@eltako.de
Lower Saxony
Detlef Hilker
31840 Hessisch Oldendorf/Barksen
05152 6984480
0173 3180390
hilker@eltako.de
Bavaria (North)
Horst Rock
91126 Schwabach
09122 61179
09122 61159
rock@eltako.de
North Rhine-Westphalia (North)
Stefan Krause
32351 Stemwede
0162 2575119
krause@eltako.de
Bavaria (South)
Austria (West)
Norway
Representative Robert Goedicke
+43 664 1823322
goedicke@eltako.com
Malthe Winje Automasjon AS
NO-1415 Oppegard
Austria (East)
Representative Andreas Kaider
+43 699 11090025
kaider@eltako.com
Austria (East)
Representative Winfried Rac
+43 660 8081310
rac@eltako.com
Belgium/France/ Luxembourg
Serelec n.v.
B-9000 Gent
+32 9 2234953
info@serelec-nv.be
Cyprus
MeshMade Ltd
CY 1096, Nicosia
+357 7000 6374
info@meshmade.com
Czech Republic
Elka Hugo Krischke GmbH
82024 Taufkirchen
089 3090409-0
089 3090409-50
krischke@eltako.de
North Rhine-Westphalia (South)
Jörg Kleimann
53340 Meckenheim
0162 2575120
kleimann@eltako.de
Representative Peter Loužecký
CZ-40011 Ústí nad Labem
+420 475 621132
+420 724 175676
louzecky@eltako.com
Denmark
Berlin/Brandenburg/
Saxony (East)
North Rhine-Westphalia (East)
Olaf Knobel
15746 Groß-Köris
033766 21240
033766 21241
0176 13582503
knobel@eltako.de
Kay Westphal
44265 Dortmund
0176 13582506
0231 734171
westphal@eltako.de
Hamburg/Schl.-Holstein/Bremen
Gunnar Wetteborn
25355 Barmstedt
0176 13582502
04123 6834673
wetteborn@eltako.de
Rhineland-Palatinate/Saarland
Rainer Brilmayer
55411 Bingen
0176 13582516
brilmayer@eltako.de
Thuringia/Saxony (West)/
Saxony-Anhalt (South)
Hessen
Andreas Misch
39218 Schönebeck OT Elbenau
Daniel Böth
63811 Stockstadt am Main
0173 3180391
boeth@eltako.de
0176 13582505
misch@eltako.de
Technical support:
+49 176 13582514
+49 711 94350002
Export Sales Manager:
+49 711 94350005
thuente@eltako.de
technik-beratung1@eltako.de
export@eltako.de
Eltako GmbH
Hofener Straße 54, D-70736 Fellbach
+49 711 94350000
+49 711 5183740
info@eltako.de
www.eltako.de
SOLAR A/S
DK-6600 Vejen
+45 76 961200
jni@solar.dk
Gulf area
M/S Golden Sand Trading
U.A.E. – Dubai
+9 71 43595611
vasu2000@emirates.net.ae
Iceland
+47 66996100
firmapost@mwa.no
Netherlands (North)
Representative Hans Oving
NL-7701 VV Dedemsvaart
+31 523 616688
+31 6 21816115
oving@eltako.com
Netherlands (South)
Representative Dennis Schellenberg
NL-5854 PC Bergen (LB)
+31 6 50419067
schellenberg@eltako.com
Portugal
TEV2 – Dist. Mat. Eléctrico, Lda
P-4470-434 Maia
+351 229 478 170
info@tev.pt
Russia
ATLAS Group JSC
RU-127591 Moscow
+7 495 6423463
eltako@atlasgroup.ru
Sweden (North / Middle)
Representative Patrick Savinainen
S-69332 Degerfors
+46 070 9596906
patrick@eltako.com
Sweden (West/East)
Representative Dan Koril
S-57010 Korsberga
+46 070 3201102
dan@eltako.com
Sweden (South)
Representative Jonas Lundquist
S-26433 Klippan
+46 073 5815692
jonas@eltako.com
Reykjafell Ltd.
IS-125 Reykjavik Iceland
+35 4 5886010
reykjafell@reykjafell.is
Switzerland
Israel
Spain
Avital B.S. Ltd
Il-Holon
+97 23 5587717
avitalbs@zahav.net.il
Italy
Representative Tommaso Scrofani
I-64025 Pineto TE
+39 085 9491796
+39 347 3774888
scrofani@eltako.com
Demelectric AG
CH-8954 Geroldswil
+41 43 4554400
info@demelectric.ch
Representative Thomas Klassmann
E-08397 PINEDA/Poble Nou
+34 93 7692419
+34 650 959702
klassmann@eltako.com
South Africa
Innomatic (Pty) Ltd - Franz Marktl
ZA-Midrand
+27 11 8400840
sales@innomatic.co.za
Download PDF
Similar pages
Sitecom CN-205
Trust Multimedia Keyboard
Conceptronic CLHDMIMCHDMI video converter
Manual Eltako FVS, high