Document code: MN67291_ENG Revision 1.001 Page 1 of 25

User Manual

Revision 1.001

English

CANopen / RS232 / RS485 - Converter

(Order Code: HD67291-A1) for Website information: http://www.adfweb.com/?Product=HD67291 for Price information: http://www.adfweb.com/?Price=HD67291-A1

Benefits and Main Features:

Very easy to configure

Mountable on Rail DIN

RS232 / RS485 serial port changeable with software

Industrial temperature range:

-40°C / 85°C (-40°F / 185°F)

For others Converter / Adapter:

CANopen / Ethernet

See also the following link: www.adfweb.com?Product=HD67503

RS232 / RS485

See also the following link: www.adfweb.com?Product=HD67118

USB / RS485

See also the following link: www.adfweb.com?Product=HD67119

Do you need to choose a device? do you want help?

Ask it to the following link: www.adfweb.com?Cmd=helpme

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

Industrial Electronic Devices

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 2 of 25

INDEX:

INDEX

UPDATED DOCUMENTATION

REVISION LIST

WARNING

TRADEMARKS

SECURITY ALERT

EXAMPLE OF CONNECTION

CONNECTION SCHEME

CHARACTERISTICS

CONFIGURATION

POWER SUPPLY

FUNCTION MODES

LEDS

CANopen

RS232

RS485

USE OF COMPOSITOR SW67291

NEW PROJECT / OPEN PROJECT

SET COMMUNICATION

SET TRANSLATE PDO

SET TRANSMIT PDO

UPDATE DEVICE

ETHERNET PROTOCOL

Write Frames PDO

Write Frames SDO

Read Frames PDO

Read Frames SDO

ChecckSum

MECHANICAL DIMENSIONS

ORDER CODE

ACCESSORIES

DISCLAIMER

OTHER REGULATIONS AND STANDARDS

WARRANTIES AND TECHNICAL SUPPORT

RETURN POLICY

PRODUCTS AND RELATED DOCUMENTS

Pagina 2 di 25

6

7

8

9

4

5

6

Page

2

2

2

2

2

3

15

16

18

18

19

10

11

11

12

12

13

14

20

21

21

22

23

23

24

24

25

25

25

UPDATED DOCUMENTATION:

Dear customer, we thank you for your attention and we remind you that you need to check that the following document is:

Updated;

Related to the product you own.

To obtain the most recently updated document, note the “document code” that appears at the top right-hand corner of each page of this document.

With this “Document Code” go to web page www.adfweb.com/download/ and search for the corresponding code on the page. Click on the proper “Document

Code” and download the updates.

To obtain the updated documentation for the product that you own, note the

“Document Code” (Abbreviated written "Doc. Code" on the label on the product) and download the updated from our web site www.adfweb.com/download/

REVISION LIST:

Revision

1.000

1.001

Date

08/11/2012

04/03/2013

Author Chapter

Dp All

Dp All

Description

First release version

Added new chapters

WARNING:

ADFweb.com reserves the right to change information in this manual about our product without warning.

ADFweb.com is not responsible for any error this manual may contain.

TRADEMARKS:

All trademarks mentioned in this document belong to their respective owners.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 3 of 25

SECURITY ALERT:

G

ENERAL

I

NFORMATION

To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for each individual application, legal and safety regulation. The same applies also when using accessories.

I

NTENDED

U

SE

Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit switches, mechanical interlocks, etc.).

Q

UALIFIED

P

ERSONNEL

The device can be used only by qualified personnel, strictly in accordance with the specifications.

Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who have appropriate qualifications for their job.

R

ESIDUAL

R

ISKS

The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated by personnel untrained. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the possibility of damage.

CE

CONFORMITY

The declaration is made by us. You can send an email to [email protected]

or give us a call if you need it.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

Industrial Electronic Devices

EXAMPLE OF CONNECTION:

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 4 of 25

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

Industrial Electronic Devices

CONNECTION SCHEME:

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 5 of 25

Figure 1: Connection scheme for HD67291-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 6 of 25

CHARACTERISTICS:

The configurable “PROFIBUS Master / Ethernet” converter allows the following characteristics:

RS232 or RS485 selectable like serial;

Mountable on 35mm Rail DIN;

Power Supply 8...24V AC or 12...35V DC;

Temperature range -40°C to 85°C.

CONFIGURATION:

You need Compositor SW67291 software on your PC in order to perform the following:

Define the parameter of the CANopen;

Define the parameter of the Serial;

Define the PDOs used.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

Industrial Electronic Devices

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 7 of 25

POWER SUPPLY:

The device can be powered between a wide range of tensions. For more details see the two tables below.

VAC VDC

Vmin Vmax Vmin Vmax

HD67291-A1 8V 24V 12V 35V

Consumption at 24V DC:

HD67291-A1

Device W/VA

4

Caution: Not reverse the polarity power

HD67291-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 8 of 25

FUNCTION MODES:

HD67291-A1

The device has got two functions mode depending of the position of the Dip2 of ‘Dip-Switch A’:

The first, with Jumper3 inserted, is used for upload the Project/Firmware.

The second, with Jumper3 removed (factory setting), is used for the normal working of the device.

For the operations to follow for the updating (see ‘UPDATE DEVICE’ section).

According to the functioning mode, the LEDs will have specifics functions (see ‘LEDS’ section).

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 9 of 25

Industrial Electronic Devices

LEDS:

The device has got five LEDs that are used to give information of the functioning status.

The various meanings of the LEDs are described in the table below.

HD67575-A1

WITH C

.

S

.

B153

LED Normal Mode Boot Mode

1: (Yellow)

2: (green)

3: Device State (green) Blinks slowly (~1Hz) Blinks quickly

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 10 of 25

CANopen:

For terminate the CAN line with a 120R resistor it is necessary to insert the Jumper1 near the terminal block, like in figure.

Cable characteristics:

DC parameter:

AC parameters:

Length

Impedance

Impedance

70 Ohm/m

120 Ohm/m

Delay 5 ns/m

Baud Rate [bps] Length MAX [m]

10 K 5000

20 K

50 K

100 K

125 K

250 K

500 K

800 K

1000 K

2500

1000

650

500

250

100

50

25

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 11 of 25

RS232:

The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a Null

Modem cable (a serial cable where the pins 2 and 3 are crossed).

It is recommended that the RS232 cable not exceed 15 meters.

RS485:

For terminate the RS485 line with a 220Ω resistor it is necessary to insert the Jumper2 near the terminal block, like in figure.

The maximum length of the cable should be 1200m (4000 feet).

Here some codes of cables:

Belden: p/n 8132 - 2x 28AWG stranded twisted pairs conductor + foil shield + braid shield;

Belden p/n 82842 - 2x 24AWG stranded twisted pairs conductor + foil shield + braid shield;

Tasker: p/n C521 - 1x 24AWG twisted pair conductor + foil shield + braid shield;

Tasker: p/n C522 - 2x 24AWG twisted pairs conductor + foil shield + braid shield.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

USE OF COMPOSITOR SW67291:

To configure the Converter, use the available software that runs with Windows, called SW67291. It is downloadable on the site www.adfweb.com and its

Document code: MN67291_ENG Revision 1.001 Page 12 of 25 operation is described in this document. (This manual is referenced to the last

version of the software present on our web site). The software works with

MSWindows (MS 2000, XP, Vista, Seven, 8).

When launching the SW67291 the right window appears (Fig. 2).

Figure 2: Main window for SW67291

NEW PROJECT / OPEN PROJECT:

The “

New Project

” button creates the folder which contains the entire device configuration.

A device configuration can also be imported or exported:

To clone the configurations of a programmable “PROFIBUS Master / Ethernet” Converter in order to configure another device in the same manner, it is necessary to maintain the folder and all its contents;

To clone a project in order to obtain a different version of the project, it is sufficient to duplicate the project folder with another name and open the new folder with the button

Open Project

”.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 13 of 25

Industrial Electronic Devices

SET COMMUNICATION:

This section defines the fundamental communication parameter of two buses, CANopen and Serial.

By pressing the “

Set Communication

” button from the main window for SW67291 (Fig. 2) the window

“Set Communication” appears (Fig. 3).

The window is divided in two sections, one for the CANopen and the other for the Serial.

The means of the fields for “CANopen” are:

In the field “

ID Dev.

” the address of the CANopen side is defined;

In the field “

Baudrate

” the baudrate for the CANopen side is defined;

In the field “

Set Operational State at Start-Up

” the state of the CANopen is defined. I.e. If it is checked the board start in Operational State, else it start in Pre-Operational;

In the field “

Network Start at Start-Up

” the state of the CANopen network is defined. I.e. If it is checked the board send a command to set the Operational State of all the devices present in the network, after the time defined in the “

Delay

” field;

In the field “

Delay

” the delay before send the network command for the CANopen is defined;

SDO Timeout

” is the is the maximum time that the device attends for the answer from the Slave interrogated;

The means of the fields for “Ethernet” are:

In the field “

Serial

” the physical Serial to use is defined ;

In the field “

Baudrate

” the baudrate for the Serial side is defined;

In the field “

Parity

” the parity for the Serial side is defined;

Figure 3: “Set Communication” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 14 of 25

SET TRANSLATE PDO:

By pressing the “Set Translate PDO” button from the main window for SW67291-A1 (Fig. 2) the window “Receive PDOs” appears (Fig. 4).

The means of the fields are:

In the field “

COB-ID

” insert the Cob_ID of the CANopen Bus frame;

In the field “

Dimension

” insert the number of bytes of the CANopen Bus frame (the maximum dimension is 8 bytes);

In the field “

Mnemonic

” you can insert a brief description.

Figure 4: “Receive PDOs” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 15 of 25

SET TRANSMIT PDO:

By pressing the “Set Transmit PDO” button from the main window for SW67291-A1 (Fig. 2) the window “Transmit PDOs” appears (Fig. 5).

The means of the fields are:

In the field “

COB-ID

” insert the Cob_ID of the CANopen Bus frame;

In the field “

Dimension

” insert the number of bytes of the CANopen Bus frame (the maximum dimension is 8 bytes);

In the field “

Mnemonic

” you can insert a brief description.

Figure 5: “Transmit PDOs” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 16 of 25

Industrial Electronic Devices

UPDATE DEVICE:

Section “Update device” (Fig. 6):

In order to load the parameters or update the firmware in the gateway, follow these instructions:

Turn off the Device;

Connect the Null Modem Cable form your PC to the Gateway;

Insert the Boot Jumper (For more info see Fig. 1);

Select the COM port and press the “

Connect

” button;

Turn on the device;

Check the BOOT Led. It must blink quickly (For more info see Fig. 1);

Press the “

Next

” button;

Select which operations you want to do. You can select only “

Firmware

”, only

Project

” or both of them;

Press the “

Execute update firmware

” button to start the upload;

When all the operations are “OK” turn off the device;

Disconnect the Boot jumper;

Disconnect the RS232 Cable;

Turn on the device.

At this point the configuration/firmware on the device is correctly updated.

Figure 6: “Update Device” window

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 17 of 25

Industrial Electronic Devices

Note:

When you install a new version of the software it is better if the first time you do the update of the Firmware in the

HD67291-A1 device.

Note:

When you receive the device, for the first time, you have to update also the Firmware in the HD67053-B2-xxx or HD67053M-xxx devices.

Warning:

If the Fig. 7 appears when you try to do the Update before require assistance try these points:

Check if the serial COM port selected is the correct one;

Check if the USB or serial cable is connected between the PC and the device;

Try to repeat the operations for the updating;

If you are using a USB RS232 converter try with a native COM port or change the converter (only for HD67053M series);

Try with another PC;

Try to restart the PC;

If you are using the program inside a Virtual Machine, try to use in the main

Operating System;

If you are using Windows Seven or Vista, make sure that you have the administrator privileges;

Take attention at Firewall lock.

Figure 7: “Protection” window

In the case of HD67291-A1 you have to use the software “SW67291”: www.adfweb.com\download\filefold\SW67291.zip

.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 18 of 25

Industrial Electronic Devices

SERIAL PROTOCOL:

For the CANopen it is possible to use two types of data: SDO and PDO. It is possible to have no more than ten PDO, which must be declared in the “SW67291 Compositor”, while SDO should not be reported.

Write Frames

P

DO

The transmission of PDO is very simple: it has a fixed structure that consist in a maximum of fourteen bytes:

Byte Number Description

1 Start Byte (fixed to 0x55)

2 Number of Byte (without CheckSum)

3

4

5

Write Identifier (0x02)

Type of Data (PDO=0x01)

Number of frame to send (number of row of

“SW67291 compositor”)

6÷n+5

N+6

Data

CheckSum

The respons is compose from four bytes: n=number of byte defined in the Compositor

Byte Number Description

1 Start Byte (fixed to 0xAA)

2 Number of Byte (Fixed to 0x01)

3

4

Ok=0x01 / Error in sending=0x02

CheckSum

Example:

We want to write the frame number one of SW67291 Compositor:

Type of Data: PDO; Number of frame to send: 1; Data: 0x01020304

So the string of hexadecimal numbers is:

REQ:[55][07][02][01][01][01][02][03][04][6A]

RES:[AA][01][01][AC]

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 19 of 25

S

DO

The transmission of SDO is very simple: it has a fixed structure that consist in a maximum of fourteen bytes.

Byte Number Description

1 Start Byte (fixed to 0x55)

2 Number of Byte (without CheckSum)

3

4

Write Identifier (Write=0x02)

Type of Data (SDO=0x02)

5

6

7

8

Address of CANopen device connect to the HD67291

Index SDO Hi

Index SDO Lo

SubIndex SDO

9

10÷n+9

Number of byte of frame to send (n)

Data n+10 CheckSum n=number of byte defined in the Compositor

The Number of byte of frame to send (Byte 9) can have three values:

0x01: Send one byte;

0x02: Send two byte;

0x04: Send four byte.

The respons is compose from four bytes:

Byte Number Description

1 Start Byte (fixed to 0xAA)

2 Number of Byte (Fixed to 0x01)

3

4

Ok=0x01 / Parameter Error=0x02 / Error in sending=0x03

CheckSum

Example:

We want to write:

Address of CANopen device: 0x14; Type of Data: SDO; Index: 0x2000; SubIndex: 0x01; Number of byte of frame to send: 2;

Data: 0x1122

So the string of hexadecimal numbers is:

REQ:[55][09][02][02][14][20][00][01][02][11][22][CC]

RES:[AA][01][01][AC]

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Read Frames

P

DO

The Bytes that compose the request are six:

5

6

Document code: MN67291_ENG Revision 1.001 Page 20 of 25

Byte Number Description

1 Start Byte (fixed to 0x55)

2 Number of Byte (without CheckSum)

3

4

Read Identifier (Read=0x01)

Type of Data (PDO=0x01)

Number of frame to send (number of row of

“SW67291 Compositor”)

CheckSum

The Bytes that compose the respons are:

Byte Number Description

1 Start Byte (fixed to 0xAA)

2

3

Number of Byte (without CheckSum)

Ok=0x01 / Parameter Error=0x02

4÷n+3 n+4

Data

CheckSum

Example: n=number of byte declared in the Compositor for the selected frame

We want to read the first PDO configured in the “SW67291 Compositor”. This PDO contains six bytes. So the string of hexadecimal numbers is:

REQ:[55][03][01][01][01][5B]

RES:[AA][07][01][11][22][33][44][55][66][17]

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 21 of 25

Industrial Electronic Devices

S

DO

The Bytes that compose the request are ten:

Byte Number Description

1 Start Byte (fixed to 0x55)

2 Number of Byte (without CheckSum)

7

8

9

10

3

4

5

6

Read Identifier (Read=0x01)

Type of Data (SDO=0x02)

Address of CANopen device connect to the HD67291

Index SDO Hi

Index SDO Lo

SubIndex SDO

Number of byte of frame to read

CheckSum

The Byte that compose the respons is:

Byte Number Description

1 Start Byte (fixed to 0xAA)

2 Number of Byte (without CheckSum)

3

Ok=0x01 / Parameter Error=0x02 / Error in sending=0x03

4÷n+3 n+4

Data

CheckSum

Example: n=number of byte for the selected frame

We want to read:

Address of CANopen device: 0x14; Type of Data: SDO; Index: 0x2000; SubIndex: 0x01; Number of byte: 4.

So receive the value 0x1A2B3C4D.

The string of hexadecimal numbers is:

REQ:[55][07][01][02][14][20][00][01][04][98]

RES:[AA][05][01][1A][2B][3C][4D][7E]

CheckSum

To calcolate the CheckSum is enough to sum all bytes from the start byte and take the less significative byte like result.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

Industrial Electronic Devices

MECHANICAL DIMENSIONS:

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 22 of 25

Figure 8: Mechanical dimensions scheme for HD67291-A1

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

Industrial Electronic Devices

ORDER CODE:

The ordering part number is formed by a valid combination of the following:

User Manual CANopen / RS232 / RS485 - Converter

Document code: MN67291_ENG Revision 1.001 Page 23 of 25

HD67291 – A 1

Connectors Type

1: Removable 5mm Screw Terminal

Enclosure Type

A: 1M, 35mm DIN Rail mounting

Device Family

HD67291: CANopen / RS232 / RS485 - Converter

ACCESSORIES:

Order Code: AC34001 - Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V AC

Order Code: AC34002

-

Rail DIN - Power Supply 110V AC 50/60Hz – 12 V AC

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

Document code: MN67291_ENG Revision 1.001 Page 24 of 25

DISCLAIMER

All technical content within this document can be modified without notice. The content of the document content is a recurring audit.

For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS

WEEE

INFORMATION

Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate collection systems).

This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed correctly, you will help prevent potential negative environmental factors and human health, which could otherwise be caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased the product.

R

ESTRICTION OF

H

AZARDOUS

S

UBSTANCES DIRECTIVE

The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE

MARKING

The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

User Manual CANopen / RS232 / RS485 - Converter

Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

Document code: MN67291_ENG Revision 1.001 Page 25 of 25

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.

Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:

1) Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to provide detailed information about the problem.

2) Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be accepted).

If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no longer under warranty, you will receive a repair estimate.

PRODUCTS AND RELATED DOCUMENTS:

Part Description URL

HD67503-A1 CANopen / Ethernet - Converter

HD67118 RS232 / RS485 - Converter

HD67119

HD67507-A1

USB / RS485 - Converter

Modbus TCP Slave / Modbus Master -

Converter

HD67510-B1

Modbus Slave / Modbus TCP Master -

Converter www.adfweb.com?product=HD67503 www.adfweb.com?product=HD67118 www.adfweb.com?product=HD67119 www.adfweb.com?product=HD67507 www.adfweb.com?product=HD67510

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com

Phone +39.0438.30.91.31

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement