1797-IN003


Add to my manuals
52 Pages

advertisement

1797-IN003 | Manualzz

Installation Instructions

FLEX Ex 8 Output and HART Analog Modules

Catalog Numbers 1797-OE8, 1797-OE8H

Topic

Important User Information

Environment and Enclosure

Prevent Electrostatic Discharge

Removal and Insertion Under Power

European Communities (EC) Directive Compliance

Installation in Zone 1

Installation in Zone 22

Install the Module

Wire the Module to a 1797-TB3 or 1797-TB3S Terminal Base Unit

Ground the Module

Outputs

1797-OE8 Input Map (Read Words)

1797-OE8H Input Map (Read Words)

1797-OE8 Output Map (Write Words)

1797-OE8H Output Map (Write Words)

1797-OE8H Configuration Map

Data Format - Write Words 2 and 3

Cyclic HART Input DataCyclic HART Input Data

Page

3

15

16

16

17

10

12

13

15

18

19

7

8

6

7

4

5

5

2 FLEX Ex 8 Output and HART Analog Modules

Topic

HART Input Data

HART Input Data Descriptions

HART Read Back Threshold

1797-OE8 Configuration Map

1797-OE8H Extended Configuration Data Table

1797-OE8H Secondary Master Enable (SME)/ Primary Master Inhibit (PMI)

Field Descriptions

1797-OE8 FLEX Ex Output Module Operation

Cooperative Operation of the Adapter and the 1797-OE8H Output Module

Specifications

27

32

33

34

24

25

26

26

Page

19

23

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 3

Important User Information

S olid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls

(Publication SGI-1.1

available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com

) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell

Automation, Inc., is prohibited.

Throughout this manual we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

IMPORTANT

ATTENTION

Identifies information that is critical for successful application and understanding of the product.

Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you: identify a hazard, avoid a hazard, and recognize the consequence

SHOCK HAZARD

Labels may be located on or inside the equipment to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be located on or inside the equipment to alert people that surfaces may be dangerous temperatures.

Publication

1797-5.3 - September 2011

4 FLEX Ex 8 Output and HART Analog Modules

Environment and Enclosure

ATTENTION

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

In addition to this publication, see:

• Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1

.

• NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 5

Prevent Electrostatic Discharge

ATTENTION

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

• Touch a grounded object to discharge potential static.

• Wear an approved grounding wriststrap.

• Do not touch connectors or pins on component boards.

• Do not touch circuit components inside the equipment.

• Use a static-safe workstation, if available.

• Store the equipment in appropriate static-safe packaging when not in use.

• Post a sign near these modules:

Attention! Avoid electrostatic charging.

ATENÇÃO! PREVENIR CONTRA O ACÚMULO DE CARGA

ELETROSTÁTICA

For your convenience, a sign that can be cut out and posted is included in this publication.

Removal and Insertion Under Power

WARNING

These modules are designed so you can remove and insert them under

power. However, take special care when removing or inserting modules in an active process. I/O attached to any module being removed or inserted can change states due to its input/output signal changing conditions.

If you insert or remove the terminal base while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

Publication

1797-5.3 - September 2011

6 FLEX Ex 8 Output and HART Analog Modules

European Communities (EC) Directive Compliance

If these products have the CE mark they are approved for installation within the European Union and EEA regions. They have been designed and tested to meet the following directives.

EMC Directive

These products are tested to meet the Council Directive 2004/108/EC by applying the following standards:

• EN 61000-6-4:2007, Electromagnetic Compatibility (EMC) - Part 6-4:

Generic Standard for Industrial Environments (Class A)

• EN 61000-6-2:2005, Electromagnetic Compatibility (EMC) - Part 6-2:

Generic Standards - Immunity for Industrial Environments

• EN61326-1:2006 (Industrial), Electrical Equipment For

Measurement, Control, and Laboratory Use - Industrial EMC

Requirements

ATEX Directive

These products are tested in conjunction with associated I/O modules to meet the Council Directive 94/9/EC (ATEX) Equipment and Protective

Systems Intended for Use in Potentially Explosive Atmospheres by applying the following standards:

• EN60079-11:2007, Explosive atmospheres - Part 11 : equipment protection by intrinsic safety "i"

• EN60079-0:2006, Electrical apparatus for explosive gas atmospheres -

Part 0 : general requirements

• EN 60079-26 : 2004, Electrical apparatus for explosive gas atmospheres - Part 26 : construction, test and marking of Group II

Category 1 G electrical apparatus

• EN61241-0 : 2006, Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements

• EN61241-11:2006, Electrical apparatus for use in the presence of combustible dust – Part 11: Protection by intrinsic safety 'iD'

Publication

1797-5.3 - September 2011

7 FLEX Ex 8 Output and HART Analog Modules

Installation in Zone 1

These modules must not be exposed to the environment. Provide a suitable metal enclosure. This module has a protection factor of IP20.

WARNING

These modules cannot be used in an intrinsically safe environment after they have been exposed to nonintrinsically safe signals.

Installation in Zone 22

When the module is installed in Zone 22, the following cabinets must be used:

IVK-ISRPI-V16LC; IVK-ISRPI-V8HYW; or IVK-ISRPI-V8LC. These cabinets can be purchased from:

Pepperl+Fuchs GmbH

Konigsberger Allee 85-87, D-68307

Mannheim, Germany

Attn: PA Sales Dept.

Kirsten Becker

Telephone +49 776 1298 www.pepperl-fuchs.com

The IS-RPI cabinets (type IVK2-ISRPI-V8LC, IVK2-ISRPI-V8HYW, or

IVK2-ISPRI-V16LC) ensures the basic protection for the intrinsically safe apparatus of the FLEX Ex system for use in Zone 22. It corresponds with category 3D according to RL 94/9 EG and with the type label marked with the following information:

Pepperl+Fuchs GmbH

68307 Mannheim

IVK2-ISRPI-V8LC (or IVK2-ISRPI-V8HYW or

IVK2-ISRPI-V16LC)

II 3 D Ex tD A22 IP54 T70 °C

CE

Serial (manufacturing) number

Model year

Publication

1797-5.3 - September 2011

8 FLEX Ex 8 Output and HART Analog Modules

Install the Module

Read this for information about how to install the module which must be used with a 1797-TB3 or 1797-TB3S intrinsically safe terminal base unit.

7

3

1

8

2

6

4

5

Label here or under here

41439

ATTENTION

This equipmment is considered Group 1, Class A industrial equipement according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessiblity to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional infromation regarding specific enclosure type ratings that are required to comply with certain productsafety certifications.

ATTENTION

During mounting of all devices, be sure that all debris (such as metal chips or wire strands) is kept from falling into the module. Debris that falls into the module could cause damage on power up.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 9

ATTENTION

Do not remove or replace a Terminal Base unit while power is applied.

Interruption of the backplane can result in unintentional operation or machine motion.

To install the module on a 1797 terminal base, see the figure and complete the following.

1.

Rotate the keyswitch (1) on the terminal base (2) clockwise to position

4 as required for this type of module.

IMPORTANT

Do not change the position of the keyswitch after wiring the terminal base unit.

2.

Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring terminal base or adapter.

IMPORTANT

You cannot install the module unless the connector is fully extended.

3.

Make sure the pins on the bottom of the module are straight so they align properly with the connector in the terminal base.

4.

Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base.

5.

Press firmly and evenly to seat the module in the terminal base unit, noting that the module is seated when the latching mechanism (7) is locked into the module.

6.

Remove cap plug (8) and attach another intrinsically safe terminal base unit to the right of this terminal base unit if required.

IMPORTANT

Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically safe backplane.

Publication

1797-5.3 - September 2011

10 FLEX Ex 8 Output and HART Analog Modules

41307

Wire the Module to a 1797-TB3 or 1797-TB3S Terminal Base Unit

WARNING

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

Module Wiring

Row A

Row B

Row C

No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20,

23, 24, 27, 28, 31, 32, 36, 37, 38, 39, 46, 47, 48, 49.

41440B

1.

Connect the individual output wiring to (+) terminals (0, 4, 8, 12) on the 0…15 row (A) and on the 16…33 row (B) (terminals 17, 21, 25,

29) as indicated in the table,

Wire Connections

.

1.

Connect the associated output to the corresponding (-) terminal (1, 5,

9, 13) on the 0…15 row (A), and on the 16…33 row (B) (terminals 18,

22, 26, 30) for each output as indicated in the table, Wire Connections .

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 11

2.

Connect +V DC power to terminal 34 on the 34…51 row (C).

3.

Connect -V to terminal 35 on the 34…51 row (C).

WARNING

Make certain that you power these modules with an intrinsically safe power supply. Do not exceed the values listed in the specifications for these modules.

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

4.

If continuing power to the next terminal base unit, connect a jumper from terminal 50 (+V) on this base unit to terminal 34 on the next base unit.

5.

If continuing common to the next terminal base unit, connect a jumper from terminal 51 (-V) on this base unit to terminal 35 on the next base unit.

ATTENTION

To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies.

Wire Connections

Output

Output 0

Output 1

Output 2

Output 3

+V

-V

Output +

A-0

A-4

A-8

Output -

A-1

A-5

A-9

A-12 A-13

Terminals 34 and 50

Terminals 35 and 51

Output

Output 4

Output 5

Output 6

Output 7

Output +

B-17

B-21

B-25

B-29

Output -

B-18

B-22

B-26

B-30

ATTENTION

Do not use the unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module, or unintended operation of your system, or both.

Publication

1797-5.3 - September 2011

12 FLEX Ex 8 Output and HART Analog Modules

Ground the Module

All I/O wiring must use shielded wire. Shields must be terminated external to the module, such as bus bars and shield-terminating feed-throughs.

44862

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 13

Outputs

Each output channel can operate an analog field device. Do not apply any

nonintrinsically safe signals to these modules.

When using an intrinsically safe electrical apparatus according to EN50020, the European Community directives and regulations must be followed.

The channels in these modules are electrically connected to each other.

1797-OE8

160

Ω

Flexbus

Bus uC

15.5V

45

Ω

-

+V

-V

+

Power

Supply

4…20 mA

Valve

I

F

4…20 mA

Actuator

41441

1797-OE8H/B

250

Ω

Flexbus

Bus uC

21.6V

HART

Modem

45

Ω

-

+V

-V

+

Power

Supply

4…20 mA

Valve

I

F

4…20 mA

Actuator

43849

Publication

1797-5.3 - September 2011

14 FLEX Ex 8 Output and HART Analog Modules

Output Voltage versus Current Capability

Output Voltage versus Current Capability for the 1797-OE8 Module

V DC

Voltage

16

14

12

10

8

6

4

2

0

0 5

10 15

20 25

mA

43002

Output Voltage versus Current Capability for the 1797-OE8H Module

Voltage

20.5

15

V DC

0

0 5 10

mA

15 20 25

43850

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 15

1797-OE8 Input Map (Read Words)

Bit

Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 FA FA FA FA FA FA FA FA Reserved Diagnostic Status

Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0

1 Res Module Command Response

Where: Ch = channel

FA = fault

Res = Reserved

Module Response Data

1797-OE8H Input Map (Read Words)

Bit

Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 FA

Ch7

FA

Ch6

FA

Ch5

FA

Ch4

FA

Ch3

FA

Ch2

FA

Ch1

FA

Ch0

HR Reserved Diagnostic Status

1

2

Reserved

HCF

Ch7

HCF

Ch6

HCF

Ch5

HCF

Ch4

HCF

Ch3

HCF

Ch2

3 HP

Ch7

HP

Ch6

HP

Ch5

HP

Ch4

HP

Ch3

HP

Ch2

Where: Ch = channel

FA = fault

HR = HART rebuilding

HCF = HART current fault

HF = HART communication fault

HP = HART present

HC = HART communication

HP

Ch1

HCF

Ch1

HCF

Ch0

HP

Ch0

HF

Ch7

HC

Ch7

HF

Ch6

HF

Ch5

HC

Ch6

HC

Ch5

HF

Ch4

HC

Ch4

HF

Ch3

HF

Ch2

HC

Ch3

HC

Ch2

HF

Ch1

HC

Ch1

HF

Ch0

HC

Ch0

Publication

1797-5.3 - September 2011

16 FLEX Ex 8 Output and HART Analog Modules

1797-OE8 Output Map (Write Words)

3

4

1

2

Bit

Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 OE FR Reserved DD

Ch7

DD

Ch6

DD

Ch5

DD

Ch4

DD

Ch3

DD

Ch2

DD

Ch1

DD

Ch0

Channel 0 Output Data

Channel 1 Output Data

Channel 2 Output Data

Channel 3 Output Data

5

6

Channel 4 Output Data

Channel 5 Output Data

7 Channel 6 Output Data

8 Channel 7 Output Data

Where: Res = reserved, Ch = channel

DD = digital data, FR = fault reset

OE = output enable

1797-OE8H Output Map (Write Words)

3

4

1

2

Bit

Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 Res FR Reserved DD

Ch7

DD

Ch6

DD

Ch5

DD

Ch4

DD

Ch3

DD

Ch2

DD

Ch1

DD

Ch0

Channel 0 Output Data

Channel 1 Output Data

Channel 2 Output Data

Channel 3 Output Data

5

6

Channel 4 Output Data

Channel 5 Output Data

7 Channel 6 Output Data

8 Channel 7 Output Data

Where: Res = reserved, Ch = channel

DD = digital data, FR = fault reset

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 17

1797-OE8H Configuration Map

13

14

15

16

17

9

10

11

12

Bit

2

3

Word 15 14 13 12 11 10 9 8 7

0 LFM VR FE FE FE FE Byte HS

1 HD

Ch7

HD

Ch6

Ch7

HD

Ch5

Ch6

HD

Ch4

Ch5

HD

Ch3

Ch4

HD

Ch2

Order

Group B

HD HD

Ch1 Ch0

LEDs

HHE

Ch7

6 5 4 3 2 1 0

HSI FE

Ch3

FE

Ch2

FE

Ch1

FE

Ch0

Byte

Order

Group A

HHE

Ch6

HHE HHE

Ch5 Ch4

HHE HHE

Ch3 Ch2

HHE

Ch1

HHE

Ch0

Data Format Ch3 Data Format Ch2 Data Format Ch1 Data Format Ch0

4

5

6

7

8

Data Format Ch7 Data Format Ch6 Data Format Ch5

HART Read Back FLE AFM HART Read Back

Threshold Ch1 Ch1 Ch1 Threshold Ch0

HART Read Back

Threshold Ch3

FLE

Ch3

AFM

Ch3

HART Read Back

Threshold Ch2

HART Read Back

Threshold Ch5

HART Read Back

Threshold Ch7

DF

Ch7

DF

Ch6

DF

Ch5

DF

Ch4

DF

Ch3

FLE

Ch5

AFM

Ch5

FLE

Ch7

AFM

Ch7

DF

Ch2

DF

Ch1

DF

Ch0

HART Read Back

Threshold Ch4

HART Read Back

Threshold Ch6

DM

Ch7

DM

Ch6

DM

Ch5

DM

Ch4

Data Format Ch4

FLE AFM

Ch0 Ch0

FLE

Ch2

AFM

Ch2

FLE

Ch4

FLE

Ch6

DM

Ch3

DM

Ch2

AFM

Ch04

AFM

Ch06

DM

Ch1

DM

Ch0

Fault Value Ch0

Fault Value Ch1

Fault Value Ch2

Fault Value Ch3

Where

Fault Value Ch4

Fault Value Ch5

Fault Value Ch6

Fault Value Ch7

HR

Ch7

HR

Ch6

HR

Ch5

HR

Ch4

HR

Ch3

HR

Ch2

HR

Ch1

LFM = local fault mode

FE = fault enable

HHE = HART handheld enable

AFM = analog fault mode

DM = digital mode

HC = HART CMD3 disable

HR

Ch0

HC

Ch7

HC

Ch6

HC

Ch5

HC

Ch4

HC

Ch3

HC

Ch2

VR = verify replacement

HD = HART disable

FLE = fault latch enabled

DF = digital fault mode

HR = HART rebuild

HC

Ch1

HC

Ch0

Publication

1797-5.3 - September 2011

18 FLEX Ex 8 Output and HART Analog Modules

Data Format - Write Words 2 and 3

5

6

7

8

9

10

11

0

1

2

3

Data

Format

4

12

13

14

15

Bits

15 14 13 12

11 10 9 8

Format Signal Range User Range Resolution

7 6 5 4

3 2 1 0

LO HI LO

0 0 0 0 0…20 mA as

Milliamps

0 0 0 1 0…20 mA as

%

0.00

22.00

0

(0.000 mA)

0.00

22.00

0

(0%)

HI

22000

(22.000 mA)

11000

(110.00%)

0.1% of

0...20 mA

0.2% of

0...20 mA

0 0 1 0 Not assigned

0 0 1 1 0…20 mA as unsigned integer

0.00

20.00

0

(0.000 mA)

0 1 0 0 4…20 mA as mA

2.00

22.00

2000

(2.000 mA)

65535

(22.000 mA)

0.03% of

0...20 mA

22000

(22.000 mA)

0.01% of

4...20 mA

0 1 0 1 Not assigned

0 1 1 0

0 1 1 1 4…20 mA as unsigned integer

4.00

20.00

0

(4 mA)

65535

(20 mA)

0.03% of

4...20 mA

1 0 0 0 Not assigned

1 0 0 1

1 0 1 0

1 0 1 1 0...20 mA as

D/A count

1 1 0 0 Not assigned

0.00

22.00

0

(0 mA)

1 1 0 1 4...20 mA as

%

1 1 1 0 4...20 mA as

%

3.00

21.00

-625

(-6.25%)

2.00

22.00

-1250

(-12.50%)

1 1 1 1 Not assigned

8000

(22 mA)

10625

(106.25%)

11250

(112.50%)

0.28% of

0...20 mA

0.16% of

4...20 mA

0.16% of

4...20 mA

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 19

Cyclic HART Input Data

The HART input data holds the primary variables for the "live" HART device, and other information gathered during the normal HART scan.

Additional "documentary" data is available through the pass through message interface in the device information tables. Pass through messages are defined in detail in the User Manual.

IMPORTANT

The HART Input Data for a channel may be zeroes if HART communications is disabled for that channel. For more information on disabling HART communications, refer to the Disable HART communications and HART CMD

3 Disable functions in the Configuration Map table.

HART Input Data

13

14

15

16

17

9

10

11

12

3

4

1

2

7

8

5

6

Word Bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 Reserved Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0

(HART Communications Status)

Reserved

Ch0 HART Field Device Status Ch0 HART Comm Status

Reserved Ch0 HART Loop Status

Ch0 HART Primary Value

(IEEE 754-1985 Single-Precision 32 bit floating point)

Ch0 HART Secondary Value

Ch0 HART Tertiary Value

(IEEE 754-1985 Single-Precision 32 bit floating point)

(IEEE 754-1985 Single-Precision 32 bit floating point)

Ch0 HART Fourth (Quaternary) Value

(IEEE 754-1985 Single-Precision 32 bit floating point)

Ch0 Secondary Value Units Code

Ch0 Fourth Value Units Code

Ch1 HART Field Device Status

Reserved

Ch1 HART Primary Value

Ch0 Primary Value Units Code

Ch0 Tertiary Value Units Code

Ch1 HART Communication Status

Ch1 HART Loop Status

Publication

1797-5.3 - September 2011

20 FLEX Ex 8 Output and HART Analog Modules

HART Input Data

44

45

46

47

40

41

42

43

36

37

38

39

32

33

34

35

28

29

30

31

24

25

26

27

20

21

22

23

Word Bit

18

19

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Ch1 HART Secondary Value

Ch1 HART Teritiary Value

Ch1 HART Fourth Value

Ch1 HART Secondary Value Units Code Ch1 HART Primary Value Units Code

Ch1 HART Fourth Value Ch1 HART Tertiary Value Units Code

Ch2 HART Field Device Status

Reserved

Ch2 HART Primary Value

Ch2 HART Communication Status

Ch2 HART Loop Status

Ch2 HART Secondary Value

Ch 2 HART Tertiary Value

Ch2 HART Fourth Value

Ch2 HART Secondary Value Units Code Ch2 HART Primary Value Units Code

Ch2 HART Fourth Value

Ch3 HART Field Device Status

Reserved

Ch3 HART Primary Value

Ch3 HART Secondary Value

Ch3 HART Tertiary Value

Ch3 HART Fourth Value

Ch2 HART Tertiary Value Units Code

Ch3 HART Communication Status

Ch0 HART Loop Status

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 21

HART Input Data

72

73

74

75

76

77

68

69

70

71

64

65

66

67

60

61

62

63

56

57

58

59

52

53

54

55

Word Bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

48

49

50

51

Ch3 HART Secondary Value Units Code

Ch3 HART Fourth Value

Ch4 HART Field Device Status

Reserved

Ch4 HART Primary Value

Ch3 HART Primary Value Units Code

Ch3 HART Tertiary Value Units Code

Ch4 HART Communication Status

Ch4 HART Loop Status

Ch4 HART Secondary Value

Ch4 HART Tertiary Value

Ch4 HART Fourth Value

Ch4 HART Secondary Value Units Code

Ch4 HART Fourth Value

Ch5 HART Field Device Status

Reserved

Ch5 HART Primary Value

Ch4 HART Primary Value Units Code

Ch4 HART Tertiary Value Units Code

Ch5 HART Communication Status

Ch5 HART Loop Status

Ch5 Secondary Value

Ch5 Tertiary Value

Ch5 Fourth Value

Ch5 HART Secondary Value Units Code Ch5 HART Primary Value Units Code

Ch5 HART Fourth Value Ch5 HART Tertiary Value Units Code

Ch6 HART Field Device Status

Reserved

Ch6 HART Primary Value

CH6 HART Communication Status

Ch6 HART Loop Status

Publication

1797-5.3 - September 2011

22 FLEX Ex 8 Output and HART Analog Modules

HART Input Data

92

93

94

95

96

97

88

89

90

91

84

85

86

87

80

81

82

83

Word Bit

78

79

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Ch6 Secondary Value

Ch6 Tertiary Value

Ch6 Fourth Value

Ch6 HART Secondary Value Units Code Ch6 HART Primary Value Units Code

Ch6 HART Fourth Value Ch6 HART Tertiary Value Units Code

Ch7 HART Field Device Status

Reserved

Ch7 HART Primary Value

CH7 HART Communication Status

Ch7 HART Loop Status

Ch7 Secondary Value

Ch7 Tertiary Value

Ch7 Fourth Value

Ch7 HART Secondary Value Units Code

Ch7 HART Fourth Value

Ch7 HART Primary Value Units Code

Ch7 HART Tertiary Value Units Code

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 23

HART Input Data Descriptions

Chn: HART CMD 3 Communication

Status

0: HART CMD3

Communication Disabled or

No Error

1: HART CMD3

Communication Error between Adapter &

Module

Chn: HART Comm Status (HART CMD3

Response first status byte):

Refer to User Manual

Chn: HART Field Device Status (HART

CMD3 Response second status byte):

Chn: HART Loop Status:

Bit 0: HART enable

Bit 1: Device Connected

Bit 2: Response Error

Bit 3: CMD 48 Update

Bit 4: HART Loop Tolerance Error

Bit 5: HART Update

Bit 6: HART message

Bit 7:

Refer to User Manual

0: Disabled

0: Not Connected

0: No HART message failure

0: CMD 48 not updated

0: No HART Current

Fault

0: HART Device information not updated

0: No new message

1: Enabled

1: Connected

1: Response ended in error

1: CMD 48 updated

1:HART Current Fault

1: HART Device information updated since last read

1: HART user message queue has completed a message

Reserved

Where PVA = The primary variable for this channel has been acquired.

SVA = The secondary variable for this channel has been acquired.

TVA = The tertiary variable for this channel has been acquired.

FVA = The fourth (quaternary) variable for this channel has been acquired.

Publication

1797-5.3 - September 2011

24 FLEX Ex 8 Output and HART Analog Modules

HART Read Back Threshold

HART Read Back

6%

7%

8%

9%

10%

30%

31%

Disabled

Not applicable

(1)

Not applicable

Not applicable

Not applicable

5%

Decimal

Value

0

1

8

9

6

7

4

5

2

3

10

30

31

0

0

0

0

0

0

0

0

1

1

0

Bits

7

15

0

0

1

1

0

0

0

0

0

0

1

1

1

0

0

6

14

0

0

1

1

1

1

0

0

1

1

0

0

0

5

13

0

0

1

1

0

0

1

1

1

1

1

0

0

4

12

0

1

0

1

0

1

0

1

0

1

0

0

1

3

11

(1)

1, 2, 3, and 4 are not applicable. Values between 1 and 4 will lead the IOM to automatically use an internal value of 5%.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 25

1797-OE8 Configuration Map

7

8

5

6

3

4

Config Bit

Word 15

0

1

2

14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

LFM Res FM

Ch2...3

LM

Ch4...7

DFS

Ch7

LM

Ch6

Ch0...3

DFS

FM

Ch5

Ch6...7

DFS

FM

Ch0...1

FM

Ch4...5

DFS

Ch4

AFState

Ch2...3

AFState

Ch0...1

AFState

Ch6...7

DFS DFS

Ch3 Ch2

AFState

Ch4...5

DFS DFS

Ch1 Ch0

Data Format

Ch2...3

Data Format

Ch6...7

AD

M

Ch7

AD

M

Ch6

AD

M

Ch5

AD

M

Ch4

Data Format

Ch0...1

Data Format

Ch4...5

AD

M

Ch3

AD

M

Ch2

AD

M

Ch1

AD

M

Ch0

Analog Fault State Value Channel 0

Analog Fault State Value Channel 1

Analog Fault State Value Channel 2

Analog Fault State Value Channel 3

Analog Fault State Value Channel 4

Analog Fault State Value Channel 5

9

10

Analog Fault State Value Channel 6

Analog Fault State Value Channel 7

Where: LFM = Local Fault Mode

FM = Fault Mode

AFState = Analog Fault State

DFS = Digital Fault State

Res = Reserved

Ch = Channel

LM = Latch Mode

ADM = Analog/Digital Mode

Publication

1797-5.3 - September 2011

26 FLEX Ex 8 Output and HART Analog Modules

The extended configuration data table is accessed (read/write) by using a

MSG or CIO instruction. See the table,

Field Descriptions on page 27 for

more information.

1797-OE8H Extended Configuration Data Table

Config Bit

Word 15 14 13 12 11 10 9 8 7 6 5

0

1

PM

Ch7

PM

Ch6

Reserved

PM

Ch5

PM

Ch4

PM

Ch3

PM

Ch2

PM

Ch1

PM

Ch0

HART Read Back Threshold

Ch4...7

Where: Ch = Channel

SME = Secondary Master Enable

HS Inht = HART Status Inhibit

4 3 2 1 0

SME SME SME

Ch7 Ch6 Ch5

SME SME SME SME SME

Ch4 Ch3 Ch2 Ch1 Ch0

HS HS 50/60 HART Read Back Threshold

LED Inht Hz Ch0...3

PM = Primary Master Inhibit

HS LED = HART Status LEDs

The SME and PMI bits control a few module internal functions individually for channels 0…7.

1797-OE8H Secondary Master Enable (SME)/ Primary Master Inhibit (PMI)

PMI

SME

Bits

(1) 1 (Default)

8, 9, 10, 11, 12, 13, 14, 15 0

0, 1, 2, 3, 4, 5, 6, 7

HART Smooth Filter

Rebuild

0

Pulsed

On

2

0

1

On

On

HART Read Back

Primary Master

Secondary Master

On

On

Off

On

On

On

3

Off

Off

Off

1

0

Off

Off

4

Off

Off

On

1

1

On

Off

(1)

Where:

Ch 0 - bits 0 and 8; Ch 1 - bits 1 and 9; Ch 2 - bits 2 and 10; Ch 3 - bits 3 and 11; Ch 4 - bits 4 and

12; Ch 5 - bits 5 and 13; Ch 6 - bits 6 and 14; Ch 7 - bits 7 and 15

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 27

Field Descriptions

Analog/Digital

Output Mode

Selects if the channel acts as a normal analog output or as a switched digital output.

Analog Output mode will follow the Analog Data Format selected.

Digital Output mode will output 0 mA = OFF, 22 mA = ON if the Fault mode is 0 = disable. Digital Output mode will output 2 mA = OFF,

22 mA = ON if the Fault mode is 1 = wire off fault detection enabled.

Range: 0 = normal analog output, 1 = switched digital output.

Analog Output Data Specifies the value of the analog output data to the module. Specific format is controlled by Module Data Format Control parameter. This data is used when the channel is in Analog Output mode.

Digital Output Data Specifies the value of the digital output data to the module. This data is used when the channel is in digital output mode.

Range: 0 = output, 0 mA = OFF, 1 = 22 mA = ON if the Fault mode is 0 = disable. 0 = output, 2 mA = OFF, 1 = 22 mA = ON if the Fault mode is 1

= wire-off fault detection enabled.

Global Reset This bit acts to reset all outputs to accept normal system output data.

It acts in conjunction with the Latch Retry parameter. If any channel faults occur, the Latch Retry parameter can be set to cause the fault to be latched and the output to go to its safe state value.

This is an edge-triggered signal. It must first be set (1). Reset will then occur on the set-to-reset transition.

Output Enable Signals module that communications has been interrupted to the network. Output modules should execute their fault routine or go to safe state.

On power-up, the module remains OFF, 0 mA out.

After normal power-up, this bit must be set (1) by the user program to begin normal module functioning. If the bit is reset to 0 by a communication fault, the module should use the information contained in the Module Safe State data until the value is set to 1, when normal function continues.

Analog Fault State Determines how module reacts to faults when channel is used in

Analog Normal mode.

Range: 0 = go to minimum value of data range, 1 = go to maximum value of data range, 2 = hold last state, 3 = 50% of data range

(1797-OE8) or use analog fault state value (1797-OE8H).

Publication

1797-5.3 - September 2011

28 FLEX Ex 8 Output and HART Analog Modules

Field Descriptions

Analog Fault State

Value

Specifies the fault state value of the analog output data to the module.

Specific format is controlled by Module Data Format Control parameter. This data is used when the channel is in Analog Output mode and the analog fault state is configured to use analog fault state value.

Digital Fault State Determines how module reacts to faults when channel is used in digital mode.

Range: 0 = reset, 1 = hold last state.

Fault Mode Selects whether the channel pair fault detection is enabled or disabled. There is a 100 Hz (10 ms) filter for wire-off/lead-break detection.

Range: 0 = disable, 1 = wire-off fault detection enabled.

Latch Retry Mode Latch Retry determines channel operation under wire-off fault conditions. These bits control the action of two channel groups - channels 0…3 and channels 4…7. When a channel fault occurs, the channel fault alarm will be set (if enabled) and the safe state mode will be enabled. If retry is selected, the channel will periodically try to reestablish proper output. If latch is selected, the fault will be latched until a Global Reset is issued.

Range: 0 = retry, 1 = latch.

Local Fault Mode This parameter determines how the Module Safe State will be used for bus communication and internal module faults. This parameter sets this characteristic for the module.

Range: 0 = fault states activated by bus communication faults, 1 = fault states activated by any failure (for example, bus communications).

Fault Alarm (8 or 1 Bit

Each)

Alarm signal for open wire channel fault, detected at < 2 mA. This alarm is disabled when a data format is selected which includes 0 mA.

Range: 0 = normal, 1 = wire-off fault detected.

HART Rebuild Flag

(1 of 1 Bit)

(1797-OE8H)

During the time the system is rebuilding the HART table, the HART rebuild flag is set.

Range: 0 = normal, 1 = HART rebuilding.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 29

Field Descriptions

HART Read Back

(1797-OE8H)

The HART Read Back bits show deviations between the analog measured current value on a loop (by the 1797-OE8H) and the digital

(real) current (sensed by the HART device on its own) received by the

1797-OE8H during HART communication in the background.

When this bit is set (1), it indicates that HART communications are failing on the associated channel.

Range: 0 = normal, 1 = HART communication failure.

Range: 0 = normal, 1 = HART communication is currently occurring.

HART

Communication

(1797-OE8H)

HART Transmitter

List (1797-OE8H)

Extended

Configuration

(1797-OE8H)

When this bit is set (1), it indicates that a HART field device was found during the rebuild sequence on the associated channel.

Range: 0 = transmitter was not found, 1 = HART transmitter was found.

Configuration additions are needed for HART communications. An extended configuration area is provided. This Extended Configuration table is configured by writing a CIO or MSG instruction with the following:

Class = 0x7D

Instance = Product location on flexbus

(Use 1 for the module located next to the adapter.)

Attribute = 0x65

Service = Set Attribute Single (0x10).

HART Status

Indicators

(1797-OE8H)

See on page 31.

When this bit is set (1), the indicators are used for HART diagnostic.

Indicator behavior changes to show communication on HART. Each status indicator represents a HART loop. Flashing yellow indicates that communication is currently being processed. Solid yellow means that this device is in the transmitter list.

Publication

1797-5.3 - September 2011

30 FLEX Ex 8 Output and HART Analog Modules

Field Descriptions

HART Status Inhibit

(1797-OE8H)

When this bit is set (1), the HART communication status is not shown in the realtime data table. The appropriate areas are cleared with zeroes.

Range: 0 = normal, 1 = inhibit HART.

Range: 0 = 50 Hz, 1 = 60 Hz.

50/60 Hz Filter

(1797-OE8H)

HART Read Back

Threshold

(1797-OE8H)

Delivers the percentage value (in steps of 1%) of the threshold for forcing the HART read back indication (input signal deviation

HART/Analog) with a 31% maximum deviation.

If there is no HART transmitter on the loop or the loop is not in the transmitter list, the function is switched off internally in the I/O module.

Range: 0 = disabled, 1…4 = not supported from I/O module (set to 5 internally), 5…31 = percentage threshold data (5…31%).

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 31

Cooperative Operation of the ControlNet Ex Adapter and the

1797-OE8 Output Module

The ControlNet Ex adapter (1797-ACNR15) combined with the 1797-OE8 output module provides a two-tier fault state mechanism. It is important to consider and understand the operation of this mechanism when designing your system.

Two sets of programmable fault states are available, one each in the adapter and 1797-OE8 module. This two-tier method is meant to give you a wider fault coverage compared with normal methods.

Adapter Operation with the 1797-OE8 Module

Network Communication Monitoring

The adapter is the primary monitor of network activity. If it detects loss of network communication, it can be configured to:

• continue writing the last valid received data to the module (hold last state).

• apply local module safe states.

(1)

• write a programmable fault state value to the module, depending upon the module type.

(2)

This mechanism primarily targets fault behavior for loss of network communication.

(1)

(2)

This selection could be shown as Reset Outputs but its action is Apply Local Module Safe States.

This option is only available in some adapters.

Publication

1797-5.3 - September 2011

32 FLEX Ex 8 Output and HART Analog Modules

Program Mode Behavior

The adapter also monitors the state of the controlling processor or scanner.

Two states can be detected: run mode and program mode (idle).

When program mode is detected, the adapter can be configured to:

• continue writing the last valid received data to the module (hold last state).

• apply local module safe states.

(1)

• write a programmable fault state value to the module, depending upon the module type.

(2)

1797-OE8 FLEX Ex Output Module Operation

Flexbus Communication Monitoring

The module monitors flexbus communication activity and the state of its

Output Enable bit. If it detects loss of flexbus communication activity or the

Output Enable bit transitioning to 0, it can be programmed to:

• continue writing the last valid received data to the outputs (hold last state).

• reset the outputs.

• write the local module fault state value to the output, depending upon the module type.

This mechanism primarily targets fault behavior for loss of backplane communication.

(1)

This selection could be shown as Reset Outputs but its action is Apply Local Module Safe States.

(2)

This option is only available in some adapters.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 33

Power-up State Behavior

The system and modules use the Output Enable bit at system power-up. The power-up state of the Output Enable bit is 0 and must be transitioned to 1 through application program control to initialize activity of a module’s outputs.

Before the Output Enable bit is transitioned to 1, module outputs remain off.

Once the initial power-up and application-program control transitions the

Output Enable bit to 1, and module output activity begins, subsequent transitions of the Output Enable bit by any source will cause the output module to apply the local module fault state.

Cooperative Operation of the Adapter and the 1797-OE8H Output

Module

The 1797-OE8H module has more intelligence than the 1797-OE8 module.

The ControlNet adapter, the EtherNet adapter, and the FlexLogix controller are aware of this. These adapters convey the Run/Program (Idle) Mode and

Communication Fault status directly to the 1797-OE8H module. The

1797-OE8H module monitors this information and determines its own fault state actions according to your configuration. This allows for a more simplified approach to your connections. With regard to the Program Mode

Behavior and Network Communication Fault, the 1797-OE8H module can be configured to provide the following:

• Set Analog Output to Minimum Value

• Set Analog Output to Maximum Value

• Hold Last Analog Value

• Go to User Programmable Analog Value

• Set Digital Output to Minimum Value

• Hold Last Digital Value

IMPORTANT

After the 1797-OE8H module is powered up and prior to it receiving its configuration information from the network, the

1797-OE8H will default its fault states to Set Analog Output to Minimum Value and Set Digital Output to Minimum Value.

Publication

1797-5.3 - September 2011

34 FLEX Ex 8 Output and HART Analog Modules

Repair

ATTENTION

This module is not field repairable. Any attempt to open the module will void the warranty and IS certification. If repair is necessary, return the module to the factory.

Status Indicators

Input Status

Power Status

45096

Interpret the Status Indicators

Status

Flashing red

Solid green

Description

Channel fault -

Channel 0 indicator will turn red while power-up check is running

Power applied to module

Specifications

Specifications - 1797-OE8

Number of Outputs

IS input type

8 single-ended, nonisolated

Ex ia IIB/IIC T4

AEx ia IIC T4

Class I, II, III Division 1 Group A-G T4

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 35

IS module type Ex ib IIB/IIC T4

AEx ib IIC T4

Class I, II, III Division 1 Groups A-D T4

Resolution

Transfer Characteristics

Accuracy at 20

Load Range

Current

Module Field-side Power

Consumption o

C (68

Temperature Drift o

F)

Voltage Available at 22 mA

Load

13 bit

0.1% of output signal range

0.010%/°C of output signal range

0…22 mA

>11V

0…500

Ω

@ 22 mA

Configurable Data Format

Step Response to 99% of FS 4 ms

Module from Adapter 200 ms/1600

μ s

Best/Worst Update Time

Indicators 8 red fault indicators

Output Ch0…Ch 7

(Intrinsically Safe)

(Terminals: 0…1; 4…5;

1 green power

I

U o o

< 21V

< 100 mA

P o

< 520 mW

8…9; 12…13; 17…18;

21…22; 25…26; 29…30)

Isolation Path

Output to Power Supply

Output to Flexbus

Output to Output

Power Supply to Flexbus

Power Supply

(+V, -V Intrinsically Safe)

(Terminals: 34/50 (+);

35/51 (-))

Isolation Type

Galvanic to DIN EN60079-11

Galvanic to DIN EN60079-11

None

Galvanic to DIN EN60079-11

I

U i i

< 9.5V dc

< 1 A

L i

= Negligible

C i

= Negligible

6.3 W

Power Dissipation

Thermal Dissipation

Module Location

Dimensions Metric

Imperial

5.4 W

18.4 BTU/hr

Cat. No. 1797-TB3 or 1797-TB3S Terminal Base Unit

2

(12 gauge) stranded max

1.2 mm (3/64 in.) insulation max

46 mm x 94 mm x 75 mm

(1.8 in. x 3.7 in. x 2.95 in.)

Publication

1797-5.3 - September 2011

36 FLEX Ex 8 Output and HART Analog Modules

Weight

Keyswitch Position

Environmental Conditions

Operational Temperature

200 g (approximately)

4

Storage Temperature

-20…+70 o

C (-4…+158 o

F)

-40…+85 o

C (-40…+185 o

F)

Relative Humidity

Shock Operating

5…95% noncondensing

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Vibration

Nonoperating Tested to 15 g peak acceleration, 11(+1) ms pulse width

Tested 2 g @ 10…500 Hz per IEC68-2-6

Agency Certification

CENELEC II (1) 2G Ex ib[ia] IIC T4

II (1) D [Ex iaD]

UL, C-UL Class I, Groups A, B, C and D; Class II, Groups E, F and G;

Class III Hazardous Locations

Class I, Zone 1, AEx ib[ia] IIC T4

FM Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4.

Associated Apparatus with intrinsically safe Connections

Class I, II, III, Div 1, Groups A--G

Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.

IECEx [Zone 0] Ex ib[ia] IIC T4

[Ex iaD]

INMETRO BR-Ex ia/ib IIB/IIC T4

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 37

Certificates

CENELEC DMT 00 ATEX E 042 X

UL, C-UL File No.: E197983

Class I Division 1 Hazardous

FM FM Certificate Number 3009806

FM

IECEx IECEx BVS 09.0023X

INMETRO 05/UL-BRAE-0017X

Publication

1797-5.3 - September 2011

38 FLEX Ex 8 Output and HART Analog Modules

Specifications - 1797-OE8H

Number of Outputs

IS Input type

IS Module type

8 single-ended, non-isolated

Ex ia IIB/IIC T4

AEx ia IIC T4

Class I, Division I Groups A-G T4 (FM only)

Ex ib IIB/IIC T4

AEx ib IIC T4

Class I, Division I Groups A-D T4 (FM only)

Resolution

Transfer Characteristics

Accuracy at 20

Load Range

Current

Module Field-side Power

Consumption o

C (68

Temperature Drift o

F)

Voltage Available at 22 mA

Load

13 bits

0.1% of output signal range

0.010%/°C of output signal range

0…22 mA

> 15V

0…680

Ω

@ 22 mA, 0…770

Ω

@ 20 mA

Configurable Data Format

Step Response to 99% of FS 4 ms

Module from Adapter 200 ms/1600

μ s

Best/Worst Update Time

Indicators 8 red fault indicators

1 green power

Output Ch0…Ch 7

(Intrinsically Safe)

(Terminals: 0…1; 4…5;

8 yellow HART comm indicators

I

U o o

< 21.6V

< 92 mA

P o

< 500 mW

8…9; 12…13; 17…18;

21…22; 25…26; 29…30)

Isolation Path

Output to Power Supply

Output to Flexbus

Output to Output

Power Supply to Flexbus

Power Supply

(+V, -V Intrinsically Safe)

(Terminals: 34 and 50 (+);

35 and 51 (-))

Isolation Type

Galvanic to DIN EN60079-11

Galvanic to DIN EN60079-11

None

Galvanic to DIN EN60079-11

I

U i i

< 9.5V dc

< 1 A

L i

= Negligible

C i

= 120 nF

6.1 W

Power Dissipation 5.4 W

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 39

Thermal Dissipation

Module Location

Conductors Wire Size

Dimensions Metric

Imperial

Weight

Keyswitch Position

Environmental Conditions

Operational Temperature

20.8 BTU/hr

Cat. No. 1797-TB3 or 1797-TB3S Terminal Base Unit

4 mm

2

(12 gauge) stranded max

1.2 mm (3/64 in.) insulation max

46 mm x 94 mm x 75 mm

(1.8 in. x 3.7 in. x 2.95 in.)

200 g (approximately)

4

-20…+70

°

C (-4…+158

°

F)

Storage Temperature

Relative Humidity

ShockOperating

Nonoperating

Vibration

-40…+85

°

C (-40…+185

°

F)

5…95% noncondensing

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Tested to 15 g peak acceleration, 11(+1) ms pulse width

Tested 2 g @ 10…500 Hz per IEC68-2-6

Agency Certification

CENELEC II (1) 2G Ex ib[ia] IIC T4

II (1) D [Ex iaD]

FM Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4.

Associated Apparatus with intrinsically safe

Connection Class I, II, III, Div 1, Groups A--G

Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.

IECEx II (1) 2G Ex ib[ia] IIC T4

II (1) D [Ex iaD]

Certificates

CENELEC DMT 00 ATEX E 042 X

FM FM Certificate Number 3009806

FM

IECEx IECEx BVS 09.0023X

Publication

1797-5.3 - September 2011

40 FLEX Ex 8 Output and HART Analog Modules

Entity Parameters

CE, CENELEC I/O Entity Parameters (1797-OE8)

Signal output (+ to -) for ch 0 to ch 7

(terminals: 0 and 1; 4 and 5; 8 and 9; 12 and 13; 17 and 18; 21 and 22; 25 and

26; 29 and 30)

Protection Group

EEx ia IIB

IIC

Allowed

Capacitance

1.27

μ

F

188 nF

Allowed

Inductance

8 mH

2 mH

I

U o o

= 21V

= 100 mA

P o

= 520 mW

If concentrated capacitance and/or inductance are available, use the following values.

EEx ia IIB

IIC

295 nF

70 nF

10 mH

2 mH

CE, CENELEC I/O Entity Parameters (1797-OE8H)

Signal output (+ to -) for ch 0 to ch 7

(terminals: 0 and 1; 4 and 5; 8 and 9; 12 and 13; 17 and 18; 21 and 22; 25 and

26; 29 and 30)

I

U o o

= 21.6V

= 92 mA

P o

= 500 mW

Protection Group Allowed

EEx ia IIB

Capacitance

1.18

μ

F

IIC 164 nF

Allowed

Capacitance

1.18

μ

F

164 nF

Internal

Capacitance

10 nF

10 nF

Internal

Inductance

0 mH

0 mH

UL, C-UL I/O Entity Parameters (1797-OE8 Only)

If this product has the UL/C-UL mark, it has been designed, evaluated, tested, and certified to meet the following standards:

• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III Division 1, Hazardous (Classified)

Locations

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 41

• UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical

Equipment for Use in Hazardous (Classified) Locations

• UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2

Hazardous (Classified) Locations

• UL 61010, UL Standard for Safety Electrical Equipment For

Measurement, Control, and Laboratory Use; Part 1: General

Requirements

• CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive

Equipment for Use in Hazardous Locations

• CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in

Class I Hazardous Locations

• CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres,

Part 0: General Requirements

• CSA-E79-11-95, Electrical Apparatus for Explosive Gas

Atmospheres, Part 11: Intrinsic Safety “i”

• CSA C22.2 No. 14-95, Industrial Control Equipment

Wiring Methods

• Wiring method 1 - Each channel is wired separately.

• Wiring method 2 - Multiple channels in one cable, providing each channel is separated in accordance with the National Electric Code

(NEC) or Canadian Electric Code (CEC).

Publication

1797-5.3 - September 2011

42 FLEX Ex 8 Output and HART Analog Modules

Table 1

Wiring

Method

Channel Terminals V oc

(V)

I sc

(mA)

V t

(V)

0(+), 1(-) 21.0

100.0

1 and 2 Any one channel

(for example, ch0)

I t

(mA)

-

Groups C a

(

μ

F)

L a

(mH)

A, B, IIC 0.08

2.0

C, E, IIB 0.24

8.0

D, F, G,

IIA

0.64

16.0

FLEX Ex Analog

Output I/O

Indicators

Female Bus

Field Wiring

IMPORTANT

Key Position for

Terminal Base

Insertion

Male Bus

Connection

Terminal Base

Key

Terminal Base

42013

A terminal base may or may not have an I/O module installed.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 43

Hazardous (Classified) Location

Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA

Class I, Div. 1 & 2 Groups A, B, C, D

Class II, Div. 1 & 2 Groups E, F, G

Class III, Div. 1 & 2 ch0

Any Simple Apparatus or I.S. device with Entity Concept parameters (V max

, I max

, C i

, L appropriate for connection to i

) associated apparatus with

Entity Concept parameters listed in Table 1.

ch1

0 (+)

1 (-)

4 (+)

5 (-) ch2

8 (+)

9 (-) ch3 ch4 ch5

21 (+)

22 (-) ch6

17 (+)

18 (-)

25 (+)

26 (-) ch7

12 (+)

13 (-)

29 (+)

30 (-)

Hazardous (Classified) Location

Class I, Zones 1 & 2 Groups IIC, IIB, IIA

Class I, Div. 1 & 2 Groups A, B, C, D

Female Bus

Connector

C i

L i

V max

I max

=5.8V

=400mA

=1350nF

=negligible 34

I

V

C i

L i max max

=9.5V

=1A

=negligible

=negligible

35

51

50

Male Bus

Connector

1797-OE8

16

33

40

41

42

43

44

45

To any intrinsically safe device or associated apparatus with Entity

Concept parameters of

V oc

< 5.8V; I sc

< 400 mA.

T o any intrinsically safe device or associated apparatus with Entity

Concept parameters of

V oc

< 9.5V; I sc

< 1 A.

To any IS device with Entity

Concept parameters of

(V max

, I max

, C i

, L i

) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 2.

Shield Connection

Only

42016

Publication

1797-5.3 - September 2011

44 FLEX Ex 8 Output and HART Analog Modules

Table 2

Terminals

Male Bus

Connector

V t

(V)

5.8

I t

(mA)

400

Groups

A-G

C a

(

μ

F)

3.0

L a

(

μ

H)

3.0

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of V oc

and I sc

or V t

and I t

of the associated apparatus are less than or equal to V max

and I max

of the intrinsically safe apparatus and the approved values of C a

and L a

of the associated apparatus are greater than C i

+ C cable

and L i

+ L cable

respectively for the intrinsically safe apparatus.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1 A, 20

μ

J, or 25 mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA

C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA

RP12.6.

This module, 1797-OE8, must be used with terminal base 1797-TB3 or

1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36 to 39, and 46 to 49 shall not be connected.

WARNING:

Substitution of components may impair intrinsic safety.

AVERTISSEMENT:

La substitution de composant peut compromettre la securite intrinseque.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 45

FM I/O Entity Parameters

If this product has the FM mark, it has been designed, evaluated, tested, and certified to meet the following standards:

• FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous

(Classified) Locations General Requirements

• FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated

Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)

Locations

• FM C1. No.3615:1989, Explosionproof Electrical Equipment General

Requirements

• FM C1. No.3810:1989, 1995, Electrical and Electronic Test,

Measuring and Process Control Equipment

• ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment

Wiring Methods

• Wiring method 1 - Each channel is wired separately.

• Wiring method 2 - Multiple channels in one cable, providing each channel is separated in accordance with the National Electric Code

(NEC).

Publication

1797-5.3 - September 2011

46 FLEX Ex 8 Output and HART Analog Modules

FM I/O Entity Parameters for 1797-OE8

Wiring

Method

Channel Terminals V oc

(V)

I sc

(mA)

1 and 2 Any one channel

(for example, ch0)

0(+), 1(sig) 21.0

100.0

-

V t

(V)

I t

(mA)

-

Groups C a

(

μ

F)

A, B

L a

(mH)

0.20

3.5

C, E 0.60

10.5

D, F, G 1.60

28.0

FM I/O Entity Parameters for 1797-OE8H

Wiring

Method

Channel Terminals V oc

(V)

I sc

(mA)

1 and 2 Any one channel

(for example, ch0)

0(+), 1(sig) 21.6

92

V t

(V)

-

I t

(mA)

-

Groups C a

(

μ

F)

A, B

L a

(mH)

0.164

3.5

C, E 0.49

10.5

D, F, G 1.31

28.0

FLEX Ex Analog

Output I/O

Indicators

Female Bus

Field Wiring

Publication

1797-5.3 - September 2011

Key Position for

Terminal Base

Insertion

Male Bus

Connection

Terminal Base

Key

Terminal Base

42055

FLEX Ex 8 Output and HART Analog Modules 47

IMPORTANT

Hazardous (Classified) Location

Class I, Zones 0 Groups IIC, IIB, IIA

Class I, Div. 1 Groups A, B, C, D

Class II, Div. 1 Groups E, F, G

Class III, Div. 1

Any Simple Apparatus or FM approved device with Entity

Concept parameters (V max

I max

, C i

, L i

) appropriate for connection to associated

, apparatus with Entity Concept parameters listed in Table 1.

A terminal base may or may not have an I/O module installed.

Hazardous (Classified) Location

Class I, Zones 1 Groups IIC

Class I, Div. 1 Groups A, B, C, D ch0 ch1 ch2 ch3 ch4 ch5 ch6 ch7

0 (+)

1 (sig)

2 (-)

4 (+)

5 (sig)

6 (-)

8 (+)

9 (sig)

10 (-)

12 (+)

13 (sig)

14 (-)

Female Bus

Connector

V max

I max

C i

=5.8V

=400mA

=1350nF

L i

=negligible

V max

I max

C i

L i

=9.5V

=1A

=negligible

=negligible

34

35

51

50

17 (+)

18 (sig)

19 (-)

21 (+)

22 (sig)

23 (-)

Male Bus

Connector

25 (+)

26 (sig)

27 (-)

1797-OE8 or

29 (+)

30 (sig)

31 (-)

-OE8H

16

33

40

41

42

43

44

45

For connection to other modules, refer to the

General FM Certification

Information on page 29-1 of publication 1797-6.5.6.

From FM approved devices,

1797-PS1N, -PS2N, or

-PS2N2.

For connection to other modules, refer to the General

FM Certification Information on page 29-1 of publication

1797-6.5.6.

Shield Connection Only

42056

Table 2

Terminals

Male Bus

Connector

V t

(V)

5.8

I t

(mA)

400

Groups

A to G

C a

(

μ

F)

3.0

L a

(

μ

H)

3.0

Publication

1797-5.3 - September 2011

48 FLEX Ex 8 Output and HART Analog Modules

Table 3: Flexbus Entity Values for this Module

Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.

Terminals

Female Bus

Connector

V max

(V) I max

(mA)

5.8

400

Groups

A to D

C i

(

μ

F)

1.35

L i

(

μ

H)

0

The entity concept allows interconnection of intrinsically safe apparatus with associated apparatus not specifically examined in combination as a system when the approved values of V oc

and I sc

or V t

and I t

of the associated apparatus are less than or equal to V max

and I max

of the intrinsically safe apparatus and the approved values of C a

and L a

of the associated apparatus are greater than C i

+ C cable

and L i

+ L cable

respectively for the intrinsically safe apparatus. The internal capacitances Ci of the terminal base must be taken into account to verify the intrinsic safety.

Simple apparatus is defined as a device which neither generates nor stores more than 1.2V, 0.1 A, 20

μ

J, or 25 mW.

Wiring methods must be in accordance with the National Electric Code,

ANSI/NFPA 70, Article 504 and 505. For additional information refer to

ANSI/ISA RP12.6.

This module, 1797-OE8 or 1797-OE8H, must be used with terminal base

1797-TB3 or 1797-TB3S.

Terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36 to 39, and 46 to 49 shall not be connected.

WARNING:

Substitution of components may impair intrinsic safety.

IMPORTANT

For detailed certification information, refer to the FLEX

Ex System Certification Reference Manual, publication

1797-6.5.6.

Publication

1797-5.3 - September 2011

FLEX Ex 8 Output and HART Analog Modules 49

Attention: Avoid electrostatic charging.

ATENÇÃO! PREVENIR CONTRA O

ACÚMULO DE CARGA ELETROSTÁTICA

.

Publication

1797-5.3 - September 2011

50 FLEX Ex 8 Output and HART Analog Modules

Notes:

Publication

1797-5.3 - September 2011

Notes:

FLEX Ex 8 Output and HART Analog Modules 51

Publication

1797-5.3 - September 2011

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com

, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com

.

Installation Assistance

If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer

Support number for initial help in getting your product up and running.

United States 1.440.646.3434

Monday – Friday, 8 a.m. – 5 p.m. EST

Outside United States Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number

(see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Allen-Bradley, Rockwell Automation, TechConnect, and Flex Ex are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication

1797-5.3 - September 2011 PN-121052

Supersedes Publication 1797-IN003H-EN-P - December 2005 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement