Autonics SPR1 Series LED Display Slim Power Controller offers precise control of load output with its phase control, cycle control, and ON/OFF control capabilities. It features normal control, constant current, constant voltage, and constant power feedback control modes for versatile use. The device boasts an accuracy of within ±10% F.S. of rated load voltage in normal control mode and within ±3% F.S. of rated load current, voltage, or power in feedback control modes.
advertisement
DRW171280AB
LED Display Slim Power Controller
SPR1 Series
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
※ Please observe all safety considerations for safe and proper product operation to avoid hazards.
※ symbol represents caution due to special circumstances in which hazards may occur.
Warning
Failure to follow these instructions may result in serious injury or death.
Caution
Failure to follow these instructions may result in personal injury or product damage.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on the device panel, and ground to the bracket separately.
Failure to follow this instruction may result in electric shock or fire.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or fire.
4. Check 'Connections' before wiring.
Failure to follow this instruction may result in fire.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or fire.
Caution
1. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage.
2. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or fire.
3. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in fire or explosion.
4. Keep metal chip, dust, and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
5. Since leakage current still flows right after turning off the power or in the output OFF status, do not touch the load terminal.
Failure to follow this instruction may result in electric shock.
Ordering Information
SPR 1 2 70 T F F
Fuse
N
F
N
F
Non-fuse ※1
Fuse
Feedback control
Option output
Rated load current
N
T
25
35
50
70
100
150
Normal control
Normal/constant current/constant voltage/constant power control
Alarm output
Alarm+RS485 comm. output
25A
35A
50A
70A
100A
150A
Rated load voltage
3
4
1
2
110VAC
220VAC
380VAC
440VAC
Control phase
1 1-phase
Item
SPR Solid State Power Regulator
※ 1: Product is not equipped with a rapid fuse inside. Install the suitable fuse for rated load current of the model separately.
(The performance of the product is guaranteed only when using the fuse provided by us.)
※ The above specifications are subject to change and some models may be discontinued
※ without notice.
Be sure to follow cautions written in the instruction manual, user manual, and the technical descriptions (catalog, homepage).
Specifications
Model
Control phase
SPR1-1
1-phase
SPR1-2
Rated load voltage (50/60Hz) 110VAC ᜠ
Power supply 100-240VAC ᜠ
220VAC
50/60Hz
ᜠ
Min. load current 1A
SPR1-3
380VAC ᜠ
SPR1-4
440VAC ᜠ
Permissible voltage range 90 to 110% of rated voltage
Power consumption
Display method
Rated load current 25A/35A/50A: max. 7VA
Rated load current 70A/100A/150A: max. 12VA
3-digit 7-segemnet LED
Indicator
Control method
Operation indicator/Manual control indicator: green LED
Alarm indicator/output indicator/unit (V, A) indicator: red LED
Phase control: normal control mode, constant current/constant voltage/ constant power feedback control mode
Cycle control: fixed cycle control mode, variable cycle control mode
ON/OFF control
Applied load
Control input
Phase control, ON/OFF control: resistance load, inductive load
Cycle control: resistance load
Auto control: DC4-20mA, 1-5VDC ᜡ , ON/OFF contact (no-voltage input), pulse voltage (5-12VDC ᜡ )
Manual control: outside adjuster (10kΩ), inside adjuster (output limit)
Digital input (DI)
Output
Alarm
RUN/STOP switching, AUTO/MAN switching, RESET
250VAC ᜠ 3A, 30VDC ᜡ 3A, 1c resistive load
Communication RS485 communication output (Modbus RTU method), max. connection: 31 units
Output range
Output accuracy
Set method
Functions
Alarm
Cooling method
Phase control: 0 to 98% Cycle control: 0 to 100% ON/OFF control: 0%, 100%
Normal control : within ±10% F.S. of rated load voltage
Constant current feedback control : within ±3% F.S. of rated load current
Constant voltage feedback control : within ±3% F.S. of rated load voltage
Constant power feedback control : within ±3% F.S. of rated load power
By front keys, by communication
Output limit (OUT ADJ), AUTO/MAN selection, control method selection, RESET,
SOFT START, SOFT UP/DOWN, output high/low limit, input correction, input slope correction, monitoring (control input, load voltage/current/power/resistance, power supply frequency, heatsink temperature)
Overcurrent alarm, overvoltage alarm, fuse break alarm, element error alarm, heater break alarm, heatsink overheat alarm
Rated load current 25A/35A/50A: natural cooling
Rated load current 70A/100A/150A: forced air cooling (with the cooling fan)
Over 200MΩ (at 500VDC megger) Insulation resistance
Dielectric strength 2,000VAC 50/60Hz for 1 min (between input terminals and power terminals)
Output leakage current Max. 10mArms
Noise immunity ±2kV the square wave noise (pulse width: 1 ㎲ ) by the noise simulator
Memory retention
Vibration
Environ ment
Mechanical
Malfunction
Approx. 10 years (when using non-volatile semiconductor memory type)
0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction for 2 hours
0.5mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction for 10 min
Ambient temp. -10 to 55 ℃ , storage: -20 to 80 ℃
Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Accessory
Approval
11-pin connector
Weight ※ 1
ᜢ
Rated load current 25A/35A/50A: approx. 1.6kg (approx. 1.3kg)
Rated load current 70A: approx. 1.65kg (approx. 1.35kg)
Rated load current 100A/150A: approx. 3.2kg (approx. 2.8kg)
※ 1: The weight includes packaging. The weight in parenthesis is for unit only.
※ Environment resistance is rated at no freezing or condensation.
Dimensions
Rated load current 25A/35A/50A
55
48
30 4-Ø6
223
168.5
②
③
⑤
⑦
⑫
Unit Description
①
④
⑥
⑧
⑩
⑪
⑨
Wire Specification by Load Current
Rated load current
25A/35A/50A/70A
100A/150A
Wire specification
Alarm output/ power input
AWG 18 to 14
223
168.5
Load output
S
AWG 18 to 14
⑫
R, U
AWG 13 to 4
AWG 4 to 2/0
⑬
① Bracket
② Indicator
Indicator
RUN
MAN
Operation indicator
R
Manual control indicator
S
Color
U
Green LED
Green LED
Function
Turns on in the RUN mode.
Turns on when adjusting load output in the manual control mode.
ALM
OUT
Alarm indicator
Output indicator
Red LED
Red LED
Flashes in alarming status.
Turns on when load control outputs.
③ Display part : DIS ] parameter in RUN mode, and displays
Indicator
V A parameter and setting value in setting mode.
④ Unit indicator
( : Light ON/ : Light OFF)
Display
⑤ key: Enters parameter group, returns to RUN mode, moves parameters, and saves the setting value.
⑥ Setting value adjustment key
: Enters SV setting mode and move digits.
Resistance, load
Voltage
Current
Power
⑦ Output limit adjuster (OUT ADJ)
: Limits output from 0 to 100%.
⑧ 11-pin connector terminal
⑨ Terminal cover
⑩ Alarm output and power input terminals
⑪ R, S, U load output terminals
⑫ Cooling fan: For models with the rated load current of 70A/100A/150A, a cooling fan is attached.
⑬ Heatsink
Rated load current 70A
55
48
30 4-Ø6
Spacing
4-Ø6
(unit: mm)
Panel
80°
Rated load current 100A/150A
80
71
40 4-Ø6
80°
250.1
184.4
80°
50
Panel
※ When installing multiple power controllers, please keep space at least 50mm in horizontal and 100mm in vertical between power controllers for heat radiation.
High Temperature Caution
While supplying power to the load or right after turning off the power of the load, do not touch the body and heatsink.
Failure to follow this instruction may result in a burn due to the high temperature.
Connections
Control input/Comm. output
①
ON/OFF
※ 1
VR
1-5
VDC
4-20mA
RUN/STOP
AUTO/MAN
RS485
RESET
A(+)
B(-)
②
③
⑧
⑨
⑩
⑪
④
⑤
⑥
⑦
Alarm output/power input
Alarm Output
(250VAC 3A 1c)
(30VDC 3A 1c)
Resistive Load
100-240VAC
50/60Hz
N.C.
1
COM
2
N.O.
3
N
4
L
5
Load output
※ 2
Noise filter
Rapid fuse
R S U
CAP
※ 2
※ 1: This is only for models with RS485 communication output (SPR1-
※ 2: When connecting noise filter and capacitor, it is appropriate for EMC.
T
CAP : Rated load voltage 110VAC-220VAC → 1uF/250VAC
: Rated load voltage 380VAC-440VAC → 0.47uF/500VAC
※ Tighten the terminal screw with the below tightening torque.
Rated load current
25A, 35A,
50A, 70A
100A, 150A
Specification
Alarm output/ power input
Screw M3
Tightening torque 0.5N.m
Screw M3
Tightening torque 0.5N.m
Load output
S
M3
0.5N.m
M3
0.5N.m
※ Use crimp terminals or terminals of size specified below.
).
R, U
M6
5.5 to 6.0N.m
M8
6.5 to 7.0N.m
(unit: mm) a Terminal type
Terminal number c b a b c
<Crimp terminal>
Input
(11-pin)
1 to 11 6 to 7 Max. 1.5 Max. 3.5
<Round> a b
Terminal type
Alarm output/power input
S
Load output R, U
Rated load current
25A/35A/50A/70A
Rated load current
100A/150A a b
Min. 3.0 Max. 6.0
Min. 3.0 Max. 8.0
Min. 6.0 Max. 16.0
Min. 8.0
Max. 26.0
Removing the Case
①
②
Case fixing bolts
Spec. of case fixing bolts
Rated load current
25A, 35A, 50A, 70A
Spec. of bolts
M3
100A, 150A M4
Replacement of Fuse
Fuse Fuse fixing bolts
Spec. of fuse fixing bolts
Rated load current Spec. of bolts
25A, 35A, 50A, 70A M6
100A, 150A M8
Recommended fuse specifications
For replacing the fuse, please use the recommended fuse which has the below specifications.
(manufacture: BUSSMANN)
Rated load current
25A
Model
50FE
Rated load current
50A
Model
80ET
Rated load current
100A
Model
FWH-150B
35A 63ET 70A 100FE 150A FWH-200B
※ The performance of the product is guaranteed only when using the fuse provided by us.
Parameter Group
RUN mode
2 sec 4 sec
Monitoring group Parameter 1 group[ PR1 ]
3 sec
Parameter 2 group[ PR2
3 sec
]
※ If there is no key input for 30 sec while setting SV or the parameters, the new settings are ignored, and the unit will return to RUN mode with previous settings.
※ Hold the key for 3 sec while in setting mode to return to RUN mode.
Monitoring group
※ 1: : Press any key among , , .
※ 2: Press the next parameter
key once after changing the setting value, to save the setting value and move to the
※ Hold the setting value.
key for 3 sec to save the setting value and return to RUN mode after changing the
※ Dotted parameters may not appear by model type or other parameter settings.
RUN mode
Control input
IN
※ 1
Load voltage
L-V
100
※ 2
Measuring range: 0 to 100%
220
※ Displayed only for feedback control models.
Measuring range: 0 to rated voltage range[V]
Load current
L-A 50 Measuring range: 0 to rated current range[A]
Load power
L-W
Load resistance
L-R
10 Measuring range: 0 to rated power range[VA]
Heatsink temp.
TMP
50
Measuring range: Percentage [%] of the currently measured resistance value compared to the set resistance value of full load auto recognition.
25 Measuring range: 0 to 100 ℃
Power supply frequency
FRQ 60 Measuring range: 50, 60Hz
Parameter 1 group
3 sec
RUN mode
2 sec
PR1
SOFT START
S-T
※ 1
SOFT UP
U-T
SOFT DOWN
D-T
Output low-limit value
L-L
Output high-limit value
H-L
000
※ 2
000
Setting range: 0 to 100 sec
※ When control method
[ C-M ]
is ONF , settings can not be changed.
000
000
100
Setting range
: 0% ≤ Output low-limit value[ L-L ] ≤ Output high-limit value[ H-L ] ≤ 100%
Parameter 2 group
3 sec
RUN mode
PR2
4 sec
※ 1: : Press any key among , , .
※ 2: Press the key once after changing the setting value, to save the setting value and move to the next parameter
※ Hold the key for 3 sec to save the setting value and return to RUN mode after changing the setting value.
※ Dotted parameters may not appear by model type or other parameter settings.
※ 1
Control input
INT
DC4-20mA
420
1-5VDC
1-5
5-12VDC
512
ON/OFF contact
ONF
RS485 comm.
COM
※ 2
Control method
C-M
Phase -
Normal
PA
Phase -
Constant voltage
V-F
Phase -
Constant current
C-F
Phase -
Constant power
W-F
External output limit adjuster
E-R
Input correction
INB
Input slope correction
SPN
Setting range: Normal control
Feedback control
( normal/constant current/constant voltage/ constant power control)
PA , F-C , V-C , ONF
PA , V-F , C-F , W-F ,
F-C , V-C , ONF
OFF
00
00
Cycle-Fixed
F-C
ON
Cycle-Variable
V-C
Setting range: -99 to 99%
Setting range: -99 to 99%
ON/OFF
ONF
Functions
Output limit (OUT ADJ)
This function will be [Control input (%) × OUT ADJ (%) =
Output] and it controls the power supplied into the load.
Although control input is 100% (5V or 20mA), the output is the 50% which is proportioned with OUT ADJ.
※ This function can not be used for ON/OFF control method.
Output high limit/low limit value [
H-L
/
L-L
]
This function is to limit output range to protect load.
SOFT START [
S-T
]
When the power is supplied, this function is able to protect the load when it controls load (molybdan, white gold, infrared lamp) with inrush current or the width of rising temperature in big (SV is big).
SOFT START set time (T) is the required time that output reaches to 100%, and it is differentiated by
OUT ADJ set value.
※ This function can not be used for ON/OFF control method.
SOFT UP/DOWN [
U-T / D-T
]
Unlike SOFT START which operates only once at supplying power, this function protects load from the inrush current in the RUN mode. When reached to the target output value, operation stops.
※ This function can not be used for ON/OFF control method.
A: SOFT START function finished.
B: SOFT UP function finished.
C: SOFT DOWN function finished.
Input correction [
INB
]
It compensates the offset between actual input value and measured input value.
E.g.) When input monitoring value is 5% at 4mA in
DC4-20mA control input, setting INB to -5 calibrates the input monitoring value to 0%.
Front display
DIS
Overcurrent alarm value
OCV
Overcurrent alarm delay time
OCT
Overvoltage alarm value
OVV
Overvoltage alarm delay time
OVT
Full load auto recognition
F-L
Heater break alarm value
HBV
Comm. address
ADR
Comm. speed
BPS
Comm. parity bit
PRT
Comm. stop bit
STP
Resistance and input
IN
Load voltage
L-V
Load current
L-A
Load power
L-W
Setting range: Normal control
Feedback control
( normal/constant current/constant voltage/ constant power control)
IN
IN , L-V , L-A , L-W
120
005
120
005
OFF
010
001
9,600bps
96
NON
2
※ Displayed only for feedback control models.
Setting range: 0 to 120%
Setting range: 0 to 100 sec
Setting range: 0 to 120%
Setting range: 0 to 100 sec
ON
Setting range: 10 to 100%
※ Displayed only for modelswithRS485communicationoutput.
Setting range: 1 to 99
19,200bps
192
EVE
1
38,400bps
384
ODD
2,400bps
24
4,800bps
48
100
75
50
25
100
50
0 50
0
SOFT START set time
100
50
0
SOFT START set time
100
80
60
40
20
100
Time
SOFT UP set time
Time
Setting value = 100%
Setting value = 50%
Control input [%]
When output applied to load is 100%,
When output applied to load is 50%,
SOFT DOWN set time
: Actual input signal (%)
: Input corrected signal (%)
Input slope correction [
SPN
]
It compensates the gain of the measured 100% input for actual 100% input value.
Calibrated monitoring value=Monitoring value+ Monitoring value
×
SPN
E.g.) When the input monitoring value is 99% at 4mA in
DC4-20mA control input, setting SPN to 1 calibrates the input monitoring value to 100%.
0
100
80
60
40
20
25 50 75 100
Actual input signal [%]
RUN/STOP switching
AUTO/MANUAL selection
0 25 50 75 100
Actual input signal [%]
RUN/STOP status of the power controller can be switched with the external
RUN/STOP contact.
In the RUN mode, the operation indicator on the front turns on.
ON/OFF
: Actual input signal (%)
: Input corrected signal (%)
Operation mode (auto control/manual control) of the power controller can be selected with the external AUTO/MAN contact.
In the manual control mode, the manual control indicator on the front turns on.
RESET
In the event of system anomalies and alarms, RESET input restarts the power controller.(Parameters are not initialized.)
Or, hold the , keys for 2 sec, to operates RESET.
Alarm
ON/OFF
ON
Type
Element (SCR) error alarm
1
※ 1
Overcurrent alarm
※
Fuse break alarm
Heatsink overheat alarm
Overvoltage alarm ※ 1
Error
SCR
O-C
FUS
TEM
O-V
Operation
Output stops.
(SCR OFF)
Clear alarm
- Re-supply the power.
- RESET
- Switch to STOP mode
Display priority
1
4
5
2
3
Heater break alarm ※ 1 H-B
Continues operation
Automatically cleared when returning within the setting range 6
※ 1: This is only for feedback control models.
※ For models with alarm output, the error message and alarm indicator flash at the same time, and alarm output turns on.
※ When multiple alarms occur at the same time, the highest priority error message will be displayed based on priority.
1) Element (SCR) error alarm
Even though output is 0%, if the current of 10% or more of the rated load current flows for over 3 sec continuously, element error alarm occurs and output stops.
2) Overcurrent alarm [ OCU / OCT ]
This function protects the load from overcurrent.
If the current flows over the overcurrent alarm setting value and setting delay time, overcurrent alarm occurs and output stops.
3) Heatsink overheat alarm
When the temperature of a heatsink is over 85 ℃ , heatsink overheat alarm occurs and output stops.
4) Overvoltage alarm [ OVV / OVT ]
This function protects the load from overvoltage.
If the current flows over the overvoltage alarm setting value and setting delay time, overvoltage alarm occurs and output stops.
5) Heater break alarm [ HBV ]
Comparing the full load resistance value and the current load resistance value, if the current load resistivity is maintained under the setting value for over 3 sec continuously, heater break alarm occurs.
Output does not stop and operates normally.
Comm. response waiting time
RW.T
Comm. write
CM.W
Lock
LOC
Parameter reset
INI
020
Enables
EN.A
Setting range: 5 to 99ms
Disables
DsA
OFF
NO
LC1 LC2
Setting range:
PR1 PR2
OFF
LC1
LC2
: Available to check/set
: Available to check/Unavailable to set YES
※ Hold the , , keys for 5 sec, to enter parameter reset parameter.
Cautions during Use
1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
2. Use the product, after 3 sec of supplying power.
3. Before use, set the mode and function according to the specification. Especially, be cautious that the product does not operate when OUT ADJ. is set to 0%. Since changing the mode/parameter during operation may result in malfunction, set the mode and function after disconnecting load output.
4. Re-supply the power to the unit after the unit is discharged completely.
Failure to follow this instruction may result in malfunction.
5. To ensure the reliability of the product, install the product on the panel or metal surface vertically to the ground.
6. Install the unit in the well ventilated place.
7. While supplying power to the load or right after turning off the power of the load, do not touch the body and heat sink. Failure to follow this instruction may result in a burn due to the high temperature.
8. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power.
9. Do not wire to terminals which are not used.
10. Since inter element can be damaged when using with coil load, inductive load, etc., the inrush current must be under the rated load current.
11. Do not use near the equipment which generates strong magnetic force or high frequency noise.
12. This unit may be used in the following environments.
① Indoors (in the environment condition rated in 'Specifications') ② Altitude max. 2,000m
③ Pollution degree 2 ④ Installation category III
Rated load current 25A
25
20
15
10
5
0
0 10 20 30 40 50 60 70
Ambient temperature [ ℃ ]
Rated load current 50A
50
40
30
20
10
0
0 25
Ambient temperature [ ℃ ]
Rated load current 100A
100
80
60
40
20
0
0 10 20 30 40 50 60 70
Ambient temperature [ ℃ ]
Rated load current 35A
35
28
21
14
7
0
0 10 20 30 40 50 60 70
Ambient temperature [ ℃ ]
Rated load current
70A
70
56
42
28
14
0
0 35
Ambient temperature [ ℃ ]
Rated load current
150A
150
120
90
60
30
0
0 10 20 30 40 50 60 70
Ambient temperature [ ℃ ]
Comprehensive Device Management Program [DAQMaster]
DAQMaster is a comprehensive device management software for setting parameters and monitoring processes. DAQMaster can be downloaded from our website at www.autonics.com.
Item
System
Minimum specifications
IBM PC compatible computer with Pentium Ⅲ or above
Operations Windows 98/NT/XP/Vista/7/8/10
Memory 256MB+
Hard disk
VGA
Others
1GB+ of available hard disk space
Resolution: 1024×768 or higher
RS232C serial port (9-pin), USB port
Derating Curve
User Manual for Communication
For the detail information and instructions, please refer to user manual for communication, and be sure to follow cautions written in the technical descriptions (catalog, homepage).
Visit our homepage (www.autonics.com) to download manuals.
RS485 Communication Output
※ Applicable for models with RS485 communication output through option output (SPR1- T ).
Please refer to ' Ordering Information'.
1. Communication Specifications
Comm. protocol Modbus RTU
Connection method RS485
Comm. speed
2400, 4800, 9600, 19200,
38400 bps
Application standard Compliance with EIA RS485 Comm. response time 5 to 99ms (default: 20ms)
Max. connections 31 units (address: 1 to 99) Start bit 1-bit (fixed)
Synchronization method Asynchronous Data bit 8-bit (fixed)
Comm. method
Comm. distance
Two-wire half duplex
Max. 800m
2.
Application of system organization
Parity bit
Stop bit
None, Even, Odd
1-bit, 2-bit
RS232C/
USB/Wi-Fi RS485
Terminating resistance
(100 to 120Ω)
B(-)
A(+)
RS485
DEVICE
#31
Comm. converter
B(-) A(+) B(-) A(+) B(-) A(+) B(-)
Computer
ON
A(+)
OFF
RS485
DEVICE
#1
RS485
DEVICE
#2
RS485
DEVICE
#30
※ It is recommended to use Autonics communication converter; SCM-WF48 (Wi-Fi to RS485·USB wireless communication converter, sold separately), SCM-US48I (USB to RS485 converter, sold separately),
SCM-38I (RS232C to RS485 converter, sold separately). Please use twisted pair wire, which is suitable for RS485 communication, for SCM-WF48, SCM-US48I and SCM-38I.
Major Products
Photoelectric Sensors
Fiber Optic Sensors
Door Sensors
Door Side Sensors
Area Sensors
Proximity Sensors
Pressure Sensors
Rotary Encoders
Temperature Controllers
Temperature/Humidity Transducers
SSRs/Power Controllers
Counters
Timers
Panel Meters
Tachometer/Pulse (Rate) Meters
Display Units
Connector/Sockets Sensor Controllers
Switching Mode Power Supplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/Logic Panels
Field Network Devices
Laser Marking System (Fiber, CO
Laser Welding/Cutting System
₂ , Nd: YAG) http://www.autonics.com
HEADQUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
South Korea, 48002
TEL: 82-51-519-3232
E-mail: [email protected]
DRW171280AB
advertisement
Related manuals
advertisement
Table of contents
- 1 Safety Considerations
- 1 Ordering Information
- 1 Specifications
- 1 Unit Description
- 1 Wire Specification by Load Current
- 1 Dimensions
- 1 Connections
- 1 Removing the Case
- 1 Replacement of Fuse
- 2 Parameter Group
- 2 Functions
- 2 Derating Curve
- 2 Comprehensive Device Management Program [DAQMaster]
- 2 User Manual for Communication
- 2 RS485 Communication Output
- 2 Cautions during Use
- 2 Major Products