Model

CX-90M-03

CX-90M-03 Magnetic Lock

300 Lbs Mortise Mount, Single Door

Installation Instructions

Description

Single

Features

Basic

Current Draw

360 mA @ 12VDC

180 mA @ 24 VDC

SHOCK HAZARD. Care must be taken to keep the power supply and wiring isolated from ground (earth). Use of an ohmmeter to test for shorts is recommended prior t o service.

A. 12V DC Input:

Set jumpers for 12V DC operation. (See diagram below)

Connect the ground (-) lead from a 12V DC power source to terminal 2.

Connect the positive (+) lead from a 12V DC power source to terminal 1.

B. 24V DC Input:

Unit is delivered from Factory with single jumper ON for 24V operation.

Connect the ground (-) lead from a 24V DC power source to terminal 2.

Connect the positive (+) lead from a 24V DC power source to terminal.

Note: Only use UL/CUL Listed Regulated Power Limited Power Source.

Important

Power switch should always be wired as shown below in order to minimize the effect of residual magnetism.

Contact Camden for other wiring considerations.

CX-90M-03 Installation Instructions

Important! Please read before installation

A. Handle the components with care. Damaging the surfaces of the magnet or armature plate may reduce locking efficiency.

B. The magnet mounts to the door frame. The armature plate must be mounted to the door with the hardware supplied.

This allows it to pivot about its center to compensate for door wear and misalignment.

C. Affix template with the door in its normally closed position.

D. Mark and drill holes. Mount magnet and armature plate with screws installed finger tight at first. Verify all parts align correctly, then firmly tighten screws.