- No category
advertisement
Guide d'exploitation
User's manual
Altivar 68
Coupleur de communication
Protocole Modbus
Communication coupler
Modbus protocol
VW3-A68303
Altivar 68
Coupleur de communication protocole Modbus
Communication coupler Modbus protocol
Page 2
Page 82
2
83
When the drive is powered up, the power components and some of the control components are connected to the line supply.
It is extremely dangerous to touch them. The drive cover must be closed.
As a rule,
the drive power supply must be disconne
before any operation on either the electrical or mechanical parts of the installation or machine.
After the ALTIVAR has been switched off,
wait for at least 1 minutes before working on the equipment
required for the capacitors to discharge. Check that the voltage between the + and - terminals is lower than 60 V
a
.
The products and equipment described in this document may be changed or modified at any time, either from a technical point of view or in the way they are operated. Their description can in no way be considered contractual.
This document is designed to be used in conjunction with the ATV-68 programming manual.
Contents
Hardware Installation _______________________________________________________________ 84
Presentation _______________________________________________________________ 84
Mounting the module on a DIN rail ______________________________________________ 85
Supplying the module with power _______________________________________________ 86
Connecting the module to the drive _____________________________________________ 87
Connecting the module to the Modbus network ____________________________________ 89
Example of connection _______________________________________________________ 90
Wiring recommendations _____________________________________________________ 91
Pin-outs __________________________________________________________________ 91
Configuring the communication functions _________________________________________ 92
Signalling ________________________________________________________________________ 95
Notation Conventions _______________________________________________________________ 96
Parameter Conversion to Physical Values _______________________________________________ 97
Modbus Protocol __________________________________________________________________ 98
RTU mode ________________________________________________________________ 98
Principle __________________________________________________________________ 98
Addresses _________________________________________________________________ 98
Modbus functions ___________________________________________________________ 99
Exception responses _______________________________________________________ 103
Calculating the CRC16 ______________________________________________________ 103
Module Modbus Data ______________________________________________________________ 104
Module Management ______________________________________________________________ 105
ATV68 Control and Monitoring _______________________________________________________ 106
ATV68 Control ___________________________________________________________________ 110
ATV68 Monitoring ________________________________________________________________ 116
Description of the ETA status word ____________________________________________ 116
Managing Communication Errors _____________________________________________________ 121
PKW Parameter-Setting Service _____________________________________________________ 122
ATV68 Configuration ______________________________________________________________ 128
Key to tables ______________________________________________________________ 128
B6. Serial Port configuration __________________________________________________ 128
D3. Configuration of analogue outputs __________________________________________ 134
D4. Configuration of logic outputs _____________________________________________ 135
ATV68 Diagnostics ________________________________________________________________ 136
A4. Display reference values _________________________________________________ 139
Example of Use __________________________________________________________________ 141
List of Parameters ________________________________________________________________ 145
84
Hardware Installation
Presentation
This module acts as an interface between the drive terminal port and the Modbus network.
Only one ATV68 can be connected to the module; the terminal port protocol is point-to-point (and RS232).
The term gateway is used in other documents. The gateway is designed to interconnect two networks. A gateway can perform the function of a module.
VW3-A68303 includes the Modbus module for ATV68 shown below.
The cables and other connection accessories should be ordered separately.
4
5
1 2 3
6
Modbus
RTU
Configuration ATV68
Key:
1
Module power supply plug-in connector (24V ±10%).
2
Female RJ45 connector for PC link and ABC Configurator software.
The Modbus module for ATV68 is factory-preset to operate in a standard mode, which don’t request the ABC Configurator software. This manual describes the functions in this standard mode.
The ABC Configurator software is included in the PowerSuite offer. It allows to:
• modify the factory-preset of the module,
• diagnose the module.
The configurator has an online help which describes how to use it.
Female RJ45 connector for ATV68 link. Only one ATV68 can be connected to this port.
3
4
Six diagnostic LEDs.
5
6
Cover concealing the module configuration switches (see Configuring the communication functions section, page 93). The LED descriptive label is attached to this.
Modbus 9-pin female SUB-D connector.
85
Hardware Installation
Mounting the module on a DIN rail
Mounting the module
1
Removing the module
1
2
Start by placing the module rear base on the top of the rail, pushing downwards (1) to compress the module spring. Then push the module against the
DIN rail (2) until the base of the module casing clips onto the rail.
2
Start by pushing the module downwards (1) to compress the module spring. Then pull the bottom of the module casing forwards (2) until the back of the casing unclips from the rail.
Note: The spring also performs the function of earthing the module (Protective Earth).
86
Hardware Installation
Supplying the module with power
Modbus module for ATV68 — View of underside
–
+
Power supply
24 V AC isolated
(± 10%) 280 mA max.
The module is not supplied by the drive, but requires a separate power supply.
Note: The negative terminal of the 24 V power supply should be connected to the installation earth.
87
Hardware Installation
Connecting the module to the drive
The connection accessories should be ordered separately (consult the catalogue).
During installation, the module and drive should be switched off.
1 Use the VW3-A68313 cable.
2 Remove the ATV68 cover.
3 Attach the “ATV68” connector to the control card X4 connector (RJ45 port) and the “Gateway” connector to the module RJ45 connector located closest to the front panel (marked “ATV68” on the following diagram).
ATV68
(control card)
VW3-A68303
Control keypad
ATV68
Configuration
Control card
RJ45
(X4 connector)
RJ45
VW3-A68313
88
Hardware Installation
It is possible to communicate with the ATV68 when its power is switched off (line switch or circuit-breaker open).
To do this, it is necessary to connect an auxiliary control supply voltage:
• 24 V DC for the ATV68••N4 range (400 V/500 V)
• 230 V AC for the ATV68••Y range (690 V)
See the user manuals for how to connect the auxiliary control power supply.
Pin-out for the ATV68-module cable:
ATV68 (RJ5)
(X4 port)
VW3-A68313 cable
Module (RJ45)
(ATV68 port)
89
Hardware Installation
Connecting the module to the Modbus network
The connection accessories should be ordered separately (consult the catalogue).
Attach the cable 9-pin male SUB-D connector to the 9-pin female SUB-D connector on the module front panel, as shown in the following diagram:
VW3 A68 303
9-pin female
SUB-D
VW3 A68 313
90
Hardware Installation
Example of connection
The Schneider Electric catalogue offers a variety of accessories to simplify equipment connection.
Connection on TSXSCA62 and TSXSCA50 cable connectors is one example of the different options for connecting Modbus (please consult our catalogues).
- Shielded double twisted pair cable: TSXCSA100 (100 m)
TSXCSA200 (200 m)
TSXCSA500 (500 m)
- TSXSCA62
2-channel subscriber socket:
This passive box can be used for connection on two screw terminals and two 15-pin female SUB-D connectors. It includes the line termination required when the socket is located at the end of the line.
- TSXCA50 junction box:
- Drop cables:
This passive box can be used for connection on three screw terminals. It includes line termination.
VW3A8306 3 m long, equipped with 2 RJ45 and male SubD15 connectors.
VW3A8306D30 3 m long, equipped with an RJ45 connector, stripped at the other end.
PLC PC
TSX CSA •00
VW3 A68 303
VW3 A68 303
91
VW3 A68 313
VW3 A68 313
TSX SCA 62
Hardware Installation
Wiring recommendations
• Use a shielded cable with 2 pairs of twisted conductors
• Link the reference voltages together
• Maximum line length: 1000 metres
• Maximum drop length: 20 metres
• Cable routing: keep the bus separate from the power cables (30 cm minimum), make crossovers at right angles if necessary, connect the cable shielding to the ground of each device
• Add line terminations at both ends
120
Ω
D(A)
1 nF
Line termination recommended at both ends
D(B)
Pin-outs
• Modbus module for ATV68
9-pin female SUB-D
NC
1
RS232 - TX (not used)
2
RS232 - RX (not used)
NC
3
4
GND (GALV)
+ 5 (GALV)
5
6
RS485 B-LINE
RS485 A-LINE
7
8
NC
9
• VW3A68306 cable for TSX SCA 62
9-pin male SUB-D 15-pin male SUB-D
GND
D(B)
D(A)
6
7
4
5
8
9
1
2
3
15
14
7
92
Hardware Installation
Configuring the communication functions
Configuration must be performed with the module switched off.
Both blocks of switches used to configure the communication functions are concealed behind the module cover
5
(see Presentation section, page 85). To remove this cover, simply slide the tip of a small screwdriver between the top of the cover and the module casing, then carefully remove the cover. Once the cover has been removed, take care not to touch any electrical circuits or electronic components. Both blocks of switches are represented schematically below, with each switch shown in its factory-set position:
Address Speed Parity
A switch is at state 0 when it is in the OFF position and state ON 1 when it is in the ON position.
Any modification to the module communication functions will only take effect when the module is next switched on.
Note: When all the switches are in the OFF position, the LED
4
"Hardware Settings Status" turns red. This also occurs if an configuration is incorrect.
Coding the Modbus address
An Altivar 68 is identified on a Modbus bus by its module address, coded from 1 to 31.
The drive address corresponds to the binary number given by the ON (1) or OFF (0) position of switches 1
(MSB) to 7 (LSB) in the block of 8 switches. It should be configured before the module is switched on:
Address Speed Parity
93
Hardware Installation
Switches
1 2 3 4 5 6 7 8 1 2 3 4
0 0 0 0 0 0 0 x x x x x
0 0 0 0 0 0 1 x x x x x
0 0 0 0 0 1 0 x x x x x
0 0 0 0 0 1 1 x x x x x
0 0 0 0 1 0 0 x x x x x
0 0 0 0 1 0 1 x x x x x
0 0 0 0 1 1 0 x x x x x
0 0 0 0 1 1 1 x x x x x
0 0 0 1 0 0 0 x x x x x
0 0 0 1 0 0 1 x x x x x
0 0 0 1 0 1 0 x x x x x
0 0 0 1 0 1 1 x x x x x
0 0 0 1 1 0 0 x x x x x
0 0 0 1 1 0 1 x x x x x
0 0 0 1 1 1 0 x x x x x
0 0 0 1 1 1 1 x x x x x
0 0 1 0 0 0 0 x x x x x
Modbus address
Invalid configuration
13
14
15
16
9
10
11
12
5
6
7
8
1
2
3
4
Switches
1 2 3 4 5 6 7 8 1 2 3 4
0 0 1 0 0 0 1 x x x x x
0 0 1 0 0 1 0 x x x x x
0 0 1 0 0 1 1 x x x x x
0 0 1 0 1 0 0 x x x x x
0 0 1 0 1 0 1 x x x x x
0 0 1 0 1 1 0 x x x x x
0 0 1 0 1 1 1 x x x x x
0 0 1 1 0 0 0 x x x x x
0 0 1 1 0 0 1 x x x x x
0 0 1 1 0 1 0 x x x x x
0 0 1 1 0 1 1 x x x x x
0 0 1 1 1 0 0 x x x x x
0 0 1 1 1 0 1 x x x x x
0 0 1 1 1 1 0 x x x x x
0 0 1 1 1 1 1 x x x x x
0 1 0 0 0 0 0 x to
1 1 1 1 1 1 1 x x x x x x x x x
Modbus address
23
24
25
26
17
18
19
20
21
22
27
28
29
30
31
Invalid configurations
Coding the Modbus speed
The module speed should be identical to that of the Modbus master.
The factory setting is 19,200 bps.
The value of this speed depends on switch 8 (MSB) in the block of 8 switches and switches 1 and 2 (LSB) in the block of 4 switches.
Address Speed Parity
Switches
1 2 3 4 5 6 7 8 1 2 3 4 x x x x x x x 0 0 0 x x x x x x x x x 0 0 1 x x x x x x x x x 0 1 0 x x x x x x x x x 0 1 1 x x x x x x x x x 1 0 0 x x x x x x x x x 1 0 1 x x x x x x x x x 1 1 0 x x x x x x x x x 1 1 1 x x
Modbus speed
Invalid configuration
1,200 bps
2,400 bps
4,800 bps
9,600 bps
19,200 bps
Invalid configurations
94
Hardware Installation
Coding the Modbus parity
The module parity should be identical to that of the Modbus master. The factory setting is no parity.
Address Speed Parity
Switches
1 2 3 4 5 6 7 8 1 2 3 4 x x x x x x x x x x 0 0 x x x x x x x x x x 0 1 x x x x x x x x x x 1 0 x x x x x x x x x x 1 1
Examples of configuration
Modbus parity
Invalid configuration
No parity
Even
Odd
Address Speed Parity
Address Speed Parity
Address = 12
Speed = 9,600 bps
Parity = Even
Address = 5
Speed = 2,400 bps
Parity = No parity
95
Signalling
1
3
5
2
4
6
VW3A68303
1 2
3
5
4
6
1 B
US
E
RROR
2 B
US
R
EADY
3 P
ROCESSING
4 HW S
ET
. S
TAT
.
5 S
UBNET
S
TATUS
6 D
EVICE
S
TATUS
1 Bus Error
Red
Off
3
Processing
Flashing green
Off
Modbus error.
More than 10% of requests have an incorrect CRC value.
Modbus operational or module not initialized
2 Bus Ready
Green
Off
Receiving a Modbus request or sending a Modbus response
No request is being processed
Modbus operating normally
Anomaly during module initialization
Red Modbus fault (time-out)
4
Hardware settings status
Red
Green
The module switches are all in the
OFF state or
Incorrect configuration
Switch hardware configuration replaced by a software configuration
5 Subnet Status
Green
Red
ATV68-module link OK
ATV68-module link fault
Off
6 Device Status
Switches OK and in use
Off Module not supplied with power Off
Flashing green Initializing the ATV68-module link Green
Flashing green
Red
Flashing green/ red
Module not supplied with power
Initializing the module
Module operational
Module internal fault
Configuration missing
Note : If the “D
EVICE
S
TATUS
” LED flashes according to a sequence beginning with one or more red flashes, you should make a note of the order in which this sequence occurs, and communicate this information to Schneider Electric’s repair department.
96
Notation Conventions
16#••••
••••h
2#••••
Value expressed in hexadecimal, equivalent to the notations H••••, ••••hex and 0x•••• sometimes used in other documents
Example: 16#0100 = 256
Value expressed in binary. The number of ‘•’ digits depends on the size of the represented data item. Each 4-bit byte is separated from the others by a space
Examples: byte 2#0010 0111 = 39, word 2#0110 1001 1101 0001 = 16#69D1 = 27089
Decimal values are written without a prefix ••••
Lo
Hi f n
Low-order byte in a word or low-order word in a double word
High-order byte in a word or high-order word in a double word
Frequencies (Hz or submultiple)
Speed of rotation (rpm)
Wxxx Address of a Modbus word
Wxxx:y Bit y of Modbus word xxx
Example: W0: 12 = bit 12 of word 0
97
Parameter Conversion to Physical Values
N2 type of data (16-bit standardized value)
Physical value =
Parameter value
16384.0
x Standardization factor
Example 1: Output frequency
Parameter value
Standardization factor
Unit
Frequency =
2500
16384.0
x 163.84 = 25.0 Hz
Example 2: Power output on the motor shaft
Parameter value
Standardization factor
Unit
16#1333 = 4915
400.0
kW
Power =
4951
16384.0
16#09C4 = 2500
163.84
Hz
x 400.0 = 120 kW
Example 3: Percentage
%
199,9939
100,0000
0.0061
0.0000
-0.0061
-100,0000
-200,0000
Binary
2#0111 1111 1111 1111
2#0100 0000 0000 0000
2#0000 0000 0000 0001
2#0000 0000 0000 0000
2#1111 1111 1111 1111
2#1100 0000 0000 0000
2#1000 0000 0000 0000
Hexadecimal
16#7FFF
16#4000
16#0001
16#0000
16#FFFF
16#C000
16#8000
T2 type of data (time constant 16)
Physical value = Parameter value x Standardization factor
Example 4: Display of acceleration time (T2 type of data)
Parameter value 16#0064 = 100
Standardization factor 0.005 (5 ms internal clock)
Unit s
Time = 100 dec x 0.005 s = 0.5 s
Other types of data (02, V2)
It is not necessary to repeat standardization.
Decimal
32767
16384
1
0
-1
-16384
-32768
98
Modbus Protocol
RTU mode
The transmission mode used is RTU mode. The frame does not contain a message header byte, nor any end of message bytes. It is defined as follows:
Slave address
Request code Data
The data is transmitted in binary.
CRC16: cyclical redundancy check.
The end of the frame is detected after a silence
≥
3 characters.
Principle
Modbus protocol is a master-slave protocol.
Master
CRC16
There can only be one device on the line which is sending a message.
The master manages the exchanges and only it can take the initiative.
It interrogates each of the slaves in succession.
No slave can send a message of its own accord without having been requested.
The master repeats the question if there is an incorrect exchange, and decrees that the interrogated slave is missing after failure to respond within a given time period.
If a slave does not understand a message, it sends an exception response to the master. The master can repeat the request or not.
Slave j
Slave i Slave k
Direct slave-to-slave communications are not possible.
For slave-to-slave communication, the master application software must have been designed to permit this: interrogating one slave and sending the data received to the other slave.
Two types of dialog are possible between master and slaves:
• the master sends a request to a slave and waits for its response
• the master sends a request to all the slaves without waiting for a response (broadcast communication principle)
Addresses
• The drive Modbus address can be configured from 1 to 31
• Address 0 coded in a request sent by the master is reserved for broadcast communication. ATV68 drives take account of the request, but do not respond to it
• When the ATV68 is configured with address 0 (default value), it does not respond
99
Modbus Protocol
Modbus functions
The following table indicates which Modbus functions are managed by the Modbus module for ATV68, and specifies the limits.
The "read" and "write" functions are defined as seen by the master.
Code
(decimal)
3
4
6
8
16
Function name
Read N output words
Read N input words
Write one output word
Diagnostics
Write N output words
Broadcast comm.
NO
NO
YES
NO
YES
Max. value of N
11 words max.
11 words max.
—
—
11 words max.
Modbus standard name
Read Holding Registers
Read Input Registers
Preset Single Register
Diagnostics
Preset Multiple Regs
The content of the frames described below is systematically expressed in hexadecimal notation. The “16#” prefix has therefore been left out to make it easier to read.
Read N output words or N input words: functions 3 and 4
Function 3 is used to read output words (words which can be written and read by the master in the slave), whereas function 4 is used to read input words (word which the master can only read). Apart from their respective code, these two functions are strictly identical.
Request
Slave no.
03 or 04
1 byte 1 byte
No. of the 1st word Number of words
Hi Lo Hi Lo
2 bytes 2 bytes
CRC16
2 bytes
Response
Slave no.
03 or 04
1 byte 1 byte
Number of bytes read
1 byte
Value of 1st word
Hi Lo
2 bytes
-------
Value of last word
Hi Lo
2 bytes
CRC16
2 bytes
Example: read 5 words W6 to W10 (monitoring PZD2 to PZD6) in slave 2. The number of bytes read and present in the slave response equals 10 (16#0A).
Question 02 03 0006 0005 65FB
Response 02 03 0A 25BC
Value of: W6
10C0
W7
0000
W8
7CD1
W9
457C
W10
EB10
100
Modbus Protocol
Write one output word: function 6
Function 6 is used to write an output word (word which can be written and read by the master in the slave).
Request and response (the frame format is identical)
Slave no.
06
1 byte 1 byte
Word number
Hi
2 bytes
Lo
Word value
Hi
2 bytes
Lo
CRC16
2 bytes
Example: write value 16#004D (77 in decimal notation) in word W1032 (1032 = 16#0408) of slave 2 (bus
Link reference 3 = 77).
Question and
Response
02 06 0408 004D C93E
Diagnostics: function 8
Function 8 is used to read the value of one of the internal event counters of the Modbus module for ATV68 or to ask it to perform diagnostic commands. The code for this function is always accompanied by a sub-code, thus characterizing a diagnostic sub-function. The complete list of sub-codes that can be used with the Modbus module for ATV68 is given in a table appearing after the description of the request and response frames. A second table contains the descriptions of these sub-functions, as well as the data they use. Finally, the description of the “diagnostics” function ends with a short example (sub-function 0: echo of the master’s request).
Request
Slave no.
08
1 byte 1 byte
Sub-code
Hi Lo
2 bytes
Request data
Hi Lo
2 bytes
CRC16
2 bytes
Response
Slave no.
08
1 byte 1 byte
Sub-code
Hi Lo
2 bytes
Request data
Hi
2 bytes
Lo
Sub-codes (decimal notation) and diagnostic sub-functions
CRC16
2 bytes
Sub-
Code
0
10
12
13
14
Name of diagnostic sub-function
Echo of the master’s request
Reset counters and diagnostics
Read number of requests received with checksum error
Read number of exception responses
Read number of requests addressed to the slave
Modbus standard name
Return Query Data
Clear Counters and Diagnostic Register
Return Bus Communication Error Count
Return Bus Exception Error Count
Return Slave Message Count
101
Modbus Protocol
Diagnostic sub-function data and description
Sub-
Code
0
10
12
13
14
Request
Data
Response
Data
Function performed
XX YY XX YY This sub-function asks the interrogated slave to return, in its response, all the request data sent by the master (XX YY).
— — — — This sub-function asks the slave to reset the monitoring counters and the status indicators relating to its exchanges, ie. the Modbus error counters.
These counters include those which are used by the other diagnostic functions, ie. the “CRC Error Counter”, “Exception Illegal Function
Counter”, “Exception Illegal Address Counter”, “Exception Data Value
Counter” and “Received Queries Counter”.
— — XX YY Reads the value (XX YY) of a 16-bit counter totalizing the number of requests received, with CRC error, by a slave. This error counter, “CRC
Error Counter”, is reset when the drive is switched on or the slave is restarted, as well as on execution of a “reset counters and diagnostics” command (sub-function 10).
— — XX YY Reads the sum (XX YY) of 16-bit counters totalizing the number of exception responses sent by the slave to a Modbus master. The three exception response counters affected by this sub-function, “Exception
Illegal Function Counter”, “Exception Illegal Address Counter” and
“Exception Data Value Counter”, are reset when the drive is switched on or the slave is restarted, as well as on execution of a “reset counters and diagnostics” command (sub-function 10).
The first three types of exception response, described below and characterized by their error code, cause incrementation of one of the three counters presented above:
• The “Exception Illegal Function Counter” counter is incremented by exception responses with error code = 1.
• The “Exception Illegal Address Counter” counter is incremented by exception responses with error code = 2.
• The “Exception Data Value Counter” counter is incremented by exception responses with error code = 3.
— — XX YY Reads the value (XX YY) of a 16-bit counter totalizing the number of requests addressed to the slave, whatever their type, including requests broadcast to all slaves. This request counter, “Received Queries
Counter”, is reset when the drive is switched on or the slave is restarted, as well as on execution of a “reset counters and diagnostics” command
(sub-function 10).
Example: echo requested for slave 2, with the value 16#53DC for the echo data.
Request and
Response
02 08 0000 53DC DD51
102
Modbus Protocol
Write N output words: function 16 (16#10)
Function 16 is used to write output words (words which can be written and read by the master in the slave).
Request
Slave no.
1 byte
10
1 byte
No. of the
1st word
Number of words
Hi Lo Hi Lo
2 bytes 2 bytes
Number of bytes
1 byte
Value of
1st word
------
Hi Lo
2 bytes
Value of last word
Hi Lo
2 bytes
CRC16
2 bytes
Response
Slave no.
1 byte
10
No. of the
1st word
Number of words
Hi Lo Hi Lo
2 bytes 2 bytes
CRC16
2 bytes 1 byte
Example: write values 16#0020 and 16#0100 (32 and 256 in decimal notation) in words W1032 and W1033
(16#0408 and 16#0409) of slave 2 (bus Link Reference 3 = 32 and bus Link Reference 4 = 256).
Request 02 10 0408 0002 04 0020 0100
Values to be written at addresses: W1032 W1033
CFD7
Response 02 10 0408 0002 C109
103
Modbus Protocol
Exception responses
An exception response is returned by a slave when it cannot execute the request addressed to it.
Exception response format:
Slave no.
1 byte
Response
code
1 byte
Error code
CRC16
1 byte 2 bytes
Response code: request function code + 16#80.
Error code:
1 = The function requested is not recognized by the slave.
2 = The bit and word addresses indicated when the request is made do not exist in the slave.
3 = The bit and word values indicated when the request is made are not permitted in the slave.
4 = The slave has begun to execute the request, but cannot continue processing it fully.
Calculating the CRC16
The CRC16 is calculated on all message bytes by applying the following method:
Initialize the CRC (16-bit register) with 16#FFFF.
From the 1st message byte to the last, enter:
CRC
Enter
XOR <byte> —> CRC
8 times
Shift the CRC one bit to the right
If the output bit = 1, enter CRC XOR 16#A001—> CRC
End of entry
End of entry
The CRC obtained will be sent with the least significant bits first, then the most significant bits (unlike the other data contained in the Modbus frames).
XOR = exclusive OR.
104
Module Modbus Data
Only the addresses and values defined in this document can be used. Any other address or value should be considered as reserved and should never be the object of a write operation.
Failure to comply with this precaution risks causing drive malfunctions.
Service
Module
Response
PKW
Monitoring
PZD
Input words
W0
W1
W2
W3
W4
W5
W6
W7
W8
W9
W10
Description
Module status word
PKE
IND
PWE Hi
PWE Lo
ETA status word
Actual value 1 AO/AI
Actual value 2 AO/AI
Actual value 3 AO/AI
Actual value 4 AO/AI
Actual value 5 AO/AI
Service
Request
PKW
Control
PZD
Output words Description
W1025 PKE
W1026
W1027
W1028
W1029
IND
PWE Hi
PWE Lo
CMD control word
W1030
W1031
W1032
W1033
W1034
Main reference 1
Aux. reference 2
Aux. reference 3
Aux. reference 4
Aux. reference 5
To ensure consistency of the data, it is advisable to:
• Read all accessible input words in a single Modbus exchange (W0 to W10)
• Write all accessible output words in a single Modbus exchange (W1025 to W1034)
These exchanges only occur between the Modbus master and the module. The module is responsible for transferring the output word values to the ATV68 to which it is connected, then retrieving the input word values from the drive.
It is important to maintain cyclic communication between the Modbus master and the module, even when the user does not need to modify either the drive status or commands. This avoids the Modbus communication timeout being tripped by the module.
105
Module Management
Module status word (W0)
Bits Name and Identifier Description
15-13 —
12 Subnet Status
Reserved
= 0 : ATV68-module link not started or faulty
= 1 : ATV68-module link OK
11-0 — Reserved
106
ATV68 Control and Monitoring
Principle of ATV68 control and monitoring
The ATV68 drive is controlled in accordance with the PROFIDRIVE standard.
Two status charts are presented here: a simplified chart and a complete chart.
The common states of these charts are identified in the same way.
The PLC output words are used to control the drive (control PZD):
Control
PZD1
PZD2 *
PZD3 *
PZD4 *
PZD5 *
PZD6 *
Word
W1029
W1030
W1031
W1032
W1033
W1034
Description
CMD control word
Main reference 1
Aux. reference 2
Aux. reference 3
Aux. reference 4
Aux. reference 5
Assignment
B6.21:
•
bits 0 to 10: Profidrive standardized
•
bits 11 to 15 *: assignable
B6.06 (default value = not used)
B6.07 (default value = not used)
B6.08 (default value = not used)
B6.09 (default value = not used)
B6.10 (default value = not used)
The PLC input words are used to find out what stage the drive is at, and also which drive values have been read (monitoring PZD):
Monitoring
PZD1
PZD2 *
PZD3 *
PZD4 *
PZD5 *
PZD6 *
Word
W5
W6
W7
W8
W9
W10
Description
ETA status word
Actual value 1 AO/AI
Actual value 2 AO/AI
Actual value 3 AO/AI
Actual value 4 AO/AI
Actual value 5 AO/AI
Assignment
B6.26:
•
bits 0 to 10: Profidrive standardized
• bits 11 to 15 *: assignable
B6.11 (default value = Output frequency)
B6.13 (default value = Output speed)
B6.15 (default value = Output current)
B6.17 (default value = Output torque)
B6.19 (default value = Output power)
107
ATV68 Control and Monitoring
Simplified Profidrive status chart
List of main states:
0 Not ready to switch on
1 Ready to switch on
3 Ready to run
7 Run
19 Lock switching on
20 Fault x : Bit state can be 0 or 1.
ETA Status Word bits
15…12 * 11…8 * x x x x x x 1 x
7…4 x 0 x x
3…0
0 0 0 0 x x x x x x x x x x 1 x x x 1 x x 0 x x x 0 x x
0 0 0 1
0 0 1 1 x x x x x x x x x x x x x x 1 x x x 1 x x x 1 x x 0 1 1 x 1 x x x 0 x x
0 1 1 1
0 0 0 0
1 0 0 0
ETA masked
16#0200
16#0201
16#0203
16#0207
16#0237
16#0240
16#0208
Mask
16#024F
16#024F
16#024F
16#024F
16#027F
16#024F
16#024F
108
ATV68 Control and Monitoring
Complete Profidrive status chart
For more information, see the "F3 menu" in the programming manual.
109
ATV68 Control and Monitoring
110
ATV68 Control
Description of the CMD control word
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
5 free bits which can be configured for internal or external commands
Bit 10 Control by communication link enabled
Bit 9
Bit 8
---
Activate Jog 1
Bit 7
Bit 6
Bit 5
Bit 4
External reset
Activate reference
Release ramp
Activate ramp output
Bit 3
Bit 2
Bit 1
Bit 0
Enable operation (unlock)
Operating condition
Operating condition
On (run)
= 1
Control by communication link disabled
---
Disable Jog 1
---
Disable reference
Inhibit ramp
Disable ramp output
Inhibit operation (lock/freewheel)
OFF 3 (fast stop)
OFF 2 (lock/freewheel stop)
OFF1 (stop on ramp)
= 0
111
ATV68 Control
Bit
0
1
2
Value
1
0
1
0
1
0
Meaning
ON
OFF 1 (stop on ramp)
Operating condition
OFF2 (lock/ freewheel stop)
Operating condition
OFF3
(fast stop)
Comment
Controls the change of the device status from "1 Ready to switch on" to
"3 Ready to run", if the "power capacitor" stage (DC bus) has already been charged.
If the "line contactor control" function is active, the device status changes to "2 Charge bus DC" while the capacitors are charging, and changes to "3 Ready to run" when the DC bus capacitors are charged.
After accepting the command, the device status changes to "13 OFF1 active" and stops the motor in accordance with the deceleration ramp.
When the output frequency reaches 0 Hz, the device status changes, passing through "0 Not ready to switch on", to "1 Ready to switch on", if the basic command (bit 1 = 0, bit 2 = 1, bit 3 = 1 and bit 10 = 1) is applied.
If a new ON command is sent during the deceleration phase, the value of the reference applied is executed in accordance with the acceleration ramp. The device status therefore changes to "7 Run".
If the "line contactor control" function is active, the contactor is disabled on switching to "1 Ready to switch on".
"OFF2" command disabled.
Command required to authorize operation.
After accepting the command, the drive is locked, and the status changes to "19 Lock switching on".
If the “line contactor control” function is active, the contactor is disabled.
The OFF2 command can also be sent using the bus connector "Unlock" function. When the basic command (bit 1 = 0, bit 2 = 1, bit 3 = 1 and bit
10 = 1) is applied, the device status changes to "1 Ready to switch on".
"OFF3" command disabled.
Command required to authorize operation.
After accepting the command, the device status changes to "14 OFF3 active", producing the fastest possible motor stop at maximum power or at maximum voltage of the power capacitor stage (DC bus).
When the output frequency reaches zero Hz, the device status changes to "19 Lock switching on".
If the “line contactor control” function is active, the contactor is disabled.
If the OFF3 command (bit 2 = 1) is cancelled during deceleration, the fast stop is still performed.
112
ATV68 Control
Bit
3
4
5
6
Value
1
0
1
0
1
0
1
0
Meaning
Enable operation
(unlock)
Comment
After accepting the command, the drive is activated in the "3 Ready to run" (lock) status and the device status changes to "4 Operation enabled".
Inhibit operation
(lock/freewheel)
After accepting the command, the drive is locked, and the device status changes to "3 Ready to run".
If the device status "13 OFF1 active" is applied, the drive is locked, and the status "0 Not ready to switch on" is applied.
If the “line contactor control” function is active, the contactor is disabled.
If the basic command (bit 1 = 0, bit 2 = 1, bit 3 = 1 and bit 10 = 1) is applied, the device status changes to "1 Ready to switch on".
If the device status "14 OFF3 active" is applied, the action is still performed.
Activate ramp output
Disable ramp output
Release ramp
Inhibit ramp
Device status "5 Ramp output active", the motor accelerates in accordance with the acceleration ramp.
After accepting the command, the ramp output is reset. The motor stops at maximum power or at the maximum voltage for the power capacitor stage (DC bus).
The device status changes to "4 Operation enabled".
Activation of status "6 Ramp release", used to unblock changes in the ramp.
After accepting the command, the after-ramp reference value is blocked, and stops changing.
The device status changes to "5 Ramp output active".
Activate reference After accepting the command, the selected reference value is used on the ramp input. The device status changes to "7 Run".
Disable reference After accepting the command, the ramp input is reset. This produces motor deceleration in accordance with the ramp set. The device status changes to "6 Ramp release".
113
ATV68 Control
Bit
7
8
9
10
0
1
1
0
1
Value
1
0
0
Meaning
External reset
Comment
The external reset command is accepted, on a positive state "20 Trip".
When the current fault has been cleared, the status changes to "19
Lock switching on".
If the fault persists, the device status remains "20 Trip".
The external reset command can also be sent via the bus connector
"External reset" function, and via the red STOP/Reset button located on the keypad.
—
Activate Jog 1
Disable Jog 1
Activate Jog 2
Disable Jog 2
Control by communication link enabled
Control by communication link disabled
The command Activate Jog 1 is only accepted if the device status is "4
Operation enabled". For this reason, the motor accelerates as fast as possible to the frequency of the parameter in C1.13; the device status changes to "11 Jog 1 active".
The command is only accepted if "Activate Jog 1" has previously been set to "1". The motor returns to zero Hz as fast as possible, then changes to the state "12 Jog 1 Pause".
If a new Jog 1 stop command is sent within two seconds, it is immediately executed.
At the end of the "Jog Timer" 2 seconds, the device status returns to the initial status "4 Operation enabled".
Command not available
Command not available
The drive is controlled by the PLC via Modbus.
The control process data is now valid.
The reaction depends on bit 9 of the ETA status word.
Bit 9 = 0 (local mode).
The drive is in local mode, the PLC can only perform monitoring.
Bit 9 = 1 (control by communication link expected).
The drive is in communication link mode, the ATV68 trips on "LS2
Loss". The drive reaction depends on the setting of parameter B6.03
"Type of stop on TO". An alarm is always sent.
114
ATV68 Control
Summary of the main commands
Function CMD control word
Binary
0000 0100 0111 1111 ON
Starting in accordance with the acceleration ramp
OFF 1
Stop in accordance with the deceleration ramp
0000 0100 0111 1110 basic command
Hexadecimal
047F
047E
OFF 2
Lock (freewheel stop)
0000 0100 0111 1101 produces the status
"19 Lock switching on"
047D
OFF 3
Fast deceleration is performed up to the DC bus current or voltage limits
Jog 1
0000 0100 0111 1011 produces the status
"19 Lock switching on"
047B
0000 0101 0000 1111 050F
Reset
(External reset) xxxx x1xx 1xxx xxxx example:
0480
Key:
F/n = frequency or speed
Ver = lock
115
ATV68 Control
Assignment of the free bits 11 to 15 of the CMD control word
Bits 11 to 15 of the control word (CMD) are not fixed by Profidrive; they can be assigned to:
• internal commands (conforming to use of the logic input)
• external commands in a totally separate way from the ATV68 functions, for the transmission of data via the logic outputs (bit 10 of the CMD control word should be at 1)
Use
"Internal"
"External"
Free bits of the CMD control word
Logic input A
Logic input B
Logic input C
Manual/Auto
2 nd
Ramp
External Trip
EXT-Mot.Trip
EXT-T Limit
PID-enable
Mains ON(OFF)
…
(See parameters B6.21 to B6.25)
D4.00: 24V logic output
D4.01: Relay output 1
D4.02: Relay output 2_2
D4.03: Relay output 3_2
(See configuration of logic outputs)
•
•
Assignment of communication link references
Communication link references 1 to 5 can be assigned to: internal values, such as for example speed reference "Freq.ref.man" and reference "PID-ref"; assignments made using parameters B6.06 to B6.10 respectively, for communication link references 1 to 5.
external values, for the analogue outputs, without influencing control of the ATV68 (bit 10 of the CMD control word should equal 1 so that this data can be taken into account by the ATV68); assignments made using parameters D3.00 (for AO1) and D3.04 (for AO2), taking care that parameter B6.06 to B6.10 which corresponds to the communication link used be left as "not assigned". For these "external" values, it is possible to assign the same communication link reference to both analogue outputs AO1 and AO2, but there is no particular advantage to be gained.
Use
"Internal"
Communication link references
Freq.ref.man
Freq.ref.aut
F-ref correction
Torque limit
PID-ref.
Actual PID Feedback Val.
(See parameters B6.06 to B6.10)
"External" D3.00: Analogue output 1 (AO1)
D3.04: Analogue output 2_2 (AO2)
(See configuration of analogue outputs)
The reference values are presented as standardized linear values (N2).
116
ATV68 Monitoring
Description of the ETA status word
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
5 free bits which can be configured for internal or external states
Threshold attained
Control by communication link expected
Reference reached
Alarm
Lock switching on
OFF 3 No
OFF 2 No
Trip
Operation Enable
Ready to RUN
Ready to switch on
= 1
Below the threshold
Locked
Outside reference
No alarm
Switching on enabled
OFF 3 (fast stop)
OFF 2 (lock)
Trip inv.
Operation inhibited
Not ready to run
Not ready to switch on
= 0
117
ATV68 Monitoring
Bit Value Meaning
0 1 Ready to switch on
Comment
The device status is "1 Ready to switch on".
The drive is locked.
If the “line contactor control” function has been activated, the line contactor is disabled.
0 Not ready to switch on
The device status is "0 Not ready to switch on" or "19 Lock switching on".
1 1
2
3
0
1
0
1
Ready to run The device status is "3 Ready to run ". This means that the DC Bus stage is powered up, and there are no faults. However, the drive remains locked.
If the "line contactor control" function has been activated, this control message is sent during the power capacitor charging phase: "2 Charge bus DC".
Not ready to run
Operation enabled The states are "4 Operation enabled", "5 Ramp output active", "6 Ramp release", "7 Run", "13 OFF1 active", or "14 OFF3 active".
The ATV68 is unlocked, the power bridge (IGBT) is active, the output terminals are powered up.
Operation inhibited
Trip Fault present. The device status is "20 Trip". After the fault has disappeared and been reset, the status changes to "19 Lock switching on".
Trip inv.
4
5
6
0
1
0
1
0
1
OFF2 No
OFF2 (lock)
OFF3 No
An OFF2 command has been sent.
OFF3 (Fast Stop) An OFF3 command has been sent.
Lock switching on This state is obtained by the commands OFF2, OFF3 and "Enable operation" of the CMD control word, after the fault has been reset. This status is cleared by setting the parameters for bit 0 of the CMD control word = 0.
With bit 1 of the CMD control word (OFF1), the "Lock switching ON" status no longer applies.
7
0
1
0
Switching on enabled
Alarm
No alarm
An alarm has been sent, there is no need for an external reset.
118
ATV68 Monitoring
Bit Value Meaning
8 1 Reference
Comment
Comparison of the reference value and the actual value of the frequency or the speed. The tolerance band and time delay for starting and de-energization depend on parameter D4.08.
9
0
1
Outside reference
Control by communication link expected
When the ATV68 has been configured for "bus" mode using parameter
B6.01, it asks the Modbus master to accept commands once the drive has been switched on (power or control).
If the master does not accept commands, an alarm (ETA bit 7) is sent.
0
10 1
0
Locked The ATV68 has changed to local mode (control via the programming terminal keypad or via the terminals defined in local mode).
If the master does not send a command via the communication link
(CMD bit 10 = 0), an alarm is sent.
If the drive is switched to remote mode again, the PLC should respond with a command via the communication link within 2 seconds, otherwise the drive is automatically switched back to local mode.
Threshold reached The actual value of the frequency is
≥
the threshold in D4.06
Below the threshold The actual value of the frequency is
≤
the threshold in D4.07
119
ATV68 Monitoring
Assignment of the free bits 11 to 15 of the ETA status word
Bits 11 to 15 of the ETA status word are not fixed by Profidrive, and they can be assigned to:
• internal states (conforming to the logic outputs)
• external states separate from the ATV68 functions
Use
"Internal"
"External"
Free bits of the ETA status word
Ready
Run
Trip
Ready+Run
Alarm
Generat.oper
Contactor control
Local (remote)
Motor frequency > threshold
Lift Brake
Output C1
…
(See parameters B6.26 to B6.30)
DI1
DI2
DI3
DI4
DI6_2
DI7_2
DI8_2
…
(See parameters B6.26 to B6.30)
120
ATV68 Monitoring
•
•
Assignment of actual values
Actual values can be assigned to: internal actual values, such as the frequency output “f- out (signed)”, the output current “Out.current”, etc.
(conforming to the ATV68 analogue outputs).
external actual values (commands) coming from the analogue inputs, for external use by the Modbus master, without influencing control of the ATV68 (bit 10 of the CMD control word should be set to 1 so that this data can be made available to the Modbus master by the drive).
Actual values, like communication link reference values, are presented as standardized linear values (in Hz or as a %) (N2).
Use Actual values
"Internal" Output freq. (signed)
Output freq. (unsigned)
Out.current
Torque (signed)
Torque (unsigned)
Motor power
Motor voltage
N-out sig (signed)
N-out sig (unsigned)
Internal frequ. reference
Torque limit reference
PID-ref.
PID-feedback
PID-error
DC-voltage
Fault number
Drive status
…
(See parameters B6.11 to B6.20)
"External" Analogue input AIC
Analogue input AI_2
Analogue input AIV
…
(See parameters B6.11 to B6.20)
121
Managing Communication Errors
Managing communication errors on the Modbus network
When the Modbus connection is lost, the module can no longer communicate with the Modbus master.
However, the connection to the drive remains operational and the module continues to communicate with it.
All the values of the PZD and PKW output data transmitted to the drive are reset when the Modbus time-out trips on the module. The duration of this time-out equals 10 seconds.
These resets include resetting Bit 10 of the CMD control word (W1029), and hence activation of “control by communication link disabled”.
Managing communication errors on the ATV68-module link
When the ATV68-module link is lost, the module can no longer communicate with the drive. However, the connection with the Modbus network remains operational.
• The drive trips at the end of 10 s + x s.
The type of fault or stop on timeout applied by the drive can be configured by parameter B6.03 (BUS fault).
The value of x can be adjusted by parameter B6.04 (B6.03 Time delay).
• A second module time-out trips at the end of 10 s. From then on, all the PKW and PZD input word values transmitted to the Modbus master by the module are reset:
W1 to W10 = 16#0000
• The whole time that communication is stopped, the module informs the Modbus master, via bit 12 of the module status word (W0), that the ATV68-module link is no longer active (bit 12 = 0).
Example 1
• B6.03 = Fault / B6.04 = 4.0 s
If communication between the module and the drive is interrupted for more than 14 s, the drive performs a freewheel stop and the fault relay trips, changing to the “20 – Trip” status. To be able to control the drive again, the following sequence should be sent by the control word:
- CMD = 16#x4FF = External reset, then
- CMD = 16#x47E = Basic command
Example 2
• B6.03 = Deceleration / B6.04 = 5.0 s
If communication between the module and the drive is interrupted for more than 15 s, the drive stops on a ramp. The fault relay does not trip. To be able to control the drive again, the following value should be sent by the control word:
- CMD = 16#x47E = Basic command
122
PKW Parameter-Setting Service
PKW, or configuration and adjustment process data, consist of 4 consecutive input and output words. They are used to read and write the drive parameter values.
Request PKW
Address Words
W1025
W1026
W1027
W1028
PKE
IND
PWE Hi
PWE Lo
15
Request code
AK
12 11 10
Fields
Parameter address
PNU
Reserved
High order parameter value
Low order parameter value
0
Response PKW
Address Words
W1
W2
W3
W4
PKE
IND
PWE Hi
PWE Lo
Response code
AK
15
Fields
Parameter address
PNU
12 11 10
Reserved
High order parameter value
Low order parameter value or
Error code
0
Principles for processing the PKW request/response
To perform a complete transaction, the Modbus master must first write the PKW request (W1025 to W1028), then read the PKW response words (W1 to W4) in an iterative manner, so long as the response corresponding to the PKW request is not available (comparison of the values of PKE and IND in the request and in the response).
The ATV68 retains its response values until the master formulates a new request, or until the communications change to downgraded mode.
• The master must identify the response to its request: a) by evaluating the response code b) by evaluating the parameter number (PNU) c) if necessary by evaluating the parameter index d) if necessary by evaluating the parameter value
• If there is no need to exchange information via PKW message handling, the master should use the "No command" request code.
• If the response code is 7 (error), a request code 0 (no command) must be sent to clear the error and be able to address this same parameter again.
123
PKW Parameter-Setting Service
Saving to the Flash EPROM
The modified parameters are not saved automatically in the event of loss of the electrical line supply. They are saved in the EPROM using the "PNU 971 – Record saved" parameter.
To launch this procedure, the parameter value should be at 1.
After saving, the parameter should be reset to 0.
AK Request codes (master
➞
ATV68)
Request code Meaning
0
1
2
3
6
No request
Read a parameter value
Write a parameter value (word)
Write a parameter value (double word, floating point)
Read the value of the table parameter
Response code pos.
neg.
0
1.2
1
2
4.5
7
7
7
7
7
Only descriptive elements with a maximum length of 4 bytes can be transmitted to the PKW part.
AK Response codes (master
➞
ATV68)
Response code Meaning
4
5
7
0
1
2
No response
Correct reading or writing of a parameter value (word)
Correct reading or writing of a parameter value (double word, floating point)
Correct reading of a parameter value (word table)
Correct reading of the parameter value (double word table)
Error
124
PKW Parameter-Setting Service
PWE Parameter value - error code
The PWE field contains either the parameter value or the error code.
• The following types of data are possible:
For simple variables:
For table:
N2
O2
T2
NF
V2
OS4[ ]
O2[ ]
16-bit standardized linear value
16-bit unsigned
16-bit time constant
32-bit floating point
16-bit sequence
String of 4 bytes (ASCII character table)
16-bit unsigned
Font: Characters (text) should be represented using the ISO/IEC 10367 Latin Alphabet character table no. 1
(= Windows font).
• In the event of an error response code (AK = 7), PKE Lo contains an error code.
Error code Meaning
0 Incorrect logic address
3
4
1
2
5
9
Parameter writing refused
Value outside max. and min. limit
Error in the sub-index
No table
Incorrect type of data
Descriptive data not available
101
103
104
105
106
11
13
14
17
No parameter-setting priority for parameter (1)
Impossible to read text (or text table) during cyclic network operation
Impossible to read name during cyclic network operation
Request not taken into account because drive not locked
Incorrect request code (request not supported)
Access to parameter blocked by code
Unable to adjust the parameter, value or assignment already used
Type of table
Impossible to execute the request because Macro User 2 active or parameter locked
(logic input). See B2.04
(1) This error will always be returned by the drive if the Modbus master attempts to access a parameter when parameter F6.02 has not been set to value 2 (Access mode = via RS232) from the terminal.
125
PKW Parameter-Setting Service
ASCII Code table
ISO/IEC 10 367 – Basic set GO – Additional set Latin Alphabet no. 1
hex Char.
hex Char.
hex Char.
hex Char.
hex Char.
hex Char.
Space
126
PKW Parameter-Setting Service
Example 1: Reading the mechanical power (Menu A2.04, PNU 114)
Request
PKE
IND
PWE Hi
PWE Lo
W 1025
W 1026
W 1027
W 1028
16#
16#
16#
16#
1072
0000
0000
0000
Request code 1: Read a parameter value.
PNU = 114 = 16#72
Response
PKE
IND
PWE Hi
PWE Lo
W1
W2
W3
W4
16#
16#
16#
16#
1072
0000
0000
1333 = 4915
Response code 1: Correct reading of a parameter value.
Parameter A2.04 is described on page 80:
- Type N2
- Standardization factor B3.00 (Nominal power), 400 kW in the example
Physical value = 4915/16384.0 X 400 (standardization factor, eg. motor Pn) = 120 kW.
Example 2: Reading the causes of faults (Menu A2.04, PNU 823)
PKE W 1025 16#
Request
1337
IND
PWE Hi
PWE Lo
W 1026
W 1027
W 1028
16#
16#
16#
0000
0000
0000
Request code 1: Read a parameter value.
PNU = 823 = 16#337
Response
PKE
IND
PWE Hi
PWE Lo
W1
W2
W3
W4
16#
16#
16#
16#
1337
0000
0000
0039 = 57
Response code 1: Correct reading of a parameter value.
Parameter F3.03 is described on pages 64 and 80:
- Type O2
- Value 57: 4/20 mA fault
127
PKW Parameter-Setting Service
Example 3: Writing the max. value of the analogue output (Menu D3.03,
PNU 453)
PKE W 1025 16#
Request
21C5
IND
PWE Hi
PWE Lo
W 1026
W 1027
W 1028
16#
16#
16#
0000
0000
6000
Request code 2: Write a parameter value.
PNU = 453 = 16#1C5
Value to be written: 150 %
Parameter D3.03 is described on page 88:
- Type N2
- Standardization factor 100.0
Value of PWE = 150 / 100 * 16384.0 = 24576 = 16#6000.
Response
PKE
IND
PWE Hi
PWE Lo
W1
W2
W3
W4
16#
16#
16#
16#
11C5
0000
0000
6000
Response code 1: Correct writing of a parameter value.
PWE contains the written value.
128
ATV68 Configuration
Key to tables
B3.03 Nominal freq. VICB 25.00 ...
50.00
... 300.0 Hz
MENU
Parameter name
Parameter number
Min. value
Factory settings or Adjusted value
Max. value
Parameter identification:
Modification by valid access only (1)
Modification if unlocked by access code (2)
Modifiable when stopped (drive locked) (3)
Modifiable parameter
B6. Serial Port configuration
In menu B6 "Communication parameters", the minimum configuration for starting Modbus communication is:
- B6.00 "Selection of the communication bus" at 2 "RS232/Gateway"
- B6.01 "Select remote" at:
1 "Line, Gateway" if the command comes from a PLC via Modbus
0 "Terminals" if the PLC is only monitoring the drive
Menu Name
B6.00
Select bus
0 … no bus
1 … PROFIBUS DP
2 … RS232 / Gateway (19200 bauds)
3 … Gateway (35700 bauds)
Access Default value - range
VICB No bus
Profibus DP
FIPIO / Modbus / Modbus plus
To use the Modbus module, select value 2.
B6.01
Select remote VCB Terminals
0 … Terminals terminals + bit 11 to 15 of the CMD control word if bit 10 of the
CMD control word = 1
1 … Line, Gateway control word (CMD)
Parameter B6.01 defines whether remote commands (Start, Stop) should be accepted via the terminals (logic inputs) or by using the control word (CMD) (bits 0-10) via the communication link.
B6.02
Address VCB 0 ...
0
... 126
Not used by the interface
129
ATV68 Configuration
Menu Name
B6.03
BUS fault
Access Default value - range
VICB Alarm
0 … Alarm
1 … Trip
2 … Lock
3 … Deceleration
(immediately)
(after the time set with B6.04)
(after the time set with B6.04)
(after the time set with B6.04)
This parameter defines the drive reaction to a communication fault on the bus ATV68-module link.
The effect can be delayed using parameter B6.04 (see B6.33 also).
0 … Alarm
1 … Trip: the drive performs a freewheel stop and generates a fault (the fault relay is tripped).
2 … Lock: the drive performs a freewheel stop and does not generate a fault.
3 … Deceleration: the drive stops the motor in accordance with the deceleration ramp and does not generate a fault.
For options 2 and 3: the drive restarts automatically if a run command has been enabled.
For option 1: the drive only restarts after the fault has been reset, and a "Basic status" command and a run command have been issued.
B6.04
Delay B6.03
VCB 0 ...
0.0
... 3200.0 s
This parameter sets the time delay for the reaction occurring after B6.03.
B6.05
ON after OFF1,3 VICB Not authorized
0 … not authorized
1 … authorized
This parameter defines whether another start is possible during deceleration (caused by an OFF1 or OFF3 command).
In the "not authorized" configuration, the drive is "locked" once the motor has come to a complete stop. The master should write the "Basic status" in the control word (CMD) before restarting.
130
ATV68 Configuration
Menu Name
B6.06
Main reference 1
0 … not used
1 … Freq.ref.man
2 … Freq.ref.aut
3 … Freq. Correct.
4 … Torque Limit.
5 …PID-ref.
6 … PID-feedback
Access Default value - range
VICB Not used
100% = fmax C3.01
100% = fmax C3.01
100% = fmax C3.01
100% = nom. motor torque
100% = 100%
100% = 100%
If the desired reference cannot be selected, it has already been assigned.
See D1, etc.
Main reference 1 can be used as a source for various references, as illustrated in the figure below.
The selection is made by parameter B6.06.
Reference types "Freq.ref.man", " Freq.ref.aut" and "F-ref correction" are standardized in Hz,
100% corresponding to the maximum frequency set using parameter C3.01.
The torque limit references, the PID reference and the PID feedback are standardized directly as a %.
LOC = Local
REM = Remote
LOC MP = Local motorized potentiometer
Local/Remote is used to select either:
Local: references generated by the "Local" motorized potentiometer issued by the programming terminal keypad or the terminals (loc. + speed, loc. - speed).
Remote: references issued by the communication link or the terminals (other than 1).
B6.07
Aux. reference 2
B6.08
Aux. reference 3
B6.09
Aux. reference 4
VICB
VICB
VICB
Not used
Not used
Not used
131
ATV68 Configuration
Menu Name
B6.10
Aux. reference 5
For authorized settings see B6.06.
B6.11
Actual val.1
0 … not used
1 … f- out (signed)
2 … f- out (unsigned)
3 … Out.current
4 … Torque (signed)
5 … (Torque) (unsigned)
6 … Motor power
7 … Motor voltage
8 … N-out sig (signed)
9 … N-out sig (unsigned)
10 …Int.f-ref
11 …Int. T-ref.
12 …PID-ref.
13 … PID-feedback
14 …PID-error
15 …AIV
16 …AIC
17 …AI_2
18 …AI_3
19 … DC voltage
20 …Th. State Mot.
21…Braking Resistor Thermal
22 … Fault number
23 … Drive state
Access Default value - range
VICB Not used
VCB Out.freq.sig
A3.00
A2.03
A2.01
A2.04
A4.13
C4.00
C4.01
A4.00
A4.02
A4.04
A4.06
A3.02
A2.12
A3.12
F3.02
AI.03
output not assigned
100% = high speed (C3.01)
100% = high speed (C3.01)
100% = nominal motor current (B3.01)
100% = nominal motor torque (B3.00, B3.04)
100% = nominal motor torque (B3.00, B3.04)
100% = nominal motor power (B3.00)
100% = nominal motor voltage (B3.02) V
100% = high speed in rpm (C3.01 x 60/p) (1)
100% = high speed in rpm (C3.01 x 60/p) (1)
100% = high speed (C3.01). Internal frequency reference before the ramp and before slip compensation.
100% = nominal motor torque (B3.00, B3.04)
Torque limit internal reference
100% = 100% (C4.00)
100% = 100% (C4.01)
100% = 100% (C4.02)
100% = 10 V = 4000 hex
100% = 20 mA = 4000 hex
100% = 20 mA = 4000 hex
100% = 20 mA = 4000 hex
100% = 813 V on the ATV68 400 and 500;
1200 V on ATV68 700
Thermal state M
Fault code (see programming manual)
State, alarm or limit (see programming manual)
A2.13
A2.14
24 …Position Low
24 …Position High
With this parameter, the information relating to the selected analogue value is assigned to the
AO/AI actual value 1 with adequate standardization. All the actual values can be filtered by the adjustable "actual value filter".
Note: Assignment of the actual value configures the display values of the "Save" function in the
ATV68SOFT PC software.
(1) where p = number of pairs of poles.
B6.12
Act 1 filt.time
VCB 0.00 ...
0.10
... 10.00 s
Filter on B6.11
B6.13
Aux.-act.val.2
B6.14
Act 2 filt.time
B6.15
Aux.-act.val.3
B6.16
Act 3 filt.time
B6.17
Aux.-act.val.4
VCB n-output sig
VCB 0.00 ...
0.10
... 10.00 s
VCB Out.current
VCB 0.00 ...
0.10
... 10.00 s
VCB Torque
132
ATV68 Configuration
Menu Name
B6.18
Act 4 filt.time
B6.19
Aux.-act.val.5
B6.20
Act 5 filt.time
For authorized settings see B6.11
B6.21
Bit 11 Contr.W
0 … not used
Access Default value - range
VCB 0.00 ...
0.10
... 10.00 s
VCB Power
VCB 0.00 ...
0.10
... 10.00 s
VCB Not used
1 … 13 not permitted
14 …Pre-set A
15 …Pre-set B
16 …Pre-set C
17 …Manual (Aut)
18 …Local/remote
19 …2.ramp
20 …User macro 2/1
21 …Not permitted
22 …External trip
23 …EXT-Mot.Trip
24 …Insulation fault
25 …Brake fault
26 …Not permitted
27 …EXT-T limit.
28 …PID active
29 …PID-enable
30 …Speed ctrl.act
31 …Brake open
32 …Mains ON(OFF)
33 …ON lock
34 …Force local
35 …Paramet-locked
36 …FWD (REV.)
See table of preset references
C1 = Manual reference
As a result, program with E3.02 as well
As a result, program with E2.11 as well
Parameter B6.21 assigns the digital input commands corresponding to bit 11 of the CMD control word (configured in the master). For details concerning the function of these commands, refer to the ATV68 Programming manual. See "Parameter Group D2".
B6.22
Bit 12 Contr.W
VCB Not used
B6.23
Bit 13 Contr.W
B6.24
Bit 14 Contr.W
B6.25
Bit 15 Contr.W
VCB Not used
VCB Not used
VCB Not used
For authorized settings see B6.21
In addition to F6.00
1 = Clockwise field
133
ATV68 Configuration
Menu Name
B6.26
Bit 11 Stat.-W (ETA)
0 … not used
1 … Ready
2 … Run
3 … Trip
4 … Ready+Run
5 … Alarm
6 … Generat.oper
7 … Contact ctrl
8 … Local (Remote)
9 … f > f-level
10 …Lift Brake
11 …Output C1
12 …Output C2
13 …Output C3
14 …Output C4
15 …Output L5
16 …Output L6
17 …Thyrist.-ON
18 …DI1 •
19 …DI2
20 …DI3
21 …DI4
22 …DI6_2
23 …DI7_2
24 …DI8_2
25 …DI5_3
26 …DI6_3
27 DI7_3
28 …DI8_3
29 …Manual
30 …User Macro 2
31 …EXT-T limit.
32 …PID active
33 …PID enabled
34 …Speed ctrl.act
Access Default value - range
VCB DI1
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Parameter B6.26 assigns bit 11 of the status word.
For a description of functions, see the Programming manual "Menu D4".
Note: Assignment of bits 11 to 15 of the STATUS word (ETA) configures the display values of the
"Save" function in the ATV68SOFT PC software.
B6.27
Bit 12 Stat.-W (ETA)
B6.28
Bit 13 Stat.-W (ETA)
VCB
VCB
DI2
DI3
B6.29
Bit 14 Stat.-W (ETA)
B6.30
Bit 15 Stat.-W (ETA)
VCB DI4
VCB DI6_2
For authorized settings for B6.27 to B6.30 see B6.26
134
ATV68 Configuration
D3. Configuration of analogue outputs
The PLC can directly control the drive analogue outputs AO1 and AO2 using control words PZD2 to PZD6, ie.
using communication link references 1 to 5.
Menu Name
D3.00
AO1-selection
0-14 see Programming manual
15 Bus Main reference 1
15 Bus Aux. reference 2
15 Bus Aux. reference 3
15 Bus Aux. reference 4
15 Bus Aux. reference 5
20-21 see Programming manual
D3.04
AO2_2-selection
Access Default value - range
VCB not used
—
100% = 16#4000
100% = 16#4000
100% = 16#4000
100% = 16#4000
100% = 16#4000
—
VCB not used
Note: For this operating mode, parameters B6.06 to B6.10 (depending on the communication link reference to be used) should be left on the factory setting ("Not used"), thus leaving communication link references 1 to 5 unassigned. Bit 10 of the CMD control word should be set to 1 by the master ("Control by communication link
OK") so that the module can take account of the communication link references.
135
ATV68 Configuration
D4. Configuration of logic outputs
The PLC can control the drive logic outputs directly using the free bits (bits 11 to 15) of the CMD control word.
Menu Name
D4.00
+24 dig.output
0-19 see Programming manual
20 Bus Cont.W 11.
21 Bus Cont.W 12.
22 Bus Cont.W 13.
23 Bus Cont.W 14.
24 Bus Cont.W 15.
25-32 see Programming manual
D4.01
Relay output 1
D4.02
Relay output 2_2
D4.03
Relay output 3_2
Access Default value - range
VC +24 V
—
The relay is energized if bit 11 of the CMD control word equals 1
The relay is energized if bit 12 of the CMD control word equals 1
The relay is energized if bit 13 of the CMD control word equals 1
The relay is energized if bit 14 of the CMD control word equals 1
The relay is energized if bit 15 of the CMD control word equals 1
—
VCB Ready+Run
VCB not used
VCB not used
Note: For this operating mode, parameters B6.21 to B6.25 (depending on the free bit to be used) should be left on the factory setting ("Not used"), thus leaving bits 11 to 15 of the CMD control word unassigned. Bit 10 of the CMD control word should be set to 1 by the master ("Control by communication link OK") so that the module can take account of the references assigned to the free bits.
136
ATV68 Diagnostics
B6. Diagnostics for the Serial Port
Menu Name
B6.31
Slave status
B6.32
Trans. speed
B6.33
Watchdog status
B6.34
Com. PPO Type
Access Default value - range
Read only
Read only
Read only
VCB Type 2
Parameters B6.31 to B6.34 are not significant in the case of Modbus.
B6.35
Bus CMD word Read only
Displays the control word (CMD) transmitted by the master in hexadecimal format.
B6.36
Bus main ref. 1 Read only
B6.37
Bus aux. ref. 2
B6.38
Bus aux. ref. 3
B6.39
Bus aux. ref. 4
B6.40
Bus aux. ref. 5
Read only
Read only
Read only
Read only
Parameters B6.36 to B6.40 display the references supplied by the ATV68 in hexadecimal format.
B6.41
Bus STATUS word Read only
Displays the status word (ETA) generated by the ATV68 in hexadecimal format.
B6.42
Bus actual val.1
Read only
B6.43
Bus actual val.2
B6.44
Bus actual val.3
B6.45
Bus actual val.4
B6.46
Bus actual val.5
Read only
Read only
Read only
Read only
Parameters B6.42 to B6.46 display the actual values supplied by the ATV68 in hexadecimal format.
B6.47
STATUS requested Read only
Displays the CMD control word which is valid internally, generated from CMD control word commands to the bus and from the terminals, if necessary. The position in the ATV68 status chart depends on the internal CMD control word. It is displayed in hexadecimal format.
137
ATV68 Diagnostics
B6.48
Active state Read only
This parameter indicates the internal drive status conforming to the Profibus status chart.
(This parameter is identical to parameter A3.11).
For more details, see "Cyclic control and monitoring variable" and "ATV68 status chart".
0 … Not Ready ON
1 … Rdy. switch ON
2 … Charge Bus DC
3 … Ready to run
4 … Oper. release
5 … Ramp enable
6 … Ramp release
7 … Run
8 … Flux.
9 … Rel. brake 1
10 …Crane active
11 …JOG1 active
12 …JOG1 pause
13 …OFF1 active
14 …OFF3 active
15 …Close brake
16 …Fr. DC-brake 1
17 …Fr. DC-brake 2
18 …OFF2 active
19 …Lock switching on
20 …Trip
21 …Auto tune
22 …Power test
23 … Rel. brake 2
24 … Rel. brake 3
25 …Heating motor.
26 …Trip condition 1
27 …Trip condition 2
138
ATV68 Diagnostics
Menu Name
B6.49
Param. Buffer 1
B6.50
Param. Buffer 2
B6.51
Param. Buffer 3
B6.52
Param. Buffer 4
B6.53
Param. Buffer 5
B6.54
Param. Buffer 6
B6.55
Param. Buffer 7
B6.56
Config. Buffer 1
B6.57
Config. Buffer 2
B6.58
Diag. Buffer 1
B6.59
Diag. Buffer 2
B6.60
Diag. Buffer 3
B6.61
Diag. Buffer 4
B6.62
Diag. Buffer 5
B6.63
Diag. Buffer 6
B6.64
Global Control
Access Default value - range
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Parameters B6.49 to B6.64 are not significant in the case of Modbus.
139
ATV68 Diagnostics
A4. Display reference values
Menu Name
A4.18
Bus Main Reference 1 scaled
A4.19
Bus Aux. Reference 2 scaled
A4.20
Bus Aux. Reference 3 scaled
A4.21
Bus Aux. Reference 4 scaled
A4.22
Bus Aux. Reference 5 scaled
Access Default value - range
Read only
Read only
Read only
Read only
Read only
Parameters A4.18 to A4.22 display the bus references using the standardized value.
Reference transmitted by the master: 0 to ± 200% in hexadecimal format
Scaled reference
140
ATV68 Diagnostics
Causes of faults (parameter F3.03 / PNU 823)
28
29
30
24
25
26
27
19
20
21
22
15
16
17
18
23
11
12
13
14
7
8
9
10
5
6
3
4
1
2
Fault Number
0
Fault Text
Loss of +24V
UI-Flt.1.0
UI-Flt.2.0
UI-Flt.2.1
UI-Flt.3.0
UI-Flt.3.1
UI-Flt.3.2
UI-Flt.4.0
UI-Flt.4.1
UI-Flt.4.2
AR-Flt. 3.0
AR-Flt. 3.1
UI-Flt.5.0
UI-Flt.6.0
UI-Flt.7.0
Int.Com1.0
Int.Com1.1
Int.Com1.2
Int.Com1.3
Int.Com2.0
Int.Com1.4
Com.card-Flt
Bus comm. 1
AR-Flt. 3.2
Not used
Not used
Not used
Not used
Not used
Not used
Protection disabled
46
47
48
49
42
43
44
45
38
39
40
41
Fault Number
35
36
37
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
31
32
33
34
Not used
Fault log
Overcurrent 1
Overvoltage
66
67
68
70
For all additional information on individual errors, see the Programming manual.
Fault Text
AR-Flt. 1.0
Power stage
Int.Com3.0
BU Fault
Frequency error
Overcurrent 2
Card temperature
Power supply fault
Not used
Not used
Not used
Not used
Temperature of heatsink 2
AR-Flt. 2.0
Temperature of heatsink 1
Bus comm. 2
Undervoltage 1
Undervoltage 2
Crane overload
External trip
External motor trip
Isolation Fault
4/20 mA fault
Thermistor temperature exceeded?
PTC short-circuit
Motor thermal fault
Stall prot
Mot. overspeed
Encoder fault
Braking unit trip
Thermal fault on the DC bus charging resistor
ON lock
Braking resistor overload
Process fault
Underload
141
Example of Use
Configuration of the Modbus master
Application requirement:
• The master controls a drive located at address "1" and at one of the two ends of a Modbus network with the following characteristics:
- Communication speed = 19,200 bauds
- Parity = None
• The master sends:
• The master receives:
- the CMD control word without assignment of the free bits
- the frequency reference
- the ETA status word with default assignments of the free bits
- the motor frequency
- the motor current (actual value 2)
- the motor torque (actual value 3)
W5
W6
W7
W8
W9
W10
Object
W1029
W1030
W1031
W1032
W1033
W1034
Description
CMD control word
Main reference 1: Frequency reference
Aux. reference 2: Not used
Aux. reference 3: Not used
Aux. reference 4: Not used
Aux. reference 5: Not used
ETA status word
Actual value 1: Motor frequency
Actual value 2: Motor current
Actual value 3: Motor torque
Actual value 4: Not used
Actual value 5: Not used
Configuration of the Modbus module for ATV68
The slave address should be set at "1", the communication speed at "19,200 bauds" (factory setting) and the parity at "none" (factory setting).
Address Speed Parity
Switches
1 2 3 4 5 6 7 8 1 2 3 4
Description
0 0 0 0 0 0 1 x x x x x Module address on the Modbus network = 1.
x x x x x x x 1 0 1 x x Communication speed on the Modbus RTU network = 19,200 bauds (factory setting).
x x x x x x x x x x 0 1 No parity on the Modbus network (factory setting).
142
Example of Use
ATV68 configuration
The following settings should be applied to the drive itself. To apply these settings from the drive terminal keypad, parameter F6.02 must equal 0 (Access mode = via keypad). Settings marked with a large dot ‘
•
’ do not need to be modified, as these are factory settings:
B6.00
Select bus = 02 … R232/Gateway
B6.01
Select remote = 01 … Link, Gatew.
B6.06
Main reference 1 = 02 … Freq.ref.aut
B6.07
Aux. reference 2 = 00 … not used
•
. . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
B6.10
Aux. reference 5 = 00 … not used
•
B6.11
Actual val.1
= 01 … f- out (signed) •
B6.13
Aux.-act.val.2
B6.15
Aux.-act.val.3
= 03 … Out.current
= 04 … Torque (signed)
B6.17
Aux.-act.val.4
B6.19
Aux.-act.val.5
B6.25
Bit 15 Contr.W
B6.26
Bit 11 Stat.-W
B6.27
Bit 12 Stat.-W
B6.28
Bit 13 Stat.-W
B6.29
Bit 14 Stat.-W
B6.30
Bit 15 Stat.-W
= 00 … not used
= 00 … not used
B6.21
Bit 11 Contr.W
= 00 … not used
•
. . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
= 00 … not used
•
= 18 … DI1
•
= 19 … DI2
•
= 20 … DI3
•
= 21 … DI4
•
= 22 … DI6_2
•
(19,200 bps)
Control word (CMD)
100% = fmax C3.01
—
. . .
—
100% = high speed (C3.01)
100% = nominal motor current (B3.01)
100% = nominal motor torque (B3.00, B3.04) output not assigned output not assigned
—
. . .
—
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Contact closed = "1"
Once these settings have been applied, parameter F6.02 should be set at 2 (Access mode = via RS232) so that the Modbus master can access any parameter via the PKW service.
Address
W1029
W1030
W1031
W1032
W1033
W1034
W5
W6
W7
W8
W9
W10
Drive description
Bits 0 0 to 10: CMD control word
Bit 11 to 15: Free bits (not assigned)
Main link reference = Freq.ref.aut
Aux. reference 2 = Not assigned
Aux. reference 3 = Not assigned
Aux. reference 4 = Not assigned
Aux. reference 5 = Not assigned
Bit 0 to 10: ETA status word
Bit 1 to 11: DI1 (default assignment)
Bit 1 to 12: DI2 (default assignment)
Bit 1 to 13: DI3 (default assignment)
Bit 1 to 14: DI4 (default assignment)
Bit 1 to 15: DI6_2 (default assignment)
Main actual value = f- out (signed)
Actual value 2 = Out.current
Actual value 3 = Torque (signed)
Actual value 4 = Not assigned
Actual value 5 = Not assigned
Assigned by
———
B6.21 to B6.25
B6.06
B6.07
B6.08
B6.09
B6.10
———
B6.26
B6.27
B6.28
B6.29
B6.30
B6.11
B6.13
B6.15
B6.17
B6.19
143
Example of Use
Exchanges on the bus
Master outputs
• Control PZD1 (W1029) = CMD control word: controls the drive according to the PROFIDRIVE standard
(see ATV68 Control and Monitoring section).
• Control PZD2 (W1030) = Main link reference = Freq.ref.aut as internal value: 100% = fmax C3.01, irrespective of the setting of C3.01; main link reference = C3.01, in Hz, if W1030 = 16384 = 16#4000. To determine the numerical value to be applied to the "Freq.ref.aut" reference in PZD2 (W1030), expressed in
Hz, use the following equation:
W1030 =
16384
×
Desired value (in Hz)
C3.01 (in Hz)
Example: C3.01 = 50 Hz and you wish to control the motor at 25 Hz. The value to be applied to word W1030 is given by the following equation:
W1030 =
16384
×
25
50
= 8192 = 16#2000
Master inputs
• Module status word (W0): The Modbus master monitors the value of bit 12 (Subnet Status) of word W0 to determine whether the ATV68-module link is working or not (see ATV68 Control and Monitoring section).
If W0: 12 = 1, this means that the input data located in the module memory are updated periodically. If W0:
12 = 0, the values of the input data should not be taken into account by the Modbus master, since they have not been refreshed.
- Link active if W0 = 16#1000
- Link inactive if W0 = 16#0000
• Monitoring PZD1 (W5) = ETA status word: Reads the internal drive status according to the PROFIDRIVE standard (see ATV68 Control and Monitoring section).
• Monitoring PZD2 (W6) = Main actual value = f- out (signed) as an internal value: 100% = high speed
(C3.01), irrespective of the setting of C3.01; Main actual value = C3.01, in Hz, if W6 = 16384 = 16#4000. To determine the actual value of the output frequency "f- out (signed)", expressed in Hz, as a function of the numerical value located in PZD2 (W6), use the following equation:
Actual value (in Hz) =
W6
×
C3.01 (in Hz)
16384
Example: C3.01 = 50 Hz and the read value is W6 = 16#2000 = 8192. The actual value of the output frequency
"f- out (signed)", read in word W6, is given by the following equation:
Actual value (in Hz) =
8192
×
50
16384
= 25 Hz
144
Example of Use
• Monitoring PZD3 (W7) = Actual value 2 = Out.current as an internal value: 100% = nominal motor current (B3.01), irrespective of the setting of B3.01; Out.current = B3.01, in A, if W7 = 16384 = 16#4000. To determine the actual value of the output current "Out.current", expressed in A, as a function of the numerical value read in W7, use the following equation:
Actual value (in A) =
W7
×
B3.01 (in A)
16384
Example: 110 kW drive, B3.01 = 156.3 A and the read value is W7 = 16#2000 = 8192. The actual value of the output current "Out.current", read in word W7, is given by the following equation:
Actual value (in A) =
8192
×
156.3
16384
= 78.15 A
• Monitoring PZD4 (W8) = Actual value 3 = Torque (signed) as an internal value: 100% = nominal motor current Tn; Torque (signed) = 100% if W8 = 16384 = 16#4000. To determine the actual value of the torque
"Torque (signed)", expressed as a % of Tn, as a function of the numerical value read in W8, use the following equation:
Actual value (as a % of Tn) =
W8
×
100
16384
Example: The read value is W8 = 16#2000 = 8192. The actual value of the torque "Torque (signed)", read in word W8, is given by the following equation:
Actual value (as a % of Tn) =
8192
×
100
16384
= 50% of Tn
145
List of Parameters
Voltage:
Reference:
Serial no:
Customer/Company:
Code:
Supplier/Company:
Delivery date: Commissioning date:
Parameter adjustments
Para.
No.
Description
A1 Display
A 1 03 Device mode 2
A 1 04 LED state
A2 Display Motor value
A 2 00 Speed
A 2 01 Torque
PNU Code Type D Standardization
A 1 00 Configuration/
Settings
971
A 1 01 Device mode 1 100
A 1 02 Control mode 891
VB
101
102
110
111
O2
O2
O2
O2
O2
N2
N2
---
---
---
---
---
16384.0
Motor m nom.
(B3.00/B3.04*60/2/pi)
A 2 02 Motor load
A 2 03 Motor current
112
113
A 2 04 Mech. power 114
A 2 05 Apparent power 115
A 2 06 Motor voltage 116
A 2 07 Slip frequency 117
A 2 08 Linear speed
[v]
118
N2
N2
N2
N2
N2
N2
NF
100.0
Min.
0
---
---
---
---
---
---
Device I nom (A3.06) ---
Motor P nom. (B3.00) ---
SN (B3.01*B3.02)
812.81875
(1200.0 at 690 V)
163.84
---
---
---
---
---
---
----A 2 09 Speed of rotation [n]
119 NF
A 2 10 Process scaling 120 VCB NF
A 2 11 Process scaling 121 VCB NF
A3 Display Drive value
A 3 00 Output freq.
130 N2
---
---
163.84
---
Max.
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
(5) Stop
(0) Remote
0
(1) READY
+0 rpm
+0 Nm
0%
0.0 A
+0.0 kW
0.0 kVA
3 V
0.0 Hz
+0.00 m/min
-10,000 +10,000 +1,000
-10,000 +10,000 +1,000
---
Trip
(0) Begin 0->1
+0.00 rpm
+0.00 Hz
Value
146
List of Parameters
Para.
No.
Description
A 3 01 Drive load
A 3 02 DC-voltage
A 3 03 Heatsink temperature
A 3 04 Switching frequency
133
134
A 3 05 Drive reference 802
A 3 06 Nom. drive current ‘C’
136
A 3 07 Hardware vers.
803
A 3 08 Software-type 801
A 3 09 Software vers.
800
A 3 10 Serial No.
804
A 3 11 Drive ETA status word
(ZSW)
135
A4 Display drive references
A 4 00 AIV 0..10V
140
A 4 01 AIV scaled 141
A 4 02 AIC 0(4)..20mA 142
A 4 03 AIC scaled 143
A 4 04 AI_2 0(4)..20mA 144
A 4 05 AI_2 scaled 145
A 4 06 AI_3 0(4)..20mA 146
A 4 07 AI_3 scaled 147
A 4 08 Preset reference 148
A 4 09 Local reference 149
A 4 10 Remote reference
150
A 4 11 Freq. before ramp
151
A 4 12 Freq. after ramp 152
A 4 13 Max. torque reference
153
A 4 14 Digital input X1 160
A 4 15 Digital input X2 161
A 4 16 Digital input X3 162
PNU Code Type D Standardization
131
132
N2
N2
100.0
812.81875 (1200.0 at
690 V)
0.01
Min.
---
---
--N2
O2
OS4[4]
NF
OS4[4]
OS4[2]
OS4[2]
OS4[4]
O2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
O2
O2
O2
---
---
---
---
---
---
---
---
100.0
163.84 (100.0)
100.0
163.84 (100.0)
100.0
163.84 (100.0)
100.0
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
163.84
163.84
100.0
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Max.
---
---
---
---
---
---
---
---
---
0
1
0
+0.5%
+0.25 Hz
+0.0%
+0.00 Hz
+0.0%
+0.01 Hz
+0.0%
+0.01 Hz
+0.00 Hz
+0.00 Hz
+0.01 Hz
+0.00 Hz
+0.00 Hz
200.0%
Trip
0%
604 V
+32 ° C
(0) 2.5 kHz
ATV68 iiiii
208 A
8844110.01
PSR3_A1
8782400.04/04
123456
(1)
RdyswitchON
Value
147
List of Parameters
Para.
No.
Description
A 4 17 BUS CTRL word
(STW)
A 4 18 Main reference
1
PNU Code Type D Standardization
154
155
V2
N2
---
163.84 (100.0)
A 4 19 Aux. reference 2 156
A 4 20 Aux. reference 3 157
A 4 21 Aux. reference 4 158
A 4 22 Aux. reference 5 159
N2
N2
N2
N2
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
A5 Time / kWh
A 5 00 Motor operating hours
A 5 01 Drive operating hours
810
812
811 A 5 02 kWh metre
[MWh]
A6 Display configuration
A 6 00 Select zone 1
A 6 01 Select zone 2
A 6 02 Select zone 3
NF
NF
NF
190 VCB O2
191 VCB O2
192 VCB O2
---
---
---
---
---
---
--A 6 03 Display Limits
B1 Choice of language
B 1 00 Language
Selection
193
850
VCB
VCB
O2
O2
B2 Selection of an application macro
B 2 00 Display macro
B 2 01 Store USER
Macro 1
864 O2
861 VCB O2
862 VCB O2 B 2 02 Store USER
Macro 2
B 2 03 Selection of the application macro
860 VICB O2
B 2 04 Multi configuration/ motor
863 VCB O2
B3 Motor data
B 3 00 Nominal power 10 VICB NF
B 3 01 Nominal current 11 VICB NF
B 3 02 Nominal voltage 12 VICB NF
B 3 03 Nominal frequency
13 VICB NF
---
---
---
---
---
---
---
---
---
---
0
---
---
---
---
0
0
0
0
0
0
0
0
---
---
---
---
---
Min.
---
---
---
---
---
---
Max.
---
Trip
0406 hex
+0.00 Hz
+0.00 Hz
+0.00 Hz
+0.00 Hz
+0.00 Hz
---
---
---
19
18
19
1
3
---
1
1
11
2
0.00 hr
0.67 hr
0.000 MWh
(0) output freq.
(11) Int. f-ref
(5) Motor current
(0) no display
(1) English
(0) Conveyor
(0) Begin 0->1
(0) Begin 0->1
(0) Conveyor
(0) not active
0.0
0.0
0
25
2500.0
132.0 kW
2500.0
239.0 A
1000
300
400 V
50 Hz
Value
148
List of Parameters
Para.
No.
Description PNU Code Type D Standardization
B 3 04 Nominal speed 14 VICB NF
B 3 05 Line voltage 16 VICB O2
---
B 3 06 Overmodulation 17 VICB O2
B 3 07 Motor output filter
15 VICB O2
B4 Autotuning
B 4 00 Autotuning 870 VICB O2
B 4 01 Rotor coefficient 20 VICB NF
21 VICB NF B 4 02 Rotor time
Const.
B 4 03 Stator Resist.
22 VICB NF
B 4 04 Fluxing current 23 VICB NF
B 4 05 Autotuning current
24 N2
B6 Communication parameter
B 6 00 Select bus 928 VICB O2
B 6 01 Select remote
B 6 02 Address
701 VICB O2
918 VCB O2
---
---
---
---
---
---
Inom device (A3.06)
---
---
---
Min.
0
0
0
0
0
0
0
Max.
1
1
18000
3
Trip
1488 rpm
(0) 400V; 50/
60Hz
(0) not active
(0) not used
0
0
1
0.000
4.000
(0) Begin 0->1
999999 3611
1.246 s
0.00
0.0
---
20000.0
0
15.24 mOhm
2500.0
72.7 A
--+0.0 A
B 6 03 BUS fault
B 6 04 Delay B6.03
703
704
885
709
886
711 VCB T2
887 VCB O2
713
888
715
VCB
VCB
VCB
VCB
VCB
VCB
VCB
VCB
O2
T2
B 6 05 ON after OFF1,3 705 VICB O2
B 6 06 Main reference 1 880 VICB O2
B 6 07 Aux. reference 2 881 VICB O2
B 6 08 Aux. reference 3 882 VICB O2
B 6 09 Aux. reference 4 883 VICB O2
B 6 10 Aux. reference 5 884 VICB O2
B 6 11 Actual val.1
B 6 12 Act 1 filt.time
B 6 13 Aux.-act.val.2
B 6 14 Act 2 filt.time
B 6 15 Aux.-act.val.3
B 6 16 Act 3 filt.time
B 6 17 Aux.-act.val.4
B 6 18 Act 4 filt.time
O2
T2
O2
T2
O2
T2
---
0.1
---
---
---
---
---
---
---
0.005
---
0.005
---
0.005
---
0.005
0
0.0
0
0
0
0
0
0
0
0.00
0
0.00
0
0.00
0
0.00
6
6
6
6
6
19
10.00
19
10.00
19
2
1
126
(0) no bus
(0) terminals
Not used by the interface (0)
3 (0) Alarm
3200.0
0.0 s
1 (0) not authorized
(0) not used
(0) not used
(0) not used
(0) not used
(0) not used
(1) out.freq.sig
0.10 s
(8) n-output sig
0.10 s
(3) Output current
10.00
19
10.00
0.10 s
(4) Torque
0.10 s
Value
149
List of Parameters
Para.
No.
Description
B 6 19 Aux.-act.val.5
B 6 20 Act 5 filt.time
PNU Code Type D Standardization
889 VCB O2
717 VCB T2
B 6 21 Bit 11 Contr.W
933 VCB O2
B 6 22 Bit 12 Contr.W
934 VCB O2
---
0.005
---
---
B 6 23 Bit 13 Contr.W
935 VCB O2
B 6 24 Bit 14 Contr.W
936 VCB O2
B 6 25 Bit 15 Contr.W
937 VCB O2
B 6 26 Bit 11 Stat.-W 939 VCB O2
---
---
---
---
B 6 27 Bit 12 Stat.-W
B 6 28 Bit 13 Stat.-W
B 6 29 Bit 14 Stat.-W
B 6 30 Bit 15 Stat.-W
B 6 31 Slave status
940 VCB O2
941 VCB O2
942 VCB O2
943 VCB O2
728 O2
---
---
---
---
---
B 6 32 Trans. speed
B 6 33 Watchdog status
963
B 6 34 Com. PPO Type 731 VCB O2
B 6 35 Contr.W on BUS 967
B 6 36 Bus main ref. 1
B 6 37 Bus aux. ref. 2
B 6 38 Bus aux. ref. 3
B 6 39 Bus aux. ref. 4
B 6 40 Bus aux. ref. 5
B 6 41 Bus STATUS word
B 6 42 Bus actual val.1
B 6 43 Bus actual val.2
B 6 44 Bus actual val.3
B 6 45 Bus actual val.4
730
733
734
735
736
737
968
739
740
741
742
O2
O2
V2
O2
O2
O2
O2
O2
V2
O2
O2
O2
O2
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Max.
34
34
34
34
---
36
36
36
34
19
10.00
36
36
Min.
0
0
0
0
0
0
0
0.00
0
0
0
0
---
---
---
0
---
---
3
Trip
(6) Power
0.10 s
(0) not used
(0) not used
(0) not used
(0) not used
(0) not used
(18) DI1
(19) DI2
(20) DI3
(21) DI4
(22) DI6_2
Not used by the interface (3)
ATV68 missing
Not used by the interface (0) 12
MBaud
Not used by the interface (0) not connected
Not used by the interface (1)
Type 2
0000 hex
0000 hex
0000 hex
0000 hex
0000 hex
0000 hex
0031 hex
Value
0000 hex
0000 hex
0000 hex
0000 hex
150
List of Parameters
Para.
No.
Description
B 6 48 Active state
PNU Code Type D Standardization
B 6 46 Bus actual val.5
743
B 6 47 STATUS requested
760
761
O2
V2
O2
---
---
---
B 6 49 Param. Buffer 1 744 O2 ---
B 6 50 Param. Buffer 2 745
B 6 51 Param. Buffer 3 746
B 6 52 Param. Buffer 4 747
B 6 53 Param. Buffer 5 748
B 6 54 Param. Buffer 6 749
B 6 55 Param. Buffer 7 750
B 6 56 Config. Buffer 1 751
B 6 57 Config. Buffer 2 752
B 6 58 Diag. Buffer 1
B 6 59 Diag. Buffer 2
B 6 60 Diag. Buffer 3
B 6 61 Diag. Buffer 4
B 6 62 Diag. Buffer 5
B 6 63 Diag. Buffer 6
757
758
B 6 64 Global Control 759
C1 General functions
C 1 00 Inc.start Tor.
307 VCB
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
300 VCB N2
C 1 01 Inc.steady Tor.
301 VCB N2
C 1 02 Stop mode
C 1 03 Braking mode
C 1 04 Preset.ref.
C 1 05 Preset.ref. 1
C 1 06 Preset.ref. 2
C 1 07 Preset.ref. 3
C 1 08 Preset.ref. 4
C 1 09 Preset.ref. 5
753
754
755
756
302
316
303 VICB O2
304 VCB N2
305 VCB N2
306 VCB N2
308
VCB
VICB O2
VCB
O2
N2
N2
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
100.0
163.84
---
---
---
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Min.
---
---
---
---
Max.
---
---
Trip
0000 hex
0406 hex
(1)
Rdy.switchON
Not used by the interface (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Same (0000 hex)
Value
0
0
0
5
30
45
2
4
1%
10 Hz
(1) Decel. ramp
(0) no brake oper.
0 5 (0) not used
-327.68 +327.67
+0.00 Hz
-327.68 +327.67
+0.00 Hz
-327.68 +327.67
+0.00 Hz
-327.68 +327.67
+0.00 Hz
-327.68 +327.67
+0.00 Hz
151
List of Parameters
Para.
No.
Description
C 1 10 Preset.ref. 6
C 1 11 Preset.ref. 7
PNU Code Type D Standardization
309 VCB N2
310 VCB N2
C 1 12 Preset.ref. 8 311 VCB N2
C 1 13 Jog-Frequency 312 VCB N2
163.84 (100.0)
163.84 (100.0)
163.84 (100.0)
163.84
--C 1 14 Economy mode 313 VCB O2
C2 Ramps
C 2 00 Accel. ramp 1
C 2 01 Decel. ramp 1
320
321
VCB
VCB
T2
T2
C 2 02 Accel. ramp 2
C 2 03 Decel. ramp 2
C 2 04 S-ramp
C 2 05 S-ramp mode
322
323
324
325
VCB
VCB
VCB
VCB
T2
T2
O2
O2
0.1
0.1
0.1
0.1
---
---
C3 Speed range
C 3 00 Min. frequency 330 VCB N2
C 3 01 Max. frequency 331 VCB N2
C 3 02 Dir. Enable 332 VICB O2
163.84
163.84
---
C4 PID configuration
C 4 04 PID enable 344 VICB O2
C 4 05 Prop. gain (kp) 345 VCB N2
C 4 06 Integ.time (Tn) 346 VCB T2
C 4 07 Deriv.time (Tv) 347 VCB T2
C 4 08 Ref. acc. ramp 348 VCB T2
C 4 09 Ref. dec. ramp 349 VCB T2
C 4 10 Out. scaling -
C 4 11 Out. scaling +
351
352
VCB
VCB
N2
N2
C6 Special functions
C 6 00 Contactor cont.
380 VICB O2
C 6 01 Crane-function 381 VICB O2
C 6 02 Release freq.
382 VCB N2
C 6 03 Release time
C 6 04 Engage freq.
C 6 05 Engage time
386
387
388
VCB
VCB
VCB
T2
N2
T2
---
1600.0
0.01
0.01
0.1
0.1
163.84
163.84
---
---
163.84
0.005
163.84
0.005
0
0
0
0
0.0
0.0
0.00
300.00
0.00 Hz
25.00
300.00
50.00 Hz
0 2 (2) FW/RV active
0
0.0
0.00
0.00
0.0
0.0
0.0
0.0
Min.
Max.
Trip
-327.68 +327.67
+0.00 Hz
-327.68 +327.67
+0.00 Hz
-327.68 +327.67
+0.00 Hz
-10.00
+10.00
+0.00 Hz
0 4 (0) not active
Value
3200.0
3200.0
3200.0
3200.0
3
1
5.0 s
5.0 s
20.1 s
20.1 s
(0) no S ramp
(0) Begin + End
0.0
0.0
3200.0
0.0 s
3200.0
0.0 s
-300.00 +300.00
0.00 Hz
-300.00 +300.00
0.00 Hz
0.0
0.0
1 (0) no
3199.9
0.0%
320.00
0.00 s
320.00
0.00 s
1
2
20.0
160.0
20.0
160.0
(0) not active
(0) not active
1.7 Hz
0.3 s
1.5 Hz
0.3 s
152
List of Parameters
Para.
No.
Description PNU Code Type D Standardization
C 6 06 DC braking time 383 VCB T2
C 6 07 DC braking curr 384 VCB N2
0.005
100.0
C 6 08 Restart delay
C 6 09 Hoist mode
C 6 10 Max (n)error.
D1 Analogue inputs
389 VCB T2
390 VCB O2
385 VCB N2
0.005
---
16384.0
D 1 00 AIV-selection
D 1 01 AIV-value 0%
400 VICB O2
401 VCB N2
D 1 02 AIV-value 100% 402 VCB N2
D 1 03 AIV-filter time 403 VCB T2
D 1 04 AIC-selection
D 1 05 AIC-level
404 VICB O2
405 VCB O2
D 1 06 AIC-value 0% 406 VCB N2
D 1 07 AIC-value 100% 407 VCB N2
---
163.84 (100.0)
163.84 (100.0)
0.005
---
---
163.84 (100.0)
163.84 (100.0)
0.005
---
---
163.84 (100.0)
163.84 (100.0)
D 1 08 AIC-filter time 408 VCB T2
D 1 09 AI_2-selection 409 VICB O2
D 1 10 AI_2-level 410 VCB O2
D 1 11 AI_2-value 0% 411 VCB N2
D 1 12 AI_2-value
100%
412 VCB N2
D 1 13 AI_2-filter time 413 VCB T2
D 1 14 AI_3-selection 414 VICB O2
D 1 15 AI_3-level 415 VCB O2
D 1 16 AI_3-value 0% 416 VCB N2
D 1 17 AI_3-value
100%
417 VCB N2
D 1 18 AI_3-filter time 418 VCB T2
D2 Logic inputs
D 2 00 DI1-selection
D 2 01 DI2-selection
441
442
VICB O2
VICB O2
D 2 02 DI3-selection
D 2 03 DI4-selection
443 VICB O2
444 VICB O2
0.005
---
---
163.84 (100.0)
163.84 (100.0)
0.005
---
---
---
---
D 2 04 DI6_2-selection 445 VICB O2
D 2 05 DI7_2-selection 446 VICB O2
---
---
0
0
0
0
0
0
Min.
0.0
0
0.0
0
0
Max.
160.0
150
10.0
1
300
Trip
0.3 s
100%
0.7 s
(0) no
5
0 6 (0) not used
-327.68 +327.67
+0.01 Hz
-327.68 +327.67
+50.01 Hz
0.00
10.00
0.05 s
0
0
6
1
(2) Freq.ref.aut
(1) 4-20mA
-327.68 +327.67
+0.00 Hz
-327.68 +327.67
+50.00 Hz
0.00
0
10.00
6
0.05 s
(0) not used
0 1 (0) 0-20mA
-327.68 +327.67
+0.01 Hz
-327.68 +327.67
+50.01 Hz
0.00
0
10.00
6
0.05 s
(0) not used
0 1 (0) 0-20mA
-327.68 +327.67
+0.01 Hz
-327.68 +327.67
+50.01 Hz
0.00
10.00
0.05 s
35
35
35
35
35
35
(1) Begin FWD
(2) Begin REV
(19) 2 nd
ramp
(26) EXT reinitial.
(0) not used
(0) not used
Value
153
List of Parameters
Para.
No.
Description PNU Code Type D Standardization
D 2 06 DI8_2-selection 447 VICB O2
D 2 07 DI5_3-selection 448 VICB O2
---
---
D 2 08 DI6_3-selection
D 2 09 DI7_3-selection
D 2 10 DI8_3-selection
D3 Analogue outputs
D 3 00 AO1-selection
449
465
466
VICB O2
VICB O2
VICB O2
215 VCB O2
---
---
---
---
D 3 01 AO1_level
D 3 02 AO1-min. value
451
452
D 3 03 AO1-max. value 453
D 3 04 AO2_2selection
D 3 05 A02_2-level
D 3 06 AO2_2min.value
D 3 07 AO2_2max.value
455
456
457
VCB
VCB
VCB
VCB
VCB
VCB
O2
N2
N2
216 VCB O2
O2
N2
N2
D 3 08 AO2_3selection
D 3 09 AO2_3-level
D 3 10 AO2_3min.value
217
459
460
VCB
VCB
VCB
O2
O2
N2
D 3 11 AO2_3max.value
461 VCB N2
D4 Logic outputs
D 4 00 +24 dig.output
200 VCB O2
D 4 01 Output relay 1 201 VCB O2
D 4 02 Output relay 2_2 202 VCB O2
D 4 03 Output relay 3_2 203 VCB O2
D 4 04 Output relay 2_3 204 VCB O2
D 4 05 Output relay 3_3 205 VCB O2
D 4 06 f-Level ON
D 4 07 f-Level OFF
476 VCB N2
477 VCB N2
D 4 08 Hyst. f =f-ref
D5 Encoder configuration
478 VCB N2
570 VICB O2 D 5 00 Encoder/
Slipcom
D 5 01 Dyn.
SlipCompens
581 VCB O2
---
100.0
100.0
---
0
-200
-200
0
--0
100.0 -200
100.0
---
---
100.0
100.0
---
---
---
---
---
---
163.84
163.84
163.84
---
---
0
0
0
0
0
0
0
0.00
0.00
0.1
Min.
0
0
0
0
0
0
0
-200
0
0
-200
-200
Max.
35
35
35
35
35
21
2
2
1
+200
+200
21
1
+200
+200
21
1
+200
+200
Trip
(0) not used
(0) not used
(0) not used
(0) not used
(0) not used
(2) out.freq.sig mssg
(1) 4-20mA
+0%
+100%
(0) not used
(1) 4-20mA
+0%
+100%
(0) not used
(1) 4-20mA
+0%
+100%
31
31
31
31
31
31
(25) ON (+24V)
(4) Ready +
Run
(0) not used
(0) not used
(0) not used
(0) not used
300.00
5.01 Hz
300.00
2.01 Hz
10.0
0.5 Hz
(0) no encoder
(0) low
Value
154
List of Parameters
Para.
No.
Description
D 5 02 Speed ctrl.act
D 5 03 Pulse/rotation
D 5 04 Speed ctrl. Kp
D 5 05 Speed ctrl. Tn
PNU Code Type D Standardization
571 VICB O2
572 VICB N2
573
574
VCB
VCB
N2
T2
D 5 06 Speed ctrl.Stat
575 VCB N2
D 5 07 ActVal.PT1 time 576 VCB T2
---
16384.0
1638.4
0.005
1638.4
0.005
D 5 08 ActVal.DT1 time 577 VCB T2
D 5 09 SetVal.PT1 time 578 VCB T2
D 5 10 Ref-Val.offer.D
579 VCB N2
D 5 11 R-Val.offer.PT1
580 VCB T2
0.005
0.005
1638.4
0.005
D6 Electronic potentiometer
D 6 00 Loc.MP select.
480 VICB O2
D 6 01 Loc.MP min. val. 481 VCB N2
D 6 02 Loc.MP max. val.
482 VCB N2
D 6 03 Loc.MP acc.time 483 VCB T2
D 6 04 Loc.MP dec.time
484 VCB T2
D 6 05 Loc.ref.storage
485 VCB O2
D 6 06 Rem.MP select.
486 VICB O2
487 VCB N2 D 6 07 Rem.MP min.val.
D 6 08 Rem.MP max.val.
488 VCB N2
D 6 09 Rem.MP acc.time
D 6 10 Rem.MP dec.time
489 VCB T2
490 VCB T2
---
163.84 (100.0)
163.84 (100.0)
0.1
0.1
---
---
163.84 (100.0)
163.84 (100.0)
0.1
0.1
D 6 11 Rem.MP control 492 VCB O2
D 6 12 Rem.ref.storage 491 VCB O2
E1 Drive overload
E 1 00 Curr. max.val
500 VCB N2
E 1 01 Torque max.val. 501 VCB N2
E2 Motor protection
E 2 00 Thermistor input 522 VCB O2
E 2 01 Thermist.protec
511 VCB O2
E 2 02 I max at 0 Hz 512 VCB N2
E 2 03 I max at f nom.
513 VCB N2
---
---
100.0
100.0
---
---
100.0
100.0
0
0
Min.
Max.
Trip
0.0
0.00
0.00
0.00
0 2 (0) not active
-10000 +10000 +1024
0.0
0.00
200.0
10.00
0.0
0.00 s
0.0
0.00
20.0
10.00
1.00
10.00
10.0
1.00
0.0%
0.00 s
0.00 s
0.00 s
0.0
0.00 s
Value
0 1 (0) Ref. freq.
+0.00
+327.67
+0.00 Hz
+0.00
+327.67
+50.00 Hz
0.0
0.0
3200.0
10.0 s
3200.0
10.0 s
0
0
1
5
(0) not active
(0) not used
-327.68 +327.67
+0.01 Hz
-327.68 +327.67
+50.01 Hz
0.0
0.0
10
10
0
0
0
30
3200.0
3200.0
1
1
150
200
3
1
150
150
10.0 s
10.0 s
(1) terminals
(0) not active
150%
200%
(0) not active
(0) trip
50%
100%
155
List of Parameters
Para.
No.
Description PNU Code Type D Standardization
E 2 04 Therm.f-limit 514 VCB N2
E 2 05 Motor-tme const 515 VCB T2
163.84
0.1067 (6.4s/60)
E 2 06 Stalling time
E 2 07 Stalling frequ.
E 2 08 Stalling curr.
E 2 09 n. Prot.
516
517
518
519
VCB
VCB
VCB
VCB
T2
N2
N2
O2
0.1
163.84
100.0
---
E 2 10 N max motor
E 2 11 EXT-mot.trip
E 2 12 M Delay f.
E3 Fault configuration
E 3 00 Autorestart 530 VCB O2
E 3 01 Loss of 4-20mA 531 VCB O2
E 3 02 External trip
E 3 03 Delay f.
536
537
VCB
VCB
O2
T2
E 3 04 Insulation Fault
E 3 05 Insul. Delay f.
E 3 06 Trip of ext. BU
520
523
524
538
539
525
VCB
VCB
VCB
VCB
VCB
VCB
N2
O2
T2
O2
T2
O2
16384.0
---
0.005
---
---
---
0.005
---
0.005
---
E 3 07 Brake delay f.
E 3 08 Undervoltage
E 3 09 Undervoltge delay
E 3 10 Local reset
E4 Control configuration
E 4 00 Loc/Rem ref.
526 VCB T2
534 VCB O2
544 VCB T2
535 VCB O2
540 VICB O2
0.005
---
0.005
---
---
E 4 01 Operate-Mode
E 4 02 Loc/Rem-switch 543 VICB O2
E 4 03 Ctrl.mode local 545 VICB O2
E 4 04 Local STOP
541 VICB O2
542 VCB O2
E5 Skip frequency
E 5 00 Skip frequency 550 VCB N2
E 5 01 Hysteresis
E6 Switching frequency
551 VCB N2
---
---
---
---
163.84
163.84
0
0
0
0.0
Min.
0
0
200
0
0.0
0
0
0
0
Max.
300
3200
160
20
150
2
18000
6
160.0
Trip
30 Hz
5 min
60 s
5 Hz
80%
(1) trip
3200 rpm
(0) not active
1.0 s
Value
0
0.0
0
0
0
0
0
0.0
0
0.0
0
0
5.00
0.00
1
3
1
1
1
6
160.0
6
160.0
6
160.0
2
20.0
1
2
2
300.00
4.00
(0) not active
(0) not active
(0) not active
0.0 s
(0) not active
10.0 s
(2)
N.O.rdy+run
5.0 s
(0) no trip
2.0 s
(1) active
(0) Local/ remote
(0) Local/ remote
(0) keypad
(0) keypad
(0) Loc. feedback only
5.00 Hz
0.00 Hz
156
List of Parameters
Para.
No.
Description PNU Code Type D Standardization
E 6 00 Min.pulse freq.
560 VCB O2
E 6 01 Max.switch.freq
561 VCB O2
---
---
F1 Contextual help on a fault
F 1 00 Test power part 871 VICB O2
F 1 01 Test-cont.part
F 1 02 DC Bus
Overvoltage
F 1 03 DC Bus
Undervoltage
872 VICB O2
602 O2
603 O2
---
---
---
---
F 1 04 Overcurrent
F 1 05 External trip
F 1 06 4mA trip
F 1 07 Motor Temp.
(Thermistor)>>
F 1 08 PTC shortcircuit
604
605
606
607
608
O2
O2
O2
O2
O2
---
---
---
---
---
O2 --F 1 09 External motor fault
F 1 10 Motor thermal fault
609
610
F 1 11 Shaft stall 611
F 1 12 Insulation fault 623
F 1 13 Braking unit trip 627
F 1 14 Overspeed 612
F 1 15 Encoder fault
F 1 16 Heatsink overheating
624
613
F 1 17 T° C. card>>
F 1 18 Power stage
614
615
616 F 1 19 Fault on daughter board
F 1 20 Internal fault
F 1 21 Fault on control card
617
618
F 1 22 Crane overload 619
F 1 23 Bus comm. 1 620
F 1 24 Bus comm. 2 621
F 1 25 Communication option fault
622
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
O2
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Min.
0
0
Max.
2 (1)
2 (1)
Trip
(0) 2.5 kHz
(0) 2.5 kHz
Value
3
1
3
3
3
1
1
4
2
2
3
2
1
3
2
2
3
1
2
2
2
0
2
3
2
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) Begin 0->1
(0) Begin 0->1
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
(0) text
157
List of Parameters
Para.
No.
Description PNU Code Type D Standardization
F 1 26 T° fault on the
DC bus charging resistor
629 O2 ---
F 1 27 ON lock
F 1 28 Loss of 24V
F 1 29 Fault log
F2 Factory settings
628
625
626
O2
O2
O2
---
---
---
630 VICB O2
631 VICB O2
---
---
F 2 00 Ret.fact.appli.
F 2 01 Ret.fact.motor
F3 Fault log
F 3 00 Fault code
F 3 01 Review
F 3 02 Trip number
F 3 03 Fault
952
821
822
823
VB
N2
O2
N2
O2
16384.0
---
16384.0
---
F 3 04 Operat.hours
FI A
F 3 05 F-out
F 3 06 Speed
F 3 07 Motor current
F 3 08 DC-voltage
824
825
835
826
827
NF
N2
N2
N2
N2
---
0
0
---
163.84
16384.0
---
---
Inom device (A3.06) ---
812.81875
(1200.0 at 690 V)
---
0.01
163.84
---
---
---
---
---
---
-----
0
0
0
---
0
---
---
Min.
0
---
---
---
---
1
1
4
2
2
Max.
2
---
---
---
---
---
---
---
---
---
---
---
---
---
15
---
---
Trip
(0) text
(0) text
(0) text
(0) text
(0) Begin 0->1
(0) Begin 0->1
5
(0) last event
4
(58) Mot.temp
>
380.09 hr
+42.00 Hz
+1258 rpm
88 A
615 V
+58 ° C
+42.00 Hz
(0) remote
(7) run
047F hex
(1) n=n ref.
0000 hex
Value
---
0.005
100.0
---
100.0
0
0.0
19
160.0
(0) 0.0%
0.1 s
-200.0
+200.0
+0.0%
0 3 (0) E1 > E2
+0.0
+100.0
+5.0%
158
List of Parameters
Para.
No.
Description
F 4 05 C1 time-funct
F 4 06 C1 time-set
F 4 07 C1 selection
F 4 08 C2 signal E1
F 4 09 C2 filter f. E1
F 4 10 C2 Reference
PNU Code Type D Standardization
685 VCB O2
686 VCB T2
687
688
VICB O2
VCB O2
689 VCB T2
690 VCB N2
F 4 11 C2 compFunction 691 VCB O2
F 4 12 C2 comHyst/Band 692 VCB N2
---
0.1
---
---
0.005
100.0
---
100.0
Min.
0
0.0
0
0
0.0
3
33
19
(0) delay ON
3200.0
0.0 s
(0) not used
(0) 0.0%
-200.0
+200.0
+0.0%
0
+0.0
Max.
160.0
3
+100.0
Trip
0.1 s
(0) E1 > E2
+5.0%
F 4 13 C2 time-funct
F 4 14 C2 time-set
F 4 15 C2 selection
F 4 16 C3 signal E1
693
694
695
640
VCB
VCB
O2
T2
VICB O2
VCB O2
---
0.1
---
---
0
0.0
0
0
3
33
19
(0) delay ON
3200.0
0.0 s
(0) not used
(0) 0.0%
F 4 17 C3 filter f. E1
F 4 18 C3 signal E2
F 4 19 C3 filter f. E2
F 4 20 C3 Reference
662 VCB T2
641 VCB O2
667 VCB T2
642 VCB N2
F 4 21 C3 compFunction 643 VCB O2
F 4 22 C3 comHyst/Band 644 VCB N2
F 4 23 C3 signal D1
F 4 24 C3 signal D2
210
211
VCB
VCB
O2
O2
0.005
---
0.005
100.0
---
100.0
---
---
0
0
0.0
0
0.0
160.0
0.1 s
-200.0
+200.0
+0.0%
0
+0.0
160.0
6
3
+100.0
45
45
0.1 s
(0) reference
(0) E1 > E2
+5.0%
(0) logical ZERO
(0) logical ZERO
F 4 25 C3 log.'a'funct
F 4 26 C3 log.'b'funct
F 4 27 C3 time-funct
F 4 28 C3 time-set
F 4 29 C3 selection
F 4 30 C4 signal E1
F 4 31 C4 filter f. E1
F 4 32 C4 signal E2
647 VCB O2
648 VCB O2
649 VCB O2
650 VCB T2
668 VICB O2
651 VCB O2
669 VCB T2
652 VCB O2
F 4 33 C4 filter f. E2
F 4 34 C4 Reference
676 VCB T2
653 VCB N2
F 4 35 C4 compFunction 654 VCB O2
F 4 36 C4 comHyst/Band 655 VCB N2
F 4 37 C4 signal D1
F 4 38 C4 signal D2
F 4 39 C4 log.'a'funct
212
213
658
VCB
VCB
VCB
O2
O2
O2
---
---
---
0.1
---
---
0.005
---
0.005
100.0
---
100.0
---
---
---
0
0
0
0
0
0
0
0
0.0
0.0
0
7
7
33
19
160.0
6
(1) OR
(1) OR
3 (0) Delay ON
3200.0
0.0 s
(0) not used
(0) 0.0%
0.1 s
(0) reference
0.0
160.0
0.1 s
-200.0
+200.0
+0.0%
0
0.0
3
100.0
(0) E2 > E2
5.0%
45
45
7
(0) logical ZERO
(0) logical ZERO
(1) OR
Value
159
List of Parameters
Para.
No.
F6 Code
Description
F 4 40 C4 log.'b'funct
F 4 41 C4 time-funct
F 4 42 C4 time-set
F 4 43 C4 selection
F 4 44 L5 signal D1
F 4 45 L5 signal D2
F 4 46 L5 logic funct.
F 4 47 L5 time-funct
F 4 48 L5 time-set
F 4 49 L5 selection
F 4 50 L6 signal D1
F 4 51 L6 signal D2
F 4 52 L6 logic funct.
F 4 53 L6 time-funct
F 4 54 L6 time-set
F 4 55 L6 selection
F 5 03 SensB5kHz-Off.
F 5 05 SensB10kHz-Off.
PNU Code Type D Standardization
659 VCB O2
660 VCB O2
661
677
587
588
591
592
595
596
673
675
VCB
VCB
VCB
VCB
VCB
VCB
VCB
VCB
T2
VICB O2
585 VCB O2
586 VCB O2
O2
O2
589 VCB T2
590 VICB O2
O2
O2
593 VCB O2
594 VCB O2
T2
VICB O2
F5
F 5 02 SensA5kHz-Off.
672 VCB N2
N2
F 5 04 SensA10kHz-Off.
674 VCB N2
N2
---
---
0.1
---
---
---
---
---
0.1
---
---
---
---
---
0.1
---
16384.0
16384.0
16384.0
16384.0
Min.
0
0
0.0
0
0
0
0
0
0.0
0
0
0
0
0
0.0
0
-100
-1000
-1000
Max.
7
3
3200.0
0.0 s
33 (0) not used
45
45
7
3
3200.0
0.0 s
33
45
45
7
3
3200.0
33
+1000
-1000 +1000
+1000
+1000
Trip
(1) OR
(0) Delay ON
(0) logical ZERO
(0) logical ZERO
(1) OR
(0) Delay ON
(0) not used
(0) logical ZERO
(0) logical ZERO
(1) OR
(0) Delay ON
0.0 s
(0) not used
+0
+0
+0
+0
Value
F 6 00 Code
F 6 01 Code value
855
856
VB
VB
F 6 02 Paramet.-Access 927 V
N2
N2
O2
16384.0
16384.0
---
0
0
0
9999
9999
2
0
0
(0) keypad
Caution: The following parameters only have a PNU number.
Reference and feedback parameters
Communication link reference
915
Communication link value
916
Freq.ref.man
Freq.ref.aut
F-ref correction
790
791
792
O2[6]
O2[6]
N2
N2
N2
-----
----f_max(C3.01)/100.0
--f_max(C3.01)/100.0
--f_max(C3.01)/100.0
---
---
---
---
---
---
[...]
[...]
...
...
...
160
List of Parameters
Reference and feedback parameters
Torque limit ref.
793
Output freq.
Motor current
794
795
Motor voltage
Speed
796
797
Ref. val before ramp
Ref. val after ramp
798
799
PC setup software: ATV68SOFT
ATV68SOFT LOCAL 890
N2
N2
N2
N2
N2
N2
N2 100.0
V O2
100.0
f_max(C3.01)/100.0
Inom-Motor (B3.01)
Unom-Motor (B3.02) f_max(C3.01)/100.0
*60.0/ppz f_max(C3.01)/100.0
---
---
---
ATV68SOFT CMD
ATV68SOFT local frequency reference
892
893
V2
N2
--f_max(C3.01)/100
ATV68SOFT local torque reference
PZD watchdog
PKW watchdog
894
895
896
Parameters for memory loss
PNU fault log
Factory Anomaly
820
970
List of existing and modified parameters
N2
VCB T2
VCB T2
O2[116]
O2
100.0
0.005
0.005
---
---
PNU existing Part 1 980
PNU existing Part 2 981
PNU existing Part 3 982
PNU existing Part 4 983
PNU existing Part 5 984
PNU existing Part 6 985
PNU modified Part 1 990
PNU modified Part 2 991
PNU modified Part 3 992
PNU modified Part 4 993
PNU modified Part 5 994
PNU modified Part 6 995
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
O2[116]
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0
---
---
---
1.00
1.00
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
...
2
---
---
---
160.00
10.0 s
160.00
10.0 s
---
---
---
---
---
---
---
---
---
---
---
---
[...]
[...]
[...]
[...]
[...]
[...]
[...]
[...]
[...]
[...]
[...]
[...]
...
...
...
...
...
...
Not active
...
...
...
161
VVDED301064
29820
W9 1623787 01 11 A01
2002-07
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement