Model:
PEFY-P12NMAU-E2
Job Name:
Schedule Reference:
Date:
Specifications
Capacity*
Cooling………………………………………….…12,000 Btu/h
Heating………………………………………….…13,500 Btu/h
General FEATURES
• Dual set point functionality
• Multiple fan speed settings
• Auto fan mode
• 9-7/8” (250mm) high for low ceiling heights
• Built-in condensate lift; lifts to 27-9/16" (700 mm)
• Ducted fan coil supporting multiple configurations for flexible
installation
Power
Power Source……………..........208 / 230V, 1-phase, 60Hz
Power Consumption
Cooling………………………………………….………0.09 kW
Heating………………………………………….………0.07 kW
Current
Cooling……................................................……………0.66 A
Heating……................................................……………0.55 A
Minimum Circuit Ampacity (MCA)……...…….…..……...1.20 A
Maximum Overcurrent Protection (MOCP) Fuse.......…..15 A
External Finish……………...….….….Galvanized-steel Sheet
External Dimensions
Inches……………………….9-7/8 H x 27-9/16 W x 28-7/8 D
mm…………………………………….250 H x 700 W x 732 D
Net Weight…………..…...……………..................49 lbs. / 22 kg
Coil Type………………...........................................….Cross Fin
(Aluminum Plate Fin and Copper Tube)
OPTIONS
□□ External Heater Adapter………………CN24RELAY-KIT-CM3
□□ Filter Box (Includes 2” MERV 13 filter)………………FBM2-1
Fan
Type x Quantity…………………………………Sirocco Fan x 1
Airflow Rate (Low-Mid-High)………………… 265 - 318 - 371 CFM
External Static Pressure…..0.14 - 0.20 - 0.28 - 0.40 - 0.60"WG
Motor Type…………………..…………..………………DC Motor
Air Filter..…………………………….Polypropylene Honeycomb
Refrigerant Piping Dimensions
Liquid (High Pressure)……............1/4" / 6.35 mm (Brazed)
Gas (Low Pressure)………………..1/2" / 12.7 mm (Brazed)
Drainpipe Dimension……............……...…O.D. 1-1/4" / 32 mm
Sound Pressure Levels
Low-Mid-High….…………….……………28 - 30 - 34 dB(A)
* Cooling / Heating capacity indicated at the maximum value at
operation under the following conditions:
Cooling | Indoor: 80° F (27° C) DB / 67° F (19° C) WB,
Cooling | Indoor: Outdoor 95° F (35° C) DB
Heating | Indoor: 70° F (21° C) DB,
Heating | Outdoor 47° F (8° C) DB / 43° F (6° C) WB
Notes:
Specifications are subject to change without notice.
© 2012 Mitsubishi Electric & Electronics USA, Inc.
23 (15/16)
(DUCT)
15 (5/8)
Model
40 (1-5/8)
1
2
100(3-15/16)X(E-1)=F
30 (1-3/16)
100(3-15/16)
D(Duct)
20 (13/16)
Refrigerant piping
brazing connection (gas)
2×2-Ø2.9(1/8)
Refrigerant piping
brazing connection (liquid)
32 (1-5/16)
57 (2-1/4)
10 (7/16)
Air
outlet
732 (28-7/8)
40 (1-5/8)
40 (1-5/8)
67
D
660
(26)
860
(33-7/8)
1060
(41-3/4)
1360
(53-9/16)
1560
(61-7/16)
135
41 (1-5/8)
°
16
14
11
9
7
E
F
600
(23-5/8)
800
(31-1/2)
1000
(39-3/8)
1300
(51-3/16)
1500
(59-1/16)
G
H
800
658
(25-15/16) (31-1/2)
858
1000
(33-13/16) (39-3/8)
1058
1200
(41-11/16) (47-1/4)
1358
1500
(53-1/2) (59-1/16)
1700
1558
(61-3/8) (66-15/16)
J
44
(1-3/4)
54
(2-3/16)
49
(1-15/16)
54
(2-3/16)
54
(2-3/16)
18 (3/4)
210
(8-5/16)
K
L
150
300
(5-15/16) (11-13/16)
260
(10-1/4)
330
(13)
320
(12-5/8)
370
(14-5/8)
Suspension bolt hole
4-14x30(9/16X1-3/16) Slot
Control box
Terminal block(Transmission)
Terminal block(Power source)
Drain pipe(O.D.Ø32(1-1/4))(Spontaneous draining)
Air
inlet
(5-3/8)
3-Ø2.9(1/8) mounting hole
Ventilation air intake Ø100(3-15/16)
knock out hole
Note 5
C
153 (6-1/16)
120
Drain pipe
(O.D.Ø32(1-1/4))
Drain pump
700 (27-9/16)
(2-11/16)
356 (1/16)
C
800
(31-1/2)
1000
(39-3/8)
1200
(47-1/4)
1500
(59-1/16)
1700
(66-15/16)
136
(5-3/8)
10 (7/16)
238 (9-3/8)
(Suspension bolt pitch)
643 (25-3/8)
Ø125
(4-15/16)
120°
A
217 (8-9/16)
2xE-Ø2.9(1/8)
378 (14-15/16)
B(Suspension bolt pitch)
23 (15/16)
Drain pipe(O.D. Ø32(1-1/4))
(Emergency draining)
58 (2-5/16)
73 (2-7/8)
122 (4-13/16)
100 (3-15/16)
G
21 (7/8)
200(7-7/8)
B
A
754
PEFY-P06,08,12NMAU-E2 700
(27-9/16) (29-11/16)
900
954
PEFY-P15,P18NMAU-E2
(35-7/16) (37-9/16)
1154
PEFY-P24,27,30NMAU-E2 1100
(43-5/16) (45-7/16)
1454
1400
PEFY-P36,48NMAU-E2
(55-1/8) (57-1/4)
1600
1654
PEFY-P54NMAU-E2
(63)
(65-1/8)
178 (7-1/16)
5
5
4
4
M
780
(30-3/4)
990
(39)
1280
(50-7/16)
1480
(58-5/16)
N
6(1/4)
P- 2.9(1/8)
Air filter
12
12
10
10
10
P
J
1
Note2
2)
50(
More than 10(7/16)
More than 20(13/16)
FORM# PEFY-P12NMAU-E2 - 201207
Ceiling surface
Ø15.88
(5/8)
Ø12.7
(1/2)
Gas pipe
K
0
50(
2)
/8~1 250~30
1-13 0
/16)
(9-7
Ø9.52
(3/8)
Ø6.35
(1/4)
Unit:mm(in.)
2 Liquid pipe
450
(17
-3/4
)
450
Access door
Mo
)
-3/4
(17
K
Drain hose (I.D. 32(1-1/4))
<accessory>
(11-13/16)
Less than 300
(B)
(A)
Kx(M-1)=N
L
65 -100
(2-9/16 -7/16)
(Actual length)
H
)
-5/8
(30
Access door
J
300
an /16)
re th (11-13
777
(27-9/16)
Less than 700
Specifications are subject to change without notice.
© 2012 Mitsubishi Electric & Electronics USA, Inc.
11(7/16)
Note
33 (1-5/16)
Space required for service and maintenance.
Provide an access door for maintenance at the bottom.
250 (9-7/8)
(A)
(B)
112 112
(4-7/16) (4-7/16)
Model:
PEFY-P12NMAU-E2 – DIMENSIONS
1 Use M10 suspension bolts. (not supplied)
2 Provide an access door for maintenance at the bottom.
3 The dimensions in the table are those of the PEFY-P24, 27, 30, 36, 48, 54NMAU-E2 models, which have 2
fans. The PEFY-P06, 08, 12, 15, 18NMAU-E2 model have 1 fan.
4 To connect an intake duct, uninstall the air filter on the unit, and install a field supplied air filter on the intake
duct on the intake side.
5 If using a ventilation air connection, air temperature must be at neutral conditions.
3400 Lawrenceville Suwanee Rd
Suwanee, GA 30024
Tele: 678-376-2900 • Fax: 800-889-9904
Toll Free: 800-433-4822 (#4)
www.mitsubishipro.com
Specifications are subject to change without notice.
100 (3-15/16)