R615DC1016 Series
CCTV Rack Mount DC Power Supplies
Models Include:
R615DC1016
- 6-15VDC @ 10A.
- Sixteen (16) Fuse Protected Outputs
R615DC1016CB
- 6-15VDC @ 10A.
- Sixteen (16) PTC Protected Outputs
Installation Guide
Rev. 050106
More than just power.
TM
Installing Company: _______________ Service Rep. Name: __________________________________
Address: _____________________________________________ Phone #: __________________
Overview:
Altronix R615DC1016 Series Rack Mount CCTV Power Supplies provide 6-15VDC distributed via sixteen (16) fuse or PTC protected outputs for powering CCTV cameras, heaters, and other video accessories.
Sixteen (16) Output Rack Mount Configuration Reference Chart:
Altronix
Model Number
R615DC1016
R615DC1016CB
Total
Output
Current
Output
Voltage
Number of Outputs
10A 6-15VDC 16
PTC
Protected
Outputs
(autoresettable)
–
P
Fuse
Protected
Outputs
P
–
Output
Current
(max per output)
3.5A
2.5A
115VAC
50/60Hz
Input
Current
1.9A
Input:
• 115VAC, 50/60Hz, 1.9A.
Specifications:
Output:
• Sixteen (16) fuse or PTC protected outputs.
• 6-15VDC @ 10A total output current.
(0.625A per device, 3.5A max.)
• Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Features:
• Sixteen (16) power LEDs.
• Illuminated master power disconnect
circuit breaker with manual reset.
• 3-wire grounded line cord.
• Removable terminal blocks with locking
screw flange.
• Spare fuses provided.
Electrical:
• System AC input VA requirement: 218.5VA.
Rack Dimensions
(H x W x D approximate)
:
• 2U rack mount chassis for use in standard
EIA 19” rack.
3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm).
Installation Instructions:
1. Unit is factory set at 12VDC. To adjust the output voltage remove the bottom cover to access trimpot on the power supply board (Fig. 1b, pg. 3) .
2. Mount unit in the desired rack location (Space unit at least 3” from any video monitors).
3. Set power switch on the back of the unit to the OFF position (Fig. 1e, pg. 3).
4. Plug power cord into a grounded 115VAC, 50/60Hz receptacle ( Fig. 1d, pg. 3) .
5. Set power switch to the ON (RESET) position and measure output voltage before connecting devices
( Fig. 1e, pg. 3) . This helps avoiding potential damage.
6. Set power switch on the back of the unit to the OFF position (Fig. 1e, pg. 3).
7. Connect devices to the removable terminal blocks marked [1P & 1N through 16P & 16N] (Fig. 1c, pg. 3) .
When wiring is completed on terminal blocks, they can be locked down by tightening screw flanges.
All terminals with common suffix (P) “1P, 2P...” are the same polarity (positive).
All terminals with common suffix (N) “1N, 2N...” are the same polarity (negative).
8. Upon completion of the wiring set power switch on the back of the unit to the ON (RESET) position
(Fig. 1e, pg. 3) .
9. Green power LEDs on faceplate will illuminate when AC power is present. When an output is in a trouble condition (blown fuse or tripped PTC), the corresponding LED will not be illuminated (Fig. 1, pg. 3) .
a. Blown fuse (R615DC1016) - Set power switch on the back of the unit to the OFF position ( Fig. 1e, pg. 3).
Remove front faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA (Altronix model # Fuse1).
b. Tripped PTC (R615DC1016CB) - To reset PTC set power switch on back of unit to the OFF position.
After approximately 30 secs. set power switch to the ON (RESET) position ( Fig. 1e, pg. 3) .
10. Power switch with built-in circuit breaker:
OFF position - Switch not illuminated. Outputs not powered.
RESET (ON) position - Switch illuminated. Outputs powered.
Circuit breaker tripped - Switch not illuminated. Power LEDs on faceplate are not illuminated.
Outputs not powered.
To reset circuit breaker set power switch to the ON (RESET) position ( Fig. 1e, pg. 3) .
- 2 - R615DC1016 Series Installation Guide
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to the National
Electrical Code and all local codes.
CAUTION: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
Fig. 1
Fig. 1a
Used on PTC
Models
Power
LEDs
Power
LEDs
Power
LEDs
Power
LEDs
(Green Wire
Earth GND)
PTC1
+ AC -- + DC --
Power Supply
Board
ALTRONIX CORP.
BKLYN, NY 11220
MADE IN U.S.A.
Trimpot
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
XFMR XFMR
Fig. 1b
Trimpot
Fig. 1c
Removable Terminal
Block
Fig. 1d
Strain Relief
Line Cord
Fig. 1e
Power Switch
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
R615DC1016 Series Installation Guide
CAUTION: To reduce the risk of electric shock do not open enclosure.
There are no user serviceable parts inside.
Refer servicing to qualified service personnel.
- 3 -
Rack Mechanical Drawing and Dimensions:
3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm)
19.125” (486mm)
17.5” (444.5mm)
Front View
0.65” (16.5mm)
2.52”
(64mm)
RESET
1.5”
(38mm)
OFF
Bottom View
1.0” (25.4mm)
Rear View
16
N P
15
N P
14 13
N P N P
12
N P
11
N P
10 9
N P N P
8
N P
7
N P
6 5
N P N P
4
N P
3
N P
2 1
N P N P
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––