advertisement
▼
Scroll to page 2
of 16
3227484 Rev. F AUGUST 2012 RNH SERIES HIGH TEMPERATURE REFRIGERATED DRYERS OPERATOR MANUAL RNH20 RNH50 RNH125 RNH25 RNH75 RNH35 RNH100 GENERAL SAFETY INFORMATION 1. Pressurized devices This equipment is a pressure containing device. • Do not exceed maximum operating pressure as shown on equipment serial number tag. • Make certain equipment is depressurized before servicing. 2. Electrical This equipment requires electricity to operate. • Install equipment in compliance with national and local electrical codes. • Standard equipment is supplied with NEMA 1 electrical enclosures and is not intended for installation in hazardous environments. • Disconnect power supply to equipment when performing any electrical service work. 3. Breathing air • Air treated by this equipment may not be suitable for breathing without further purification. Refer to OSHA standard 1910.134 for the requirements for breathing quality air. 2 1.0 INSTALLATION 1.1 Location 2. Location in the compressed air system A. Air compressor intake - Locate air compressor so that contaminants potentially harmful to the dryer are not drawn into the air system. A. B. Free air flow - Do not block either side of the cabinet. Observe minimum installation clearances as shown. 1) For maximum capacity, install unit in air system at highest pressure possible (e.g. before pressure reducing valves) 36" wall 6" Maximum working pressure - 250 psig, 17.6 kgf/cm2. Do not exceed unit’s Maximum Working Pressure. 2) For maximum capacity, install unit at coolest compressed air temperature possible. Maximum inlet compressed air temperature: 180°F, 82°C. If inlet air exceeds this temperature, precool the air by extending the piping between the compressor and the dryer. 12" B. Air Outlet - Connect air outlet to downstream air lines. 24" C. By-pass piping - If servicing the unit without interrupting the air supply is desired, piping should include inlet and outlet isolation valves and an air by-pass valve. 1.2 Mounting Dryer is suitable for floor or shelf mounting. D. Condensate drain - It is advisable to connect drain outlet to the condensate drainage system. 1.3 Piping connections A. Air Inlet - Connect compressed air line from air compressor to air inlet using strainer supplied. 1. Install strainer (included in shipping carton) prior to dryer inlet using pipe nipple supplied or other piping as required. NOTE: Drain discharge is at system pressure. Drain line should be anchored to prevent whipping. 1.4 Electrical connections A. Dryer is designed to operate on power supply (voltage) listed on serial number tag located on the back of the dryer. B. Dryer is supplied with an electrical cord. Install in receptacle of proper voltage. NOTE: Observe flow direction arrows on strainer. NOTE: Install strainer where it is easily accessible for cleaning. NOTE: Use vibration dampener, if vibration exists in air line at inlet to dryer. NOTE: Models 50 and 75 (115v only) - Install plug in receptacle rated for 20 amps. Units are supplied with 20 amp plug. Plug NOTE: Refrigeration system is designed to run continuously and should NOT be wired to cycle on/off with the air compressor. Ambient Air Filter Serial Number Tag Control Panel O Serial Number Tag I Air Inlet Connection Separator and Integral Filter Drain Mechanism Strainer (shipped separately) Electrical Connection Pipe Nipple Drain Connection Air Outlet Connection Left Side Front Right Side Back 3 2.0 OPERATION D. Maximum flow capacity NOTE: Installations above 6000 feet, 1825 meters Unit is adjusted to operate in altitudes up to 6000 feet, 1825 meters. If unit is installed in an altitude above this, and has not been preset at the factory for this altitude, contact Manufacturer’s Service Department. 1. For dryers without an aftercooler installed upstream. Flow capacity in scfm (m3/min) @ 180°F, 82°C inlet temperature, 160°F, 71°C inlet pressure dew point, 95°F, 35°C ambient temperature, 50°F, 10°C outlet pressure dew point, and less than 5 psi, 0.35 kgf/cm2 pressure drop. 2.1 Start-up 60 HZ Start refrigeration system by pushing the on/off switch to the ON position (depress rocker switch on side marked “I”). NOTE: The fault light may illuminate when unit is energized. Light should go out approximately 5 minutes after start-up. If light remains lit after 30 minutes or illuminates after going out, refer to Troubleshooting Guide. On/Off Switch O Inlet Pressure 175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0) psig (kgf/cm2) 20 23 (0.65) 22 (0.62) 20 (0.57) 18 (0.51) 25 29 (0.82) 27 (0.76) 25 (0.71) 23 (0.65) 35 41 (1.16) 38 (1.08) 35 (0.99) 32 (0.91) Model 50 58 (1.64) 54 (1.53) 50 (1.42) 45 (1.27) 75 87 (2.46) 81 (2.29) 75 (2.12) 68 (1.93) 100 116 (3.29) 108 (3.06) 100 (2.83) 91 (2.58) 125 145 (4.12) 135 (3.82) 125 (3.54) 114 (3.23) 50 HZ Fault Light I Control Panel 2.2 Operating check points Check the following on a periodic basis: A. Rocker switch is in the ON position. B. Amber fault light is out. C. Condensate is being regularly discharged. 2.3 Minimum/maximum operating conditions A. Minimum/Maximum air pressure: 20/250 psig, 1.4/17.6 kgf/cm2 B. Maximum inlet air temperature: 180°F, 82°C C. Minimum/Maximum ambient temperature: 40/110°F, 4/43°C Inlet Pressure 175 (12.3) 150 (10.6) 125 (8.8) psig (kgf/cm2) 20 20 (0.57) 18 (0.51) 17 (0.48) 25 24 (0.68) 23 (0.65) 21 (0.59) 35 31 (0.88) 29 (0.82) 27 (0.76) Model 50 58 (1.64) 54 (1.53) 50 (1.42) 75 71 (2.01) 66 (1.87) 61 (1.73) 100 97 (2.75) 90 (2.55) 83 (2.35) 125 121 (3.43) 112 (3.17) 104 (2.95) 100 (7.0) 15 (0.42) 19 (0.54) 24 (0.68) 45 (1.27) 55 (1.56) 76 (2.15) 95 (2.69) 2. For dryers with an aftercooler installed upstream Flow capacity in scfm (m3/min) @ 100°F, 38°C inlet temperature, 100°F, 38°C inlet pressure dew point, 100°F, 38°C ambient temperature, 50°F, 10°C outlet pressure dew point, and less than 10 psi, 0.7 kgf/cm2 pressure drop. 60 HZ Inlet Pressure psig (kgf/cm2) 20 25 35 Model 50 75 100 125 175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0) 32 (0.91) 30 (0.85) 28 (0.79) 25 (0.71) 40 (1.13) 37 (1.05) 34 (0.96) 31 (0.88) 55 (1.56) 51 (1.44) 47 (1.33) 43 (1.22) 78 (2.21) 73 (2.07) 67 (1.90) 61 (1.73) 118 (3.34) 110 (3.12) 102 (2.89) 92 (2.61) 157 (4.45) 146 (4.14) 136 (3.85) 123 (3.48) 197 (5.58) 183 (5.18) 170 (4.82) 155 (4.39) 50 HZ Inlet Pressure 175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0) psig (kgf/cm2) 20 27 (0.76) 25 (0.71) 23 (0.65) 21 (0.59) 25 33 (0.93) 31 (0.88) 29 (0.82) 26 (0.74) 35 43 (1.22) 40 (1.13) 37 (1.05) 33 (0.93) Model 50 78 (2.21) 73 (2.07) 67 (1.90) 61 (1.73) 75 96 (2.72) 90 (2.55) 83 (2.35) 75 (2.12) 100 131 (3.71) 122 (3.46) 113 (3.20) 102 (2.89) 125 164 (4.65) 152 (4.31) 142 (4.02) 129 (3.65) 4 3.0 MAINTENANCE DRYER IS A PRESSURE CONTAINING DEVICE. DEPRESSURIZE BEFORE SERVICING. 3.1 Ambient air filter - Clean accumulated dust and dirt from ambient air filter monthly or more often if air flow across the condenser is impeded. 3.3 Replace separator/filter element yearly or more often if pressure drop across the dryer is excessive. A. Shut-off compressed air supply to the dryer and depressurize. A. Remove top panel. B. Remove top panel. B. Remove ambient air filter by sliding upwards. C. Remove two screws holding side panel and remove side panel by sliding upwards. D. Disconnect drain tube from bulkhead fitting in cabinet base. To remove, press the plastic collar in, toward the fitting, while pulling the tube out of the fitting. C. E. Remove bowl - push bowl up, turn bowl 1/8th turn to your left, and pull straight down. F. Clean filter bowl. G. Replace element. 1. Replacing complete element Wash with soap and water and allow to dry before reinstalling. NOTE: Do not use solvents to clean ambient air filter. D. Reinstall filter and top panel. 3.2 Inlet strainer - clean inlet strainer monthly or more often if rapid clogging occurs. A. Shut-off compressed air supply to the strainer and depressurize. B. Remove screen and clean or replace. C. Reinstall. a) Pull off old element and discard. b) Make certain O-ring inside top of replacement element is in place and push element onto filter head. Screen 2. Replacing sleeve only a) Pull element straight down to remove. b) Remove bolt and bottom cap and remove disposable filter sleeve. c) Clean separator core with soap and water if necessary d) Slide new filter sleeve over separator core and replace bottom cap and hand tighten bolt. e) Make certain O-ring inside top of element is in place and push element onto filter head. 5 H. After making sure that O-ring and wave spring inside top of bowl are in place, reassemble bowl to head. 3.4 Automatic condensate drain • Check daily to be sure automatic drain is discharging. NOTE: Make certain O-ring is generously lubricated NOTE: Wave spring ends should be pointed down to prevent the wave spring from interfering with reassembly. I. Reconnect drain tube to bulkhead fitting by pushing tube into fitting until it locks in position. J. Reinstall side and top panels. K. Repressurize dryer and resume operation. • Replace drain mechanism yearly. A. Shut-off compressed air supply to the dryer and depressurize. B. Remove top panel. C. Remove two screws holding side panel then remove side panel by sliding upwards. D. Disconnect drain tube from bulkhead fitting in cabinet base. To remove, press the plastic collar in, toward the fitting, while pulling the tube out of the fitting. Element o-ring Bowl o-ring E. Remove bowl - push bowl up, turn 1/8th turn to your left, and pull bowl straight down. F. Remove drain tube fitting from bottom of bowl. G. Remove old drain mechanism by turning knurled fitting to the right (clockwise) and remove. Separator Element Wave Spring Drain Mechanism Tube Hose Barb H. Install new drain mechanism. If necessary, use a wire or pencil to guide the new mechanism into place. I. Reassemble drain tube fitting to bowl. J. After making sure that large O-ring in filter head is in place, reassemble bowl to head. K. Reconnect drain tube to bulkhead fitting by pushing tube into fitting until it locks in position. L. Reinstall top and side panels. M. Repressurize dryer and resume operation. 6 TROUBLESHOOTING GUIDE SYMPTOM A) Water downstream of dryer POSSIBLE CAUSE(S) 1. Residual free moisture remaining in downstream pipelines 2. Air by-pass system is open 3. Inlet and Outlet connections are reversed 4. Temperatures surrounding air lines downstream of dryer have dropped below dryers dew point rating. 5. Excessive free moisture (bulk liquid) at dryer inlet 6. Condensate not being automatically drained Drain mechanism is clogged or inoperative. Drain line is restricted or frozen. 7. Dryer overloaded resulting in elevated dew point. 8. Refrigeration system not functioning properly resulting in elevated dew point. B) High pressure drop across dryer 1. 2. 3. 4. Inlet air strainer clogged Excessive air flow Separator filter clogged. Freezing of moisture in evaporator because of refrigeration system improperly functioning. C) Fault Alarm 1. Dryer overloaded resulting in high air outlet temperature. 2. Refrigeration system not functioning properly resulting in high air outlet temperature. 3. Unit functioning normally but thermostatic switch is malfunctioning or not securely mounted. CORRECTIVE ACTION Blow out system with dry air Check valve positions Check for correct connection Insulate or heat trace air lines exposed to low ambients or dry air to lower dew point Install separator ahead of dryer Replace drain mechanism if inoperative Open drain line Check inlet air temperature and pressure, flow rate (compressor capacity) and ambient air temperature See D below Clean inlet air strainer Check flow rate Replace filter sleeve See D below See A 7 See D below Contact qualified refrigeration repairman or manufacturer’s service department D) Refrigeration system not functioning properly 1. When dryer on/off switch in on or "I" position a. b. c. d. Power failure Line disconnect switch open Blown fuses, open breaker Faulty wiring, loose terminals 2. Refrigerant compressor cycles on and off a. High or low ambient conditions b. Ambient air filter clogged c. Condenser fins clogged d. Fan motor or fan control switch malfunction e. Refrigerant leak f. Low voltage Check power to unit Close disconnect switch Check for continuity Have electrician check electrical connections Check minimum/maximum temperature ranges Clean ambient air filter Clean condenser Replace fan motor or fan control switch Contact qualified refrigeration repairman or manufacturer's service department Check wiring 7 SPECIFICATIONS - Models 20 thru 75 Description 20 25 Model 35 50 75 20 / 17 0.57 / 0.48 25 / 21 0.71 / 0.59 35 / 27 0.99 / 0.76 50 / 50 1.42 / 1.42 75 / 61 2.12 / 1.7 4.5 / 4.5 (0.32 / 0.32) 3.8 / 2.2 (0.27 / 0.15) Operating Conditions Rated Capacity @125 psig, 8.8 kgf/cm2* scfm m3/min 60 / 50 Hz 60 / 50 Hz Maximum Working Pressure 250 psig (17.6 kgf/cm2) Maximum Inlet Temperature 180°F (82°C) Min/Max. Ambient Temperature Pressure Drop @ rated capacity 40-110°F (4-43°C) psi (kgf/cm2) 60 / 50 Hz 60 / 50 Hz 4.5 / 2.9 (0.32 / 0.20) 3.3 / 2.4 (0.23 / 0.17) 4.7 / 2.9 (0.33 / 0.20) Refrigeration System Data Compressor Type Hermetic, Rotary, Permanent Split Capacitor BTU/HR - Refrigeration Only @ ASRE-T Conditions 60 / 50 Hz 8720 / 7043 Outlet Air Temperature (nominal @ rated conditions) 155°F (68°C) Refrigerant Type Refrigerant Charge R-407C oz (grams) 60 / 50 Hz See Dryer Serial Tag Suction Pressure Setting 67 psig (4.7 kgf/cm2) Factory Test (design) Pressure high side/low side 330/178 psig (23.2/12.5 kgf/cm2) Condenser Fan Switch Setting (in-out) Air Flow Across Condenser 12500 / 9970 cfm m3/min 240-180 psig (16.9-12.7 kgf/cm2) 60 / 50 Hz 60 / 50 Hz 280 / 235 (7.9 / 6.7) 620 /515 (17.6 / 14.6) Electrical Data Unit VAC/phase/Hz 115/1/60 115/1/60 Minimum/maximum volts 98-127 Full Load AmpS (FLA) 8.7 12.6 Branch Circuit Fuse Size (amps) 15 20 Compressor Volts/phase/Hz 115/1/60 Rated Load amps (RLA) 7.5 Locked Rotor amps (LRA) 44.0 67.0 Watts (input) 853 1220 Overload (External) Thermal and Current (Auto Reset) Condenser fan motor Volts/phase/Watts (output) Full Load Amps (FLA) Unit VAC/phase/Hz 11.0 115/1/25 115/1/35 1.2 1.6 220-240/1/50 220-240/1/50 Minimum/maximum volts Full Load Amps (FLA) 198-264 3.4 6.0 Branch Circuit Fuse Size (amps) 15 Compressor Volts/phase/Hz 220-240/1/50 Rated Load amps (RLA) 2.8 5.1 Locked Rotor amps (LRA) 18.6 28.0 Watts (input) 690 Overload (External) Condenser fan motor Volts/phase/Watts (output) Full Load Amps (FLA) 990 Thermal and Current (Auto Reset) 220-240/1/18.3 220-240/1/25.6 0.6 0.8 * Capacity @ 180°F, 82°C inlet temperature, 160°F, 71°C inlet pressure dew point, 95°F, 35°C ambient temperature, 50°F, 10°C outlet pressure dew point, and less than 5 psi, 0.35 kgf/cm2 pressure drop. 8 SPECIFICATIONS - Models 100 and 125 Model Description 100 125 100 / 83 2.83 / 2.35 125 / 104 3.54 / 2.95 Operating Conditions Rated Capacity @125 psig, 8.8 kgf/cm2* scfm m3/min 60 / 50 Hz 60 / 50 Hz Maximum Working Pressure 250 psig (17.6 kgf/cm2) Maximum Inlet Temperature 180°F (82°C) Min/Max. Ambient Temperature Pressure Drop @ rated capacity 40-110°F (4-43°C) psi (kgf/cm2) 60 / 50 Hz 60 / 50 Hz 3.5 / 2.6 (0.25 / 0.18) 4.6 / 3.1 (0.32 / 0.22) Refrigeration System Data Compressor Type Hermetic, Rotary, Permanent Split Capacitor BTU/HR - Refrigeration Only @ ASRE-T Conditions 60 / 50 Hz Outlet Air Temperature (nominal @ rated conditions) 155°F (68°C) Refrigerant Type Refrigerant Charge R-407C oz (grams) 60 / 50 Hz Suction Pressure Setting See Dryer Serial Tag 67 psig (4.7 kgf/cm2) Factory Test (design) Pressure high side/low side 330/178 psig (23.2/12.5 kgf/cm2) Condenser Fan Switch Setting (in-out) Air Flow Across Condenser 25140 / 20110 cfm m3/min 240-180 psig (16.9-12.7 kgf/cm2) 60 / 50 Hz 60 / 50 Hz 830 / 690 (23.5 / 19.5) Electrical Data Unit VAC/phase/Hz 208-230/1/60 230/1/60 Minimum/maximum volts 187-253 Full Load AmpS (FLA) 12.2 Branch Circuit Fuse Size (amps) 20 Compressor Volts/phase/Hz 208-230/1/60 Rated Load amps (RLA) 11.3 Locked Rotor amps (LRA) 71.0 Watts (input) 2530 Overload (Internal) Thermal and Current (Auto Reset) Condenser fan motor Volts/phase/Watts (output) 230/1/60 Full Load Amps (FLA) Unit VAC/phase/Hz Minimum/maximum volts Full Load Amps (FLA) Branch Circuit Fuse Size (amps) Compressor Volts/phase/Hz Rated Load amps (RLA) 0.85 220/1/50 220/1/50 207-242 14.1 20 200-220/1/50 13.2 Locked Rotor amps (LRA) 71.0 Watts (input) 2212 Overload (Internal) Condenser fan motor Volts/phase/Watts (output) Full Load Amps (FLA) Thermal and Current (Auto Reset) 230/1/50 0.85 * Capacity @ 180°F, 82°C inlet temperature, 160°F, 71°C inlet pressure dew point, 95°F, 35°C ambient temperature, 50°F, 10°C outlet pressure dew point, and less than 5 psi, 0.35 kgf/cm2 pressure drop. 9 ELECTRICAL SCHEMATICS Models 50 and 75 Models 20, 25, and 35 LINE SW 2 4 3 1 14 3 2 5 1 OLT C RC 6 S 4 M G 3 HTS 7 3 FPS 8 REFRIGERANT COMPRESSOR 4 R LT A FM 4 HIGH TEMPERATURE 4 CONDENSER FAN MOTOR WIRING SCHEMATIC Models 100 and 125 LEGEND LINE SW 2 4 3 1 5 C S RC 6 4 M 4 R G 3 HTS 7 3 FPS 8 LT A FM REFRIGERANT COMPRESSOR 4 HIGH TEMPERATURE 4 CONDENSER FAN MOTOR WIRING SCHEMATIC SW OLT M RC HTS LT FPS FM TB CT - On/Off Switch Thermal Overload Compressor Motor Run Capacitor High Temperature Switch Fault Light Fan Pressure Switch Fan Motor Terminal Block Contactor w/115V Coil Models 50 and 75 Models 20, 25, 35, 100, and 125 FM SW FM HTS LT SW OLT HTS LT OLT Front of Dryer (Outside) M RC TB Right Side of Dryer (Inside) COMPONENT LOCATIONS 10 FPS FPS M Front of Dryer (Outside) RC CT Right Side of Dryer (Inside) COMPONENT LOCATIONS DIMENSIONS AND WEIGHTS Models 20, 25, 35 257 mm Model Weight 20 79 lbs (36 kg) 25 80 lbs (36 kg) 35 81 lbs (37 kg) 6 mm 5.1/16 " 128 mm 718 mm 317 mm 1.9/16 " 40 mm 1" 25 mm 21 mm 5 mm 105 mm 217 mm 257 mm 327 mm 216 mm 168 mm 1.1/2" 38 mm 105 mm 287 mm 41 mm 130 mm 11 DIMENSIONS AND WEIGHTS Models 50 and 75 425 mm Model Weight 50 150 lbs (68 kg) 75 155 lbs (70 kg) 6 mm 933 mm 8 7/16" 213 mm 419 mm 1.1/2" 38 mm 25 mm 15 1/4" 387 mm 5 mm 117 mm 429 mm 232 mm 160 mm 39 mm 59 mm 129 mm 12 175 mm 21 mm DIMENSIONS AND WEIGHTS Models 100 and 125 Model Weight 100 187 lbs (85 kg) 125 189 lbs (86 kg) 1" 1" 13 PARTS LIST PARTS DESCRIPTION 20 25 35 50 75 CE9-16 CE9-16 CE9-16 CE9-20 CE9-24 Separator *Separator/Filter Cartridge Filter Sleeve CS9-16 CS9-16 CS9-16 CS9-20 CS9-24 *Drain Mechanism 3152270 3152270 3152270 3152270 3152270 Bowl 3240333 3240333 3240333 3223457 3241108 *O-ring Bowl 3154585 3154585 3154585 3162913 3162913 Strainer, inlet 4009634 4009634 4009634 4009635 4009635 *Screen, strainer 3230672 3230672 3230672 3230673 3230673 Inlet (Compressed Air) Strainer Electrical 3230775 3230775 3230775 3230775 3230775 Light, Fault (amber) 115/1/60 3227423 3227423 3227423 3227423 3227423 Light, Fault (amber) Switch on/off 220-240/1/50 3227424 3227424 3227424 3227424 3227424 Cord Set 115/1/60 3221571 3221571 3221571 3221572 3221572 Cord Set 220-240/1/50 3221422 3221422 3221422 3221422 3221422 Capacitor, run 115/1/60 3220878 3220878 3220878 3220878 3220878 Capacitor, run 220-240/1/50 3220872 3220872 3220872 3220878 3220878 3240331 3240331 3240331 3240597 3240597 Switch, fault light w/conn. Condenser Fan Fan Motor 115/1/60 3228001 3228001 3228001 3227992 3227992 Fan Motor 220-240/1/50 3228002 3228002 3228002 3227986 3227986 Fan Blade 115/1/60 3219394 3219394 3219394 3219395 3219395 Fan Blade 220-240/1/50 3219394 3219394 3219394 3219399 3219399 Compressor 115/1/60 3221265 3221265 3221265 3221267 3221267 Compressor 220-240/1/50 Refrigeration System 3221266 3221266 3221266 3221268 3221268 Condenser 3221323 3221323 3221323 3221324 3221324 Hot gas by-pass valve 3232549 3232549 3232549 3232526 3232526 Filter/Dryer 3223809 3223809 3223809 3223809 3223809 Fan Pressure Switch 3230755 3230755 3230755 3230756 3230756 *Filter, Ambient Air 3223805 3223805 3223805 3223806 3223806 Grommet (light & switch, front panel) 3224016 3224016 3224016 3224016 3224016 Foot, mounting 3223838 3223838 3223838 3223838 3223838 Cabinet * Maintenance kits for the above models are available "*" indicates items included in the kits. Maintenance Kits 14 For Dryer Models Kit Number 20, 25, 35 RNHFMK1 50, RNHFMK2 75 RNHFMK3 PARTS LIST PARTS DESCRIPTION 100 125 CE9-24 CE9-24 Separator *Separator/Filter Cartridge Filter Sleeve CS9-24 CS9-24 *Drain Mechanism 3152270 3152270 Bowl 3241108 3241108 *O-ring Bowl 3162913 3162913 Strainer, inlet 4009636 4009636 *Screen, strainer 3230662 3230662 Switch on/off 3230775 3230775 Light, Fault 230v 3227424 3227424 Electrical Cord Set 3221573 3221573 Capacitor, run 230/1/60 3264639 3264639 Capacitor, run 220/1/50 3264639 3264639 3240597 3240597 Fan Motor 3227986 3227986 Fan Blade 3219404 3219404 Switch, fault light w/conn. Condenser Fan Refrigeration System Compressor 230/1/60 3264172 3264172 Compressor 220/1/50 3264172 3264172 Condenser 3221325 3221325 Hot gas by-pass valve 3232526 3232526 Filter/Dryer 3223814 3223814 Fan Pressure Switch 3230756 3230756 *Filter, Ambient Air 3223807 3223807 Grommet (light & switch, front panel) 3224016 3224016 Foot, mounting 3223838 3223838 Cabinet * Maintenance kits for the above models are available "*" indicates items included in the kits. Maintenance Kits For Dryer Models Kit Number 100 RNHFMK4 125 RNHFMK4 15 WARRANTY The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and maintained in accordance with procedures and recommendations outlined in manufacturer’s instruction manuals, to be free from defects in material or workmanship for a period as specified below, provided such defect is discovered and brought to the manufacturer’s attention within the aforesaid warranty period. The manufacturer will repair or replace any product or part determined to be defective by the manufacturer within the warranty period, provided such defect occurred in normal service and not as a result of misuse, abuse, neglect or accident. Normal maintenance items requiring routine replacement are not warranted. The warranty covers parts and labor for the warranty period unless otherwise specified. Repair or replacement shall be made at the factory or the installation site, at the sole option of the manufacturer. Any service performed on the product by anyone other than the manufacturer must first be authorized by the manufacturer. Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid. Products repaired or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to the original product. The foregoing is the exclusive remedy of any buyer of the manufacturer’s product. The maximum damages liability of the manufacturer is the original purchase price of the product or part. THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, OR STATUTORY, AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN, MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY LATENT DEFECTS INHERENT THEREIN. THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER, WHETHER ARISING FROM BREACH OF WARRANTY , NEGLIGENCE OR STRICT LIABILITY IN TORT. The manufacturer does not warrant any product, part, material, component, or accessory manufactured by others and sold or supplied in connection with the sale of manufacturer’s products. Warranty Period Parts and labor for two (2) years from the date of shipment from the factory; heat exchangers are covered (parts only) for an additional three (3) years (total of five [5]). On units that manufacturer requests be returned to the factory, a one time removal/reinstallation labor allowance as noted in the Service Warranty Policies and Procedures Handbook will apply. Freight to the factory from the installation site and to the installation site from the factory will be paid by the manufacturer; means of transportation to be specified by manufacturer. AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE MATERIAL IS RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE. SERVICE DEPARTMENT: (724) 746-1100 Curtis-Toledo, Inc. 1905 Kienlen Avenue, St. Louis Missouri 63133 phone: 314-383-1300 fax: 314-381-1439 email: [email protected] WWW.FSCURTIS.COM
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project