FScurtis RNH20, RNHI125 Operator Manual


Add to my manuals
16 Pages

advertisement

FScurtis RNH20, RNHI125 Operator Manual | Manualzz
3227484
Rev. F
AUGUST 2012
RNH SERIES
HIGH TEMPERATURE REFRIGERATED DRYERS
OPERATOR
MANUAL
RNH20
RNH50
RNH125
RNH25
RNH75
RNH35
RNH100
GENERAL SAFETY INFORMATION
1.
Pressurized devices
This equipment is a pressure containing device.
• Do not exceed maximum operating pressure as
shown on equipment serial number tag.
• Make certain equipment is depressurized before
servicing.
2.
Electrical
This equipment requires electricity to operate.
• Install equipment in compliance with national and
local electrical codes.
• Standard equipment is supplied with NEMA 1 electrical enclosures and is not intended for installation
in hazardous environments.
• Disconnect power supply to equipment when performing any electrical service work.
3.
Breathing air
• Air treated by this equipment may not be suitable
for breathing without further purification. Refer to
OSHA standard 1910.134 for the requirements for
breathing quality air.
2
1.0 INSTALLATION
1.1 Location
2. Location in the compressed air system
A. Air compressor intake - Locate air compressor so that
contaminants potentially harmful to the dryer are not
drawn into the air system.
A.
B. Free air flow - Do not block either side of the cabinet. Observe minimum installation clearances as shown.
1) For maximum capacity, install unit in air system
at highest pressure possible (e.g. before pressure
reducing valves)
36"
wall
6"
Maximum working pressure - 250 psig,
17.6 kgf/cm2. Do not exceed unit’s Maximum Working
Pressure.
2) For maximum capacity, install unit at coolest compressed air temperature possible. Maximum inlet
compressed air temperature: 180°F, 82°C. If inlet
air exceeds this temperature, precool the air by
extending the piping between the compressor and
the dryer.
12"
B. Air Outlet - Connect air outlet to downstream air lines.
24"
C. By-pass piping - If servicing the unit without interrupting the air supply is desired, piping should include inlet
and outlet isolation valves and an air by-pass valve.
1.2 Mounting
Dryer is suitable for floor or shelf mounting.
D. Condensate drain - It is advisable to connect drain
outlet to the condensate drainage system.
1.3 Piping connections
A. Air Inlet - Connect compressed
air line from air compressor to
air inlet using strainer supplied.
1. Install strainer (included in
shipping carton) prior to
dryer inlet using pipe nipple
supplied or other piping as
required.
NOTE: Drain discharge is at system pressure. Drain line
should be anchored to prevent whipping.
1.4 Electrical connections
A. Dryer is designed to operate on power supply (voltage)
listed on serial number tag located on the back of the
dryer.
B. Dryer is supplied with an electrical cord. Install in receptacle of proper voltage. NOTE: Observe flow direction arrows on strainer.
NOTE: Install strainer where it is easily accessible for cleaning.
NOTE: Use vibration dampener, if vibration exists in air line
at inlet to dryer.
NOTE: Models 50 and 75 (115v only) - Install plug
in receptacle rated for 20 amps. Units are supplied with 20 amp plug.
Plug
NOTE: Refrigeration system is designed to run continuously and should NOT be wired to cycle on/off with the air
compressor.
Ambient Air Filter
Serial Number
Tag
Control
Panel
O
Serial
Number
Tag
I
Air Inlet
Connection
Separator and
Integral Filter
Drain
Mechanism
Strainer
(shipped
separately)
Electrical
Connection
Pipe Nipple
Drain
Connection
Air Outlet
Connection
Left Side
Front
Right Side
Back
3
2.0 OPERATION
D. Maximum flow capacity
NOTE: Installations above 6000 feet, 1825 meters
Unit is adjusted to operate in altitudes up to 6000 feet,
1825 meters. If unit is installed in an altitude above this,
and has not been preset at the factory for this altitude,
contact Manufacturer’s Service Department.
1. For dryers without an aftercooler installed upstream.
Flow capacity in scfm (m3/min) @ 180°F, 82°C inlet
temperature, 160°F, 71°C inlet pressure dew point,
95°F, 35°C ambient temperature, 50°F, 10°C outlet
pressure dew point, and less than 5 psi, 0.35 kgf/cm2
pressure drop.
2.1 Start-up
60 HZ
Start refrigeration system by pushing the on/off switch
to the ON position (depress rocker switch on side marked
“I”).
NOTE: The fault light may illuminate when unit is energized. Light should go out approximately 5 minutes after
start-up. If light remains lit after 30 minutes or illuminates after going out, refer to Troubleshooting Guide.
On/Off Switch
O
Inlet Pressure
175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0)
psig (kgf/cm2)
20
23 (0.65) 22 (0.62) 20 (0.57) 18 (0.51)
25
29 (0.82) 27 (0.76) 25 (0.71) 23 (0.65)
35
41 (1.16) 38 (1.08) 35 (0.99) 32 (0.91)
Model
50
58 (1.64) 54 (1.53) 50 (1.42) 45 (1.27)
75
87 (2.46) 81 (2.29) 75 (2.12) 68 (1.93)
100 116 (3.29) 108 (3.06) 100 (2.83) 91 (2.58)
125 145 (4.12) 135 (3.82) 125 (3.54) 114 (3.23)
50 HZ
Fault Light
I
Control Panel
2.2 Operating check points
Check the following on a periodic basis:
A.
Rocker switch is in the ON position.
B.
Amber fault light is out. C.
Condensate is being regularly discharged.
2.3 Minimum/maximum operating conditions
A.
Minimum/Maximum air pressure: 20/250 psig,
1.4/17.6 kgf/cm2
B.
Maximum inlet air temperature: 180°F, 82°C
C.
Minimum/Maximum ambient temperature:
40/110°F, 4/43°C
Inlet Pressure
175 (12.3) 150 (10.6) 125 (8.8)
psig (kgf/cm2)
20
20 (0.57) 18 (0.51) 17 (0.48)
25
24 (0.68) 23 (0.65) 21 (0.59)
35
31 (0.88) 29 (0.82) 27 (0.76)
Model
50
58 (1.64) 54 (1.53) 50 (1.42)
75
71 (2.01) 66 (1.87) 61 (1.73)
100 97 (2.75) 90 (2.55) 83 (2.35)
125 121 (3.43) 112 (3.17) 104 (2.95)
100 (7.0)
15 (0.42)
19 (0.54)
24 (0.68)
45 (1.27)
55 (1.56)
76 (2.15)
95 (2.69)
2. For dryers with an aftercooler installed upstream
Flow capacity in scfm (m3/min) @ 100°F, 38°C inlet
temperature, 100°F, 38°C inlet pressure dew point,
100°F, 38°C ambient temperature, 50°F, 10°C outlet
pressure dew point, and less than 10 psi, 0.7 kgf/cm2
pressure drop.
60 HZ
Inlet Pressure
psig (kgf/cm2)
20
25
35
Model
50
75
100
125
175 (12.3) 150 (10.6)
125 (8.8)
100 (7.0)
32 (0.91) 30 (0.85) 28 (0.79) 25 (0.71)
40 (1.13) 37 (1.05) 34 (0.96) 31 (0.88)
55 (1.56) 51 (1.44) 47 (1.33) 43 (1.22)
78 (2.21) 73 (2.07) 67 (1.90) 61 (1.73)
118 (3.34) 110 (3.12) 102 (2.89) 92 (2.61)
157 (4.45) 146 (4.14) 136 (3.85) 123 (3.48)
197 (5.58) 183 (5.18) 170 (4.82) 155 (4.39)
50 HZ
Inlet Pressure
175 (12.3) 150 (10.6) 125 (8.8) 100 (7.0)
psig (kgf/cm2)
20
27 (0.76) 25 (0.71) 23 (0.65) 21 (0.59)
25
33 (0.93) 31 (0.88) 29 (0.82) 26 (0.74)
35
43 (1.22) 40 (1.13) 37 (1.05) 33 (0.93)
Model
50
78 (2.21) 73 (2.07) 67 (1.90) 61 (1.73)
75
96 (2.72) 90 (2.55) 83 (2.35) 75 (2.12)
100 131 (3.71) 122 (3.46) 113 (3.20) 102 (2.89)
125 164 (4.65) 152 (4.31) 142 (4.02) 129 (3.65)
4
3.0 MAINTENANCE
DRYER IS A PRESSURE CONTAINING DEVICE.
DEPRESSURIZE BEFORE SERVICING.
3.1 Ambient air filter - Clean accumulated dust and
dirt from ambient air filter monthly or more often if air flow across the condenser is impeded.
3.3 Replace separator/filter element yearly or
more often if pressure drop across the dryer is
excessive.
A.
Shut-off compressed air supply to the dryer and depressurize.
A.
Remove top panel.
B.
Remove top panel.
B.
Remove ambient air filter by sliding upwards.
C.
Remove two screws holding side panel and remove
side panel by sliding upwards.
D. Disconnect drain tube from bulkhead fitting in
cabinet base. To remove, press the plastic collar in,
toward the fitting, while pulling the tube out of the
fitting.
C.
E.
Remove bowl - push bowl up, turn bowl 1/8th turn to
your left, and pull straight down.
F.
Clean filter bowl.
G.
Replace element.
1.
Replacing complete element
Wash with soap and water and allow to dry before reinstalling.
NOTE: Do not use solvents to clean ambient air filter.
D. Reinstall filter and top panel.
3.2 Inlet strainer - clean inlet strainer monthly or
more often if rapid clogging occurs.
A.
Shut-off compressed air supply to the strainer and
depressurize.
B.
Remove screen and clean or replace.
C.
Reinstall.
a)
Pull off old element and discard.
b)
Make certain O-ring inside top of replacement
element is in place and push element onto filter
head.
Screen
2.
Replacing sleeve only
a)
Pull element straight down to remove.
b)
Remove bolt and bottom cap and remove disposable filter sleeve.
c)
Clean separator core with soap and water if necessary
d)
Slide new filter sleeve over separator core and
replace bottom cap and hand tighten bolt.
e)
Make certain O-ring inside top of element is in
place and push element onto filter head.
5
H. After making sure that O-ring and wave spring inside
top of bowl are in place, reassemble bowl to head.
3.4 Automatic condensate drain
• Check daily to be sure automatic drain is discharging.
NOTE: Make certain O-ring is generously lubricated
NOTE: Wave spring ends should be pointed down to prevent the wave spring from interfering with reassembly.
I.
Reconnect drain tube to bulkhead fitting by pushing
tube into fitting until it locks in position.
J.
Reinstall side and top panels.
K.
Repressurize dryer and resume operation.
• Replace drain mechanism yearly.
A.
Shut-off compressed air supply to the dryer and depressurize.
B.
Remove top panel.
C.
Remove two screws holding side panel then remove
side panel by sliding upwards.
D. Disconnect drain tube from bulkhead fitting in
cabinet base. To remove, press the plastic collar in,
toward the fitting, while pulling the tube out of the
fitting.
Element o-ring
Bowl o-ring
E.
Remove bowl - push bowl up, turn 1/8th turn to your
left, and pull bowl straight down.
F.
Remove drain tube fitting from bottom of bowl. G.
Remove old drain mechanism by turning knurled
fitting to the right (clockwise) and remove.
Separator Element
Wave Spring
Drain Mechanism
Tube
Hose
Barb
H. Install new drain mechanism. If necessary, use a
wire or pencil to guide the new mechanism into
place.
I.
Reassemble drain tube fitting to bowl.
J.
After making sure that large O-ring in filter head is
in place, reassemble bowl to head.
K.
Reconnect drain tube to bulkhead fitting by pushing tube into fitting until it locks in position.
L.
Reinstall top and side panels.
M. Repressurize dryer and resume operation.
6
TROUBLESHOOTING GUIDE
SYMPTOM
A) Water downstream of dryer
POSSIBLE CAUSE(S)
1. Residual free moisture remaining in
downstream pipelines
2. Air by-pass system is open
3. Inlet and Outlet connections are
reversed
4. Temperatures surrounding air
lines downstream of dryer have
dropped below dryers dew point
rating.
5. Excessive free moisture (bulk liquid)
at dryer inlet
6. Condensate not being automatically drained
Drain mechanism is clogged or
inoperative.
Drain line is restricted or frozen.
7. Dryer overloaded resulting in elevated dew point.
8. Refrigeration system not functioning properly resulting in elevated
dew point.
B) High pressure drop across
dryer
1.
2.
3.
4.
Inlet air strainer clogged
Excessive air flow
Separator filter clogged.
Freezing of moisture in evaporator
because of refrigeration system
improperly functioning.
C) Fault Alarm
1. Dryer overloaded resulting in high
air outlet temperature.
2. Refrigeration system not functioning properly resulting in high air
outlet temperature.
3. Unit functioning normally but thermostatic switch is malfunctioning
or not securely mounted.
CORRECTIVE ACTION
Blow out system with dry air
Check valve positions
Check for correct connection
Insulate or heat trace air lines exposed
to low ambients or dry air to lower
dew point
Install separator ahead of dryer
Replace drain mechanism if inoperative
Open drain line
Check inlet air temperature and pressure, flow rate (compressor capacity)
and ambient air temperature
See D below
Clean inlet air strainer
Check flow rate
Replace filter sleeve
See D below
See A 7
See D below
Contact qualified refrigeration repairman or manufacturer’s service department
D) Refrigeration system not functioning properly
1. When dryer on/off switch in on or
"I" position
a.
b.
c.
d.
Power failure
Line disconnect switch open
Blown fuses, open breaker
Faulty wiring, loose terminals
2. Refrigerant compressor cycles on
and off
a. High or low ambient conditions
b. Ambient air filter clogged
c. Condenser fins clogged
d. Fan motor or fan control switch
malfunction
e. Refrigerant leak
f. Low voltage
Check power to unit
Close disconnect switch
Check for continuity
Have electrician check electrical connections
Check minimum/maximum temperature ranges
Clean ambient air filter
Clean condenser
Replace fan motor or fan control
switch
Contact qualified refrigeration repairman or manufacturer's service department
Check wiring
7
SPECIFICATIONS - Models 20 thru 75
Description
20
25
Model
35
50
75
20 / 17
0.57 / 0.48
25 / 21
0.71 / 0.59
35 / 27
0.99 / 0.76
50 / 50
1.42 / 1.42
75 / 61
2.12 / 1.7
4.5 / 4.5
(0.32 / 0.32)
3.8 / 2.2
(0.27 / 0.15)
Operating Conditions
Rated Capacity
@125 psig, 8.8 kgf/cm2*
scfm
m3/min
60 / 50 Hz
60 / 50 Hz
Maximum Working Pressure
250 psig (17.6 kgf/cm2)
Maximum Inlet Temperature
180°F (82°C)
Min/Max. Ambient Temperature
Pressure Drop @
rated capacity
40-110°F (4-43°C)
psi
(kgf/cm2)
60 / 50 Hz
60 / 50 Hz
4.5 / 2.9
(0.32 / 0.20)
3.3 / 2.4
(0.23 / 0.17)
4.7 / 2.9
(0.33 / 0.20)
Refrigeration System Data
Compressor Type
Hermetic, Rotary, Permanent Split Capacitor
BTU/HR - Refrigeration Only
@ ASRE-T Conditions 60 / 50 Hz
8720 / 7043
Outlet Air Temperature
(nominal @ rated conditions)
155°F (68°C)
Refrigerant Type
Refrigerant Charge
R-407C
oz (grams)
60 / 50 Hz
See Dryer Serial Tag
Suction Pressure Setting
67 psig (4.7 kgf/cm2)
Factory Test (design) Pressure
high side/low side
330/178 psig (23.2/12.5 kgf/cm2)
Condenser Fan Switch Setting (in-out)
Air Flow Across Condenser
12500 / 9970
cfm
m3/min
240-180 psig (16.9-12.7 kgf/cm2)
60 / 50 Hz
60 / 50 Hz
280 / 235
(7.9 / 6.7)
620 /515
(17.6 / 14.6)
Electrical Data
Unit
VAC/phase/Hz
115/1/60
115/1/60
Minimum/maximum volts
98-127
Full Load AmpS (FLA)
8.7
12.6
Branch Circuit Fuse Size (amps)
15
20
Compressor
Volts/phase/Hz
115/1/60
Rated Load amps (RLA)
7.5
Locked Rotor amps (LRA)
44.0
67.0
Watts (input)
853
1220
Overload (External)
Thermal and Current (Auto Reset)
Condenser fan motor
Volts/phase/Watts (output)
Full Load Amps (FLA)
Unit
VAC/phase/Hz
11.0
115/1/25
115/1/35
1.2
1.6
220-240/1/50
220-240/1/50
Minimum/maximum volts
Full Load Amps (FLA)
198-264
3.4
6.0
Branch Circuit Fuse Size (amps)
15
Compressor
Volts/phase/Hz
220-240/1/50
Rated Load amps (RLA)
2.8
5.1
Locked Rotor amps (LRA)
18.6
28.0
Watts (input)
690
Overload (External)
Condenser fan motor
Volts/phase/Watts (output)
Full Load Amps (FLA)
990
Thermal and Current (Auto Reset)
220-240/1/18.3
220-240/1/25.6
0.6
0.8
* Capacity @ 180°F, 82°C inlet temperature, 160°F, 71°C inlet pressure dew point, 95°F, 35°C ambient temperature, 50°F, 10°C outlet pressure dew
point, and less than 5 psi, 0.35 kgf/cm2 pressure drop.
8
SPECIFICATIONS - Models 100 and 125
Model
Description
100
125
100 / 83
2.83 / 2.35
125 / 104
3.54 / 2.95
Operating Conditions
Rated Capacity
@125 psig, 8.8 kgf/cm2*
scfm
m3/min
60 / 50 Hz
60 / 50 Hz
Maximum Working Pressure
250 psig (17.6 kgf/cm2)
Maximum Inlet Temperature
180°F (82°C)
Min/Max. Ambient Temperature
Pressure Drop @
rated capacity
40-110°F (4-43°C)
psi
(kgf/cm2)
60 / 50 Hz
60 / 50 Hz
3.5 / 2.6
(0.25 / 0.18)
4.6 / 3.1
(0.32 / 0.22)
Refrigeration System Data
Compressor Type
Hermetic, Rotary, Permanent Split Capacitor
BTU/HR - Refrigeration Only
@ ASRE-T Conditions 60 / 50 Hz
Outlet Air Temperature
(nominal @ rated conditions)
155°F (68°C)
Refrigerant Type
Refrigerant Charge
R-407C
oz (grams)
60 / 50 Hz
Suction Pressure Setting
See Dryer Serial Tag
67 psig (4.7 kgf/cm2)
Factory Test (design) Pressure
high side/low side
330/178 psig (23.2/12.5 kgf/cm2)
Condenser Fan Switch Setting (in-out)
Air Flow Across Condenser
25140 / 20110
cfm
m3/min
240-180 psig (16.9-12.7 kgf/cm2)
60 / 50 Hz
60 / 50 Hz
830 / 690
(23.5 / 19.5)
Electrical Data
Unit
VAC/phase/Hz
208-230/1/60
230/1/60
Minimum/maximum volts
187-253
Full Load AmpS (FLA)
12.2
Branch Circuit Fuse Size (amps)
20
Compressor
Volts/phase/Hz
208-230/1/60
Rated Load amps (RLA)
11.3
Locked Rotor amps (LRA)
71.0
Watts (input)
2530
Overload (Internal)
Thermal and Current (Auto Reset)
Condenser fan motor
Volts/phase/Watts (output)
230/1/60
Full Load Amps (FLA)
Unit
VAC/phase/Hz
Minimum/maximum volts
Full Load Amps (FLA)
Branch Circuit Fuse Size (amps)
Compressor
Volts/phase/Hz
Rated Load amps (RLA)
0.85
220/1/50
220/1/50
207-242
14.1
20
200-220/1/50
13.2
Locked Rotor amps (LRA)
71.0
Watts (input)
2212
Overload (Internal)
Condenser fan motor
Volts/phase/Watts (output)
Full Load Amps (FLA)
Thermal and Current (Auto Reset)
230/1/50
0.85
* Capacity @ 180°F, 82°C inlet temperature, 160°F, 71°C inlet pressure dew point, 95°F, 35°C
ambient temperature, 50°F, 10°C outlet pressure dew point, and less
than 5 psi, 0.35 kgf/cm2 pressure drop.
9
ELECTRICAL SCHEMATICS
Models 50 and 75
Models 20, 25, and 35
LINE
SW
2
4
3
1
14
3
2
5
1
OLT
C
RC
6
S
4
M
G
3
HTS
7
3
FPS
8
REFRIGERANT
COMPRESSOR
4
R
LT
A
FM
4
HIGH
TEMPERATURE
4
CONDENSER
FAN MOTOR
WIRING SCHEMATIC
Models 100 and 125
LEGEND
LINE
SW
2
4
3
1
5
C
S
RC
6
4
M
4
R
G
3
HTS
7
3
FPS
8
LT
A
FM
REFRIGERANT
COMPRESSOR
4
HIGH
TEMPERATURE
4
CONDENSER
FAN MOTOR
WIRING SCHEMATIC
SW
OLT
M
RC
HTS
LT
FPS
FM
TB
CT
-
On/Off Switch
Thermal Overload
Compressor Motor
Run Capacitor
High Temperature Switch
Fault Light
Fan Pressure Switch
Fan Motor
Terminal Block
Contactor w/115V Coil
Models 50 and 75
Models 20, 25, 35, 100, and 125
FM
SW
FM
HTS
LT
SW
OLT
HTS
LT
OLT
Front of Dryer
(Outside)
M
RC
TB
Right Side of Dryer
(Inside)
COMPONENT LOCATIONS
10
FPS
FPS
M
Front of Dryer
(Outside)
RC
CT
Right Side of Dryer
(Inside)
COMPONENT LOCATIONS
DIMENSIONS AND WEIGHTS
Models 20, 25, 35
257 mm
Model Weight
20
79 lbs (36 kg)
25
80 lbs (36 kg)
35
81 lbs (37 kg)
6 mm
5.1/16 "
128 mm
718 mm
317 mm
1.9/16 "
40 mm
1" 25 mm
21 mm
5 mm
105 mm
217 mm
257 mm
327 mm
216 mm
168 mm
1.1/2"
38 mm
105 mm
287 mm
41 mm
130 mm
11
DIMENSIONS AND WEIGHTS
Models 50 and 75
425 mm
Model Weight
50
150 lbs (68 kg)
75
155 lbs (70 kg)
6 mm
933 mm
8 7/16"
213 mm
419 mm
1.1/2"
38 mm
25 mm
15 1/4"
387 mm
5 mm
117 mm
429 mm
232 mm
160 mm
39 mm
59 mm
129 mm
12
175 mm
21 mm
DIMENSIONS AND WEIGHTS
Models 100 and 125
Model Weight
100 187 lbs (85 kg)
125 189 lbs (86 kg)
1"
1"
13
PARTS LIST
PARTS DESCRIPTION
20
25
35
50
75
CE9-16
CE9-16
CE9-16
CE9-20
CE9-24
Separator
*Separator/Filter Cartridge
Filter Sleeve
CS9-16
CS9-16
CS9-16
CS9-20
CS9-24
*Drain Mechanism
3152270
3152270
3152270
3152270
3152270
Bowl
3240333
3240333
3240333
3223457
3241108
*O-ring Bowl
3154585
3154585
3154585
3162913
3162913
Strainer, inlet
4009634
4009634
4009634
4009635
4009635
*Screen, strainer
3230672
3230672
3230672
3230673
3230673
Inlet (Compressed Air) Strainer
Electrical
3230775
3230775
3230775
3230775
3230775
Light, Fault (amber)
115/1/60
3227423
3227423
3227423
3227423
3227423
Light, Fault (amber)
Switch on/off
220-240/1/50
3227424
3227424
3227424
3227424
3227424
Cord Set
115/1/60
3221571
3221571
3221571
3221572
3221572
Cord Set
220-240/1/50
3221422
3221422
3221422
3221422
3221422
Capacitor, run
115/1/60
3220878
3220878
3220878
3220878
3220878
Capacitor, run
220-240/1/50
3220872
3220872
3220872
3220878
3220878
3240331
3240331
3240331
3240597
3240597
Switch, fault light w/conn.
Condenser Fan
Fan Motor
115/1/60
3228001
3228001
3228001
3227992
3227992
Fan Motor
220-240/1/50
3228002
3228002
3228002
3227986
3227986
Fan Blade
115/1/60
3219394
3219394
3219394
3219395
3219395
Fan Blade
220-240/1/50
3219394
3219394
3219394
3219399
3219399
Compressor
115/1/60
3221265
3221265
3221265
3221267
3221267
Compressor
220-240/1/50
Refrigeration System
3221266
3221266
3221266
3221268
3221268
Condenser
3221323
3221323
3221323
3221324
3221324
Hot gas by-pass valve
3232549
3232549
3232549
3232526
3232526
Filter/Dryer
3223809
3223809
3223809
3223809
3223809
Fan Pressure Switch
3230755
3230755
3230755
3230756
3230756
*Filter, Ambient Air
3223805
3223805
3223805
3223806
3223806
Grommet (light & switch, front panel)
3224016
3224016
3224016
3224016
3224016
Foot, mounting
3223838
3223838
3223838
3223838
3223838
Cabinet
* Maintenance kits for the above models are available "*" indicates items included in the kits.
Maintenance Kits
14
For Dryer Models
Kit Number
20, 25, 35
RNHFMK1
50,
RNHFMK2
75
RNHFMK3
PARTS LIST
PARTS DESCRIPTION
100
125
CE9-24
CE9-24
Separator
*Separator/Filter Cartridge
Filter Sleeve
CS9-24
CS9-24
*Drain Mechanism
3152270
3152270
Bowl
3241108
3241108
*O-ring Bowl
3162913
3162913
Strainer, inlet
4009636
4009636
*Screen, strainer
3230662
3230662
Switch on/off
3230775
3230775
Light, Fault 230v
3227424
3227424
Electrical
Cord Set
3221573
3221573
Capacitor, run
230/1/60
3264639
3264639
Capacitor, run
220/1/50
3264639
3264639
3240597
3240597
Fan Motor
3227986
3227986
Fan Blade
3219404
3219404
Switch, fault light w/conn.
Condenser Fan
Refrigeration System
Compressor
230/1/60
3264172
3264172
Compressor
220/1/50
3264172
3264172
Condenser
3221325
3221325
Hot gas by-pass valve
3232526
3232526
Filter/Dryer
3223814
3223814
Fan Pressure Switch
3230756
3230756
*Filter, Ambient Air
3223807
3223807
Grommet (light & switch, front panel)
3224016
3224016
Foot, mounting
3223838
3223838
Cabinet
* Maintenance kits for the above models are available "*" indicates
items included in the kits.
Maintenance Kits
For Dryer Models
Kit Number
100
RNHFMK4
125
RNHFMK4
15
WARRANTY
The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and
maintained in accordance with procedures and recommendations outlined in manufacturer’s instruction manuals, to be free from defects in material or workmanship for a period as specified below, provided such defect is
discovered and brought to the manufacturer’s attention within the aforesaid warranty period.
The manufacturer will repair or replace any product or part determined to be defective by the manufacturer
within the warranty period, provided such defect occurred in normal service and not as a result of misuse, abuse,
neglect or accident. Normal maintenance items requiring routine replacement are not warranted. The warranty
covers parts and labor for the warranty period unless otherwise specified. Repair or replacement shall be made at
the factory or the installation site, at the sole option of the manufacturer. Any service performed on the product
by anyone other than the manufacturer must first be authorized by the manufacturer.
Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid. Products
repaired or replaced under warranty shall be warranted for the unexpired portion of the warranty applying to the
original product.
The foregoing is the exclusive remedy of any buyer of the manufacturer’s product. The maximum damages liability of the manufacturer is the original purchase price of the product or part.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER WRITTEN, ORAL, OR
STATUTORY, AND IS EXPRESSLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY
REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN, MANUFACTURE
OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY LATENT DEFECTS
INHERENT THEREIN.
THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER, WHETHER ARISING FROM BREACH OF WARRANTY , NEGLIGENCE OR STRICT LIABILITY IN TORT.
The manufacturer does not warrant any product, part, material, component, or accessory manufactured by others and sold or supplied in connection with the sale of manufacturer’s products.
Warranty Period
Parts and labor for two (2) years from the date of shipment from the factory; heat exchangers are covered (parts
only) for an additional three (3) years (total of five [5]). On units that manufacturer requests be returned to the
factory, a one time removal/reinstallation labor allowance as noted in the Service Warranty Policies and Procedures Handbook will apply. Freight to the factory from the installation site and to the installation site from the
factory will be paid by the manufacturer; means of transportation to be specified by manufacturer.
AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE MATERIAL IS
RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE.
SERVICE DEPARTMENT: (724) 746-1100
Curtis-Toledo, Inc.
1905 Kienlen Avenue, St. Louis Missouri 63133
phone: 314-383-1300
fax: 314-381-1439
email: [email protected]
WWW.FSCURTIS.COM

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement