Standard Delivery Schedule


Add to my manuals
31 Pages

advertisement

Standard Delivery Schedule | Manualzz
MTE Corporation
MTE –Series RL
Line/ load Reactors
USER MANUAL
PART NO. INSTR -011
REL. 060227
© 2006 MTE Corporation
Important User Information
NOTICE
MTE Series RL Line/Load Reactors are components designed to improve the reliability of
adjustable frequency drives, DC drives and a wide variety of other types of power
electronic equipment. In addition they provide limited input line current harmonic
mitigation and aid in long lead protection for inverter fed motors. Note: (See MTE
harmonic filters and motor protection products for guaranteed results.) MTE reactors are
available in a large number of current ratings and a variety of inductance values. The
suitability of a line/load reactor for a specific application must therefore be ultimately
determined by the customer. In no event will MTE Corporation assume responsibility or
liability for any direct or consequential damages resulting from the use or application of
reactors. Nor will MTE Corporation assume patent liability with respect to the use of
information, circuits or equipment described in this instruction manual.
This manual includes recently redesigned performance enhanced reactors. These reactors are
physically smaller and weigh less than the reactors they replace. Enhanced reactors have base
mounting brackets with additional slotted holes to accommodate past mounting hole centers. You
may uses your existing drill pattern or choose the new layout. The tables contained in this manual
reflect historical mounting dimensions for previous reactors.
This document supports computer searches and is best viewed with Adobe Acrobat™
PDF viewer (6 or 7). Click links are incorporated throughout the document to speedup
document navigation.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
2 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Table of Contents
IMPORTANT USER INFORMATION ........................................................................................... 2
TABLE OF CONTENTS ............................................................................................................... 3
IMPORTANT SAFETY INFORMATION ....................................................................................... 4
INTRODUCTION .......................................................................................................................... 5
MODEL NUMBER CODES .......................................................................................................... 6
SPARE PARTS ............................................................................................................................ 7
LUG OPTION DETAILS: .............................................................................................................. 8
PRODUCT SPECIFICATIONS ................................................................................................... 10
DE-RATING CURVES ................................................................................................................ 13
DIMENSION REFERENCE ........................................................................................................ 14
MOUNTING COMPATIBILITY ................................................................................................... 15
MECHANICAL DETAILS OPEN REACTORS ........................................................................... 16
NEMA1 MECHANICAL DATA ................................................................................................... 18
RECOMMENDED CONDUIT ENTRY FOR FLOOR MOUNTED ............................................... 20
ENCLOSURE DIMINSIONS ....................................................................................................... 21
TECHNICAL DATA .................................................................................................................... 25
INSTALLATION INSTRUCTIONS.............................................................................................. 27
POWER WIRING CONNECTION ............................................................................................... 28
TYPICAL CONNECTION DIAGRAMS ....................................................................................... 29
SEQUENCE OF OPERATION ................................................................................................... 30
STARTUP ................................................................................................................................... 31
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
3 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
IMPORTANT SAFETY INFORMATION
WARNING
ONLY A QUALIFIED ELECTRICIAN CAN CARRY OUT THE ELECTRICAL
INSTALLATION OF LINE/LOAD REACTORS
WARNING
High voltage is used in the operation of line/load reactors. Use Extreme caution to avoid contact with high
voltage when operating, installing or repairing equipment containing line/load reactors
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.
Line/load reactors are used in conjunction with inverters, or other electrical equipment that may feedback
lethal voltages. Follow the safety instructions in the equipment used with the reactor in addition to the
safety instruction in this manual.
WARNING
The opening of the branch circuit protective device may be an indication that a fault current has been
interrupted. To reduce the risk of fire or electrical shock, line/load reactors should be examined and
replaced if damaged.
WARNING
An upstream disconnect/protection device must be used as required by the National Electrical Code
(NEC).
WARNING
Even if the upstream disconnect/protection device is open, a drive or inverter down stream of the
line/load reactor may feed back high voltage to the reactor. The inverter or drive safety instructions
must be followed.
INJURY OR DEATH MAY RESULT IF THE DRIVE SAFETY PRECAUTIONS ARE NOT
OBSERVED.
WARNING
The frame of line/load reactors must be grounded at least at one of the reactor’s mounting holes.
WARNING
Only spare parts obtained from MTE Corporation or an authorized MTE distributor can be used
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
4 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
INTRODUCTION
This manual was specifically developed to
assist in the installation, interconnection and
operation of MTE Corporation Series RL
Line/Load Reactors
This manual is intended for use by
personnel experienced in the operation and
maintenance of electronic drives, inverters
and similar types of power electronic
equipment. Because of the high voltages
required by the equipment connected to
line/load reactors and the potential dangers
presented by rotating machinery, it is
essential that all personnel involved in the
operation and maintenance of line/load
reactors know and practice the necessary
safety precautions for this type of
equipment. Personnel should read and
understand the instructions contained in this
manual before installing, operating or
servicing line/load reactors and the drive to
which the reactor is connected.
Upon Receipt of a Reactor:
In the event of damage, please contact
and file a claim with the freight carrier
involved immediately.
If the equipment is not going to be put into
service upon receipt, cover and store the
reactor in a clean, dry location. After
storage, ensure that the equipment is dry
and that no condensation has accumulated
on the reactor before applying power.
Repair/Exchange Procedure
MTE Corporation requires a Returned
Material Authorization Number before it can
accept any reactors that qualify for return or
repair. If problems or questions arise during
installation, setup, or operation of the filter,
please call us for assistance at:
Phone: 1-262-253-8200
FAX: 1-262-253-8222
MTE Line/load Reactors have been
subjected to demanding factory tests before
shipment. Carefully inspect the shipping
container for damage that may have
occurred in transit. Then unpack the filter
and carefully inspect for any signs of
damage. Save the shipping container for
future transport of the reactor.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
5 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
MODEL NUMBER CODES
Fundamental Current Amps
1000 100
10
1
MOV
option
RL
none
240 Volts
380 - 415 volts
480 Volts
600 Volts
Custom design
Z No.
Option
suffix
↑
1
2
3
4
↑
blank
208 Volts
Style
A
C
E
G
J
X
Open Frame
NEMA 1
OVERSIZE NEMA 1
NEMA 3R
0
1
2
3
↑
↑
↑
↑
↑
none
Substitute Box Lug for terminal block
Substitute Tab terminal w/clearance hole
Substitute flexible leads (18 inches typical)
Substitute next larger Box Lug
Substitute 35 amp terminal block for smaller terminal block
Rotate terminal block 90 degrees
Add 3-point control circuit terminal block to 45 amps
Add 3-point control circuit terminal block to 750 amps
Sub. accessory wiring t/b
Substitute front facing tab (flag) terminal
Substitute next larger terminal block 12 to 35 amps
Add 3-NC over temp switches w/ 6 point terminal block
Add 1 thermocouple per coil (customer supplied)
Add 3-NC over temp switches with leads
Add 1-NC over temp switch w/ 2 point terminal block
Add 3-NO over temp switches w/6 point terminal block
Add thermocouple to center coil only (customer supplied)…
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
6 of 31
blank
B
B1
B5
B6
B7
B8
B9
B11
B10
B14
B18
T
T1
T2
T5
T6
T7
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Spare Parts
For standard type “RL” AC Line / Load Reactors
Description
Part No.
To adds “SLU 225” box lugs on B14
To adds “XT 500” box lugs on B14
Lug Kit 001
Lug Kit 002
Terminal Blocks
Description
Part No.
For RL-00101 thru RL-00804
For RL-01201 thru RL-03502
For RL-03503 thru RL-04503
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
36-822-049
36-825-004
TERMBLK-013
7 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
LUG OPTION DETAILS:
“B1” Terminal Modification
“B14” Terminal Modification
“B8” Terminal Modification
“SLU” Lug Option
Wire range:
2 - 0000
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
Wire range: 00 – 500 mcm
8 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
SLU Lug Options cont.
SLU 225 shown on 200 amp Reactor
XT 500 shown on 250 amp Reactor
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
9 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
PRODUCT SPECIFICATIONS
Standard impedance values
1-1/2%, 2, 3%, 4%, 5% available
Impedance basis
Reactor fundamental current rating
Service Factor
(Continuous)
Reactors rated 1 to 750 Amps
Reactors rated above 750 Amps
150% of fundamental rating
125% of fundamental rating minimum
Note: Select reactor based on fundamental current
rating
Overload Rating
200% of fundamental for 30 minutes
300% of fundamental for 1 minute
Maximum system voltage
600 Volts ( units with terminal blocks)
690 Volts (units with box lugs or tab terminals)
Maximum switching frequency
20 KHz
Insulation system
Class N (200° C)
Temperature rise
Open or enclosed reactors
135° C (average)
Ambient temperature
Open or enclosed reactors
45° C (maximum)
Altitude (maximum)
1000 meters
Fundamental frequency
Line or Load
50/60 Hz
Approvals:
CE, UL-508, CSA C22.2
Inductance curve (typical)
100% at 100% current
100% at 150% current
50% at 350% current (minimum)
Inductance tolerance
+/- 10%
Impregnation:
High Bond Strength “Solvent less” Epoxy, 200° C
UL94HB recognized
Dielectric Strength
3000 volts rms (4243 volts peak)
dv/dt Protection
motors)
Meets NEMA MG-1, part 31 (same as inverter duty
Protection:
meet IP20
Open reactors with terminal blocks through 45 amps
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
10 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
PRODUCT SPECIFICATIONS (cont’d)
AGENCY APPROVALS:
UL-508,
UL-508,
CSA C22.2,
Class N, 200° C,
CE Marked
MATERIAL:
Core Steel:
Windings:
Enclosures:
Grey
Brackets:
Terminations:
File E180243 Component Listed (1 amp – 2400 amps)
File E180243 UL Listed NEMA 1 units (1 amp – 2400 amps)
File LR29753-13 CSA Certified (1 amp – 2400 amps)
File E66214, Type 200-18, UL Recognized Insulation System
Electrical grade silicon steel
High dielectric withstand solid copper conductor (220° C)
Sheet steel in accordance with UL and CSA requirements. Painted ANSI-61
Sheet Insulation:
Epoxy:
ASTM structural steel or structural aluminum
1 – 45 amps - Finger safe terminal block
55 - 160 amps - Solid copper box lugs (Tab terminals are optional)
200 + amps - Copper tab terminals
DuPont Nomex 410 (220° C)
Ripley Resin Type 468-2 (220° C)
CONSTRUCTION:
CORE:
Electrical grade silicon steel magnetic laminations.
WINDINGS:
Meet 3000 volts rms dielectric strength (coil – to coil and coil- to – core).
ASSEMBLY:
Windings are assembled onto EI laminations, secured in place and epoxy
impregnated for minimum noise and maximum structural rigidity.
COLOR:
Royal Blue
TESTING:
Electronic Turns Count (Zero Tolerance)
Inductance
Hi-Pot 3000 Volts rms (5656 volts peak)
Mechanical Inspection
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
11 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
PRODUCT SPECIFICATIONS (cont’d)
AUDIBLE NOISE:
Guard-AC Line/Load Reactors offer low noise operation. Core and coil
construction, flux density control, harmonic compensation as well as our epoxy impregnation process
assure minimal audible noise radiation. Although our reactors are typically “quiet”, waveforms vary by
drive type and application and therefore reactor audible noise may vary by application. Noise levels may
be affected by type of motor and motor conductor as well as motor conductor length.
Typical audible noise levels for units selected from our catalog by HP rating are:
2 thru 12 amps
18 thru 100 amps
130 thru 400 amps
500 thru 1200 amps
55 dBA
65 dBA
70 dBA
75 dBA
Service Factor:
Guard-AC reactors are compensated for the additional currents and high
frequencies caused by the presence of harmonics. The reactor fundamental current rating indicates the
typical full load motor current and is also the basis of impedance rating. Standard reactors rated 1 amps
thru 750 amps offer a full 1.5 service factor rating which allows them to carry overload current up to 150%
of their fundamental rating when applied as an input line reactor. Since the nameplate ratings of motor
drives (ASD) varies widely by manufacturer, this helps to assure that the reactor maximum current rating
is compatible with the nameplate current rating on the ASD. The service factor rating compensates for
ASD manufacturer variances in motor drive current ratings and for harmonic currents. Nominal
inductance is assured all the way up to the service factor current rating.
PWM / IGBT PROTECTION: Guard-AC reactors are protected against the high peak voltage and fast
rise time voltage pulses associated with PWM waveforms. The dielectric strength is 4000 volts rms and
Guard-AC reactors meet the ratings of an inverter duty motor (NEMA MG-1, part 31). For convenience,
they can be located either at the motor or at the drive.
HARMONIC ATTENUATION: Our unique harmonic compensation assures maximum circuit inductance
in the presence of complex waveforms and can be relied upon to minimize input total harmonic current
distortion (THID). Additionally it offers superior absorption of transient voltage spikes. Our standard
reactors will typically reduce 6-pulse rectifier input current harmonics to the following levels at full load
operating conditions:
3% reactor alone
5% reactor alone
3% AC reactor + 3% DC link choke
5% AC reactor + 3% DC link choke
(DC link choke inductance is equivalent ac impedance).
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
45% or less THID
35% or less THID
33% or less THID
28% or less THID
12 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
DE-RATING CURVES
Current De-Rating Factor
Altitude Derating Curve
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0
3300
6600
9900
13200
16500
Altitude (Feet)
Reactor Temperature De-Rating
Current De-Rating Factor
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
40
45
50
55
60
65
70
75
80
85
Ambient Temperature Deg. C
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
13 of 31
INSTR-011 REL. 060227
90
MTE AC Line / Load Reactors
User Manual
Dimension Reference
Open Type
Visit the MTE web for reactor detail drawings www.mtecorp.com
Dimensions A, B, C show overall spacing allowances
Use dimension D and E for mounting pattern
See “Mechanical Details Table” for dimensional data
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
14 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Mounting Compatibility
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
15 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Mechanical Details Open Reactors
MTE
Cat. No.
RL-00101
RL-00102
RL-00103
RL-00104
RL-00201
RL-00202
RL-00203
RL-00204
RL-00401
RL-00402
RL-00403
RL-00404
RL-00801
RL-00802
RL-00803
RL-00804
RL-01201
RL-01202
RL-01203
RL-01801
RL-01802
RL-01803
RL-02501
RL-02502
RL-02503
RL-03501
RL-03502
RL-03503
RL-04501
RL-04502
RL-04503
RL-05501
RL-05502
RL-05503
RL-08001
RL-08002
RL-08003
RL-10001
RL-10002
RL-10003
RL-13001
RL-13002
RL-13003
RL-16001
RL-16002
A
Inches
3.8
3.8
3.8
3.8
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
8.1
7.2
7.2
7.2
7.2
7.2
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
10.8
9.0
9.0
10.8
9.0
9.0
11.0
9.0
10.8
mm
97
97
97
97
112
112
112
112
112
112
112
112
152
152
152
152
152
152
152
152
152
206
183
183
183
183
183
229
229
229
229
229
229
229
229
229
274
229
229
274
229
229
279
229
274
B
Inches
3.5
3.5
3.5
3.5
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.8
4.8
4.8
4.8
5.0
5.0
5.0
5.3
5.3
6.1
5.8
5.8
5.8
5.8
5.8
7.4
7.4
7.4
7.3
7.3
7.0
7.0
7.2
7.2
8.5
7.3
7.3
8.3
7.0
7.2
8.5
7.2
8.3
mm
89
89
89
89
104
104
104
104
104
104
104
104
122
122
122
122
127
127
127
135
135
155
147
147
147
147
147
188
188
188
185
185
178
178
183
183
216
185
185
210
178
183
216
183
211
C
Inches
1.2
1.2
1.2
1.2
2.8
2.8
2.8
2.5
2.8
2.8
3.4
3.4
3.0
3.0
3.4
3.4
3.3
3.3
3.9
3.2
3.5
4.0
3.5
3.5
4.3
4.0
4.0
4.7
4.7
4.7
5.3
5.3
5.3
6.0
6.3
6.5
6.8
6.5
6.8
6.2
4.7
6.8
6.2
6.8
6.0
mm
30
30
30
30
71
71
71
64
71
71
86
86
76
76
86
86
84
84
99
81
89
102
89
89
109
102
102
119
119
119
135
135
135
152
160
165
173
165
173
156
118
173
156
173
152
D
Inches
2.40
1.98
1.98
1.98
1.98
1.98
1.98
1.73
1.98
1.98
2.35
2.60
2.10
2.10
2.62
2.48
2.10
2.10
2.75
2.10
2.48
2.60
2.35
2.35
3.10
2.60
2.75
3.16
3.16
3.16
3.66
3.16
3.16
3.91
3.47
3.47
4.16
3.30
3.66
4.16
3.16
3.66
4.16
3.16
3.47
mm
61.0
50.3
50.3
50.3
50.3
50.3
50.3
43.9
50.3
50.3
59.7
66.0
53.3
53.3
66.5
63.0
53.3
53.3
69.9
53.3
63.0
66.0
59.7
59.7
78.7
66.0
69.9
80.3
80.3
80.3
93.0
80.3
80.3
99.3
88.1
88.1
105.7
83.8
93.0
105.7
80.3
93.0
105.7
80.3
88.1
E
Inches
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
1.44
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.63
3.63
3.63
3.63
3.63
3.63
3.00
3.63
3.63
3.63
3.63
mm
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
36.6
50.8
50.8
50.8
50.8
50.8
50.8
50.8
50.8
50.8
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
76.2
92.2
92.2
92.2
92.2
92.2
92.2
76.2
92.2
92.2
92.2
92.2
Weight
Lbs
4
4
3
3
4
4
4
3
4
4
5
6
7
8
11
13
9
10
18
9
12
16
11
14
20
14
16
30
23
28
39
24
27
41
25
33
61
29
37
74
29
43
64
41
50
See www.mtecorp.com “Line load Reactors” for current dimensions and CAD details
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
16 of 31
INSTR-011 REL. 060227
Mass
Kg
1.8
1.8
1.4
1.4
1.8
1.8
1.8
1.4
1.8
1.8
2.3
2.7
3.2
3.6
5.0
5.9
4.1
4.5
8.2
4.1
5.4
7.3
5.0
6.3
9.1
6.3
7.3
14
10
13
18
11
12
19
11
15
28
13
17
34
13
20
29
19
23
MTE AC Line / Load Reactors
User Manual
Mechanical Data Open Type Cont.
MTE
Cat. No.
RL-20001B14
RL-20002B14
RL-20003B14
RL-25001B14
RL-25002B14
RL-25003B14
RL-32001B14
RL-32002B14
RL-32003B14
RL-40001B14
RL-40002B14
RL-40003B14
RL-50001
RL-50002
RL-50003
RL-60001
RL-60002
RL-60003
RL-75001
RL-75002
RL-75003
RL-85001
RL-85002
RL-85003
RL-100001
RL-100002
RL-100003
RL-120001
RL-120002
RL-120003
RL-140001
RL-140002
RL-140003
RL-150001
RL-150002
RL-150003
RL-180001
RL-180002
RL-180003
RL-210001
RL-210002
A
Inches
9.0
9.0
10.8
9.0
10.8
14.4
10.8
10.8
14.4
10.8
15.0
14.4
10.8
14.4
14.4
14.4
14.4
14.4
14.4
14.4
14.4
20.3
22.0
22.5
21.6
20.3
20.3
22.5
21.5
16.8
22.0
19.0
22.0
22.0
16.9
22.0
22.0
22.0
22.0
24.0
24.0
B
C
D
E
mm Inches mm Inches mm Inches mm Inches mm
229
7.5
191
7.3
185 4.16 105.7 3.63
92.2
229
7.5
191
8.3
211 4.41 112.0 3.63
92.2
274
8.3
211 10.0 254 5.91 150.1 3.63
92.2
229
7.5
191
9.0
229 4.19 106.4 3.63
92.2
274
8.5
216
9.0
229 5.16 131.1 4.60 116.8
366 11.2 284 10.3 262 5.82 147.8 4.60 116.8
274
9.0
229
8.3
211 5.16 131.1 4.60 116.8
274
9.0
229 10.0 254 5.88 149.4 4.60 116.8
366 11.3 286 10.5 267 7.13 181.1 4.60 116.8
274 10.0 254 10.0 254 5.16 131.1 4.60 116.8
381 11.3 286 11.5 292 6.76 171.7 4.60 116.8
366 11.3 286 12.5 318 7.26 184.4 4.60 116.8
274
9.0
229 10.5 267 5.50 139.7 4.60 116.8
366 11.5 292 11.5 292 6.76 171.7 4.60 116.8
366 11.5 292 13.3 338 9.76 247.9 4.60 116.8
366 11.5 292 10.0 254 5.26 133.6 4.60 116.8
366 11.3 286 12.0 305 8.00 203.2 4.60 116.8
366 11.3 286 15.0 381 9.26 235.2 4.60 116.8
366 11.5 292 11.0 279 6.63 168.4 7.20 182.9
366 11.5 292 12.5 318 8.01 203.5 7.20 182.9
366 14.5 368 14.0 356 9.26 235.2 7.20 182.9
514 16.8 425 13.0 330 7.60 193.0 7.20 182.9
559 16.8 425 13.0 330 8.00 203.2 7.20 182.9
572 16.8 427 18.0 457 9.00 228.6 7.20 182.9
549 16.8 425 11.0 279 7.26 184.4 7.20 182.9
514 16.8 425 13.0 330 8.50 215.9 7.20 182.9
514 16.8 425 15.0 381 10.76 273.3 7.20 182.9
572 17.0 432 13.0 330 11.00 279.4 7.20 182.9
546 17.0 432 20.0 508 10.76 273.3 7.20 182.9
427 17.0 432 18.5 470 11.00 279.4 7.20 182.9
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
483 17.0 432 19.0 483 11.00 279.4 7.20 182.9
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
429 17.0 432 16.0 406 11.00 279.4 7.20 182.9
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
559 17.0 432 22.0 559 10.38 263.7 7.20 182.9
559 17.0 432 22.0 559 11.00 279.4 7.20 182.9
610 18.0 457 24.0 610 11.00 279.4 7.20 182.9
610 18.0 457 24.0 610 11.00 279.4 7.20 182.9
Weight Mass
Lbs
Kg
38
17
54
24
100
45
47
21
80
36
125
57
80
36
102
46
160
73
84
38
118
54
149
68
93
42
118
54
210
95
120
54
175
79
270
122
140
63
190
86
265
120
285
129
370
168
452
205
320
145
408
185
589
267
425
193
440
200
560
254
500
227
525
238
850
385
635
288
675
306
900
408
700
317
860
390
1090
494
800
363
970
440
See www.mtecorp.com “Line load Reactors” for current dimensions and CAD details
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
17 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
NEMA1 Mechanical Data
Catalog
Number
RL-00211
RL-00212
RL-00213
RL-00214
RL-00411
RL-00412
RL-00413
RL-00414
RL-00811
RL-00812
RL-00813
RL-00814
RL-01211
RL-01212
RL-01213
RL-01811
RL-01812
RL-01813
RL-02511
RL-02512
RL-02513
RL-03511
RL-03512
RL-03513
RL-04511
RL-04512
RL-04513
RL-05511
RL-05512
RL-05513
RL-08011
RL-08012
RL-08013
RL-10011
RL-10012
RL-10013
RL-13011
RL-13012
RL-13013
RL-16011
RL-16012
RL-16013
Cabinet
Number
CAB-8
CAB-13V
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
Weight
Lbs
11
11
11
10
11
11
12
13
14
15
18
20
16
17
25
16
19
34
29
32
38
32
34
48
41
46
57
42
45
59
43
51
79
47
55
92
47
61
82
59
68
85
18 of 31
Mass
Kg
5
5
5
5
5
5
5
6
6
7
8
9
7
8
11
7
9
15
13
15
17
15
15
22
19
21
26
19
20
27
20
23
36
21
25
42
21
28
37
27
31
39
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
MECHANICAL DATA NEMA 1 Cont.
Catalog
Number
RL-20011B14
RL-20012B14
RL-20013B14
RL-25011B14
RL-25012B14
RL-25013B14
RL-32011B14
RL-32012B14
RL-32013B14
RL-40011B14
RL-40012B14
RL-40013B14
RL-50011
RL-50012
RL-50013
RL-60011
RL-60012
RL-60013
RL-75011
RL-75012
RL-75013
RL-85011
RL-85012
RL-85013
RL-100011
RL-100012
RL-100013
RL-120011
RL-120012
RL-120013
RL-140011
RL-140012
RL-140013
RL-150011
RL-150012
RL-150013
RL-180011
RL-180012
RL-180013
RL-210011
RL-210012
RL-210013
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
Cabinet
Number
CAB-13V
CAB-17V
CAB-26C
CAB-30B
CAB-42C
19 of 31
Weight
Lbs
56
72
118
65
107
152
107
129
187
111
145
176
120
262
354
264
319
414
299
349
424
444
529
611
479
567
748
584
599
719
803
828
1153
938
978
1203
1003
1163
1393
1103
1273
1573
Mass
Kg
25
33
54
30
49
69
49
59
85
50
66
80
54
119
161
120
145
188
136
158
192
202
240
277
217
257
340
265
272
326
365
376
523
426
444
546
455
528
632
501
578
714
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Recommended conduit entry for Floor Mounted
NEMA 1 enclosed reactors
Note: The entry locations shown above are for reference only. The electrician installing the reactor
guided by the local codes determines the final entry wiring. MTE does not pre- punch entry holes or
provide wiring hardware with the standard product.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
20 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
ENCLOSURE DIMINSIONS
CAB-8
CAB-12C
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
21 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
ENCLOSURE DIMENSIONS
CAB-13V
CAB-17V
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
22 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
ENCLOSURE DIMENSIONS
CAB-17C
CAB-26C
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
23 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
ENCLOSURE DIMENSIONS
CAB-30B
CAB-42C
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
24 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
TECHNICAL DATA
Catalog
Number
RL-00101
RL-00102
RL-00103
RL-00104
RL-00201
RL-00202
RL-00203
RL-00204
RL-00401
RL-00402
RL-00403
RL-00404
RL-00801
RL-00802
RL-00803
RL-00804
RL-01201
RL-01202
RL-01203
RL-01801
RL-01802
RL-01803
RL-02501
RL-02502
RL-02503
RL-03501
RL-03502
RL-03503
RL-04501
RL-04502
RL-04503
RL-05501
RL-05502
RL-05503
RL-08001
RL-08002
RL-08003
RL-10001
RL-10002
RL-10003
RL-13001
RL-13002
RL-13003
RL-16001
RL-16002
RL-16003
Watts Loss
(watts)
13.5
12.8
11.9
9.6
8
12
16
11
15
20
20
21
20
29
26
28
26
31
41
36
43
43
48
52
61
49
54
54
54
62
65
64
67
71
82
86
96
94
84
108
108
180
128
116
149
138
Wire Range
(AWG)
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 14
22 – 5
22 – 5
22 – 5
22 – 5
22 – 5
22 – 5
22 – 5
22 – 5
22 – 5
22 – 5
22 – 5
18 – 4
18 – 4
18 – 4
18 – 4
6–0
6–0
6–0
6–0
6–0
6–0
6–0
6–0
6–0
2 – 0000
2 – 0000
2 – 0000
2 – 0000
2 – 0000
2 – 0000
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
Terminal Torque
(in – lbs)
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
6-4(45) & 2-0(50)
150
150
150
150
150
150
25 of 31
Ind.
mH
100
50
36
18
12
20
32
6
3
6.5
9
12
1.5
3
5
7.5
1.25
2.5
4.2
0.8
1.5
2.5
0.5
1.2
1.8
0.4
0.8
1.2
0.3
0.7
1.2
0.25
0.5
0.85
0.2
0.4
0.7
0.15
0.3
0.45
0.1
0.2
0.3
0.075
0.15
0.23
Fund
Amps
1
1
1
1
2
2
2
2
4
4
4
4
8
8
8
8
12
12
12
18
18
18
25
25
25
35
35
35
45
45
45
55
55
55
80
80
80
100
100
100
130
130
130
160
160
160
Max
Amps
1.5
1.5
1.5
1.5
3
3
3
3
6
6
6
6
12
12
12
12
18
18
18
27
27
27
37.5
37.5
37.5
52.5
52.5
52.5
67.5
67.5
67.5
82.5
82.5
82.5
120
120
120
150
150
150
195
195
195
240
240
240
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
TECHNICAL DATA (cont’d)
Catalog
Number
RL-20001B14
RL-20002B14
RL-20003B14
RL-25001B14
RL-25002B14
RL-25003B14
RL-32001B14
RL-32002B14
RL-32003B14
RL-40001B14
RL-40002B14
RL-40003B14
RL-50001
RL-50002
RL-50003
RL-60001
RL-60002
RL-60003
RL-75001
RL-75002
RL-75003
RL-85001
RL-85002
RL-85003
RL-90001
RL-90002
RL-90003
RL-100001
RL-100002
RL-100003
RL-120001
RL-120002
RL-120002
RL-140001
RL-140002
RL-140003
RL-150001
RL-150002
RL-150003
Watts Loss
(watts)
124
168
146
154
231
219
224
264
351
231
333
293
266
340
422
307
414
406
427
630
552
798
930
1133
860
1020
1365
940
1090
1500
980
1130
1550
1523
1680
1432
1671
1815
Wire Range
(AWG)
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper Tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Copper tab
Terminal Torque
(in – lbs)
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Ind
mH
0.055
0.11
0.185
0.045
0.09
0.15
0.04
0.075
0.125
0.03
0.06
0.105
0.025
0.05
0.085
0.02
0.04
0.065
0.015
0.029
0.048
0.015
0.027
0.042
0.013
0.025
0.04
0.011
0.022
0.038
0.009
0.019
0.03
0.008
0.016
0.027
0.008
0.015
0.025
Fund
Amps
200
200
200
250
250
250
320
320
320
400
400
400
500
500
500
600
600
600
750
750
750
850
850
850
900
900
900
1000
1000
1000
1200
1200
1200
1400
1400
1400
1500
1500
1500
Max
Amps
300
300
300
375
375
375
480
480
480
600
600
600
750
750
750
900
900
900
1125
1125
1125
1063
1063
1063
1125
1125
1125
1250
1250
1250
1500
1500
1500
1750
1750
1750
1875
1875
1875
Contact factory for higher ratings.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
26 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
INSTALLATION INSTRUCTIONS
Open Line/Load Reactor Installation
NEMA 1 Line/Load Reactor Installation
MTE line/load reactors are available in open
construction and in NEMA 1 enclosures.
Open reactors are designed for mounting within
an appropriate electrical equipment
enclosure. Reactors rated 300 amperes RMS
and under are designed for mounting in both a
vertical and horizontal position. Larger
reactors must be mounted in a horizontal
position typically on the floor of the enclosure.
Include the power dissipation of the reactor
along with all the other components located in
the enclosure to determine the internal
temperature rise and cooling requirements
of the enclosure.
Top conduit entry recommended for
NEMA 1 enclosed reactors.
MTE line/load reactors mounted in enclosures
with part number, CAB-8, are designed for
wall mounting. All other enclosures are
designed for floor mounting.
WARNING
Reactors may be located in any region of the
enclosure where the ambient temperature
does not exceed 45 degrees C. Allow a minimum
side clearances of four (4) inches and vertical
clearances of six (6) inches for proper heat
dissipation and access. Do not locate the
reactor next to resistors or any other component
with operating surface temperatures above 125
degree C.
Select a well ventilated, dust-free area away from
direct sunlight, rain or moisture. Do not install in or
near a corrosive environment. Avoid locations
where the reactor will be subjected to
excessive vibrations.
MTE NEMA 1 enclosures designed for floor
mounting must be mounted with the
enclosure base horizontal for proper
ventilation. Wall mounting a floor
mounted enclosure with the base against
the wall will cause the reactor to over heat
resulting in equipment damage.
Allow a minimum side, front, and back
clearances of twelve (12) inches and vertical
clearances of eighteen (18) inches for proper
heat dissipation and access. Do not locate the
enclosure next to resistors or any other
component with operating surface temperatures
above 125 degree C.
Select a well ventilated, dust-free area away
from direct sunlight, rain or moisture
where the ambient temperature does not
exceed 40 degrees C.
Do not install in or near a corrosive environment.
Avoid locations where the reactor will be
subjected to excessive vibrations.
Where desirable, enclosures may be mounted
on vibration isolating pads to reduce audible
noise. Standard vibration control pads made
from neoprene or natural rubber and
selected for the weight of the enclosed reactor
are effective. Using flexible conduit is also
helpful in abatement of audible noise.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
27 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Power Wiring Connection
WARNING
WARNING
Input and output power wiring to the
reactor should be performed by
authorized personnel in accordance
with the NEC and all local electrical
codes and
REGULATIONS
Verify that the power source to which the reactor
is to be connected is in agreement with the
nameplate data on the reactor. A fused
disconnect switch or circuit breaker should be
installed between the reactor and its source of
power in accordance with the requirements of
the NEC and all local electrical codes and
regulations. Refer to the drive, inverter, or other
electrical equipment user manual for selection of
the correct fuse rating and class.
The reactor is suitable for use on a circuit
capable of delivering not more than 65,000 rms
symmetrical amperes at 480 volts when
protected by Bussman type JJS, KTK, KTK-R,
SPP or T class fuses.
Reactor are designed for use with copper
conductors with a minimum temperature rating
of 75 degrees C. Table 2 lists the wire range and
terminal torque requirements for the power input
and output connections by reactor part number.
Refer to Figure 4 for typical electrical diagrams
describing the application of reactors in both line
and load applications. For reactors supplied as a
component part of a drive system or a
component part of power electronic apparatus
follow the interconnection diagram supplied by
the System Engineer.
Failure to connect reactors supplied
as a component part of a drive
system or other power electronic
system according to the system
interconnection diagram supplied by
the System Engineer will result in
equipment damage, injury, or death.
WARNING
If a line reactor or a line reactor and a load
reactor are used with a drive equipped with a
bypass circuit, the reactors must be removed
from the motor circuit in the bypass mode.
Damage to the motor and other equipment will
result if this warning is not observed.
Grounding
A stud is provided on enclosed reactors for
grounding the enclosure. The enclosure must be
grounded. Open reactors must be grounded at
the designated grounding terminal or the reactor
mounting holes if no designated grounding
terminal is provided.
WARNING
The frame of line/load reactors must be
grounded at the designated grounding terminal
or one of the reactor mounting holes if no
designated grounding terminal is provided. The
enclosure of reactors supplied in enclosures
must be grounded.
INJURY OR DEATH MAY RESULT IF
SAFETY PRECAUTIONS ARE NOT
OBSERVED.
Where desirable, a flexible conduit connection to
the reactor enclosure should be made to reduce
audible noise.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
28 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Typical Connection Diagrams
Fig 4a LINE Reactor
Connects between power source and VFD
Fig. 4b LOAD Reactor
Connects between ASD and load (motor)
Fig 4c Use individual Line Reactors for
independent start/ stop drives connected to a
common power source. If inverters are slaved
and will always run together a single reactor
sized for total motor current may be used.
Figure 5.Single Phase connection diagram.
Standard three phase reactors may be used for single phase applications. Refer to application note
AN0102 for proper selection. Application Notes are available on our website at www.mtecorp.com.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
29 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
Sequence of Operation
1. Read and follow safety precautions.
2. After installation, ensure that:
• All Reactor ground terminals are connected to ground.
• Power wiring to the utility, drive and motor is in accordance with the
interconnection diagrams supplied by the System Engineer.
3. Check that moisture has not condensed on the Reactor. If moisture is
present, do not proceed with startup until the moisture has been removed.
4. Proceed with startup according to the instructions provided by the system
supplier.
WARNING
Reactors are a component part of an electrical system. Do not proceed with startup until
the system startup instructions provided by the System Engineer are understood and
followed. Injury, death and damage to equipment may result if the system startup
instructions are not followed.
WARNING
Use extreme caution to avoid contact with line voltage when checking for
power.
INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE
NOT OBSERVED.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
30 of 31
INSTR-011 REL. 060227
MTE AC Line / Load Reactors
User Manual
STARTUP
Safety Precautions
Before startup, observe the following warnings and instructions:
WARNING
A Reactor is at line potential when the Reactor is connected to the utility. This voltage
is extremely dangerous and may cause death or severe injury if you come in contact
with it.
WARNING
High voltage is used in the operation of line/load reactors. Use Extreme caution to
avoid contact with high voltage when operating, installing or repairing equipment
containing line/load reactors. Line/load reactors are used in conjunction with
inverters, or other electrical equipment that may feedback lethal voltages.
Follow the safety instructions in the equipment used with the reactor in addition
to the safety instruction in this manual.
INJURY OR DEATH MAY RESULT IF SAFETYPRECAUTIONS ARE NOT
OBSERVED.
Data subject to change without notice
See www.mtecorp.com for current data and CAD drawings
31 of 31
INSTR-011 REL. 060227

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement