ENGLISH

Quick start guide - Altistart 22

Preliminary information

Information below is designed to use for simple applications with 2-wire control mode and freewheel stop.

If you need more information, or for other applications, see the User manual on www.schneider-electric.com

. For a hard copy, contact your local sales Office or Schneider Electric representative.

Note:

DO NOT USE this guide for Altistart 22 connected inside the delta of the motor (it means Altistart 22 connected to the motor with delta connections in series with each motor windings). In this case, see User manual on www.schneider-electric.com

.

Read and understand these instructions before performing any procedure with this soft starter.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION AND ARC FLASH

Read and understand this manual before installing or operating the Altistart 22 starter. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.

• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment.

• Many parts of this soft starter, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.

• DO NOT touch unshielded components or terminal strip screw connections with voltage present.

• Before servicing the starter:

- Disconnect all power, including external control power that will be present.

- Place a “DO NOT TURN ON” label on all power disconnects.

- Lock all power disconnects in the open position.

• Before applying power section close the enclosure.

Failure to follow these instructions will result in death or serious injury.

Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by

Schneider Electric for any consequences out of the use of this material.

Check the delivery of the soft starter

Remove Altistart 22 from the packaging and check that it has not been damaged.

WARNING

DAMAGED SOFT STARTER EQUIPMENT

Do not operate or install any soft starter or soft starter accessory that appears damaged.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Check that the soft starter reference on the nameplate is similar to the purchase order delivery note.

Write the soft starter model Reference: ATS22 ______

and Serial Number :___________________

Check the line voltage compatibility

Check that the line voltage is compatible with the supply range of the soft starter.

Line voltage __________ Volts Soft starter voltage range ______________ Volts

Control voltage _______ Volts Soft starter control voltage range _______ Volts

Mount the soft starter vertically

For a surrounding air temperature up to 40 °C (104°F) .

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION AND ARC FLASH

ATS22 soft starters are open devices and must be mounted in a suitable enclosure.

Failure to follow these instructions will result in death or serious injury.

For other thermal conditions, see user manual on www.schneider-electric.com

.

www.schneider-electric.com 1/4 S1A10388 - 08/2009

Connect the soft starter

For ATS22 ppp Q or ATS22 ppp S6

2-wire control, freewheel stop a) Connect Power:

- Wire the soft starter to the ground.

- Wire the soft starter to the line supply: 1/L1 – 3/L2 – 5/L3.

- Check that the motor voltage is compatible with the soft starter voltage.

- Wire the soft starter to the motor.

(1) Check the operating limits of the contact.

(2) Select a voltage transformer in accordance with the mains voltage.

b) Connect Control:

Check that the control supply

is 230V

for CL1 and CL2.

- Remove the red sticker which covers the CL1-CL2 terminals.

- Wire control supply: CL1 and CL2.

- Wire logical inputs: LI1 and LI2.

- Wire the relay: R2A and R2C.

Note: For additional information in order to size the protective and control devices, refer to the catalog or the user manual available on www.schneider-electric.com

www.schneider-electric.com 2/4 S1A10388 - 08/2009

Connect the soft starter

For ATS22 ppp S6U

2-wire control, freewheel stop a) Connect Power:

- Wire the soft starter to the ground.

- Wire the soft starter to the line supply: 1/L1 – 3/L2 – 5/L3.

- Check that the motor voltage is compatible with the soft starter voltage.

- Wire the soft starter to the motor.

(1) Check the operating limits of the contact.

(2) Select a voltage transformer in accordance with the mains voltage.

b) Connect Control:

Check that the control supply

is 110V

for CL1 and CL2.

- Remove the red sticker which covers the CL1-CL2 terminals.

- Wire control supply: CL1 and CL2.

- Wire logical inputs: LI1 and LI2.

- Wire the relay: R2A and R2C.

Note: For additional information in order to size the protective and control devices, refer to the catalog or the user manual available on www.schneider-electric.com

www.schneider-electric.com 3/4 S1A10388 - 08/2009

Power on the control

• Check that S3 is open.

• Switch on: Q1, Q2, Q3 and Q4.

• The soft starter displays nrdY.

Adjust

UIn

line voltage

• Push scroll down button to reach conF menu.

Adjust

In

motor rated current

• In conF menu

Push scroll down button to reach In parameter.

• See Nominal Motor Current on Motor Nameplate • Push scroll down button to reach UIn parameter.

• Set UIn to the main line voltage ac value, using scroll Up/down.

• Push button to validate the UIn value.

(Motor Full Load Amps) in STAR connection, note the “Amps” value.

Set In to this value using scroll Up/down.

Push button to validate the In value.

Apply power to the Altistart 22 and start the motor

• Close the enclosure.

• Push S2 button.

• The soft starter displays rdY .

• Close S3, the motor starts.

Factory settings

The Altistart 22 is factory configured for most standard applications. If the factory configuration is not suitable for your application, refer to

User manual on www.schneider-electric.com. Here is the list of writable parameters in an “easy start up” mode.

Menu Code Description Factory setting Customer setting conF

Configuration

ICL dLtA

UIn

In

Cod

LAC t90

ILt tLS

Soft starter rated current

Connection type (Line or delta)

Line voltage

Motor rated current

Setting lock

Advanced mode

Initial voltage

Current limit

Max start time

According to the soft starter rating

LInE

ATS22 pppQ range: 400 Vac

ATS22 pppS6-S6U ranges: 480 Vac

According to the soft starter rating nLoC (Not locked) oFF

30 % of input voltage

350 % of In

IS s

SEt

Adjustments

ACC dEC

Acceleration time

Deceleration time

ID s

FrEE (Freewheel)

EdC tHP

Final torque

Motor thermal protection

O

IO (IEC class 10) rdY : soft starter ready, when power and control voltage are present and the motor is not operating.

nrdY : when power is not supplied and control voltage is supplied or when power and control voltage are present with LI1 not connected and

LI2 present (run command).

Short-circuit rating and branch circuit protection

(use in place of Q1 shown on page 2 and 3)

Recommended fuse ratings for UL and CSA requirements. Components for use together in accordance with standard UL508

ATS22

Stand-alone product

Max. short circuit current rating (SCCR)

X

Branch circuit protection

Rating

Soft starter 208/600 V- 60 Hz (+10% -15%) - Standard rating.

ATS22D17ppp

ATS22D32ppp

ATS22D47ppp

ATS22D62ppp

ATS22D75ppp

ATS22D88ppp

ATS22C11ppp

ATS22C14ppp

ATS22C17ppp

ATS22C21ppp

ATS22C25ppp

ATS22C32ppp

ATS22C41ppp

ATS22C48ppp

ATS22C59ppp

5 kA

10 kA

18 kA

30 kA

Z1 (1)

AJT40

AJT70

AJT100

AJT125

AJT175

AJT200

AJT250

AJT300

AJT400

AJT500

AJT600

2 x AJT350

2 x AJT400

2 x AJT500

2 x AJT600

Z2

40 A

70 A

100 A

125 A

175 A

200 A

250 A

300 A

400 A

500 A

600 A

2 x 350 A

2 x 400 A

2 x 500 A

2 x 600 A

Suitable for use on a circuit capable of delivering not more than

___X____ rms symmetrical Amperes, 575 Volts maximum, when protected by ___Z 1____ with a maximum rating of___Z 2___.

(1) Ferraz Shawmut manufacturer.

www.schneider-electric.com 4/4 S1A10388 - 08/2009

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals