Airblock FG
Air handling unit with EC single-phase motor
Airblock FG modules for heating, cooling and ventilating
Installation and Operating Instructions
Keep these instructions in a safe place for future use!
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Key to symbols:
1. Intended Use ................................................................................. 4
Caution! Danger!
2. Safety Information ....................................................................... 5
Failure to comply with these instructions can result in serious personal injury ordamage to property.
Danger from
electrocution!
Failure to comply with these instructions can result in serious personal injury or damage to property from electrocution.
Please read these instructions carefully before starting assembly and installation work!
All persons involved in installation, commissioning and use of this product have a duty to pass these instructions onto parallel or subsequent trades right through to the end user or operator. Please retain these instructions until the unit is finally decommissioned!
3. Operation ...................................................................................... 6
4. Standard System Set-up ............................................................... 7
5. Supply Air Module (incl. heat exchanger and F7-filter) ............ 10
5.1 Unit Construction .......................................................................... 10
5.2 Installation ..................................................................................... 11
5.3 Hydraulic Connection .................................................................... 11
5.4 Electrical Wiring ............................................................................. 12
5.5 Control Components ..................................................................... 13
5.6 Maintenance ................................................................................. 14
5.6.1 Safety Information ...................................................................... 14
5.6.2 Opening the Service Hatch ......................................................... 14
5.6.3 Housing ...................................................................................... 15
5.6.4 Fan Motor .................................................................................. 15
5.6.5 Cu/Al Heat Exchanger ................................................................. 15
5.6.6 Filter Change .............................................................................. 16
6. Exhaust Air Module ...................................................................... 17
6.1 Unit Construction .......................................................................... 17
6.2 Installation ..................................................................................... 18
6.3 Electrical Wiring ............................................................................. 18
6.4 Control Components ..................................................................... 20
6.5 Maintenance ................................................................................. 21
6.5.1 Safety Information ...................................................................... 21
6.5.2 Opening the Service Hatch ......................................................... 21
6.5.3 Housing ...................................................................................... 22
6.5.4 Fan Motor .................................................................................. 22
7. Commissioning the Fan Modules ................................................ 23
8. Connecting Airblock Modules ..................................................... 24
Changes to the content or design can be made without prior notification!
9. Heat Recovery Module ................................................................. 25
9.1 Unit Construction .......................................................................... 25
9.2 Installation ..................................................................................... 26
9.3 Control Components ..................................................................... 27
9.4 Maintenance ................................................................................. 27
9.4.1 Safety Information ...................................................................... 28
9.4.2 Opening the Service Hatches ...................................................... 28
9.4.3 Housing ...................................................................................... 29
9.4.4 Counterflow Heat Exchanger ...................................................... 29
9.4.5 Filter Change .............................................................................. 32
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
10. Chiller Module ............................................................................. 33
10.1 Unit Construction ........................................................................ 33
10.2 Installation ................................................................................... 34
10.3 Hydraulic Connection .................................................................. 35
10.4 Control Components ................................................................... 36
10.5 Maintenance ............................................................................... 37
10.5.1 Safety Information .................................................................... 37
10.5.2 Opening the Service Hatches .................................................... 37
10.5.3 Housing .................................................................................... 38
10.5.4 Cu/Al Heat Exchanger ............................................................... 38
10.5.5 Filter Change (Optional) ............................................................ 39
11. Bag Filter Module ....................................................................... 40
11.1 Unit Construction ........................................................................ 40
11.2 Installation ................................................................................... 41
11.3 Control Components ................................................................... 42
11.4 Maintenance ............................................................................... 43
11.4.1 Safety Information .................................................................... 43
11.4.2 Opening the Service Hatches .................................................... 43
11.4.3 Housing .................................................................................... 44
11.4.4 Filter Change ............................................................................ 44
12. Particle Filter Module ................................................................. 45
12.1 Unit Construction ........................................................................ 45
12.2 Installation ................................................................................... 46
12.3 Control Components ................................................................... 47
12.4 Maintenance ............................................................................... 48
12.4.1 Safety Information .................................................................... 48
12.4.2 Opening the Service Hatches .................................................... 48
12.4.3 Housing .................................................................................... 49
12.4.4 Filter Change ............................................................................ 49
13. Spare Parts .................................................................................. 50
13.1 Filter ............................................................................................ 50
13.2 Control Components ................................................................... 50
3
4
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
1. Intended Use
The Kampmann Airblock range offers an all-purpose air handling system for a range of different applications. Kampmann Airblock units are built in line with the state of the art and recognised safety regulations. Nevertheless their use can result in danger to people or damage to the unit or other material property if they are not properly installed or properly used.
The units are solely intended for heating, cooling and ventilation. Any use other than the use specified above is deemed not to be correct and proper.
The user/operator of the unit alone will be liable for any damage resulting from this. Correct and proper use is deemed to include observing the instructions relating to safety, operation and commissioning/maintenance.
Any sound-absorbing measures needed, such as isolation of the air ducts, have to be done on site!
Protect the products from any moisture during storage and installation.
Check the application with the manufacturer in case of any doubt. Any use other than the use specified above is deemed not to be correct and proper.
The operator of the unit is solely responsible for any damage arising as a result of this.
The installation of this product requires specialist knowledge of heating, cooling, ventilation and electrical engineering. This knowledge, generally learned in vocational training in the fields mentioned in section 2, is not described separately. Damage caused by improper installation is the responsibility of the operator.
Airblock supply air modules are not suitable for connecting to cold water!
Chiller modules from the accessories range are intended for use for cooling mode. These are suitable for connection to CPW (cold potable water, type
**302140) or for refrigerant (type **302230) and have an integral condensation tray below the heat exchanger for a horizontal fitting position.
Operating limits for the unit
Caution! Frost protection must always be used if there is a risk of frost!
Place of installation
Airblock FG is intended for use in dry, dust-free and frost-free interior rooms and must be protected from the wind and weather. Temperatures should ideally be between 5 °C and 30 °C.
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
2. Safety Information
Installation, assembly and maintenance work on electrical units should only be performed by a qualified electrician in compliance with the VDE guidelines. Ensure that the connection complies with the applicable VDE regulations and provisions laid down by the regional electricity providers.
Non-compliance with the regulations and operating instructions can result in the units malfunctioning with consequential damage and danger to people. The units can be incorrectly wired by the wires being swapped – danger of fatal injury!
Disconnect all parts of the system from the mains power supply and prevent them from being reconnected before starting any connection and maintenance work!
Check the electrical equipment on the fan regularly (see fan operating instructions). Replace loose connections and defective cables immediately.
Electrical charge (>50 C) between the mains conductor and protective conductor connection after disconnecting the mains supply with the parallel connection of several fans (e.g. model size 7 and 9).
• Ensure that sufficient protection against accidental contact is provided.
The mains supply and PE must be short-circuited before working on the electrical supply.
There is voltage at terminals and connections even when the unit is switched off.
• Do not only the unit until 5 minutes after disconnecting the voltage at all poles.
There is electrical voltage on the rotor and impeller in the event of a fault.
The rotor and impeller have basic insulation.
• Do not touch when installed!
The fan will start up again automatically if control voltage is applied or when a speed setpoint is stored, e.g. after a power failure.
• Therefore, do not stand in the danger zone of the unit.
• Disconnect the mains voltage when working on the unit and secure it again being switched on again.
• Wait until the unit is at a standstill.
• Remove any tools used, the short-circuiting equipment or other objects from the unit after working on the unit.
High temperatures occur on the electronics housing of the fan.
• Risk of burns.
The fan has anti-lock protection.
5
6
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
3. Operation
The supply air module draws in room air or fresh air via the filter through the integral radial fan or fans and delivers this though the heat exchanger
(heating medium LPHW). The heated air is fed into the room using suitable attachments. The exhaust air module consists of the fan section. The
Airblock FG with attachments can be used for cooling (CPW, direct evaporator) or as an overpressure system with a particle filter class H13 for food stores. A bag filter module F7 (in accordance with DIN EN 779) can also be fitted.
The components described in these instructions have a connection (electrics, hydraulics, condensation connection) with the direction of the air flow to the left.
The installation and maintenance of units with the connection to the right are carried out in the same way.
Heat recovery module
Chiller module with evaporator
Chiller module
Particle filter module
Bag filter module
Exhaust air module
Supply air module
7
8
5
6
9
3
4
1
2
Weather protection grille
Weather protection grille frame
Wall duct
Mixed air unit, short
Sound absorber
Insulated connections
Airblock supply air module
Airblock chiller module CPW
Flexible pipe connection unit
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
4. Standard System Set-up
Top view
Example 1: Mixed air system
Installation in a suspended ceiling, fresh air intake through the wall; horizontal installation of the Airblock FG supply air module in a suspended ceiling.
• Recirculating air /fresh air through the mixed air unit, short, regulated.
• Height alignment to the suspended ceiling using sliding supports.
• Recirculating air intake through linear grille.
• Supply air and intake side with sound absorber for noise reduction.
• Supply air side with optional chiller module.
7
8
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Flexible pipe connection unit
Sound absorber
Compact filter unit
Insulated connections
Airblock exhaust air module
T-piece, compact
Heat recovery module (counterflow)
Louvre
Louvre, compact
90° bend, long
Empty duct
Wall duct
Weather protection grille frame
Weather protection grille
Airblock supply air module
Airblock chiller module CPW
Example 2: Heat recovery system
Installation in a suspended ceiling, fresh air intake and extract air discharge through the wall; horizontal installation of the Airblock FG supply air module in a suspended ceiling.
• Fresh air intake via a weather protection grille through the wall
• Air routing through the heat recovery module for controllable heat recovery via a bypass.
• Recirculating air / heat recovery operation through a combined mixed air unit, compact (optional), regulated.
• Post-heating of the supply air through the LPHW element in the supply air module or cooling in the chiller module (optional).
• Supply of exhaust air through a flexible pipe connection unit, air routing through the heat recovery module for heat recovery.
• Extract air routing via a louvre and weather protection grille through the outer wall.
Note: The exhaust air module is arranged on the pressure side when using the mixed air unit (optional); an arrangement on the suction side is recommended for optimum flow of the heat recovery module!
8
9
6
7
4
5
2
3
Flexible pipe connection unit
Sound absorber
Insulated connections
Pre-filter as slide-in filter G4
Airblock chiller module
Droplet separator
Airblock exhaust air module
Particle filter module
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Example 3: Overpressure system (as recirculating air system)
Installation in a suspended ceiling; horizontal installation of the Airblock FG exhaust air module in a suspended ceiling.
• Recirculating air intake through a flexible pipe connection unit and sound absorber.
• Cooling of the air (as required) through the chiller module with a mounting option for a droplet separator (optional).
• Filter insert G4 (optional) can be used as a pre-filter in the filter holder of the chiller module.
• Downstream particle filter H13.
• Air discharge through a flexible pipe connection unit with distribution to several flexible pipes (spiral ducts) and supply air slot outlets above the sales counter.
8
9
6
7
4
5
2
3
Flexible pipe connection unit
Sound absorber
Insulated connections
Airblock exhaust air module
Louvre
Wall duct
Weather protection grille
Weather protection grille frame
Top view
Example 4: Exhaust air system
Installation in a suspended ceiling, exhaust air intake through the ceiling; horizontal installation of the Airblock FG exhaust air module in a suspended ceiling.
• Air intake through a flexible pipe connection unit and sound absorber.
• Extract air routing via a louvre and weather protection grille through the outer wall.
9
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
5. Supply Air Module (incl. Heat Exchanger and F7 Filter)
5.1 Unit Construction
1
2
L
15
5
1
13
14
10
11
3
4
9
6
12
7
6
8
10
Airblock FG supply air module
7
Fig.: Securing the suspension
brackets
1
2
3
4
5
6
7
Suspension bracket with slot
(4 no., included in pack)
Flow rate transmitter (optional accessory)
Motor terminal box
Service hatch, pre-fitted*
(indicated as an opening)
Housing
230 V EC fan
Screw-on hinge for service hatch*
(2 no. pre-fitted)
8
9
10
11
12
13
14
15
Connecting strut on air discharge side
Connecting strut on air intake side
Direction of air flow
Filter insert F7
Heat exchanger
Flow connection
Return connection
Differential pressure transmitter
(optional accessory)
* The service hatch and screw-on hinges can be rotated 180° and fitted on site depending on the space requirements; the screw-in hinges can be fixed to the connecting strut on the air discharge side and the connecting strut on the air intake side. Screw the screw-in hinges to the desired connecting strut using two M6x16 countersunk screws.
Module dimensions
Model
Model 6
Model 7
Model 8
Model 9
Length
L [mm]
1000
1000
1100
1100
All dimensions are external dimensions.
Supply air module
Width W
[mm]
740
940
940
1140
Height H
[mm]
390
390
490
490
Weight
[kg]
73
87
98
119
10
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
5.2 Installation
The Airblock housing
5
has four suspension points
1
as standard as screwable mounting brackets with a slot fixing for universal installation.
All Airblock modules are suitable for the installation of accessories or attachments with standard duct connection profiles thanks to the connecting flange with several fixing holes.
• Seal all joints with sealing tape. Screws and sealing tape are included in the delivery.
• Several Airblock filter or chiller modules can be screwed together from the inside using the connection sets included.
• Make sure that there is adequate working space for the operation and maintenance of the respective Airblock modules and attachments when installing the units. This applies in particular to the connection side area
(heating medium / electrical connection
13
/
14
+
3
etc.).
• Provide rubber pads on site to decouple noises.
• Align the unit in a horizontal position.
• Please note the following: The filter
11
can only be removed from below for maintenance purposes!
• Caution: Remove the F7 filter from the supply air module with a heat recovery module combination! Only one filter level is provided for the design of the Airblock units.
• Connect the frost and filter monitoring
15
to the control (see wiring diagrams).
Note: Service hatches are to be provided on site below and alongside the modules (connection side) for the installation and maintenance of the
Airblock modules!
5.3 Hydraulic Connections
• Connect the flow and return lines
13
+
14
according to the labelling on the housing.
• Provide for a shut-off, ventilation and drainage.
Please note the following for connecting the heat exchanger
12
:
• Hold the connections on the heat exchanger with a wrench or other suitable tool when connecting the pipework.
• Note: It is intended that the heat exchanger will be removed from
the side for maintenance purposes!
11
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
5.4 Electrical Wiring
Damage can be caused by the use of incompatible switching devices and by the use of inadequate protective equipment. The manufacturer does not accept any warranty in these cases.
Only connect up in systems that have an all-pole trip breaker from the mains power with a minimum contact opening of 3 mm! Lay electrical cables so that they are tension-free and not under stress!
6
7
8
9
All models require a 230 V/ 50/60 Hz power supply and can be controlled via a combined 0-10V / PWM control input. Models 8 and 9 can be operated alternatively via an integrated MODBUS RTU interface. A 24 V power supply is also required for the operation of a flow rate and/or differential pressure transmitter.
When using residual current circuit breakers for motors with EC technology these must be sensitive to all types of current (type B). We recommend a tripping current of 300 mA and time-delayed tripping (super-resistant, characteristic K) for optimum operating safety.
First connect up the protective conductor „PE“ on the motor terminal box.
Connect the unit according to the applicable wiring diagram as indicated in the table:
Model Without flow rate transmitter
Factory-fitted CAD no.
13084
13085
13086
13087
With flow rate transmitter
Factory-fitted CAD no.
not possible not possible
13228
13229
A potential-free 250 V / 6 A (AC1) / 2 A (AC3) changeover contact is available in the motor terminal box for the switch position 0 or power failure message. A fan error message is signalled for models 8 and 9 regardless of the control type.
Electrical data for EC motor
Type
06300300/06300600
07300300/07300600
08300300/08300600
09300300/09300600
Voltage/frequency
230 V/50/60 Hz
230 V/50/60 Hz
230 V/50/60 Hz
230 V/50/60 Hz
Please refer to the fan operating instructions for more information!
Max. current
1.4 A
2.8 A
3.2 A
6.4 A
Output
0.17 kW
0.34 kW
0.73 kW
1.46 kW
12
Description of accessory
Frost protection thermostat
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
5.5 Control Components
Please refer to the enclosed technical information for technical data on the following accessories delivered separately or fitted at the factory.
Type suffix for
Airblock type
...0F0
...00D
Type of accessory/ spare part supplied separately
Model 6: 30468
Models 7, 8, 9: 30668
30267
Enclosed technical information from manufacturer
enclosed
Filter differential switch, for use with supply air module type **300300, chiller module type **302140, heat recovery module type **301700, particle filter module type ** 303130 and bag filter module type **303170
Differential pressure transmitter, filter or fan
Flow rate transmitter for flow rate control
It is possible to combine the components, e.g. ...VFP.
...00P or ...P00
...V00
enclosed enclosed
1 2 3 4
5
1
2
3
4
5
Motor terminal box
Flow rate transmitter
Differential pressure transmitter
Differential pressure switch PS 600
Cable duct for the frost protection
thermostats installed on the inside
13
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
5.6 Maintenance
5.6.1 Safety Information
Disconnect all parts of the system and secure them against being switched on again before any wiring and maintenance work!
The housing must only be opened once the motor has come to a standstill.
Risk of injury!
Check the function of all components after completing the work.
5.6.2 Opening the Service Hatches
Stand on a solid surface to carry out maintenance on the Airblock FG, e.g. a lifting platform. Do not use a ladder! Do not stand within the swivel range of the hatch!
Caution! Two people are needed to open the service hatch
4
! The hatch weights up to 20 kg depending on the model. Never open the service hatch further than 90°!
Steps:
1. Rotate the turning bolt (4 or 6 no. per service hatch) 90° inwards using the square box spanner enclosed.
2. Lower the service hatch until the safety hook automatically hooks into the lug of the housing connecting strut; the safety hook prevents the service hatch suddenly flapping downwards.
3. Lift the service hatch slightly; push back the safety hook until it can be moved past the lug of the housing connecting strut.
4. Carefully lower the service hatch to the desired position.
Opening the service hatch (simplified diagram of a module)
14
Detailed view from below
Detail: Security hooks
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
5.6.3 Housing
The galvanised, double-walled housing
5
of the Airblock modules is maintenance-free. Dirt on the outer housing has no influence on the operation of the unit. Dirt on the inside of the housing indicates a lack of maintenance.
5.6.4 Fan Motor
The external rotor motor
6
of the Airblock is maintenance-free. The motor‘s ball bearings, sealed on both sides, are greased for life. In contrast, deposits on the fan and inlet nozzle reduce the air volume and must be removed:
• Unscrew the turn bolt fasteners and open the service hatch
4
. Swivel the service hatch fully downwards. The fans are now freely accessible for cleaning purposes.
• Check the fan and inside of the housing at regular intervals (at least once a year) and clean if dirty.
Please refer to the respective fan operating instructions for more information!
Remove the protection securing the system from being switched on after completing the work.
5.6.5 Cu/Al Heat Exchanger
The heat exchanger
12
requires no maintenance if the system is properly maintained, i.e. if the filter is monitored and changed regularly. However, please proceed as follows if maintenance or repairs are required:
• Carry out a visual inspection of the heat exchanger. To do this, open the service hatch
4
.
• The heat exchanger can be removed through the side service hatch. First remove the flow and return pipes. Then loosen the screws on the heat exchanger fastenings and pull out the heat exchanger sideways.
• Observe the safety information in 5.3.
• Residual water may remain in the heat exchanger once it has been emptied.
Cleaning the heat exchanger:
• Blast the Airblock CU/AL heat exchanger with appropriate compressed air or flush the heat exchanger with a suitable medium to remove accumulated dust. Proceed extremely carefully as the aluminium fins bend very easily and then restrict the air flow! (Bent fins have to be straightened with an appropriate tool).
15
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
5.6.6 Filter Change
Filter change on the supply air module (service hatch hidden)
Observe the safety information on page 14, sections 5.6.1 and 5.6.2! Filter cartridge in a Fiberplast frame
11
(with supply air module).
• Check the filter cartridge F7
11
at least once a year (more often if necessary). The filter cartridge must be changed if it is dirty.
• Open the service hatch
4
and unlock the safety catches. Pull out the filter cartridge F7 downwards. Use a collection bag if necessary to avoid dirt and dust dropping down.
• This filter folds in the middle with model 9 units. This makes it easier to remove and it can be folded to save space with disposal so that very little dirt can drop out.
• Push the replacement filter cartridge into the filter opening and lock the filter catches. Replacement filter cartridges F7 are available as accessories.
Filter cartridges F7 cannot be recycled.
• Dispose of the dirty filter. Filter cartridges F7 are metal-free and fully incinerable.
16
Fig.: Securing the suspension brackets
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
6. Exhaust Air Module
6.1 Unit Construction
L
2
1
10
1
5
3
6
4
9
6
7
10
8
7
1
2
3
4
5
Suspension bracket with a slot
(4 no., included in pack)
Flow rate transmitter (optional accessory)
Motor terminal box
Service hatch, pre-fitted*
(indicated as an opening)
Housing
6
7
8
9
10
EC fan
Screw-on hinge for service hatch*
(2 no. pre-fitted)
Connecting strut on air discharge side
Connecting strut on air intake side
Direction of air flow
* The service hatch and screw-on hinges can be rotated 180° and fitted on site depending on the space requirements; the screw-in hinges can be fixed to the connecting strut on the air
discharge side and the connecting strut on the air intake side. Screw the screw-in hinges to the desired connecting strut using two M6x16 countersunk screws.
Module dimensions
Model
Model 6
Model 7
Model 8
Model 9
Length L
[mm]
600
600
700
700
All dimensions are external dimensions.
Exhaust air module
Width W
[mm]
Height H
[mm]
740
940
940
1140
390
390
490
490
Weight
[kg]
43
51
61
77
17
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
6.2 Installation
The Airblock housing
5
has four suspension points
1
as standard as screwable mounting brackets with a slot fixing for universal installation.
All Airblock modules are suitable for the installation of accessories or attachments with standard duct connection profiles thanks to the connecting flange with several fixing holes.
• Seal all joints with sealing tape. Screws and sealing tape are included in the delivery.
• Several Airblock filter or chiller modules can be screwed together from the inside using the connection sets included.
• Make sure that there is adequate working space for the operation and maintenance of the respective Airblock modules and attachments when installing the units. This applies in particular to the connection side area
(electrical connection
3
etc.).
• Provide rubber pads on site to decouple noises.
• Align the unit in a horizontal position.
Note: Service hatches are to be provided on site below and alongside the modules (connection side) in the case of suspended ceilings or encased units for the installation and maintenance of the Airblock modules!
6.3 Electrical Wiring
6
7
8
9
Damage can be caused by the use of incompatible switching devices and by the use of inadequate protective equipment. The manufacturer does not accept any warranty in these cases.
All models require a 230 V/ 50/60 Hz power supply and can be controlled via a combined 0-10V / PWM control input. Models 8 and 9 can be operated alternatively via an integrated MODBUS RTU interface. A 24 V power supply is also required for the operation of a flow rate and/or differential pressure transmitter.
When using residual current circuit breakers for motors with EC technology these must be sensitive to all types of current (type B). We recommend a tripping current of 300 mA and time-delayed tripping (super-resistant, characteristic K) for optimum operating safety.
Then connect up the protective conductor „PE“.
Connect the unit according to the applicable wiring diagram as indicated in the table:
Model Without flow rate transmitter
Factory-fitted CAD no.
13084
13085
13086
13087
With flow rate transmitter
Factory-fitted CAD no.
not possible not possible
13228
13229
18
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
A potential-free 250 V / 6 A (AC1) / 2 A (AC3) changeover contact is available in the motor terminal box for the switch position 0 or power failure message. A fan error message is signalled for models 8 and 9 regardless of the control type.
Electrical data for EC motor
Type
06300300/06300600
07300300/07300600
08300300/08300600
09300300/09300600
Voltage/frequency
230 V/50/60 Hz
230 V/50/60 Hz
230 V/50/60 Hz
230 V/50/60 Hz
Please refer to the respective fan operating instructions for more information!
Max. current
1.4 A
2.8 A
3.2 A
6.4 A
Output
0.17 kW
0.34 kW
0.73 kW
1.46 kW
19
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
6.4 Control Components
Please refer to the enclosed technical information for technical data on the following accessories delivered separately or fitted at the factory.
Description of accessory
Fan differential pressure transmitter
Flow rate transmitter for flow rate control
Type suffix for
Airblock type
...P00
...V00
Type of accessory/ spare part supplied separately
Enclosed technical information from manufacturer
enclosed enclosed
20
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
6.5 Maintenance
6.5.1 Safety Information
Disconnect all parts of the system and secure them against being switched on again before any wiring and maintenance work!
The housing must only be opened once the motor has come to a standstill.
Risk of injury!
Check the function of all components after completing the work.
6.5.2 Opening the Service Hatches
Stand on a solid surface to carry out maintenance on the Airblock FG, e.g. a lifting platform. Do not use a ladder! Do not stand within the swivel range of the hatch!
Caution! Two people are needed to open the service hatch
4
! The hatch weights up to 20 kg depending on the model. Never open the service hatch further than 90°!
Steps:
1. Rotate the turning bolt (4 or 6 no. per service hatch) 90° inwards using the square box spanner enclosed.
2. Lower the service hatch until the safety hook automatically hooks into the lug of the housing connecting strut; the safety hook prevents the service hatch suddenly flapping downwards.
3. Lift the service hatch slightly; push back the safety hook until it can be moved past the lug of the housing connecting strut.
4. Carefully lower the service hatch to the desired position.
Opening the service hatch (simplified diagram of a module)
Detailed view from below
Detail: Security hooks
21
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
6.5.3 Housing
The galvanised, double-walled housing
5
of the Airblock modules is maintenance-free. Dirt on the outer housing has no influence on the operation of the unit. Dirt on the inside of the housing indicates a lack of maintenance.
6.5.4 Fan Motor
The external rotor motor
6
of the Airblock is maintenance-free. The motor‘s ball bearings, sealed on both sides, are greased for life. In contrast, deposits on the fan and inlet nozzle reduce the air volume and must be removed:
• Unscrew the turn bolt fasteners and open the service hatch
4
. Swivel the service hatch fully downwards. The fans are now freely accessible for cleaning purposes.
• Check the fan and inside of the housing at regular intervals (at least once a year) and clean if dirty.
Please refer to the respective fan operating instructions for more information!
Remove the protection securing the system from being switched on after completing the work.
22
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
7. Commissioning the Fan Modules
Check the following before commissioning the unit:
- Is the protective conductor connected properly on all units?
- Are all the lines connected properly as per the wiring diagrams?
- Do all cables comply with the necessary cross-sections?
- Are both DIP switches set correctly when controlled via the MODBUS RTU interface?
Model 8: ON
Model 9: OFF
- With a flow rate and/or differential pressure transmitter: Is the voltage
24 V in each case?
• Take into account information on the commissioning of other parts of the system.
• The Airblock can be put into operation after conducting the above checks by switching on the power supply to the motor terminal box, switching on the fan modules on the motor terminal box and changing the
0-10 VDC input signal or by transmitting a signal via the MODBUS RTU interface.
Check the following after commissioning the unit:
- Are all the impellers running smoothly or are grinding noises audible?
Determine the cause as soon as grinding noises become audible.
Switching off the units:
- Switch off the unit during operation via the control input.
- Do not switch the unit off and on (e.g. in cycle mode) via the mains power.
- Make sure that the earth conductor connection is disconnected last when disconnecting the unit.
- Observe the safety information in section 2.
23
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
8. Connecting Airblock Modules
4
3
1
2
4
5
1
2
3
4
5
Node profile
Node profile guide
M8 x 16 ratchet screw
Housing
Service hatch
Fig. Airblock module (simplified diagram)
Screw the modules together using the connecting elements included in the pack. Screw two modules to four connection points in the corners of the housing.
Installation steps for a connection point:
The corners of the housing can be accessed through the service hatch. The filter inserts (M5, F7 or H13) must be removed from the module if necessary to ensure optimum accessibility.
1. Open service hatch
5
.
2. Use two tapping screws to screw the node profile
1
to the housing
4
.
3. Use two tapping screws to screw the node profile guide
2
to the adjacent housing.
4. Position the modules in such a way that the drill holes of the screwed node profile
1
, node profile guide
2
and housing are located one above the other; use the M8 x 16 ratchet screw to screw the modules to the connection point.
24
1
2
7
16
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
9. Heat Recovery Module
9.1 Unit Construction
Note: 2 service hatches are fitted on the top and underside of the units to ensure optimum accessibility for maintenance purposes.
2
1
14
L
1
W
B
12
11 4
15
9
4
10
13
8
3
4
7
6
5
7
13
17
7
1
2
3
4
5
6
7
Suspension bracket with slot
(6 no., included in pack)
Differential pressure transmitter
(optional accessory)
Counterflow heat exchanger
Service hatch, pre-fitted*
(indicated as an opening)
Housing
Bypass flap
Screw-on hinge for service hatch*
(2 no. pre-fitted)
8
9
10
11
12
13
14
15
16
17
Connecting strut on air discharge side
Connecting strut on air intake side
Condensation tray
Drain connection on condensation tray
Flap servomotor (accessory)
Filter
Extract air
Fresh air
Supply air
Exhaust air
* The service hatch and screw-on hinges can be rotated 180° and fitted on site depending on the space requirements; the screw-in hinges can be fixed to the connecting strut on the air discharge side and the connecting strut on the air intake side. Screw the screw-in hinges to the desired connecting strut using two M6x16 countersunk screws.
25
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Module dimensions
Model
Model 6
Model 7
Model 8
Model 9
Length L
[mm]
1600
1600
1900
1900
All dimensions are external dimensions.
Heat Recovery Module
Width W
[mm]
1640
Height H
[mm]
390
2040
2040
2440
390
490
490
Weight
[kg]
211
237
322
361
9.2 Installation
The Airblock housing
5
has six suspension points
1
as standard as screwable mounting brackets with a slot fixing for universal installation. All Airblock modules are suitable for the installation of accessories or attachments with standard duct connection profiles thanks to the connecting flange with several fixing holes.
The heat recovery module has a condensation tray
10
with a gradient on all sides and a condensation drain connection on the side
11
.
• Align the unit in a horizontal position!
• Any condensation produced has to be drained off individually or through a collecting line via the siphon connected to the condensation drain connection.
• Condensation must be able to drain freely. Make sure that the condensation drain connection has an appropriate free area.
• Lay a condensation line without any kinks or restrictions with a gradient to the sewage pipe on site.
• Choose the correct condensation line diameter.
• Protect the siphon in the condensation line against drying out (use a ball siphon if necessary).
Note: Service hatches are to be provided on site below and alongside the modules (connection side) for the installation and maintenance of the
Airblock modules!
Note: The filters
13
can be removed from above and below for maintenance purposes!
26
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Condensation drains
• A siphon needs to be connected to all available condensation drain connections.
• Ensure an adequate sealing water height (Hs) (see adjacent Fig.)
Sealing water height:
Hs = H + 50 mm
H = static negative pressure in the unit (mm H
2
(1 mm H
2
O = 9.81 Pa)
O)
Min. water trapp height = 60 mm
Sealing water height Hs
9.3 Control Components
Please refer to the enclosed technical information for technical data on the following accessories delivered separately or fitted at the factory.
Description of accessory Type suffix for
Airblock type
Filter differential pressure switch, for use with supply air module type **300300, chiller module type **302140, heat recovery type **301700, particle filter module type ** 303130 and bag filter module type **303170
Filter differential pressure transmitter
...00D
...00P
A 24 V power supply is also required for the operation of a filter differential pressure transmitter.
Type of accessory/ spare part supplied separately
Enclosed technical information from manufacturer
30267 enclosed
9.4 Maintenance
Observe the maintenance intervals prescribed by the legislature. The intervals are dependent on various factors (e.g. structural conditions, level of dirt, etc.) and may therefore differ from the manufacturer‘s recommendations.
If an increased level of dirty is detected during regular checks, adjust the required maintenance intervals according to the actual wear and tear.
27
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
9.4.1 Safety Information
Disconnect all parts of the system and secure them against being switched on again before any wiring and maintenance work!
The housing must only be opened once the motor has come to a standstill.
Risk of injury!
Check the function of all components after completing the work.
9.4.2 Opening the Service Hatches
Stand on a solid surface to carry out maintenance on the Airblock FG, e.g. a lifting platform. Do not use a ladder! Do not stand within the swivel range of the hatch!
Caution! Two people are needed to open the service hatch
4
! The hatch weights up to 20 kg depending on the model. Never open the service hatch further than 90°!
Steps:
1. Rotate the turning bolt (4 or 6 no. per service hatch) 90° inwards using the square box spanner enclosed.
2. Lower the service hatch until the safety hook automatically hooks into the lug of the housing connecting strut; the safety hook prevents the service hatch suddenly flapping downwards.
3. Lift the service hatch slightly; push back the safety hook until it can be moved past the lug of the housing connecting strut.
4. Carefully lower the service hatch to the desired position.
Opening the service hatch (simplified diagram of a module)
Detailed view from below
Detail: Security hooks
28
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
9.4.3 Housing
The galvanised, double-walled housing
5
of the Airblock modules is maintenance-free. Dirt on the outer housing has no influence on the operation of the unit. Dirt on the inside of the housing indicates a lack of maintenance.
Heat recovery modules are fitted with two service hatches
4
on the top and underside.
9.4.4 Counterflow Heat Exchanger
Counterflow heat exchangers
3
require no maintenance if the system is properly maintained, i.e. if the filter is monitored and changed regularly (see page 32). However, please proceed as follows if maintenance or repairs are required: Open the service hatches and carry out a visual inspection of the counterflow heat exchanger to check for dirt.
Proceed as follows if a high level of dirt is visible:
1. Unscrew the M6 flat-head screws (2 no.) from the central support and remove the central support.
2. Remove the condensation tray; loosen the M6 ratchet screws (4 no.).
• Pull out the condensation tray with drain connection from the side panel on the connection side and remove it in a downward direction.
• Please note that residual water may remain in the condensation tray.
3. Remove the counterflow heat exchanger; – unscrew the wing screws
(2 no.) until the clamping profile can move freely.
• Push the clamping profile to the side via the slots until the counterflow heat exchanger can be removed in a downward direction.
• Remove and clean the heat exchangers one by one.
• Install the components in the reverse order to removing them.
Note: The removal of the components described refers to vertically installed units. Maintenance is carried out in the same way with horizontally installed units as the service hatches and central supports are installed on both the top and underside. Only the condensation tray is installed on the underside.
The removal of the condensation tray with vertically installed units is therefore not applicable.
Cleaning the condensation tray:
Clean the condensation tray and droplet separator (optional) at regular intervals.
Cleaning the heat exchanger:
• Blast the counterflow Airblock modules with appropriate compressed air or flush the heat exchanger with a suitable medium to remove accumulated dust. Proceed extremely carefully as the aluminium fins bend very easily and then restrict the air flow! (Bent fins have to be straightened with an appropriate tool).
29
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Unscrewing the central support
Removing the condensation tray (details)
30
Removing the condensation tray
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Removing heat recovery units
X
X
31
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
9.4.5 Filter Change
Observe the safety information on page 27 + 28, sections 9.4.1 and 9.4.2!
Filter cartridge in a Fiberplast frame
13
(filter class: M5 for exhaust air and
F7 for fresh air as per DIN EN 779).
• Check the filter cartridges
13
at least once a year (more often if necessary).
The filter cartridge must be changed if it is dirty.
• Open the service hatches
4
and unlock the safety catches. Then pull out the filter cartridges downwards or upwards. The filter must be moved past the service hatch when the service hatches are fully opened to the bottom (swivel range = 1780 mm). To do this, the slide-in rail in which the filter sits can be swivelled 10°. The filter can be pulled out easily in a downward direction in a swivelled state (see dimension 1780 mm). Use a collection bag if necessary to avoid dirt and dust dropping down.
• This filter folds in the middle with model 9 units. This makes it easier to remove and it can be folded to save space with disposal so that very little dirt can drop out.
• Push the replacement filter cartridge into the filter opening and lock the filter catches. Replacement filter cartridges are available as accessories.
Filter cartridges cannot be recycled.
• Caution: Swivel the filter holder back into the vertical position before closing the service hatches!
• Dispose of the dirty filter. Filter cartridges are metal-free and fully incinerable.
X
X
X
0 - 10°
X
0 - 20°
32
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
10. Chiller Module
10.1 Unit Construction
L
1
W
B
1
2
10
7
8 6
Please refer to the enclosed instructions from the pump manufacturer for technical data on the condensation pump!
Fig.: Securing the suspension brackets
9
4
5
13
14
12
3
11
10
13
1
2
3
4
5
6
Suspension bracket with slot
(4 no., included in pack)
Differential pressure transmitter
(optional accessory)
Heat exchanger
Service hatch, pre-fitted*
(indicated as an opening)
Housing
Filter
7
8
9
10
11
12
13
14
Flow connection
Return connection
Drain connection on condensation tray
Direction of air flow
Connecting strut on air discharge side
Connecting strut on air intake side
Screw-on hinge for service hatch*
(2 no. pre-fitted)
Condensation tray
* The service hatch and screw-on hinges can be rotated 180° and fitted on site depending on the space requirements; the screw-in hinges can be fixed to the connecting strut on the air discharge side and the connecting strut on the air intake side. Screw the screw-in hinges to the desired connecting strut using two M6x16 countersunk screws.
Module dimensions
Model
Model 6
Model 7
Model 8
Model 9
Length L
[mm]
700
700
700
700
All dimensions are external dimensions.
Chiller module
Width W
[mm]
Height H
[mm]
740
940
940
1140
390
390
490
490
Weight
[kg]
49
57
63
71
33
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
10.2 Installation
The Airblock housing
5
has four suspension points
1
as standard as screwable mounting brackets with a slot fixing for universal installation.
All Airblock modules are suitable for the installation of accessories or attachments with standard duct connection profiles thanks to the connecting flange with several fixing holes.
The chiller module has a condensation tray
14
with a gradient on all sides and a condensation drain connection on the side
9
.
• Align the unit in a horizontal position!
• Any condensation produced has to be drained off individually or through a collecting line via the siphon connected to the condensation drain connection.
• Provide all water-bearing components (pipes, valves, connections) all the way to the unit with vapour diffusion-tight insulation!
• Only use suitable pipe brackets for cooling mode (refrigeration clamps).
• Install safety-related components (e.g. expansion tanks, positive pressure and overflow valves).
• Condensation must be able to drain freely. Make sure that the condensation drain connection has an appropriate free area.
• Lay a condensation line without any kinks or restrictions with a gradient to the sewage pipe on site.
• Choose the correct condensation line diameter.
• Protect the siphon in the condensation line against drying out (use a ball siphon if necessary).
Note: Service hatches are to be provided on site below and alongside the modules (connection side) for the installation and maintenance of the
Airblock modules!
Condensation drains
• A siphon needs to be connected to all available condensation drain connections.
• Ensure an adequate sealing water height (Hs) (see adjacent Fig.)
Sealing water height:
Hs = H + 50 mm
H = static negative pressure in the unit (mm H
2
(1 mm WS = 9.81 Pa)
O)
Min. water trapp height = 60 mm
Sealing water height Hs
34
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
10.3 Hydraulic Connections
• Connect the flow and return lines
7
+
8
according to the labelling on the housing.
• Provide for a shut-off, ventilation and drainage.
Please note the following for connecting the heat exchanger:
• Hold the connections on the heat exchanger with a wrench or other suitable tool when connecting the pipework.
• Make sure that there is adequate working space for the operation and maintenance of the respective Airblock modules and attachments when installing the units. This applies in particular to the connection side area
(heating medium / electrical connection
7
/
8
+
2
etc.).
• Note: It is intended that the heat exchanger
3
will be removed from the side for maintenance purposes!
35
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
10.4 Control Components
Please refer to the enclosed technical information for technical data on the following accessories delivered separately or fitted at the factory.
Description of accessory
Frost protection thermostat
Type suffix for
Airblock type
...0F0
Filter differential pressure switch, for use with supply air module type **300300, chiller module type **302140, heat recovery type **301700, particle filter module type ** 303130 and bag filter module type **303170
Filter differential pressure transmitter
...00D
...00P
It is possible to combine the components, e.g. …0FP
A 24 V power supply is also required for the operation of a filter differential pressure transmitter.
Type of accessory/ spare part supplied separately
Enclosed technical information from manufacturer
enclosed Model 6: 30468
Models 7, 8, 9: 30668
30267 enclosed
36
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
10.5 Maintenance
Observe the maintenance intervals prescribed by the legislature. Periodic maintenance is dependent on the basic conditions, see also maintenance of the heat exchanger and maintenance of the filter
6
on pages 38 and 39.
10.5.1 Safety Information
Disconnect all parts of the system and secure them against being switched on again before any wiring and maintenance work!
The housing must only be opened once the motor has come to a standstill.
Risk of injury!
Check the function of all components after completing the work.
10.5.2 Opening the Service Hatches
Note: 2 service hatches are fitted on the top and underside of the units to ensure optimum accessibility for maintenance purposes.
Stand on a solid surface to carry out maintenance on the Airblock FG, e.g. a lifting platform. Do not use a ladder! Do not stand within the swivel range of the hatch!
Caution! Two people are needed to open the service hatch
4
! The hatch weights up to 20 kg depending on the model. Never open the service hatch further than 90°!
Steps:
1. Rotate the turning bolt (4 or 6 no. per service hatch) 90° inwards using the square box spanner enclosed.
2. Lower the service hatch until the safety hook automatically hooks into the lug of the housing connecting strut; the safety hook prevents the service hatch suddenly flapping downwards.
3. Lift the service hatch slightly; push back the safety hook until it can be moved past the lug of the housing connecting strut.
4. Carefully lower the service hatch to the desired position.
37
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Opening the service hatch (simplified diagram of a module)
38
Detail: Security hooks
Detailed view from below
10.5.3 Housing
The galvanised, double-walled housing
5
of the Airblock modules is maintenance-free. Dirt on the outer housing has no influence on the operation of the unit. Dirt on the inside of the housing indicates a lack of maintenance.
Chiller modules are fitted with two service hatches
4
on the top and underside.
10.5.4 Cu/Al Heat Exchanger
The heat exchanger
3
requires no maintenance if the system is properly maintained, i.e. if the filter is monitored and changed regularly (see page
39). However, please proceed as follows if maintenance or repairs are required:
• Carry out a visual inspection of the heat exchanger. To do this, open the service hatch
4
.
• The heat exchanger can be removed through the side service hatch. To do this, first remove the flow and return pipes
7
+
8
. Then loosen the screws on the heat exchanger fastenings and pull out the heat exchanger sideways.
Check the condensation tray
14
and droplet separator (if fitted) at regular intervals and clean them if necessary.
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
Cleaning the heat exchanger:
• Blast the Airblock CU/AL heat exchanger with appropriate compressed air or flush the heat exchanger with a suitable medium to remove accumulated dust. Proceed extremely carefully as the aluminium fins bend very easily and then restrict the air flow! (Bent fins have to be straightened with an appropriate tool).
10.5.5 Filter Change (Optional)
Observe the safety information on page 37, sections 10.5.1 and 10.5.2!
Filter cartridge in a Fiberplast frame
6
(optional with the chiller unit).
If your chiller module is fitted with a filter:
• Check the filter cartridge
6
at least once a year (more often if necessary).
The filter cartridge must be changed if it is dirty.
• Open the service hatch
4
and unlock the safety catches. Pull out the filter cartridge downwards. Use a collection bag if necessary to avoid dirt and dust dropping down.
• This filter folds in the middle with model 9 units. This makes it easier to remove and it can be folded to save space with disposal so that very little dirt can drop out.
• Push the replacement filter cartridge into the filter opening and lock the filter catches. Replacement filter cartridges are available as accessories.
Filter cartridges cannot be recycled.
• Dispose of the dirty filter. Filter cartridges are metal-free and fully incinerable.
39
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
11. Bag Filter Module
11.1 Unit Construction
L
1
9
1
2
Airblock FG bag filter module
Fig.: Securing the suspension brackets
5
3
4
8
9
6
7
6
1
2
3
4
Suspension bracket with slot
(4 no., included in pack)
Differential pressure transmitter
(optional accessory)
Bag filter
Service hatch, pre-fitted*
(indicated as an opening)
5
6
7
8
9
Housing
Screw-on hinge for service hatch*
(2 no. pre-fitted)
Connecting strut on air discharge side
Connecting strut on air intake side
Direction of air flow
* The service hatch and screw-on hinges can be rotated 180° and fitted on site depending on the space requirements; the screw-in hinges can be fixed to the connecting strut on the air discharge side and the connecting strut on the air intake side. Screw the screw-in hinges to the desired connecting strut using two M6x16 countersunk screws.
Module dimensions
Model
Model 6
Model 7
Model 8
Model 9
Length L
[mm]
700
700
700
700
All dimensions are external dimensions.
Bag filter module
Width W
[mm]
Height H
[mm]
740
940
940
1140
390
390
490
490
Weight
[kg]
40
46
49
55
40
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
11.2 Installation
The Airblock housing
5
has four suspension points
1
as standard as screwable mounting brackets with a slot fixing for universal installation.
All Airblock modules are suitable for the installation of accessories or attachments with standard duct connection profiles thanks to the connecting flange with several fixing holes.
• Seal all joints with sealing tape. Screws and sealing tape are included in the delivery.
• Several Airblock filter or chiller modules can be screwed together from the inside using the connection sets included.
• Make sure that there is adequate working space for the operation and maintenance of the respective Airblock modules and attachments when installing the units. This applies in particular to the connection side area
(electrical connection
2
etc.).
• Provide rubber pads on site to decouple noises.
• Align the unit in a horizontal position.
• Note: The filter
3
can only be removed from below for maintenance purposes!
Note: Service hatches are to be provided on site below and alongside the modules (connection side) for the installation and maintenance of the
Airblock modules!
41
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
11.3 Control Components
Please refer to the enclosed technical information for technical data on the following accessories delivered separately or fitted at the factory.
Description of accessory Type suffix for
Airblock type
Filter differential pressure switch, for use with supply air module type **300300, chiller module type **302140, heat recovery type **301700, particle filter module type ** 303130 and bag filter module type **303170
Filter differential pressure transmitter
...00D
...00P
A 24 V power supply is also required for the operation of a filter differential pressure transmitter.
Type of accessory/ spare part supplied separately
Enclosed technical information from manufacturer
30267 enclosed
42
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
11.4 Maintenance
11.4.1 Safety Information
Disconnect all parts of the system and secure them against being switched on again before any wiring and maintenance work!
The housing must only be opened once the motor has come to a standstill.
Risk of injury!
Check the function of all components after completing the work.
11.4.2 Opening the Service Hatches
Stand on a solid surface to carry out maintenance on the Airblock FG, e.g. a lifting platform. Do not use a ladder! Do not stand within the swivel range of the hatch!
Caution! Two people are needed to open the service hatch
4
! The hatch weights up to 20 kg depending on the model. Never open the service hatch further than 90°!
Steps:
1. Rotate the turning bolt (4 or 6 no. per service hatch) 90° inwards using the square box spanner enclosed.
2. Lower the service hatch until the safety hook automatically hooks into the lug of the housing connecting strut; the safety hook prevents the service hatch suddenly flapping downwards.
3. Lift the service hatch slightly; push back the safety hook until it can be moved past the lug of the housing connecting strut.
4. Carefully lower the service hatch to the desired position.
Opening the service hatch (simplified diagram of a module)
Detailed view from below
Detail: Security hooks
43
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
11.4.3 Housing
The galvanised, double-walled housing
5
of the Airblock modules is maintenance-free. Dirt on the outer housing has no influence on the operation of the unit. Dirt on the inside of the housing indicates a lack of maintenance.
11.4.4 Filter Change
• Check the filter cartridge F7
3
at least once a year (more often if necessary). The bag filter must be changed if it is dirty.
• To do this, open the service hatch
4
of the bag filter module and pull out the bag filter downwards. The filter on the discharge side can be gently pressed together. Use a collection bag if necessary to avoid dirt and dust dropping down.
• Insert a replacement bag filter F7 (available as an accessory).
Bag filters F7 cannot be recycled.
Filter change on the bag filter module
(service hatch hidden)
44
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
12 Particle Filter Module
12.1 Unit Construction
L
1
W
B
9
1
2
5
4
3
8
9
6
7
Airblock FG particle filter module
Fig.: Securing the suspension brackets
6
1
2
3
4
Suspension bracket with slot
(4 no., included in pack)
Differential pressure transmitter
(optional accessory)
Particle filter
Service hatch, pre-fitted*
(indicated as an opening)
5
6
7
8
9
Housing
Screw-on hinge for service hatch*
(2 no. pre-fitted)
Connecting strut on air discharge side
Connecting strut on air intake side
Direction of air flow
* The service hatch and screw-on hinges can be rotated 180° and fitted on site depending on the space requirements; the screw-in hinges can be fixed to the connecting strut on the air discharge side and the connecting strut on the air intake side. Screw the screw-in hinges to the desired connecting strut using two M6x16 countersunk screws.
Module dimensions
Model
Model 7
Model 8
Model 9
Length L
[mm]
700
700
700
All dimensions are external dimensions.
Particle filter module
Width W
[mm]
Height H
[mm]
940
940
1140
390
490
490
Weight
[kg]
62
63
72
45
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
12.2 Installation
The Airblock housing
5
has four suspension points
1
as standard as screwable mounting brackets with a slot fixing for universal installation.
All Airblock modules are suitable for the installation of accessories or attachments with standard duct connection profiles thanks to the connecting flange with several fixing holes.
• Seal all joints with sealing tape. Screws and sealing tape are included in the delivery.
• Several Airblock filter or chiller modules can be screwed together from the inside using the connection sets included.
• Make sure that there is adequate working space for the operation and maintenance of the respective Airblock modules and attachments when installing the units. This applies in particular to the connection side area
(electrical connection
2
etc.).
• Provide rubber pads on site to decouple noises.
• Align the unit in a horizontal position.
• Note: The filter
3
can only be removed from below for maintenance purposes!
Note: Service hatches are to be provided on site below and alongside the modules (connection side) for the installation and maintenance of the
Airblock modules!
46
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
12.3 Control Components
Please refer to the enclosed technical information for technical data on the following accessories delivered separately or fitted at the factory.
Description of accessory Type suffix for
Airblock type
Filter differential pressure switch, for use with supply air module type **300300, chiller module type **302140, heat recovery type **301700, particle filter module type ** 303130 and bag filter module type **303170
Filter differential pressure transmitter
...00D
...00P
A 24 V power supply is also required for the operation of a filter differential pressure transmitter.
Type of accessory/ spare part supplied separately
Enclosed technical information from manufacturer
30267 enclosed
47
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
12.4 Maintenance
12.4.1 Safety Information
Disconnect all parts of the system and secure them against being switched on again before any wiring and maintenance work!
The housing must only be opened once the motor has come to a standstill.
Risk of injury!
Check the function of all components after completing the work.
12.4.2 Opening the Service Hatches
Stand on a solid surface to carry out maintenance on the Airblock FG, e.g. a lifting platform. Do not use a ladder! Do not stand within the swivel range of the hatch!
Caution! Two people are needed to open the service hatch
4
! The hatch weights up to 20 kg depending on the model. Never open the service hatch further than 90°!
Steps:
1. Rotate the turning bolt (4 or 6 no. per service hatch) 90° inwards using the square box spanner enclosed.
2. Lower the service hatch until the safety hook automatically hooks into the lug of the housing connecting strut; the safety hook prevents the service hatch suddenly flapping downwards.
3. Lift the service hatch slightly; push back the safety hook until it can be moved past the lug of the housing connecting strut.
4. Carefully lower the service hatch to the desired position.
Opening the service hatch (simplified diagram of a module)
48
Detailed view from below
Detail: Security hooks
Airblock FG 1.50
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
12.4.3 Housing
The galvanised, double-walled housing
5
of the Airblock modules is maintenance-free. Dirt on the outer housing has no influence on the operation of the unit. Dirt on the inside of the housing indicates a lack of maintenance.
Filter change on the particle filter module
(service hatch hidden)
12.4.4 Filter Change
The particle filter class H13
3
must be checked at least once a year and replaced on reaching the filter service life or final pressure drop:
• To do this, open the service hatch
4
on the particle filter module.
• Then loosen the clamping rod on the clamping mechanism and remove this.
• Pull out the filter carefully. Use a collection bag if necessary to avoid dirt or dust dropping down!
• Insert the replacement particle filter class H13. Pay attention to the correct direction of air flow (see arrow).
• Insert the clamping rod again and tighten this carefully to ensure that there is a good seal to the counter frame.
• Dispose of the dirty filter.
49
1.50
Airblock FG
Slimline air handling unit for decentralized, dynamic air treatment
Installation and Operating Instructions
13. Spare Parts
13.1 Filter
Overview of replacement filter types
Model Unit size
Replacement bag filter F7 for bag filter module
Replacement particle filter H13 for particle filter module
Replacement filter cartridge G4 for supply air and compact filter module, in Fiberplast frame
Replacement filter cartridge M5 for heat recovery, supply air and compact filter module, in Fiberplast frame
Replacement filter cartridge F7 for heat recovery, supply air and compact filter module, in Fiberplast frame
Model 06
06013170
06013130
06013240
06013250
06013270
Model 07
07013170
07013130
07013240
07013250
07013270
Model 08
08013170
08013130
08013240
08013250
08013270
Model 09
09013170
09013130
09013240
09013250
09013270
13.2 Control Components
Description of accessory
Frost protection thermostat
Type suffix for
Airblock type
...0F0
Type of accessory/ spare part supplied separately
Enclosed technical information from manufacturer
enclosed Model 6: 30468
Models 7, 8, 9: 30668
30267 Filter differential pressure switch, for use with supply air module type **300300, chiller module type **302140, heat recovery type **301700, particle filter module type ** 303130 and bag filter module type **303170
Differential pressure transmitter, filter or fan
...00D
...00P or ...P00
Flow rate transmitter for flow rate control ...V00
It is possible to combine the components, e.g. ...VFP.
A 24 V power supply is also required for the operation of a flow rate and / or differential pressure transmitter.
enclosed enclosed
50
Kampmann.co.uk/Airblock_FG
Kampmann GmbH
Friedrich-Ebert-Str. 128 - 130
49811 Lingen (Ems)
Germany
T
+49 591 7108-0
F
+49 591 7108-300
E
W
Kampmann.de
Kampmann UK Ltd.
Dial House, Govett Avenue
Shepperton, Middlesex, TW17 8AG
Great Britain
T
+44 (0)1932 228592
F
+44 (0)1932 228949
E
W
Kampmann.co.uk
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement