AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS

DATA BOOK

Series :

PE(H)

Cooling only

Heat pump

Model

PE-7MYC

PE-8MYC

PE-10MYC

PE-15MYC

PE-20MYC

PEH-5MYA

PEH-7MYA

PEH-8MYA

PEH-10MYA

PEH-15MYA

PEH-20MYA

Service ref.

PE-7MYC-EU

PE-8MYC-EU

PE-10MYC-EU

PE-15MYC-EU

PE-20MYC-EU

PEH-5MYA-EU

PEH-7MYA-EU

PEH-8MYA-EU

PEH-10MYA-EU

PEH-15MYA-EU

PEH-20MYA-EU

CONTENTS

SAFETY FOR USE ------------------------------------------------------2

A COMPLETE LINE UP ------------------------------------------------4

FEATURES-----------------------------------------------------------------5

DESCRIPTIONS----------------------------------------------------------5

MECHANICAL SPECIFICATIONS ----------------------------------6

TYPICAL INSTALLATION EXAMPLE ------------------------------6

MODEL-DESIGNATION BREAKDOWN ---------------------------7

SPECIFICATIONS -------------------------------------------------------8

ELECTRICAL DATA ----------------------------------------------------11

SELECTION PROCEDURE -----------------------------------------14

CAPACITY TABLES ----------------------------------------------------16

OPERATION RANGE--------------------------------------------------36

FAN PERFORMANCE-------------------------------------------------37

SOUND DATA------------------------------------------------------------40

OUTLINE DIMENSIONS----------------------------------------------41

WIRING DIAGRAMS---------------------------------------------------48

ELECTRICAL OPERATION FLOW CHARTS -------------------71

REFRIGERANT SCHEMATICS -------------------------------------74

SAFETY & CONTROL DEVICES ----------------------------------75

SPECIAL ORDER ------------------------------------------------------77

PHYSICAL DATA--------------------------------------------------------78

INSTALLATION ----------------------------------------------------------87

INSTRUCTIONS FOR USE ----------------------------------------103

HOW TO OPERATE --------------------------------------------------108

SPECIFICATION GUIDELINES ----------------------------------112

- 1 -

Specifications subject to change without notice.

SAFETY FOR USE

Before conducting installation work, please read this ''SAFETY FOR USE'' carefully

for

correct installation.

Since the caution items shown here contain important description relative to safety, please

observe them without fail.

Warning

Erroneous handling gives a high possibility to induce serious results such as

death or heavy injury.

After reading, please keep it with you together the Instruction Manual, and read it again at the

movement of the unit.

Warning

Ask your dealer or specialized subcontractor for installation.

Conducting installation work by yourself improperly may cause a fire, electric shock or water leakage.

For installation, conduct the work correctly by following the Installation Manual.

Improper installation may cause a fire, electrical shock or water leakage.

Install the unit on a spot sufficiently durable against the unit weight.

Insufficient durability can cause an injury by the falling down of unit.

All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual.

The units should be powered by dedicated power lines.

Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.

Use only the specified cables for wiring. The connections must be made secured without tension the terminals.

Improper connection or fastening can cause a fire or electrical shock.

The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.

Improper installation work can cause an injury by the falling down of the unit.

Never repair the unit, remodel or transfer it to another site by yourself.

If they are performed improperly, water leakage, electric shock or fire may result. If you need to have the unit repaired or moved, consult your dealer.

Use only the specified refrigerant (R-22) to charge the refrigerant circuit.

Do not mix it with any other refrigerant and do not allow air to remain in the circuit.

Air enclosed in the circuit can cause high pressure resulting

in a rupture and other hazards.

Ventilate the room if refrigerant leaks during

Installation.

The refrigerant heated generates poisonous gas by decomposition which can cause poisoning.

After completing installation work, make sure that refrigerant gas has not leaked.

If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases.

Please do the gas leakage inspection before starting.

Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.

The limit density is made not to be exceeded even if the refrigerant leaks by any chance.

You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused.

For the countermeasure to be taken, consult your dealer.

The outdoor unit must be installed on stable, level surface, in a place where there is no accumulation of snow , leaves or rubbish.

The outdoor unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors. The indoor unit should be securely installed.

If the unit is loosely mounted, it may fall, and cause injury.

The heating of refrigerant is noted.

When the refrigerant touches the fire etc., it was decomposed and a poisonous gas is generated.

Do not use the welding machine etc., in the room close up of the installation of the air conditioner.

The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.

Improper mounting of the cover cause electric shock or fire.

Use only optional parts authorised by Mitsubishi

Electric.

If the accessories are installed improperly, water leakage, electric shock or fire may result.

Ask your dealer or an authorised company to install them.

- 2 -

Caution

Never install on the place where a combustible gas might leak.

The gas may ignite or explode when the gas leaks and collects in surround of the unit.

Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.

The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.

When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.

The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment.

Do not wash the unit with water.

If washed with water, electric shock may be caused.

Do not handle the switch with wet hands.

Otherwise electric shock can be resulted.

For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.

As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.

Do not use the unit under a special atmosphere.

Installing the unit at the following places may cause a trouble, a place where is much machine oil, salt , humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.

Thermal insulation of the drain pipes is necessary prevent dew condensation.

If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.

Be very careful about unit transportation.

The unit should not be carried by only one person if it is more than 20kg. It occasionally causes the damage of the unit and health to be impaired.

Some unit use PP bands for packing. Do not use any PP band for delivery purpose. It may cause the injury.

Do not touch the heat exchanger fins with your bear hands.

Doing so may cut your hands.

When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it.

Be sure to safety dispose the packing materials.

Packing materials, such as catches and other metal or wooden parts, may cause stabs or other injuries.

Do not leave the mounting base being damaged.

The damaged base may cause the falling down of the unit which may give injury.

The unit should be securely installed level surface.

When the unit inclines, it causes the water leak and the breakdown.

Please confirm the horizontal with the spirit level.

Turn on the main power switch more than 6 hours before starting operation.

Do not turn the main power switch OFF during seasons of heavy use, doing so can result in failure.

Install drain piping (hose) according to this

Installation Manual to ensure proper drainage.

Improper drain piping (hose) may cause water leakage and damage to furniture or other possessions.

Do not touch the compressor or refrigerant piping without wearing glove on your hands.

Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.

The unit must be properly earth connected.

Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire.

Improper earth connection may cause electrical shock.

Do not touch the metal edges inside the unit without wearing glove on your hands.

Touching directly it may injure your hands.

When installing at a watery place, provide an electric leak breaker.

Failure to mount the electric leak breaker may cause electrical shock.

Do not remove the panel or the fan guard from the unit when it is running.

You could be injured if you touch rotating, hot or highvoltage parts.

Use breaker or fuse with proper capacity.

Make sure that each appliance has a main power switch.

Using a wire or copper wire instead of proper capacity can cause fire or trouble.

Other appliances connected to the same line could cause an overload.

Do not operate the air conditioner without the air filter set place.

Dust may accumulate, and cause a failure.

At emergency (if you smell something burning), stop operation and turn the power source switch off.

Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.

For the power lines, use standard cables of sufficient current capacity.

Otherwise, current leakage, overheating or fire may occur.

A thing embarrassed which gets wet under the unit is not put.

When the room is high humidity or when the drain pipe is clogged, water may drip from the indoor unit.

After stopping operation, be sure to wait for five minutes before turning off the main power switch.

Otherwise, water leakage or unit failure may occur.

When installing the power lines, do not apply tension to the cables.

The tighten or loosen the connections may cause generate heat and cause fire.

Remote controller is not installed for the place where direct sunshine strikes.

Remote controller is not pushed with the thing sharpening ahead.

It occasionally causes the electric shock and the breakdown.

- 3 -

A COMPLETE LINE UP

PEH-5 kW

14.4

Cooling capacity Btu/h

49,150 kcal/h

12,400

Heating capacity

(PEH only) kW

Btu/h

14.4

49,150 kcal/h

12,400

PE(H)-7

17.9

61,000

15,400

18.8

64,100

PE(H)-8

22.0

75,100

18,900

22.0

75,100

PE(H)-10

28.8

98,300

24,800

28.8

98,300

16,200 18,900 24,800

Note: Cooling & heating capacities are based following conditions.

Cooling: Indoor:27 DB, 19 WB; Outdoor: 35 DB

Heating: Indoor:21 DB; Outdoor: 7 DB, 6 WB (PEH only)

Cooling and Heating capacities are based 5m pipe length

PE(H)-15

44.0

150,200

37,900

44.0

150,200

37,900

PE(H)-20

57.6

196,600

49,600

57.6

196,600

49,600

Indoor unit

Example PEH-7

Outdoor unit

Example PUH-7

- 4 -

FEATURES

High sensible cooling capacity.

The sensible cooling capacity has been significantly improved through balanced optimised heat exchanger design.

Comfort heating. (PEH only)

The PEH series are designed to provide effective heating even when the outside temperature is down to -10 .

Highly efficient operation.

The EER(Energy Efficiency Ratio) on these models is greatly improved by revised design specifications and by being manufactured stringently to Mitsubishi

Electric high quality standards.

Flexibility of Supply Air Delivery

PE, PEH-15,20 feature belt driven Supply Air fans enabling accurate matching of actual airflow rates to the specified quantities. Accurate commissioning is assisted by the capability to change pulleys and belts if necessary to achieve the desired air balance.

Low ambient cooling.

(Special order)

In applications with relatively high internal loads, there may be a requirement for all series to operate on cooling at low ambient conditions.

Special order parts is available to maintain the refrigeration circuit in balance at outdoor temperatures as low as -5 .

Please consult your local Mitsubishi Electric Sales office for application advice on these parts.

Labour saving installation.

The unit operation can commence immediately after connecting to the power supply, refrigerant piping, drain piping, ducting and control system.

Wide electrical control capability.

All series is flexible mechanical control configuration.

In addition Global Remote Controller is prepared as special order.

The Global Remote Controller gives the programmable weekly timer, compressor anti-short cycle timer(3min.), cool/heat/fan/auto changeover etc.(Heat and auto changeover are only PEH.)

The factory standard is for provision of 24 volt terminal block to enable a field wired control of contractors choice to be connected.

Please consult your local Mitsubishi Electric Sales office for application advice on these control.

Grobal Remote Controller

DESCRIPTIONS

Mitsubishi Electric air conditioners series PE(H)/PU(H) are available in a wide range of sizes and models to enables the designer to select the best model for each application.

All series units are completely assembled, wired and strictly tested at the factory.

With the development of all series demands for such features as light weight, compactness, increased capacity, appropriate static pressure, air flow control, and having flexibility of inter facing energy saving electronic controls, Mitsubishi

Electric have met market expectations.

- 5-

MECHANICAL SPECIFICATIONS

General

All units are factory assembled, piped, internally wired.

They are also tested and checked under a strict quality

control system in the factory.

Exterior surfaces of all units of outdoor unit are

phosphatized, zinc-coated steel with powder coating

and ivory white baked enamel finish.

Refrigeration Controls

Refrigeration controls include condenser fan,

evaporator fan and compressor contactors.

Compressors

All units have high efficiency type hermetic line starting

compressors.

Compressors are equipped with thermal overload

protector, over-current relay and high pressure

protection control.

Crankcase heaters are standard.

Evaporator Coils

Highly efficient cross-finned coil are applied to provide a

larger cooling capacity with low air speed on the coil.

Coils are made of 9.52mm OD and 0.35mm thick

seamless copper tubing mechanically bonded to 0.12mm

thick aluminium fins and are factory leak tested at a

pressure of 3.3MPa. They are provided with strainers

attached to the capillary tubes to further ensure a clean

system.

Condenser Coils

Unnecessary power input due to higher discharge

pressure is avoided by high performance designs of

cross-finned coil.

Condenser coils are made of 9.52mm OD, 0.35mm

thick seamless copper tubes mechanically bonded to

0. 12mm thick aluminium fins and factory pressure and leak tested at 3.3MPa.

Evaporator Fans

The sirocco fans are made of galvanised steel and

balanced to proved accurate air flow performance at

low noise level.

Condenser Fan

The direct-drive propeller fan is dynamically balanced,

to ensure smooth airflow.

A weatherproof three-phase squirrel cage induction

motor is used to drive the condenser fan.

TYPICAL INSTALLATION EXAMPLE

PU(H)

PE(H)

PE(H)

PU(H)

- 6-

MODEL-DESIGNATION BREAKDOWN

P E - 10 M Y C

1

Service reference

Design Sequence

Electrical Supply

Y = 3 phase 380~415V 50Hz 4 wires

(

In case of PE(H)-7 Indoor unit

Y = 1 phase 220~240V 50Hz 2 wires

)

Compressor Horsepower

5 = 5 HP

7 = 7 HP

8 = 7.5 HP

10= 10 HP

15= 15 HP

20= 20 HP

Series Number

PE = Indoor unit

PEH = Indoor unit

PU = Outdoor unit

PUH = Outdoor unit

- 7 -

SPECIFICATIONS

PE-7~20MYC

Model name

Service reference

Power supply Indoor

Outdoor

Total cooling capacity

Sensible cooling capacity

Capacity step

Refrigerant

Refrigerant charge

Refrigerant control

Indoor Unit

Model name

Service reference

External finish

Dimension Height

Width

Depth

Net weight

Indoor coil

Indoor fan

Indoor fan motor

No.

Motor output

Indoor fan air flow

External static pressure

Sound pressure level

Drain connection

Outdoor unit

Model name

Service reference

External finish

Color

Dimension

Net weight

Compressor

No.

Motor output

Height

Width

Depth

Outdoor coil

Outdoor fan

Outdoor fan motor

No.

Motor output

Outdoor fan air flow

Sound pressure level

Protection devices kg mm mm mm kg kW

CMM

CFM

L/S mmAq

Pa dB(A) mm

PE-7MYC

PE-7MYC-EU kW

Btu/h kcal/h kW

Btu/h kcal/h

%

1PH 2W220~240V 50Hz

3PH 4W 380 ~ 415 V 50Hz

17.9

61,100

15,400

14.3

48,800

12,300 mm mm mm kg kW kW

CMM

CFM

L/S dB(A)

5.7

PE-7MYC

PE-7MYC-EU

PE-8MYC

PE-8MYC-EU

22.0

75,100

18,900

17.6

60,100

15,100

0-100

5.0

PE-8MYC

PE-8MYC-EU

Cooling only

PE-10MYC

PE-10MYC-EU

PE-15MYC

PE-15MYC-EU

3PH 4W380 ~ 415V 50Hz

3PH 4W380 ~ 415V 50Hz

28.8

98,300

44.0

150,200

24,800

23.0

78,500

19,800

37,900

35.2

120,200

30,200

R-22

8.7

Capillary tube

PE-10MYC

PE-10MYC-EU

2

4.8

PE-15MYC

PE-15MYC-EU

PE-20MYC-EU

0-50-100

PE-20MYC

57.6

196,600

49,600

46.1

157,300

39,600

2

9.7

PE-20MYC

PE-20MYC-EU

Galvanized steel

428 706

1,415

1,615 1,690 1,993

67

650

70 84 180

865

212

Single phase induction motor

1

0.21

60

1

70

0.7

Cross fin coil

Centrifugal (Galvanized) - Direct drive Centrifugal (Galvanized) - Belt drive

Three phase induction motor

1

1.0

90

1

2.2

140

1

3.7

180

2,119

1,000

55

2,472

1,167

12.5

125

56

3,179

1,500

4,945

2,333

61

20

200

6,358

3,000

62

PU-7MYC PU-8MYC

59

25.4

PU-10MYC PU-15MYC PU-20MYC

PU-7MYC

1

-EU(S) PU-8MYC

1

-EU(S) PU-10MYC

1

-EU(S) PU-15MYC

1

-EU(S) PU-20MYC

1

-EU(S)

Acrylic resin coating

Munsell 5Y 8/1

980

1,400

700

205

1,230

998

202

230 285

1

5.0

2

0.09

190

6,711

3,167

65

1

5.5

Hermetic line start(reciprocating)

1

7.5

Cross fin coil

Propeller-Direct drive

210

7,415

3,000

65

Three phase induction motor

2

0.15

220

7,770

3,667

65

High pressure switch, freeze & frost protection, Fuse

Over current relay (comp & indoor fan, outdoor fan)

Internal thermostat (comp & indoor fan, outdoor fan)

2

5.5

1

0.24

240

8,477

4,000

67

998

961

1,996

360

2

7.5

2

0.24

480

16,954

8,000

68

Note1. Cooling capacity is based on the following conditions.

Indoor;27˚CDB,19˚CWB, Outdoor;35˚CDB

Cooling capacity is based 5m pipe length.

2. Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.

3. Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.

4. The measuring point of the Sound pressure level is 1m from the unit surface.

5. Specification subject to change without notice.

- 8 -

PEH-5,7,8MYA

Model name

Service reference

Power supply Indoor

Outdoor

Total cooling capacity

Sensible cooling capacity

Sensible heating capacity kW

Btu/h kcal/h kW

Btu/h kcal/h kW

Btu/h kcal/h

% kg

PEH-5MYA

PEH-5MYA-EU

PEH-7MYA

PEH-7MYA-EU

3PH 4W380~415V 50Hz

3PH 4W380~415V 50Hz

14.4

49,150

12,400

11.5

39,400

10,000

14.4

49,150

12,400

5.0

PEH-5MYA

1PH 2W220~240V 50Hz

3PH 4W380~415V 50Hz

17.9

61,100

15,400

14.3

48,800

12,300

18.8

64,100

16,200

0-100

R-22

5.7

Capillary tube

PEH-7MYA

PEH-5MYA-EU PEH-7MYA-EU

Heat pump

PEH-8MYA

PEH-8MYA-EU

3PH 4W380~415V 50Hz

3PH 4W380~415V 50Hz

22.0

75,100

18,900

17.6

60,100

15,100

22.0

75,100

18,900

Capacity step

Refrigerant

Refrigerant charge

Refrigerant control

Indoor Unit Model name

Service reference

External finish

Dimension

Net weight

Indoor coil

Indoor fan

Indoor fan motor

No.

Motor output

Indoor fan air flow

Height

Width

Depth

External static pressure

Sound pressure level

Drain connection

Outdoor unit

Model name

Service reference

External finish

Color

Dimension

Net weight

Compressor

No.

Motor output

Height

Width

Depth

Outdoor coil

Outdoor fan

Outdoor fan motor

No.

Motor output

Outdoor fan air flow

Sound pressure level

Protection devices

6.6

PEH-8MYA

PEH-8MYA-EU mm mm mm kg kW

CMM

CFM

L/S mmAq

Pa dB(A) mm

Galvanized steel

428

1,095

1,415

650

60 67 70

Three phase induction motor Single phase induction motor

1

0.45

42

1

0.21

60

1,483

700

Cross fin coil

Centrifugal (Galvanized) - Direct drive

Three phase induction motor

2,119

1,000

1

0.7

70

2,472

1,167

12.5

125

55 56

25.4

PUH-5MYE

PUH-7MYC

PUH-8MYC PUH-8MYE

PUH-8MYE-EU mm mm mm kg kW kW

CMM

CFM

L/S dB(A)

PUH-5MYE-EU PUH-7MYC1-EU(S) PUH-8MYC1-EU(S)

1

1,175

1,000

550

150

3.73

1

0.15

95

3,355

1,583

57

Acrylic resin coating

Munsell 5Y 8/1

980

1,400

700

211

214

Hermetic line start(reciprocating)

1

5.5

Cross fin coil

Propeller-Direct drive

Three phase induction motor

2

0.09

167

5,898

2,783

65

High pressure switch, freeze & frost protection, Fuse

Over current relay (comp & indoor fan, outdoor fan)

Internal thermostat (comp & indoor fan, outdoor fan)

1,175

1,250

550

188

1

0.35

200

7,063

3,333

65

Note 1. Cooling and heating capacities are based on the following conditions.

Cooling indoor; 27˚CDB, 19˚CWB, outdoor :35˚CDB

Heating indoor; 21˚CDB, outdoor :7.0˚CDB, 6.0˚CWB

Cooling and heating capacities are based 5m pipe length.

2. Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.

3. Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.

4. The measuring point of the Sound pressure level is 1m from the unit surface.

5. Specification subject to change without notice.

- 9 -

PEH-10,15,20MYA

Model name

Service reference

Power supply Indoor

Outdoor

Total cooling capacity

Sensible cooling capacity

Sensible heating capacity kW

Btu/h kcal/h kW

Btu/h kcal/h kW

Btu/h kcal/h

%

Capacity step

Refrigerant

Refrigerant charge

Refrigerant control

Indoor Unit Model name

Service reference

External finish

Dimension

Net weight

Indoor coil

Indoor fan

Indoor fan motor

No.

Motor output

Indoor fan air flow

Height

Width

Depth kg mm mm mm kg kW

CMM

CFM

L/S mmAq

Pa dB(A) mm

External static pressure

Sound pressure level

Drain connection

Outdoor unit

Model name

Service reference

External finish

Color

Dimension

Net weight

Compressor

No.

Motor output

Height

Width

Depth

Outdoor coil

Outdoor fan

Outdoor fan motor

No.

Motor output

Outdoor fan air flow

Sound pressure level

Protection devices mm mm mm kg kW kW

CMM

CFM

L/S dB(A)

PEH-10MYA

PEH-10MYA-EU

28.8

98,300

24,800

23.0

78,500

19,800

28.8

98,300

24,800

0-100

9.9

Heat pump

PEH-15MYA

PEH-15MYA-EU

PEH-20MYA

PEH-20MYA-EU

3PH 4W380 ~ 415V 50Hz

3PH 4W380 ~ 415V 50Hz

44.0

150,200

37,900

35.2

120,200

30,200

44.0

150,200

37,800

57.6

196,600

49,600

46.0

157,000

39,600

57.6

196,600

49,500

R-22

2

6.6

Capillary tube

PEH-15MYA

PEH-15MYA-EU

0-50-100

2

9.7

PEH-20MYA

PEH-20MYA-EU

PEH-10MYA

PEH-10MYA-EU

Galvanized steel

428

1,615

650

84

1,690

180

706

865

1,993

212

Centrifugal (Galvanized) - Direct drive Centrifugal (Galvanized) - Belt drive

Three phase induction motor

1

1.0

90

3,179

1,500

12.5

125

59

Cross fin coil

1

2.2

140

4,945

2,333

61

20

200

1

3.7

180

6,358

3,000

62

25.4

PUH-10MYC PUH-10MYE PUH-15MYC PUH-20MYC

PUH-10MYC

1

-EU(S) PUH-10MYE-EU PUH-15MYC

1

-EU(S) PUH-20MYC

1

-EU(S)

980

1,400

700

240

1

7.5

Acrylic resin coating

Munsell 5Y 8/1

1,175

1,250

550

221 431

Hermetic line start(reciprocating)

2

5.5

Cross fin coil

Propeller-Direct drive

Three phase induction motor

0.35

2

0.15

190

6,711

3,167

200

7,063

3,333

65

High pressure switch, freeze & frost protection, Fuse

Over current relay (comp & indoor fan, outdoor fan)

Internal thermostat (comp & indoor fan, outdoor fan)

1,200

1,951

1,080

2

0.35

2

185

2

6,534

2

3,083

69

472

2

7.5

Note 1. Cooling and heating capacities are based on the following conditions.

Cooling indoor; 27˚CDB, 19˚CWB, outdoor :35˚CDB

Heating indoor; 21˚CDB, outdoor :7.0˚CDB, 6.0˚CWB

Cooling and heating capacities are based 5m pipe length.

2. Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.

3. Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.

4. The measuring point of the Sound pressure level is 1m from the unit surface.

5. Specification subject to change without notice.

- 10 -

ELECTRICAL DATA

PE-7~20MYC-EU

Cooling

VOLT ITEM

PE-7

240V

PE-

8 20

415V

PE-7

220V

PE-

8 20

380V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT kW

A kW

A kW

A kW

A

%

A kW

A kW

A kW

A kW

A

%

A

PE-7MYC-EU

PU-7MYC

1

-EU

7.2

14.6

-

74

6.0

10.7

0.8

3.2

0.4

0.7

PE-8MYC-EU

PU-8MYC

1

-EU

7.8

14.2

74

83

6.8

12.3

0.6

1.2

0.4

0.7

PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU

PU-10MYC

1

-EU PU-15MYC

1

-EU PU-20MYC

1

-EU

10.1

18.9

74

82

8.6

15.9

1.0

2.0

0.5

1.0

17.6

29.6

83

119

2X7.65

2X12.45

1.7

3.5

0.6

1.2

22.0

39.1

78

140

2X9.2

2X15.95

2.4

4.8

2X0.6

2X1.2

7.2

15.9

-

81

6.0

11.6

0.8

3.5

0.4

0.8

7.8

15.5

74

91

6.8

13.4

0.6

1.3

0.4

0.8

10.1

20.7

74

90

8.6

17.6

1.0

2.1

0.5

1.0

17.6

32.3

83

131

2X7.65

2X13.65

1.7

3.8

0.6

1.2

22.0

42.7

78

152

2X9.2

2X17.55

2.4

5.2

2X0.6

2X1.2

- 11 -

PEH-5,7,8MYA-EU

Cooling

VOLT ITEM

PEH-7

240V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

415V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT

PEH-7

220V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

380V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT kW

A kW

A kW

A kW

A

%

A kW

A kW

A kW

A kW

A

%

A

PEH-5MYA-EU

PUH-5MYE-EU

5.5

9.5

80

69

4.7

8.1

0.54

0.9

0.25

0.5

5.5

10.4

80

69

4.7

8.85

0.54

1.0

0.25

0.55

PEH-7MYA-EU

PUH-7MYC

1

-EU

7.2

14.6

-

74

6.0

10.7

0.8

3.2

0.4

0.7

7.2

15.9

-

81

6.0

11.6

0.8

3.5

0.4

0.8

7.8

15.5

76

91

6.8

13.4

0.6

1.3

0.4

0.8

PEH-8MYA-EU

PUH-8MYC

1

-EU PUH-8MYE-EU

7.8

14.2

76

83

6.8

12.3

0.6

1.2

0.4

0.7

7.9

14.7

75

83

6.77

12.3

0.6

1.2

0.53

1.2

7.9

16.0

75

91

6.77

13.4

0.6

1.3

0.53

1.3

Heating

VOLT ITEM

PEH-7

240V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

415V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT

PEH-7

220V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

380V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT kW

A kW

A kW

A kW

A

%

A kW

A kW

A kW

A kW

A

%

A

PEH-5MYA-EU

PUH-5MYE-EU

4.5

8.5

73

69

3.7

7.1

0.54

0.9

0.25

0.5

4.5

9.2

74

69

3.7

7.75

0.54

1.0

0.25

0.55

6.3

14.9

-

81

5.1

10.6

0.8

3.5

0.4

0.8

PEH-7MYA-EU

PUH-7MYC

1

-EU

6.3

13.6

-

74

5.1

9.7

0.8

3.2

0.4

0.7

6.5

13.6

73

91

5.5

11.5

0.6

1.3

0.4

0.8

PEH-8MYA-EU

PUH-8MYC

1

-EU

6.5

12.4

73

83

5.5

10.5

0.6

1.2

0.4

0.7

PUH-8MYE-EU

6.6

12.9

71

83

5.47

10.5

0.6

1.2

0.53

1.2

6.6

14.1

71

91

5.47

11.5

0.6

1.3

0.53

1.3

- 12 -

PEH-10,15,20MYA-EU

Cooling

VOLT ITEM

PEH-7

240V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

415V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT

PEH-7

220V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

380V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT kW

A kW

A kW

A kW

A

%

A kW

A kW

A kW

A kW

A

%

A

PUH-10MYC

1

-EU

10.1

18.9

74

82

8.57

15.9

1.0

2.0

0.53

1.0

PEH-10MYA-EU

PUH-10MYE-EU

10.2

19.1

74

82

8.67

15.9

1.0

2.0

0.53

1.2

10.1

20.7

74

90

8.57

17.6

1.0

2.1

0.53

1.1

10.2

21.0

74

90

8.67

17.6

1.0

2.1

0.53

1.3

PEH-15MYA-EU

PUH-15MYC

1

-EU

16.9

30.9

76

119

2X6.77

2X12.2

2.3

4.1

2X0.53

2X1.2

16.9

33.7

76

131

2X6.77

2X13.3

2.3

4.5

2X0.53

2X1.3

PEH-20MYA-EU

PUH-20MYC

1

-EU

21.8

39.3

77

140

2X9.12

2X16.1

2.5

4.7

2X0.53

2X1.2

21.8

42.9

77

152

2X9.12

2X17.6

2.5

5.1

2X0.53

2X1.3

Heating

VOLT ITEM

PEH-7

240V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

415V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT

PEH-7

220V

TOTAL INPUT

TOTAL RUN CURRENT

POWER FACTOR

START CURRENT

PEH-

8 20

380V

COMPRESSOR INPUT

RUN CURRENT

INDOOR FAN INPUT

RUN CURRENT

OUTDOOR FAN INPUT

RUN CURRENT kW

A kW

A kW

A kW

A

%

A kW

A

%

A kW

A kW

A kW

A

PEH-10MYA-EU

PUH-10MYC

1

-EU

8.3

16.0

72

82

6.77

13.0

1.0

2.0

0.53

1.0

PUH-10MYE-EU

8.6

16.2

72

82

7.07

13.0

1.0

2.0

0.53

1.2

8.3

17.5

72

90

6.77

14.4

1.0

2.1

0.53

1.1

8.6

17.8

72

90

7.07

14.4

1.0

2.1

0.53

1.3

PEH-15MYA-EU

PUH-15MYC

1

-EU

14.5

26.9

75

115

2X5.57

2X10.2

2.3

4.1

2X0.53

2X1.2

14.5

29.4

75

126

2X5.57

2X11.15

2.3

4.5

2X0.53

2X1.3

PEH-20MYA-EU

PUH-20MYC

1

-EU

17.2

33.2

72

136

2X6.82

2X13.05

2.5

4.7

2X0.53

2X1.2

17.2

36.3

72

148

2X6.82

2X14.25

2.5

5.1

2X0.53

2X1.3

- 13 -

SELECTION PROCEDURE

1. Model Selection (With actual examples)

First step, to select the approximate model:

Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.

Second step, to select the model:

To select the model, the following conditions must be known:

(1) Total cooling load or sensible cooling load

(2) Indoor conditioned temperature (WB*1, DB)

(3) Designed outdoor temperature (DB)*2

(4) Designed air flow

(5) Designed external static pressure (= Wind pressure loss of air duct)*3

Notes:

*1. The correct WB is required since it has a serious effect on the capacity.

*2. The cooling capacity decreases as the outdoor temperature increases. Therefore, the estimated highest temperature during an air conditioning time frame is the "designed outdoor temperature". However, it is recommended that the abnormal outdoor temperature which may occur once or twice a year be excluded from the calculation to avoid selection of an excessively large capacity model.

*3. The wind pressure loss of an air duct should be calculated correctly. If a value having an excessive allowance is used, an excessively large model will be selected. Moreover, an excessively high air flow will be induced during actual operation causing the generation of high operating sounds and carry-over of condensed water.

(Step-1) Confirmation of operation range

Confirm that the conditions given above for the model to be selected are within the operation range listed on Page 36.

(Step-2) Calculation of actual air flow, external static pressure, and fan motor input

Based on the designed air flow and external static pressure, obtain the actual air flow, actual external static pressure, and fan motor power input from the fan performance table for the model selected. For an explanation of how to use the fan performance table, see the following examples.

Example: PE-8MYC, 50Hz

Example 1. (To operate with values near to the designed air flow and external static pressure.)

Condition : Designed air flow 70CMM

Designed external static pressure 60Pa

Calculation : The designed point is A. Therefore, duct resistance line passing A is

Fan Performance Curve 50Hz dotted line.

Therefore, actual point is B for

∆ connection

(Pa)

450

Recommended Range

400

Actual air flow = 77CMM

For connection operation line

Fan speed

(rpm)

1400

350

Actual external static pressure = 70Pa

1300

B

Notes: Duct resustance line is secondary curve.

300

1200

A

250

60Pa

1100

200

For connection operation line

1000

150

100

Inter nal SP

900

50

800

- 14 -

0

50 55 60 65 70

Air flow (CMM)

75 77 80

(Step-3) Calculation of net capacity

Based on the indoor conditioned temperature (WB,DB), designed outdoor temperature (DB), and the actual air flow obtained in Step-2, obtain the gross capacity from the gross capacity tables (pages

16~35). Then, calculate the net capacity from the formula below by using the fan motor input obtained in Step-2.

Net capacity (kW) = Gross capacity (kW) - Fan motor input (kW)

Example: PE-8MYC

Condition:

Indoor conditioned temp. : 26˚CDB, 19˚CWB

Designed outdoor temp. : 40˚CDB

Actual air flow : 77CMM

Fan motor input : 0.6kW (See P.11)

Calculation :

The sections of the gross capacity table applicable for the above conditions are shown right.

At 26˚CDB, 19˚CWB of Indoor,

Q = 21.3, SHC = 16.3, T/I = 8.3

INDOOR INDOOR

DB˚C

WB˚C

26 19

OUTDOOR DB˚C

40.0

Q kW SHC kW SHF T/I kW

21.3

16.3

0.77

Factor for Various Air Flow

PE-8MYC-EU

COOLING

AIR VOLUME

CAPACITY

TOTAL INPUT

SHC

CMM

L/S

60

1,000

0.976

0.991

0.963

8.3

70

1,167

1.0

1.0

1.0

80

1,330

1.025

1.009

1.044

Therefore, when air flow is 77(CMM)

Q = 21.3

(1+(1.025 - 1.0)

7/10*) 21.7(kW)

SHC = 16.3

(1+(1.044 - 1.0)

7/10*) 16.8(kW)

T/I = 8.3

(1+(1.009-1.0))

7/10*) 8.4(kW)

Therfore, the net capacity is,

Net total cooling capacity = 21.7 (kw) - 0.6(kW)

= 21.1 (kW)

Net sensible cooling capacity = 16.8 (kW) - 0.6 (kW)

= 16.2 (kW)

Note * : 7/10 = (77-70)/(80-70)

2. Efficiency Calculation

• Refrigerant cycle energy efficienty

(1) COP =

Gross total cooling capacity (kW)

Compressor input (kW)

(2) ERR =

Gross total cooling capacity (kW)

Total input (kW)

• System energy efficienty

(1) COP =

Net cooling capacity (kW)

Compressor input (kW)

(2) ERR =

Net cooling capacity (kW)

Total input (kW)

1kW = 3412Btu/h

Notes: 1. COP : Coefficient of performance

2. EER : Energy efficiency ratio

3. Temperature condition of COP, EER (ARI Standard Ratings)

Indoor entering air temp. : 80˚FDB (=27˚CDB), 66˚FWB(=19˚CWB)

Outdoor entering air temp. : 95˚FDB (=35˚CDB)

4. Total input = Compressor input + Indoor fan motor input + Outdoor fan motor input (page 11).

- 15 -

CAPACITY TABLES

- 16 -

- 17 -

- 18 -

- 19 -

- 20 -

- 21 -

- 22 -

- 23 -

- 24 -

- 25 -

- 26 -

- 27 -

- 28 -

- 29 -

- 30 -

- 31 -

- 32 -

- 33 -

- 34 -

- 35 -

OPERATION RANGE

The range of working temperatures is as below.

Make sure which unit you are using and confirm the range of application.

Cooling Heating

(PEH only)

50

46

40

30

20

10

Range for continuous operation

0

-5

-10

10 15 20 24 25 30

Indoor temp.(˚CWB)

Range for continuous operation

Use for low ambient cooling parts

15

10

5

0

- 5

-10

-15

Range for continuous operation

Indoor temp.(˚CDB)

Note

As an applicable humidity outside standard for both indoors and outdoors, we recommend use within a range of 35-80% relative humidity.

However, it is a condition that there is no be dewy in surfaces of electric parts.

Caution:

The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.

- 36 -

PEH-5MYA-EU

Fan Performance Curve

50Hz

(Pa)

450

Recommended Range

400

FAN PERFORMANCE

Fan speed

(rpm)

PE-7MYC-EU

PEH-7MYA-EU

Fan Performance Curve

50Hz

(Pa)

450

Recommended Range

400

Fan speed

(rpm)

350 350

1400

1300

300 300

For Hi speed operation line

For connection operation line

1200

250 250

1300

For Low speed operation line

1100

200 200

1000

150

For connection operation line

1200

150

900

100

50

0

35

Inter nal SP

900

800

40 45 50

Air flow (CMM)

55

PE-8MYC-EU

PEH-8MYA-EU

Fan Performance Curve

50Hz

(Pa)

450

Recommended Range

1100

1000

400

Fan speed

(rpm)

For connection operation line

1400

350

1300

300

1200

250

1100

200

For connection operation line

150

100

Inter nal SP

1000

900

50

800

0

50 55 60 65 70

Air flow (CMM)

75 80

- 37 -

100

50

800

0

48 50 55 60 65

Air flow (CMM)

70 72 75

PE-10MYC-EU

PEH-10MYA-EU

Fan Performance Curve

50Hz

(Pa)

450

Recommended Range

400

350

Fan speed

(rpm)

For connection

operation line

1400

300

250

200

150

100

50

0

Inter nal SP

For connection operation line

Inter nal SP

1300

1200

1100

1000

60 70 80

Air flow (CMM)

800

90 100

900

PE-15MYC-EU

PEH-15MYA-EU

(Pa)

1000

Fan speed

(rpm)

1300

800

1200

600

1100

1000

400

200

0

900

800

700

600

500

110

Fan Performance Curve

50Hz

Recommended Range

3.7kW

2.2kW

Inter nal SP

120 130 140 150 160

Air flow (CMM) standard point

170

Total static pressure

(Pa)

200

300

400

500

600

700

800

Model

CMM

L/S

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR rpm mm inch mm inch inch kw rpm mm inch mm inch inch kw rpm mm inch mm inch inch kw kw rpm mm inch mm inch inch kw rpm mm inch mm inch inch mm inch mm inch inch kw rpm mm inch mm inch inch kw rpm

Std.

110

1830

768

139.7

5.5

254

10

B45

2.2

120

2000

768

139.7

5.5

254

10

B45

2.2

Airflow

PE-15MYC-EU, PEH-15MYA-EU

130

2170

768

139.7

5.5

254

10

B45

2.2

898

114.3

4.5

177.8

898

114.3

4.5

177.8

898

114.3

4.5

177.8

7 7 7

B38X2 B38X2 B38X2

2.2

942

2.2

942

2.2

942

140

2330

768

139.7

5.5

254

10

B45

2.2

898

114.3

4.5

177.8

7

B38X2

2.2

942

150

2500

768

139.7

5.5

254

10

B45

2.2

898

114.3

4.5

177.8

7

B38X2

2.2

971

152.4

6

228.6

9

B44

2.2

1008

127

5

152.4

6

228.6

9

B44

2.2

1008

127

5

152.4

6

228.6

9

B44

2.2

1008

127

5

177.8

7

177.8

7

177.8

7

B37X2 B37X2 B37X2

3.7

3.7

3.7

1119

139.7

1119

139.7

1119

139.7

5.5

177.8

5.5

177.8

5.5

177.8

7 7 7

B38X2 B38X2 B38X2

3.7

1190

127

3.7

1190

127

3.7

1190

127

5

152.4

5

152.4

5

152.4

6 6 6

B36X2 B36X2 B36X2

3.7

3.7

3.7

1258

177.8

7

203.2

8

B42

3.7

-

-

-

-

-

-

-

-

-

-

-

-

-

-

5.5

177.8

7

B38X2

3.7

-

-

-

-

-

-

-

-

-

-

-

-

-

-

139.7

5.5

203.2

8

B40X2

3.7

1067

152.4

6

203.2

8

B40X2

3.7

1119

139.7

5.5

177.8

7

B38X2

3.7

1190

127

5

152.4

6

B36X2

3.7

-

-

-

-

-

-

-

152.4

6

228.6

9

B44

2.2

1008

127

5

177.8

7

B37X2

3.7

1119

139.7

5.5

177.8

7

B38X2

3.7

-

-

-

-

-

-

-

-

-

-

-

-

-

-

139.7

5.5

203.2

8

B40X2

3.7

1067

152.4

6

203.2

8

B40X2

3.7

1119

139.7

898

114.3

4.5

177.8

7

B38X2

2.2

971

160

2670

-

-

-

-

-

-

-

5.5

177.8

7

B38X2

3.7

-

-

-

-

-

-

-

-

-

-

-

-

-

-

139.7

5.5

203.2

8

B40X2

3.7

1067

152.4

6

203.2

8

B40X2

3.7

1119

139.7

898

114.3

4.5

177.8

7

B38X2

2.2

971

170

2830

-

-

-

-

-

-

-

PE-20MYC-EU

PEH-20MYA-EU

(Pa)

1000

Fan speed

(rpm)

1300

800

1200

Fan Performance Curve

Recommended Range

5.5kW

600

1100

1000

400

200

900

800

700

600

3.7kW

Inter nal SP

0

150 160 180 195200

Air flow (CMM) standard point

220 240

Total static pressure

(Pa)

200

300

400

500

600

700

800

Model

CMM

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

L/S

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR

FAN SPEED

PULLEY SIZE

(MOTOR SIDE)

PULLEY SIZE

(FAN SIDE)

BELT SIZE

MOTOR kw rpm mm inch mm inch inch inch inch kw rpm mm inch mm inch inch rpm mm inch mm inch inch kw rpm mm inch mm inch inch kw rpm mm inch mm kw rpm mm inch mm inch inch kw kw rpm mm inch mm inch inch

Std.

150

2500

627

127

5

279.4

11

Airflow

PE-20MYC-EU, PEH-20MYA-EU

160

2670

180

3000

200

3330

220

3670

627

127

5

279.4

11

692

127

5

254

10

B44X2 B44X2 B42X2

3.7

3.7

3.7

768

139.7

768

139.7

773

127

5.5

254

5.5

254

5

228.6

10 10 9

B43X2 B43X2 B40X2

3.7

3.7

3.7

692

127

5

254

10

B42X2

3.7

773

127

5

228.6

9

B40X2

3.7

-

-

-

-

-

-

-

773

127

5

228.6

9

B40X2

3.7

942

152.4

6

228.6

942

152.4

6

228.6

942

152.4

6

228.6

9 9 9

B42X2 B42X2 B42X2

3.7

1008

3.7

1008

3.7

1008

127

5

177.8

7

127

5

177.8

7

127

5

177.8

7

B37X2 B37X2 B37X2

3.7

3.7

3.7

1119

139.7

5.5

177.8

1119

139.7

5.5

177.8

1119

139.7

5.5

177.8

7 7 7

B37X2 B37X2 B37X2

5.5

5.5

5.5

1229

152.4

6

177.8

1229

152.4

6

177.8

1229

152.4

6

177.8

7 7 7

B38X2 B38X2 B38X2

5.5

5.5

5.5

1258

177.8

7

203.2

1258

177.8

7

203.2

1258

177.8

7

203.2

8 8 8

B41X2 B41X2 B41X2

5.5

5.5

5.5

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1119

139.7

5.5

177.8

7

B37X2

5.5

942

152.4

6

228.6

9

B41X2

5.5

1067

152.4

6

203.2

8

B39X2

5.5

1119

139.7

5.5

177.8

7

B37X2

5.5

1229

152.4

6

177.8

7

B38X2

5.5

942

152.4

6

228.6

9

B42X2

3.7

1067

152.4

6

203.2

8

B39X2

5.5

-

-

-

-

-

-

-

-

-

-

-

-

-

-

942

152.4

6

228.6

9

B41X2

5.5

1067

152.4

6

203.2

8

B39X2

5.5

-

-

-

-

-

-

-

240

4000

-

-

-

-

-

-

-

773

127

5

228.6

9

B40X2

3.7

- 38 -

Pulley outside dimensions are shown below: (Unit : mm)

(1) Shape of belt groove e f w

L

0 r

1 r

3

Shape of

V-belt

Nominal

Dia. øP.C

a

(˚)

W L

0

K K

0 e f a r

2 r

2

B r

1 r

2 r

3

Over 125

Under 160

Over 160

Under 200

Over 200

34 15.86

36 16.07

12.5 5.5

9.5 19.0 12.5 0.2~0.5 0.5~1.0

1~2

38

16.29

V-belt thickness

(Reference)

11

Sectional plan of V-belt

16.5mm

40˚

B type

(2) Shape of motor pulley boss (Unit : mm)

C

A

MOTOR

CAPACITY

(kW)

2.2, 3.7

5.5

A

28

+0.028

+ 0.007

38

+0.028

+ 0.007

B

31

41

+ 0.128

+ 0.007

+ 0.128

+ 0.009

C

8

10

+0.018

-0.018

+0.018

-0.018

- 39 -

SOUND DATA

Indoor units

Sound Levels

MODEL

PWL dB(A)

SPL dB(A)

PEH-5MYA-EU

PE-7MYC-EU

PEH-7MYA-EU

PE-8MYC-EU

PEH-8MYA-EU

PE-10MYC-EU

PEH-10MYA-EU

PE-15MYC-EU

PEH-15MYA-EU

PE-20MYC-EU

PEH-20MYA-EU

Outdoor units

Sound Levels

63

63

64

67

69

70

MODEL

PUH-5MYE-EU

PU-7MYC

1

-EU

PUH-7MYC

1

-EU

PU-8MYC

1

-EU

PUH-8MYC

1

-EU

PUH-8MYE-EU

PU-10MYC

1

-EU

PUH-10MYC

1

-EU

PUH-10MYE-EU

PU-15MYC

1

-EU

PWL dB(A)

68

76

78

76

76

76

76

PU-20MYC

1

-EU

79

PUH-15MYC

1

-EU

PUH-20MYC

1

-EU

80

80

65

67

68

69

69

SPL dB(A)

57

65

65

65

65

55

55

56

59

61

62

63Hz

60.5

62

63

62

25

32

66

43

43

63Hz

68

62

62

45.4

64.5

45.4

68

Position mesurement

Indoor unit

PE(H)

Outlet

125Hz

57.5

60

61

62.5

40

44

250Hz

57.5

54

55

58.5

47

49

OCTAVE BAND FREQ. Hz

500Hz

52.5

53

54

59.5

52

53.5

1000Hz

50.5

50

51

53

55

56.5

2000Hz

43

42.5

43.5

48

57.5

57.5

4000Hz

34.5

37

38

43.5

52

53

8000Hz

28.5

31.5

32.5

36

36.5

51

125Hz

58

63.5

63.5

58

65

58

72

69

51

51

250Hz

57

OCTAVE BAND FREQ. Hz

500Hz

52.5

1000Hz

52

62

62

58

64

62

62

58.5

62.5

60

60

61

60

2000Hz

47.5

57.5

57.5

60

57

58

70

58.5

65

61

60

60

57

70.5

59

59

65

64

64.5

62

65

65

59

64

64

4000Hz

49

54

54

51.5

54.5

51.5

53

56.5

55

55.5

8000Hz

40

54

54

47

53

47

49.5

53

50.5

51.5

Inlet

Outdoor unit

PU(H)

1m

1m

Service panel side

1m

- 40 -

OUTLINE DIMENSIONS

PEH-5

50

15

AIR INLET

DRAIN:RC1

33

650

530 70

15

562

POWER SUPPLY

CABLE ENTRY ø27

(Bottom side)

CONTROL

CABLE ENTRY ø27

(Bottom side)

OPTIONAL PARTS

CABLE ENTRY ø27

(Bottom side)

CONTROL BOX

HOLES:14-ø3.1

20

104

135 66

105 40

AIR OUTLET DUCT

FLANGE

55

782

130 130 130 130 130

960

130 130 130 55

40

210

1095

1000

920

500 210

REFRIGERANT

PIPE ø19.05

(3/4)

AIR OUTLET

REFRIGERANT

PIPE ø12.7

(1/2)

34

66

20

40

HOLES:18-ø3.1

AIR INLET DUCT

FLANGE

HOLES:4-ø12

944

PE(H)-7,8

50

15

AIR

INLET

DRAIN:Rc1

33

650

530

562

70

15

POWER SUPPLY

CABLE ENTRY 27

(Bottom side)

CONTROL

CABLE ENTRY 27

(Bottom side)

OPTIONAL PARTS

CABLE ENTRY 27

(Bottom side)

CONTROL BOX

104 1102

130 130 130 130 130 130 130 130

34

31

135 31

105

40

20 1280 20

HOLES:24- 3.1

AIR INLET DUCT

FLANGE

HOLES:22- 3.1

AIR OUTLET DUCT

FLANGE

40

AIR

OUTLET

REFRIGERANT PIPE

25.4

(1)

REFRIGERANT PIPE

15.88

(5/8)

45 130 130 130 130 130 130 130 45

120

1415

1320

1240

1000 120

40

1264

HOLES:4- 12

- 41 -

PE(H)-10

50

15

650

530

AIR

INLET

33

DRAIN:Rc 1

PE(H)-15

562

70

15

POWER SUPPLY

CABLE ENTRY 27

(Bottom side)

CONTROL

CABLE ENTRY 27

(Bottom side)

OPTIONAL PARTS

CABLE ENTRY 27

(Bottom side)

CONTROL BOX

HOLES:22- 3.1

AIR OUTLET DUCT

FLANGE

40

REFRIGERANT PIPE

28.6

(1-1/8)

REFRIGERANT PIPE

AIR

OUTLET

15.88

(5/8)

20

104 1302

135

105 40

66 130 130 130 130 130 130 130 130 130 66

34

1480 20

220

45 130 130 130 130 130 130 130 45

1615

1520

1440

1000 220

40

HOLES:26- 3.1

AIR INLET DUCT

FLANGE

HOLES:4- 12

1464

VIEW A

81

34

POWER SUPPLY

CABLE ENTRY 27

(BOTTOM SIDE)

REFRIGERANT

PIPE 15.88 (5/8)

CONTROL

CABLE ENTRY 27

(BOTTOM SIDE)

REFRIGERANT

PIPE 25.4 (1)

REFRIGERANT

OPTIONAL PARTS

CABLE ENTRY 27

PIPE 15.88 (5/8)

CONTROL BOX

REFRIGERANT

PIPE 25.4 (1)

25

AIR OUTLET DUCT

FLANGE

70 120

59

484

46

1690

1418

1300=130X10

HOLES:34- 3.1

130

59

49

AIR INLET DUCT

FLANGE

1637

910=130X7

1002

25

HOLES:4- 12

130

46

101

HOLES:24- 3.1

15

69

865

746 50

15

AIR OUTLET

AIR INLET

A

AIR OUTLET

AIR INLET

1587

50 50

DRAIN: Rc1

- 42 -

PE(H)-20

AIR INLET

A

VIEW A

50

81

44

POWER SUPPLY

CABLE ENTRY 27

(BOTTOM SIDE)

CONTROL

CABLE ENTRY 27

(BOTTOM SIDE)

REFRIGERANT

PIPE 15.88 (5/8)

REFRIGERANT

PIPE 28.6

OPTIONAL PARTS

(1-1/8)

CABLE ENTRY 27

REFRIGERANT

PIPE 15.88 (5/8)

CONTROL BOX

25

REFRIGERANT

PIPE 28.6 (1-1/8)

AIR OUTLET DUCT

FLANGE

70 193

44

536

21

1993

1648

1560=130X12

HOLES:38- 3.1

130

44

49

AIR INLET DUCT

FLANGE

1940

1170=130X9

1212

130

25

HOLES:4- 12

21

142

HOLES:28- 3.1

15

69

AIR OUTLET

AIR OUTLET

50

1890

50

DRAIN:Rc 1

865

746 50

15

AIR INLET

- 43 -

PUH-5

Holes :4-12X20

21

550

SERVICE PANEL

REFRIGERANT PIPE

ø12.7 (1/2)

131

126

REFRIGERANT PIPE

ø19.05(3/4)

75 400 75

CABLE ENTRY

Holes : 2-ø15

21

18

PU(H)-7,8,10

(Upper blow)

AIR INLET

AIR INLET

1040

1000

AIR OUTLET

21

AIR INLET

275 275

Hole : ø15

AIR INLET

CABLE ENTRY 25X40

AIR OUTLET

SERVICE PANEL

REFRIGERANT PIPE

ø15.88 (5/8)

REFRIGERANT PIPE

PU(H)- 7,8:ø25.4(1)

PU(H)- 10:ø28.6(1-1/8)

120

25

108

160

700

540

25

AIR INLET

34

18

25

- 44 -

200

350

1000

700

1400 25

Holes: 4-12X20

PUH-8,10

(Side blow)

Holes : 4-12X20

21

550

SERVICE PANEL

REFRIGERANT PIPE

ø15.88(5/8)

130

REFRIGERANT PIPE

PUH-8:ø25.4(1)

PUH-10:ø28.6(1-1/8)

75 400 75

CABLE ENTRY

Holes : 2-ø15

44 49

56

AIR INLET

1290

AIR OUTLET

1250

21

AIR INLET

275 275

Hole : ø15

PU-15

AIR INLET

AIR INLET

AIR OUTLET

998

AIR INLET

998 HOLES: 4-Uø15

SERVICE PANEL

REFRIGERANT PIPE

ø15.88(5/8)

REFRIGERANT PIPE

ø25.4(1)

No.1

No.2

169

242 50

CONTROL

CABLE ENTRY ø27

POWER SUPPLY

CABLE ENTRY ø43

78

137 721 137

- 45 -

PU-20

AIR INLET

AIR INLET

998

AIR OUTLET

No.1

No.2

17

SERVICE PANEL

REFRIGERANT PIPE

ø28.6(1-1/8)

2036

REFRIGERANT PIPE

ø15.88(5/8)

1996

CONTROL

CABLE ENTRY ø27

POWER SUPPLY

CABLE ENTRY ø47

213 80

392 75 64 75

AIR INLET

17

HOLES: 6-ø15

PUH-15,20

Holes : 4-12X20

830

27

478.5

2005

994

1080

68

25

54

- 46 -

911

No.1

No.2

128

1951

2059

CONTROL BOX

27

SERVICE PANEL

REFRIGERANT PIPE

ø15.88 (5/8)

REFRIGERANT PIPE

PUH-15:ø25.4(1)

PUH-20:ø28.6(1-1/8)

54

Note: In the case of installation are shown below, it is possible to use the unit by connecting the duct.

However, the pressure loss must be 30Pa (3mmAg) or less.

Duct work is local supply.

DUCT

DUCT

- 47 -

WIRING DIAGRAMS

PE-7MYC-EU (STANDARD)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

RED

PU-7MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

BLUE

F3(3.15A)

RED

WHITE

BLACK

52C

PE

52C

49C

51F2

63H

51C

CZ2

CH

30

CZ

52C

30

CZ

CR2

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

51C

GRAY

15

TB5

CZ2

14

1

2

3

1

C4

2

3

C5

RED

WHITE

BLACK

RED

WHITE

BLACK

MF2

MF3

MC

Power supply,

220 240Volt,

Single Phase

50Hertz

TB2

L

PE-7MYC-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N

PE

RED

BLUE

RED

F1 (3.15A)

BLUE

30

FZ

51F1

C3

1

26L

C3

3

FZ

30FZ

TB1 5

F1 3

26L

CZ1, 2

30CZ, FZ

C

C1, 3 ~ 5

CR1, 2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat (compressor)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat

(freeze protection)

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (check)

Switch (on)

Switch (Fan Hi-Low)

Thermostat (room temp.)

Run capacitor

Connector

Surge killer

52F

Tr

AC

220

240V

CR1

52F

GRAY

F2

(3.15A)

AC

24V

TB4

1

51F1

SWITCH BOX

(FIELD SUPPLY)

JUMPER

TB4

5

TB4

Hi

6

Low

7

SW2(FIELD SUPPLY)

52F

1

C1

RED

2

5

C1

BROWN

MF1 6

4 BLUE

C

TB3

CZ1

15

15

23WA

OUTDOOR

SW1

CZ2

TB4

2

CZ1

3

GRAY

4

FZ

14

14

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Please remove the jumper wire ( Mark) in the above

diagram if you use the Switch <SW2> at local.

If the Switch <SW2> is not used, the Fan motor

(indoor) drives at high speed.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

Power (Active)

Cooling operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

FAN HI

24VAC(N)

- 48 -

PE-8,10MYC-EU (STANDARD)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

PU-8, 10MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

RED

BLUE

F3(3.15A)

RED

WHITE

52C

BLACK

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

51C

PE

49C

52C

51F2

63H

51C

CZ2

CH

30

CZ

52C

30

CZ

CR2

GRAY

15

TB5

CZ2

14

1

2

3

1

C4

2

3

C5

RED

WHITE

BLACK

RED

WHITE

BLACK

MF2

MF3

MC

Power supply,

380 415Volt,

3Phase

50Hertz

L1

TB2

L2

L3

PE-8,10MYC-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A N

PE

BLUE

RED

WHITE

BLACK

RED

F1(3.15A)

52F

51F1

C1

4

49F

C1

5

C3

1

26L

C3

3

FZ

30FZ

52F

Tr

CR1

AC

220

240V

30

FZ

51F1

GRAY

F2

(3.15A)

1

C1

2

3

RED

WHITE

BLUE

TB4

AC

24V

TB4

CZ1

2

GRAY

4

1

MF1

RED

WHITE

BLUE

C2

1

2

3

SWITCH BOX

(FIELD SUPPLY)

23WA

SW1

FZ

3

TB1 5

F1 3

49F

26L

CZ1, 2

30CZ, FZ

C1~5

CR1, 2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat (indoor fan)

Internal thermostat (compressor)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

52F

TB3

CZ1

15

15

OUTDOOR

CZ2

14

14

1

C1

2

3

MF1

Attach the accessory

C2

1

2

3

1

2

3

Remove

This circuit diagram shows connections.

(If the external static Pressure is less than 30 Pa, change to connections.)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

Power (Active)

Cooling operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

FAN HI

24VAC(N)

- 49 -

PE-15MYC-EU (STANDARD)

OUTDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PU-15MYC

1

-EU ---100A

TB1

L1

L2

L3

N

RED

WHITE

BLACK

BLUE

RED

WHITE

BLACK

RED

WHITE

BLACK

F3

(3.15A)

51

F2

52C2

RED

WHITE

BLACK

51C2

49C1

49C2

52

C1

52

C2

51C1 51C2

MC2

52

C1

52

C2

CH1 CH2

63H1

30

CZ1

30

CZ1

CZ2-1

52

C1

63H2

CR2

30

CZ2

30

CZ2

CZ2-2

52

C2

2

CR3

2

52

F2

52C1

RED

WHITE

BLACK

RED

WHITE

BLACK

52F2

51C1

MC1

51F2

1

2

C1

RED

WHITE

3

BLACK

MF2

TB4

GRAY

11 12

CZ

2-1

CZ

2-2

13

INDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

TB2

L1

L2

L3

N

BLUE

CIRCUIT BREAKER

(FIELD SUPPLY)

PE-15MYC-EU ---30A

RED

WHITE

BLACK

F1

(3.15A)

52F1

30

FZ

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

FZ

30

FZ

Tr

AC

220

240V

CR1

52

F1

GRAY

F2

(3.15A)

AC

24V

GRAY

1

TB3

51F1

23

WA

23

WA

SW1

FZ

4

MF1

52F1

SWITCH BOX (FIELD SUPPLY)

TB3

2

CZ

1-1

CZ

1-2

3

5

CZ

1-1

CZ

1-2

TB3

11 12 OUTDOOR

11 12

CZ

2-1

CZ

2-2

13

13

Symbol

MC1,2

MF1

MF2

52C1,2

52F1

52F2

TB1 4

CH1,2

F1 3

Tr

49C1,2

51C1,2

51F1

51F2

63H1,2

26L1,2

FZ

30FZ

CZ1-1,2/2-1,2

30CZ1,2

<SW1>

<23WA>

C1, 3, 8

CR1 3

2

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (fan)

Auxiliary relay

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

Timer

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C1,2>, <51F1,2,3> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB3

1

2

Power (Active)

Cooling operation

3 Cooling operation

4 Fan operation

5 Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

FAN HI

24VAC(N)

- 50 -

PE-20MYC-EU (STANDARD)

OUTDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

L1

TB1

L2

L3

N

RED

WHITE

BLACK

BLUE

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PU-20MYC

1

-EU---125A

RED

WHITE

BLACK

RED

WHITE

BLACK

52C1

52C2

F3 (3.15A)

RED

WHITE

BLACK

52F2

52

C1

52

C2

49C1

51

F2

63H1

49C2

51

F3

63H2

CH1 CH2

51C1

30

CZ1

30

CZ1

CZ2-1

52

C1

51C2

CR2

30

CZ2

30

CZ2

CZ2-2

52

C2

2

CR3

2

52

F2

52

C1

52

C2

TB4

GRAY

11 12

CZ

2-1

CZ

2-2

13

INDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

TB2

L1

L2

L3

N BLUE

CIRCUIT BREAKER

(FIELD SUPPLY)

PE-20MYC-EU---30A

RED

WHITE

BLACK

F1

(3.15A)

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

FZ

30

FZ

Tr

AC

220

240V

52F1

CR1

52

F1

30

FZ

GRAY

F2

(3.15A)

AC

24V

GRAY

1

TB3

51F1

MF1

52F1

SWITCH BOX (FIELD SUPPLY)

23

WA

23

WA

SW1

TB3

2

CZ

1-1

CZ

1-2

3

5

FZ

4

CZ

1-1

CZ

1-2

TB3

11 12 OUTDOOR

11 12

CZ

2-1

CZ

2-2

13

13

RED

WHITE

BLACK

51C1

RED

WHITE

BLACK

51C2

RED

WHITE

BLACK

51F2

51F3

MC1

MC2

1

C1

2

RED

WHITE

3

BLACK

1

C2

2

3

RED

WHITE

BLACK

MF2

MF3

Symbol

MC1,2

MF1

MF2,3

52C1,2

52F1

52F2

TB1 4

CH1,2

F1 3

Tr

49C1,2

51C1,2

51F1,2

51F2,3

63H1,2

26L1,2

FZ

30FZ

CZ1-1,2/2-1,2

30CZ1,2

<SW1>

<23WA>

C1~3, 8

CR1 3

2

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (fan)

Auxiliary relay

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

Timer

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C1,2>, <51F1,2,3> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol

TB3

No.

Function

1

2

Power (Active)

Cooling operation

3 Cooling operation

4 Fan operation

5 Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

FAN HI

24VAC(N)

- 51 -

PE-7MYC-EU

(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)

Power supply,

380 415Volt,

3Phase

50Hertz

PU-7MYC

1

-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

TB1

L1

L2

L3

RED

BLUE

F3(3.15A)

RED

WHITE

BLACK

52C

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

51C

PE

52C

49C

51F2

63H

51C

CZ2

CH

30

CZ

30

CZ

52C

CR2

TB5

15

GRAY

CZ2

14

Power supply,

220 240Volt,

Single Phase

50Hertz

TB2

L

PE-7MYC-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N

PE

RED

BLUE

RED

F1

(3.15A)

51F1

C3

1

26L

C3

3

FZ

30FZ

BLUE

30

FZ

3

1

2

3

1

C4

2

RED

WHITE

BLACK

RED

WHITE

BLACK

C5

MF2

MF3

Tr

52F

CR1

AC

220

240V

52F

GRAY

F2

(3.15A)

TB4

1

51F1

SWITCH BOX

(FIELD SUPPLY)

JUMPER

TB4

5

TB4

Hi

6

Low

7

SW2(FIELD SUPPLY)

52F

1

C1

RED

2

5

C1

BROWN

MF1 6

4

BLUE

C

CZ1

23WA

SW1

TB3

TM

(3MIN)

15

15

OUTDOOR

AC

24V

TB4

CZ1

GRAY

4

2

FZ

3

TM

CZ2

14

14

MC

TB1 5

F1 3

26L

CZ1, 2

30CZ, FZ

C

C1, 3~5

CR1, 2

TM

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat

(compressor)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (check)

Switch (on)

Switch (Fan Hi-Low)

Thermostat (room temp.)

Run capacitor

Connector

Surge killer

Timer (Anti short cycle)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Please remove the jumper wire ( Mark) in the above

diagram if you use the Switch <SW2> at local.

If the Switch <SW2> is not used, the Fan motor

(indoor) drives at high speed.

6.When PAC-204RC is used, Timer(TM)is unneccessary.

7.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

Power (Active)

Cooling operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

FAN HI

24VAC(N)

- 52 -

PE-8,10MYC-EU

(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

PU-8, 10MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

RED

BLUE

PE

F3(3.15A)

RED

WHITE

52C

BLACK

52C

49C

51F2

63H

51C

CZ2

CH

30

CZ

30

CZ

52C

CR2

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

51C

TB5

15

GRAY

CZ2

14

1

2

3

1

C4

2

3

RED

WHITE

BLACK

RED

WHITE

BLACK

C5

MF2

MF3

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

PE-8, 10MYC-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N

PE

BLUE

RED

WHITE

BLACK

F3(3.15A)

RED

52F

51F1

C1

4

49F

C1

5

C3

1

26L

C3

3

FZ

30

FZ

30FZ

TB1 5

F1 3

49F

26L

CZ1, 2

30CZ, FZ

C1~ 5

CR1, 2

TM

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat (indoor fan)

Internal thermostat

(compressor)

Over current relay

(compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

Timer (Anti short cycle)

MC

51F

2

3

1

C1

RED

WHITE

BLUE

MF1

RED

C2

1

WHITE

BLUE

2

3

Tr

52F

AC

CR1

220

240V

GRAY

TB4

1

SWITCH BOX

(FIELD SUPPLY)

F2

(3.15A)

23WA

SW1

AC

24V

TB4

CZ1

2

GRAY

4

FZ

3

52F

TM

CZ1

TB3

TM

(3MIN)

15

15

OUTDOOR

CZ2

14

14

- 53 -

1

C1

2

3

MF1

Attach the accessory

C2

1

2

3

1

2

3

Remove

This circuit diagram shows connections.

(If the external static Pressure is less than 30 Pa, change to connections.)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.When PAC-204RC is used, Timer(TM)is unneccessary.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

Power (Active)

Cooling operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

FAN HI

24VAC(N)

PE-15MYC-EU

(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)

OUTDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PU-15MYC1-EU ··· 100A

TB1

L1

L2

L3

N

RED

WHITE

BLACK

BLUE

RED

WHITE

BLACK

RED

WHITE

BLACK

F3(3.15A)

52C2

RED

WHITE

BLACK

51C2

MC2

52C1

RED

WHITE

BLACK

RED

WHITE

BLACK

51

F2

49C1

49C2

52

C1

52

C2

CH1 CH2

51C1 51C2

TM

(3min)

63H1

30

CZ1

30

CZ1

CZ2-1

52

C1

TM

(3min)

CR2

52

C1

63H2

30

CZ2

30

CZ2

CZ2-2

52

C2

2(2sec)

CR3

52

C2

2

52

C1

52

C2

CZ2-1

CZ2-2

52

F2

TM

52

C1

52

C2

52F2

51C1

MC1

51F2

1

C1

2

3

RED

WHITE

BLACK

MF2

TB4

GRAY

11 12

CZ

2-1

CZ

2-2

13

INDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PE-15MYC-EU ··· 30A

TB2

L1

L2

L3

N BLUE

RED

WHITE

BLACK

F1

(3.15A)

52F1

30

FZ

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

FZ

30

FZ

Tr

AC

220~

240V

CR1

52

F1

GRAY

F2

(3.15A)

AC

24V

GRAY

1

TB3

51F1

SWITCH BOX (FIELD SUPPLY)

23

WA

23

WA

SW1

TB3

2

CZ

1-1

CZ

1-2

3

5

FZ

4

MF1

52F1

CZ

1-1

CZ

1-2

TB3

11 12 OUTDOOR

11

CZ

2-1

12

CZ

2-2

13

13

Symbol

MC1,2

MF1

MF2

52C1,2

52F1

52F2

TB1~4

CH1,2

F1~3

Tr

49C1,2

51C1,2

51F1

51F2

63H1,2

26L1,2

FZ

30FZ

CZ1-1,2/2-1,2

30CZ1,2

<SW1>

<23WA>

C1, 3, 8

CR1~3

2

TM

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (fan)

Auxiliary relay

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

Timer

Timer (Anti short cycle.)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.When PAC-204RC is used, Timer(TM)is unneccessary.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,

do not change factory set value of Over current relays.

2.To protect the starting Compressor<MC1,2>at the same time, Timer

<2> is installed. Therefore, do not change factory set value of this Timer.

3.To protect the starting Compressor<52C1,2>frequently, Timer

<TM> is installed. Therefore, do not change factory set value of this Time

Option controller connection.

Symbol No.

Function

TB3

4

5

1 Power (Active)

2 Cooling operation

3 Cooling operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

FAN HI

24VAC(N)

- 54 -

PE-20MYC-EU

(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)

OUTDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

TB1

L1

RED

L2

L3

N

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PU-20MYC1-EU ··· 125A

WHITE

BLACK

BLUE

RED

WHITE

BLACK

RED

WHITE

BLACK

52C1

52C2

52

C1

CH1

F3 (3.15A)

52

C2

CH2

49C1

51

F2

63H1

51C1

30

CZ1

30

CZ1

CZ2-1

52

C1

52F2

RED

WHITE

BLACK

49C2

51

F3

TM

(3min)

63H2

52

C1

51C2

CR2

30

CZ2

CZ2-2

52

C2

2(2sec)

CR3

52

C2

30

CZ2

2

52

F2

52

C1

52

C2

TM

CZ2-1 CZ2-2

52

C1

52

C2

RED

WHITE

BLACK

TB4

GRAY

11 12

CZ

2-1

13

INDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

TB2

L1

L2

L3

N BLUE

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PE-20MYC-EU ··· 30A

RED

WHITE

BLACK

F1

(3.15A)

52F1

30

FZ

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

FZ

Tr

AC

220~

240V

30

FZ CR1

52

F1

GRAY

F2

(3.15A)

AC

24V

GRAY

1

TB3

51F1

23

WA

23

WA

SW1

FZ

4

MF1

52F1

SWITCH BOX (FIELD SUPPLY)

TB3

2

CZ

1-1

CZ

1-2

3

5

CZ

1-1

CZ

1-2

TB3

11 12 OUTDOOR

11

CZ

2-1

12

CZ

2-2

13

13

51C1

RED

WHITE

BLACK

51C2

RED

WHITE

BLACK

51F2

51F3

MC1

MC2

1

C1

RED

2

3

WHITE

BLACK

MF2

1

C2

RED

2

3

WHITE

BLACK

MF3

Symbol

MC1,2

MF1

MF2,3

52C1,2

52F1

52F2

TB1~4

CH1,2

F1~3

Tr

49C1,2

51C1,2

51F1

51F2,3

63H1,2

26L1,2

FZ

30FZ

CZ1-1,2/2-1,2

30CZ1,2

<SW1>

<23WA>

C1~3, 8

CR1~3

2

TM

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (fan)

Auxiliary relay

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

Timer

Timer (Anti short cycle.)

- 55 -

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.When PAC-204RC is used, Timer(TM)is unneccessary.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,

do not change factory set value of Over current relays.

2.To protect the starting Compressor <MC1,2>at the same time, Timer

<2> is installed. Therefore, do not change factory set value of this Time

3.To protect the starting Compressor<52C1,2> frequently, Timer

<TM> is installed. Therefore, do not change factory set value of this Ti

Option controller connection.

Symbol No.

Function

TB3

1

2

Power (Active)

Cooling operation

3 Cooling operation

4 Fan operation

5 Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

FAN HI

24VAC(N)

PE-7MYC-EU

(SPECIAL ORDER : LOW AMBIENT COOLING)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

PU-7MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

RED

BLUE

F3(3.15A)

PE

49C

52C

51F2

C4

4

49F

C4

5

63H

CH

51C

CZ2

30

CZ

30

CZ

52C

52F4

CR2

3

1

23C

H

5

52

F3

52

F2

52F2 52F3

Power Supply, Single Phase

220 240Volt,50Hertz

TB2

L

PE-7MYC-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N

RED

BLUE

RED

F1 (3.15A)

PE

51F1

C3

1

26L

C3

3

FZ

Tr

30

FZ

30FZ

52F1

AC

220

240V

CR1

BLUE

RED

WHITE

BLACK

52C

TB5

15

GRAY

CZ2

14

RED

WHITE

BLACK

RED

WHITE

51F2

BLACK

51C

MC

52F4

1

2

3

1

C4

RED

2

3

WHITE

BLACK

52F2

C5

RED

WHITE

BLACK

MF2

MF3

WHITE

C6

2

BLACK

RED

3

1

52F1

GRAY

F2

(3.15A)

AC

24V

TB4

1

51F1

SWITCH BOX

(FIELD SUPPLY)

JUMPER

TB4

5

TB4

Hi

6

Low

7

SW2(FIELD SUPPLY)

52F1

1

C1

RED

2

5

C1

BROWN

MF1 6

4

BLUE

C

TB3

CZ1

15

15

23WA OUTDOOR

SW1

CZ2

TB4

2

CZ1

3

GRAY

4

FZ

14

14

52F3

52F1

52F2 4

23C

TB1 5

CH

F1 3

Tr

49F

26L

CZ1, 2

30CZ, FZ

C

C1, 3~6

CR1, 2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Ambient temperature

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat

(compressor)

Internal thermostat(fan O/D)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

Thermostat (freeze protection)

High-pressure switch

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (check)

Switch (on)

Switch (Fan Hi-Low)

Thermostat (room temp.)

Run capacitor

Connector

Surge killer

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Please remove the jumper wire ( Mark) in the above

diagram if you use the Switch <SW2> at local.

If the Switch <SW2> is not used, the Fan motor

(indoor) drives at high speed.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

3

4

1

2

Power (Active)

Cooling operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

FAN HI

24VAC(N)

- 56 -

PE-8,10MYC-EU

(SPECIAL ORDER : LOW AMBIENT COOLING)

Power Supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

PU-8,10MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY)100A N

RED

BLUE

F3(3.15A)

RED

WHITE

BLACK

52C

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

51C

MC

1

C4

2

3

RED

WHITE

BLACK

MF2

WHITE

BLACK

RED

C6

2

3

1

52F2

PE

49C

52C

51F2

C4

4

49F2

C4

5

63H

51C

CZ2

CH

30

CZ

52C

30

CZ

52F4

CR2

3

1

23C

5

H

52

F3

52

F2

52F2 52F3

TB5

GRAY

15

CZ2

14

52F4

1

2

3

C5

RED

WHITE

BLACK

MF3

Power Supply,

380 415Volt,

3Phase

50Hertz

TB2

L1

L2

L3

PE-8,10MYC-EU CIRCUIT BREAKER

(FIELD SUPPLY)15A N

PE

BLUE

RED

WHITE

BLACK

RED

F1(3.15A)

52F1

51F1

C1

4

49F1

C1

5

C3

1

26L

C3

3

FZ

30FZ

Tr

52F1

AC

220

CR1 240V

30

FZ

51F

GRAY

F2

(3.15A)

AC

24V

2

3

1

C1

RED

WHITE

BLUE

MF1

RED

C2

1

WHITE

BLUE

2

3

TB4

TB4

CZ1

GRAY

4

1

2

SWITCH BOX

(FIELD SUPPLY)

23WA

SW1

FZ

3

52F1

52F3

TB3

CZ1

15

15

OUTDOOR

CZ2

14

14

52F1

52F2 4

23C

TB1 5

CH

F1 3

Tr

49F1

49F2

26L

CZ1, 2

30CZ, FZ

C1~6

CR1, 2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Ambient temperature

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat

(indoor fan)

Internal thermostat (outdoor fan)

Internal thermostat (compressor)

Over current relay

(compressor)

Over current relay(fanI/D,O/D)

Thermostat (freeze protection)

High-pressure switch

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

1

C1

2

3

Attach the accessory

Remove

MF1

C2

1

2

3

1

2

3

This circuit diagram shows connections.

(If the external static Pressure is less than 30 Pa, change to connections.)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

3

4

1

2

Power (Active)

Cooling operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

FAN HI

24VAC(N)

- 57 -

PE-15MYC-EU

(SPECIAL ORDER : LOW AMBIENT COOLING)

OUTDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PU-15MYC1-EU ··· 100A

TB1

L1

L2

L3

N

RED

WHITE

BLACK

BLUE

RED

WHITE

BLACK

RED

WHITE

BLACK

F3(3.15A)

51

F2

49C1

52

C1

52

C2

51C1

52C2

RED

WHITE

BLACK

51C2

MC2

49C2

51C2

52

C1

52

C2

26D

CH1 CH2

63H1

30

CZ1

30

CZ1

CZ2-1

52

C1

63H2

CR2

30

CZ2

30

CZ2

CZ2-2

52

C2

2

CR3

2

52

F3

52

F2

H

52

F2

52

F3

52C1

RED

WHITE

BLACK

51F2

RED

WHITE

BLACK

51C1

1

C1

2

3

RED

WHITE

BLACK

52F2

MF2

MC1

RED

WHITE

BLACK

C2

2

3

1

52F3

TB4

GRAY

11 12

CZ

2-1

CZ

2-2

13

INDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

TB2

L1

L2

L3

N

BLUE

CIRCUIT BREAKER

(FIELD SUPPLY)

PE-15MYC-EU ··· 30A

RED

WHITE

BLACK

F1

(3.15A)

52F1

30

FZ

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

FZ

30

FZ

Tr

AC

220~

240V

CR1

52

F1

GRAY

F2

(3.15A)

AC

24V

GRAY

1

TB3

51F1

SWITCH BOX (FIELD SUPPLY)

23

WA

23

WA

SW1

TB3

2

CZ

1-1

CZ

1-2

3

5

FZ

4

MF1

52F1

TB3

11

CZ

1-1

CZ

1-2

12

OUTDOOR

11

CZ

2-1

12

CZ

2-2

13

13

Symbol

MC1,2

MF1

MF2

52C1,2

52F1

52F2

TB1~4

CH1,2

F1~3

Tr

49C1,2

51C1,2

51F1

51F2,3

63H1,2

26L1,2

FZ

30FZ

CZ1-1,2/2-1,2

30CZ1,2

<SW1>

<23WA>

C1~3, 8

CR1~3

2

26D

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fan)

Auxiliary relay (fan)

Auxiliary relay

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

Timer

Thermostat (ambient temp.)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays <51C1,2>,<51F1,2> are installed. Therefore,

do not change factory set value of Over current relays.

2.To protect the starting Compressor <MC1,2>at the same time,Timer

<2> is installed. Therefore, do not change factory set value of this Timer.

Option controller connection.

Symbol

TB3

No.

Function

1

2

Power (Active)

Cooling operation

3 Cooling operation

4 Fan operation

5 Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

FAN HI

24VAC(N)

- 58 -

PE-20MYC-EU

(SPECIAL ORDER : LOW AMBIENT COOLING)

OUTDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

N

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PU-20MYC1-EU ··· 125A

TB1

L1

L2

L3

BLUE

RED

WHITE

BLACK

52

C1

CH1

F3(3.15A)

RED

WHITE

BLACK

RED

WHITE

BLACK

52

C2

CH2

49C1

51

F2

63H1

51C1

30

CZ1

30

CZ1

CZ2-1

52

C1

49C2

51

F3

63H2

52

C1

52

C2

51C2

CR2

30

CZ2

30

CZ2

CZ2-2

52

C2

2

CR3

2

FZ2

H

26D1

FZ3

H

FZ

2

26D2

FZ

2

FZ

3

FZ

3

FZ

4

FZ5

H

26D3

FZ6

H

FZ

5

26D4

FZ

5

52

F6

FZ

6

52

F7

FZ

7

TB4

GRAY

11 12

CZ

2-1

CZ

2-2

FZ4

FZ7

13

52C1

52C2

51C1

RED

WHITE

BLACK

51C2

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

L1-1

TB5

L2-1

L3-1

RED

WHITE

BLACK

52F3

52F2

Tr2

52F4

RED

WHITE

BLACK

51F4

L1-1

TB6

L2-1

L3-1

RED

WHITE

BLACK

52F6

52F5

Tr3

52F7

MC1

MC2

51F3

RED

WHITE

BLACK

TB5

L1-2

L2-2

L3-2

1

C1

2

3

RED

WHITE

BLACK

MF2

51F5

RED

WHITE

BLACK

TB6

L1-2

L2-2

L3-2

1

C2

2

3

RED

WHITE

BLACK

MF3

INDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PE-20MYC-EU ··· 30A

TB2

L1

L2

L3

N

BLUE

RED

WHITE

BLACK

F1

(3.15A)

52F1

30

FZ

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

FZ1

30

FZ

Tr1

AC

220~

240V

CR1

52

F1

GRAY

F2

(3.15A)

AC

24V

GRAY

1

TB3

51F1

SWITCH BOX (FIELD SUPPLY)

23

WA

23

WA

SW1

TB3

2

CZ

1-1

CZ

1-2

3

5

4

FZ1

MF1

52F1

CZ

1-1

CZ

1-2

TB3

11 12 OUTDOOR

11 12

CZ

2-1

CZ

2-2

13

13

Symbol

MC1,2

MF1

MF2,3

52C1,2

52F1

52F2~7

TB1~6

CH1,2

F1~3

Tr1~3

49C1,2

51C1,2

51F1

51F2~F5

63H1,2

26L1,2

FZ1

30FZ

CZ1-1,2/2-1,2

30CZ1,2

<SW1>

<23WA>

C1~3, 8

CR1~3

2

26D1~4

FZ2~7

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Auxiliary relay (fanI/D)

Auxiliary relay (fanI/D)

Auxiliary relay

Auxiliary relay (check)

Switch (on)

Thermostat (room temp.)

Connector

Surge killer

Timer

Thermostat (ambient temp.)

Auxiliary relay (fan O/D)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays <51C1,2>,<51F1~5> are installed. Therefore,

do not change factory set value of Over current relays.

2.To protect the starting Compressor <MC1,2>at the same time,Timer

<2> is installed. Therefore, do not change factory set value of this Timer.

- 59 -

Option controller connection.

Symbol No.

Function

TB3

1

2

Power (Active)

Cooling operation

3 Cooling operation

4 Fan operation

5 Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

FAN HI

24VAC(N)

PEH-5MYA-EU (STANDARD)

Power Supply,

380~415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

RED

N

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PUH-5MYE-EU···50A

BLUE

F3(3.15A)

RED

WHITE

BLACK

52C

HZ2

RED

WHITE

BLACK

51F2

51C

X1

RED

WHITE

BLACK

1

C4

2

3

RED

WHITE

BLACK

MF2

52C

CH

51F2

63H

51C

CZ2

30

CZ

30

CZ

52C

X3 X1 X2 T1 X1

CR2

T1

21

S4

X3

C6

1

26

D1

C6

3

C7

3

26

D2

C7

1

X2

GRAY

15 13

TB4

CZ2

14

HZ2

X1 X2

Power Supply, 3Phase

380~415Volt, 50Hertz

N

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PEH-5MYA-EU···15A

TB2

L1

L2

L3

F1

RED

WHITE

BLACK

F1(3.15A)

51F1

C1

4

49F

C1

5

52F

FZ

51F1

1

C1

RED

2

3

WHITE

BLUE

V

W

U

MF1

X

Y

Z

WHITE

C2

2

BLUE

RED

3

1

52F

Tr

AC

220~

CR1

240V

GRAY

TB3

1

F2

(3.15A)

COOL

SW1

HEAT

SWITCH BOX

(FIELD SUPPLY)

C H

23

WA

SW2

AC

24V

TB3

2 3

CZ1

HZ1

GRAY

5

FZ

4

30FZ

30

FZ

BLUE

Symbol

MC

MF1

MF2

52C

52F

TB1~4

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

CH

F1~3

Tr

49F

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(indoor fan)

51C

51F1,2

Over current relay(compressor)

Over current relay(fanI/D,O/D)

63H High-pressure switch

26D1,2 Thermostat (defrost)

21S4

FZ

CZ1,2

HZ1,2

30CZ,FZ

X1

X2,3

<SW1>

4-Way valve

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

<SW2> Switch (on)

<23WA> Thermostat (room temp.)

C1,2,4,6,7

T1

Connector

Timer (defrost)

CR1,2 Surge killer

1

C1

2

3

MF1

52F

Attach the accessory

C2

2

3

1

2

3

1

Remove

This circuit diagram shows connections.

(If the external static Pressure is less than 30 Pa, change to connections.)

MC

INTERNAL

PROTECTOR

TB3

CZ1 HZ1

15 13

15 13

OUTDOOR

CZ2 HZ2

- 60 -

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays<51C>,<51F1,2>are installed. Therefore,

do not change factory set value of Over current relays.

Option controller connection.

Symbol

TB3

No.

Function

4

5

1

2

3

Power (Active)

Cooling operation

Revercing Valve for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

4WV

FAN HI

24VAC(N)

14

14

PEH-7MYA-EU (STANDARD)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

PUH-7MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

RED

BLUE

PE

F3(3.15A)

52C

CH

30

CZ

49C

51F2

63H

51C

CZ2

30

CZ

RED

WHITE

BLACK

52C

HZ2

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

51C

X1

52C

X3 X1 X2

T1

X1

T1

21

S4

CR2

X3

C6

1

26

D1

C6

3

C7

3

26

D2

C7

1

X2

TB5

15

GRAY

CZ2

14

HZ2

13

X1 X2

1

2

3

1

C4

2

3

RED

WHITE

BLACK

RED

WHITE

BLACK

C5

MF2

MF3

MC

Power supply,

220 240Volt,

Single Phase

50Hertz

TB2

L

PEH-7MYA-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N

PE

RED

BLUE

RED

F1 (3.15A)

51F1

BLUE

30

FZ

C3

1

26L

C3

3

HZ1

FZ

30FZ

TB1 5

F1 3

26L

CZ1, 2

HZ1, 2

30CZ, FZ

3

C

C1, C3 7

T1

CR1, 2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat

(compressor)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Thermostat (defrost)

4-Way valve

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Switch (Fan Hi-Low)

Thermostat (room temp.)

Run capacitor

Connector

Timer (defrost)

Surge killer

Tr

52F

AC

220

240V

CR1

52F

51F1

GRAY

TB4

1

F2

(3.15A)

COOL

SW1

HEAT

SWITCH BOX

(FIELD SUPPLY)

JUMPER

TB4

6

TB4

Hi

7

Low

8

SW3(FIELD SUPPLY)

52F

1

C1

RED

2

BROWN

MF1

6

5

C1

4 BLUE

C

TB3

CZ1 HZ1

15

15

13

13

OUTDOOR

C H

23

WA

SW2

CZ2

HZ2

24V

TB4

2 3 4

CZ1 HZ1

14

FZ

GRAY

5

14

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Please remove the jumper wire ( Mark) in the above

diagram if you use the Switch <SW3> at local.

If the Switch <SW3> is not used, the Fan motor

(indoor) drives at high speed.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB3

1

2

3

4

5

Power (Active)

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

4WV

FAN HI

24VAC(N)

- 61 -

PEH-8,10MYA-EU (STANDARD)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

RED

RED

WHITE

BLACK

52C

RED

WHITE

BLACK

51C

51F2

CIRCUIT BREAKER

(FIELD SUPPLY)

N

BLUE

F3(3.15A)

RED

WHITE

BLACK

X1

PUH-8, 10MYC1-EU ··· 100A

PUH-8,10MYE-EU ···100A

PE

52C

CH

30

CZ

49C

51F2

63H

51C

CZ2

30

CZ

HZ2

1

2

3

1

C4

2

3

RED

WHITE

BLACK

RED

WHITE

BLACK

C5

MF2

MF3

MF3 is only PUH-8,10MYC1-EU.

52C

X3 X1 X2

T1

X1

CR2

T1

21

S4

X3

C7

3

26

D2

C7

1

C6

1

26

D1

C6

3

X2

GRAY

15

CZ2

14

HZ2

TB4 (In case of PUH-8,10MYE-EU)

13

TB5 (In case of PUH-8,10MYC1-EU)

X1

X2

MC

Power supply,

380 415Volt,

3Phase

50Hertz

L1

TB2

L2

L3

PEH-8,10MYA-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N

PE

BLUE

TB1 5

F1 3

49F

26L

CZ1, 2

HZ1, 2

30CZ, FZ

C1~7

T1

CR1, 2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat (indoor fan)

Internal thermostat

(compressor)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Thermostat (defrost)

4-Way valve

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Thermostat (room temp.)

Connector

(C5 is PUH-8,10MYC1-EU only.)

Timer (defrost)

Surge killer

RED

WHITE

BLACK

RED

F1(3.15A)

52F

30

FZ

C3

1

26L

C3

3

51F1

C1

4

49F

C1

5

HZ1

FZ

30FZ

52F

Tr

CR1

AC

220

240V

51F1

1

C1

2

3

RED

WHITE

BLUE

MF1

RED

WHITE

BLUE

C2

1

2

3

TB4 1

GRAY

F2

(3.15A)

COOL

SW1

HEAT

SWITCH BOX

(FIELD SUPPLY)

C H

23

WA

SW2

AC

24V

TB4

2

3

CZ1

HZ1

GRAY 5

FZ

4

52F

1

C1

2

3

MF1

Attach the accessory

C2

1

2

3

1

2

3

Remove

This circuit diagram shows connections.

(If the external static Pressure is less than 30 Pa, change to connections.)

TB3

CZ1 HZ1

15 13

15 13

OUTDOOR

CZ2 HZ2

14

14

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

5

Power (Active)

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

4WV

FAN HI

24VAC(N)

- 62 -

PEH-15,20MYA-EU (STANDARD)

Power supply, 3 Phase

380~415 Volt, 50Hertz

L1

L2

L3

N

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PUH-15MYC1-EU---100A

PUH-20MYC1-EU---125A

RED

WHITE

BLACK

BLUE

CH1 CH2

RED

WHITE

BLACK

RED

WHITE

BLACK

F3 (3.15A)

49C1

63H1

51C1

30

CZ1

CZ2-1

49C2

HZ2

63H2

51C2

CR2

30

CZ2

CZ2-2

2

CR3

X1 X2 X5

T1

X3

C6

C6

C4

C4

3

1

26

D3

1

3

26

D1

X3

RED

WHITE

BLACK

RED

WHITE

BLACK

RED

WHITE

BLACK

X2 X6

T2

C7 3

C7 1

26

D4

X4

GRAY

RED

WHITE

BLACK

C5

C5

1

3

26

D2

X4

S4-2

S4-1

Power supply, 3 Phase

380~415 Volt, 50Hertz

L1

L2

L3

N

BLUE

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PEH-15,20MYA-EU---30A

RED

WHITE

BLACK

F1

(3.15A)

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

HZ1

AC

220

240V

30

FZ

CR1

GRAY

F2

(3.15A)

AC

24V

COOL

HEAT

C H C H

1-1 1-2

GRAY

CZ

1-1

CZ

1-2

HZ1

Symbol

MC1,2

MF1

MF2,3

52C1,2

52F

TB1 4

CH1,2

F1 3

Tr

49C1,2

51C1,2

51F1

51F2,3

63H1,2

26L1,2

26D1 4

21S4-1,2

FZ

30FZ

CZ1-1,2/2-1,2

HZ1,2

30CZ1,2

X1,2

X3 6

<SW1>

<SW2>

<23WA>

C1~8

T1,2

2

CR1 3

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Thermostat (defrost)

4-Way valve

Auxiliary relay (fan)

Auxiliary relay (fan)

Auxiliary relay

Auxiliary relay (heater)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Thermostat (room temp.)

Connector

Timer (defrost)

Timer

Surge killer

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays<51C1,2>,<51F1,2,3> are installed. Therefore,

do not change factory set value of Over current relays.

Option controller connection.

Symbol No.

1

2

TB3

3

4

5

6

Function

Power (Active)

Cooling or Heating

operation

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

4WV

FAN HI

24VAC(N)

- 63 -

RED

WHITE

BLACK

RED

WHITE

BLACK

(

PEH-5MYA-EU

SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,

PROTECT FOR COOL AIR BLOW.

)

Power Supply,

380~415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

RED

N

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PUH-5MYE-EU···-50A

BLUE

F3(3.15A)

RED

WHITE

BLACK

52C

HZ2

RED

WHITE

BLACK

51F2

51C

X1

RED

WHITE

BLACK

1

C4

2

3

RED

WHITE

BLACK

MF2

52C

CH

51F2

63H

51C

CZ2

30

CZ

30

CZ

52C

X3 X1 X2 T1 X1

CR2

T1

21

S4

X3

C7

3

26

D2

C7

1

C6

1

26

D1

C6

3

X2

GRAY

15 13

TB4

CZ2

14

HZ2

X1 X2

16

X3

17

MC

INTERNAL

PROTECTOR

Power Supply,

380~415Volt,

3Phase

50Hertz

TB2

L1

L2

L3

PE

N

CIRCUIT BREAKER

(FIELD SUPPLY)

PEH-5MYA-EU···U15A

RED

WHITE

BLACK

F1(3.15A)

52F

51F1

30

FZ

C1

4

49F

C1

5

30FZ

FZ

OUT

DOOR

16

16

X3

17

Tr

17

AC

CR1

220~

240V

52F

51F1

1

C1

RED

2

WHITE

3

BLUE

V

U

W

MF1

X

Y

Z

WHITE

C2

2

BLUE

RED

3

1

GRAY

TB3

1

SWITCH BOX

(FIELD SUPPLY)

F2

(3.15A)

COOL

C H

23

WA

AC

24V

SW1

HEAT

TB3

2

3

CZ1 HZ1

SW2

FZ

4

GRAY

5

52F

TM

TB3

TM

(3MIN)

15 13

15 13

BLUE

Symbol

MC

MF1

MF2

52C

52F

TB1~4

CH

F1~3

Tr

49F

51C

51F1,2

63H

26D1,2

Name

Compressor motor

Fan motor (indoor)

Symbol

21S4

FZ

Name

4-Way valve

Auxiliary relay (fan)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(indoor fan)

Over current relay(compressor)

CZ1,2

HZ1,2

30CZ,FZ

X1

X2,3

<SW1>

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

<SW2> Switch (on)

<23WA> Thermostat (room temp.)

C1~4,6,7 Connector

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (defrost)

T1

CR1,2

TM

Timer (defrost)

Surge killer

Timer (Anti short cycle)

Option controller connection.

Symbol No.

Function

TB3

1

2

3

4

5

Power (Active)

Cooling operation

Revercing Valve for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

4WV

FAN HI

24VAC(N)

1

C1

2

3

MF1

Attach the accessory

C2

2

3

1

2

3

1

Remove

This circuit diagram shows connections.

(If the external static Pressure is less than 30 Pa, change to connections.)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.When PAC-204RC is used, Timer(TM)is unneccessary.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays<51C>,<51F1,2>are installed. Therefore,

do not change factory set value of Over current relays.

CZ1 HZ1

CZ2

HZ2

14

14

OUTDOOR

- 64 -

(

PEH-7MYA-EU

SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,

PROTECT FOR COOL AIR BLOW.

Power supply,

3Phase

50Hertz 380 415Volt,

TB1

L1 RED

52C

RED

51C

RED

L2

WHITE WHITE

L3 BLACK

BLACK

51F2

PUH-7MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

BLUE

F3(3.15A)

52C

49C

HZ2

X3 X1 X2 T1 X1 15 13

16

RED

WHITE

BLACK

X1

1

2

3

1

C4

2

3

RED

WHITE

BLACK

RED

WHITE

BLACK

)

PE

TB5

GRAY

C5

51F2

63H

C7

3

26

D2

C7

1

CZ2 HZ2

X3

17

51C

CZ2

T1

21

S4

C6

1

26

D1

CH

30

CZ

X3

X2

14

CR2

C6

3

52C

30

CZ

X1

X2

MF2

MF3

MC

Power supply,

220 240Volt,

Single Phase

50Hertz

TB2

L

PEH-7MYA-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N

PE

RED

BLUE

RED

F1 (3.15A)

51F1

C3

1

26L

C3

3

HZ1

FZ

30FZ

BLUE

30

FZ

TB1 5

F1 3

26L

CZ1, 2

HZ1, 2

30CZ, FZ

3

C

C1, 3~7

T1

CR1, 2

TM

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat

(compressor)

Over current relay

(compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Thermostat (defrost)

4-Way valve

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Switch (Fan Hi-Low)

Thermostat (room temp.)

Run capacitor

Connector

Timer (defrost)

Surge killer

Timer (Anti short cycle)

OUT

DOOR

16

Tr

16

X3

17

17

CR1

AC

220

240V

52F

52F

GRAY

TB4

1

51F1

SWITCH BOX

(FIELD SUPPLY)

JUMPER

TB4

6

TB4

Hi

7

Low

8

SW3(FIELD SUPPLY)

52F

1

C1

RED

2

5

C1

BROWN

MF1 6

4

BLUE

CZ1 HZ1

C

F2

(3.15A)

COOL

SW1

HEAT

TB3

TM

(3MIN)

15

13

15 13

C H

23

WA

SW2

OUTDOOR

AC

24V

4

CZ2 HZ2

TB4

2

3

CZ1 HZ1

TM

GRAY

5

FZ

14

14

- 65 -

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Please remove the jumper wire ( Mark) in the above

diagram if you use the Switch <SW3> at local.

If the Switch <SW3> is not used, the Fan motor

(indoor) drives at high speed.

6.When PAC-204RC is used, Timer(TM)is unneccessary.

7.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

5

Power (Active)

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

4WV

FAN HI

24VAC(N)

(

PEH-8,10MYA-EU

SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,

PROTECT FOR COOL AIR BLOW.

)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

RED

RED

WHITE

52C

BLACK

RED

WHITE

BLACK

51C

MC

51F2

PUH-8, 10MYE-EU

PUH-8, 10MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

PE

BLUE

F3(3.15A)

49C

HZ2

RED

WHITE

BLACK

X1

1

2

3

1

C4

2

3

RED

WHITE

BLACK

RED

WHITE

BLACK

C5

MF2

MF3

MF3 is only PUH-8,10MYC1-EU.

X3 X1 X2

T1

X1

52C

51F2

63H

C7

3

26

D2

C7

1

TB4 (In case of PUH-8,10MYE-EU)

TB5 (In case of PUH-8,10MYC1-EU)

15 13

16

GRAY

X3

51C

CZ2

CH

T1

CR2

21

S4

X3

C6

1

26

D1

C6

3

X2

CZ2 HZ2

17

30

CZ

14

52C

30

CZ X1 X2

Power supply,

380 415Volt,

3Phase

50Hertz

TB2

L1

L2

L3

PEH-8, 10MYA-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

N BLUE

PE

RED

WHITE

BLACK

F3(3.15A)

RED

52F

51F1

C1

4

49F

C1

5

C3

1

26L

C3

3

HZ1

FZ

30

FZ

30FZ

BLUE

TB1 5

F1 3

49F

26L

CZ1, 2

HZ1, 2

30CZ, FZ

C1~7

CR1, 2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat (indoor fan)

Internal thermostat

(compressor)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Thermostat (defrost)

4-Way valve

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Thermostat (room temp.)

Connector

(C5 is PUH-8,10MYC-EU only.)

Timer (defrost)

Surge killer

Timer (Anti short cycle)

51F

1

C1

RED

2

3

WHITE

BLUE

MF1

RED

C2

1

WHITE

BLUE

2

3

OUT

DOOR

16

16

X3

17

Tr

17

CR1

AC

220

240V

52F

GRAY

TB4

1

F2

(3.15A)

COOL

SW1

HEAT

SWITCH BOX

(FIELD SUPPLY)

C H

23

WA

SW2

AC

24V

TB4

2 3

CZ1

HZ1

GRAY

5

FZ

4

52F

1

C1

2

3

MF1

Attach the accessory

C2

1

2

3

1

2

3

Remove

TM

CZ1 HZ1

TB3

TM

(3MIN)

15 13

15 13

OUTDOOR

CZ2 HZ2

14

14

- 66 -

This circuit diagram shows connections.

(If the external static Pressure is less than 30 Pa, change to connections.)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.When PAC-204RC is used, Timer(TM)is unneccessary.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

5

Power (Active)

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

4WV

FAN HI

24VAC(N)

PEH-15,20MYA-EU

(SPECIAL WIRING : ANTI SHORT CYCLE TIMER)

OUTDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

TB1

L1

L2

L3

RED

WHITE

BLACK

N

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PUH-15MYC1-EU ··· 100A

PUH-20MYC1-EU ··· 125A

BLUE

RED

WHITE

BLACK

52

C1

CH1

RED

WHITE

BLACK

F3 (3.15A)

49C1

52

C2

CH2

HZ2

CZ2-1

CZ2-2 49C2

51

F2

63H1

51C1

30

CZ1

30

CZ1

CZ2-1

52

C1

51

F3

TM

(3min)

TM

(3min)

52

C1

63H2

51C2

CR2

30

CZ2

30

CZ2

CZ2-2

52

C2

2

CR3

52

C2

2

TM

52

C1

52

C2

X1 X2 X5

T1

X3

52C1

52C2

X2 X6

T2

X4

21

S4-1

T1

C6

C6

C4

C4

3

1

26

D3

1

26

D1

3

X3

X1

X3

X5

21

S4-2

T2

X2

C7

C7

C5

C5

3

1

26

D4

1

3

26

D2

X4

X4

X6

RED

WHITE

BLACK

51F2

RED

WHITE

BLACK

RED

WHITE

BLACK

RED

WHITE

BLACK

51F3

51C1

51C2

X1

X2

GRAY

11 12

TB4

13

CZ

2-1

CZ

2-2

HZ2

14

MC1

1

C1

RED

2

3

WHITE

BLACK

MF2

MC2

1

C2

RED

2

3

WHITE

BLACK

MF3

INDOOR UNIT

Power supply, 3 Phase

380~415 Volt, 50Hertz

PE

TB2

L1

L2

L3

N

BLUE

CIRCUIT BREAKER

(FIELD SUPPLY)

PEH-15,20MYA-EU ··· 30A

52F

RED

WHITE

BLACK

F1

(3.15A)

51F1

Tr

C3

1

26L1

C3

3

C8

1

26L2

C8

3

HZ1

FZ

30

FZ

OUT

DOOR

AC

220~

240V

CR1

30

FZ

52F

51F1

GRAY

F2

(3.15A)

1

TB3

AC

24V

GRAY

Symbol

MC1,2

MF1

MF2,3

52C1,2

52F

TB1~4

CH1,2

F1~3

Tr

49C1,2

51C1,2

51F1

51F2,3

63H1,2

26L1,2

26D1~4

21S4-1,2

FZ

30FZ

CZ1-1,2/2-1,2

HZ1,2

30CZ1,2

X1,2

X3~6

<SW1>

<SW2>

<23WA>

C1~8

T1,2

2

CR1~3

TM

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D)

Over current relay(fanO/D)

High-pressure switch

Thermostat (freeze protection)

Thermostat (defrost)

4-Way valve

Auxiliary relay (fan)

Auxiliary relay (fan)

Auxiliary relay

Auxiliary relay (heater)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Thermostat (room temp.)

Connector

Timer (defrost)

Timer

Surge killer

Timer (Anti short cycle)

MF1

COOL

SW1

HEAT

C H C

23

WA

H

SW2

TB3

CZ

1-1

2 3

CZ

1-2

HZ1

4

FZ

5

6

52F

SWITCH BOX (FIELD SUPPLY)

Caution,

CZ

1-1

CZ

1-2

HZ1

TB3

11

11

CZ

2-1

CZ

2-2

12

12

13

13

OUTDOOR

HZ2

14

14

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.When PAC-204RC is used, Timer(TM)is unneccessary.

6.Specification subject to change without notice.

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,

do not change factory set value of Over current relays.

2.To protect the starting Compressor <MC1,2>at the same time, Timer

<2> is installed. Therefore, do not change factory set value of this Timer.

3.To protect the starting Compressor<52C1,2> frequently, Timer

<TM> is installed. Therefore, do not change factory set value of this Timer.

Option controller connection.

Symbol No.

Function

TB3

1

2

3

4

5

6

Power (Active)

Cooling or Heating

operation

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

4WV

FAN HI

24VAC(N)

- 67 -

PEH-7MYA-EU

(SPECIAL ORDER : LOW AMBIENT COOLING)

Power supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

L2

L3

PUH-7MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY) 100A

N

RED

BLUE

Power Supply,

PEH-7MYA-EU

Single Phase

220 240Volt,50Hertz

CIRCUIT BREAKER

(FIELD SUPPLY) 15A

PE

TB2

L

N

PE

F3(3.15A)

52C

49C

51F2

C4

4

49F

C4

5

63H

CH

51C

CZ2

30

CZ

30

CZ

52C

52F4

CR2

HZ2

3

52F2

1

23C

H

52

F3

52

F2

5

52F3

RED

BLUE

RED

F1 (3.15A)

BLUE

30

FZ

51F1

C3

1

26L

C3

3

HZ1

30FZ

FZ

52F1

Tr

AC

220

240V

CR1

RED

WHITE

BLACK

52C

X3 X1 X2 T1

RED

WHITE

BLACK

RED

WHITE

51F2

BLACK

X1

51C

X1

TB5

15

GRAY

13

MC

T1

21

S4

X3

C7

3

26

D2

C7

1

C6

1

26

D1

C6

3

X2

X1 X2

CZ2

14

HZ2

52F4

1

2

3

1

C4

2

3

RED

WHITE

BLACK

52F2

C5

RED

WHITE

BLACK

MF2

MF3

WHITE

C8

2

BLACK

RED

3

1

52F3

52F1

GRAY

F2

(3.15A)

TB4

COOL

1

SW1

HEAT

51F1

SWITCH BOX

(FIELD SUPPLY)

JUMPER

TB4

6

TB4

Hi

7

Low

8

SW3(FIELD SUPPLY)

52F1

1

C1

RED

2

5

C1

BROWN

MF1 6

4

BLUE

C

TB3

CZ1

15

HZ1

13

15 13

OUTDOOR

C H

23

WA

SW2

CZ2

HZ2

AC

24V

TB4

2

3

4

CZ1 HZ1

FZ

14

14

GRAY

5

MC

MF1

MF2, 3

52C

52F1

52F2, 3

52F4

23C

TB1 5

CH

F1 3

Tr

49C

49F

51C

51F1,2

63H

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Contactor (fan O/D)

Ambient temperature

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat (compressor)

Internal thermostat (fan O/D)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

FZ

CZ1, 2

HZ1, 2

30CZ, FZ

X1

X2, 3

<SW1>

<SW2>

<SW3>

<23WA>

C

C1, 3 8

T1

CR1, 2

21S4

26D1, 2

26L

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Switch (Fan Hi-Low)

Thermostat (room temp.)

Run capacitor

Connector

Timer (defrost)

Surge killer

4-Way valve

Thermostat (defrost)

Thermostat (freeze protection)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Please remove the jumper wire ( Mark) in the above

diagram if you use the Switch <SW3> at local.

If the Switch <SW3> is not used, the Fan motor

(indoor) drives at high speed.

6.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

5

Power (Active)

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

4WV

FAN HI

24VAC(N)

- 68 -

PEH-8,10MYA-EU

(SPECIAL ORDER : LOW AMBIENT COOLING)

Power Supply,

380 415Volt,

3Phase

50Hertz

TB1

L1

PUH-8,10MYC1-EU

CIRCUIT BREAKER

(FIELD SUPPLY)100A

PUH-8,10MYE-EU

N

L2

L3

RED

BLUE

PE

F3(3.15A)

RED

WHITE

BLACK

52C

49C

52C

51F2

C4

4

49F2

C4

5

63H

51C

CZ2

CH

30

CZ

52C

30

CZ

52F4

CR2

HZ2

3

1

23C

5

H

52

F3

52

F2

52F2 52F3

RED

WHITE

BLACK

RED

WHITE

BLACK

51F2

51C

X1

MC

HZ2

T1

X3 X1 X2 T1 X1

21

S4

X3

C7

3

26

D2

C7

1

C6

1

26

D1

C6

3

X2

X1

X2

Power Supply,

380 415Volt,

3Phase

50Hertz

TB2

L1

L2

L3

PEH-8,10MYA-EU

CIRCUIT BREAKER

(FIELD SUPPLY)15A N

PE

BLUE

RED

WHITE

BLACK

RED

F1(3.15A)

52F1

51F1

C1

4

49F1

C1

5

C3

1

26L

C3

3

HZ1

FZ

30FZ

Tr

52F1

AC

220

CR1 240V

30

FZ

51F

1

C1

RED

2

3

WHITE

BLUE

MF1

RED

WHITE

BLUE

C2

1

2

3

GRAY

TB4

1

F2

(3.15A)

COOL

SW1

HEAT

SWITCH BOX

(FIELD SUPPLY)

C H

23

WA

SW2

AC

24V

TB4

2

CZ1 HZ1

3

GRAY

5

FZ

4

1

C4

RED

2

3

WHITE

BLACK

MF2

WHITE

BLACK

RED

C8

2

3

1

52F2

CZ2 HZ2

14

52F1

52F3

52F4

1

C5

RED

2

3

WHITE

BLACK

MF3 is only PUH-8,10MYC1-EU.

MF3

GRAY

TB4 (In case of PUH-8,10MYE-EU)

TB5 (In case of PUH-8,10MYC1-EU)

15 13

TB3

CZ1 HZ1

15 13

15 13

OUTDOOR

CZ2 HZ2

14

14

MC

MF1

MF2, 3

52C

52F1

52F2, 3

52F4

23C

TB1 5

CH

F1 3

Tr

49C

49F1

49F2

51C

51F1,2

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Contactor (fan O/D)

Contactor (fan O/D)

FZ

CZ1, 2

HZ1, 2

30CZ, FZ

X1

X2, 3

<SW1>

Ambient temperature

Terminal block

Crankcase heater

Fuse (3.15A)

<SW2>

<SW3>

<23WA>

63H

Transformer

Internal thermostat (compressor)

C1~8

T1

Internal thermostat (fan I/D)

Internal thermostat (fan O/D)

Over current relay (compressor)

Over current relay(fanI/D,O/D)

CR1, 2

21S4

26D1, 2

26L

Auxiliary relay (fan)

Auxiliary relay (compressor)

Auxiliary relay (4-way valve)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Switch (Fan Hi-Low)

Thermostat (room temp.)

High-pressure switch

Connector

(C5 is PUH-8,10MYC1-EU only.)

Timer (defrost)

Surge killer

4-Way valve

Thermostat (defrost)

Thermostat (freeze protection)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal

current, Over current relays <51C>, <51F1,2> are installed.

Therefore, do not change factory set value of Over current

relays.

Option controller connection.

Symbol No.

Function

TB4

1

2

3

4

5

Power (Active)

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP

4WV

FAN HI

24VAC(N)

- 69 -

PEH-15,20MYA-EU

(SPECIAL ORDER : LOW AMBIENT COOLING)

OUTDOOR UNIT

Power supply,

3 Phase

380~415 Volt,

50Hertz

TB1

L1

L2

L3

RED

WHITE

BLACK

N

BLUE

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PUH-15MYC1-EU ··· 100A

PUH-20MYC1-EU ··· 125A

52

C1

CH1

WHITE

BLACK

F3 (3.15A)

52

C2

CH2

RED

WHITE

BLACK

RED

49C1

51

F2

63H1

51C1

30

CZ1

30

CZ1

CZ2-1

52

C1

52C1

52C2

RED

WHITE

51C1

MC1

BLACK

RED

WHITE

BLACK

RED

WHITE

BLACK

51C2

51F2

MC2

L1-1

TB5

L2-1

L3-1

Tr2

RED

WHITE

BLACK

52F2

52F3

52F4

HZ2

49C2

51

F3

63H2

51C2

CR2

30

CZ2

CZ2-2

52

C2

30

CZ2

2

CR3

2

FZ2

H

26D5

FZ3

H

FZ

2

26D6

52

FZ

3

FZ

2

FZ

3

FZ

4

52

F3

FZ5

H

26D7

FZ6

H

FZ

5

26D8

52

FZ

6

FZ

5

FZ

6

FZ

7

52

F7

X1

21

S4-1

X2 X5

T1

X3 X2 X6

T2

X4

C6

C6

C4

C4

1

3

26

D1

3

1

26

D3

X3

C7 3

C7 1

26

D4

C5

C5

1

3

26

D2

X4

T1

X1

X3

X5

21

S4-2

T2

X2

X4

X6

RED

WHITE

BLACK

GRAY

11 12

51F4

CZ

2-1

CZ

2-2

HZ2

TB4

13

L1-1

TB6

L2-1

L3-1

FZ4

FZ7

RED

WHITE

BLACK

52F6

Tr3

52F7

52F5

14

INDOOR UNIT

Power supply,

3 Phase

380~415 Volt,

50Hertz

TB2

L1

L2

L3

N

BLUE

PE

CIRCUIT BREAKER

(FIELD SUPPLY)

PEH-15,20MYA-EU ··· 30A

52F1

RED

WHITE

BLACK

F1

(3.15A)

30

FZ

51F1

C3

1

26L1

C3

3

C8

1

26L2

C8

3

HZ1

FZ1

30

FZ

Tr1

AC

220~

240V

CR1

52

F1

GRAY

F2

(3.15A)

AC

24V

TB3

1

51F1

SWITCH BOX (FIELD SUPPLY)

COOL

SW1

HEAT

C

H

C

23

WA

H

SW2

TB3

CZ

1-1

2 3 4

CZ

1-2

HZ1

FZ1

5

MF1

52F

CZ

1-1

CZ

1-2

HZ1

TB3

11 12 13

OUTDOOR

11 12 13

CZ

2-1

CZ

2-2

HZ2

14

GRAY

6 14

51F3

RED

WHITE

TB5

L1-2

L2-2

L3-2

BLACK

2

3

1

C1

RED

WHITE

BLACK

MF2

51F5

RED

WHITE

BLACK

TB6

L1-2

L2-2

L3-2

1

C2

RED

2

WHITE

3

BLACK

MF3

Symbol

MC1,2

MF1

MF2,3

52C1,2

52F1

TB1~6

CH1,2

F1~3

Tr1~3

49C1,2

51C1,2

51F1~5

63H1,2

26L1,2

26D1~4

21S4-1,2

FZ1,30FZ

CZ1-1,2/2-1,2

HZ1,2

30CZ1,2

X1,2

X3~6

<SW1>

<SW2>

<23WA>

C1~8

T1,2

2

CR1~3

26D5~8

52F2~7

FZ2~7

Name

Compressor motor

Fan motor (indoor)

Fan motor (outdoor)

Contactor (compressor)

Contactor (fan I/D)

Terminal block

Crankcase heater

Fuse (3.15A)

Transformer

Internal thermostat(compressor)

Over current relay(compressor)

Over current relay(fanI/D,O/D)

High-pressure switch

Thermostat (freeze protection)

Thermostat (defrost)

4-Way valve

Auxiliary relay (fan I/D)

Auxiliary relay

Auxiliary relay (heater)

Auxiliary relay (check)

Contactor (fan O/D)

Auxiliary relay (defrost)

Switch (operation mode)

Switch (on)

Thermostat (room temp.)

Connector

Timer (defrost)

Timer

Surge killer

Thermostat (ambient temp.)

Contactor (fan O/D)

Auxiliary relay (fan O/D)

Note:1.The dotted lines show field wiring.

2.The figure in the parentheses show field supply parts.

3.Color of earth wire is yellow and green twisting.

4.Not specified color of wire is brown.

5.Specification subject to change without notice.

Caution,

1.To protect each Fan motor and Compressor from abnormal current,

Over current relays<51C1,2>,<51F1~5>are installed. Therefore,

do not change factory set value of Over current relays.

2.To protect the starting Compressor <MC1,2>at the same time,Timer

<2> is installed. Therefore, do not change factory set value of this Timer.

Option controller connection.

Symbol No.

Function

TB3

1

2

3

4

5

6

Power (Active)

Cooling or Heating

operation

Cooling or Heating

operation

Reversing valve

for Heating operation

Fan operation

Power (Neutral)

PAC-204RC (Option) terminal no.

24VAC(L)

COMP1

COMP2

4WV

FAN HI

24VAC(N)

- 70 -

ELECTRICAL OPERATION FLOW CHARTS

PE-7,8,10MYC-EU PEH-5MYA-EU, PEH-7,8,10MYA-EU

START

POWER ON

CH ON

30FZ,30CZ ON (SELF HOLD)

START

POWER ON

CH ON

30FZ,30CZ ON (SELF HOLD)

NO

SW1 ON?

YES

FZ ON

52F ON

MF1 OPERATE

NO

SW2 ON?

YES

FZ ON

52F ON

MF1 OPERATE

NO

23WA ON?

YES

CZ1,2 ON

52C ON

MC OPERATE

MF2, 3 OPERATE

CH OFF

NO

SW1 COOL?

YES

23WA ON?

YES

CZ1 ON

NO

NO

HZ1,2 ON

21S4 ON

NO

52C ON

MC OPERATE

MF2, 3 OPERATE

CH OFF

23WA ON?

YES

CZ1,2 ON

52C ON

MC OPERATE

MF2, 3 OPERATE

CH OFF

SAFETY

DEVICE OFF?

YES

30CZ OFF

52C OFF

MC STOP

MF1 Note

MF2,3 STOP

CH ON

SERVICE CALL

SAFETY

DEVICE OFF?

YES

30CZ OFF

52C OFF

MC STOP

MF1 Note

MF2,3 STOP

NO

NO

CONDENSING

TEMP -12 ?

YES

26D1, 2 ON

X1 ON

X2 ON (SELF HOLD)

21S4 OFF

MF2, 3 STOP

CH ON

SERVICE CALL

NO

Note.

1. When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.

But the unit doesn't work correctly (not cooling and heating ).

Then, turn off the power supply and check outdoor unit.

CONDENSING

TEMP 6 ?

YES

26D1, 2 OFF

X1, 2 OFF

21S4 ON

MF2, 3 OPERATE

- 71 -

PE-15MYC-EU

START

POWER ON

CH1,2 ON

30FZ,30CZ1,2 ON (SELF HOLD)

NO

SW1 ON?

YES

FZ ON

52F1 ON

MF1 OPERATE

23WA ON?

YES

CZ1-1,CZ2-1 ON

52C1 ON

MC1 OPERATE

MF2 OPERATE

CH 1 OFF

CZ1-2,CZ2-2 ON

TIMER 2 ON

NO

PASS THE 3 MIN?

NO

52C2 ON

MC2 OPERATE

CH2 OFF

PE-20MYC-EU

START

POWER ON

CH1,2 ON

30FZ,30CZ1,2 ON (SELF HOLD)

NO

SW1 ON?

YES

FZ ON

52F1 ON

MF1 OPERATE

23WA ON?

YES

CZ1-1,CZ2-1 ON

52C1 ON

MC1 OPERATE

MF2 OPERATE

CH 1 OFF

CZ1-2,CZ2-2 ON

TIMER 2 ON

NO

PASS THE 3 MIN?

NO

52C2 ON

MC2 OPERATE

MF3 OPERATE

CH2 OFF

NO No.1 SAFETY

DEVICE OFF?

YES

30CZ1 OFF

52C1 OFF

MC1 STOP

MF2 STOP

CH1 ON

No.2 SAFETY

DEVICE OFF?

YES

30CZ2 OFF

52C2 OFF

MC2 STOP

MF2 STOP

CH2 ON

NO NO No.1 SAFETY

DEVICE OFF?

YES

30CZ1 OFF

52C1 OFF

MC1 STOP

MF2,3 STOP

CH1 ON

SERVICE CALL SERVICE CALL

Note. When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.

But the unit doesn't work correctly (not cooling ).

Then, turn off the power supply and check outdoor unit.

When the fault of indoor unit is occurred, both indoor unit and outdoor unit is stop.

- 72 -

No.2 SAFETY

DEVICE OFF?

YES

30CZ2 OFF

52C2 OFF

MC2 STOP

MF2,3 STOP

CH2 ON

NO

PEH-15,20MYA-EU

START

POWER ON

CH1,2 ON

30FZ,30CZ1,2 ON (SELF HOLD)

NO

SW2 ON?

YES

FZ ON

52F1 ON

MF1 OPERATE

NO

SW1 COOL?

YES

23WA ON?

YES

CZ1-1,CZ2-1 ON

52C1 ON

MC1 OPERATE

MF2 OPERATE

CH 1 OFF

CZ1-2,CZ2-2 ON

TIMER 2 ON

NO

PASS THE 3 MIN?

YES

52C2 ON

MC2 OPERATE

MF3 OPERATE

NO

CH 2 OFF

HZ1,2 ON

21S4-1,2 ON

T1,T2 ON

23WA ON?

YES

CZ1-1,CZ2-1 ON

52C1 ON

MC1 OPERATE

MF2 OPERATE

CH 1 OFF

CZ1-2,CZ2-2 ON

TIMER 2 ON

NO

PASS THE 3 MIN?

YES

52C2 ON

MC2 OPERATE

MF3 OPERATE

NO

CH 2 OFF

NO

No.1 SAFETY

DEVICE OFF?

YES

30CZ1 OFF

52C1 OFF

MC1 STOP

MF2 STOP

CH1 ON

SERVICE CALL

No.2 SAFETY

DEVICE OFF?

YES

30CZ2 OFF

52C2 OFF

MC2 STOP

MF3 STOP

CH2 ON

NO NO

No.1 SAFETY

DEVICE OFF?

YES

30CZ1 OFF

52C1 OFF

MC1 STOP

MF2 STOP

CH1 ON

SERVICE CALL

No.2 SAFETY

DEVICE OFF?

YES

30CZ2 OFF

52C2 OFF

MC2 STOP

MF3 STOP

CH2 ON

NO

NO

CONDENSING

TEMP -12 ?

YES

26D1 4 ON

X1,2,5,6 ON

X3,4 ON (SELF HOLD)

21S4-1,2 OFF

MF2, 3 STOP

NO

CONDENSING

TEMP 6 ?

YES

26D1 4 OFF

X1 6 OFF

21S4-1,2 ON

MF2, 3 OPERATE

Note. When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.

But the unit doesn't work correctly (not cooling ).

Then, turn off the power supply and check outdoor unit.

When the fault of indoor unit is occurred, both indoor unit and outdoor unit is stop.

- 73 -

REFRIGERANT SCHEMATICS

PE-7,8,10,15,20MYC-EU

INDOOR

PE

Evaporator

COOL

OUTDOOR

PU

Service port

Strainer

Ball valve

Interconnecting refrigerant piping

(by others)

High

pressure

switch

Check

joint

Condenser

Muffler

Accumulator

Check

joint

Compressor

Interconnecting refrigerant piping

(by others)

Ball valve

Note:PE-15,20MYC-EU is comprised of two refrigerant cycles.

Capillary

Tube

Strainer

PEH-5,7,8,10,15,20MYA-EU

INDOOR

PEH

Evaporator

HEAT COOL

Strainer

Capillary

Tube

Check

valve

Strainer

OUTDOOR

PUH

Service port

Strainer

Ball valve

Interconnecting refrigerant piping

(by others)

High

pressure

switch

Check

joint

4-Way

valve

Condenser

Muffler

Accumulator

Check

joint

Compressor

Inter connecting refrigerant piping

(by others)

Capillary

Tube

Ball valve

Strainer Check

valve

Note:PEH-15,20MYA-EU is comprised of two refrigerant cycles.

- 74 -

SAFETY & CONTROL DEVICES

PE-7,8,10MYC-EU

PE-15,20MYC-EU

ITEM NO.

COMPRESSOR OVER CURRENT RELAY

COMPRESSOR INTERNAL THERMOSTAT

HIGH PRESSURE SWITCH

INDOOR FAN MOTOR OVER CURRENT RELAY

51C

49C

63H

51F1

INDOOR FAN MOTOR INTERNAL THERMOSTAT -

OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2

OUTDOOR FAN MOTOR INTERNAL THERMOSTAT

FUSE

-

F1 3

PE-7MYC-EU

PU-7MYC

1

-EU

PE-8MYC-EU

PU-8MYC

1

-EU

19.0A

22.0A

105 ± 5 ˚C OFF

31.0A

83 ± 11 ˚C ON

2.94MPa OFF

PE-10MYC-EU

PU-10MYC

1

-EU

5.0A

3.5A

5.0A

150 ˚ C OFF

2.5A

150 ˚C OFF

3.15A

ITEM NO.

PE-15MYC-EU

PU-15MYC

1

-EU

PE-20MYC-EU

PU-20MYC

1

-EU

COMPRESSOR OVER CURRENT RELAY 51C1,2 22.0A 31.0A

COMPRESSOR INTERNAL THERMOSTAT

HIGH PRESSURE SWITCH

49C

105 ± 5 ˚C OFF 83 ± 11 ˚C ON

63 3.24MPa OFF

INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 4.6A

OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2,3 2.5A

7.2A

OUTDOOR FAN MOTOR INTERNAL THERMOSTAT - 150 ˚C OFF

FUSE F1 3 3.15A

- 75 -

PEH-7,8,10MYA-EU

PEH-15,20MYA-EU

ITEM

COMPRESSOR OVER CURRENT RELAY

COMPRESSOR INTERNAL THERMOSTAT

HIGH PRESSURE SWITCH

FROST PROTECTOR

INDOOR FAN MOTOR OVER CURRENT RELAY

NO.

PEH-5MYA-EU

PUH-5MYE-EU

51C 15.0A

49C 110 ± 5˚C OFF

61 ± 9˚C ON

PEH-7MYA-EU

PUH-7MYC1-EU

19.0A

PEH-8MYA-EU

PUH-8MYC1-EU

PUH-8MYE-EU

22.0A

105 ± 5˚C OFF

83 ± 11˚C ON

2.94MPa OFF 63H

26D1 -12 ± 2 ˚C ON

6 ± 2 ˚C OFF 26D2

51F1 3.5A

5.0A

3.5A

INDOOR FAN MOTOR INTERNAL THERMOSTAT -

OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2

OUTDOOR FAN MOTOR INTERNAL THERMOSTAT

FUSE

-

F1 3

150˚ C OFF

2.5A

150˚C OFF

3.15A

ITEM NO.

COMPRESSOR OVER CURRENT RELAY 51C1,2

PEH-10MYA-EU

PUH-10MYC

1

-EU

PUH-10MYE-EU

PEH-15MYA-EU

PUH-15MYC

1

-EU

31.0A

PEH-20MYA-EU

PUH-20MYC

22.0A 31.0A

1

-EU

COMPRESSOR INTERNAL THERMOSTAT

HIGH PRESSURE SWITCH

49C

63H

105 ± 5 ˚ C OFF 83 ± 11˚C ON

2.94MPa OFF

FROST PROTECTOR

26D1

26D2

INDOOR FAN MOTOR OVER CURRENT RELAY

OUTDOOR FAN MOTOR OVER CURRENT RELAY

51F1

51F

OUTDOOR FAN MOTOR INTERNAL THERMOSTAT -

FUSE F1 3

5.0A

-12 ± 2 ˚C ON

6 ± 2 ˚C OFF

4.6A

2.5A

150˚ C OFF

3.15A

7.2A

- 76 -

SPECIAL ORDER

Description

Model

Cooling only

Service ref.

Heat pump

*

Low Ambient Cooling

PE-7MYC PE-8MYC PE-10MYC PE-15MYC PE-20MYC

PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU

Model

PEH-5MYA PEH-7MYA PEH-8MYA PEH-10MYA PEH-15MYA PEH-20MYA

Service ref.

PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU

Release

2000 year

Global Remote Controller

Anti corrosion

(Service reference)

* Low ambient cooling

(PUH-5MYE-EUS) (PUH-7MYC-EUS)

(PUH-8MYC-EUS,

PUH-8MYE-EUS)

(PUH-10MYC-EUS,

PUH-10MYE-EUS) (PUH-15MYC-EUS) (PUH-20MYC-EUS)

It is possible to conduct cooling operation under an outdoor temperature even down to -5 ˚C.

- 77 -

PE-7,8,1015,20MYC-EU

PHYSICAL DATA

[

PRODUCT]

Product type

PACKAGE AIR COOLED HEATPUMP UNITS

PE SERIES

PE-8MYC-EU PE-10MYC-EU

PU-8MYC

1

-EU PU-10MYC

1

-EU

Cooling capacity (AS1861) kW 17.9 22.0 28.8

Sensible Cooling capacity (AS1861)

Cooling power consumption (Input) kW 14.3 17.6 23.0

kW 7.2 7.8 10.1

Basic temperature condition cooling

Basic temperature condition cooling

Indoor

Outdoor

27 DB/19 WB

35 DB

PE-15MYC-EU

PU-15MYC

1

-EU

44.0

35.2

16.9

PE-20MYC-EU

PU-20MYC

1

-EU

57.6

46.1

22.7

[ ELECTRICAL ]

<Indoor unit>

Design voltage

Cycles

Power supply

Volts 240 415

Hz 50

Volts 1PH-240V 3PH-415V

Control voltage

Voltage change Max.

Voltage change Min.

240/24

Volts 240 415

Volts 220 380

Fan motor output

Fan motor current

HP(kW) 0.28(0.21) 0.94(0.70) 1.34(1.0)

Amps 3.2 1.2 2.0

2.95(2.2)

3.5

<Outdoor unit>

Design voltage

Cycles

Power supply

Voltage change Max.

Voltage change Min.

Volts 415

Hz 50

Volts 3PH-415V

Volts 415

Volts 380

HP(kW) 2X0.12(2X0.09)

2X0.2(2X0.15)

Amps 0.7 1.0

0.32(0.24)

1.2

Fan motor output

Fan motor current

[COMPRESSOR]

Make

Model

Type

Number of compressor

Nominal motor

Locked rotor current

Normal run current (AS1861)

Swept volume

Bore

Stroke

Speed

Number of cylinders

Oil charge

Type of oil

Crankcase heater

4.96(3.7)

4.8

2X0.32(2X0.24)

2X1.2

MITSUBISHI

JH519YE JH521YE JH527YE

JH521YE JH527YE

HERMETIC LINE START (RECIPROCATING)

2 1

HP(kW) 6.7(5.0) 7.4(5.5) 10.1(7.5)

Amps 76 83 85

Amps 13.0 15.5 19.2

cc/rev 149 160.8 201 mm

ø44.45

mm 24.0 25.9

7.4(5.5)

83

15.5

160.8

10.1(7.5)

85

19.2

201 rpm 2900

4 5 ml 3000 4500

4

3000

DIAMOND MS32(N-1) OR SUNISO 3GS(D) watts 62 72

62

5

4500

72

[REFRIGERATION SYSTEM]

Refrigerant

Refrigerant charge per circuit

Refrigerant control

Limit of pipe's leng th

Limit of pipe's height difference kg

R22

5.7 5.0 8.7

4.8

2

Capillary tube m 50 mtrs 20 (In case of indoor unit above outdoor unit) mtrs 30 (In case of outdoor unit above indoor unit)

9.7

- 78 -

Product number Indoor unit

Outdoor unit

[INDOOR AIR CIRCUIT]

PE-7MYC-EU

PU-7MYC

1

-EU

PE-8MYC-EU

PU-8MYC

1

-EU

PE-10MYC-EU

PU-10MYC

1

-EU

PE-15MYC-EU

PU-15MYC

1

-EU

PE-20MYC-EU

PU-20MYC

1

-EU

Diameter of blowers

Width of blowers

Blower drive

Fan motor output mm 250 mm 245 275

Direct drive kW 0.21 0.70 1.00

Air quantity

External static pressure

Supply air dimensions(hxw)

Return air dimensions(hxw)

[EVAPORATOR]

L/s 1000 1167 1500

Pa 125 mm mm

341

X

1102

248

X

998

341

X

1302

Number of evaporator

Face area

Fin per meter

Fin material thickness

1 sq.m 0.42 0.50

Rows deep 4

Rows high

15

Finned length

Face velocity

mm 1100

1300 m/s 2.2 2.8 3.0

mm

474/2.11 513/1.95

0.115

380

270 374

Belt drive

2.2

3.7

3.5

2333

4.8

3000

200

412X1000 412X1209

596X1415

0.86

1.00

4

1415

2.7

474/2.11

24

1615

3.0

513/1.95

Tube diameter

Gauge of copper tube

Pipe type

Number of circuit

[OUTDOOR AIR CIRCUIT] mm

mm

Plain tube

10

9.52

0.35

Groove tube

16 24

Blower drive

Quantity of motor

Fan motor output

1 2

Direct drive

2 kW 2X0.09

0.7

2X0.15

1.0

L/s 3167 3000 3667

1

0.24

1.2

4000

954

2

2X0.36

2X1.2

8000

Air quantity

[CONDENSER]

Number of condensers 2

Rows high

30

32

30

1.32

1.35

2

40

2

30

1299

1.5

6.25/1.6

1775

3.0

0.115

Pipe type

Groove tube Plain tube

6

- 79 -

Product number Indoor unit

Outdoor unit

[ENCLOSURE AND FRAME]

Dimension height

Dimension

Outdoor unit depth height width depth

External finish (indoor unit)

External finish

Panel thickness

(outdoor unit)

Condense drain size

Weight Indoor unit

Weight Outdoor unit

Sound pressure level (indoor unit)

Sound pressure level (outdoor unit)

Sound power level (indoor unit)

Sound power level (outdoor unit)

PE-7MYC-EU

PU-7MYC

1

-EU

PE-8MYC-EU

PU-8MYC

1

-EU

PE-10MYC-EU

PU-10MYC

1

-EU

PE-15MYC-EU

PU-15MYC

1

-EU

PE-20MYC-EU

PU-20MYC

1

-EU mm 428 mm 1415 1615 1690

706

1993 mm 650 865 mm 980

1230 961 mm 1400

998 1996 mm 700

998

Galvanized steel

Acrylic resin coationg (Color: Munsell 5Y8/1) mm 1.2

mm 25.4

kg kg

67 70 84

202 205 230 dbA 55 56 59 dbA 65 65 65 dbA 63 64 67 dbA 76 76 76

180

285

61

67

69

78

212

360

62

68

70

79

- 80 -

PEH-5,7,8MYA-EU

[

PRODUCT]

Product type

PACKAGE AIR COOLED HEATPUMP UNITS

PEH SERIES

Product number : Indoor unit

Outdoor unit

Cooling capacity (AS1861) kW

Sensible Cooling capacity (AS1861) kW

Coolin g power consumption (Input) kW

Heating capacity (AS1861)

Heating power consumption kW kW

Basic temperature condition cooling

Basic temperature condition cooling

Indoor

Outdoor

Basic temperature condition heating

Basic temperature condition heating

Indoor

Outdoor

[ ELECTRICAL ]

<Indoor unit>

Design voltage

Cycles

Power supply

Control voltage

Voltage change Max.

Voltage change Min.

Fan motor output

Fan motor current

PEH-5MYA-EU

PUH-5MYE-EU

14.4

11.5

6.0

14.4

4.5

PEH-7MYA-EU

PUH-7MYC

1

-EU

17.9

14.3

7.2

18.8

Volts

415 240

Hz 50

Volts

3PH-415V 1PH-240V

Volts

Volts

HP(kW)

Amps

415

380

0.6(0.45)

1.1/1.0

240/24

240

220

0.28(0.21)

3.2

PEH-8MYA-EU

PUH-8MYC

1

-EU

22.0

PUH-8MYE-EU

17.6

6.3

27 DB/19 WB

35 DB

21 DB

7 DB/6 WB

7.8

22.0

6.5

415

3PH-415V

415

380

0.94(0.70)

1.2

<Outdoor unit>

Design voltage

Cycles

Power supply

Voltage change Max.

Voltage change Min.

Fan motor output

Fan motor current

[COMPRESSOR]

Make

Volts 415

Hz 50

Volts 3PH-415V

Volts 415

Volts 380

HP(kW) 0.2(0.15)

2X0.12(2X0.09)

Amps 1.0

0.7

0.47(0.35)

Model

Type

Number of compressor

Nominal motor

Locked rotor current

Normal run current (AS1861)

Swept volume

Bore

Stroke

Speed

Number of cylinders

Oil charge

Type of oil

Crankcase heater

HP(kW)

Amps

Amps cc/rev mm mm rpm ml watts

Copeland MITSUBISHI

CRNQ-0500-TFD JH519YE

JH521YE

HERMETIC LINE START (RECIPROCATING)

1

5.0(3.73)

65

8.6

101.92

6.7(5.0)

76

13.0

149

7.4(5.5)

83

15.5

160.8

ø49.78

26.19

2

1952

CALUMET RO 15 OR WITCO 3GS

40

ø44.45

24.0

25.9

2900

4

3000

DIAMOND MS32(N-1) OR SUNISO 3GS(D)

62

[REFRIGERATION SYSTEM]

Refrigerant

Refrigerant charge per circuit

Number of refrigerant controls

Refrigerant control

Reverse cycle valve

Defrost system

Limit of pipe's leng th

Limit of pipe's height difference kg

5.0

R22

5.7

1

Capillary tube

4-way valve

Reverse cycle defrost m 50

6.6

mtrs 20 (In case of indoor unit above outdoor unit) mtrs 30 (In case of outdoor unit above indoor unit)

- 81 -

Product number Indoor unit

Outdoor unit

[INDOOR AIR CIRCUIT]

Number of blowers

Diameter of blowers

Width of blowers

Blower drive

Fan motor output

Nominal air quantity

External static pressure

Supply air dimensions(hxw)

Return air dimensions(hxw)

[EVAPORATOR] mm mm kW

L/s

Pa mm mm

PEH-5MYA-EU

PUH-5MYE-EU

1

275

0.45

1.1/1.0

700

100

342X781

248X498

PEH-7MYA-EU

PUH-7MYC

1

-EU

PEH-8MYA-EU

PUH-8MYC

1

-EU PUH-8MYE-EU

2

250

245

Direct drive

0.21

3.2

1000

125

341X1102

248X998

275

0.70

1.2

1167

342X1118

Number of evaporator

Face area sq.m

0.3

1

Rows deep 4

Rows high

Finned length

Face velocity

Fin per meter / pitch

Fin material thickness

mm m/s mm

15

780

2.5

513/1.95

1100

2.2

474/2.11

0.115

0.42

15

1100

2.8

474/2.11

Fin coating

Tube diameter

Gauge of copper tube

Pipe type

Number of circuit

[OUTDOOR AIR CIRCUIT]

Number of fans

Blower drive

Quantity of motor

Fan motor output

NA 510 D*

1 mm 9.52

mm 0.35

Groove tube

7

Plain tube

10 kW

L/s

1

1

0.35

1.2

1583

2

600

Direct drive

2

2X0.09

0.7

2783

Groove tube

1

800

1

0.35

1.2

3333

Nominal air quantity

[CONDENSER]

Number of condensers

Rows deep

Rows high

1

1.3

44

1000

1.56

2

2X2.1

2

30

2706

1.35

474 /2.11

0.115

1

1.58

44

1400

1.95

513 /1.95

Pipe type

Groove tube

7

Specifications subject to change without noice

*1 Corrosion proof property : Salt spray JIS Z 2371, 500hrs Humiditiy test 50C 98% 500hrs.

*2 Corrosion proof property : Salt spray JIS Z 2371, 1000hrs Humiditiy test 50C 98% 1000hrs.

11

- 82 -

Product number Indoor unit

Outdoor unit

[ENCLOSURE AND FRAME]

Dimension height

Dimension

Outdoor unit depth height width depth

External finish (indoor unit)

External finish

Panel thickness

(outdoor unit)

Condense drain size

Weight Indoor unit

Weight Outdoor unit

Sound pressure level (indoor unit)

Sound pressure level (outdoor unit)

Sound power level (indoor unit)

Sound power level (outdoor unit)

PEH-5MYA-EU

PUH-5MYE-EU

PEH-7MYA-EU

PUH-7MYC

1

-EU

PE-8MYA-EU

PUH-8MYC

1

-EU PUH-8MYE-EU mm mm mm mm mm mm

428

1095 1415

650

1175

1000

980

1400

1175

1250

550

700

550

Galvanized steel

Acrylic resin coationg (Color: Munsell 5Y8/1) mm 1.2

mm 25.4

kg kg

60

150

67

211 dbA dbA dbA dbA

57

68

55

63

214

65

76

70

56

64

188

- 83 -

PEH-10,15,20MYA-EU

[

PRODUCT]

Product type

Product number : Indoor unit

Outdoor unit

Cooling capacity (AS1861) kW

Sensible Cooling capacity (AS1861) kW

Coolin g power consumption (Input)

Heating capacity (AS1861)

Heating power consumption kW kW kW

Basic temperature condition cooling

Basic temperature condition cooling

Indoor

Outdoor

Basic temperature condition heating

Basic temperature condition heating

Indoor

Outdoor

[ ELECTRICAL ]

<Indoor unit>

Design voltage

Cycles

Power supply

PACKAGE AIR COOLED HEATPUMP UNITS

PEH-10MYA-EU

PUH-10MYC

1

-EU

28.8

PEH SERIES

PEH-15MYA-EU

PUH-10MYE-EU PUH-15MYC

44.0

1

-EU

PEH-20MYA-EU

PUH-20MYC

1

-EU

57.6

23.0

10.1

28.8

8.3

Volts

415

Hz 50

Volts

3PH-415V

35.2

16.8

44.0

14.1

27 DB/19 WB

35 DB

21 DB

7 DB/6 WB

46.0

22.7

57.6

19.3

Control voltage

Voltage change Max.

Voltage change Min.

Fan motor output

Fan motor current

Volts

Volts

HP(kW)

Amps

1.34(1.0)

2.0

1.34(1.0)

240/24

415

380

2.95(2.20)

2.0

4.1

4.96(3.70)

4.7

<Outdoor unit>

Design voltage

Cycles

Power supply

Voltage change Max.

Voltage change Min.

Fan motor output

Fan motor current

[COMPRESSOR]

Make

Volts 415

Hz 50

Volts 3PH-415V

Volts 415

Volts 380

HP(kW)

2X0.2(2X0.15) 0.47(0.35)

Amps 1.0

1.2

2X0.47(2X0.35)

2X1.2

Model

Type

Number of compressor

Nominal motor

Locked rotor current

Normal run current (AS1861)

Swept volume

Bore

Stroke

Speed

Number of cylinders

Oil charge

Type of oil

Crankcase heater

HP(kW)

Amps

Amps cc/rev mm mm rpm ml watts

JH527YE

MITSUBISHI

JH521YE JH527YE

HERMETIC LINE START (RECIPROCATING)

2 1

10.1(7.5)

85

19.2

201

7.4(5.5)

83

15.5

160.8

10.1(7.5)

85

19.2

201

ø44.45

25.9

2900

5

4500

4

3000

DIAMOND MS32(N-1) OR SUNISO 3GS(D)

5

4500

72 62 72

[REFRIGERATION SYSTEM]

Refrigerant

Refrigerant charge per circuit

Number of refrigerant controls

Refrigerant control

Reverse cycle valve

Defrost system

Limit of pipe's leng th

Limit of pipe's height difference

R22 kg

9.9

1

6.6

Capillary tube

4-way valve

Reverse cycle defrost m 50

2

9.7

mtrs 20 (In case of indoor unit above outdoor unit) mtrs 30 (In case of outdoor unit above indoor unit)

- 84 -

Product number Indoor unit

Outdoor unit

[INDOOR AIR CIRCUIT]

Number of blowers

Diameter of blowers

Width of blowers

Blower drive

Fan motor output

Nominal air quantity

External static pressure

Supply air dimensions(hxw)

Return air dimensions(hxw)

[EVAPORATOR] mm mm kW

L/s

Pa mm mm

PEH-10MYA-EU

PUH-10MYC

1

-EU PUH-10MYE-EU

1.00

2.0

1500

250

275

Direct drive

1.00

1.8

1500

125

341X1302 342X1318

248X998

2

PEH-15MYA-EU

PUH-15MYC

1

-EU

PEH-20MYA-EU

PUH-20MYC

1

-EU

245

2.20

4.5

2333

280

Belt drive

275

3.70

4.7

3000

200

412X1000 412X1209

596X1415

Number of evaporator 1

Face area sq.m

0.50

Rows deep 4

Rows high

Finned length

Face velocity

Fin per meter / pitch

Fin material thickness

mm m/s mm

15

1300

3.0

513/1.95

0.115

0.86

1415

2.7

513/1.95

2

24

0.98

1615

3.0

592/1.69

Fin coating

Tube diameter

Gauge of copper tube

Pipe type

Number of circuit

[OUTDOOR AIR CIRCUIT]

Number of fans

Plain tube

NA 510 D*

1

(NA 549

*2

) mm 9.52

mm 0.35

10

Groove tube

16 24

2

600

Blower drive

Quantity of motor

Fan motor output kW

L/s

2

2X0.15

1.0

3167

1

1

800

Direct drive

0.35

1.2

3333

2

2

2X0.35

1.3

2X3083

Nominal air quantity

[CONDENSER]

Number of condensers 2

2X2.1

Rows deep

Rows high

Fin per meter/Pitch

30

2706

1.35

474/2.11

1

1.58

3

44

1400

1.95

513/1.95

0.115

2X1.07

2.89

2

37

2800

2X1.32

474 /2.11

2.34

Pipe type

Groove tube

11

Specifications subject to change without noice

*1 Corrosion proof property : Salt spray JIS Z 2371, 500hrs Humiditiy test 50˚C 98% 500hrs.

*2 Corrosion proof property : Salt spray JIS Z 2371, 1000hrs Humiditiy test 50˚C 98% 1000hrs.

(anti corrosion as special order)

14

- 85 -

Product number Indoor unit

Outdoor unit

[ENCLOSURE AND FRAME]

Dimension height

Dimension

Outdoor unit depth height width depth

External finish

External finish

(indoor unit)

(outdoor unit)

Panel thickness

Condense drain size

Weight Indoor unit

Weight Outdoor unit

Sound pressure level (indoor unit)

Sound pressure level (outdoor unit)

Sound power level (indoor unit)

Sound power level (outdoor unit)

PEH-10MYA-EU

PUH-10MYC

1

-EU PUH-10MYE-EU

PEH-15MYA-EU

PUH-15MYC

1

-EU

PEH-20MYA-EU

PUH-20MYC

1

-EU mm mm mm

428

1615

1690

706

1993 mm mm mm

980

1400

700

650

1175

1250

550

Galvanized steel

865

1200

1951

1080

Acrylic resin coationg (Color: Munsell 5Y8/1) mm 1.2

mm 25.4

kg kg

240

84

221 dbA dbA dbA dbA

59

65

67

76

180

431

61

69

69

80

212

472

62

70

- 86 -

INSTALLATION

1.

Space required around unit.

Indoor unit

Dimension of the unit and space necessary for sevicing.

PEH-5 PE(H)-7, 8, 10

PE(H)-15,20

380

B

A

180

400

B

A

200

Ceiling access panel

PEH - 5

PE(H) - 7, 8

A B

1560 1000

1880 1320

PE(H) - 10

2080 1520

Ceiling access panel

A

PE(H) - 15

2187

PE(H) - 20

2490

B

1587

1890

Outdoor unit

Secure enough space necessary for servicing, installing, and for proper function of the unit.

To prevent short-cycling, remove obstacles as much as possible.

PUH-5, 8, 10 (Side blow)

(1) At a single installation

150 over

Inlet surface

150 over

500 over

Inlet surface

Outlet surface

Service panel

With the inlet surface facing a wall.

Service panel

300 over

Inlet surface

150 over

Inlet surface

Outlet surface

With the outlet surface facing a wall.

(2) Relation of unit when many set up unit.

300 over

500 over 500 over 500 over 500 over

Please set the unit that the inlet air and the outlet air are not influenced.

- 87 -

PU(H)-7,8, 10 (Upper blow)

(1) At a single installation

The obstacle is on the outlet side. (Fig 1)

The obstacle is in three directions. (Fig 2,3)

The obstacle is in four directions. (Fig 4)

ceiling

Fig 1

1200 over

The right and left side and the back and forth side must be opened.

300 over

Fig 2

500 over

Service Panel

However, the outlet side must be opened.

300 over

Fig 3

If this side is service panel, you need 500 over. If this side is inlet, you need 300 over.

300 over

However, if the service panel is an interior side, the right or left side need 500 over.

(2) Relation of unit when many set up unit. (Fig 5,6,7)

A

Fig 4

A

All "A" is 500 over.

However, outlet side must be opened.

And the obstacle in two directions must be lower than the unit.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

Service-panel

500 over

500 over

Fig 5

300 over

300 over

A A

A A

Fig 6 All "A" is 500 over.

300 over

A A A A A

Fig 7 All "A" is 500 over in any case.

Service-panel

- 88 -

PU-15

(1) At a single installation

The obstacle is on the outlet side. (Fig 1)

The obstacle is in four directions. (Fig 2)

300 over ceiling

1500 over

The right and left side and the back and forth side must be opened.

300 over

Fig 1

(2) Relation of unit when many set up unit. (Fig 3,4)

Service Panel

Fig 2

500 over

However, the outlet side must be opened.

300 over

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

Service-panel

300 over

500 over

300 over

Service-panel

Fig 3

PU-20

(1) At a single installation

The obstacle is on the outlet side. (Fig 1)

The obstacle is in four directions. (Fig 2)

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A

Fig 4 All "A" is 500 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

ceiling

1500 over

The right and left side and the back and forth side must be opened.

300 over

Fig 1

(2) Relation of unit when many set up unit. (Fig 3,4,5)

300 over

300 over

500 over

However, the outlet side must be opened.

Service Panel

Fig 2

300 over

300 over

Service-panel

500 over

Service-panel

Fig 3

300 over

500 over

300 over

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A A

Fig 4 All "A" is 500 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A

Fig 5 All "A" is 500 over in any case.

300 over

- 89 -

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

PUH-15, 20

(1) At a single installation

The obstacle is on the outlet side. (Fig 1)

The obstacle is in four directions. (Fig 2)

The obstacle is in three directions. (Fig 3,4) ceiling

1500 over

The right and left side and the back and forth side must be opened.

Fig 1

However, the outlet side must be opened.

300 over

Service Panel

Fig 2

500 over

300 over

However, outlet side must be opened.

And the obstacle in two directions must be lower than the unit.

300 over

Service-panel

300 over

Fig 3

(2) Relation of unit when many set up unit. (Fig 5,6,7)

Fig 4

300 over

Service-panel

500 over

300 over

Service-panel

500 over

Service-panel

Fig 5

300 over

500 over

300 over

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A A

Fig 6 All "A" is 500 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A

Fig 7 All "A" is 500 over in any case.

300 over

2. Preparation before installing

Indoor unit

Please use the specified hanging bolt in any case.

Hanging bolt is local supply.

Please use the method below or use the angle and the rectangular lumber, etc. and install the hanging bolt.

Insert etc

100-150kg

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

Reinforcement

Hanging bolt

M10 (PEH-5,PE(H)-7,8,10)

M12 (PE(H)-15,20)

- 90 -

3. Installation of the unit.

Indoor unit

Please carry the packed until parallelly to installed place.

Please install the unit before construction of the ceiling -lined.

PEH-5 PE(H)- 7, 8, 10

U washer

100 over

Nut

Washer

Nut

100 over

PE(H)- 15, 20

100 over

Nut (M10)

Washer

Nut (M10)

Nut (M10)

Washer

Nut (M10)

Outdoor unit

Fix unit tightly with bolts as shown below so that unit will be securely fixed in place use concrete or angle foundation of unit.

At the time of bottom piping of refrigerant pipe, build a 100mm or higher foundation so that piping will go through bottom of unit.

Ceiling

Installation pitch

Anchor bolt (local arrangement)

PUH-5 PU(H)-7, 8, 10 M8

PU(H)-15, 20 M10

Concrete foundation

- 91 -

Duct construction.

Provide canvas flexible ducting between unit when connect to the duct-work.

The duct unit must use a nonflammable material.

Provide sufficient insulation for prevent dewdrop.

Duct earth

Duct earth

Canvas Duct

Canvas Duct

Duct

Duct

Drain pan

Inlet

Outlet

Duct-work length 850mm or more

Lifting method.

When the unit is to be lifted and moved, attach ropes to the suspension plates(3 p.c.s) provided on the top of the unit.

When the unit is lifted, it 's center of gravity tends to shift the unit one side and so balance, such as that in the figure below, should be attained.

The angles at which the ropes suspend the unit should be at least 60 at the compressor end and at least 45 at the condenser end. Care should be taken to avoid contact with the main unit while carrying.

It is necessary to protect the unit with the blanket so that the ropes should not injure the unit.

Hook (as directly aligned over the center of gravity as possible.

Example PUH-15, 20

- 92 -

MITSUBISHI

ELECTRIC

Piping connection

Warning.

Please follow the following procedures, during the piping connection work is carried out.

If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve.

It might cause the injury.

In case of Brazing type

1. Open the ball valve cap before removing the by-pass tube.

Then, turn the knob of the ball valve from ’close’ to ’open’ position.

2. Please repeat to close and open the ball valve of gas and liquid side at the same time (3 times or more).

And finally make sure the ball valve is at close position.

CLOSE OPEN

3. Cut part A (two places) of the by-pass tube as shown in figure below.

CUT

CUT

Caution

There will be small amount of refrigerant gushed out of the by-pass tube at the moment.

4. Make sure that the ball valve is wrapped with enough wet cloth, during the brazing of the by-pass tube

(for cooling purpose). Make sure the temperature of ball valve is below 100 degree centigrade. (If the temperature of the ball valve is over 100 degree centigrade, the refrigerant and valve sheet might gush out from the ball valve. It might cause the injury.) enough wet cloth

5. Please make sure the ball valve is cool enough when removing the by-pass tube. Wait for a while for further cooling of the ball valve, before the piping connection work begins.

6. When the piping connection begins. Again, make sure that the ball valve is wrapped with enough wet cloth, during the brazing for cooling the ball valve. Make sure the temperature of ball valve is below 100 degree centigrade. (If the temperature of the ball valve is over 100 degree centigrade, the refrigerant and valve sheet might gush out from the ball valve. It might cause the injury.)

7. Before charging the refrigerant, vacuum the pipes to clear all the air and water.

8. Charge the additional amount of refrigerant according to the table.

9. Turn the knob of the ball valve to ’open’ position after leak check.

10. Finally, put the cap back to the ball valve.

- 93 -

In case of Flare, Flange type

1. PROCEDURE TO CONNECT THE EXTENSION PIPE.

Proceed with the connection as follows:

(1) Open the ball valve cap before cutting the by-pass tube.(Fig.1)

(2) Check the ball valve section is completely closed.(Fig.2)

(3) Cut two parts of the by-pass tube.(Fig.4)

Caution

There will be small amount of refrigerant gushed out of the by-pass tube at the moment.

Valve knob

Fig. 1

Valve knob

(4) Remove the connection pipe assy.(Fig.5)

Throw away the packing.

Do not brazing the pipe while the flange assy connect the ball valve. (Except the PUH-5)

(5) Remove the by-pass tube.(Fig.6)

Braze the extension pipe with the flange assy. (Except the PUH-5)

(6) Connect the extension pipes with the packing between the ball valve and the flange.(Fig.7)

Use the attached new packing certainly.

Close Fig. 2 cut cut

Pipe assy

Open

Fig. 3

Fig. 4

Unit side

2. HANDLING PRECAUTIONS.

(1) The extension pipes should be connected with the valve knob completely closed. (Fig.2)

Check leak test the part of flange and flare.

(2) Before charging the refrigerant, vacuum the pipes to clear all the air and water.

(3) Charge the additional amount of refrigerant according to the table.

(4) Turn the ball valve knob to "Open" position after leak check again.

(Fig.3)

(5) Finally, put the cap back to the ball valve.

Extension pipe throw away Fig. 5

By-pass tube

Flange assy

Fig. 6

Unit side

Extension pipe use the attached new packing

Fig. 7

- 94 -

4.

Refrigerant piping.

Extension piping and installation parts are field supply.

Perform the work only after carefully reading the appropriate instructions.

A

Install the unit where the refrigerant piping is shortest, the difference between the indoor unit and outdoor unit is smallest.

As pipes purchased in the market may contain dust, below them off with dry inlet gas.

Take care not to allow dust and water content to enter the piping during pipe processing or installing.

Minimize the number of bends, and make the bending radius as long as possible.

When the outdoor unit is lower.

B

Always observe the restriction(allowable length, height difference, pipe diameter) on the refrigerant piping.

When the outdoor unit is higher.

For soldering & brazing, use high-quality materials.

Never purge air with a refrigerant. Always use a vacuum pump for purging.

Provide proper insulation to the piping . Insufficient insulation cause poor cooling/heating performance or condensation drip, leading to unexpected trouble.

Do not insulate gas or low pressure pipe and liquid or high pressure pipe together.

For the connection of the refrigerant piping, leave the valve of the outdoor unit fully closed

(as set before shipment), and no operate it until the connection between the indoor/outdoor units and refrigerant piping, refrigerant leak test and evacuation work have been completed.

The maximum permissible values are shown below.

Remove the cover (grommet) attached sheet metal at exit of heat exchanger pipe of indoor unit before connecting the local piping.

(This cover is protect the pipe from sheet metal edge at unit transportation.)

Please insulate liquid pipe & gas pipe (two places for each) with an insulated pipe of the attachment after connecting piping.

Good example

Bad example

Insulating material Finishing tape

Insulating material

Finishing tape

Gas pipe

Liquid pipe

Electric wire

Gas pipe

Liquid pipe

Electric wire

Dimension A (m)

Dimension B (m)

Number of bends

Total piping length (m)

Piping size

Liquid pipe (mm)

Gas pipe (mm)

PEH-5

20

30

15

50

12.7

19.05

PE(H)-7 PE(H)-8 PE(H)-10 PE(H)-15 PE(H)-20

20 20 20 20 20

30

15

50

15.88

25.4

30

15

50

15.88

25.4

30

15

50

15.88

28.6

30

15

50

2x15.88

2x25.4

30

15

50

2x15.88

2x28.6

- 95 -

a.

b.

c.

d.

e.

f.

g.

h.

i.

j.

Airtight test

Airtight test should be made by pressurizing nitrogen gas to 3Mpa.

For the test method, refer to the following figure.

(Make a test with the valve closed. Be also sure to pressurize both liquid and gas pipe.)

The test result can be judged good if the pressure has not been reduced after leaving for about one day after completion of nitrogen pressurization.

Nitrogen gas

To indoor unit

System analyzer

Low knob

High knob

Valve

Liquid gas

Gas pipe

Outdoor unit

Service port

a d c b e f j g h i

Evacuation

Evacuation should be made from the service port provided on the outdoor unit’s valve to the vacuum pump commonly used for both liquid pipe and gas pipe.

(Make evacuation from both liquid pipe and gas pipe with valve closed.)

Remember :Never carry out air purge by refrigerant.

d.

e.

f.

g.

h.

i.

j.

a.

b.

c.

System analyzer

To indoor unit

Low knob

High knob

Valve

Liquid gas

Gas pipe

Outdoor unit

Service port

Vacuum pump

c a b d e i f g j h

Additional refrigerant charge

The mount of refrigerant charged in this unit is a appropriate for 5-meter long refrigerant pipes.

Refer to the table below and add the corresponding amount of refrigerant if the pipes are extended.

(The refrigerant is charged in the outdoor unit.)

The outdoor unit of PE-5,8,10 have side blow type and upper blow type.

Factory charge refer to the table below.

5m

Refrigerant piping length

10m 15m 20m 25m 30m 35m 40m 45m 50m

Factory charge

Outdoor unit unit

PU-7

PU-8

PU-10

PU-15 charge mount

R-22

(kg)

PU-20

PUH-5

PUH-7

PUH-8

PUH-10

PUH-15

PUH-20

0

0

0

0

0

0

0.8

1.6

2.4

3.2

4.0

4.8

5.6

6.4

7.2

2x0.8

2x1.6 2x2.4 2x3.2 2x4.0 2x4.8 2x5.6 2x6.4

2x7.2

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

0.8

1.6

2.4

3.2

4.0

4.8

5.6

6.4

7.2

0.8

1.7

2.5

3.3

4.2

5.0

5.8

6.7

7.5

2x0.8

2x1.7 2x2.5 2x3.3 2x4.2 2x5.0 2x5.8 2x6.7

2x7.5

Side blow charge mount

R-22

(kg)

PUH-5

PUH-8

PUH-10

5.0

6.6

9.9

Upper blow

PU-7

PU-8

PU-10

PU-15

PU-20

PUH-7

PUH-8

PUH-10

PUH-15

PUH-20

5.7

5.0

8.7

2x4.8

2x9.7

5.7

6.6

9.9

2x6.6

2x9.7

- 96 -

5.

Drain piping

•Incline the drain piping to the outside (drain side) as shown in the figure below.

•The outlet of the indoor unit drain pipe is Rc1.

•After completion of piping, confirm that drainage is good and that there are no leaks.

Indoor unit drain piping

Install thermal insulation to prevent dew

The drain piping should have a drain trap.

A 70mm

B 2xC 70mm

C 35mm

Drain pan

Drain piping

Slope

20mm/m

Drain trap

The drain pipe should extend below this level.

Open drain

- 97 -

6.

Electric wiring

Construct the earth connection.

All electrical work must be carried out by a suitable qualified electrical trades-person and in accordance with local supply authority requirements and associated regulators.

The outdoor unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse.

Fix power source wiring to control box by using buffer bushing for tensible force (PG connection or the like). Connect control wiring to control terminal block through the knockout hole of control box using ordinary bushing.

NOTE: Earth wiring must be connected.

Arrangement such as terminal block in control box

Control module of indoor unit

PEH-5, PE(H)-7, 8,10

Control module of indoor unit

PE(H)-15, 20

PE(H)-7 only

Terminal block for connection wires to

Outdoor unit and remote controller

PEH-15, 20 only

30FZ

C

30FZ

F1

F2

Terminal block for connection wires to

Outdoor unit and remote controller

FZ

TB3

Tr

F1

F1 3.15A

F2 3.15A

F2

CZ1-1

PEH-15, 20 52F&51F1

PE-15, 20 52F1&51F1

PEH only

Tr

TB3

52F

&

51F1

CZ1-2

Terminal block for power supply wires

FZ

Terminal block for power supply wires

TB2

PEH-15, 20 HZ1

PE-15, 20 FZ

TB2

HZ1 CZ1

Bush and band for the power supply

Bush for the thermistor

Screw for earth connection

Bush and band for the connection wires to Outdoor unit and remote controller

Screw for earth connection

Bush and band for the power supply

Bush for the thermistor

Bush and band for the connection wires to Outdoor unit and remote controller

Control module of outdoor unit (PUH-5, 8, 10)

Side blow

Screw for earth connection

51F2

Terminal block for power supply wires

TB1

F3

T1

30CZ

X2

X3

52C

&

51C

TB4

CZ2 HZ2

X1

Terminal block for connection wires to Indoor unit

Band for wires

- 98 -

Control module of outdoor unit PU(H)-7, 8, 10

Upper blow

PUH only

Control module of outdoor unit PU-15

F3

T1

52C

&

51C

PUH only

51F2

X1

PUH only

Terminal block for connection wires to

Indoor unit

Screw for earth connection

Terminal block for power supply wires

TB1

X2 X3

TB5

Band for wires

TB1

Terminal block for power supply wires

52C1

&

51C1

52F2

&

51F2

52C2

&

51C2

TB4

2

30CZ1 30CZ2

CZ

2-1

CZ

2-2

Screw for earth connection

Bush for wires

Terminal block for connectioon wires to Indoor unit

F3

F3 3.1

Control module of outdoor unit PU-20 Control module of outdoor unit PUH-15,20

52F2&

51F2

52C2

&

51C2

51F3

52C1

&

51C1

2

30

CZ1

30

CZ2

Screw for earth connection

TB1

TB4

CZ

2-1

CZ

2-2

F3

Terminal block for connection wires to Indoor unit

Terminal block for power supply wires

Bush for wires

TB1

Screw for earth connection

52C1

&

51C1

51F2

X1

52C2

&

51C2

51F3

T1 T2 2

X3 X4 X5

F3

X2

X6

CZ

2-1

30CZ1 30CZ2

CZ

2-1 HZ2

TB4

Terminal block for power supply wires

Bush for wires

Terminal block for connectioon wires to Indoor unit

- 99 -

Method for connecting electric wire

Please do the wiring after consulting the electric power company of jurisdiction beforehand in the instruction.

(1) The entire wiring diagram of unit.

j

PE e b a g c

In case of PE-7, 8, 10

In case of PEH-15, 20 a

In case of PE-15, 20

PEH-5, 7, 8, 10 b d f

PE j

In case of PE-7,8,10

In case of PE-15,20

PEH-5, 7, 8, 10

In case of PEH-15,20 h i d.

e.

f.

a.

b.

c.

g.

Power supply

Main switch/fuse (field supply)

Power supply wiring for outdoor unit

Power supply wiring for indoor unit

Outdoor unit

Indoor unit

Connection wiring for indoor

/ outdoor units (polarity) h.

i.

j.

Remote controller (field supply)

Connection wiring for indoor

/ remote controller (no polarity)

Earth

(2) Power supply construction and electric wiring connection of indoor and outdoor unit.

In case of PE(H)-15,20

A

3phase

PE(H)-7:Single phase

PEH-5 15A

PE(H)-7,8,10 15A

PE(H)-15,20 30A

B

G

L

1

L

2

L

3

NPE

In case of

PEH-5

PE(H)-7,8,10

H

13 14 15

C

H

11 12 13 14

C

D

3 phase

PUH-5 50A

PU(H)-7,8 50A

PU(H)-10 60A

PU(H)-15 100A

PU(H)-20 125A

E F

L

1

L

2

L

3

NPE

G

13 14 15

H

PEH only

11 12 13 14

H

PEH only

A.

B.

C.

D.

E.

F.

G.

H.

Indoor unit

Power cable wiring

Control cable wiring

(Fixing wire-- Do not remove)

Outdoor unit

Breaker

Fuse

Power supply terminal bed

Control cable terminal bed

- 100 -

(3) Indoor unit and remote controller.(OPTION:PAC-204RC)

Connect the wires on the basis of the following wiring diagram.

PEH-5, PE(H)-7,8,10

GRAY

TB4 1

F2

(3.15A)

Tr

AC

220

240V

AC24V

GRAY

TB4

2

CZ1

4

FZ

3

PE(H)-15,20

GRAY

F2

(3.15A)

TB3 1

Tr

AC

220

240V

AC24V

GRAY

TB3

2

CZ

1-1

CZ

1-2

3

5

4

FZ

(4) Wiring example (For metal piping)

PEH - 5

PE(H) - 7

PE(H) - 8

Power cable

2.0mm

2

2.0mm

2

2.0mm

2

PE(H) -10

PE(H) -15

2.0mm

2

2.0mm

2

PE(H) -20

2.0mm

2

PUH - 5

PU(H) - 7

PU(H) - 8

PU(H) -10

PU(H) -15

PU(H) -20

8mm

2

8mm

2

8mm

2

14mm

2

14mm

2

22mm

2

Breaker capacity

15A

15A

15A

15A

30A

30A

50A

50A

50A

60A

100A

125A

Over current protection switch

15A

15A

15A

15A

30A

Earth cable

2

2.0mm over

Control wiring

Cable or wire of

0.75mm

2

(24VDC)

30A

50A

50A

50A

60A

100A

125A

2

8mm over

Cable or wire of

0.75mm

2

(24VDC)

The grounding wire must be of the same diameter as the power cable wires.

Table above is an example.

The selection of other capacities should be determined in accordance with the relevant standards.

(5) Selecting earth leakage breaker (NV)

To select NF or NV instead of a combination of Class B fuse switch use the following.

In the case of Class B fuse rated 15A.

PEH - 5

PE(H) - 7

PE(H) - 8

PE(H) - 10

PE(H) -15

PE(H) -20

PUH - 5

PU(H) - 7

PU(H) - 8

PU(H) - 10

PU(H) - 15

PU(H) - 20

Fuse

(class B)

15A

15A

15A

15A

30A

30A

50A

Earth leakage breaker

(with over-load protection)

NV30-CA

NV30-CA

NV30-CA

NV30-CA

15A

15A

15A

15A

30mA 0.1s or less

30mA 0.1s or less

30mA 0.1s or less

30mA 0.1s or less

NV50-CP

NV50-CP

NV50-CA

50A

50A

60A

NV50-CA

NV50-CA

NV60-CA

100A NV100-CP

125A NV225-CP

30A

30A

50A

50A

50A

60A

100A

125A

30mA 0.1s or less

30mA 0.1s or less

100mA 0.1s or less

100mA 0.1s or less

100mA 0.1s or less

100mA 0.1s or less

100mA 0.1s or less

100mA 0.1s or less

NV is a product of

MITSUBISHI ELECTRIC.

Table above is an example.

The selection of other capacities should be determined in accordance with the relevant standards.

Note.

All electrical wiring must be comply with local electrical authority regulations.

- 101 -

7. The putting condition of the belt.

(PE(H)-15,20 only)

1.Set the parallel angle of the fan and the motor pulley as shown in the table and figure 1 below.

2.Set the tension of the per one belt when the flexion load is within the range as shown in the figure 1

below at the proper flexion. (A=4.5mm)

3.Adjust the suitable tension after the belt sit properly across the pulley (after more 24-28 hours working).

When the new belt is used, adjust the suitable tension about the 1.3 times of the maximum value of the

flexion load.

4.Readjust the belt every 2,000 hours after the first adjustment.

Exchange the belt when the belt's surroundings length has expanded by 2% including the first expansion

of the belt. (about 1%)

(about 8,000 hours converted working time) table pulley pulley parallel angle

K ( ) note

10 or less gap of 3mm every 1m

K

K

Flexion load(W)

1.4 2.2kg

K

A

A=4.5mm

K

K

Figure1 Parallel degree of pulley Figure2 Belt tension

8. Before starting the Trial run.

Check items

(1) Check to see wheter there are refrigerant leakage, and slack power or transmission cable.

(2) Conform that 500V megohmmeter shows 1.0M ohm or more between power supply terminal and ground.

(3) Do not operate in the case of 1.0M ohm or less.

Note : Never carry out megger-ohm check over terminal control board.

Otherwise the control board would be broken.

(4) Check to see wheter both gas and liquid valves are fully opened.

Note : Be sure to tighten caps.

(5) Turn universal power supply at least 6 hours before gettig test run in order to current to crank heater.

If current-carrying hours are too short, it may result in a malfunction of compressor.

(6) Confirm operation of high-pressure switch.

If the two lead wires of the outdoor unit fan motor are disconnected from the connector and cooling is performed, the high-pressure switch should operate and stop the unit after 5 to 10 minutes.

(7) Confirm that the fans of the indoor and outdoor unit rotate in the correct direction.

Change the power supply phase connections if it is rotating in the reverse direction.

Perform trial operation after completion of the above items.

- 102 -

INSTRUCTIONS FOR USE

1.Check points for operation.

Check the following points before you operate your air conditioner.

(1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet.

Indoor unit

Outlet grille

Inlet grille

Ceiling Ceiling

Obstacle blocking air outlet Obstacle blocking air inlet

Outdoor unit

Obstacle blocking air inlet.

(2)Make sure the air conditioner is properly grounded by checking the ground terminal.

- 103 -

Ground

2.Caution for use.

Keep the following points in mind to safeguard against failures and breakdowns.

(1) This air conditioner does not restart within 3min.

after shut down.

(These models have a crankcase heater in the compressor. If the air conditioner is shut down for a short time, please do not turn the power switch to OFF, but turn the operation switch to OFF.)

(2) If the air conditioner is shut down by a power failure,

set the operation switch to OFF. When the power

is restored, normal air conditioner operation can

be resumed.

(3) Do not stick rods or other objects through the air

outlet during operation since this may result in

equipment damage or personal injury.

Shutdown

3 Minutes

Operation

3.Maintenance.

For superior performance and lasting durability, please do not forget to conduct proper and regular maintenance

.

Warning

1.Do not wash the unit with water.

If washed with water, electrical shock may be caused.

2.Ahead of the maintenance.

For safety, turn the power source off before service work.

3.1 Cleaning the Air Filter

Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location.

Clean more regularly if the air filter gets very dirty.

If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate.

Failure to clean the air filter may result in equipment breakdown or malfunctions.

3.2 Cleaning panels

Clean dirt off front panel as follows.

Use a household neutral cleanser such as for dishes or

vegetables. Moisten a soft cloth with the cleanser, then wipe

lightly. Next,wipe three or four times with another soft cloth

moisten with water. Finally, wipe off all the remaining

cleanser with a soft cloth.

Moisten a soft cloth with the alcohol, then wipe off lightly.

Isopropyl alcohol is sold at stores as reagents in small

quantities.

Note:

Alcohol is highly combustible. Take extreme care

when handling. Also, do not use paint or adhesive

thinner.

Fingermarks

Grease

Adhesive

Paste

Neutral

Cleanser

Isopropyl alcohol

- 104 -

3.3 Cleaning the Outdoor Unit Heat Exchanger

If you use your air conditioner for prolonged periods,

the outdoor heat exchanger will become dirty, impairing

its function and reducing air conditioners performance.

Consult your equipment supplier or air conditioning

contractor on how to clean the heat exchanger.

Heat exchanger

4.When beginning to use air conditioner again.

Please turn on the power supply after confirming an following check is done and abnormality is not found.

(1) It is confirmed that air inlet and outlet are not blocked.

(2) It is confirmed that the earth connection line does not come off.

The earth connection line is occasionally installed in the outdoor unit.

(3) It is confirmed that there are neither lifting , blocking , nor bending about the drain-hose.

Keep the power switch ON for more than 6hours before starting operation, to operate the crankcase heater to drive refrigerant out of oil.

Do not turn the power supply OFF during seasons of heavy use.

Doing so can result in failure .

5.When the air conditioner is not to be used for a long time.

(1) If the air conditioner is not to be used for a long time due to a seasonal change etc.,run it for 4-5hours with the air blowing until the inside is completely dry.

Failing to do so can result the growth of unhygienic, unhealthy mold in scattered areas throughout

the room.

(2) When it is not to be used for an extended time, keep the < power supply >turned OFF.

If the power supply is kept on, several watts or several tens of watts will be wasted.

Also, the accumulation of dust, etc., can result in fire.

5-1 In case of failure.

(1) Never remodel the air conditioner.

Consult your dealer for any repair service.

Improper repair work can result in water leakage, electric shock, fire, etc.

(2) If the poser breaker is frequently activated, get in touch with your dealer.

Leaving the unit as it is under such conditions can result in fire or failure.

(3) If the refrigeration gas blows out or leaks, stop the operation of the air conditioner.

(4) Thoroughly ventilate the room, and contact your dealer.

Leaving the unit as it is can result in accidents due to oxygen deficiency.

6.Transferring work, and construction

6-1 Transfer of installation.

(1) When removing and reinstalling the air conditioner when you enlarge your home, remodel, or move,

consult with your dealer in advance to ascertain the cost of the professional engineering work required

for transferring the installation.

(2) Please do not mix the one other than a specified refrigerant when you add the refrigerant (R-22) at the

installation and the transferring.

(3) When moving or reinstalling the air conditioner, consult with your dealer.

Defective installation can result in electric shock, fire, etc.

- 105 -

6-2 Place for installation.

Please do not use the unit in the following places.

(1) Place where a lot of oil (The machine oil is contained), moistures, and dust exist.

(2) Place where a lot of salinities such as beach districts exists.

(3) Place where sulfur gas, volatile gas, and corroded gas are filled.

(4) Place where acid solution is frequently used.

(5) Place where special spray is frequently used.

(6) Hot spring zone.

(7) Never machine (high cycle welding machine etc.) generating highcycle.

(8) Place where ventilation entrance of outdoor units is closed by snowfall.

(9) The unit must be installed on stable, level surface.

The main body might corrode when the unit is used in such a place, the refrigerant leak, the performance of the unit decrease remarkably, and it cause the damage of parts of the unit.

6-3 Regarding electric work.

(1) The electrical work must be undertaken by a person who is qualified as an electric engineer according to

the (technical standard respecting electrical installation), (internal wiring rules), and the installation

instruction manual with the absolute use of exclusive circuits.

(2) Please install a special power supply in the power supply.

(3) Please install the earth connection for the electric shock prevention.

(4) Never connect the grounding wire to a gas pipe, water pipe, arrester, or telephone grounding wires.

For details, consult with your dealer.

(5) In some types of installation sites, the installation of an earth leakage breaker is mandatory. For details,

consult with your dealer.

(6) The breaker and the fuse must use the one of correct capacity.

6-4 Conseration of the noise.

(1) Take sufficient measures against noise when installing the air conditioners at hospitals or

communication-related businesses.

(2) If the air conditioner is used in any of the above-mentioned environments, frequent operational failure

can be excepted.

It is advisable to avoid these type of installation sites.

For further details, consult with your dealer.

(3) Choose a place where cool or warm air and noise from the outdoor air outlet of the air conditioner do

not inconvenience the neighbours.

(4) If any alien object is placed near the air outlet of the unit, decreased performance and increased noise

can result.

Avoid placing any obstacles adjacent to the air outlet.

(5) If the air conditioner produces any abnormal sound, consult with your dealer.

6-5 Disposing of the unit.

When you need to dispose of the unit, consult your dealer.

If pipes are removed incorrectly, refrigerant (fluorocarbon gas) may blow out and come into contact with your skin, causing injury.

Releasing refrigerant into the atmosphere also damages the environments.

6-6 Maintenance and inspection.

(1) If the air conditioner is used throughout several seasons, the insides can get dirty, reducing the

performance.

(2) Depending upon the conditions of usage, foul odours can be generated and drainage can deteriorate

due to dust and dirt, etc.

- 106 -

7.Trouble shooting

Air flows out but it does not cool or heat enough.

Before you ask for repair service, check the following points:

State of Machine

It does not run.

Cause

Power failure.

The power supply is turned OFF.

The fuse in the power supply is gone.

The earth leakage breaker is gone.

Improper temperature adjustment.

Cool or warm air does not come out.

Troubleshooting

Press the [ON/OFF] button after power restoration.

Turn the power supply ON.

Replace fuse.

Put in the earth leakage breaker.

After checking the set temperature.

The filter is filled with dust and dirt.

There are some obstacles at the air inlet and outlet of the units.

Windows and doors are open.

Clean up the filter.

Remove.

Close.

Insufficient refrigerant charge.

Contact with your installing contractor.

The restart-preventing circuit is in operation for

3 minutes.

Wait for a while.

(To protect the compressor, a 3-minute restartpreventing circuit is built into the unit.

Therefore, there are occasions sometimes when the compressor does not start running immediately.

There are cases when it does not run for as long as 3 minutes.)

Indoor unit operation was started anew during the heating and defrosting operation.

(5 10 HP only)

Wait for a while.

(Heating operation starts after ending defrosting operation.)

Fan runs but compressor do not run.

Fan runs but stops immediately.

Fogged white steam is discharged from the indoor unit.

Water or steam is discharged from the outdoor unit.

On heating, the air flow stops although a set temperature is not reached. (PEH only)

The set temperature of thermostat is excessively high for cooling.

excessively low for heating. (PEH only)

The room temperature is excessively low for cooling.

excessively high for heating. (PEH only)

Air outlet and inlet are blocked.

When the indoor temperature and humidity are high, such a phenomenon is occasionally had at the beginning of system operation.

At cooling, water which places to cooling piping and piping connection part drops.

When heating, water which places to the heat exchanger drops. (PEH only)

Frost adheres to the outdoor coil when the temperature on the outside is low and humidity is high. This frost is melted.

For temperature control, decrease the set temperature at cooling.

increase the set temperature at heating. (PEH only)

Can not be operated as it is out of temperature control range.

Remove blocking matter.

It is not a breakdown.

Please use as it is.

It is not a breakdown.

Please use as it is.

It is not a breakdown.

Please use as it is.

- 107 -

H

A

HOW TO OPERATE (OPTION PAC-204RC)

Display section

G

C

B

D F

E

A

B

C

[Current/start/ending time] Display

Operation mode

Displays the status of operation.

[Checking] Display

This displays indication when some abnormality

occurs in the unit.

D

E

F

G

H

[Set temperature] Display

Displays the set temperature.

[Operation] Lamp

Lights up during operation, goes off during stop.

[Room temperature] Display

Displays the temperature of the air sucked in

during operation.

[Fan speed] Display

This displays indication High-speed or Low-speed.

[Key lock] Display

This display indication during key lock function active.

For purposes of explanation, all the displays on this page are shown in their lit condition. This configuration does not occur in the actual unit.

Before starting operation

* Make sure that the power supply is turned ON before use. (Keep the power supply turned ON at all times when the air conditioner is in use. Use of the unit without power can result in compressor failure.)

Warning:

Check and confirm the power circuit before use. For the contents, refer to the previously described chapter

[Crucial points to be observedfor safety].

1-1 ON / OFF

A

Start an operation

Press the [ON/OFF] button

Operation lamp lights up and operation starts.

1

Stop an operation

Press the [ON/OFF] button again

Operation lamp goes off and operation stops.

* Once the buttons have been set, pressing of the [ON/OFF] button only can repeat the same operation thereafter.

* During operation, the operation lamp above the [ON/OFF] button lights up.

A Operation lamp

Caution:

Even if the operation button is pressed immediately after the operation is once stopped, operation is not restarted for about 3 minutes. This function protects the machine. It automatically starts operation after the lapse of approximately 3 minutes.

- 108 -

1-2 Selecting operation

A Operation mode display

A

1

When selecting operation

Press the [MODE] button

Consecutive press of the [MODE] button switches the operation over to "FAN", "COOL", "HEAT" and "AUTO". For the contents of operation,check the display.

For fan

Press the [MODE] button and bring up the "FAN" display.

* The fan operation functions to circulate the air in the room.

* The temperature of the room cannot be set by fan operation.

Caution:

Never expose your body directly to cool air for a long time.

Excessive exposure to cool air is bad for your health, and should therefore be avoided.

For cooling

Press the [MODE] button and bring up the "COOL" display.

For heating

Press the [MODE] button and bring up the "HEAT" display.

Caution:

* When the air conditioner is used together with burners, thoroughly ventilate the area. Insufficient ventilation can result in accidents due to oxygen deficiency.

* Never place a burner at a place where it is exposed to the airflow from the air conditioner.

Doing so can result in imperfect combustion of the burner.

For Auto change over

Press the [MODE]button and bring up the "AUTO" display

This function is special order. Please consult your local Mitsubishi Electric Sales office for application advice on this function.

Because this function need low ambient cooling parts as option.

Indoor temperature can be set within the following range.

Indoor temperature setting range:17

~

30˚C

1-3 Room temperature adjustment

A

1

To change room temperature

1 Press the room temperature button and set the room temperature of your choice.

Press or once changes the setting by 1 .

If the pressing is continued, the setting continues to change by 1 .

* Indoor temperature can be set within the following range.

Cooling 19 30

Heating 17 28

* It is impossible to set the room temperature by the air-blow

operation

1 Press and together, the unit of temperature

A Set temperature display and room temperature display heit)

- 109 -

1-4 Time setting

A

B

2

3

5

Clock key

1 Press the key one time will activate set clock mode.

Press the key again will disable set clock mode.

2 4

Under set clock mode, the real time clock and present day setting can be changed by pressing Day key, Hour key or

Minute key.

7-Days timer key

1 There are two keys for timer. One is ON Timer, another is

Off Timer.

Press the key one time will activate set timer mode.

Press the key again will disable set timer mode.

2 4

Under set timer mode, the 7-days timer setting can be changed by pressing Day key, Hour key or Minute key.

A

B

1 4

Current time display

Timer Hold/Resume display

Day key

2 During set clock mode or set timer mode, press the key will change the day setting.

Hour key

3 During set clock mode or set timer mode, press the key will change the hour setting.

Minute key

4 During set clock mode or set timer mode, press the key will change the minute setting.

Timer Hold/Resume key

5

If 7-days timer is set, then the word "Timer Active" is displayed.

To clear all the timers setting, Press and hold the hold key until the word "Timer Active" is not displayed.

To resume the timer setting after timers have been held, press and hold the key until the word " Timer

Active" is displayed.

1-5 Other function

Key lock

1

Press the "MINUTE" key three times consecutively,

"KEY LOCK" symbol will appear on LCD screen.

At this time, only "ON-OFF" key is valid.

This function purpose is protect from mischief of child etc.

To cancel the key lock function, Please press "MINUTE" key three times consecutively again.

Test run

2 Press the "TEST" key two times consecutively.

The unit will run and finished automatically after two hours.

1

2

- 110 -

1-6.Trouble shooting

Before you ask for repair service, check the following points:

State of Machine

It does not run

Remote Controller

"ON-OFF "display is not lit up

No display appears even when the [ON/

OFF] button is pressed.

Power failure

Cause

The power supply is turned OFF.

The fuse in the power supply is gone.

The earth leakage breaker is gone.

Troubleshooting

Press the [ON/OFF] button after power restoration.

Turn the power supply ON.

Replace fuse.

Put in the earth leakage breaker.

After checking the set temperature and inlet temperature on the liquid crystal display, refer to

[To change room temperature] on page 107, and operate the adjustment button.

Air flows out but it does not cool enough or heat enough.

The liquid crystal display shows that it is in the state of operation.

Improper temperature adjustment.

Cool air or warm air does not come out.

Can not change to Heat mode

The liquid crystal display shows that it is in operation.

Can not change to

Heat mode when press the "MODE" key.

The filter is filled with dust and dirt.

DIP switch1 is not correct

Clean up the filter.

There are some obstacles at the air inlet and outlet of the indoor and outdoor units.

Windows and doors are open.

Remove.

Close.

The restart-preventing circuit is in operation for

3 minutes.

Wait for a while.

(To protect the compressor, a 3-minute restartpreventing circuit is built into the indoor unit.

Therefore, there are occasions sometimes when the compressor does not start running immediately. There are cases when it does not run for as long as 3 minutes.)

Indoor unit operation was started anew during the heating and defrosting operation.

(5 10 HP only)

Wait for a while.

(Heating operation starts after ending defrosting operation.)

Change the DIP switch off to on.

(Refer to Instruction manual for Installation.)

Error Display

Indicate

E01

E02

E03

Cause

Room temperature sensor open.

Room temperature sensor short.

Error input from Indoor unit or

Outdoor unit.

Troubleshooting

Automatically reset to restoration error.

Automatically reset to restoration error.

Push the On-Off switch.(OFF to ON)

- 111 -

SPECIFICATION GUIDELINES

Air to air reverse cycle split air conditioning system.

The systems shall operate at out door ambient temperatures as high as .

The system shall have a total cooling capacity of kW or greater with an indoor air quantity of L/s at DB and WB entering indoor coil temperature with a temperature entering the outdoor coil.

The system shall have a sensible heat capacity of kW or greater with a room DB temperature of .

The total heating capacity (without electric element heaters) shall be kW or greater at DB,

WB outdoor air conditions, with of indoor air entering indoor coil at DB.

The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be equipped with a crankcase heater.

Coils shall be of non-ferrous construction with mechanically bonded aluminum plate fins Outdoor coils shall be made, of 9.52mm OD, 0.35mm thick formless copper tubes mechanically bonded to 0.12mm

thick aluminum plate fins.

Face area of the coil shall not be less than m

2

The coil shall be factory pressure and leak tested at

3.3 MPa pressure. The indoor coil face area shall be not less than m

.

2

Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to ensure smooth airflow and shall discharge vertically and be direct driven by a weatherproof three phase squirrel cage kW induction motor.

The system shall be factory wired and all electrical wiring must comply with the Local wiring code (Controls and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal and current sensitive overload devices.

An automatic defrost control shall be included to accomplish defrosting (only if required) every minutes for a period of minutes.

High pressure switch (pre-set) shall be factory installed.

The enclosure is weatherproof casing constructed of phosphatized, zinc coated steel with powder coating.

(OUTDOOR UNIT)

The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall be located in the pillars. (OUTDOOR UNIT)

The unit shall have a drain connection provided (25mm BSP:male thread).

The enclosure shall have openings provided for power connections.

Access for both service and installation shall be provided to compressors, control wiring, and fans.

Side panels and top panels shall be removable for easy service access.

The unit maximum dimensions shall be : height: mm, width: mm and depth: INDOOR UNIT

)

: height: mm, width: mm and depth: OUTDOOR UNIT)

Due to continuous product development, these guidelines are subject to change.

- 112 -

MEMO

- 113 -

DATA BOOK PE,PEH

MITSUBISHI ELECTRIC CORPORATION

HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100-0005,TELEX J24532 CABLE MELCO TOKYO

Issuued in Dec. 1999 MEE99K014 New publication effective Dec. 1999.

Specifications subject to change without notice.