T1kVA and T1.5kVA Tower Uninterruptible Power
Supplies
Product Guide
The T1kVA and T1.5kVA Tower Uninterruptible Power Supply (UPS) offerings provide power protection with increased efficiency and simplified power management to safeguard the high-availability of System x® and ThinkServer® server environments. With efficiency ratings of up to 97%, these compact tower designs can help reduce energy usage without compromising performance or reliability.
The Tower UPS unit (T1kVA or T1.5kVA) is shown in Figure 1.
Figure 1. Tower UPS unit (T1kVA or T1.5kVA)
Did you know?
T1kVA and T1.5kVA Tower UPS units feature Advanced Battery Management (ABM) technology that uses a unique three-stage charging technique that significantly extends battery service life and optimizes recharge time, compared to traditional charging.
T1kVA and T1.5kVA Tower UPS units can enhance system availability with individual receptacle groups or load segments that can be programmed and controlled, which allows mission-critical devices to be prioritized during shutdown to preserve battery run time if there is a prolonged power outage.
T1kVA and T1.5kVA Tower UPS units come standard with UPS Power Manager (UPM) power management software that integrates seamlessly with the major virtual platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.
Check for Updates
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 1
Ordering information
Table 1 shows the part numbers and feature codes for the T1kVA and T1.5kVA Tower UPS models and options.
Table 1. Ordering part numbers and feature codes
Description
UPS units
T1kVA Tower UPS (100-125VAC)
T1kVA Tower UPS (200-240VAC)
T1.5kVA Tower UPS (100-125VAC)
T1.5kVA Tower UPS (200-240VAC)
Options
UPS Network Management Card
Environmental Monitoring Probe
Part number
55951AX
55951KX
55952AX
55952KX
46M4110
46M4113
Feature code
A548 (5595-TU1)
A549 (5595-TU1)
A54A (5595-TU2)
A54C (5595-TU2)
6145
6146
The UPS models ship the following items:
An accessory kit, which contains the following items:
Serial cable: 3.7 m (12 ft)
USB cable
Remote emergency power-off (REPO) connector
A documentation kit, which contains the following items:
Warranty flyer
Important Notices Manual
Documentation CD
Software CD, which contains UPM software
The 100 - 125 V models (1AX and 2AX) ship with fixed 1.8 m NEMA 5-15P line cord. The 200 - 240 V models (1KX and 2KX) do not ship with line cords. Table 2 lists the compatible line cords, which are suitable for models 1KX and 2KX.
Table 2. Line cords for 200 - 240 V models (models 1KX and 2KX)
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 2
Description
10A/250V C13 to NEMA 6-15P 2.8m line cord
Argentina 10A line C13 to IRAM 2063 (2.8M)
Australia/NZ 10A line C13 to SAA-AS C112 (2.8M)
Brazil 10A line C13 to NBR 6147 (2.8M)
China 6A line C13 to GB 2099.1 (2.8M)
Denmark 10A line C13 to DK2-5A (2.8M)
European 10A line C13 to CEE 7/7 (2.8M)
India 6A line C13 to Fig 68 (2.8M)
Israel 10A line C13 to SI 32 (2.8M)
Italy 10A line C13 to CEE 7/7 (2.8M)
Korea 7A line C13 to KETI 15A/250V (2.8M)
South Africa 10A line C13 to SABS 164/1 (2.8M)
Switzerland 10A line C13 to SEV 1011 (2.8M)
Taiwan 10A/250V C13/CNS 10917 2.8m line cord
United Kingdom 10A line C13 to BS 1363 (2.8M)
Part number
46M2592
39Y7930
39Y7924
39Y7929
39Y7928
39Y7918
39Y7917
39Y7927
39Y7920
39Y7921
39Y7925
39Y7922
39Y7919
81Y2375
39Y7923
6269
6218
6217
6219
6214
6216
A0RF
6215
Feature code
A1RF
6222
6211
6223
6210
6213
6212
The T1kVA and T1.5kVA Tower UPS models also come equipped with a communication bay for the installation of an optional Network Management Card (46M4110). The Network Management Card (NMC) provides convenient, over-the-network UPS remote monitoring and management through a standard web browser or UPM software. The following figure shows the UPS NMC.
Figure 2. UPS Network Management Card
The NMC has the following features:
Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
Simultaneous shutdown of protected servers
Configuration of automatic email messages in response to UPS alarms and to transmit periodic reports
Customizable actions, including automatic shutdown if there is an extended power failure with standard UPS Power Protector software
Control of UPS on/off switching with a web browser
Adjustment and control of load segments through the HTML interface, including sequential starting of the installation and optimization of backup time by shutting down non-priority systems
Automatic date and time adjustment through an NTP server
Dual stack IP v4/IP v6
Recording of events and measurements in the card log
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 3
Data and event logging in the nonvolatile memory
Card firmware update through the network
10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
Measurement of humidity and temperature with the optional Environmental Monitoring Probe (EMP)
Easy installation (can be installed while the UPS is online to maintain the highest system availability)
An optional EMP (part number 46M4113) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC. The EMP is shown in the following figure.
Figure 3. Environmental Monitoring Probe
The EMP has the following features:
Monitors temperature, humidity, and status of two user-provided contact devices or sensors
Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable included with the EMP)
Can be located up to 20 m (65.6 ft) from the UPS
Measures ambient temperatures 0 - 80 °C (32 - 176 °F) with an accuracy of ±1 °C
Measures relative humidity 10 - 90% with an accuracy of ±5%
Displays temperature, humidity, and contact closure status through a web browser
Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
Stores events in the NMC's event log
Sends SNMP alarms to network management systems
Sends e-mail notifications through SMTP
Features
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 4
Features
A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems. It conditions, regulates, and filters out power disturbances to ensure a clean power source for IT equipment. A UPS also provides battery backup if there is a power failure.
In today’s high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial effect on all sized businesses. The typical utility power is 99.9% available, but that means that there can be almost 9 hours of downtime a year, which includes brownouts and other power quality problems.
Selecting the right UPS can help protect against these potentially costly incidents.
The T1kVA and T1.5kVA Tower UPS units are most effective against five power problems: power failures, power sags, power surges, under-voltage, and over-voltage.
The T1kVA and T1.5kVA Tower UPS models offer the following features:
High-efficiency protection delivers more real power (watts) in a compact design, lowering power, and cooling consumption
Graphical Liquid Crystal Display (LCD) provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
English
French
German
Spanish
Russian
Portuguese
Italian
Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
Standard UPS Power Manager software provides effective local or remote power monitoring and management for servers and virtual machines and allows for graceful remote system shutdown
ABM technology significantly extends battery service life and optimizes recharge time
Load segments for individual control of receptacle groups to manage sequential shut downs and start ups and reserve battery run time for the most critical equipment
Optional NMC for enhanced UPS monitoring and control over-the-network through a standard web browser
Optional Environmental Monitoring Probe for thermal management requirements (temperature and humidity)
Allows dual channel communication through the USB or RS-232 port and an optional NMC at the same time to maximize communications flexibility
Remote flash upgradeable firmware for the UPS and NMC, which makes it an ideal solution for remote locations
Includes a Remote On/Off (ROO)/Remote Power Off (RPO) port to control power of the UPS unit through a wired remote switch
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 5
Technical specifications
Table 3 lists the technical specifications for the T1kVA and T1.5kVA Tower UPS units.
Table 3. Technical specifications
Specification
General
Part number
Form factor
Topology
VA/Watts rating
Efficiency (on utility power)
Energy Star compliant
Electrical input
T1kVA Tower UPS
(100-125VAC)
55951AX
Tower
T1kVA Tower UPS
(200-240VAC)
55951KX
Tower
T1.5kVA Tower UPS
(100-125VAC)
55952AX
Tower
Line interactive, high frequency, sinewave output
1000 VA/770 W
Up to 97%
1150 VA/770 W
Up to 97%
1440 VA/1100 W
Up to 97%
No Yes
Input voltage
Input frequency
Max input amperage
Input connector
Input line cord
100 - 125 V AC
50/60 Hz
8.8 A
Electrical output
Output voltage settings
100/120/125 V AC
Output frequency 50/60 Hz
Output power capacity
100 V AC:
833 VA/641
W
200 - 240 V AC
50/60 Hz
5.3 A
NEMA 5-15P (12 A) IEC 320 C14 (10 A)
Fixed 1.8 m (6 ft)
NEMA 5-15P
Optional (See Table
3)
200/208/220/230/240
V AC
50/60 Hz
200 - 208 V
AC: 1035
VA/693 W
120 - 125 V
AC: 1000
VA/770 W
220 - 240 V
AC: 1150
VA/770 W
Yes
100 - 125 V AC
50/60 Hz
12 A
NEMA 5-15P (12 A)
Fixed 1.8 m (6 ft)
NEMA 5-15P
100/120/125 V AC
50/60 Hz
100 V AC:
1080 VA/825
W
120 - 125 V
AC: 1440
VA/1100 W
T1.5kVA Tower UPS
(200-240VAC)
55952KX
Tower
1550 VA/1100 W
Up to 97%
Yes
200 - 240 V AC
50/60 Hz
7.1 A
IEC 320 C14 (10 A)
Optional (See Table 3)
200/208/220/230/240
V AC
50/60 Hz
200 - 208 V
AC: 1395
VA/990 W
220 - 240 V
AC: 1550
VA/1100 W
Output connectors 8x NEMA 5-15R (12
A)
Output load segments
Primary: 4x 5-
15R
Group 1: 2x
5-15R
Group 2: 2x
5-15R
8x IEC 320 C13 (10
A)
Primary: 4x
C13
Group 1: 2x
C13
Group 2: 2x
C13
Batteries
Battery type
Battery capacity 9 Ah 9 Ah
8x NEMA 5-15R (12
A)
9 Ah
Primary: 4x 5-
15R
Group 1: 2x 5-
15R
Group 2: 2x 5-
15R
8x IEC 320 C13 (10 A)
Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, and leak-proof
9 Ah
Primary: 4x
C13
Group 1: 2x
C13
Group 2: 2x
C13
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 6
Specification
T1kVA Tower UPS
(100-125VAC)
T1kVA Tower UPS
(200-240VAC)
T1.5kVA Tower UPS
(100-125VAC)
T1.5kVA Tower UPS
(200-240VAC)
Battery management
Battery replacement
External battery support
Typical backup times
ABM technology or temperature-compensated charging method (user selectable), automatic battery test, and deep discharge protection
Hot-swap internal battery
No
See Table 5
No No
See Table 6
No
Communications and management
USB port (Type B) Yes
Yes RS-232 serial port
(RJ-45)
10/100 Mbps
Ethernet port (RJ-
45)
Environmental monitoring
Yes
Yes
Yes
Yes
Optional with Network Management Card, 46M4110
Optional with Environmental Monitoring Probe, 46M4113 (requires Network Management
Card 46M4110)
UPS Power Manager and UPS Power Protector Management software
Control panel Intelligent 5-button graphical LCD
Power On, On Battery, and Alarm
Yes
Yes
LED indicators
Remote On/Off and Power Off
Remote On/Off (ROO) and Remote Power Off (RPO) terminal block connector
The following two tables list the expected period that the T1kVA and T1.5kVA Tower UPS models operate solely on batteries, depending on the load.
Table 4. T1kVA Tower UPS runtime chart
Percentage
Load
Watts
20%
30%
40%
50%
60%
70%
80%
90%
100%
154 W
231 W
308 W
385 W
462 W
539 W
616 W
693 W
770 W
Run time in minutes
T1kVA Tower UPS (100-125VAC) T1kVA Tower UPS (200-240VAC)
7
6
9
8
5
33
21
15
12
33
21
15
11
9
7
6
5
4
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 7
Table 5. T1.5kVA Tower UPS runtime chart
Percentage
Load
Watts
20%
30%
220 W
330 W
40%
50%
60%
70%
440 W
550 W
660 W
770 W
80%
90%
100%
880 W
990 W
1100 W
6
5
4
18
13
11
8
Run time in minutes
T1.5kVA Tower UPS (100-125VAC) T1.5kVA Tower UPS (200-240VAC)
42
25
42
25
18
13
11
8
6
5
4
Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and temperature.
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 8
Connectors and controls
The T1kVA and T1.5kVA Tower UPS units have a 5-button graphical LCD on the front. The LCD provides useful information about the UPS, load status, events, measurements, and settings.
The following figure shows the control panel on the front of the Tower UPS.
Figure 4. Control panel on the front of the Tower UPS
The following functions are available on the control panel:
Status information: Displays the battery status, load percentage, output power, operational mode, and load group information.
Measurements: Displays the output watts VA, amperage, power factor, voltage, frequency, input voltage, input frequency, battery voltage, efficiency, and power usage.
Control: Displays the battery test, reset error state, configure load segments, clear power usage measurements, and restore settings.
Settings: Allows you to change product general parameters and set input and output parameters, on/off conditions, and battery configuration.
Fault log: Displays the event log and alarm history.
Identification: Displays the machine type, model, and serial number of the unit and the firmware level of the UPS, including the optional NMC’s firmware level, and IP address, if installed.
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 9
The following figure shows the rear view of the T1kVA Tower UPS (100-125 VAC) (55951AX).
Figure 5. Rear view of the T1kVA Tower UPS (100-125VAC) (55951AX)
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 10
The following figure shows the rear view of the T1kVA Tower UPS (200-240VAC) (55951KX).
Figure 6. Rear view of the T1kVA Tower UPS (200-240VAC) (55951KX)
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 11
The following figure shows the rear view of the T1.5kVA Tower UPS (100-125VAC) (55952AX).
Figure 7. Rear view of the T1.5kVA Tower UPS (100-125VAC) (55952AX)
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 12
The following figure shows the rear view of the T1.5kVA Tower UPS (200-240VAC) (55952KX).
Figure 8. Rear view of the T1.5kVA Tower UPS (200-240VAC) (55952KX)
Physical specifications
The T1kVA Tower UPS unit has the following physical specifications (approximate):
Height: 233 mm (9.1 in.)
Width: 150 mm (5.9 in.)
Depth: 345 mm (13.6 in.)
Weight: 11.5 kg (24.4 lb)
The T1.5kVA Tower UPS unit has the following physical specifications (approximate):
Height: 233 mm (9.1 in.)
Width: 150 mm (5.9 in.)
Depth: 445 mm (17.5 in.)
Weight: 16.2 kg (35.3 lb)
Operating environment
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 13
Operating environment
The T1kVA and T1.5kVA Tower UPS units are supported in the following environment:
Temperature (operation):
T1kVA Tower UPS: 0 - 35 °C (32 - 95 °F)
T1.5kVA Tower UPS: 0 - 40 °C (32 - 104 °F)
Relative humidity: 5 - 95%
Maximum altitude (operation): 3,000 m (9,843 ft)
Note: These UPS units are not supported in a maritime environment.
Agency approvals
The T1kVA and T1.5kVA Tower UPS units conform to the following regulations:
FCC
UL
CSA or cUL
CE Mark
NOM
GOST
BSMI Taiwan
CB Report
VCCI
C-Tick (Australia)
IRAM (Argentina)
Warranty
The T1kVA and T1.5kVA Tower UPS models include a three-year limited warranty. Optional features include a one-year warranty.
Management software
The T1kVA and T1.5kVA Tower UPS units come standard with UPS Power Manager (UPM) and UPS
Power Protector (UPP) software.
UPM brings managing many power and environmental devices under control through a single, web-based interface. The UPM software solution ensures system uptime and data integrity by allowing you to remotely monitor, manage, and control the devices on your network.
The UPM user interface is shown in Figure 9.
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 14
Figure 9. UPM user interface
The UPM software includes the following features:
Monitors and manages multiple power and environmental devices from a web browser or your virtual machine management dashboard
Integrates seamlessly into popular virtualization infrastructures, such as VMware ESXi, Microsoft
Hyper-V, Citrix XenServer, and Linux KVM
Triggers live migration for virtual machines during power outages
Enables grouping, access, and management of multiple devices across multiple locations by using a user-definable tree structure
Monitors power consumption to help track ways to improve energy efficiency
Provides fast installation by using auto discovery, which automatically detects devices on the network
Mass-upgrades firmware, which reduces network management card setup and maintenance time
UPP software facilitates automatic, graceful shutdown of computers, servers, and network devices that are powered by a UPS. This capability saves all work-in-progress and ensuring data integrity. UPP's user interface provides detailed information about connected servers and UPS units through USB and serial or network communication.
The UPP user interface is shown in Figure 10.
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 15
Figure 10. UPP user interface
The UPP software offers the following features:
Helps avoid data loss by gracefully shutting down computers and virtual machines and servers that are powered by a UPS during an extended power outage
Provides watchdog capability that keeps servers running smoothly by automatically identifying hang-ups and rebooting the machine
Provides redundancy capability for dual-cord servers
Includes easy-to-use web browser interface
Communicates with the protected device directly (via USB or serial) or through the network (via
NMC)
Supported servers
The T1kVA and T1.5kVA Tower UPS offerings are compatible with all System x and ThinkServer servers and other devices that require AC power.
The T1kVA and T1.5kVA Tower UPS units are intended for use with the following System x and
ThinkServer 1- and 2-socket tower servers:
System x x3100 M4 x3100 M4 x3300 M4 x3500 M4 (T1.5kVA only)
ThinkServer
TS140
TS440
TD340
TD350 (T1.5kVA only)
Related publications and links
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 16
Related publications and links
For more information, see the following resources:
US Announcement Letter http://ibm.com/common/ssi/cgi-bin/ssialias?infotype=dd&subtype=ca&&htmlfid=897/ENUS114-100
Tower UPS product page http://www-03.ibm.com/systems/x/options/rackandpower/ups.html
Installation and User's Guide - Tower UPS
http://ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5096507
Network Management Card User Guide
http://ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5085199
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 17
Notices
Lenovo may not offer the products, services, or features discussed in this document in all countries. Consult your local Lenovo representative for information on the products and services currently available in your area. Any reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any
Lenovo intellectual property right may be used instead. However, it is the user's responsibility to evaluate and verify the operation of any other product, program, or service. Lenovo may have patents or pending patent applications covering subject matter described in this document. The furnishing of this document does not give you any license to these patents. You can send license inquiries, in writing, to:
Lenovo (United States), Inc.
1009 Think Place - Building One
Morrisville, NC 27560
U.S.A.
Attention: Lenovo Director of Licensing
LENOVO PROVIDES THIS PUBLICATION ”AS IS” WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR
IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF NON-INFRINGEMENT,
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some jurisdictions do not allow disclaimer of express or implied warranties in certain transactions, therefore, this statement may not apply to you.
This information could include technical inaccuracies or typographical errors. Changes are periodically made to the information herein; these changes will be incorporated in new editions of the publication. Lenovo may make improvements and/or changes in the product(s) and/or the program(s) described in this publication at any time without notice.
The products described in this document are not intended for use in implantation or other life support applications where malfunction may result in injury or death to persons. The information contained in this document does not affect or change Lenovo product specifications or warranties. Nothing in this document shall operate as an express or implied license or indemnity under the intellectual property rights of Lenovo or third parties. All information contained in this document was obtained in specific environments and is presented as an illustration. The result obtained in other operating environments may vary. Lenovo may use or distribute any of the information you supply in any way it believes appropriate without incurring any obligation to you.
Any references in this publication to non-Lenovo Web sites are provided for convenience only and do not in any manner serve as an endorsement of those Web sites. The materials at those Web sites are not part of the materials for this Lenovo product, and use of those Web sites is at your own risk. Any performance data contained herein was determined in a controlled environment. Therefore, the result obtained in other operating environments may vary significantly. Some measurements may have been made on development-level systems and there is no guarantee that these measurements will be the same on generally available systems. Furthermore, some measurements may have been estimated through extrapolation. Actual results may vary. Users of this document should verify the applicable data for their specific environment.
© Copyright Lenovo 2016. All rights reserved.
This document, TIPS1230, was created or updated on December 9, 2015.
Send us your comments in one of the following ways:
Use the online Contact us review form found at: http://lenovopress.com/TIPS1230
Send your comments in an e-mail to: [email protected]
This document is available online at http://lenovopress.com/TIPS1230 .
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 18
Trademarks
Lenovo, the Lenovo logo, and For Those Who Do are trademarks or registered trademarks of Lenovo in the
United States, other countries, or both. A current list of Lenovo trademarks is available on the Web at http://www.lenovo.com/legal/copytrade.html
.
The following terms are trademarks of Lenovo in the United States, other countries, or both:
Lenovo®
ThinkServer®
System x®
The following terms are trademarks of other companies:
Linux® is a trademark of Linus Torvalds in the United States, other countries, or both.
Microsoft® is a trademark of Microsoft Corporation in the United States, other countries, or both.
Other company, product, or service names may be trademarks or service marks of others.
T1kVA and T1.5kVA Tower Uninterruptible Power Supplies 19
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 T1kVA and T1.5kVA Tower Uninterruptible Power Supplies Product Guide
- 1 Did you know?
- 2 Ordering information
- 5 Features
- 6 Technical specifications
- 9 Connectors and controls
- 13 Physical specifications
- 14 Operating environment
- 14 Agency approvals
- 14 Warranty
- 14 Management software
- 16 Supported servers
- 17 Related publications and links
- 18 Notices
- 19 Trademarks