8910W Home Comfort Control with Wi-Fi Installation Instructions


Add to my manuals
13 Pages

advertisement

8910W Home Comfort Control with Wi-Fi Installation Instructions | Manualzz
Home Comfort Control™ with Wi-Fi
Model 8910W
READ AND SAVE THESE INSTRUCTIONS
Safety &
Installation
Instructions
Table of contents
WI-FI Setup
POWER & RESET OPTIONS
Wi-Fi Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Setup & Testing
Installation
Thermostat installation location recommendations . .
Thermostat mounting . . . . . . . . . . . . . . . . . . . . . . . . . .
Equipment control module installation location
recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Equipment control module mounting . . . . . . . . . . . . . .
Thermostat wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote temperature sensor (optional) . . . . . . . . . . . . .
Equipment control module wiring . . . . . . . . . . . . . . . .
Outdoor temperature sensor (included) . . . . . . . . . . . .
Optional wireless outdoor temperature sensor . . . . . .
Return air temperature sensor (optional) . . . . . . . . . . .
Leaving air temperature sensor (optional) . . . . . . . . . .
2
2
2
2
3
3
4
5
5
6
6
HVAC WIRING DIAGRAMS
Conventional heat/cool single transformer . . . . . . . . .
Conventional heat/cool two transformer . . . . . . . . . . .
Heat pump single transformer . . . . . . . . . . . . . . . . . . .
Heat pump two transformer . . . . . . . . . . . . . . . . . . . . .
Power and reset options . . . . . . . . . . . . . . . . . . . . . . . 10
Removal of Indoor Air Quality control buttons . . . . . . 10
Equipment type selection switch (SW1) . . . . . . . . . . 11
Installer setup menu . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Change system settings . . . . . . . . . . . . . . . . . . . . . . . 11
HVAC installer system settings table . . . . . . . . . . . 12-13
Indoor Air Quality system settings tables . . . . . . . . . 14
Air cleaning system settings table . . . . . . . . . . . . . 14
Humidifier system settings table . . . . . . . . . . . . . . 14
Dehumidifier system settings table . . . . . . . . . . . . 15
Ventilation system settings table . . . . . . . . . . . . 15-16
System test menu . . . . . . . . . . . . . . . . . . . . . . . . . . 17-18
System test tables . . . . . . . . . . . . . . . . . . . . . . . . . 18-20
References
7
7
8
8
Indoor Air Quality WIRING DIAGRAMS
Indoor Air Quality wiring with separate transformers . . . 9
Indoor Air Quality wiring with a single transformer . . . . . 9
Quick reference to controls & display . . . . . . . . . . 21-22
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22-23
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Home Comfort Control features . . . . . . . . . . . . . . . . . 23
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
WI-FI Setup
Installation
For detailed instructions for connecting the Home Comfort Control™ to a Wi-Fi network and registering it to an
Aprilaire account, refer to the Wi-Fi Quick Start Guide included in the box.
Thermostat Wiring
Wire specifications:
18-24 gauge thermostat wire
Installation
Installation notes:
Thermostat Installation location recommendations
Thermostat should be mounted:
• On an interior wall, in a frequently
occupied space.
• Approximately 5‘ above floor.
• At least 18” from outside wall.
• Thermostat can be mounted to a
vertical junction box.
1
• Ensure power at the HVAC equipment is off.
Do not mount thermostat:
• Behind doors, in corners or other dead air spaces.
• In direct sunlight, near lighting fixtures, or other appliances that
give off heat.
• On an outside or unconditioned area wall.
• In the flow of a supply register, in stairwells, or near outside doors.
• On a wall with concealed pipes or ductwork.
2
3
T1 T2
• Loosen screw terminals, insert stripped wire
and re-tighten.
• Push the excess wire back into the opening and plug the wall opening to prevent drafts.
1 – Connection to terminal 1 at equipment control module
2 – Connection to terminal 2 at equipment control module
3 – Connection to terminal 3 at equipment control module
T1 & T2 – Remote temperature sensor (optional)
Thermostat mounting
Remote temperature sensor (optional)
1.Remove the rear mounting plate from the thermostat.
2.Pull wires through the opening on the rear mounting plate.
3.Position and level the mounting plate of the thermostat on wall and
mark the hole locations with a pencil.
4. Drill 1/4” holes and insert supplied anchors (drywall only).
5. Place mounting plate over anchors, insert and tighten screws.
6.Seal wire entry holes to prevent drafts affecting temperature readings.
A remote temperature sensor can be used for control if the thermostat is to be mounted in a concealed location
or a remote sensor can be averaged with the thermostat sensor to control a large space. An 8051 flush mount
or 8053 surface mount remote temperature sensor can be attached to the T1 and T2 terminals and mounted in a
recommended area. The remote sensor must be enabled in the installer set-up menu, and once enabled will override
or be averaged with the thermostat’s internal temperature sensor, based on the setting.
Equipment Control Module Installation Location Recommendations
Note: Installer must touch a grounded metal object before handling the Equipment Control Module to avoid potential
damage due to electrical discharge.
Equipment control module should be mounted:
• In a location where the temperature will not exceed
158°F (70°C) or drop below 32°F (0°C).
Do not mount equipment control module:
• On foundation walls or on the HVAC equipment or
ductwork. These locations can cause moisture to
condense on the equipment control module.
Remote temperature sensor should be
mounted:
• On an interior wall, in a frequently occupied
space.
• Approximately 5‘ above floor.
• At least 18” from outside wall.
• Using less than 300’ of wire.
Do not mount remote sensor:
• Behind doors, in corners or other dead air
spaces.
Equipment Control Module Mounting
The Equipment Control Module has the following features to simplify mounting and wiring and provide for a clean
and neat installation.
• In direct sunlight, near lighting fixtures, or
other appliances that give off heat.
• Six (6) mounting holes. One on each corner and two centered top and bottom. Any combination of these holes may
be utilized. Mount the Equipment Control Module using 2 to 4 #8 screws appropriate for the mounting surface
substrate. (See Figure 2.)
• On an outside or unconditioned area wall.
• Wires can be routed through
the top, bottom, sides or back.
1
2
3
T1 T2
• In the flow of a supply register, in stairwells,
or near outside doors.
• On a wall with concealed pipes or ductwork.
• Near 120 VAC lines.
• Nylon wire ties can be used
to secure wires in 10 places.
Installation Steps
1.Select mounting location.
2.Pull from bottom to remove
front cover. (See Figure 1.)
3.Mount base using 2 to 4 #8
screws (field supplied).
2
Figure 1
Figure 2
3
Installation
Installation
Equipment Control Module Wiring
Outdoor temperature sensor (included)
Outdoor temperature can be measured by installing an 8052 sensor to the ODT terminals and enabling the outdoor
sensor in the installer set-up menu. When an outdoor sensor is installed, the features below will be enabled.
In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump:
• When the outdoor temperature is less than the Low Balance Point, the heat pump will be locked out and only
auxiliary heating will be used to provide heating.
• When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and
only the heat pump will be used to provide heating.
Indoor Air Quality functions can use the outdoor temperature sensor to:
• Control humidification setpoint based on outdoor temperature to prevent condensation
• Lock out humidification for temperatures over 60°F or below -30°F.
• Lock out ventilation based on high and/or low outdoor temperatures.
• Display outdoor temperature on thermostat.
Outdoor temperature sensor should
be mounted:
• On side of building out of direct sunlight
(north side recommended).
• Above snow line.
• At least 3’ away from exhaust vents and
condensing lines.
• Using less than 300’ of wire.
Wire specifications:
C – 24VAC common
18-24 gauge thermostat wire
R – 24VAC
Installation notes:
• Ensure power at the HVAC equipment is off.
• Loosen screw terminals, insert stripped wire
and re-tighten.
• Use zip tie to route wiring through the wiring
channels.
1 – Connection to terminal 1 at thermostat
2 – Connection to terminal 2 at thermostat
• Do not route wires along 120 VAC lines.
RC – 24VAC cooling
RH – 24VAC heating
W – First stage heat (conventional)/auxiliary (heat pump)
W2 – Second stage heat (conventional)/ auxiliary (heat
pump)
W3/B – Third stage heat (conventional)/reversing valve
(heat pump)
Y – First stage cooling (conventional)/first stage compressor
(heat pump)
3 – Connection to terminal 3 at thermostat
Y2 – Second stage cooling (conventional)/second stage
compressor (heat pump).
RAT – Return air temperature sensor (optional)
LAT – Leaving air temperature sensor (optional)
Y3/0 – Third stage cooling (conventional)/reversing valve
(heat pump)
ODT – Outdoor temperature sensor (optional)
G – Fan
optional wireless Outdoor temperature sensor
For installations where it is difficult to wire the included 8052 outdoor temperature sensor, a Model 8056 wireless
outdoor temperature module can be used. The Model 8056 module has two radio units, one that is placed on the
equipment control module as shown below, and a second radio that is placed outside. See the Model 8056 Installation
Instructions for detailed directions regarding installation.
Outdoor Sensor
L – System fault indicator (heat pump only) (optional)
CEQ – 24VAC common from heat pump for system fault
indicator (optional)
HUM – Humidifier
DHno & DHcom – Normally open dehumidifier control
DHnc & DHcom – Normally closed dehumidifier control
VENT – Ventilation
EAC – Electronic Air Cleaner
4
5
Installation
HVAC WIRING DIAGRAMS
Return Air Temperature Sensor (Optional)
Conventional Heat/Cool Single Transformer (Use Jumper)
Return air temperature can be measured by attaching an 8052 sensor to the RAT terminals. The return sensor must
be enabled in the installer set-up menu. The return air temperature sensor provides protection in the event that the
equipment control module loses connection with the thermostat. In the event that the thermostat connection is lost,
the equipment control module will use the return air temperature sensor to maintain a temperature greater than 40°F
and less than 100°F.
1.Locate the Aprilaire Model 8052 sensor
in the return trunk.
C
THERMOSTAT
2.Mount the sensor according to the
installation instructions provided with
the sensor.
1
R
2
RC
3
RH
HC
3.Wire the sensor to the equipment
control module RAT terminals.
TRANSFORMER
HP
W
W
1st HEATING
W2
W2
2nd HEATING
W3
B
3rd HEATING
Y
Y
1st COOLING
Y2
Y2
2nd COOLING
Y3
O
3nd COOLING
G
G
FAN
L
C EQ
Leaving Air Temperature Sensor (Optional)
Conventional Heat/Cool Two Transformer (remove Jumper)
Leaving air temperature can be measured by attaching an 8052 sensor to the LAT terminals. The leaving air
temperature sensor measurement is displayed during the installer test for diagnostic purposes.
IMPORTANT
Do not mount the sensor in direct line-of-sight of the heat exchanger, cooling coils, or UV lights as this may cause
the sensor to report false temperature readings.
1. Locate the Aprilaire Model 8052 sensor in the supply trunk, after the heat exchanger and cooling coils. (See
shaded areas in figure below.)
C
THERMOSTAT
2.Mount the sensor according to the installation instructions provided with the sensor.
R
2
RC
3
RH
HC
3.Wire the sensor to the equipment control module LAT terminals.
1
LOCATE
SENSOR
IN SHADED
AREA.
1
R and C can be
powered from the
HVAC equipment
transformer or any
other constantly
powered 24VAC
source.
1
TRANSFORMER
COOLING TRANSFORMER
HEATING TRANSFORMER
HP
W
W
1st HEATING
W2
W2
2nd HEATING
W3
B
3rd HEATING
Y
Y
1st COOLING
Y2
Y2
2nd COOLING
Y3
O
3rd COOLING
G
G
FAN
L
C EQ
6
7
HVAC WIRING DIAGRAMS
Indoor Air Quality WIRING DIAGRAMS
Heat Pump Single Transformer (Use Jumper Wire)
Indoor Air Quality wiring with separate transformers
TRANSFORMER
C
THERMOSTAT
1
R
2
RC
HUM
HEAT PUMP TRANSFORMER
RH
3
DHnc
HC
HP
W
W
1st HEATING
W2
W2
2nd HEATING
W3
B
REVERSING VALVE
Y
Y
1st COMPRESSOR
Y2
Y2
2nd COMPRESSOR
Y3
O
REVERSING VALVE
G
G
L
HUMIDIFIER
DHcom
FAN
FAULT DETECT
DHno
VNT
EAC
DEHUMIDIFIER
NORMALLY
CLOSED DAMPER
PILOT RELAY FOR
120 VAC TO EAC
TRANSFORMER
TRANSFORMER
C EQ
Note: Outputs are 24VAC dry contact. Refer to individual product installation instructions for more details.
Heat Pump Two Transformer (Remove Jumper Wire)
C
THERMOSTAT
1
R
2
RC
RH
3
HC
1
R and C can be
powered from the
HVAC equipment
transformer or any
other constantly
powered 24VAC
source.
HP
Indoor Air Quality wiring with a single transformer
1
TRANSFORMER
HEAT PUMP TRANSFORMER
HEATING TRANSFORMER
W
W
1st HEATING
W2
W2
2nd HEATING
W3
B
REVERSING VALVE
Y
Y
1st COMPRESSOR
Y2
Y2
2nd COMPRESSOR
Y3
O
REVERSING VALVE
G
G
L
FAN
FAULT DETECT
HUM
HUMIDIFIER
TRANSFORMER
DHnc
DHcom
DHno
VNT
EAC
DEHUMIDIFIER
NORMALLY
CLOSED DAMPER
PILOT RELAY FOR
120 VAC TO EAC
C EQ
Note: Outputs are 24VAC dry contact. Refer to individual product installation instructions for more details.
8
9
Power & Reset options
The equipment control module is powered from 24VAC.
The thermostat is powered from the equipment control
module. In the case of power loss the thermostat will
maintain the clock for 24 hours. The thermostat has a
memory backup that saves the thermostat settings in
case of power interruption.
The reset button located under the cover on the front
of the thermostat can be used to reset the thermostat
to factory defaults. The system settings will also be set
to default.
Setup & Testing
EQUIPMENT TYPE SELECTION SWITCH (SW1)
RESET
BUTTON
This Home Comfort Control has the option of being used
in heat pump or heat/cool systems. Switch SW1 located
on the back of the thermostat’s face is used to select this
option. This setting is displayed in the Installer System
Settings under Equipment Type.
SW1
HEAT/COOL
HEAT PUMP
HC
HP
Note: Home Comfort Control reboots within 10 seconds
after switch position is changed.
HC
HP
90-2012
Installer setup menu
Setup & Testing
How to enter the installer setup menu AND SELECT EQUIPMENT TO SETUP:
Removal of Indoor Air Quality Control Buttons
In the Installer Setup, HVAC or Indoor Air Quality setup can be selected. If Indoor Air Quality setup is selected, the
user can then select to set up Air Cleaning, Humidification, Dehumidification or Ventilation.
If any of the Indoor Air Quality control features are not installed, the corresponding button can be removed using the
following procedure:
Step 1: Verify the specific Indoor Air
Quality control feature is not
installed in the installer set-up
(see pages 14-16).
Step 2: From the home screen (see
page 21), press and hold the
Indoor Air Quality button you
wish to remove for 7 seconds.
Indoor Air Quality CONTROL
Buttons
Press [MODE] to set system to OFF.
Press
Press [MENU] to enter main menu.
Press [MENU] to exit.
Press and hold [SETUP] for seven seconds, [INSTALL
SETUP] appears.
Press [NEXT] to select option.
Press [INSTALL SETUP] to enter installer setup menu.
or
to adjust the option.
If IAQ (Indoor Air Quality) was selected, Press
or
to adjust the Outdoor Sensor setting or IAQ (Indoor
Air Quality) option.
Press [NEXT] to select Outdoor Sensor setting or IAQ
(Indoor Air Quality) option.
System Settings can now be changed.
Step 3: The message center will
display REMOVE BUTTON and
the options of NO and YES
(NO will be flashing).
Step 4: Press
or
to select YES.
Step 5: Press [DONE].
Step 6: The button is now removed.
Change System Settings
Note: Once the button is removed it can be brought back by installing the corresponding Indoor Air Quality feature
(see pages 14-16).
SETTING
DESCRIPTION
SETTING
OPTIONS
SETTING
NUMBER
Press [NEXT] or [BACK] to page through the settings.
Press
or
to adjust the setting.
Press [DONE] to save and exit, or [CANCEL] to exit
without saving.
The thermostat will discard changes and exit if nothing
is pressed within 60 seconds.
To reset the installer settings to the default, reset
the thermostat by pressing the [RESET] button for 5
seconds.
10
11
Setup & Testing
Setup & Testing
HVAC INSTALLER SYSTEM SETTINGS TABLE
HVAC INSTALLER SYSTEM SETTINGS TABLE (CONTINUED)
The following table contains the system settings and their details. Default settings are shown in bold. Some settings
are only available dependent upon the value of other settings.
12
System setting
Description
Factory default setting (bold)
and setting range
Factory default setting (bold)
and setting range
21. A
uto Changeover Time
Minimum time between heating and cooling
calls.
4 minutes
1 to 5 minutes
System setting
Description
01. E quipment Type
Equipment type set by SW1.
Heat/Cool
Heat Pump
22. F irst Stage Differential
First stage differential.
1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
02. T emperature Scale
Set the thermostat to Fahrenheit or Celsius
mode.
Fahrenheit
Celsius
23. S econd Stage Differential
Second stage differential.
1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
04. C ontrol Setup
Used to lockout heating or cooling outputs.
Note: Only available if Equipment Type is set to
Heat/Cool.
Heat and Cool
Heat Only
Cool Only
24. T hird Stage Differential
Third stage differential.
1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
25. F ourth Stage Differential
Fourth stage differential.
05. Heat/Cool: Cooling Stages
Heat Pump: Compressor
Stages
Heat/Cool: Number of Cooling Stages.
Heat Pump: Number of Compressor Stages.
One
Two
Three (only available in Heat/Cool)
1°F (0.5°C)
1°F to 9°F (0.5°C to 4.5°C)
26. Away
Disable
Enable
06. Heat/Cool: Heating Stages
Heat Pump: Aux Heat
Stages
Heat/Cool: Number of Heat Stages.
Heat Pump: Number of Auxiliary Heat Stages.
One
Two
Three (only available in Heat/Cool)
07. Heat/Cool: Fan Control
in Heating
Heat Pump: Auxiliary
Equipment Type
Heat/Cool: Determines if the thermostat or
equipment controls the fan in heating.
Heat Pump: Auxiliary Equipment type.
Gas/Oil Heat (equipment controls fan)
Electric Heat (thermostat controls fan)
Enables the Away feature. The Away feature
allows the user to set the thermostat to a
predefined setpoint(s) using a single button
press in the Aprilaire mobile and web apps. The
predefined setpoint(s) is set by the user in the app.
The thermostat will hold the setpoint(s) until Away
is canceled with the app or at the thermostat.
27. Heat Blast
Enables the Heat Blast feature.
Disable
Enable
08. Extended Fan – Heat
Extends fan operation after heat call ends.
Disable
Enable (90 second extension)
28. Blast Offset
Amount of heating when Heat Blast is initiated.
3°F (1.5°C)
3°F to 5°F (1.5°C to 2.5°C)
09. Extended Fan – Cool
Extends fan operation after cool call ends.
Disable
Enable (90 second extension)
37. Stage Rate
2
1 to 5 or “OFF” to ignore accumulated
run time.
10. Temperature Sensor Offset
Field adjustment of controlling temperature
sensor(s).
0° (no offset applied)
-4°F to +4°F (-2°C to +2°C)
Accumulation of equipment run time in
equipment staging determination.
1 = more rapid staging of equipment (comfort).
5 = slower staging of equipment (economy).
38. Progressive Recovery
Enable or disable progressive recovery.
11. Humidity Offset
Field adjustment of internal RH sensor.
0 (no offset applied)
-5% to +5%
Disable
Enable
39. Low Balance Point
12. Auto Changeover
Enable or disable auto changeover mode.
Disable
Enable
Outdoor temperature low balance point.
Note: This option is only available if the outdoor
sensor is enabled.
20°F or -8°C
0°F to 60°F (-18°C to 12°C) or OFF to
ignore LBP
13. Deadband
Auto Changeover mode deadband.
3°F (1.5°C)
2°F to 9°F (1°C to 4.5°C)
40. High Balance Point
Outdoor temperature high balance point.
Note: This option is only available if the outdoor
sensor is enabled.
65°F or 14.5°C
0°F to 80°F (-18°C to 22°C) or OFF to
ignore HBP
14. Remote Sensor
Select if remote sensor is attached, and if it is
attached, if it is the primary control or averaged
with the built-in sensor. If the remote sensor is
the primary control it can be configured to use
the built-in sensor as a back-up sensor.
Not installed
Control no backup
Control with built-in backup
Average with thermostat built-in sensor
41. Program Format
Enables the 7 day program.
7-Day
Non-Prog
42. Reset Service Reminders
No
Yes
15. O
utdoor Sensor
Select if outdoor sensor is attached or not.
Not installed
Installed
17. R eturn Sensor
Select if return sensor is attached or not.
No
Yes
Clears the Change Air Filter and HVAC and
Dehumidifier Service reminders if they are active
and resets the start date to the current date.
Clears the Change Water Panel reminder if it is
active. If the reminder is set to Timed, the timer
will be reset.
43. HVAC Service Reminder
18. C ompressor Min Off Time
Minimum off time for compressor protection.
5 minutes
1 to 5 minutes
The period for displaying the “HVAC Service
Reminder” message.
Off
1 to 12 months or “Off” to disable
44. Constant Backlight
Enable constant, low intensity backlight when
24VAC is present.
Disable
Enable
45. Backlight Intensity
Set the active backlight intensity.
Note: The minimum setting is 40% when
Constant Backlight is enabled.
100 Percent
0 to 100 Percent
19. H
eating Min Off Time
Minimum off time for heating.
2 minutes
1 to 5 minutes
20. E quipment Min On Time
Minimum on time for heating and cooling.
2 minutes
1 to 5 minutes
13
Setup & Testing
Setup & Testing
Dehumidifier System Settings Table
Indoor Air Quality System SettingS Tables
The following tables contain the Indoor Air Quality system settings and their details. Default settings are shown in
bold. Some settings are only present dependent upon the value of other settings.
The use of an outdoor temperature sensor (recommended) enables additional Indoor Air Quality functionality. If the
outdoor temperature sensor was not enabled in the HVAC system settings, HVAC system setting 15, Outdoor Sensor,
will be presented prior to entering the Indoor Air Quality system settings.
System setting
Dehumidifier Control
Description
Selects method of dehumidification. (If set to None, no
other dehumidifier settings will be available.)
Humidity Setpoint Deadband
Select the minimum difference between the humidifier
and dehumidifier setpoints. (Only available if both a
humidifier and dehumidifier are installed. Available in
both set-ups.)
Selects if dehumidification is disabled during a cooling
call.
Select if dehumidification can turn on the fan.
Please refer to the Model 8910W Owner’s Manual for further information about Home Comfort Control features.
Air Cleaning System Settings Table
System setting
Air Cleaner Installed
Change Air Filter Reminder
Description
Selects if an air cleaner is installed. (If set to No, no other
air cleaning settings will be available.)
The period for displaying the “Change Air Filter” message.
Factory default setting (bold)
and setting range
No
Yes
Off
1 to 12 months or “Off” to disable
Humidifier System Settings Table
System setting
Humidifier Installed
Humidity Setpoint
Deadband
Humidifier Mode
Humidifier Operation
Change Water Panel
Reminder
Selects the when the “Change Water Panel” message is
displayed.
Reminder Month (Change
Water Panel Reminder set
to 1 Per Season)
Change Water Panel Reminder set to 1 Per Season:
Determines the month the “Change Water Panel” message
is displayed.
First Reminder Month
(Change Water Panel
Reminder set to 2 Per
Season)
Change Water Panel Reminder set to 2 Per Season:
Determines the first month the “Change Water Panel”
message is displayed.
Second Reminder Start
Month
14
Description
Selects if a humidifier is installed. (If set to No, no other
humidifier settings will be available.)
Select the minimum difference between the humidifier and
dehumidifier setpoints. (Only available if both a humidifier
and dehumidifier are installed. Available in both set-ups.)
Selects auto or manual mode. Auto mode controls humidity
based on the humidity setting and outdoor temperature.
Manual mode controls humidity based on the %RH setpoint.
(Auto mode is only available if Outdoor Sensor is set to Yes.)
Selects when humidification is allowed to occur relative to
heating and fan operation.
Determines the second month the “Change Water Panel”
message is displayed. (Only available when Change Water
Panel Reminder set to 2 Per Season.)
Factory default setting (bold)
and setting range
No
Yes
10 Percent RH
10 to 20 Percent RH
Auto
Manual
Lockout Dehumidifier During
Cooling
Dehumidifier Forces Fan
Dehumidifier Service
Reminder
Dehumidifier Overcooling
Limit
Dehumidify in Vacation
Mode
Vacation Dehumidifier Low
Temp Limit
The period for displaying the “Dehum Service
Reminder” message.
Selects the amount of overcooling that can occur
for dehumidification. (Only available if Dehumidifier
Control is set to Air Conditioner.)
Selects if dehumidification with the air conditioner is
done in Vacation Mode. (Only available if Dehumidifier
Control is set to Air Conditioner.)
Sets the lowest temperature the air conditioner
will cool to, to meet RH setpoint in Vacation Mode.
(Only available if Dehumidifier Control is set to Air
Conditioner.)
Factory default setting (bold)
and setting range
None (no dehumidification installed)
Whole Home
Air Conditioner
10 Percent RH
10 to 20 Percent RH
No
Yes
No
Yes
Off
1 to 12 months or “Off” to disable
3°F (1.5°C)
1°F to 3°F (0.5°C to 1.5°C)
No
Yes
75°F (23.5°C)
70°F to 85°F (21°C to 28.5°C)
Note: Refer to manuals for humidifier, dehumidifier, air cleaner, and ventilation products for recommended
installation and operation.
Ventilation System Settings Table
Heat Only
Heat or Fan
Forces Fan
Off
1 Per Season
2 Per Season
300 Hours
600 Hours
October
November
December
January
February
March
April
May
June
July
August
September
October
November
December
January
February
March
April
May
June
July
August
September
System setting
Description
Factory default setting (bold)
and setting range
Fresh Air Vent Installed
Selects if ventilation is installed.
(If set to No, no other ventilation settings will be available.)
No
Yes
Fresh Air Forces Fan
Selects if ventilation forces the fan on.
No
Yes
Fresh Air Setup
Selects if ventilation is configured through the ASHRAE setup
or Timed. If ASHRAE setup is selected, the hourly ventilation
time will be calculated using the ASHRAE recommendations.
If Timed set-up is selected, the hourly ventilation time will be
determined based on the Fresh Air Time value.
Timed
ASHRAE
Fresh Air Time
Selects how many minutes per hour that ventilation will be
active. (Only available if Fresh Air Setup is set to Timed.)
30 MIN/HR
0 to 60 MIN/HR
High Limit Outdoor
Temp
Selects if ventilation is disabled if the outdoor temperature
exceeds the outdoor high limit. (Only available if Fresh Air Setup
is set to Timed and an outdoor temperature sensor is installed.)
No
Yes
Outdoor High Limit
Sets the high temperature limit for ventilation. (Only available if
High Limit Outdoor Temp is set to Yes.)
100°F (38°C)
90°F to 100°F (32°C to 38°C)
Low Limit Outdoor Temp
Selects if ventilation is disabled if the outdoor temperature
exceeds the outdoor low limit. (Only available if Fresh Air Setup
is set to Timed and an outdoor temperature sensor is installed.)
No
Yes
Outdoor Low Limit
Sets the low temperature limit for ventilation. (Only available if
Low Limit Outdoor Temp is set to Yes.)
10°F (-12°C)
-10°F to 30°F (-24°C to 0°C)
High Limit Indoor RH
Selects if ventilation is disabled if the indoor RH exceeds the
indoor RH limit. (Only available if Fresh Air Setup is set to Timed.)
No
Yes
Indoor RH Limit
Sets the high indoor RH limit for ventilation. (Only available if
High Limit Indoor RH is set to Yes.)
60%
50% to 70%
15
Setup & Testing
Setup & Testing
Ventilation System Settings Table (continued)
System test menu
Factory default setting (bold)
and setting range
System setting
Description
Number of Bedrooms
3 Bedrooms
Selects the number of bedrooms to be used for the ASHRAE
calculation. (Only available if Fresh Air Setup is set to ASHRAE.) 1 to 6 Bedrooms
Number of Occupants
4 Occupants
Selects the number of occupants to be used for the ASHRAE
calculation. (Only available if Fresh Air Setup is set to ASHRAE.) 1 to 10 Occupants
2500 SQ FT
1000 to 5000 SQ FT
Home Size
Selects the home size to be used for the ASHRAE calculation.
(Only available if Fresh Air Setup is set to ASHRAE.)
Fresh Air CFM
60 CFM
Selects the ventilation CFM to be used for the ASHRAE
calculation. (Only available if Fresh Air Setup is set to ASHRAE.) 30 to 200 CFM
Select Climate
Selects the climate to be used for the ASHRAE calculation.
(Only available if Fresh Air Setup is set to ASHRAE.) To
determine what region you are in, refer to the map below.
Normal
Very Hot/Humid
Very Cold
ASHRAE Cycle Time
Displays the Fresh Air Time calculated by the ASHRAE
standard. (Only displayed if Fresh Air Setup is set to ASHRAE.)
Minutes/Hour
Fresh Air Service
Reminder
The period for displaying the “Fresh Air Service Reminder”
message.
Off
1 to 12 months or “Off” to disable
The system test menu is used to test a system after installation. The outputs of the Home Comfort Control can be
manually activated to test their function. The instructions below show how to enter the test mode and turn outputs
on and off.
How to enter the system test menu:
SYSTEM TEST STEPS
Press [MODE] to set system to off.
Heating equipment test
Cooling equipment test
Fan equipment test
Humidification equipment test
Dehumidification equipment test
Ventilation equipment test
Air Cleaning equipment test
Press and hold [FAN] and [MODE] for three seconds
to enter system test mode.
The first screen of the installer test displays the
equipment configuration.
Press [NEXT] to enter the first installation test or
[CANCEL] to exit.
Humidity
Note: In ASHRAE set-up temperature and humidity limits are disabled.
Temperature
CLIMATE MAP FOR ASHRAE FRESH AIR SETUP
Outdoor Temperature Equipment Configuration
VERY COLD
Each equipment test will begin with the selection of turning on the output or stage as shown below.
Press
or
to change the selection.
Press [NEXT] to accept the selection and proceed to the next step.
If YES is selected, the Home Comfort Control will test the corresponding output. If NO is selected, the Home
Comfort Control will proceed to the next step.
VERY HOT/HUMID
Humidity
Temperature
Equipment Test Selection
Outdoor Temperature Test to be run
16
17
Setup & Testing
Setup & Testing
System test menu (CONTINUED)
System test TABLES (CONTINUED)
While the equipment test is active the corresponding test information will be shown.
Heat Pump Heating Equipment Test (Electric Heat)
Press [NEXT] to accept the selection and proceed to the next test selection.
Compressor
Stages
Aux
Stages
1
1
1st Stage Test
1
1
2nd Stage Test
2
1
1st Stage Test
ON
ON
2
1
2nd Stage Test
ON
ON
ON
ON
2
1
3rd Stage Test
ON
ON
ON
ON
ON
1
2
1st Stage Test
ON
ON
ON
1
2
2nd Stage Test
ON
ON
ON
ON
1
2
3rd Stage Test
ON
ON
ON
ON
2
2
1st Stage Test
ON
ON
2
2
2nd Stage Test
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
W
W2
ON
B
Y
ON
ON
Y2
O
ON
G
ON
ON
ON
Humidity
Temperature
Outdoor Temperature Equipment Test Selection
ON
Output StatuS
Test that
is active
Leaving Air Temperature
2
2
3rd Stage Test
ON
2
2
4th Stage Test
ON
Compressor
Stages
Aux
Stages
1
1
1st Stage Test
1
1
2nd Stage Test
ON
ON
ON
ON
System test TABLES
Heat Pump Heating Equipment Test (Gas Heat)
Heat / Cool Heating Equipment Test
Heat Type
18
W
W2
Gas
1st Stage Test
ON
Gas
2nd Stage Test
ON
ON
Gas
3rd Stage Test
ON
ON
Electric
1st Stage Test
ON
Electric
2nd Stage Test
ON
ON
Electric
3rd Stage Test
ON
ON
W3
Y
Y2
Y3
G
W
W2
ON
B
Y
ON
ON
Y2
O
G
ON
ON
ON
ON
2
1
1st Stage Test
ON
ON
ON
2
1
2nd Stage Test
ON
ON
ON
2
1
3rd Stage Test
1
2
1st Stage Test
1
2
1
2
2
2
1st Stage Test
ON
ON
2
2
2nd Stage Test
ON
ON
ON
ON
2nd Stage Test
ON
ON
3rd Stage Test
ON
ON
ON
ON
ON
ON
2
2
3rd Stage Test
ON
2
2
4th Stage Test
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
19
Setup & Testing
Quick Reference to controls & Display
System test TABLES (CONTINUED)
Home Screen
ROOM TEMPERATURE
Heat / Cool Cooling Equipment Test
W
W2
W3
Y
Y2
1st Stage Test
ON
2nd Stage Test
ON
ON
3rd Stage Test
ON
ON
Y3
G
ON
ON
ON
ON
Heat Pump Cooling Equipment Test
W
W2
B
Y
1st Stage Test
ON
2nd Stage Test
ON
Y2
ON
O
G
ON
ON
ON
ON
Fan Equipment Test
W
W2
W3/B
Y
Y2
Y3/O
G
ON
Current DAY
OUTDOOR TEMPERATURE
ROOM RELATIVE HUMIDITY
TEMPERATURE SETTING
FAN MODE
SETTING
Air Cleaning Button (Enters EVENT-BASED™ Air
Cleaning Control Screen)
FAN MODE
BUTTON
Humidity Control Button (Enters Humidity Control Screen)
SYSTEM MODE
SETTING
Fresh Air Button (Enters Ventilation Control Screen)
SYSTEM MODE
BUTTON
IndicatorS show through housing
Temperature ADJUSTMENT
HEAT PUMP ONLY
Emergency heat or AUXILIARY HEAT (RED)
System FAULT (YELLOW)
EQUIPMENT
STATUS
MAINTENANCE REMINDER
(YELLOW FLASHING)
MESSAGE
CENTER
HOLD BUTTON
(SETS OR CLEARS HOLD)
(SCROLLING TEXT)
Humidification Equipment Test
HUM
DHNO/DHCOM
VENT
EAC
ON
G
CURRENT TIME & DATE
ON
Wi-Fi SIGNAL STRENGTH
HEAT BLAST BUTTON
MAIN MENU BUTTON
Note: Backlight is activated with first button press and automatically turns off.
Dehumidification Equipment Test
HUM
DHNO/DHCOM
VENT
EAC
ON
G
ON
MAIN MENU
Ventilation Equipment Test
HUM
DHNO/DHCOM
VENT
EAC
ON
G
ON
Ventilation Equipment Test
HUM
DHNO/DHCOM
VENT
EAC
G
ON
ON
SET VACATION HOLD
(HOLD–TO TIME AND DATE)
SET CURRENT
TIME AND DATE
SET SCHEDULE
BUTTON
CLEAN SCREEN
(LOCKOUT TOUCH
SCREEN FOR 30
SECONDS)
DONE BUTTON
(EXIT MENU)
USER SYSTEM SETTINGS
20
21
Quick Reference to controls & Display
Troubleshooting
Equipment Control Module LEDs
Heat/cool both on at same time
POWER/STATUS – On solid during normal operation. Flashes
when connection to the thermostat is lost and at power-up while
the thermostat connection is being established.
HEATING – On when heating outputs are active.
COOLING – On when cooling outputs are active.
“HEATING” is not displayed
• Check SW1 (Equipment Type), to make sure it is set
to match the installed heating/cooling equipment.
• Check Installer System Setting 04 (Control Setup) is
set correctly.
• Check to make sure heating and cooling wires are
not shorted together.
• Change the System Mode to Heat, and set
the temperature level above the current room
temperature.
Heating equipment is running in
cool mode
FAN – On when fan output is active.
HUMIDIFIER – On when humidifier output is active.
• Check SW1 (Equipment Type), to make sure it is set
to match the installed heating/cooling equipment
(see page 11).
DEHUMIDIFIER – On when dehumidifier output is active.
VENTILATION – On when ventilation output is active.
AIR CLEANING – On when air cleaner output is active.
“COOLING” is not displayed
• Check Installer System Setting 04 (Control Setup) is
set correctly.
• Change the System Mode to Cool, and set
the temperature level below the current room
temperature.
Error Codes
If the thermostat enters an error mode, all outputs are turned off. The thermostat attempts to recover every 10 minutes.
Error code
Message
01
Troubleshooting
Display is blank
If Power LED not illuminated at the equipment control
module check the following.
• Check circuit breaker and reset if necessary.
• Make sure power switch at heating & cooling
system is on.
• Make sure furnace door is closed securely.
Heating system does not respond
(“HEATING” appears on screen)
• Check for 24VAC at the equipment on the secondary
side of the transformer between power and
common. If voltage is not present, check the heating
equipment to find the cause of the problem.
• Check for 24VAC between the heat terminal (W)
and the transformer common. If 24VAC is present,
the Home Comfort Control is functional. Check the
heating equipment to find the cause of the problem.
• Check for loose or broken wires between the Home
Comfort Control and the heating equipment.
• Check for 24VAC at the equipment on the secondary
side of the transformer between power and
common. If voltage is not present, check the cooling
equipment to find the cause of the problem
• Check for 24VAC between the cooling terminal (Y)
and the transformer common. If 24VAC is present,
the Home Comfort Control is functional. Check the
cooling system to find the cause of the problem.
• Check for loose or broken wires between the Home
Comfort Control and the cooling equipment.
Fan does not turn on in a call for heat
• Check System Setting 07 (Fan Control), to make sure
the fan control is properly set to match the type of
system.
Heat pump issues cool air in heat mode,
or warm air in cool mode
• Check wiring at the terminal block to confirm the
reversing valve is connected to the proper terminal.
O is active in cooling and B is active in heating.
22
Open temperature sensor circuit
“SENSOR ERROR”
02
Cooling system does not respond
(“COOLING” appears on screen)
Error Description
Shorted temperature sensor circuit
03
“EEPROM ERROR”
Error in permanent memory
05
“LOST SYSTEM CONNECTION”
Thermostat lost connection to equipment interface module
06
07
Open remote temperature sensor circuit
“REMOTE SENSOR ERROR”
Shorted remote temperature sensor circuit
HOME COMFORT CONTROL™ Features
• Remote access and control over Wi-Fi.
• 7 day programmability.
• Indoor air quality control.
– Humidification automatic or manual control.
– Dehumidification.
– Event-Based™ air cleaning.
– Ventilation with temperature and humidity limits.
• Displays room temperature, room humidity,
temperature setting, and optional outdoor temperature.
• Temperature control.
• Heat Blast® raises the room temperature 3°F to 5°F.
• Support for optional wireless outdoor temperature
sensor.
• Large touch screen with adjustable backlight –
constant backlight option available.
• Message center provides feedback and instructions.
• Air filter, humidifier, dehumidifier, and HVAC service
reminders.
• Programmable fan control with fan circulation mode.
• Easy to use temperature control can override program
schedule at any time.
• Progressive recovery ensures proper temperature at
the start of a program event.
• Built in compressor protection prevents damage to
your equipment.
• System test mode.
23
Specifications
Environment
Temperature (Shipping)
-30° to 150°F (-34° to 65°C)
Temperature Thermostat (Operating)
32° to 120°F (0° to 48°C)
Temperature Equipment Control Module (Operating)
32° to 158°F (0° to 70°C)
Relative humidity
Operating: 5% to 90% R.H. (non-condensing)
Electrical
Operating voltage
24VAC (18 – 30VAC)
Current
Maximum: 2.5A (total), 1.0A (single output)
Maximum surge current: 5A
Control
Outdoor, Remote, Leaving and Return temperature sensor
Maximum distance: 300 feet
Room temperature measurement
Display range: 32° to 99°F (0° to 40°C)
Return and Leaving temperature measurement
Display range: -40° to 160°F (-40° to 71°C)
Outdoor temperature measurement
Display range: -40° to 130°F (-40° to 55°C)
Setpoint temperature range
Heat: 40° to 90°F (4° to 32°C)
Cool: 50° to 99°F (10° to 37°C)
Setpoint humidity range
Humidification: 10% to 50% R.H.
Dehumidification: 40% to 90% R.H.
P.O. Box 1467 • Madison, WI 53701-1467 • Phone: 800/334-6011 • Fax: 608/257-4357
www.aprilairepartners.com
61001131 4.15
B2206504B
24
U.S. Patent Numbers 8,146,376, 8,596,078 and other patents pending.
© 2015 Aprilaire – A division of Research Products Corporation

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement