Danfoss | application A214 | User manual | ECL Comfort 310 controller, Remote Control Units ECA 30 / 31
Add to my manuals40 Pages
advertisement
Data sheet
ECL Comfort 310 controller,
Remote Control Units ECA 30 / 31 and Application keys
Designed in Denmar k
Description
ECL Comfort 310 controller series
The ECL Comfort 310 is an electronic weather compensated temperature controller in the ECL
Comfort controller family for use in district heating, central heating and cooling systems.
Energy savings can be achieved by correct control of the flow temperature in heating and cooling systems. Up to 4 circuits can be controlled.
ECL Comfort 310 is designed for comfortable temperatures, optimum energy consumption, easy installation by means of the ECL Application
Key (Plug-and-Play) and user friendly operation.
The weather compensation function in the ECL
Comfort controllers measures the outdoor temperature and controls the flow temperature to the heating system accordingly. The weather compensated heating system increases the comfort level and saves energy.
The ECL Comfort 310 controller is configured with a selected application by means of an ECL
Application Key.
Improved energy savings are facilitated by weather compensation, adjustment of temperature according to schedule, optimization as well as limitation of return temperature, flow and power.
The ECL Comfort 310 is easily operated by means of a dial (multi-functional knob) or a Remote
Control Unit (RCU). The dial and the backlighted display guide the user through the text menus in the selected language.
The ECL Comfort 310 controller has electronic output for motorized valve control, relay output for circulation pump / changeover valve control among others, as well as alarm output.
The web based ECL Portal communicates with the
ECL Comfort 310 for an effective and easy-to-use turnkey SCADA (Supervisory Control And Data
Acquisition) tool for all users, service personnel and at commissioning. Service level can be increased and/or service costs reduced. The heating and/or cooling installation is made accessible from virtually anywhere at any time via laptops or Smartphones which increases service level and reduces response time to alarms.
The ECL Tool software for ECL Comfort 310 offers possibilities for an alternative remote control in relation to ECL Portal and OPC server software.
6 Pt 1000 temperature sensors can be connected.
In addition, 4 inputs are configured when uploading the application. The configuration can be Pt 1000 temperature sensor input, analogue input (0 – 10 V) or digital input.
Depending on application, the internal extension module ECA 32 (inserted into the controllers base part) can give additional input and output signals.
VD.KT.X3.02 © Danfoss 04/2015 1
DEN-SMT/DK
Data sheet
Description (continued)
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
The enclosure is designed for mounting on wall and DIN rail. A variant ECL Comfort 310B (without display and dial) is available. It can be used for mounting inside a panel and is operated by means of the RCU ECA 30 / 31 which can be placed in front of the panel.
The ECL Comfort 310 can work as a stand-alone controller and communicate with up to two RCUs and an extension module ECA 32 with additional inputs / outputs.
The ECL Comfort 310 can also work with up to 2 x
RCUs, ECA 32 and other ECL Comfort 210 / 310 controllers via the ECL 485 communication bus.
Ethernet connection is integrated in the controller.
Furthermore, Modbus communication to SCADA systems (Supervisory Control and Data Acquisition) and M-bus communication to heat meters are integrated.
Remote Control Unit (RCU):
The RCUs ECA 30 and ECA 31 are used for room temperature control and override of the ECL
Comfort 310. The display has backlight. The RCUs are connected to the ECL Comfort controllers by means of 2 × twisted pair cable for communication and power supply (ECL 485 communication bus).
The ECA 30 / 31 has a built-in room temperature sensor. An external room temperature sensor can be connected substituting the built-in temperature sensor.
Furthermore, the ECA 31 has a built-in relative humidity sensor and the signal is used in relevant applications. It is possible to connect up to 2 RCUs on the ECL 485 communication bus. One RCU can monitor max. 10 ECL Comfort controllers (master/ slave system).
ECL Application Key and applications:
Different ECL Application Keys make it easy for the
ECL Comfort 310 hardware to run different applications. The ECL Comfort 310 controller is loaded with the desired application by means of the ECL Application Key, which contains information about applications (basic application sketches are shown in the display), languages and factory settings.
The ECL Application Keys, series A2xx can be used in ECL Comfort 210 and ECL Comfort 310. Most of the A2xx application keys give extended functionalities when used in ECL Comfort 310, such as additional temperature sensors and M-bus communication.
The ECL Application Keys, series 3xx can be used in ECL Comfort 310 only.
The application parameters are stored in the controller and are not affected by power break.
The relevant ECL Application Keys for the ECL
Comfort 210 / 310 controller can be found in the ordering section.
2 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Key overview, sub-circuits, combinations
A333
A361
A367
A368
A376
A377
ECL Comfort 210 ECL Comfort 310
Key
A214 A214.1, A214.2, A214.3, A214.4, A214.5, A214.6 A214.1, A214.2, A214.3, A214.4, A214.5, A214.6
A314.1, A314.2, A314.3, A314.4, A314.5, A314.6,
A314.7
A217 A217.1, A217.2, A217.3
A230 A230.1, A230.2
A231 A231.1, A231.2
A232 A232.1
A237 A237.1, A237.2
A247 A247.1, A247.2
A260 A260.1, A260.2
A266 A266.1, A266.2, A266.9
A217.1, A217.2, A217.3
A317.1, A317.2
A230.1, A230.2
A231.1, A231.2
A331.1, A331.2
A232.1
A332.1, A332.2
A237.1, A237.2
A337.1, A337.2
A247.1, A247.2
A347.1, A347.2
A260.1, A260.2
A266.1, A266.2, A266.9
A275 A275.1, A275.2, A275.3
A275.1, A275.2, A275.3
A375.1, A375.2, A375.3
A333.1, A333.2, A333.3
A361.1, A361.2
A367.1, A367.2
A368.1, A368.2, A368.3, A368.4
A376.1, A376.2, A376.3, A376.9
A377.1, A377.2
This is an overview of currently available application keys for the ECL Comfort controllers.
Not all keys are for sale in your country. Please contact your local Danfoss sales company.
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 3
Data sheet
Application examples
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
All mentioned components (S = temperature sensor, P = pump, M = Motorized control valve and so on) are wired to the ECL Comfort 210 / 310.
All applications from ECL Comfort 210 can run in ECL Comfort 310. Extra functions and communication facilities are enabled.
A214.1, ex. a:
Cooling application, duct temperature based on room temperature
S1 ECL 210 / 310
A1
M2
P2
X3
S5
F1 S3
S4
S8
A214.2, ex. a:
Heating application, heating temperature based on duct temperature
S1
ECL 210 / 310
A1
M1
S3
X3
S5
P2
S6 F1 S4
S7
S8
4 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A214.3, ex. a:
Heating application, duct temperature based on room temperature
S1 ECL 210 / 310
A1
M1
P2
X3
S5
S6 F1 S3
S7
S8
S4
A214.5, ex. a:
Heating / cooling application, duct temperature based on room temperature
S1 ECL 210 / 310
A1
M1 M2
P2
X3
S5
S6
S7
F1 S3
S8
S4
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 5
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A314.1, ex. a:
Ventilation system with heating, passive cooling (outside air) and constant duct temperature control.
Analogue controlled passive cooling stage (M2).
S1
P2 M2
A
ECL 310
+ ECA 32
A1
M1
S3
X3
S5
S6 F1
S4
S7
S8
S2
A314.1, ex. b:
Ventilation system with heating, cooling and duct temperature control.
Analogue controlled cooling stage (M2).
S1
P2
S3
X3
S6
ECL 310
+ ECA 32
A1
M1 M2
A
S5
S2
F1
S4
S7
S8
6 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A314.2, ex. b:
Ventilation system with heating, cooling and room temperature control. Analogue controlled cooling stage (M2).
S1
P2
X3
S6
S5
ECL 310
+ ECA 32
A1
M1 M2
A
S2
F1
S3
S7
S8
S4
A314.3, ex. a:
Ventilation system with heating and room temperature control. Speed controlled fan.
S1 ECL 310
+ ECA 32
A1
S2
M1
S10
X3
S5
P2
S6 F1 / V1 S3
S7
S8
S4
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 7
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A217.1, ex. a:
DHW tank charging application
8
A217.1, ex. b:
DHW tank heating application
S1
S2
M1
S5
ECL 210 / 310
A1
S3
P1
A217.2, ex. a:
DHW tank charging with preheating circuit
S1 ECL 210 / 310
A1
S2 S3
M1
S5
P1
S4
B
P2
S6
A
S8 P3
S6
S8
P3
VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A217.3, ex. a:
DHW heating
A217.3, ex. c:
DHW heating on demand (flow switch). With or without circulation
A230.1, ex. a:
Indirectly connected heating system. Wind compensation as option
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 9
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A230.2, ex. a:
Indirectly connected cooling system (district cooling)
10
A231.2:
Indirectly connected heating system with 2-pump control and refill water function
S1 ECL 210
R4
P S7
S2
S3
P1
P2
M1 S5 S8
P3
V1
A331.2, ex. a:
Heating system with two-pump control and refill water function.
Supply temperature dependent flow temperature control.
S1
S2
M1
S10
S5
ECL 310
R6
S9
P S7
S3
P1
P2
S8
V1
P3
P5
VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A232.1, ex. a:
Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature.
A332.1, ex. a:
Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature. Optional return temperature limitation.
A332.2, ex. a:
Separated control of flow temperatures for heating / cooling in relation to outdoor, room and dew point temperature. Optional return temperature limitations.
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 11
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A237.1, ex. a:
Indirectly connected heating and DHW system
S1 ECL 210 / (310)
R4 / (R6)
S2
S3
P1
M1
S5
P2
S6
S8
P3
A237.2, ex. a:
Indirectly connected heating and DHW charging system
A247.1, ex. a:
Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority
DEN-SMT/DK
(S7*) = optional in ECL Comfort 310
VD.KT.X3.02 © Danfoss 04/2015 12
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A247.2, ex. a:
Indirectly connected heating and DHW tank charging system with preheating circuit.
Parallel mode or DHW priority
(S7*) = optional in ECL Comfort 310
A347.1, ex. a:
Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority
S1 ECL 310 S7
A1
S3
P1
M2
S5
S4
M1
S2
S6
A
S8 P3
B
P2
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 13
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A347.2, ex. a:
Indirectly connected heating and DHW tank charging system with preheating circuit.
Parallel mode or DHW priority
A260.1, ex. a:
Two heating systems
14 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A260.1, ex. d:
Two heating systems. Circuit 2 is a sub-circuit of circuit 1.
A266.1, ex. a:
Heating and direct DHW heating system. Parallel mode or DHW priority.
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 15
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A266.2:
Heating and direct DHW heating system. Parallel mode or DHW priority. DHW heating on demand
(flow switch)
A275.1, ex. a:
Heating system with 1-stage boiler
S1 ECL 210 / (310)
A1
S3
P1
*
S5
B1
S7
1
16 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
DEN-SMT/DK
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A275.2, ex. a:
Heating system with 1-stage boiler and DHW tank
S1 ECL 210 / 310
Danfoss 87H2165.
A1
S3
P1
*
S7
1
S5
B1
S6
2
P3
A275.3, ex. a:
Heating system with 1-stage boiler, mixing circuit and DHW tank
S1 ECL 210 / (310)
M2
S4
S2
P4
S3
P1
*
S5
B1
S8
S7
②
①
S6
③
P3
VD.KT.X3.02 © Danfoss 04/2015 17
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A375.1, ex. a:
Up to 8 x boiler ON / OFF control for a heating circuit
S1 ECL 310
+ ECA 32
A1
S3
S7
B1 B8
S5
P1
*
A375.2, ex. a:
Up to 8 x boiler ON / OFF control for a heating circuit and a DHW circuit. Optional DHW priority.
S1 ECL 310
+ ECA 32
A1
S3
①
B1 B8
S5
P1
*
S7
①
S6
P4
②
P3
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 18
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A375.3, ex. a:
Up to 8 x boiler ON / OFF control for a direct heating circuit (1), a mixing circuit (2) and a DHW circuit
(3). Optional DHW priority.
S1
S3
ECL 310
A1
+ ECA 32
M2
S4
S2
P4
S8
②
S7
B1 B8 P1
*
①
S5
S6
③
P3
Burner control overview:
A275.1
A275.2
A275.3
A375.1
A375.2
A375.3
R2
1
1
1
ECL 210 ECL 310 ECA 32
1
1
1
1
R2
1
1
R3
2
R4 R5 Triac 5 Triac 6 R7 R8 R9 R10
3 4
2
2
7
7
8
8
5
3
3
6
4
4
7
5
5
8
6
6
R2-R10 = relay nos. in ECL / ECA 32
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 19
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A333.1, ex. a:
Heating system with control of 1 or 2 circulation pumps. Refill water function with control of 1 or 2 pumps. Pressure measurements in the system.
A333.2, ex. a:
Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank.
Pressure measurements in the system.
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 20
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A333.3, ex. a:
Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Control valve M1 is 0 -
10 V controlled. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank. Pressure measurements in the system.
A361.2, ex. a:
2 x heating systems with two-pump control and refill water function. Supply temperature dependent flow temperature control.
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 21
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A367.1, ex. a:
System with 2 heating circuits and secondarily connected DHW tank with internal heat exchanger.
Optional DHW priority.
S1 ECL 310
R6
S4
S9
P5
M2
S2
S7
P1
S3
M1
S5
S6
S8
P3
P2
A367.2, ex. a:
System with 2 heating circuits and secondarily connected DHW tank charging system.
Optional DHW priority.
S1 ECL 310
R6
S4
(S7)
P5
M2
S2
(S7)
S3
P1
S9
M1
S5
S6
S8 P3
P2 P4
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 22
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A368.2, ex. a:
Heating system with two-pump control and refill water function. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps.
A368.4, ex. a:
Heating system with two-pump control and refill water function with 1 or 2 pumps. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps. Pressure measurements in the systems.
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 23
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A376.1, ex. a:
Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority.
S1 ECL 310
A1
S3
P2
S2
1
M2
S5
S9
P3
S7
2
M3
S10
S4
M1
S6
3
P1
A376.2, ex. a:
Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority.
DHW heating on demand (flow switch).
S1 ECL 310
A1
S3
P2
(S2)
1
M2
S5
S9
P3
(S2)
2
M3
S10
S4 S7
M1
S6
3
S8
P1
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 24
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A376.3, ex. a:
Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Control valves M1, M2 and M3 are 0 - 10 V controlled.
S1 ECL 310
+ ECA 32
A1
S3
P2
S2
1
A
M2
S5
S9
P3
S7
2
A
M3
S10
S4
A
M1
S6
3
P1
A376.9, ex. a:
Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Pressure measurements and temperature monitoring in the system.
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 25
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A377.1, ex. a:
Two heating circuits and one DHW tank charging system. Parallel mode or DHW priority.
S1 ECL 310
A1
S4
P5
M3
S2
S3
P2
M2
S5
S7 S9
M1
P1
S10
B
P4
S6
A
S8 P3
A377.2, ex. a:
Two heating circuits and one DHW tank charging system. Control of the DHW heating temperature.
Parallel mode or DHW priority.
S1
S4
P5
ECL 310
A1
M3
S2
P2
S3
M1
S9 S10
M2
S5
S6
A
S8 P3
P1
B
P4
26 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
Ordering
DEN-SMT/DK
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Controller, base parts and accessories:
Type
ECL Comfort 310
ECL Comfort 310
ECL Comfort 310B
ECL Comfort 310 base part
Designation
Universal hardware - 230 V a.c.
Base part is not included. Mounting guide (no text) is included.
Universal hardware - 24 V a.c.
Base part is not included. Mounting guide (no text) is included.
Universal hardware - 230 V a.c.
Without display and dial. Requires a Remote Control Unit.
Base part is not included. Mounting guide (no text) is included.
For mounting on wall or DIN rail (35 mm). ECL Comfort 210 can be mounted in an ECL Comfort 310 base part (for future upgrade). Mounting guide (no text) and cable inlet accessories is included.
Code no.
087H3040
087H3044
087H3050
087H3230
Remote Control Units and accessories
Type
ECA 30
ECA 31
ECA 30 / 31 frame kit for mounting in panel front
ECA 32
Designation
Remote Control Unit with an integrated room temperature sensor and possibility for connecting an external Pt 1000 room temperature sensor.
Base part for mounting on wall included. Mounting guide (no text) is included.
Remote Control Unit with an integrated room temperature sensor and a humidity sensor. Possibility for connecting an external Pt 1000 room temperature sensor. Used for dedicated applications. Base part for mounting on wall included. Mounting guide (no text) is included.
For mounting in a panel cut-out.
Format 144 × 96 mm, actual cut-out 139 × 93 mm. Mounting guide (no text) is included.
Internal extension module with additional inputs and outputs. To be placed in the ECL Comfort 310 base part. See separate data sheet.
Code no.
087H3200
087H3201
087H3236
087H3202
Accessories:
Type
ECA 99
Designation
230 V a.c. to 24 V a.c. transformer (35 VA)
Code no.
087B1156
ECL Application Keys
Type
A214
A217
A230
A231
A232
Application type description Controller output signals
• Temperature control (heating / cooling) of ventilation systems. Duct / room temperature control. Return temperature limitation. Flow / power limitation. Fire and frost protection as well as alarm function.
• The A214 application key contains applications related to ECL Comfort 310 for increased functionalities (control of rotating heat-exchanger).
2 x 3-point, 2 x 2-point
• Advanced temperature control of DHW (Domestic Hot Water) circuit with/ without storage charging system. Circulation pump control. Return temperature limitation. Frost protection and alarm function.
• The A217 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).
1 x 3-point, 3 x 2-point
• (A230.1) Weather compensated flow temperature control of heating systems. Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Wind compensation, frost protection and alarm function.
• (A230.2) Flow temperature control of cooling systems. Compensation for outdoor and room temperatures. Return temperature limitation.
• The A230 application key works in ECL Comfort 310 for increased functionalities (M-bus).
1 x 3-point, 2 x 2-point
1 x 3-point, 3 x 2-point • Weather compensated flow temperature control of heating systems.
2-pump control for circulation and refill water function. Sliding return temperature limitation. Frost protection and alarm function.
• The A231 application key contains applications related to ECL Comfort 310 for increased functionalities (2 pumps for refill water and M-bus).
• Weather compensated flow temperature control of heating / cooling circuit(s). Automatic change-over between heating and cooling. Circulation pump control. Dew point (cooling mode only) and surface temperature compensation.
• The A232 application key contains applications related to ECL Comfort 310 for increased functionalities (return temperature limitation and separated control of heating and cooling circuits).
1 x 3-point, 3 x 2-point
Code no.
087H3811
087H3807
087H3802
087H3805
087H3812
VD.KT.X3.02 © Danfoss 04/2015 27
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys (continued):
Type
A237
A247
A260
A266
A275
A333
A361
A367
A368
Application type description
• Weather compensated flow temperature control of heating systems.
Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger. Optional ON / OFF control of the DHW circuit in connection with primarily connected storage tank with internal heat exchanger. DHW circulation pump control. Frost protection and alarm function.
• The A237 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).
• Weather compensated flow temperature control of heating systems.
Circulation pump control. Sliding return temperature limitation. Flow / power limitation. Temperature control of DHW circuit with storage tank charging system. DHW circulation pump control through the storage tank or the heat-exchanger. Frost protection and alarm function.
• The A247 application key contains applications related to ECL Comfort 310 for increased functionalities (room temperature sensor and M-bus).
• Weather compensated flow temperature control of heating systems.
Circulation pump control, room temperature control and sliding return temperature limitation for two independent heating circuits. Flow / power limitation, frost protection and alarm function.
• The A260 application key works in ECL Comfort 310 for increased functionalities (M-bus).
Controller output signals
1 x 3-point, 3 x 2-point
2 x 3-point, 3 x 2-point
2 x 3-point, 2 x 2-point
Code no.
087H3806
087H3808
087H3801
• Weather compensated flow temperature control of heating systems.
Circulation pump control, room temperature control and sliding return temperature limitation.
• Temperature control of DHW circuit with DHW circulation. Return temperature limitation, sliding DHW priority, frost protection and alarm function. Optional control of DHW heating based on DHW demand.
• The A266 application key works in ECL Comfort 310 for increased functionalities (M-bus).
2 x 3-point, 2 x 2-point
• Weather compensated flow temperature control of 1-stage boiler based heating systems. One direct heating circuit and one mixing circuit.
Circulation pumps control, room temperature control and sliding return temperature limitation.
• Temperature control of DHW storage tank with internal heat exchanger.
Frost protection and alarm function.
• The A275 application key contains applications related to ECL Comfort 310 for increased functionalities (multiple boiler stages).
1 x 3-point, 4 x 2-point
1 x 3-point, 7 x 2-point* or
1 x 0 - 10 V control*, 7 x
2-point*
• Weather compensated flow temperature control of a heating system.
ON / OFF and speed control of 1 or 2 circulation pumps and sliding return
temperature limitation. Flow / power limitation. Frost protection and alarm
function. ON / OFF and speed control of 1 or 2 refill water pumps.
Refill water storage control. Pressure release function. Pressure and
temperature monitoring. Frost protection and alarm function.
• Weather compensated flow temperature control of 2 heating circuits.
Supply temperature dependent flow temperature control. 2-pump control
for circulation. Sliding return temperature limitation. Flow / power
limitaion. Refill water function. Frost protection and alarm function.
• Weather compensated flow temperature control of 2 heating circuits.
Circulation pump control. Room temperature control and sliding return
temperature limitation. Flow / power limitation.
• Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger.
Optional ON / OFF control of the DHW circuit in connection with primarily connected storage tank with internal heat exchanger.
DHW circulation pump control. Frost protection and alarm function.
2 x 3-point, 7 x 2-point*
2 x 3-point, 5 x 2-point
087H3800
087H3814
087H3818
087H3804
087H3813
• Weather compensated flow temperature control of a heating circuit.
Supply temperature dependent flow temperature control. 2-pump control
for circulation. Sliding return temperature limitation. Flow / power limitation
Flow / power limitation and refill water function.
• Temperature control of a DHW circuit with DHW circulation, return
temperature limitation and sliding DHW priority. Frost protection and
alarm function.
2 x 3-point, 5 x 2-point 087H3803
* ECA 32 module needed
28 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
Typical ordering, types:
Reference, additional products / software:
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Application Keys (continued):
Type
A376
A377
Application type description
• Weather compensated flow temperature control of 2 heating circuits.
Circulation pump control. Room temperature control and sliding return
temperature limitation. Flow / power limitation.
• Temperature control of a DHW circuit with DHW circulation, return temperature limitation and sliding DHW priority. Optional control of DHW heating based on DHW demand. Frost protection and alarm function.
• Weather compensated flow temperature control of 2 heating circuits.
Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation.
• Temperature control of DHW circuit with storage tank charging system or storage tank with internal heat exchanger. DHW circulation pump control.
Optional DHW heating temperature control. Frost protection and alarm function.
Controller output signals
3 x 3-point, 5 x 2-point or
3 x 0 - 10 V control*, 5 x
2-point
3 x 3-point, 5 x 2-point
Code no.
087H3810
087H3817
* ECA 32 module needed
Each of the abovementioned code nos. comprises 1 ECL Application Key, 1 mounting guide and 1 set of multi-lingual user guides.
Pt 1000 temperature sensors (IEC 751B, 1000 Ω / 0 °C):
Type
ESMT
ESM-10
ESM-11
ESMB-12
ESMC
ESMU-100
ESMU-250
ESMU-100
ESMU-250
Designation
Outdoor temperature sensor
Room temperature sensor
Pipe surface temperature sensor
Universal temperature sensor
Pipe surface temperature sensor incl. 2 m cable
Immersion sensor, 100 mm, copper
Immersion sensor, 250 mm, copper
Immersion sensor, 100 mm, stainless steel
Immersion sensor, 250 mm, stainless steel
Accessories and spare parts:
Immersion, stainless steel 100 mm, for ESMU-100, Cu (087B1180)
Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181)
Immersion, stainless steel 100 mm, for ESMB-12, (087B1184)
Immersion, stainless steel 250 mm, for ESMB-12, (087B1184)
Code No.
084N1012
087B1164
087B1165
087B1184
087N0011
087B1180
087B1181
087B1182
087B1183
087B1190
087B1191
087B1192
087B1193
ECL Comfort Controller Base part Appl. key Remote Control Unit Temperature sensors Actuators / valves
ECL 310, 230 V a.c.
ECL 310 B, 230 V a.c.
ECL 310, 24 V a.c.
for ECL 310 A2xx
A3xx
ECA 30
ECA 31
ESMT (outdoor)
ESM-11 (pipe surface)
ESMC (pipe surface)
ESMU (immersion)
ESM-10 (room)
ESMB-12 (universal) see dedicated literature
ECL Portal
ECL Tool
OPC server
Access to the ECL Comfort 310 via a web browser.
After having arranged an account, access to the ECL
Comfort 310 can also be done via a Smart phone.
Software for laptop. Connect ECL Comfort 210 / 310 directly to laptop for e.g. parameter lists, commissioning reports.
For ECL Comfort 210 (Modbus connection) and ECL
Comfort 310 (Modbus or TCP Ethernet connection).
See separate data sheet
Download from Internet
See separate data sheet and download from Internet
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 29
Data sheet
Operation
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A
B
The graphical monochrome display (A) shows all temperature values as well as status information and is used for the setting of control parameters.
The display has backlight. Different favorite displays can be selected. Navigation, browsing and selecting the current item in the menus is done by means of the dial (multi-functional knob
(B)).
The RCUs ECA 30 / 31 are used for remote setting and override of ECL Comfort controller. By means of the built-in room temperature sensor, the flow temperature can be corrected to keep a constant room temperature at comfort or saving temperature. The ECA 30 / 31 is operated as an ECL
Comfort 310 with dial and backlighted display.
Examples of favorite displays:
30 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
Functions
Communication
DEN-SMT/DK
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
General functions:
• The ECL Comfort 310 has all the required functions of a modern electronic temperature controller for heating and DHW applications.
• The controller can be used as master or slave in systems with master / slave ECL Comfort 210 /
310 controllers.
• The ECL Application Key contains the application software for flexible configuration. Furthermore, an update of the controller software is done automatically, if required.
• The ECL Comfort 310 contains, besides the standard functions, log and alarm functions.
• The built-in Real Time Clock gives automatic summer / winter time changeover, week and holiday schedule.
• Motor protection, which ensures stable control and a long life of the motorized control valve, is available for most of the applications. In periods without heat demand, the motorized control valve is exercised to avoid blocking.
• Scheduled control (Comfort and Saving mode) is based on a week program. A holiday program gives the possibility to select days with comfort or saving mode.
• The ECL Comfort 310 can receive pulses from a heat or flow meter to limit the power or the flow.
Alternatively, the data can come from heat or flow meter via the M-bus connection.
• In many applications analogue input (0 – 10 V) is configured for pressure measuring among others. The scaling is set in the controller.
• Some applications are configured to handle digital input. This function can be used to have an external switch to run comfort or saving mode or react on a flow switch signal.
• The control parameters, proportional band (Xp), integration time (Tn), running time of the motorized control valve and neutral zone (Nz) can be set individually for each output (3-point control).
• Motorized control valves in some applications can be controlled with a 0 - 10 V signal.
• Several applications fulfil the demand for refill water function and / or 2-pump control.
Heating functions:
• The heat curve (relationship between outdoor temperature and desired flow temperature) is set by means of 6 coordinate points or a slope value. Max. / min. limitation of the desired flow temperature can be set.
In some application sub-types (for example A337,
A347, A367, A375 and A377) the desired flow temperature can be set by means of a voltage in the range 0 - 10 volt.
• The return temperature limitation can work in relation to the outdoor temperature or be a fixed value.
• The heating cut-out function can switch OFF the heating and stop the circulation pump at high outdoor temperatures.
• Based on the room temperature the ECL Comfort
310 can correct the desired flow temperature in order to increase the comfort level.
• The optimizer function ensures heating in the desired periods (the lower outdoor temperature, the earlier cut-in of the heating).
• The ramping function makes a smooth cut-in of the heating valuable (district heating installations).
• The boost function makes a powerful cut-in of the heating (boiler based installations).
• The circulation pump is controlled in relation to heat demand and frost protection. In periods without heat demand, the circulation pump is exercised to avoid blocking.
• The saving function gives two possibilities:
·
reduction or reduction in relation to outdoor
temperature (the lower the outdoor
temperature, the less the reduction),
· heating off, still with active frost protection
DHW functions:
• The Auto Tuning function with automatic setting of control parameters for constant DHW temperature is integrated in the application
A217, A266, A368 and A376. However, Auto
Tuning is only applicable with valves that are approved for Auto Tuning, i.e. the Danfoss types
VB 2 and VM 2 with split characteristic as well as logarithmic valves such as VF and VFS.
• The anti-bacteria function can follow a schedule program.
• The heating circuit can have sliding DHW priority.
The ECL Comfort 310 has:
• ECL 485 bus, non-galvanic isolated, for closed
communication between master, slave and
RCUs.
• RS 485 bus, galvanic isolated, for Modbus
communication.
• M-bus, non-galvanic isolated, for M-bus
communication with meters.
• USB, type B, for ECL Tool (software for PC).
• Ethernet, RJ 45, for TCP communication to
SCADA systems.
Master / slave connections
VD.KT.X3.02 © Danfoss 04/2015 31
Data sheet
Languages
General data
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Menu languages are selectable among approx. 20 languages. See “Language list”.
Furthermore, English is always uploaded in parallel to the selected language.
ECL Comfort controller and RCU data:
ECL Comfort 310 / 310B ECA 30 / 31
Ambient temperature
Storage and transportation temperature
Mounting
Connections
Number of inputs
Temperature sensor type
Digital input
Analog input
Pulse input, frequency range
(selected applications)
Weight
Display (ECL Comfort 310 and ECA 30 / 31 only)
Vertically, on wall or DIN rail (35 mm)
Terminals in base part
8 in total:
6 temperature sensors
4*) Pt 1000 sensor, digital, analogue or pulse
Pt 1000 (1000 ohm at 0 °C), IEC 751B
Range: -60 – 150 °C
0 - 55 °C
-40 - 70 °C
-
Vertically, on wall or in panel cut-out
Terminals in base part
12 V pull-up possible -
Alternative to built-in room temperature sensor: Pt 1000 (1000 ohm at 0 °C),
IEC 751B
0 - 10 V, resolution 9 bits
For monitoring: 0.01 - 200 Hz
For limitation: Minimum 1 Hz
(recommended) and regular pulses for having a stable control.
0.46 / 0.42 kg
-
-
0.14 kg
Graphical monochrome with backlight
128 × 96 dots
Display mode: Black background, white text
Dial with intuitive push and turn function Setting (ECL Comfort 310 and ECA 30 / 31 only)
Setting (ECL Comfort 310 B)
Min. backup time for time and date
Backup of settings and data
Grade of enclosure
-marking in accordance with the standards
ECA 30 / 31
72 hours
Flash memory
IP 41
EMC directive 2004/108/EC
Immunity: EN 61000-6-1:2007
Emission: EN 61000-6-3:2007
LVD directive 2006/95/EC
EN 60730
-
Flash memory
IP 20
*) Configured at application upload.
ECL application key:
Storage type
Segmentation
Applications
Lock function
Flash memory
Part 1: Application data, not changeable
Part 2: Factory settings, not changeable
Part 3: Updating SW for the ECL Comfort controller, not changeable
Part 4: User settings, changeable
A2xx keys work in ECL Comfort 210 and ECL Comfort 310
A3xx keys work in ECL Comfort 310 only
If not inserted in the ECL Comfort controller, all settings can be seen, but not changed
32 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
DEN-SMT/DK
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL 485 communication bus data:
Purpose
Connection
Cable type
Max. total cable length (bus cable + sensor cables)
Max. number of ECL slaves connected
Max. number of Remote Control Units connected
Data sent from master
Data sent from addressed slave controller
Data sent from ECA 30 / 31
For internal ECL Comfort 210 / 310 and ECA 30 / 31 use only
(Danfoss proprietary bus)
Terminals in base part
Non-galvanic isolated
Shielded cable, 2 x twisted pair,
Min. cross section: 0,22 mm (AWG 24).
Examples:
LiYCY 2 × 2 × 0.25 mm2 (AWG 24) or Ethernet CAT5
200 m in total (inclusive sensor cables)
Units with unigue address (1 - 9): 9
Units with address “0”: 5
2
Date
Time
Outdoor temperature
Desired room temperature
DHW-priority signal
Desired flow temperature from each circuit
•
Actual and desired room temperature
•
Function selector mode
•
(ECA 31) Relative humidity
Modbus communication data:
Purpose
Connection
Protocol
Cable type
Max. bus cable length
Communication speed
Serial mode
Network
For SCADA system
Terminals 34 and 35 in base part. Modbus reference
(terminal 36) must be connected.
Galvanic isolated (500 V).
Modbus RTU
Shielded cable, 2 x twisted pair + Signal GND.
Min. cross section: 0,22 mm2 (AWG 24).
Example: LiYCY 2 × 2 × 0.25 mm2 (AWG 24)
1200 m (dependent on cable type and installation).
Half duplex.
9,6 Kbit/s (default) / 19.2 Kbit/s / 38.4 Kbit/s
8 data bit, even parity and 1 stop bit.
According to the standard Modbus Serial Line
Implementation Guide V1.0.
M-bus communication data:
Purpose
Connection
M-Bus master according to
Cable type
Max. cable length
Baud rate
Update time
Gateway function
Supported heat meters
Transmitted heat meter data
Connection to heat meters, max. 5 heat meters
Terminals 37 and 38 in base part.
Non-galvanic isolated
DS / EN 1434-3: 1997
2 x 0,8 mm2
Example: JY(St)Y 2 x 0.8 mm2 (not twisted pair)
50 m
300 baud (adjustable)
60 s (adjustable)
Allows the ECL Portal to read energy meters directly
Infocal 6 and many other marks and types.
Information about other heat meters on request
Heat meter type dependent:
• Primary flow temperature
• Primary return temperature
• Actual flow / accumulated flow
• Actual heat / power
• Accumulated heat energy
Danfoss recommends 230 V a.c. supplied heat meters Recommendations:
USB communication data:
USB CDC (Communication Device Class)
Modbus over USB
Connection, cable type
VD.KT.X3.02 © Danfoss 04/2015
For service purposes
(Windows driver is needed, to enable that Windows recognize the ECL as a virtual COM port)
Similar to the serial Modbus, but with relaxed timing
Standard USB cable (USB A -------- USB B)
33
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Ethernet communication (Modbus / TCP) data:
Purpose
Connection
Protocol
Cable type
Max. Bus cable length
Auto cross-over detection
Default Ethernet address (IP address)
Port number
Number of connections
Security
For SCADA system
RJ45 female connector
Modbus / TCP
Standard Ethernet cable (CAT 5)
According to Ethernet standard
Enabled
192.168.1.100
502 (Modbus / TCP port)
1
Must be provided by Ethernet infrastructure
A port: USB (type B female plug)
B port: Ethernet
C port: ECL Application Key
Languages
(alphabetic order)
Comparison
ECL Comfort 310 / 210
Bulgarian
Croatian
Czech
Danish
Dutch
English
Estonian
Finnish
French
German
Hungarian
The selected language + English is uploaded at application upload.
Italian
Latvian
Lithuanian
Polish
Romanian
ECL Comfort 310
M-bus communication
Modbus connection
Ethernet
Yes
Yes, galvanic isolated
Yes, RJ45 connection, Modbus / TCP. For
SCADA solutions and ECL Portal
10 Inputs
Relay outputs
Valve actuator outputs
6
3 pairs
Extension of inputs / outputs Yes, ECA 32, placed in base part.
• 6 inputs
• 2 pulse inputs
• 3 analogue outputs (0 - 10 V)
• 4 relays
Russian
Serbian
Slovak
Slovenian
Swedish
ECL Comfort 210
No
Yes, non-galvanic isolated
No
8
4
2 pairs
No
34 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
Wiring - 230 V a.c.
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - 24 V a.c.
ECL Comfort 310 wiring example
Supply voltage
Voltage range
Power consumption
Max. load on relay outputs
Max. load on actuator outputs
230 V a.c. - 50 Hz
207 to 244 V a.c. (IEC 60038)
5 VA
4(2) A - 230 V a.c. (4 A for ohmic load,
2 A for inductive load)
0.2 A - 230 V a.c.
DEN-SMT/DK
ECL Comfort 310 wiring example
Auxiliary relays (K) must be used in order to separate the 230 V a.c. supply from the 24 V a.c. supply of the controller.
Supply voltage
Voltage range
Power consumption
Max. load on relay output
Max. load on actuator output
VD.KT.X3.02 © Danfoss 04/2015
24 V a.c. - 50 Hz
21.6 to 26.4 V a.c. (IEC 60038)
5 VA
4(2) A - 24 V a.c. (4 A for ohmic load,
2 A for inductive load)
1 A - 24 V a.c.
35
Data sheet
Wiring - input
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Wiring - ECA 30 / 31 Remote
Control Unit
ECA 30 / 31
ECL 210 / 310
B
A
B
A
ESM-10
Wiring of ECL Comfort 310 / 310B and ECA 30 / 31
Supply voltage
Power consumption
External room temperature sensor
ECA 31 only
From ECL 485 communication bus
1 VA
Pt 1000 (ESM-10), substitutes the built-in room temperature sensor
Contains humidity sensor, used for special applications
Base part
36
ECL Comfort 310 base part (can be used for ECL Comfort 210 too).
VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
Dimensions
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
ECL Comfort 310
ECL Comfort 310B
ECA 30 / 31
ECA 32
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 37
Data sheet
ECA 30 / 31 cut-out for mounting in panel front
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
A frame (code no. 087H3236) is placed in the cut-out (139 × 93 mm) in which the ECA 30 / 31 is placed.
38 VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Data sheet
Tender text:
ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Electronic controller for heating and domestic hot water application
1a
Electronic weather compensator for flow temperature control in heating and domestic hot water installations.
Turn-push-dial, backlighted graphic display and menu based operation in local languages.
The controller can operate multiple application uploaded by means of application software keys.
1b
• Heat curve setting in 6 coordinates or as slope.
• Flow temperature limitations.
• Room temperature compensation and Comfort / Saving periods according to week schedule.
• Holiday schedule.
• Return temperature limitation as a fixed value (DHW) or in relation to outdoor temperature
(heating).
• Pumps controlled in relation to heat demand and frost protection.
• Alarm functions and log pictures for all sensors.
• Manuel override of the individual outputs.
• Communication: M-bus (up to 5 meters), Modbus, Ethernet, ECL 485 (internal data bus).
• Connection for commissioning / service via PC
• 6 temperature sensor (Pt 1000) inputs.
• 4 application related and configured inputs.
• 6 relay outputs
• 3 pairs of electronic output for noiseless operation of the motorized control valve.
Extension module enables:
• Additional 6 configurable inputs
• 2 pulse counters
• 4 relay outputs
• 3 analogue outputs
1c
Main data:
• Supply voltage, 230 V a.c., 50 Hz: ECL 310 and ECL 310 B
• Supply voltage, 24 V a.c., 50 Hz: ECL 310
• Power consumption: max. 5 VA
• Ambient temperature: 0 – 55 °C
• Storage temperature: -40 – 70 °C
2
Product characteristics:
• Protection class: IP 41
• DIN rail adaptor integrated
• Dimension (inclusive base part) L*W*H, 220*110*80 mm
• Ordering code no.: ECL Comfort 310, 230 V: 087H3040
• Ordering code no.: ECL Comfort 310B, 230 V: 087H3050
• Ordering code no.: ECL Comfort 310, 24 V: 087H3044
DEN-SMT/DK
VD.KT.X3.02 © Danfoss 04/2015 39
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
Additional documentation for ECL Comfort 310, modules and accessories is available on http://den.danfoss.com/
40 VD.KT.X3.02 Produced by Danfoss A/S © 04/2015