ECL Comfort 310 controller,

Remote Control Units ECA 30 / 31 and Application keys

Designed in Denmar k

Description

ECL Comfort 310 controller series

The ECL Comfort 310 is an electronic weather compensated temperature controller in the ECL

Comfort controller family for use in district heating, central heating and cooling systems.

Energy savings can be achieved by correct control of the flow temperature in heating and cooling systems. Up to 4 circuits can be controlled.

ECL Comfort 310 is designed for comfortable temperatures, optimum energy consumption, easy installation by means of the ECL Application

Key (Plug-and-Play) and user friendly operation.

The weather compensation function in the ECL

Comfort controllers measures the outdoor temperature and controls the flow temperature to the heating system accordingly. The weather compensated heating system increases the comfort level and saves energy.

The ECL Comfort 310 controller is configured with a selected application by means of an ECL

Application Key.

Improved energy savings are facilitated by weather compensation, adjustment of temperature according to schedule, optimization as well as limitation of return temperature, flow and power.

The ECL Comfort 310 is easily operated by means of a dial (multi-functional knob) or a Remote

Control Unit (RCU). The dial and the backlighted display guide the user through the text menus in the selected language.

The ECL Comfort 310 controller has electronic output for motorized valve control, relay output for circulation pump / changeover valve control among others, as well as alarm output.

The web based ECL Portal communicates with the

ECL Comfort 310 for an effective and easy-to-use turnkey SCADA (Supervisory Control And Data

Acquisition) tool for all users, service personnel and at commissioning. Service level can be increased and/or service costs reduced. The heating and/or cooling installation is made accessible from virtually anywhere at any time via laptops or Smartphones which increases service level and reduces response time to alarms.

The ECL Tool software for ECL Comfort 310 offers possibilities for an alternative remote control in relation to ECL Portal and OPC server software.

6 Pt 1000 temperature sensors can be connected.

In addition, 4 inputs are configured when uploading the application. The configuration can be Pt 1000 temperature sensor input, analogue input (0 – 10 V) or digital input.

Depending on application, the internal extension module ECA 32 (inserted into the controllers base part) can give additional input and output signals.

VD.KT.X3.02 © Danfoss 04/2015 1

DEN-SMT/DK

Data sheet

Description (continued)

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

The enclosure is designed for mounting on wall and DIN rail. A variant ECL Comfort 310B (without display and dial) is available. It can be used for mounting inside a panel and is operated by means of the RCU ECA 30 / 31 which can be placed in front of the panel.

The ECL Comfort 310 can work as a stand-alone controller and communicate with up to two RCUs and an extension module ECA 32 with additional inputs / outputs.

The ECL Comfort 310 can also work with up to 2 x

RCUs, ECA 32 and other ECL Comfort 210 / 310 controllers via the ECL 485 communication bus.

Ethernet connection is integrated in the controller.

Furthermore, Modbus communication to SCADA systems (Supervisory Control and Data Acquisition) and M-bus communication to heat meters are integrated.

Remote Control Unit (RCU):

The RCUs ECA 30 and ECA 31 are used for room temperature control and override of the ECL

Comfort 310. The display has backlight. The RCUs are connected to the ECL Comfort controllers by means of 2 × twisted pair cable for communication and power supply (ECL 485 communication bus).

The ECA 30 / 31 has a built-in room temperature sensor. An external room temperature sensor can be connected substituting the built-in temperature sensor.

Furthermore, the ECA 31 has a built-in relative humidity sensor and the signal is used in relevant applications. It is possible to connect up to 2 RCUs on the ECL 485 communication bus. One RCU can monitor max. 10 ECL Comfort controllers (master/ slave system).

ECL Application Key and applications:

Different ECL Application Keys make it easy for the

ECL Comfort 310 hardware to run different applications. The ECL Comfort 310 controller is loaded with the desired application by means of the ECL Application Key, which contains information about applications (basic application sketches are shown in the display), languages and factory settings.

The ECL Application Keys, series A2xx can be used in ECL Comfort 210 and ECL Comfort 310. Most of the A2xx application keys give extended functionalities when used in ECL Comfort 310, such as additional temperature sensors and M-bus communication.

The ECL Application Keys, series 3xx can be used in ECL Comfort 310 only.

The application parameters are stored in the controller and are not affected by power break.

The relevant ECL Application Keys for the ECL

Comfort 210 / 310 controller can be found in the ordering section.

2 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Key overview, sub-circuits, combinations

A333

A361

A367

A368

A376

A377

ECL Comfort 210 ECL Comfort 310

Key

A214 A214.1, A214.2, A214.3, A214.4, A214.5, A214.6 A214.1, A214.2, A214.3, A214.4, A214.5, A214.6

A314.1, A314.2, A314.3, A314.4, A314.5, A314.6,

A314.7

A217 A217.1, A217.2, A217.3

A230 A230.1, A230.2

A231 A231.1, A231.2

A232 A232.1

A237 A237.1, A237.2

A247 A247.1, A247.2

A260 A260.1, A260.2

A266 A266.1, A266.2, A266.9

A217.1, A217.2, A217.3

A317.1, A317.2

A230.1, A230.2

A231.1, A231.2

A331.1, A331.2

A232.1

A332.1, A332.2

A237.1, A237.2

A337.1, A337.2

A247.1, A247.2

A347.1, A347.2

A260.1, A260.2

A266.1, A266.2, A266.9

A275 A275.1, A275.2, A275.3

A275.1, A275.2, A275.3

A375.1, A375.2, A375.3

A333.1, A333.2, A333.3

A361.1, A361.2

A367.1, A367.2

A368.1, A368.2, A368.3, A368.4

A376.1, A376.2, A376.3, A376.9

A377.1, A377.2

This is an overview of currently available application keys for the ECL Comfort controllers.

Not all keys are for sale in your country. Please contact your local Danfoss sales company.

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 3

Data sheet

Application examples

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

All mentioned components (S = temperature sensor, P = pump, M = Motorized control valve and so on) are wired to the ECL Comfort 210 / 310.

All applications from ECL Comfort 210 can run in ECL Comfort 310. Extra functions and communication facilities are enabled.

A214.1, ex. a:

Cooling application, duct temperature based on room temperature

S1 ECL 210 / 310

A1

M2

P2

X3

S5

F1 S3

S4

S8

A214.2, ex. a:

Heating application, heating temperature based on duct temperature

S1

ECL 210 / 310

A1

M1

S3

X3

S5

P2

S6 F1 S4

S7

S8

4 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A214.3, ex. a:

Heating application, duct temperature based on room temperature

S1 ECL 210 / 310

A1

M1

P2

X3

S5

S6 F1 S3

S7

S8

S4

A214.5, ex. a:

Heating / cooling application, duct temperature based on room temperature

S1 ECL 210 / 310

A1

M1 M2

P2

X3

S5

S6

S7

F1 S3

S8

S4

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 5

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A314.1, ex. a:

Ventilation system with heating, passive cooling (outside air) and constant duct temperature control.

Analogue controlled passive cooling stage (M2).

S1

P2 M2

A

ECL 310

+ ECA 32

A1

M1

S3

X3

S5

S6 F1

S4

S7

S8

S2

A314.1, ex. b:

Ventilation system with heating, cooling and duct temperature control.

Analogue controlled cooling stage (M2).

S1

P2

S3

X3

S6

ECL 310

+ ECA 32

A1

M1 M2

A

S5

S2

F1

S4

S7

S8

6 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A314.2, ex. b:

Ventilation system with heating, cooling and room temperature control. Analogue controlled cooling stage (M2).

S1

P2

X3

S6

S5

ECL 310

+ ECA 32

A1

M1 M2

A

S2

F1

S3

S7

S8

S4

A314.3, ex. a:

Ventilation system with heating and room temperature control. Speed controlled fan.

S1 ECL 310

+ ECA 32

A1

S2

M1

S10

X3

S5

P2

S6 F1 / V1 S3

S7

S8

S4

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 7

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A217.1, ex. a:

DHW tank charging application

8

A217.1, ex. b:

DHW tank heating application

S1

S2

M1

S5

ECL 210 / 310

A1

S3

P1

A217.2, ex. a:

DHW tank charging with preheating circuit

S1 ECL 210 / 310

A1

S2 S3

M1

S5

P1

S4

B

P2

S6

A

S8 P3

S6

S8

P3

VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A217.3, ex. a:

DHW heating

A217.3, ex. c:

DHW heating on demand (flow switch). With or without circulation

A230.1, ex. a:

Indirectly connected heating system. Wind compensation as option

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 9

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A230.2, ex. a:

Indirectly connected cooling system (district cooling)

10

A231.2:

Indirectly connected heating system with 2-pump control and refill water function

S1 ECL 210

R4

P S7

S2

S3

P1

P2

M1 S5 S8

P3

V1

A331.2, ex. a:

Heating system with two-pump control and refill water function.

Supply temperature dependent flow temperature control.

S1

S2

M1

S10

S5

ECL 310

R6

S9

P S7

S3

P1

P2

S8

V1

P3

P5

VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A232.1, ex. a:

Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature.

A332.1, ex. a:

Control of flow temperature (heating in floor / cooling in ceiling) in relation to outdoor, room and dew point temperature. Optional return temperature limitation.

A332.2, ex. a:

Separated control of flow temperatures for heating / cooling in relation to outdoor, room and dew point temperature. Optional return temperature limitations.

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 11

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A237.1, ex. a:

Indirectly connected heating and DHW system

S1 ECL 210 / (310)

R4 / (R6)

S2

S3

P1

M1

S5

P2

S6

S8

P3

A237.2, ex. a:

Indirectly connected heating and DHW charging system

A247.1, ex. a:

Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority

DEN-SMT/DK

(S7*) = optional in ECL Comfort 310

VD.KT.X3.02 © Danfoss 04/2015 12

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A247.2, ex. a:

Indirectly connected heating and DHW tank charging system with preheating circuit.

Parallel mode or DHW priority

(S7*) = optional in ECL Comfort 310

A347.1, ex. a:

Indirectly connected heating and DHW tank charging system. Parallel mode or DHW priority

S1 ECL 310 S7

A1

S3

P1

M2

S5

S4

M1

S2

S6

A

S8 P3

B

P2

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 13

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A347.2, ex. a:

Indirectly connected heating and DHW tank charging system with preheating circuit.

Parallel mode or DHW priority

A260.1, ex. a:

Two heating systems

14 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A260.1, ex. d:

Two heating systems. Circuit 2 is a sub-circuit of circuit 1.

A266.1, ex. a:

Heating and direct DHW heating system. Parallel mode or DHW priority.

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 15

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A266.2:

Heating and direct DHW heating system. Parallel mode or DHW priority. DHW heating on demand

(flow switch)

A275.1, ex. a:

Heating system with 1-stage boiler

S1 ECL 210 / (310)

A1

S3

P1

*

S5

B1

S7

1

16 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

DEN-SMT/DK

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A275.2, ex. a:

Heating system with 1-stage boiler and DHW tank

S1 ECL 210 / 310

Danfoss 87H2165.

A1

S3

P1

*

S7

1

S5

B1

S6

2

P3

A275.3, ex. a:

Heating system with 1-stage boiler, mixing circuit and DHW tank

S1 ECL 210 / (310)

M2

S4

S2

P4

S3

P1

*

S5

B1

S8

S7

S6

P3

VD.KT.X3.02 © Danfoss 04/2015 17

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A375.1, ex. a:

Up to 8 x boiler ON / OFF control for a heating circuit

S1 ECL 310

+ ECA 32

A1

S3

S7

B1 B8

S5

P1

*

A375.2, ex. a:

Up to 8 x boiler ON / OFF control for a heating circuit and a DHW circuit. Optional DHW priority.

S1 ECL 310

+ ECA 32

A1

S3

B1 B8

S5

P1

*

S7

S6

P4

P3

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 18

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A375.3, ex. a:

Up to 8 x boiler ON / OFF control for a direct heating circuit (1), a mixing circuit (2) and a DHW circuit

(3). Optional DHW priority.

S1

S3

ECL 310

A1

+ ECA 32

M2

S4

S2

P4

S8

S7

B1 B8 P1

*

S5

S6

P3

Burner control overview:

A275.1

A275.2

A275.3

A375.1

A375.2

A375.3

R2

1

1

1

ECL 210 ECL 310 ECA 32

1

1

1

1

R2

1

1

R3

2

R4 R5 Triac 5 Triac 6 R7 R8 R9 R10

3 4

2

2

7

7

8

8

5

3

3

6

4

4

7

5

5

8

6

6

R2-R10 = relay nos. in ECL / ECA 32

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 19

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A333.1, ex. a:

Heating system with control of 1 or 2 circulation pumps. Refill water function with control of 1 or 2 pumps. Pressure measurements in the system.

A333.2, ex. a:

Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank.

Pressure measurements in the system.

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 20

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A333.3, ex. a:

Heating system with ON / OFF and speed control of 1 or 2 circulation pumps. Control valve M1 is 0 -

10 V controlled. Refill water function with ON / OFF and speed control of 1 or 2 pumps. Level control of refill water storage tank. Pressure measurements in the system.

A361.2, ex. a:

2 x heating systems with two-pump control and refill water function. Supply temperature dependent flow temperature control.

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 21

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A367.1, ex. a:

System with 2 heating circuits and secondarily connected DHW tank with internal heat exchanger.

Optional DHW priority.

S1 ECL 310

R6

S4

S9

P5

M2

S2

S7

P1

S3

M1

S5

S6

S8

P3

P2

A367.2, ex. a:

System with 2 heating circuits and secondarily connected DHW tank charging system.

Optional DHW priority.

S1 ECL 310

R6

S4

(S7)

P5

M2

S2

(S7)

S3

P1

S9

M1

S5

S6

S8 P3

P2 P4

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 22

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A368.2, ex. a:

Heating system with two-pump control and refill water function. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps.

A368.4, ex. a:

Heating system with two-pump control and refill water function with 1 or 2 pumps. Supply temperature dependent flow temperature control. DHW heating system with control of 1 or 2 circulation pumps. Pressure measurements in the systems.

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 23

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A376.1, ex. a:

Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority.

S1 ECL 310

A1

S3

P2

S2

1

M2

S5

S9

P3

S7

2

M3

S10

S4

M1

S6

3

P1

A376.2, ex. a:

Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority.

DHW heating on demand (flow switch).

S1 ECL 310

A1

S3

P2

(S2)

1

M2

S5

S9

P3

(S2)

2

M3

S10

S4 S7

M1

S6

3

S8

P1

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 24

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A376.3, ex. a:

Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Control valves M1, M2 and M3 are 0 - 10 V controlled.

S1 ECL 310

+ ECA 32

A1

S3

P2

S2

1

A

M2

S5

S9

P3

S7

2

A

M3

S10

S4

A

M1

S6

3

P1

A376.9, ex. a:

Two heating circuits and one direct DHW heating system. Parallel mode or DHW priority. Pressure measurements and temperature monitoring in the system.

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 25

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A377.1, ex. a:

Two heating circuits and one DHW tank charging system. Parallel mode or DHW priority.

S1 ECL 310

A1

S4

P5

M3

S2

S3

P2

M2

S5

S7 S9

M1

P1

S10

B

P4

S6

A

S8 P3

A377.2, ex. a:

Two heating circuits and one DHW tank charging system. Control of the DHW heating temperature.

Parallel mode or DHW priority.

S1

S4

P5

ECL 310

A1

M3

S2

P2

S3

M1

S9 S10

M2

S5

S6

A

S8 P3

P1

B

P4

26 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

Ordering

DEN-SMT/DK

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Controller, base parts and accessories:

Type

ECL Comfort 310

ECL Comfort 310

ECL Comfort 310B

ECL Comfort 310 base part

Designation

Universal hardware - 230 V a.c.

Base part is not included. Mounting guide (no text) is included.

Universal hardware - 24 V a.c.

Base part is not included. Mounting guide (no text) is included.

Universal hardware - 230 V a.c.

Without display and dial. Requires a Remote Control Unit.

Base part is not included. Mounting guide (no text) is included.

For mounting on wall or DIN rail (35 mm). ECL Comfort 210 can be mounted in an ECL Comfort 310 base part (for future upgrade). Mounting guide (no text) and cable inlet accessories is included.

Code no.

087H3040

087H3044

087H3050

087H3230

Remote Control Units and accessories

Type

ECA 30

ECA 31

ECA 30 / 31 frame kit for mounting in panel front

ECA 32

Designation

Remote Control Unit with an integrated room temperature sensor and possibility for connecting an external Pt 1000 room temperature sensor.

Base part for mounting on wall included. Mounting guide (no text) is included.

Remote Control Unit with an integrated room temperature sensor and a humidity sensor. Possibility for connecting an external Pt 1000 room temperature sensor. Used for dedicated applications. Base part for mounting on wall included. Mounting guide (no text) is included.

For mounting in a panel cut-out.

Format 144 × 96 mm, actual cut-out 139 × 93 mm. Mounting guide (no text) is included.

Internal extension module with additional inputs and outputs. To be placed in the ECL Comfort 310 base part. See separate data sheet.

Code no.

087H3200

087H3201

087H3236

087H3202

Accessories:

Type

ECA 99

Designation

230 V a.c. to 24 V a.c. transformer (35 VA)

Code no.

087B1156

ECL Application Keys

Type

A214

A217

A230

A231

A232

Application type description Controller output signals

• Temperature control (heating / cooling) of ventilation systems. Duct / room temperature control. Return temperature limitation. Flow / power limitation. Fire and frost protection as well as alarm function.

• The A214 application key contains applications related to ECL Comfort 310 for increased functionalities (control of rotating heat-exchanger).

2 x 3-point, 2 x 2-point

• Advanced temperature control of DHW (Domestic Hot Water) circuit with/ without storage charging system. Circulation pump control. Return temperature limitation. Frost protection and alarm function.

• The A217 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).

1 x 3-point, 3 x 2-point

• (A230.1) Weather compensated flow temperature control of heating systems. Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Wind compensation, frost protection and alarm function.

• (A230.2) Flow temperature control of cooling systems. Compensation for outdoor and room temperatures. Return temperature limitation.

• The A230 application key works in ECL Comfort 310 for increased functionalities (M-bus).

1 x 3-point, 2 x 2-point

1 x 3-point, 3 x 2-point • Weather compensated flow temperature control of heating systems.

2-pump control for circulation and refill water function. Sliding return temperature limitation. Frost protection and alarm function.

• The A231 application key contains applications related to ECL Comfort 310 for increased functionalities (2 pumps for refill water and M-bus).

• Weather compensated flow temperature control of heating / cooling circuit(s). Automatic change-over between heating and cooling. Circulation pump control. Dew point (cooling mode only) and surface temperature compensation.

• The A232 application key contains applications related to ECL Comfort 310 for increased functionalities (return temperature limitation and separated control of heating and cooling circuits).

1 x 3-point, 3 x 2-point

Code no.

087H3811

087H3807

087H3802

087H3805

087H3812

VD.KT.X3.02 © Danfoss 04/2015 27

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

ECL Application Keys (continued):

Type

A237

A247

A260

A266

A275

A333

A361

A367

A368

Application type description

• Weather compensated flow temperature control of heating systems.

Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation. Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger. Optional ON / OFF control of the DHW circuit in connection with primarily connected storage tank with internal heat exchanger. DHW circulation pump control. Frost protection and alarm function.

• The A237 application key contains applications related to ECL Comfort 310 for increased functionalities (M-bus).

• Weather compensated flow temperature control of heating systems.

Circulation pump control. Sliding return temperature limitation. Flow / power limitation. Temperature control of DHW circuit with storage tank charging system. DHW circulation pump control through the storage tank or the heat-exchanger. Frost protection and alarm function.

• The A247 application key contains applications related to ECL Comfort 310 for increased functionalities (room temperature sensor and M-bus).

• Weather compensated flow temperature control of heating systems.

Circulation pump control, room temperature control and sliding return temperature limitation for two independent heating circuits. Flow / power limitation, frost protection and alarm function.

• The A260 application key works in ECL Comfort 310 for increased functionalities (M-bus).

Controller output signals

1 x 3-point, 3 x 2-point

2 x 3-point, 3 x 2-point

2 x 3-point, 2 x 2-point

Code no.

087H3806

087H3808

087H3801

• Weather compensated flow temperature control of heating systems.

Circulation pump control, room temperature control and sliding return temperature limitation.

• Temperature control of DHW circuit with DHW circulation. Return temperature limitation, sliding DHW priority, frost protection and alarm function. Optional control of DHW heating based on DHW demand.

• The A266 application key works in ECL Comfort 310 for increased functionalities (M-bus).

2 x 3-point, 2 x 2-point

• Weather compensated flow temperature control of 1-stage boiler based heating systems. One direct heating circuit and one mixing circuit.

Circulation pumps control, room temperature control and sliding return temperature limitation.

• Temperature control of DHW storage tank with internal heat exchanger.

Frost protection and alarm function.

• The A275 application key contains applications related to ECL Comfort 310 for increased functionalities (multiple boiler stages).

1 x 3-point, 4 x 2-point

1 x 3-point, 7 x 2-point* or

1 x 0 - 10 V control*, 7 x

2-point*

• Weather compensated flow temperature control of a heating system.

ON / OFF and speed control of 1 or 2 circulation pumps and sliding return

temperature limitation. Flow / power limitation. Frost protection and alarm

function. ON / OFF and speed control of 1 or 2 refill water pumps.

Refill water storage control. Pressure release function. Pressure and

temperature monitoring. Frost protection and alarm function.

• Weather compensated flow temperature control of 2 heating circuits.

Supply temperature dependent flow temperature control. 2-pump control

for circulation. Sliding return temperature limitation. Flow / power

limitaion. Refill water function. Frost protection and alarm function.

• Weather compensated flow temperature control of 2 heating circuits.

Circulation pump control. Room temperature control and sliding return

temperature limitation. Flow / power limitation.

• Temperature control of secondarily connected DHW circuit with storage tank charging system or storage tank with internal heat exchanger.

Optional ON / OFF control of the DHW circuit in connection with primarily connected storage tank with internal heat exchanger.

DHW circulation pump control. Frost protection and alarm function.

2 x 3-point, 7 x 2-point*

2 x 3-point, 5 x 2-point

087H3800

087H3814

087H3818

087H3804

087H3813

• Weather compensated flow temperature control of a heating circuit.

Supply temperature dependent flow temperature control. 2-pump control

for circulation. Sliding return temperature limitation. Flow / power limitation

Flow / power limitation and refill water function.

• Temperature control of a DHW circuit with DHW circulation, return

temperature limitation and sliding DHW priority. Frost protection and

alarm function.

2 x 3-point, 5 x 2-point 087H3803

* ECA 32 module needed

28 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

Typical ordering, types:

Reference, additional products / software:

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

ECL Application Keys (continued):

Type

A376

A377

Application type description

• Weather compensated flow temperature control of 2 heating circuits.

Circulation pump control. Room temperature control and sliding return

temperature limitation. Flow / power limitation.

• Temperature control of a DHW circuit with DHW circulation, return temperature limitation and sliding DHW priority. Optional control of DHW heating based on DHW demand. Frost protection and alarm function.

• Weather compensated flow temperature control of 2 heating circuits.

Circulation pump control. Room temperature control and sliding return temperature limitation. Flow / power limitation.

• Temperature control of DHW circuit with storage tank charging system or storage tank with internal heat exchanger. DHW circulation pump control.

Optional DHW heating temperature control. Frost protection and alarm function.

Controller output signals

3 x 3-point, 5 x 2-point or

3 x 0 - 10 V control*, 5 x

2-point

3 x 3-point, 5 x 2-point

Code no.

087H3810

087H3817

* ECA 32 module needed

Each of the abovementioned code nos. comprises 1 ECL Application Key, 1 mounting guide and 1 set of multi-lingual user guides.

Pt 1000 temperature sensors (IEC 751B, 1000 Ω / 0 °C):

Type

ESMT

ESM-10

ESM-11

ESMB-12

ESMC

ESMU-100

ESMU-250

ESMU-100

ESMU-250

Designation

Outdoor temperature sensor

Room temperature sensor

Pipe surface temperature sensor

Universal temperature sensor

Pipe surface temperature sensor incl. 2 m cable

Immersion sensor, 100 mm, copper

Immersion sensor, 250 mm, copper

Immersion sensor, 100 mm, stainless steel

Immersion sensor, 250 mm, stainless steel

Accessories and spare parts:

Pocket

Pocket

Pocket

Pocket

Immersion, stainless steel 100 mm, for ESMU-100, Cu (087B1180)

Immersion, stainless steel 250 mm, for ESMU-250, Cu (087B1181)

Immersion, stainless steel 100 mm, for ESMB-12, (087B1184)

Immersion, stainless steel 250 mm, for ESMB-12, (087B1184)

Code No.

084N1012

087B1164

087B1165

087B1184

087N0011

087B1180

087B1181

087B1182

087B1183

087B1190

087B1191

087B1192

087B1193

ECL Comfort Controller Base part Appl. key Remote Control Unit Temperature sensors Actuators / valves

ECL 310, 230 V a.c.

ECL 310 B, 230 V a.c.

ECL 310, 24 V a.c.

for ECL 310 A2xx

A3xx

ECA 30

ECA 31

ESMT (outdoor)

ESM-11 (pipe surface)

ESMC (pipe surface)

ESMU (immersion)

ESM-10 (room)

ESMB-12 (universal) see dedicated literature

ECL Portal

ECL Tool

OPC server

Access to the ECL Comfort 310 via a web browser.

After having arranged an account, access to the ECL

Comfort 310 can also be done via a Smart phone.

Software for laptop. Connect ECL Comfort 210 / 310 directly to laptop for e.g. parameter lists, commissioning reports.

For ECL Comfort 210 (Modbus connection) and ECL

Comfort 310 (Modbus or TCP Ethernet connection).

See separate data sheet

Download from Internet

See separate data sheet and download from Internet

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 29

Data sheet

Operation

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A

B

The graphical monochrome display (A) shows all temperature values as well as status information and is used for the setting of control parameters.

The display has backlight. Different favorite displays can be selected. Navigation, browsing and selecting the current item in the menus is done by means of the dial (multi-functional knob

(B)).

The RCUs ECA 30 / 31 are used for remote setting and override of ECL Comfort controller. By means of the built-in room temperature sensor, the flow temperature can be corrected to keep a constant room temperature at comfort or saving temperature. The ECA 30 / 31 is operated as an ECL

Comfort 310 with dial and backlighted display.

Examples of favorite displays:

30 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

Functions

Communication

DEN-SMT/DK

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

General functions:

• The ECL Comfort 310 has all the required functions of a modern electronic temperature controller for heating and DHW applications.

• The controller can be used as master or slave in systems with master / slave ECL Comfort 210 /

310 controllers.

• The ECL Application Key contains the application software for flexible configuration. Furthermore, an update of the controller software is done automatically, if required.

• The ECL Comfort 310 contains, besides the standard functions, log and alarm functions.

• The built-in Real Time Clock gives automatic summer / winter time changeover, week and holiday schedule.

• Motor protection, which ensures stable control and a long life of the motorized control valve, is available for most of the applications. In periods without heat demand, the motorized control valve is exercised to avoid blocking.

• Scheduled control (Comfort and Saving mode) is based on a week program. A holiday program gives the possibility to select days with comfort or saving mode.

• The ECL Comfort 310 can receive pulses from a heat or flow meter to limit the power or the flow.

Alternatively, the data can come from heat or flow meter via the M-bus connection.

• In many applications analogue input (0 – 10 V) is configured for pressure measuring among others. The scaling is set in the controller.

• Some applications are configured to handle digital input. This function can be used to have an external switch to run comfort or saving mode or react on a flow switch signal.

• The control parameters, proportional band (Xp), integration time (Tn), running time of the motorized control valve and neutral zone (Nz) can be set individually for each output (3-point control).

• Motorized control valves in some applications can be controlled with a 0 - 10 V signal.

• Several applications fulfil the demand for refill water function and / or 2-pump control.

Heating functions:

• The heat curve (relationship between outdoor temperature and desired flow temperature) is set by means of 6 coordinate points or a slope value. Max. / min. limitation of the desired flow temperature can be set.

In some application sub-types (for example A337,

A347, A367, A375 and A377) the desired flow temperature can be set by means of a voltage in the range 0 - 10 volt.

• The return temperature limitation can work in relation to the outdoor temperature or be a fixed value.

• The heating cut-out function can switch OFF the heating and stop the circulation pump at high outdoor temperatures.

• Based on the room temperature the ECL Comfort

310 can correct the desired flow temperature in order to increase the comfort level.

• The optimizer function ensures heating in the desired periods (the lower outdoor temperature, the earlier cut-in of the heating).

• The ramping function makes a smooth cut-in of the heating valuable (district heating installations).

• The boost function makes a powerful cut-in of the heating (boiler based installations).

• The circulation pump is controlled in relation to heat demand and frost protection. In periods without heat demand, the circulation pump is exercised to avoid blocking.

• The saving function gives two possibilities:

·

reduction or reduction in relation to outdoor

temperature (the lower the outdoor

temperature, the less the reduction),

· heating off, still with active frost protection

DHW functions:

• The Auto Tuning function with automatic setting of control parameters for constant DHW temperature is integrated in the application

A217, A266, A368 and A376. However, Auto

Tuning is only applicable with valves that are approved for Auto Tuning, i.e. the Danfoss types

VB 2 and VM 2 with split characteristic as well as logarithmic valves such as VF and VFS.

• The anti-bacteria function can follow a schedule program.

• The heating circuit can have sliding DHW priority.

The ECL Comfort 310 has:

ECL 485 bus, non-galvanic isolated, for closed

communication between master, slave and

RCUs.

RS 485 bus, galvanic isolated, for Modbus

communication.

M-bus, non-galvanic isolated, for M-bus

communication with meters.

USB, type B, for ECL Tool (software for PC).

Ethernet, RJ 45, for TCP communication to

SCADA systems.

Master / slave connections

VD.KT.X3.02 © Danfoss 04/2015 31

Data sheet

Languages

General data

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Menu languages are selectable among approx. 20 languages. See “Language list”.

Furthermore, English is always uploaded in parallel to the selected language.

ECL Comfort controller and RCU data:

ECL Comfort 310 / 310B ECA 30 / 31

Ambient temperature

Storage and transportation temperature

Mounting

Connections

Number of inputs

Temperature sensor type

Digital input

Analog input

Pulse input, frequency range

(selected applications)

Weight

Display (ECL Comfort 310 and ECA 30 / 31 only)

Vertically, on wall or DIN rail (35 mm)

Terminals in base part

8 in total:

6 temperature sensors

4*) Pt 1000 sensor, digital, analogue or pulse

Pt 1000 (1000 ohm at 0 °C), IEC 751B

Range: -60 – 150 °C

0 - 55 °C

-40 - 70 °C

-

Vertically, on wall or in panel cut-out

Terminals in base part

12 V pull-up possible -

Alternative to built-in room temperature sensor: Pt 1000 (1000 ohm at 0 °C),

IEC 751B

0 - 10 V, resolution 9 bits

For monitoring: 0.01 - 200 Hz

For limitation: Minimum 1 Hz

(recommended) and regular pulses for having a stable control.

0.46 / 0.42 kg

-

-

0.14 kg

Graphical monochrome with backlight

128 × 96 dots

Display mode: Black background, white text

Dial with intuitive push and turn function Setting (ECL Comfort 310 and ECA 30 / 31 only)

Setting (ECL Comfort 310 B)

Min. backup time for time and date

Backup of settings and data

Grade of enclosure

-marking in accordance with the standards

ECA 30 / 31

72 hours

Flash memory

IP 41

EMC directive 2004/108/EC

Immunity: EN 61000-6-1:2007

Emission: EN 61000-6-3:2007

LVD directive 2006/95/EC

EN 60730

-

Flash memory

IP 20

*) Configured at application upload.

ECL application key:

Storage type

Segmentation

Applications

Lock function

Flash memory

Part 1: Application data, not changeable

Part 2: Factory settings, not changeable

Part 3: Updating SW for the ECL Comfort controller, not changeable

Part 4: User settings, changeable

A2xx keys work in ECL Comfort 210 and ECL Comfort 310

A3xx keys work in ECL Comfort 310 only

If not inserted in the ECL Comfort controller, all settings can be seen, but not changed

32 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

DEN-SMT/DK

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

ECL 485 communication bus data:

Purpose

Connection

Cable type

Max. total cable length (bus cable + sensor cables)

Max. number of ECL slaves connected

Max. number of Remote Control Units connected

Data sent from master

Data sent from addressed slave controller

Data sent from ECA 30 / 31

For internal ECL Comfort 210 / 310 and ECA 30 / 31 use only

(Danfoss proprietary bus)

Terminals in base part

Non-galvanic isolated

Shielded cable, 2 x twisted pair,

Min. cross section: 0,22 mm (AWG 24).

Examples:

LiYCY 2 × 2 × 0.25 mm2 (AWG 24) or Ethernet CAT5

200 m in total (inclusive sensor cables)

Units with unigue address (1 - 9): 9

Units with address “0”: 5

2

Date

Time

Outdoor temperature

Desired room temperature

DHW-priority signal

Desired flow temperature from each circuit

Actual and desired room temperature

Function selector mode

(ECA 31) Relative humidity

Modbus communication data:

Purpose

Connection

Protocol

Cable type

Max. bus cable length

Communication speed

Serial mode

Network

For SCADA system

Terminals 34 and 35 in base part. Modbus reference

(terminal 36) must be connected.

Galvanic isolated (500 V).

Modbus RTU

Shielded cable, 2 x twisted pair + Signal GND.

Min. cross section: 0,22 mm2 (AWG 24).

Example: LiYCY 2 × 2 × 0.25 mm2 (AWG 24)

1200 m (dependent on cable type and installation).

Half duplex.

9,6 Kbit/s (default) / 19.2 Kbit/s / 38.4 Kbit/s

8 data bit, even parity and 1 stop bit.

According to the standard Modbus Serial Line

Implementation Guide V1.0.

M-bus communication data:

Purpose

Connection

M-Bus master according to

Cable type

Max. cable length

Baud rate

Update time

Gateway function

Supported heat meters

Transmitted heat meter data

Connection to heat meters, max. 5 heat meters

Terminals 37 and 38 in base part.

Non-galvanic isolated

DS / EN 1434-3: 1997

2 x 0,8 mm2

Example: JY(St)Y 2 x 0.8 mm2 (not twisted pair)

50 m

300 baud (adjustable)

60 s (adjustable)

Allows the ECL Portal to read energy meters directly

Infocal 6 and many other marks and types.

Information about other heat meters on request

Heat meter type dependent:

• Primary flow temperature

• Primary return temperature

• Actual flow / accumulated flow

• Actual heat / power

• Accumulated heat energy

Danfoss recommends 230 V a.c. supplied heat meters Recommendations:

USB communication data:

USB CDC (Communication Device Class)

Modbus over USB

Connection, cable type

VD.KT.X3.02 © Danfoss 04/2015

For service purposes

(Windows driver is needed, to enable that Windows recognize the ECL as a virtual COM port)

Similar to the serial Modbus, but with relaxed timing

Standard USB cable (USB A -------- USB B)

33

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Ethernet communication (Modbus / TCP) data:

Purpose

Connection

Protocol

Cable type

Max. Bus cable length

Auto cross-over detection

Default Ethernet address (IP address)

Port number

Number of connections

Security

For SCADA system

RJ45 female connector

Modbus / TCP

Standard Ethernet cable (CAT 5)

According to Ethernet standard

Enabled

192.168.1.100

502 (Modbus / TCP port)

1

Must be provided by Ethernet infrastructure

A port: USB (type B female plug)

B port: Ethernet

C port: ECL Application Key

Languages

(alphabetic order)

Comparison

ECL Comfort 310 / 210

Bulgarian

Croatian

Czech

Danish

Dutch

English

Estonian

Finnish

French

German

Hungarian

The selected language + English is uploaded at application upload.

Italian

Latvian

Lithuanian

Polish

Romanian

ECL Comfort 310

M-bus communication

Modbus connection

Ethernet

Yes

Yes, galvanic isolated

Yes, RJ45 connection, Modbus / TCP. For

SCADA solutions and ECL Portal

10 Inputs

Relay outputs

Valve actuator outputs

6

3 pairs

Extension of inputs / outputs Yes, ECA 32, placed in base part.

• 6 inputs

• 2 pulse inputs

• 3 analogue outputs (0 - 10 V)

• 4 relays

Russian

Serbian

Slovak

Slovenian

Swedish

ECL Comfort 210

No

Yes, non-galvanic isolated

No

8

4

2 pairs

No

34 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

Wiring - 230 V a.c.

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Wiring - 24 V a.c.

ECL Comfort 310 wiring example

Supply voltage

Voltage range

Power consumption

Max. load on relay outputs

Max. load on actuator outputs

230 V a.c. - 50 Hz

207 to 244 V a.c. (IEC 60038)

5 VA

4(2) A - 230 V a.c. (4 A for ohmic load,

2 A for inductive load)

0.2 A - 230 V a.c.

DEN-SMT/DK

ECL Comfort 310 wiring example

Auxiliary relays (K) must be used in order to separate the 230 V a.c. supply from the 24 V a.c. supply of the controller.

Supply voltage

Voltage range

Power consumption

Max. load on relay output

Max. load on actuator output

VD.KT.X3.02 © Danfoss 04/2015

24 V a.c. - 50 Hz

21.6 to 26.4 V a.c. (IEC 60038)

5 VA

4(2) A - 24 V a.c. (4 A for ohmic load,

2 A for inductive load)

1 A - 24 V a.c.

35

Data sheet

Wiring - input

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Wiring - ECA 30 / 31 Remote

Control Unit

ECA 30 / 31

ECL 210 / 310

B

A

B

A

ESM-10

Wiring of ECL Comfort 310 / 310B and ECA 30 / 31

Supply voltage

Power consumption

External room temperature sensor

ECA 31 only

From ECL 485 communication bus

1 VA

Pt 1000 (ESM-10), substitutes the built-in room temperature sensor

Contains humidity sensor, used for special applications

Base part

36

ECL Comfort 310 base part (can be used for ECL Comfort 210 too).

VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

Dimensions

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

ECL Comfort 310

ECL Comfort 310B

ECA 30 / 31

ECA 32

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 37

Data sheet

ECA 30 / 31 cut-out for mounting in panel front

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

A frame (code no. 087H3236) is placed in the cut-out (139 × 93 mm) in which the ECA 30 / 31 is placed.

38 VD.KT.X3.02 © Danfoss 04/2015

DEN-SMT/DK

Data sheet

Tender text:

ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Electronic controller for heating and domestic hot water application

1a

Electronic weather compensator for flow temperature control in heating and domestic hot water installations.

Turn-push-dial, backlighted graphic display and menu based operation in local languages.

The controller can operate multiple application uploaded by means of application software keys.

1b

• Heat curve setting in 6 coordinates or as slope.

• Flow temperature limitations.

• Room temperature compensation and Comfort / Saving periods according to week schedule.

• Holiday schedule.

• Return temperature limitation as a fixed value (DHW) or in relation to outdoor temperature

(heating).

• Pumps controlled in relation to heat demand and frost protection.

• Alarm functions and log pictures for all sensors.

• Manuel override of the individual outputs.

• Communication: M-bus (up to 5 meters), Modbus, Ethernet, ECL 485 (internal data bus).

• Connection for commissioning / service via PC

• 6 temperature sensor (Pt 1000) inputs.

• 4 application related and configured inputs.

• 6 relay outputs

• 3 pairs of electronic output for noiseless operation of the motorized control valve.

Extension module enables:

• Additional 6 configurable inputs

• 2 pulse counters

• 4 relay outputs

• 3 analogue outputs

1c

Main data:

• Supply voltage, 230 V a.c., 50 Hz: ECL 310 and ECL 310 B

• Supply voltage, 24 V a.c., 50 Hz: ECL 310

• Power consumption: max. 5 VA

• Ambient temperature: 0 – 55 °C

• Storage temperature: -40 – 70 °C

2

Product characteristics:

• Protection class: IP 41

• DIN rail adaptor integrated

• Dimension (inclusive base part) L*W*H, 220*110*80 mm

• Ordering code no.: ECL Comfort 310, 230 V: 087H3040

• Ordering code no.: ECL Comfort 310B, 230 V: 087H3050

• Ordering code no.: ECL Comfort 310, 24 V: 087H3044

DEN-SMT/DK

VD.KT.X3.02 © Danfoss 04/2015 39

Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys

Additional documentation for ECL Comfort 310, modules and accessories is available on http://den.danfoss.com/

40 VD.KT.X3.02 Produced by Danfoss A/S © 04/2015