KSIX SERIES-TROUBLESHOOTING


Add to my manuals
11 Pages

advertisement

KSIX SERIES-TROUBLESHOOTING | Manualzz

KSI

X SERIES ro le oo

SPLIT TYPE ROOM

AIR CONDITIONER

For Split Wall Mounted

Series R410a Inverter

Model Type For F

KSIX009-H223 - I/KSIX009-H223-O

KSIX012-H222 - I/KSIX012-H222-O

KSIX018-H221 - I/KSIX018-H221-O

KSIX024-H220 - I/KSIX024-H220-O

Please read this owner s manual carefully and

Chapter 4 Troubleshooting Guide

13

14

15

10

11

12

4

5

2

3

6

7

8

9

F0

F1

F2

F3

E2

E3

E4

E5

F7

F8

F9

F4

F5

F6

4.1 Error Code

No.

Error Code

1

E1

16

FA

Problem

Room temperature sensor fault

Outdoor coil temperature sensor fault

Indoor coil temperature sensor fault

Indoor fan motor or DC motor feedback fault

Indoor & outdoor communication fault

Outdoor DC Fan motor fault

IPM modular fault

PFC modular fault

Compressor operation fault

Exhaust Temperature sensor fault

Compressor top cover protection

Outdoor ambient temp sensor fault

Over/under voltage protection

Outdoor modular communication fault

Outdoor E²PROM fault

Suction temperature sensor fault

(4-way valve swich failure)

10

4.2 Troubleshooting Guide

1. The Foremost Inspecting Items

The input voltage must be within +10% tolerance of the rated Voltage. If it is not the case, the air-conditioner will probably not work normally.

Check the connecting cord between indoor unit and outdoor unit to see if it is properly connected. The connecting must be done according to the wiring diagram, please also notice that even different models may have the connecting cord of the same specification.

Please check if the marks at the connecting terminal and the marks on the cord can match, otherwise, the air-conditioner will not work normally.

If the following phenomena are found, the problem is not from the air-conditioner itself.

11

NO.

1

2

3

4

5

Problems

The motor is heard operating but the air-conditioner dose not work when the indoor unit is powered on

The compressor stops running but the indoor fan motor keeps working when it is at cooling mode with the indoor temperature higher than set temperature.

The compressor works discontinuously at dehumidifying mode.

The air-conditioner does not work while the LED display is on.

The compressor works discontinuously at cooling and dehumidifying mode, and the indoor fan motor slows down.

Causes

Since the air-conditioner is powered on, it will come to working condition as long as you press the ON/OFF button of the remote control and the Signal is well received.

If you turn off the air-conditioner and restart it immediately, it will return to normal in 3 minutes, after that, the air-conditioner will automatically adjust the indoor fan speed to what you set.

The air-conditioner will automatically control the working of the compressor according to the inside temperature

The TIMER is set with the air-conditioner; it will be in hold on condition. If the TIMER setting is cancelled, the air-conditioner will return to normal working condition

The compressor stops internally or the fan motor slows down to prevent the indoor heat exchanger from being frozen.

12

2. No Power Display

⑴Items

a) Check if the input voltage is correct?

b) Check if the AC power supply connecting is correct?

c) Check if the output voltage of the manostat L7805 (IC2) is correct?

⑵Trouble shooting procedure

13

3. The Indoor Fan Motor Does Not Work

⑴Items

a) Check if the indoor fan motor is connected correctly to the connector (CN8)?

b) Check if the AC input voltage is correct?

c) Check if the IC of indoor fan motor is connected correctly to the connector

(CN2)?

d) Check if the capacity of indoor fan motor is connected correctly to the connector (CN8)?

⑵Trouble shooting procedure

14

4. The Outdoor Unit Does Not Work

⑴Items

a) Check if the input voltage is correct?

b) Check if the wire connection of the outdoor connecting terminal is correct?

⑵Trouble shooting procedure

15

5. The Step Motor Does Not Work

⑴Items

a) Check if the input voltage is correct?

b) Check if the step motor controlling the up-down movement firmly connected to Cn2?

⑵Trouble shooting procedure

16

6. Heating Mode Can Work, But No Hot Air Blow

⑴Check if the set temperature is lower than the indoor temperature?

⑵Check if the indoor PCB is connected to the terminal correctly?

17

7. Remote Control Can Not Work

Trouble shooting rocedure

18

e l a re lo o a re ere ra e ar o l a re Pro c c o r 201 l a re Pro c c

2190 NW 89 Place, Doral, FL 33172 - USA

Tel: (305) 593-8358 www.klimaire.com

Fax: (305) 675-2212 [email protected]

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement