Edco PC642 Series

Zone/Loop/Data

Power Switching & Controls

For Business-Critical Continuity

TM

The Edco PC642 Series surge protective device, (SPD) is a two-pair (four wire) module implementing three-stage hybrid technology. This SPD addresses over-voltage transients with gas tubes and silicon avalanche components. In addition, sneak and fault currents are mitigated with resettable fuses (PTCs). The PTCs increase resistance several orders of magnitude when over-currents exceed safe levels. A normal state resumes when over-currents are removed. The ability to self-restore in this manner significantly increases suppressor performance and survivability.

The Edco PC642 card edge is gold-plated, double sided and is designed to mate with the the Edco PCB1B-WKEY gold-plated female terminal connector (sold separately).

When snapped together, the data circuits “pass thru” the protector in a serial fashion from the four “Field Side” terminals to the four “Electronics Side” terminals.

Terminals 1 or 10 of the PCB1B must be attached to Building-Approved Ground.

Weight

Certifications

General Technical Specifications

Maximum Operating Voltage

Clamping Voltage

Operating Current

Peak Surge Current

Frequency Range

Insertion Loss

SPD Technology

Connection Type

Operating Temperature

Dimensions (Inches)

5-250 VDC

8-300 VDC

0.15 A

10 kA (8 x 20 µs)

0 to 20 MHz

< 0.1 dB at 20 MHz

GDT, SAD, w/Series PTC

Terminal block w/compression lugs

Terminals accept up to 10 AWG

-40°C to +85°C

2H x 1W x 2.5L

(PC642 + Base)

1 oz

UL 497B

Features

Three-stage hybrid protection

Sneak/fault current protection

Resettable fuses – PTCs

Low capacitance option

Plug-in module

Requires Edco PCB1B-WKEY base

Fast response time

UL listed 497B

5 year warranty

Caution: The hybrid design of this product includes series resistance. Do not place this product in service on any signal line capable of supplying more than 150 milliamperes continuously.

Installation Instructions

Terminal Assignments

Drawing 2

Drawing 1

Ground Terminal 1 or 10 to Building Approved Ground.

DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes.

Read and Understand These Instructions

Caution:

•These protectors are intended for indoor use on communication loop circuits which have been isolated from the Public Switch

Telephone Network.

•The communication loop circuits shall not be exposed to accidental contact with the electric light or power conductors.

•The protectors shall be installed per the applicable requirements of the National Electric Code, ANSI/NFPA 70.

•Measure DC operating voltage of system to insure it does not exceed the rating of the selected surge device (5-250 VDC depending on the device).

Installation:

1. Turn off power to circuit to be protected prior to installation.

2. Screw mounting base #PCB1B-WKEY (ordered separately) in desired location preferably as close to protected equipment as possible and in close proximity to a building approved grounding point using (2) #4 screws. PCB1B may also be DIN rail mounted using optional

DIN clip assembly #11604KIT-PC (ordered separately).

3. Attach field side pairs (26-10AWG) to positions 3/5 and 7/9, attach electronics side pairs (26-10AWG) to positions 2/4 and 6/8.

Attach ground wire (10AWG) to positions 1 or 10 on base. See Drawing 1. Torque wires to 44 lbf/in [8kgf/cm].

4. Insert PC642C module into keyed PCB1B-WKEY base. See Drawing 2.

5. Apply power to protected circuit.

Ordering Information

How to Specify the Appropriate Model

APPLICATIONS:

RS485, RS422: PC642C-008LC & PCB1B-WKEY

RS232: PC642C-036LC & PCB1B-WKEY

E-NET, 10 BASE T: PC642C-036LC & PCB1B-WKEY

4–20ma: PC642C-036LC & PCB1B-WKEY

OPTION:

DIN Rail Kit Available

Order Part # 11604KIT-PC

Emerson Network Power.

The global leader in enabling

Business-Critical Continuity TM .

AC Power

Connectivity

DC Power

Emerson Network Power Contact information

Headquarters

Surge Protection

100 Emerson Parkway

Binghamton, NY 13905

T: (607) 721-8840

T: (800) 288-6169

F: (607) 722-8713

E: [email protected]

IO-50105 11/13 Rev. 6 Printed in USA

Embedded Computing

Embedded Power

Industrial Power

Infrastructure Management & Monitoring

Outside Plant

Power Switching & Controls

Thermal Management

Racks and Integrated Cabinets

Services www.EmersonNetworkPower.com/surge