C-Bus Bus Coupler with Scenes

5102BCLEDL

5104BCL

Installation Instructions

Clipsal and C-Bus are registered trademarks of Clipsal Australia Pty Ltd

ABN 27 007 873 529.

© Copyright Clipsal Australia Pty Ltd 2008. All rights reserved. This material is copyright under Australian and international laws. Except as permitted under the relevant law, no part of this work may be reproduced by any process without prior written permission of and acknowledgement to Clipsal Australia Pty Ltd.

The information in this manual is provided in good faith. Whilst Clipsal Australia Pty

Ltd (CAPL) has endeavoured to ensure the relevance and accuracy of the information, it assumes no responsibility for any loss incurred as a result of its use.

CAPL does not warrant that the information is fit for any particular purpose, nor does it endorse its use in applications that are critical to the health or life of any human being. CAPL reserves the right to update the information at any time without notice.

C-Bus Bus Coupler with Scenes

Contents

5.0 C-Bus Network Connection

Installation Instructions

5

5

5

6

8

9

9

9

10

11

12

13

3

C-Bus Bus Coupler with Scenes

4

Installation Instructions

C-Bus Bus Coupler with Scenes Installation Instructions

5102BCLEDL C-Bus 2 Channel Bus Coupler with scenes and remote LEDs

5104BCL C-Bus 4 Channel Bus Coupler with scenes

• Do not connect building power to the C-Bus Bus Coupler.

• The input channels of the C-Bus Bus Coupler are NOT isolated from the C-Bus network. Ensure that all cables connected to C-Bus are well separated from mains wiring, earthed metal structures and electrical noise sources.

• A maximum of 1 metre of wire may be used to connect an individual switch or LED to a C-Bus Bus Coupler’s input or indicator terminal.

• A maximum of 10 metres of wire in total may be used to connect switches to all C-Bus Bus Couplers present on an individual C-Bus network. Examples of this are 10 channels at 1000 mm each or 24 channels at 415 mm each. Exceeding this length may adversely affect

C-Bus network communications. If longer connections are required, it is recommended that an L5504AUX C-Bus Auxiliary Input Unit be used.

• Use only non-flashing LEDs with a current rating of at least 10 mA to connect to the 5102BCLEDL’s indicator terminals.

• Dimming operations are best achieved using momentary, normally open switches.

• The use of any software not provided by Clipsal Integrated Systems

(CIS) in conjunction with the installation of this product may void any warranties applicable to the hardware.

3.0 Description

The 5102BCLEDL and 5104BCL C-Bus Bus Couplers are input devices that enable mechanical voltage free switches to connect to a C-Bus network.

Such mechanical switches can then be used in place of regular

C-Bus wall switches to control C-Bus devices such as dimmers and relays, or for use in logical input applications.

5

C-Bus Bus Coupler with Scenes Installation Instructions

Virtually any type of voltage free switch can be connected to the

5102BCLEDL or 5104BCL (momentary or latching). This includes standard wall switches such as the 2000 Series, Heritage, and Slimline range, and specialised switches such as reed and pressure switches.

The 5102BCLEDL provides two input channels and allows the connection of external LED indicators using wired leads. The 5104BCL provides four input channels with built-in LED indicators. Both units feature scene management and learn mode capability.

C-Bus Bus Couplers are designed to fit within a wall box, behind a wall switch. Virtually any type of insulated wire with a diameter between

0.2 mm

2

and 2.0 mm

2

may be used to connect the voltage free switches and LEDs (up to 1 metre of wire per switch/channel/indicator).

The diagram in Figure 1 shows two wiring methods for the 5102BCLEDL.

To minimise the amount of wiring required, a single common wire may be used for the channel inputs (as in the unit on the right).

6

Figure 1 - 5102BCLEDL wiring

C-Bus Bus Coupler with Scenes Installation Instructions

If an indicator is not required the relevant A and K terminals are not connected (nor are they linked together).

The diagram in Figure 2 shows two wiring methods for the 5104BCL. As with the 5102BCLEDL, a single common wire may be used for the channel inputs (as in the unit on the right).

C-Bus

5104BCL with scenes

1 2 3 4

1 C 2 C 3 C 4 C

Channel indicators

5104BCL with scenes

1 2 3

1 C 2 C 3 C 4 C

4

1 2 3 4

Switched channel inputs

Figure 2 - 5104BCL wiring

1 2 3 4

Switched channel inputs

The Common (C) terminals are internally connected to C-Bus negative.

7

C-Bus Bus Coupler with Scenes Installation Instructions

5.0 C-Bus Network Connection

Connection to the C-Bus network is made using the two-terminal connector on the top of the Bus Coupler. Use Cat-5 Unshielded Twisted

Pair (UTP) C-Bus cable. The use of bootlace ferrules (crimps) is recommended for a reliable connection.

C-Bus cable conductor assignments are provided in Figure 3 . The Clipsal catalogue number for the C-Bus Cat-5 UTP cable is 5005C305B.

C-Bus Positive:

blue + orange

C-Bus Negative: blue & white + orange & white

Remote OFF:

brown + brown & white

Remote ON:

green + green & white

Figure 3 - C-Bus cable conductor assignments

Connector pinouts are provided in Table 1 . The Remote ON and Remote

OFF conductors are not connected to this unit.

Terminal C-Bus Connection Conductors

C-Bus Negative (-) orange & white blue & white

C-Bus Positive (+) blue orange

Table 1 - C-Bus connector pinouts

8

C-Bus Bus Coupler with Scenes Installation Instructions

6.0 C-Bus Power Requirements

C-Bus Bus Couplers draw 18 mA from the C-Bus network. Adequate C-Bus

Power Supply Units must be installed to support the connected devices.

The Network window of a C-Bus Toolkit project provides a summary of a

C-Bus network according to the units added to the Database. This can be helpful in determining the power supply requirements of a particular network.

Important points when megger testing an electrical installation:

• Only megger test when mains cabling is disconnected from C-Bus output units.

• Do not megger test the C-Bus cable.

The C-Bus Bus Coupler must be programmed before it will function as part of a C-Bus network. This can be accomplished using Learn Mode. However, using the C-Bus Toolkit software provides a greater level of flexibility and customisation.

The C-Bus Toolkit software can be downloaded from the Clipsal Integrated

Systems web site (www.clipsal.com.au). Further information about programming C-Bus units is provided at this site.

9

C-Bus Bus Coupler with Scenes Installation Instructions

Parameter

C-Bus supply voltage

Description

5102BCLEDL with no LEDs : 25 to 36 V d.c.

5102BCLEDL with both LEDs or 5104BCL : 15 to 36 V d.c.

C-Bus current

C-Bus AC input impedance

Voltage across input

Operating humidity range

18 mA

100 k

Ω @ 1 kHz

External switch open: 5 V d.c.

External switch closed: 0 V d.c.

< 50 μA Current through closed external switch

Isolation between inputs Not isolated

Isolation between inputs and C-Bus Not isolated

Control functions Load switching, dimming, timers

Status indicators (5104BCL) Orange, one indicator per channel

> 10 mA LED current rating (5102BCLEDL)

Warm-up time

Operating temperature range

5 seconds

0 to 45 °C

10 to 95% RH

10

C-Bus Bus Coupler with Scenes

10.0 Mechanical Specifications

Parameter

Dimensions (W×H×D)

Description

55 × 49 × 19 mm

Input terminals

C-Bus connections

Installation Instructions

Spring loaded terminal block accommodating

0.2 to 2.0 mm

2

(24 to 14 AWG)

Terminal block accommodating

0.2 to 1.5 mm

2

(24 to 16 AWG)

49 mm

55 mm 19 mm

11

C-Bus Bus Coupler with Scenes Installation Instructions

11.0 Standards Complied

DECLARATIONS OF CONFORMITY

Australian/New Zealand EMC & Electrical Safety Frameworks and Standards

Model 5102BCLEDL and 5104BCL products comply with the following:

Regulation Standard Title

EMC (C-Tick) AS/NZS CISPR 14-1 Electromagnetic compatibility –

Requirements for household appliances, electric tools and similar apparatus – Part 1:

Emissions

AS/NZS CISPR 15 Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment

European Directives and Standards

Model 5102BCLEDL and 5104BCL products comply with the following:

Standard Title European

Council Directive

EMC Directive

204/108/EC

EN 60669-2-1 Switches for Household and

Similar Fixed Electrical

Installations Part 2-1

Other International Directives and Standards

Model 5102BCLEDL and 5104BCL products comply with the following:

Title

EMC 60669-2-1 Switches for Household and Similar Fixed

Electrical Installations Part 2-1

CISPR 14-1

CISPR 15

Electromagnetic compatibility – Requirements for household appliances, electric tools and similar apparatus – Part 1: Emissions

Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment

12

C-Bus Bus Coupler with Scenes Installation Instructions

12.0 Warranty

5102BCLEDL and 5104BCL C-Bus Bus Couplers carry a two-year warranty against manufacturing defects.

Warranty Statement

1) The benefits conferred herein are in addition to, and in no way shall be deemed to derogate; either expressly or by implication, any or all other rights and remedies in respect to Clipsal Integrated Systems

Product, which the consumer has under the Commonwealth Trade

Practices Act or any other similar State or Territory Laws.

2) The warrantor is Clipsal Australia Pty Ltd. with registered offices in all

Australian States.

3) This Clipsal Integrated Systems Product is guaranteed against faulty workmanship and materials for a period of two (2) years from the date of installation.

4) Clipsal Australia Pty Ltd reserves the right, at its discretion, to either repair free of parts and labour charges, replace or offer refund in respect to any article found to be faulty due to materials, parts or workmanship.

5) This warranty is expressly subject to the Clipsal Integrated Systems

Product being installed, wired, tested, operated and used in accordance with the manufacturer's instructions.

6) All costs of a claim shall be met by Clipsal Australia Pty Ltd, however should the product that is the subject of the claim be found to be in good working order, all such costs shall be met by the claimant.

7) When making a claim, the consumer shall forward the Clipsal

Integrated Systems Product to the nearest office of Clipsal Australia

Pty Ltd with adequate particulars of the defect within 28 days of the fault occurring. The product should be returned securely packed, complete with details of the date and place of purchase, description of load, and circumstances of malfunction.

For all warranty enquiries, contact your local Clipsal sales representative.

The address and contact number of your nearest Clipsal Australia office can be found at http://www.clipsal.com/locations or by telephoning

Technical Support (refer to the back page).

13

C-Bus Bus Coupler with Scenes

This page is left blank for formatting purposes.

14

Installation Instructions

C-Bus Bus Coupler with Scenes

This page is left blank for formatting purposes.

Installation Instructions

15

Technical Support and Troubleshooting

For further assistance in using this product, consult your nearest Clipsal

Integrated Systems (CIS) Sales Representative or Technical Support

Officer.

Technical Support Contact Numbers

Australia 1300 722 247 (CIS Technical Support Hotline)

New Zealand

Northern Asia

South Africa

Southern Asia

United Kingdom

0800 888 219 (CIS Technical Support Hotline)

+852 2484 4157 (Clipsal Hong Kong)

011 314 5200 (C-Bus Technical Support)

+603 7665 3555 Ext. 236 or 242 (CIS Malaysia)

0870 608 8 608 (Schneider Electric Support)

Technical Support email: [email protected]

Product of Clipsal Australia Pty Ltd

A member of Schneider Electric

Contact us: clipsal.com/feedback

National Customer Service Enquiries

Tel 1300 2025 25

Fax 1300 2025 56

clipsal.com

Clipsal Australia Pty Ltd reserves the right to change specifications, modify designs and discontinue items without incurring obligation and whilst every effort is made to ensure that descriptions, specifications and other information in this catalogue are correct, no warranty is given in respect thereof and the company shall not be liable for any error therein.

© Clipsal Australia Pty Ltd.

The identified trademarks and copyrights are the property of Clipsal Australia Pty Ltd unless otherwise noted.