Wheelock SP4-RMX Specifications

Add to my manuals
12 Pages

advertisement

Wheelock SP4-RMX Specifications | Manualzz

SPMNS

SPMNS-MIC

SPMNS

SAFEPATH

®

Mass Notification System & Expansion Options

SAFEPATH

®

Mass Notification System (MNS)

SAFEPATH

®

MNS Microphone

POWERPATH™ Notification Appliance Circuit (NAC)

Power Supplies

Page 2

Page 4

Page 4

Expansion Options

SAFEPATH

®

Audio Boosters

SAFEPATH

®

2-Zone Class A or 4-Zone Class B

Page 6

Speaker Audio Splitter Page 6

Notification

PS-6 & PS-8

SPB-80/4, SPB-160, SPB-320

SPAZ-A/B

®

U

L

S5361

SAFEPATH

®

Mass Notification System (SPMNS)

SPMNS

Notification

Description

Cooper Notification’s SPMNS is an In-Building MNS for fire alarm, emergency communications and voice evacuation with 24 VDC battery back up. It provides personnel and building occupants with clear, concise and intelligible voice messages that communicate how people should respond to a variety of emergency situations.

The SPMNS, which meets UL 2572 requirements for MNS, interfaces with a building fire alarm system (FAS) to provide a complete In-Building

MNS. An integral part of the fire system, the SPMNS controls all audio and visual notification appliances for both fire and MNS and reports trouble and supervisory signal through the FAS. Supervised voice speakers controlled by the SPMNS can be used for both fire and emergency communication applications.

The SPMNS single channel system is capable of delivering 40 watts of supervised high fidelity audio power and 2 amps of supervised 24 VDC synchronized strobe power. It comes standard with an on-board digital voice messaging system with 8 standard messages, a hand-held microphone for fire messages, power supply/battery charger and numerous additional features. A dedicated MNS microphone (SPMNS-MIC) will be utilized for live voice messages for emergency communications. The SAFEPATH system is expandable to 5280 watts utilizing the SPB-80/4 (80 watts and 4 amps of strobe power), the SPB-160 (160 watts) or SPB-320 (320 watts) supervised audio power boosters. All models available in 115 VAC or 220 VAC.

Applications for the SPMNS

• Multi-use applications—The system can function as an evacuation system, an emergency messaging system, and an employee notification system

• Fire code applications—The system is listed under UL 2572 for MNS, UL

Standard 864, 9th edition delivering supervised audio and voice messaging with strobes and notification appliance circuits (NAC) for visual alerting

• Economic OSHA applications—The system is OSHA 1910.165 compliant; this means that it does not require reliability inspections every two months, or the required spare parts inventory

• Wide ranging applications—from small to large facilities

System Activation

• Contact closure message activation

Benefits and Advantages

• One Supervised, Multi-Function, Voice Fire Alarm/Emergency

Communications System

• Interfaces with addressable FAS

• Built in power for visual notification appliances e.g., Strobes

• Expandable for larger system requirements

(with optional equipment)

• Controls audio and visual notification appliances for both fire and MNS

• Voice speakers can be used for both fire and emergency communication applications

• Reports trouble and supervisory signal for both the FAS and MNS.

2

Features

Approvals & Compliance

• Approvals: UL 2572 for MNS, UL Standard 864, 9th edition, UL Standard 1711

• OSHA 1910.165 and ADA Compliant

• 1 Year Warranty

Voice Messages

• Complies to NFPA-72 requirements

• Supervised NAC speaker and strobe circuits

• Live microphone override

• 5 digitally pre-recorded MNS voice messages

• 3 digitally pre-recorded fire voice messages

• User selectable pre-tones for fire messages

• Flexible, field-programmable messaging capabilities

Strobe Inputs and Activation

• 2 Amps of 24 VDC supervised strobe power with built-in Wheelock sync protocol. Power limited.

• Strobe output is selectable for control of Wheelock sync protocol or non-sync operation

• Strobe terminals have pass thru capability for Wheelock sync or non-sync operation

• 24 VDC supervised and synchronized strobe power can be expanded to meet the requirements of the installation via connecting to optional Wheelock power boosters

Speaker Output

• 40 watts of supervised audio power

• Speaker outputs: 25V or 70.7V power limited

Audio Processing

• Connectivity of optional speaker splitter modules

• Dual-tone tone generator with: Code 3 Tone and Slow Whoop for alerting of system trouble

• Audio power can be expanded by connecting to optional audio power boosters

- SPB-80/4 80 Watt Supervised Audio Power Booster with 4 Amp of Synchronized Strobe Power

- SPB-160 160 Watt Supervised Audio Power Booster

- SPB-320 320 Watt Supervised Audio Power Booster

Live & Pre-recorded Message Announcement

• Supplied with 8 pre-recorded emergency messages

• Capable of in-field recording of all messages via 1/8” line level audio input jack

• On board Push-to-Talk Fire Microphone

• Dedicated MNS Microphone

Installation/Maintenance

• Multiple trouble LED indicators for quick system diagnostics

• Fully supervised circuitry always in effect (via patent pending technology)

• Removable quick connect/disconnect terminals for ease of wiring, accepts

#12 to #22 AWG

• Power limited circuitry with Class “B” or Class “A” wiring. Class “A”

only with use of Audio Splitter

• Surge protected circuitry

Inputs – Audio and Activation

Priority Ordered Inputs

Auxiliary Microphone

Digital Message Input 1

Digital Message Input 2

Digital Message Input 3

Digital Message Input 4

Digital Message Input 5

On Board Microphone

Digital Message Input 6

Digital Message Input 7

Digital Message Input 8

Priority

Level

1

2

3

8

9

10

6

7

4

5

Type of Input

MNS Microphone

Contact Closure activation

Fire Microphone

Contact Closure activation

Power Supply & Batteries

• 24 VDC, 33AH Max rechargeable battery back-up power circuitry built-in

• Batteries can be housed in the enclosure(Up to two BAT-1212, 12 volt,

12 ampere hour batteries can fit in the enclosure). Actual battery size required will depend on speaker and/or strobe load. Batteries are sold separately.

Compatible Cooper Notification Products

All Wheelock Appliances Wheelock Strobe Power Supply

Voice Message Priority

The SPMNS will override the FAS with live voice from a separate MNS microphone or manual activation of a high-priority emergency message. After the

SPMNS relinquishes control, the following occurs:

1. Without an active fire alarm signal, the fire alarm system shall automatically restore to normal operation

2. With an active fire alarm signal, the fire alarm shall operate based on the

Emergency Response Plan (ERP)

The fire alarm signal deactivation function occurs only when both the FAS is in alarm condition and an MNS voice message is initiated by the SPMNS. When the fire alarm notification is overridden by the SPMNS priority emergency message, all other features of the FAS remain unaffected.

Priority messaging is as follows:

- Live voice messages from the MNS microphone

- Pre-recorded prioritized mass notification messages

- Live voice messages from the fire microphone

- Pre-recorded fire messages

Audio/Technical Specifications

Switch mode, Class D amplifier (40 Watts)

Speaker Outputs 25V or 70.7V power limited

Frequency Response

Signal to Noise Ratio

Dynamic Range

Total Harmonic Distortion

Stand by Current Draw

Alarm Current Draw

Voice: 275 Hz – 6.5 kHz

Meets UL Voice Evacuation

Requirements of 800 - 2800 Hz better than 65 dB better than 65 dB less than 2%

130 mA

4.7 amps

Mechanical

Dimensions

Weight

Finish

Door Lock

21” H x 16” W x 6” D

(wall mount)

36 lbs.

(without batteries)

Red exterior enclosure

Key-lock

Message Capabilities

Message and

Priority #

MNS/Fire

1 MNS

2

3

MNS

MNS

MNS

MNS

Voice

Type

Message Script

Male

Male

Three (3) seconds of 1kHz of tone (followed by): ATTENTION: There is an emergency in the building. Evacuate the building in an orderly fashion. Follow all instructions given by emergency responders.

Three (3) seconds of 1kHz of tone (followed by): ATTENTION: A severe weather conditions exist – Seek shelter immediately until further notice.

Male

Three (3) seconds of 1kHz of tone (followed by): ATTENTION: Hazardous Material Warning; Shut down all heating, ventilation, and air conditioning systems; Seek cover immediately away from doors and windows. Stay where you are until contacted by local authorities.

Female ATTENTION: The building emergency has ended. An all clear has been given. Please resume normal activities.

4

5

6

7

8

Fire

Fire

Fire

Male

Male

Male

May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Do not use the elevators.

May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Do not use the elevators.

Five (5) seconds of 1kHz tone (followed by). May I have your attention please! This is a test of the Mass Notification System, repeat, this is only a test.

• Each message can be selected to have a code 3 pre-alert tone, a 1kHz continuous pre-alert tone, or no pre-alert tone

• Post-tones are also selectable and match the pre-tones for individual messages

• Any of the 8 messages are field programmable to record your own custom message

• Each message length is 30 seconds

• A 1/8” line level audio input jack is supplied for message recording

• A two step recording procedure is required to ensure and verify that the standard message will be permanently erased

• Factory programmed messages are available for custom messages

• Contact customer service for additional information

• Form is required and can be downloaded from www.coopernotification.com

3

Notification

POWERPATH™ NAC POWER SUPPLIES

SAFEPATH

®

MNS Microphone

SPMNS-MIC

PS-EXP

4

PS-6 PS-8

Description

MNS Microphone for use with the SAFEPATH

SPMNS

Mass Notification System -

Applications

• Provides dedicated microphone for mass notification and emergency

communications applications

Features

• Approvals: UL 2572 for MNS, UL Standard 864, 9th edition and

California State Fire Marshal (CSFM)

• UFC 04-021-01 Compliant

• Supervised hand held push to talk microphone

• Key required to enable microphone use

• Individual front panel LED indication for; System

Normal, System Trouble and Alarm

• When used with the SPMNS, the priority level of the SPMNS-MIC is 1, the SPMNS on-board fire microphone is a lower priority

• Voice frequency response: 275 Hz - 6.5 kHz

• Requires 24VDC, supplied by the SPMNS, Audio

Boosters, or SP4-RMX

• Input current: Standby: 23mA

Alarm: 30mA

• Audio output level: 1.05V RMS

• 6 wire connection to the SPMNS

• Mounting plate is black and measures, 8 3/4” x 5 ¼”, fits into a 4 gang back box

• All output circuitry is Power Limited

®

U

L

THE CITY OF

NEW YORK

DEPARTMENT OF BUILDINGS

Model

Description

Cooper Notification’s POWERPATH Power Supplies PS-6 and PS-8 are 24VDC, filtered and regulated, supervised remote power supplies/battery chargers. Used for supervision and expanded power driving capability of Fire Alarm and Mass

Notification Appliance Circuits, PS-6 provides 6 amps of power distributed across

4 outputs, while the PS-8 provides 8 Amps across 4 outputs. In addition, the

PS-8 provides additional room in the chassis for accessories like an Addressable

Control Module, with mounting studs.

The Power Supplies may be connected to any 12V or 24V (FWR or DC) Fire

Alarm Control Panel (FACP) by using a Notification Appliance Circuit (NAC) or a “Dry Contact”. Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 24VDC, up to four (4) Class “B”, two (2) Class

“A”, or two (2) Class “B” and one (1) Class “A” Notification Appliance Circuits.

With the optional plug-in PS-EXP module the unit supports (8) Class “B” or (4)

Class “A” Notification Appliance Circuits. Additionally, an auxiliary power output of 2.5 Amps (disconnected upon AC power loss or an alarm condition) or up to

0.240 A of constant power on the PS-8 .

The Wheelock Power Supply can accommodate 7 or 12 AH batteries inside its lockable chassis. Using an external battery cabinet, it can charge up to 33 AH batteries (pending UL testing). Two FACP NAC circuits or two “Dry” contact initiating circuits can be connected to the inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs. Each output is rated at 3.0 Amps (Class “B”) or (Class “A”) and can be programmed to generate a steady or Code 3 Temporal Horn sound and a strobe output under alarm condition. Total load for PS-8 NAC circuits must not exceed the power supplies rated output.

The Power Supplies under non-alarm condition provides independent supervision for Class “A” and Class “B” FACP NAC circuits. In the event of circuit trouble, the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are two sets of trouble reporting terminals, one used for AC power loss reporting and the other for all troubles. The AC power loss reporting, on the common trouble terminals and on IN1 or IN2, can be delayed for either 30 seconds or 170 minutes. The AC power loss terminals will always report the trouble within 1 second after loss of AC power.

The PS-6 and PS-8 Power Supplies are UL Listed under UL 2572 for MNS and UL Standard 864, 9th Edition to be used with any 24 volt listed regulated notification appliances. They include the capability to synchronize Wheelock strobes and horns and to silence the horn signal when horn/strobes are operating on two wires.

Approvals

• Approvals Include: UL 2572 for MNS, UL Standard 864,

1481, California State Fire Marshal (CSFM), Factory Mutual (FM)

• Pending: New York City (MEA), Chicago (BFP) See Approvals by model in Specification and Ordering Information

• Compliant with NFPA 72

Dimensions Weight Comments

PS-6/PS-6B 17”H x 13”W x 3.5”D 11.5lbs (Ship) 9.4lbs (Unit) Small profile

151.92-E

PS-8 17”H x 15”W x 5.5”D 17.7lbs (Ship) 15.6lbs (Unit) Additional room for modules

PS-EXP 4.3”H x 3.7”W x 1”D 1lb. (Ship & Unit) Plugs into main pcb on all models

PS-EXP

Inputs

• 120VAC, 50/60Hz, 4.25 Amps and 5.32 Amps Operating Power in Alarm

• 240VAC, 60Hz, 3.22 Amps (PS-8E) Operating Power in Alarm

• 24VDC Battery Backup Connection

• Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA) FWR or DC

• Two (2) “Dry” Contact initiating Circuits

• Accepts two (2) Class “A” or two (2) Class “B” circuit inputs

• Built in battery charger for sealed lead acid or gel type batteries

Outputs

• NAC outputs are 24VDC, 3.0 Amps each, power limited

• 8 Amps on total alarm current

• Capable of four (4), Class “B” circuits

• Capable of two (2) Class “A” circuits

• Capable of one (1) Class “A” circuit and two (2) Class “B” circuits

• Capable of (8) Class “B” or four (4) Class “A” circuits with optional

PS-EXP module

• Temporal (Code 3), constant voltage output, Wheelock Sync output or

True input to output follower mode

• Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits

• Input and output can be synchronized with “IN>OUT SYNC” mode

(SM, DSM, 2nd POWERPATH™ or FACP with synchronization protocol is required)

• Audible silence capability

• Filtered and electronically regulated output

• 2.5 Amp auxiliary power limited output with reset capability

(Removed upon AC loss or alarm. Automatic reset 30 seconds after

AC power returns or the alarm condition is over) 0.240 Amps of auxiliary power limited output which remains on during AC loss or an alarm condition when configured for 24 hour battery backup

Supervision

• Compatible with 12V or 24V (FWR or DC) FACP

• Signaling appliance circuits are supervised and steered to either IN1 or IN2

• 10K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor

(EOLR) for supervision of all outputs

• 37 distinguishable trouble diagnostics

• AC loss trouble reported over a separate set of contacts (delay of 1 second)

• All troubles are reported over the common trouble contacts (AC loss can have a delay of 30 seconds or 170 minutes)

Specifications and Ordering Information

Model Number Order Code

• Automatic switchover to standby battery when AC fails

• Thermal and short circuit protection with auto reset

• Input and output status LED indicators

• AC fail supervision

• Battery presence and low battery supervision

• Ground Fault Detection, with diagnostics to indicate which circuit fault is on

• Latching LED’s for NAC trouble annunciation and Diagnostic trouble LED’s (latching can be disabled)

Power

• Not Battery Dependent

• Automatic switch over to standby batteries when AC fails

• Supports sealed lead acid or gel type batteries

• Fused battery protection

• Thermal and short circuit protection with auto reset

• Supports both 7AH or 12AH batteries in the same cabinet

POWERPATH™ Operating Modes

(refer to Installation Manual):

Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening on DRY1 or DRY2. The unit returns to standby mode when the input is deactivated.

Wheelock Sync Mode: Provides signals for synchronization of patented

Wheelock audible and strobe notification appliances. Audibles can also be silenced in this mode while the strobes continue to flash.

In>Out Sync Mode: Accepts a synchronization signal on the input to provide a coded output or synchronized output. This signal may come from a FACP, another POWERPATH or a Wheelock SM or DSM synchronization module.

Caution: Do not use strobes on coded output circuits.

True Input Follower Mode: Accepts a coded signal on the input to provide a coded output with the same timing as the input. The signal may come from a FACP, another POWERPATH or other coded source. Caution: Do not use strobes on coded output circuits.

Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible appliances such as horns, bells or chimes. Caution: Do not use strobes on coded output circuits.

Input Voltage/Current

PS-6

PS-8

PS-6EXP

PS-8EXP

PS-EXP

PS-EXP-RETRO

Input Circuit

Input voltage Range

105530

105531

105083

106084

105534

105527

6 Amp, red enclosure

8 Amp, red enclosure

6 Amp power supply with preinstalled expansion module

8 Amp poswer supply with preinstalled expansion module

4 class B or 2 class A expansion module

Field upgrade kit for models prior to January 2010 #

Input Voltage and Current

8 to 33 VDC

Input Current @ 12 VDC 0.005 Amps

Input Current @ 24 VDC

Output Circuit

Four (4) Class B or

Two (2) Class A or

One (1) Class A and Two (2) Class “B” or

8 Class B or 4 Class A (optional PS-EXP module necessary)

Continuous duty up to 3 Amps per circuit, up to 4 Amps maximum per panel

Standby Current

Alarm Current

Primary PS-6 (120 VAC models)

Primary PS-8 (120 VAC models)

Primary PS-8E (240 VAC models)

Secondary Power Charging Capacity

0.005 Amps

Output Voltage and Current

24 VDC @ up to 3 amps per curcuit

0.129 Amps

0.129 Amps

Enclosure can house up to two 12 AH batteries

105 to 130 VAC, 50/60 Hz @ 4.25 Amps

105 to 130 VAC 50/60 Hz @ 5.32 Amps

210 to 260 VAC 50/60 Hz @ 3.22 Amps

32 Amp hours @ 0.750 Amps per hour

Aux Output

CP Mode

MP Mode 2.5A during non alarm

PS-8 up to 250 mA

Approvals

UL CSFM

X X

X

X

X

X

X

X

X

X

X

X

X= Approved

*= Pending

#=Contact

Technical

Support for additional inforamation on upgrade options

5

SAFEPATH

®

2-Zone Class A or 4-Zone Class B

Speaker Audio Splitter

SP4Z-A/B

Notification

SAFEPATH

®

Audio Boosters

SPB-320 - 320 Watt Supervised Audio Power Booster (Four 80 watt circuits)

SPB-160 - 160 Watt Supervised Audio Power Booster (Two 80 watt circuits)

SPB-80/4 - 80 Watt Supervised Audio Power Booster with 4

Amps of Supervised and Synchronizable Strobe Power (Two 2

Amp circuits)

SPB-320

SPB-80/4

SPB-160

Description

Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the

SPMNS or Audio Boosters. Enables a single supervised speaker audio output to drive up to two Class A supervised speaker audio outputs or four Class B supervised speaker audio outputs.

Applications

• Provides for expansion of one zone to up to 2 zones of supervised speaker audio output in Class A

• Provides for expansion of one zone to up to 4 zones of supervised speaker audio output in Class B

Features

• Approvals: UL 2572 for MNS, UL Standard 864, 9th edition, and

California State Fire Marshal (CSFM), New York City (MEA)

• UFC 04-021-01 Compliant

Expands one zone to up to 2 zones of supervised speaker audio output in Class A

Expands one zone to up to 4 zones of supervised speaker audio output in Class B

• Each Class A zone can accept up to 40 watts of audio

Each Class B zone can accept up to 40 watts of audio

Operates on either 25V or 70.7V RMS

Mounts inside the enclosure of the SPMNS or Audio Boosters

Power and Trouble LED’s

Individual zone short and open LED indication

Capable of detecting wiring faults

Removable wiring terminals for quick connect/disconnect accepting

12–22 AWG

All output circuitry is Power Limited

Space provided to allow for naming of the zones

Powered by 24VDC, supplied by the either the SPMNS or Audio

Boosters

Standby and Alarm current at 24VDC is 15mA

Description

Supervised Facility Communication and Emergency Voice Evacuation Audio and

Audio/Strobe Power Boosters, UL 2572 for MNS, UL Standard 1711 and UL Standard

864, 9th edition with 24VDC battery backup capabilities. Designed to provide for additional supervised audio power for live voice or pre-recorded messages. Fully supervised patent pending circuitry is always in effect. The SPB-80/4 also provides

4 Amps of 24 VDC Supervised and Synchronized Strobe Power.

The SPB-320, SPB-160 and the SPB-80/4 easily connects to the Cooper Notification

SPMNS. Multiple SPB-320, SPB-160 and SPB-80/4 Audio Boosters can be interconnected to accommodate large installations with supervised audio power and also supervised and synchronized strobe power requirements.

The SPB-320 draws 2.4 watts of audio input power to properly operate and provide additional supervised audio output power. The SPB-160 and the SPB-80/4 draws

1.2 watts of audio input power to properly operate and provide additional supervised audio output power. A maximum of 5,280 watts of supervised audio power can be achieved. Additional strobe power can be obtained via a combination of SPB-80/4 or Wheelock Power Supplies/Chargers.

Applications

• Provides for additional supervised audio power for large installations

• Provides for additional supervised and synchronizable strobe power for large installations

• Can be used in new construction as well as in retrofit construction

Features

Approvals & Compliance

• Approvals: UL 2572 for MNS, UL Standard 864, 9th edition, UL

Standard 1711, California State Fire Marshal (CSFM), New York City (MEA)

• OSHA 1910.165, ADA and UFC 04-021-01 Compliant

• 1 Year Warranty

System Activation: Audio

70V or 25V input from the SPMNS

• 1 Volt input from SP4-RMX

System Activation: Strobe (SPB-80/4)

• 8 - 33VDC NAC input connected to the strobe input

6

Power Supply & Batteries

• Fully supervised patent pending circuitry always in effect

• Power limited circuitry

• Class D amplifiers

• Internal battery charger and power supply

• Required batteries fit inside the enclosure (sold separately)

• SPB-320 requires four 12 VDC, 12 AH batteries

• SPB-160 and SPB-80/4 require two 12 VDC, 12 AH batteries

Outputs

• SPB-320 has four 80 watt speaker output circuits

• SPB-160 has two 80 watt speaker output circuits

• SPB-80/4 has one 80 watt speaker output circuit and two 2 amp strobe circuits (4 amps total)

• Supervised Audio Speaker outputs: 70V or 25V field selectable (all boosters must be either 70 V or 25 V)

• Expansion output (supervised, 24VDC at .5A in alarm condition used for connecting multiple boosters

• DC output (unsupervised for optional splitter power). Each speaker circuit (four for the SPB-320, two for the SPB-160, one for the SPB-80/4) can connect to speaker splitters

SPB-80/4 Strobe Features

• Two 24VDC 2 Amps, NAC supervised, synchronizable, power limited, Class B strobe outputs

• Selectable outputs: Wheelock sync, pass through, or constant DC

• Trouble LED’s for open and short output conditions

• Alarm indicator: LED’s for Strobe and Expansion Outputs

Inputs

• Audio Speaker Inputs: 70V or 25V, field selectable

• Auxiliary in (for alarm input signal)

Mechanical

SPB-160, SPB-80/4

• Dimensions: 21” H x 16” W x 6” D (wall mount)

• Weight: 36 lbs. (without batteries)

• Finish: Red exterior enclosure

• Door Lock: Wheelock key-lock

SPB-320

• Dimensions: 36” H x 24” W x 6” D (wall mount)

• Weight: 80 lbs. (without batteries)

• Finish: Red or black exterior enclosure

• Door Lock: Wheelock key-lock

Technical Specifications

• 120VAC, 3.8A, 60 Hz input

• SPMNS Models 240 VAC, 2.5A, 50-60 Hz

• Standby current draw:

120mA per amplifier board

• Alarm current draw:

9 Amps per amplifier board

SPB-80/4 and SPB-160 have one amplifier board

SPB-320 has two amplifier boards

• System Frequency Response:

Voice 400 Hz - 6.5 kHz

• Removable quick connect/disconnect terminals, accept 12 - 22 AWG

• Multiple LED’s for easy indication of system diagnostic conditions

• Signal to Noise Ratio: > 70 dB

• Dynamic Range: > 65 dB

• Total Harmonic Distortion: 2%

Note: The Speaker Splitter-Mounting Bracket (SPMB4Z) is required when the Speaker Splitter is used in Audio Boosters.

The SPMB4Z can support two splitters.

Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters’ Laboratories

(UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).

NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper

Wheelock, Inc. dba Cooper Notification standard terms and conditions.

Note: Refer to the products Installation Instructions for proper installation, wiring procedures and any additional specifications.

7

8

Notification

SYSTEM COMPONENTS

Fire/MNS Speakers

SPB-160

EXPANSION OPTIONS

Fire/MNS Speakers

SPB-320

FIRE MICROPHONE

SPMNS-MIC

SPMNS

Addressable FACP

PS-8

Fire Alarm / MNS Solution

ALERT ALERT

ALERT

Fire

Strobes

MNS

PS-8

Cluster Speaker

ALERT ALERT

ALERT

Fire

Strobes

MNS

Notification

SYSTEM COMPONENTS

Fire/MNS Speakers

SPB-160

EXPANSION OPTIONS

Fire/MNS Speakers

SPB-320

FIRE MICROPHONE

SPMNS-MIC

SPMNS

Cluster Speaker

Addressable FACP

PS-8

Fire Alarm / MNS Solution

ALERT ALERT

ALERT

Fire

Strobes

MNS

PS-8

ALERT ALERT

ALERT

Fire

Strobes

MNS

Some devices here may not meet UL Standards for MNS. Consult your Cooper Notification Sales

Manager for details.

9

Notification

Ordering Information

Model Number Description

SPMNS

SPB-320

SPB-160

SPB-160-B

SPB-80/4

SPB-80/4-B

SP4Z-A/B

SPMB4Z

SPMNS-MIC

PS-6

PS-8

BATC-R

BATC-B

BAT-1212

BAT-1224

BAT-1265

In-Building Mass Notification, Messaging, and Emergency Voice Evacuation System with 24 VDC battery backup circuitry.

Single channel system with 40 watts of supervised audio power and 2 amps of supervised 24 VDC synchronized strobe power and 8 standard message, (Batteries not included, 2 required) red enclosure

320 Watt Supervised Audio Power Booster (Four 80 watt circuits)

160 Watt Supervised Audio Power Booster (Two 80 watt circuits), red enclosure

160 Watt Supervised Audio Power Booster (Two 80 watt circuits), black enclosure

80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), red enclosure

80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), black enclosure

Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SPMNS, SP40/2, SPB-320, SPB-160 or

SPB-80/4

Speaker Splitter Mounting Bracket for SPB-320, SPB-160 or SPB-80/4

Mass Notification Microphone for use with the SPMNS, black plate

6 Amp Supervised Remote Power Supply, 24VDC

8 Amp Supervised Remote Power Supply, 24VDC

Battery Cabinet, Red

Battery Cabinet, Black

12 Volt, 12 Ampere Battery Cell

12 Volt, 24 Ampere Battery Cell

12 Volt, 65 Ampere Battery Cell

10

Architects and Engineers Specifications

SAFEPATH

®

Mass Notification System

The system shall be a multi-purpose NFPA compliant, supervised, fire/emergency communications system and shall interface with a building fire alarm system

(FAS) to provide a complete In-Building MNS. The system shall control all audio and visual notification appliances for both fire and MNS and report trouble and supervisory signal through the FAS. The system shall be capable of delivering 40 watts of supervised audio power and 2 amps of supervised 24 VDC synchronized strobe power. Minimum supervised audio power shall be 40 watts, expandable to 5280 watts, depending on system configuration and with additional modules and power boosters. Supervised 24 VDC synchronized strobe power shall be 2 amps, expandable to the requirements of the installation. The system shall be capable of operating from a 120 VAC power source. SPMNS shall be capable of operating from a 240 VAC power source. All models shall have a 24 VDC battery backup. Standard on-board system features shall include: digital voice messaging, a hand-held push-to-talk microphone with override priority, and a power supply/battery charger. Form C contacts shall be provided for system alarm and trouble conditions.

The system shall have 8 message contacts with contact closure activation. The system shall have 10 priority ordered inputs, including: On Board Microphone,

Auxiliary Input (Line Level), and 8 Digital Messages. The system shall have preset audio levels for emergency messaging (prerecorded and live mic). The system shall be supplied with 8 pre-recorded messages and be capable of in-field recording of customer unique messages. The system shall have a dual-tone tone generator with Code-3 Tone and Slow Whoop.

The panel shall have power-limited circuitry with an internal battery charger and power supply. The power supply/charger section shall be able to charge 24 VDC batteries with a maximum capacity of 33 amp hours. Up to two 12 VDC, 12 AH batteries may be housed in the enclosure. Batteries larger than 12 Ah shall be housed in a separate enclosure such as the Cooper Wheelock BATC or equivalent. Batteries shall be supplied separately.

The system shall have power limited circuitry and class B wiring. Wiring terminal blocks will be removable and accept #22 - #12 AWG wire. Audio output voltage shall be selectable for 25V or 70.7V. The voice (live microphone or recorded message) frequency response shall be 275 Hz – 6.5 kHz. Stand by current draw shall be 140mA. Alarm current draw shall be 4.7 amps. The signal to noise ratio shall be better than 65 dB, dynamic range shall be better than 65 dB, total harmonic distortion shall be less than 2%.

The system shall be wall mountable, enclosed in a steel locking enclosure. The required batteries for 40-watt systems shall fit inside the enclosure. The 40 watt system shall weigh no more than 36 lbs (without batteries) and its dimensions shall not exceed 21” H x 16” W x 6” D. Approvals for the system shall include: UL

Standard 864, 9th edition, UL 2572 for MNS, and UL Standard 1711. The system shall be OSHA 1910.165, and ADA compliant. 1 Year Warranty.

Wheelock POWERPATH™ Series PS-6

The power supply shall be Wheelock POWERPATH™ Series PS-6, or equivalent. The unit shall be stand alone power supply intended for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 2572 for MNS and UL 864 Listed for power limited operation of outputs and comply with NFPA 70 (NEC), article 760.

The power supply shall support a full 6A of notification power even if the battery is in a degraded mode and only AC power is connected.

The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a“Dry contact” opening. The units shall be 6 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall operate over the voltage range of 8 to 33 VDC or FWR.

The primary application of the unit shall be able to expand fire alarm system capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories or functions. The power supply shall provide four Class “B”, two Class “A”, or two Class “B” and one Class “A”

NAC circuit(s). Eight Class “B” or Four Class “A” circuits shall be available with an optional PS-EXP module. The PS-6 unit shall supply up to 200 mA of auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm.The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at a maximum rate of 0.750 Amps per hour.

Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability ofbeing directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class “B”applications or 3 amperes each for Class “A”. The outputs shall be programmable to generate a steady or Temporal (Code 3) outputand or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class “A” or Class “B” FACP NAC circuits and shall have the capability to “steer” all alarm or trouble conditions to either incoming NAC circuit. The units shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of xx amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby current for battery back up shall be 0.130 Amps max. The power supply shall have the ability to latch trouble LED’s so the circuit in trouble can be identified. The cabinet dimensions shall be 17” H x 13” W x 3.5” D.

Wheelock POWERPATH™ Series PS-8

The power supply shall be Wheelock POWERPATH™ Series PS-8, or equivalent. The unit shall be stand alone power supply intended for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 2572 for MNS, UL 864 Listed for power limited operation of outputs and comply with NFPA 70 (NEC), article 760.

The power supply shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power is connected.

The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a “Dry contact” opening.

The units shall be 8 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall operate over the voltage range of 8 to 33 VDC or FWR. The primary application of the unit shall be able to expand fire alarm system capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories or functions. The power supply shall provide four Class “B”, two Class “A”, or two Class “B” and one

Class “A” NAC circuit(s). Eight Class “B” or Four Class “A” circuits shall be available with an optional PS-EXP module. The PS-8 unit shall supply up to 240 mA of auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm. The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at maximum rate of 0.750 Amps per hour.

Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class “B” applications or 3 amperes each for Class “A”. The outputs shall be programmable to generate a steady or Temporal (Code 3) output and or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class “A” or Class “B” FACP NAC circuits and shall have the capability to “steer” all alarm or trouble conditions to either incoming NAC circuit. The units shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of xx amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby current for battery back up shall be 0.129 Amps max. The power supply shall have the ability to latch trouble LED’s so the circuit in trouble can be identified. The cabinet dimensions shall be 17” H x 15” W x 5.5” D.

11

Architects and Engineers Specifications

SAFEPATH MNS Microphone

The Mass Notification Microphone shall be UL 2572 for MNS, UL Standard 864, 9th edition and California State Fire Marshal (CSFM) approved for use with the Mass Notification System.

The Mass Notification Microphone shall be a supervised microphone used for live voice emergency communication messages. When used with the SAFEPATH Mass Notification System, the Mass Notification Microphone shall have the capability to override the fire microphone and any fire pre-recorded messages. All output circuitry shall be power limited. Multiple on board diagnostic LED indicators shall be provided. All wiring shall be capable of accepting 12 – 22 AWG wiring.

SAFEPATH

®

Audio Boosters

The Wheelock SPB-320, SPB-160 and SPB-80/4 Audio Boosters shall be NFPA compliant supervised audio and supervised 24VDC synchronized strobe power boosters (some models will have supervised 24VDC synchronized strobe booster capability). The booster shall have 24VDC battery backup capabilities. The booster shall have the capability to be inter-connected to accommodate large installations with supervised audio power and also supervised and synchronized strobe power requirements. Three versions of the booster shall be made available: SPB-80/4, (80 watts of supervised audio power and 4 amps of supervised and synchronized strobe power), SPB-160 (160 watts of supervised audio) or SPB-320 (320 watts of supervised audio).

Each booster shall use 1.2 watts of audio input power (The SPB-320 requires 2.4 watts of audio power) to properly operate and provide additional supervised audio output power. A combination of boosters can be added together to provide for a maximum of 5,280 watts of supervised audio power. Additional strobe power can be obtained via a combination of boosters. The audio section of the booster shall be connected via a selectable 70V or 25V input from the Cooper

Notification SPMNS. The strobe section of the booster shall be divided into two sections each supplying two Amps of 24VDC, NAC, supervised, synchronizable, power limited, Class B strobe outputs, with selectable outputs offering Wheelock sync, pass through, or constant DC and can be activated via 8-33VDC NAC input or contact closure.

The internal battery charger/power supply shall be capable of charging 24 VDC batteries with a maximum capacity of 33 amp hours. The enclosure shall be capable of housing the correct number of 12 VDC rechargeable batteries (SPB-80/4 (2), SPB-160 (2), SPB-320 (4)) with a maximum capacity of 12 Amp hours.

Batteries with a larger capacity require an external battery enclosure(s) such as the Cooper Notification BATC or equivalent.

The boosters shall have power-limited circuitry and be a class D amplifier with an internal battery charger and power supply. The required batteries (purchased separately) shall fit inside the enclosure (two 12VDC, 12 AH for the SPB-80/4 or SPB-160 and four 12 VDC, 12 AH for the SPB-320). The booster shall operate on 120VAC, 3.8A, 50 – 60 Hz input. E model boosters shall operate on 240 VAC, 2.5A, 50 – 60 Hz input. The SPB-80/4 or SPB-160 standby current draw shall be 120mA and alarm current draw shall be 9 Amps. The SPB-320 consists of two SPB-160’s. Each SPB-160 shall have its own power supply and battery charger. The voice frequency response shall be 400 Hz – 6.5 kHz +/- 3 dB. Removable quick connect/disconnect terminals that accept 12 -22 AWG shall be used. Multiple LED’s for easy indication of system diagnostic conditions shall be present on the PC board. The Signal to Noise Ratio shall be > 70 dB, the dynamic range shall be > 65 dB, the Total Harmonic Distortion spec shall be 2%.

The booster shall be wall mountable, enclosed in a steel locking enclosure, with a red finish. Approvals for the booster shall include: UL 2572 for MNS, UL

Standard 864, 9th edition, UL Standard 1711, CSFM and MEA. The system shall be OSHA 1910.165, ADA and UFC 04-021-01 2002 (including October 2007

Draft) compliant. The booster shall carry a 1 Year Warranty.

The SPB-80/4 & SPB-160 enclosure dimensions are 21” H x 16” W x 6” D and the SPB-320 enclosure dimensions are 36” H x 24” W x 6” D.

4 Zone Class B Speaker Splitter

The Wheelock SP4Z-A/B shall be UL 2572 for MNS, UL Standard 864, 9th edition, California State Fire Marshal (CSFM) and New York City (MEA) approved,

2-Zone Class A or 4-Zone Class B Speaker Splitter for operation with the SPMNS, SP40/2, SPB-80/4, SPB-160 and SPB-320. The SP4Z-A/B shall enable a single supervised speaker audio output to drive up to two Class A supervised speaker audio outputs or four Class B supervised speaker audio outputs. Each

Class A zone shall be capable of accepting up to 40 watts and operate on either 25 or 70.7V RMS of audio input. Each Class B zone shall be capable of accepting up to 40 watts of audio and operate on either 25 or 70.7V RMS of audio input. The SP4Z-A/B shall be capable of supporting live microphone and prerecorded emergency voice evacuation messages.

The SP4Z-A/B shall mount inside the enclosure of the SPMNS, SP40/2, SPB-80/4, SPB-160 and SPB-320 and shall have power and trouble LED with individual zone short and open LED indication. The SP4Z-A/B shall be capable of detecting wiring faults. The SP4Z-A/B shall be powered by 24VDC, which is to be supplied by the SPMNS, SP40/2, SPB-80/4, SPB-160 or SPB-320. Standby and Alarm current at 24VDC shall be 15mA. Removable wiring terminals for quick connect/disconnect accepting 12–22 AWG shall be incorporated. All output circuitry shall be power limited. Space shall be provided to allow for naming of the zones.

WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE

TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE

PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with

Wheelock Inc. standard terms and conditions.

WE ENCOURAGE AND SUPPORT NICET CERTIFICATION

1 Year Warranty

SPMNS 09/11

NJ Location

273 Branchport Ave.

Long Branch, NJ 07740

P: 800-631-2148

F: 732-222-8707 www.coopernotification.com

12

Cooper Notification is

FL Location

7246 16th Street East, Suite 105

Sarasota, FL 34243

P: 941-487-2300

F: 941-487-2389

VA Location

103 West Broad Street, Suite 500

Falls Church, VA 22046

P: 877-459-7726

F: 703-294-6560

Notification

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement