Fire Alarm Systems | DS 10 Sounders
DS 10 Sounders
www.boschsecurity.com
u
Very robust housing made of 4 mm pressure-molded aluminum u
Compact and maintenance-free u
Great reliability and long lifespan u
Can be used in adverse environmental conditions u
Reverse polarity protected connections
The DS 10 sounders are acoustic signaling devices for connection to fire panels, available for operating voltage 230 V AC or 24 V DC.
Functions
The DS 10 sounders have an integrated tone generator with a selection of 6 sound variants, including DIN tones conforming to EN 457 (DIN 33404).
Depending on the tone type, volume set, and operating voltage, the sound pressure level varies between 105 dB(A) and 110 dB(A).
The programming/coding is undertaken via DIP switches in the signaling device.
The DS 10 sounders can be used as a monitored and non-monitored signaling devices.
Certifications and approvals
VdS ID number: G 28 609
CE DS 10
EN54-3: 2006
Region
Europe
Germany
Europe
Certification
CE
VdS
CPD
DS 10
G 28609 DS 10
0786-CPD-20005 DS10
1
2
N o
Installation/configuration notes
• For surface-mounted cable feed
• Can be connected to the following fire panels:
– BZ 1012
– BZ 1060
– BZ 500 LSN
– UEZ 1000 LSN
– UEZ 2000 LSN
– UGM 2020.
• The DS 10 sounders can be directly connected to monitored control lines.
Tone type table
Signal shape Frequency
DIN tone (increasing/decreasing tone)
Variable tone
1200-500 Hz
825/1075 Hz
2 | DS 10 Sounders
5
6
3
4
Pulse tone 1
Pulse tone 2
Continuous tone 1
Continuous tone 2
Calculation example:
Number of signaling devices used:
Maximum DS 10 sound pressure level: less 10 dB for unique audibility: less environmental sound level:
--------------------------------------------------------------------------
Attenuation through distance from siren:
Diagram: Sound Pressure Level Drop
825 Hz
500 Hz
825 Hz
500 Hz
110 dB
-10 dB
-70 dB
30 dB y
0
-10
1
-20
-30
-40
-50
-60
1 2 4 8 16 32 64 128 256 x y
1
Pos.
x
Description
Distance from loudspeaker (m)
Sound pressure level decrease (dB)
Sound pressure decrease on reflection
(depends on room volume and reverberation time)
2 Drop of sound pressure without reflection
The diagram shows a maximum distance of 32 m for this damping. It is therefore recommended that an audible notification appliance be installed approximately every 60 m.
2
32m
32m
60m
Parts included
Qty.
1
Components
Sounder red, 24 V DC or 230 V AC, surface-mounted cable feed
Technical specifications
Operating voltage
• DS 10 rot, 230 V
• DS 10 rot, 24 V
Current consumption
• 230 V type
• 24 V type
Sound pressure level at a distance of
1 m
Frequency range
Permissible operating temperature
Permissible relative humidity
Protection class as per EN 60529
Dimensions (W x H x D)
Housing material
Housing color
Weight
• 230 V type
• 24 V type
230 V AC
24 V DC
(12 V DC … 30 V DC)
Max. 60 mA
Max. 420 mA
Max. 110 dB (A)
500 Hz up to 1.2 kHz
-25 °C . . +55 °C
95%
IP 66/67
133 x 119 x 133 mm
Cast aluminum
Red, similar to RAL 2002
2,200 g
1,800 g
Ordering information
DS 10 Red, 230 V for connection to fire panels, available for operating voltage 230 V, usable in adverse environmental conditions
Order number DS10-230V
3 | DS 10 Sounders
DS 10 Red, 24 V for connection to fire panels, available for operating voltage 24 V DC, usable in adverse environmental conditions
Order number DS10-24V
Represented by:
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180 [email protected]
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330 [email protected]
www.boschsecurity.com
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699 [email protected]
www.boschsecurity.asia
© Bosch Security Systems 2013 | Data subject to change without notice
1304594315 | en, V4, 21. May 2013
China:
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398 www.boschsecurity.com.cn
America Latina:
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862 [email protected]
www.boschsecurity.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project