SPORLAN
Sporlan
Refrigeration and
Air Conditioning
Products
Oil Level Controls
Oil filters
Suction Filters
See•All
Head Pressure Control Valves
Three-Way Heat Reclaim Valves
Solenoids
Evaporator Pressure Regulating Valves
TEV
Catch-All
Discharge Bypass Valves
630
SPORLAN
THERMOSTATIC EXPANSION VALVES
• Selective Thermostat Charges — Designed to provide optimum performance for all applications — air conditioning
and heat pump, medium and low temperature refrigeration.
• Thermostatic Element Design — Long lasting and field proven stainless steel diaphragm and welded element
construction.
• Diaphragm Design — Large flat diaphragm permits precise valve control.
• Replaceable Thermostatic Elements — Field replaceable elements on all standard valves.
• Balanced Port Design — Provides perfect pin and port alignment, and prevents changes in pressure drop across
the valve from influencing Valve operation. Provides excellent control on applications with widely varying operating
conditions.
• Pin Carrier Design (Conventional Valves) — Provides precise pin and port alignment, and tighter seating.
• Accessible Internal Parts — Durable, leak proof body joint construction allows the valve to be disassembled, and
the internal parts cleaned and inspected.
• Materials of Construction — Pin and port material offer maximum protection against corrosion and erosion.
• Silver Soldered Connections — For leak proof, high strength connection-to-body joints.
• Adjustable Superheat Design — All standard valves are externally adjustable.
VALVE NOMENCLATURE/ORDERING INSTRUCTIONS
Combine the letters and numbers in the following manner to obtain the complete valve designation. Also include all connection Sizes and the capillary tube length.
CONVENTIONAL VALVES:
X
1/4” ODF
Solder
X
5’
Body
Type:
FB,F,
EF,G,
EG,
RI,RC,
S,
EBS*,
O*,
V**,
W**
S V E GA
7/8”ODF
Solder
Sporlan Code - REFRIGERANT -
Element Label Color Code
F - R-12 Yellow
E - R-13 - Blue
V - R-22 -Green
G - R-23 - Blue
M - R124 - Blue
J- R134a -Blue
X - R-401A Pink
L - R-402ASand
S- R-404A Orange
V - R-407A – Green
N - R-407 Lt. Brown
S - R-408A -Purple
F - R-409A -Yellow
R - R-502 - Purple
W - R-503 - Blue
P - R-507 - Teal
W - R-508B - Blue
A - R-717 – White
E” specifies external equalizer.
Omission of letter “E” indicates valve with internal equalizer. e.g.
EGV-1-C
Nominal
Capacity in Tons
Thermostatic
Charge
Inlet
Connection
Size and
Style
Outlet
Connection
Size and
Style
External
Equalizer
Connection
Size and
Style
Capillary
Tubing
Length
(Inches or Feet)
BALANCE PORTED VALVES:
EBF
Body
Type:
BF,SBF,
EBF
V
22 (V)
407C (N)
407A (V)
134a (J)
12 (F)
401A (X)
409A (F)
404A (S)
502 (R)
408A (S)
507 (P)
402A (L)
E
“E” specifies external equalizer.
Omission of letter “E” indicates valve with internal equalizer.
-
Port
Size
AAA
AA
A
B
C
AAA
AA
A
B
C
AAA
AA
A
B
C
AAA
AA
A
B
C
AA
Nominal
Capacity in Tons
1/8 thru 1/3
1/2 thru 2/3
3/4 thru 1-1/2
1-3/4 thru 3
3-1/4 thru 5-1/2
1/8 thru 1/5
1/4 thru 1/3
1/2 thru 1
1-1/4 thru 1-3/4
2 thru 3
1/8 thru 1/5
1/4 thru 1/3
1/2 thru 1
1-1/4 thru 2
2-1/4 thru 3
1/8 thru 1/5
1/4 thru 1/3
1/2 thru 1
1-1/4 thru 2
2-1/4 thru 3
C
Thermostatic
Charge
3/8”
Extended
ODF Solder
Inlet
Connection
Size and
Style
*EBS and O valves are balance ported valves, but follow conventional valve nomenclature.
**V and W valves have dual port semi-balance design.
X
1/2”
Extended
ODF Solder
Outlet
Connection
Size and
Style
X
1/4”
Extended
ODF Solder
External
Equalizer
Connection
Size and
Style
X
30”
Capillary
Tubing
Length
(Inches)
631
SPORLAN
RECOMMENDED THERMOSTATIC CHARGES
APPLICATION
AIR CONDITIONING
12
409A
22
407A
134a 401A
REFRIGERANT
402A 404A
408A
40
7C
502 507 717
ACTUAL
THERMOSTATIC
CHARGES
FCP60 — JCP60 XCP60 —
—
—
—
VCP100
VGA
—
—
—
—
—
—
—
—
— — — — —
—
NCP
100
— — —
FCP60
VCP100
— — — — — — VGA
— SCP115 — RCP115 — — SCP115
FC
VC
COMMERCIAL
REFRIGERATION 0°F
TO -40°F
SC
PC
LOW TEMPERATURE
REFRIGERATION 0°F
TO -40°F
— VZP40 — — — — — — — —
FZ
FZP
VZ
VZP40
SZ
SZP
EXTREME LOW TEMP.
REFRIGERATION -40°F
TO -100°F
VX
SX
• APPLICATION FACTORS
1. The type ZP charges have essentially the same characteristics as the Type Z charge with one exception: they produce a pressure limit
Maximum Operating Pressure (MOP). ZP charges are not intended as replacements for Z charges. Each should be selected for its own unique purpose.
2. All A/C and Heat pump charges are intended for use with externally equalized valves.
3. Type L liquid charges are also available for most commonly used refrigerants in most element sizes.
4. If in doubt as to which charge to use, contact Sporlan Valve Company, Washington, Missouri with complete system data.
5. The type X charges are not to be used with “EBS” and “O” valves.
• IMPORTANT NOTES
A. R-134a A/C and commercial refrigeration applications are using R-12 or R409A or R-401A valves.
B. R-404A commercial refrigeration applications are using R-502 or R-408A valves.
C. R-404A and R-507 low temperature refrigeration applications are using R-502 or R-402A or R-408A valves.
F
EF
G
EG
FB
BF
SBF
EBF
S
EMC
VALUE
TYPE
NOMINAL CAPACITY
RANGE (Tons)
R-22 R-134a
R-404A
&
1/5 thru
3
1/8 thru
2
R-507
1/8 thru
2
1/5 thru
3
1/5 thru
3
1/5 thru
3
1/4 thru
8
1/3 thru
5
1/3 thru
5
1/3 thru
5
2 thru
10
1/8 thru
2
1/8 thru
2
1/8 thru
2
1/4 thru
5
1/4 thru
3
1/4 thru
3
1/4 thru
3
2 thru
6
1/8 thru
2
1/8 thru
2
1/8 thru
2
1/4 thru
6
1/4 thru
3
1/4 thru
3
1/4 thru
3
2 thru
7
SPORLAN
CONNECTION
TYPES
SAE Flare
ODF Solder
SAE Flare
ODF Solder
SAE Flare or
ODF Solder
VALVE DESCRIPTION AND APPLICATION
Small brass bar body, externally adjustable valve for small capacity refrigeration systems. SAE flare inlet connection has a removable 100 mesh strainer. Typical applications: Refrigerated cases, coolers, freezers.
Same as the Type F valve except it features ODF solder connections. The inlet connection has a 50 mesh strainer. Typical applications: Refrigerated cases, coolers, freezers.
Forged brass bar body, externally adjustable valve for small capacity refrigeration systems. Inlet connection has a removable 100 mesh strainer. Typical applications: Refrigerated cases, coolers, freezers and small capacity air conditioners.
Same as the Type G valve except it features ODF solder connections and a forged brass inlet fitting with a removable 100 mesh strainer which can be cleaned and/or replaced without moving the valve from the line.
Small brass body valve available only with straight through connections and external adjustment. Typical applications: Small capacity air conditioning and refrigeration applications where an external adjustment
is desired
SAE Flare
Extended
ODF Solder
Extended
ODF Solder
ODF Solder
Same physical size as the Type F valve with SAE flare connection except it features a balanced port construction. Inlet connection has removable 100 mesh strainer. Typical applications: Small capacity refrigeration that operates over widely varying operating conditions.
Same as the Type BF valve except it features ODF solder connection and a forged brass inlet fitting with a removable 100 mesh strainer which can be cleaned and/or replaced without removing the valve from the line.
Same as the Type BF valve except it features ODF solder connections.
Brass bar body, externally adjustable valve. General purpose valve for air conditioning and refrigeration applications.
0.64 thru
2.34
0.46 thru
1.69
0.42 thru
1.51
ODF Solder
Multi-capacity two part valve designed to perform effectively over the range of load conditions inherent with most refrigeration systems. Large port is for pull down load and smaller port to control holding loads.
632
SPORLAN
PART
NO* SPORLAN MODEL**
TYPE F
PART
NO* SPORLAN MODEL**
TYPE BF
PART
NO* SPORLAN MODEL**
TYPE FB
FF-1-1/2-C 3X4 SAE 30"
FF-1-C 3X4 SAE 30"
FFE-1-C 3X4 SAE 30"
FFE-2-C 3X4 SAE 30"
FJ-1/2-C 2X4 SAE 30"
FJ-1/4-C 2X4 SAE 30"
FJ-1/4-Z 2X4 SAE 30"
FR-1/4-Z 2X4 SAE 30"
FRE-1/2-C 3X4 SAE 30"
FRE-1/2-Z 3X4 SAE 30"
FRE-1/2-ZP 3X4 SAE 30"
FRE-1/4-Z 2X4 SAE 30"
FRE-1-1/2-C 3X4 SAE 30"
FRE-1-1/2-Z 3X4 SAE 30"
FRE-1-1/2-ZP35 2X4 SAE 30"
FRE-1-ZP 3X4 SAE 30"
FRE-2-Z 3X4 SAE 30"
FRE-2-ZP 3X4 SAE 30"
FS-1/2-C 2X4 SAE 30"
FS-1/4-C 2X4 SAE 30"
FS-1/4-ZP 2X4 SAE 30"
FSE-1/2-Z 2X4 SAE 30"
FSE-1/2-ZP35 2X4 SAE 30"
FSE-1/4-ZP 2X4 SAE 30"
BFF-A-C 3X4 SAE 30"
BFJE-A-C 3X4 SAE 30"
BFJE-B-C 3X4 SAE 30"
BFR-A-C 3X4 SAE 30"
BFRE-A-Z 3X4 SAE 30"
BFRE-A-ZP 3X4 SAE 30"
BFRE-B-C 3X4 SAE 30"
BFRE-B-Z 3X4 SAE 60"
BFRE-B-ZP 3X4 SAE 30"
BFSE-AA-ZP 3X4 SAE 30"
BFSE-A-C 3X4 SAE 30"
BFSE-C-ZP 3X4 SAE 30"
BFV-AA-C 3X4 SAE 30"
BFV-A-C 3X4 SAE 30"
BFVE-AAA-C 3X4 SAE 30"
BFVE-AA-C 3X4 SAE 30"
BFVE-A-C 3X4 SAE 30"
BFVE-B-C 3X4 SAE 30"
TYPE G
FBS-1/4-C 3SX4 ODF 30"
FBS-1/4-Z 2SX4 ODF 30"
FBS-1/4-ZP 3SX4 ODF 30"
FBSE-1/2-C 3SX4X2 ODF 30"
FBSE-1/4-C 3SX4X2 ODF 30"
FBSE-1/4-ZP 3SX4X2 ODF 30"
FBSE-1\2-ZP 3SX4 ODF 30"
FBSE-1-1\2-C 3SX4 ODF 30"
FBSE-1-1\2-ZP 3SX4 ODF 30"
FBSE-1-C 3SX4 ODF 30"
FBSE-1-Z 3X4X2 ODF 30"
FBSE-1-ZP 3SX4 ODF 30"
FBSE-2-C 3SX4X2 ODF 30"
FBSE-2-Z 3X4X2 ODF 30"
FBSE-2-ZP 3SX4X2 ODF 30"
FBSE-3.5-C 4X7X2 ODF 60"
FBSE-3.5-ZP 4X7X2 ODF 30"
FBSE-3-C 4X7X2 ODF 60"
FBSE-3-ZP 4X7X2 ODF 30"
FBSE-4.5-C 4X7X2 ODF 60"
FBSE-4.5-ZP 4X7X2 ODF 30"
FBSE-6-C 5X7X2 ODF 60"
FBSE-6-ZP 5X7X2 ODF 30"
FBV-1/4-C 2*SX4 ODF 30"
FSE-1/4-ZP30 2X4 SAE 30"
FSE-1-C 3X4 SAE 30" GRE-1-1/2-ZP 3X4 SAE 5'
FBV-1/4-C 3*SX4 ODF 30"
FBV-1/4-ZP40 3SX4 ODF 30"
FV-1/4-C 2X4 SAE 30"
FVE-1/2-C 3X4 SAE 30"
FVE-1/4-C 2X4 SAE 30"
FVE-1-1/2-C 3X4 SAE 30"
FVE-1-C 3X4 SAE 30"
FVE-2-C 3X4 SAE 30"
FVE-3-C 3X4 SAE 30"
GRE-1-ZP 3X4 SAE 5'
GVE-1-C 3X4 SAE 5'
GVE-3/4-C 3X4 SAE 5'
GVE-3/4-ZP 3X4 SAE 5'
GVE-3-C 3X4 SAE 5'
TYPE FB
FBVE-1/2-ZP40 3*SX4X2 ODF 30"
FBVE-1/4-C 3*SX4X2 ODF 30"
FBVE-1/4-ZP40 3*SX4X2 ODF 30"
FBVE-1\2-C 3*SX4 ODF 30"
FBVE-1-1/2-ZP40 3*SX4X2 ODF 30"
FBVE-1-1\2-C 3*SX4 ODF 30"
FBVE-1-C 3*SX4 ODF 30"
FBVE-1-ZP40 3*SX4X2 ODF 30"
FBVE-2.5-C 4X5X2 ODF 60"
FBVE-2.5-ZP40 4X5X2 ODF 30"
TYPE EF
FBFE-1-C 3SX4X2 ODF 30"
FBVE-2-C 4X5X2 ODF 30"
FBVE-2-ZP40 4X5X2 ODF 30"
EFF-1/4-Z 2SX3 ODF 30"
EFJ-1/2-C 2SX3 ODF 30"
EFJ-1/4-C 2SX4 ODF 30"
EFS-1/4-C 2SX3 ODF 30"
EFS-1/4-Z 2SX3 ODF 30"
EFS-1-Z 3X4 ODF 30"
EFSE-1/2-Z 3X4 ODF 30"
EFSE-1/4-Z 3X4 ODF 30"
EFSE-1/6-Z 2X4 ODF 30"
EFVE-1/2-C 3X4 ODF 30"
EFVE-1/2-L1 3X4 ODF 30"
EFVE-1/3-C 2X4 ODF 30"
EFVE-1/3-C 3X4 ODF 30"
FBJE-1/2-CP60 3X4X2 ODF 30"
FBJE-1/2-Z 3X4X2 ODF 30"
FBR-1/2-Z 2X4 SAE 30"
FBR-1/4-Z 2X4 SAE 30"
FBS-1/2-C 3SX4 ODF 30"
FBS-1/2-Z 2SX4 ODF 30"
FBS-1/2-ZP 3SX4 ODF 30"
IMPORTANT NOTE:
00 *S - with Insert Strainer
Connection Sizes are in eighths of inch – (3x4 means 3/8” inlet x 1/2” outlet).
FBVE-3-C 4X5X2 ODF 60"
FBVE-3-ZP40 4X5X2 ODF 60"
FBVE-4-C 4X7X2 ODF 60"
FBVE-4-ZP40 4X7X2 ODF 60"
FBVE-5-C 4X7X2 ODF 60"
FBVE-5-ZP40 4X7X2 ODF 60"
FBVE-6-C 4X7X2 ODF 60"
FBVE-6-GA 4X5X2 ODF 30"
FBVE-6-ZP40 4X7X2 ODF 60"
FBVE-8-C 5X7X2 ODF 60"
FBVE-8-ZP40 5X7X2 ODF 60"
EFVE-1/3-L1 3X4 ODF 30"
EFVE-1/5-C 2X4 ODF 30"
EFVE-1-C 3X4 ODF 30"
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service Center for part number and pricing.
633
SPORLAN
PART
NO*
SPORLAN MODEL** PART
NO*
TYPE EG
SPORLAN MODEL**
EGV-1/2-ZP40 3X4 ODF 5'
EGV-1/3-C 3X4 ODF 5'
EGV-1/3-Z 3X4 ODF 5'
EGV-1/5-C 3X4 ODF 5'
EGV-1/5-Z 3X4 ODF 5'
EGV-1-C 3X4 ODF 5'
EGFE-1/2-C 3X4 ODF 5'
EGFE-1/4-C 3X4 ODF 5'
EGFE-1-C 3X4 ODF 5'
EGFE-2-C 3X4 ODF 5'
EGJ-1/4-C 3X4 ODF 5'
EGJ-1/6-C 3X4 ODF 5'
EGJ-1/8-C 3X4 ODF 5'
EGJE-1/6-C 3X4 ODF 5'
EGJE-1/8-C 3X4 ODF 5'
EGJE-1-1/2-C 3X4 ODF 5'
EGP-1/2-C 3X4 ODF 5'
EGP-1/4-C 3X4 ODF 5'
EGP-1/6-C 3X4 ODF 5'
EGP-1/8-C 3X4 ODF 5'
EGPE-1/2-C 3X4 ODF 5'
EGPE-1/4-C 3X4 ODF 5'
EGPE-1/8-C 3X4 ODF 5'
EGPE-1-1/2-C 3X4 ODF 5'
EGPE-1-C 3X4 ODF 5'
EGPE-2-C 3X4 ODF 5'
EGR-1/2-C 3X4 ODF 5'
EGR-1/2-Z 3X4 ODF 5'
EGR-1/2-ZP 3X4 ODF 5'
EGR-1/4-C 3X4 ODF 5'
EGR-1/4-Z 3X4 ODF 5'
EGR-1/6-C 3X4 ODF 5'
EGR-1/8-C 3X4 ODF 5'
EGR-1/8-Z 3X4 ODF 5'
EGR-1-C 3X4 ODF 5'
EGRE-1/4-Z 3X4 ODF 5'
EGRE-1/6-C 3X4 ODF 5'
EGRE-1/8-C 3X4 ODF 5'
EGRE-1-ZP40 3X4 ODF 5'
EGV-3/4-C 3X4 ODF 5'
EGV-3/4-Z 3X4 ODF 5'
EGV-3/4-ZP 3X4 ODF 5'
EGV-3/4-ZP40 3X4 ODF 5'
EGVE-1/2-C 3X4 ODF 5'
EGVE-1/2-L1 3X4 ODF 5'
EGVE-1/2-Z 3X4 ODF 5'
EGVE-1/2-ZP40 3X4 ODF 5'
EGVE-1/3-C 3X4 ODF 5'
EGVE-1/5-C 3X4 ODF 5'
EGVE-1-1/2-C 3X4 ODF 5'
EGVE-1-1/2-Z 3X4 ODF 5'
EGVE-1-1/2-ZP40 3X4 ODF 5'
EGVE-1-C 3X4 ODF 5'
EGVE-1-Z 3X4 ODF 5'
EGVE-1-ZP40 3X4 ODF 5'
EGVE-2-C 3X4 ODF 5'
EGVE-2-Z 3X4 ODF 5'
EGVE-2-ZP40 3X4 ODF 5'
EGVE-3/4-C 3X4 ODF 5'
EGVE-3/4-L1 3X4 ODF 5'
EGVE-3/4-X 3X4 ODF 5'
EGVE-3/4-Z 3X4 ODF 5'
EGVE-3/4-ZP 3X4 ODF 5'
EGVE-3/4-ZP40 3X4 ODF 5'
EGVE-3-C 3X4 ODF 5'
EGVE-3-Z 3X4 ODF 5'
EGVE-3-ZP40 3X4 ODF 5'
EGX-1/2-C 3X4 ODF 5'
TYPE SBF
PART
NO*
SPORLAN MODEL**
SBFP-AAA-Z 3X4 ODF 30"
SBFP-AA-C 3X4 ODF 30"
SBFP-AA-Z 3X4 ODF 30"
SBFP-A-C 3X4 ODF 30"
SBFP-B-C 3X4 ODF 30"
SBFPE-AAA-C 3X4 ODF 30"
SBFPE-AA-C 3X4 ODF 30"
SBFPE-AA-Z 3X4 ODF 30"
SBFPE-B-C 3X4 ODF 30"
SBFPE-C-C 3X4 ODF 30"
SBFR-AAA-Z 3X4 ODF 30"
SBFR-AAA-ZP 3X4 ODF 30"
SBFR-AA-C 3X4 ODF 30"
SBFR-AA-Z 3X4 ODF 30"
SBFR-AA-ZP 3X4 ODF 30"
SBFR-A-C 3X4 ODF 30"
SBFR-A-ZP 3X4 ODF 30"
SBFR-B-C 3X4 ODF 30"
SBFRE-AAA-C 3X4 ODF 30"
SBFRE-AAA-Z 3X4 ODF 30"
SBFRE-AA-Z 3X4 ODF 30"
SBFRE-A-Z 3X4 ODF 30"
SBFRE-B-Z 3X4 ODF 30"
SBFS-AAA-C 3X4 ODF 30"
SBFSE-AAA-ZP 3X4 ODF 30"
SBFSE-AA-C 3X4 ODF 30"
SBFSE-AA-ZP 3X4 ODF 30"
SBFSE-A-C 3X4 ODF 30"
SBFSE-A-ZP 3X4 ODF 30"
SBFSE-B-C 3X4 ODF 30"
SBFSE-B-Z 3X4 ODF 30"
SBFSE-B-ZP 3X4 ODF 30"
SBFSE-C-C 3X4 ODF 30"
SBFSE-C-Z 3X4 ODF 30"
SBFSE-C-ZP 3X4 ODF 30"
SBFV-AAA-C 3X4 ODF 30"
SBFV-AAA-Z 3X4 ODF 30"
SBFV-AA-C 3X4 ODF 30"
SBFV-AA-Z 3X4 ODF 30"
SBFV-AA-ZP40 3X4 ODF 30"
PART
NO*
SPORLAN MODEL**
TYPE EBF
EBFF-AAA-C 3X4 ODF 30"
EBFF-A-C 3X4 ODF 30"
EBFFE-A-C 3VX4 ODF 30"
EBFFE-B-C 3X4 ODF 30"
EBFLE-A-C 3X4 ODF 30"
EBFLE-A-Z 3X4 ODF 30"
EBFPE-C-C 3X4 ODF 30"
EBFPE-C-Z 3X4 ODF 30"
EBFR-A-C 3EX4 ODF 30"
EBFRE-AA-Z 3VX4 ODF 30"
EBFRE-AA-ZP 3VX4 ODF 30"
EBFRE-A-Z 3EX4 ODF 30"
EBFRE-A-Z 3X4 ODF 30"
EBFRE-A-ZP 3EX4 ODF 30"
EBFS-AAA-ZP 2X4 ODF 30"
EBFSE-AAA-Z 2SX4 ODF 30"
EBFSE-AAA-ZP 3VX4 ODF 30"
EBFSE-AA-C 3X4 ODF 30"
EBFSE-A-C 3VX4 ODF 30"
EBFSE-A-Z 3VX4 ODF 30"
EBFSE-B-C 3VX4 ODF 30"
EBFSE-B-Z 3VX4 ODF 30"
EBFSE-B-ZP 3X4 ODF 30"
EBFSE-C-C 3X4 ODF 30"
EBFSE-C-Z 3X4 ODF 30"
EBFSE-C-ZP 3VX4 ODF 30"
EBFV-AAA-C 3EX4 ODF 30"
EBFV-AA-C 3EX4 ODF 30"
EBFV-AA-Z 3EX4 ODF 30"
EBFV-AA-ZP40 3EX4 ODF 30"
EBFV-A-C 3EX4 ODF 30"
EBFV-B-C 3X4 ODF 30"
EBFVE-AAA-C 3X4 ODF 30"
EGRE-2-C 3X4 ODF 5'
EGRE-2-Z 3X4 ODF 5'
EGSE-1/2-C 3X4 ODF 5'
EGSE-1/2-Z 3X4 ODF 5'
EGSE-1/2-ZP 3X4 ODF 5'
EGSE-1/4-C 3X4 ODF 5'
EGSE-1/4-ZP 3X4 ODF 5'
EGSE-1-1/2-C 3X4 ODF 5'
EGSE-1-1/2-Z 3X4 ODF 5'
EGSE-1-1/2-ZP 3X4 ODF 5'
EGSE-1-C 3X4 ODF 5'
EGSE-1-X 3X4 ODF 5'
EGSE-1-Z 3X4 ODF 5'
EGSE-1-ZP 3X4 ODF 5'
EGSE-2-C 3X4 ODF 5'
EGSE-2-ZP 3X4 ODF 5'
EGV-1/2-C 3X4 ODF 5'
EGV-1/2-Z 3X4 ODF 5'
SBFF-AA-ZP 3X4 ODF 30"
SBFF-A-ZP 3X4 ODF 30"
SBFFE-AA-ZP 3X4 ODF 30"
SBFFE-A-ZP 3X4 ODF 30"
SBFFE-B-ZP 3X4 ODF 30"
SBFJ-AAA-C 3X4 ODF 30"
SBFJ-AA-C 3X4 ODF 30"
SBFJ-A-C 3X4 ODF 30"
SBFJ-B-C 3X4 ODF 30"
SBFJE-AAA-C 3X4 ODF 30"
SBFJE-AA-C 3X4 ODF 30"
SBFJE-A-C 3X4 ODF 30"
SBFJE-B-C 3X4 ODF 30"
SBFJE-C-C 3X4 ODF 30"
SBFP-AAA-C 3X4 ODF 30"
SBFV-A-C 3X4 ODF 30"
SBFV-B-C 3X4 ODF 30"
SBFVE-AAA-C 3X4 ODF 30"
SBFVE-AAA-ZP40 3X4 ODF 30"
SBFVE-AA-C 3X4 ODF 30"
SBFVE-AA-Z 3X4 ODF 30"
EBFVE-AA-C 3EX4 ODF 30"
EBFVE-AA-CP100 3VX4 ODF 30"
EBFVE-AA-Z 3EX4 ODF 30"
EBFVE-AA-ZP40 3EX4 ODF 30"
EBFVE-A-C 3EX4 ODF 30"
EBFVE-A-Z 3X4 ODF 30"
SBFVE-AA-ZP40 3X4 ODF 30"
SBFVE-A-C 3X4 ODF 30"
SBFVE-A-Z 3X4 ODF 30"
SBFVE-A-ZP 3X4 ODF 30"
SBFVE-A-ZP40 3X4 ODF 30"
SBFVE-B-C 3X4 ODF 30"
SBFVE-B-Z 3X4 ODF 30"
SBFVE-B-ZP40 3X4 ODF 30"
SBFVE-C-C 3X4 ODF 30"
SBFVE-C-Z 3X4 ODF 60"
SBFVE-C-ZP40 3X4 ODF 30"
EBFVE-A-ZP40 3VX4 ODF 30"
EBFVE-B-C 3X4 ODF 30"
EBFVE-B-CP100 3X4 ODF 30"
EBFVE-B-Z 3X4 ODF 30"
EBFVE-B-ZP40 3X4 ODF 30"
EBFVE-C-C 3X4 ODF 30"
EBFVE-C-CP100 3X4 ODF 30"
EBFVE-C-ZP40 3VX4 ODF 30"
IMPORTANT NOTES:
E – Elbow Inlet
V – 877 Series (100 Mesh) Strainer
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service Center for part number and pricing.
634
SPORLAN
PART
NO*
SPORLAN MODEL** PART
NO*
SPORLAN MODEL**
TYPE EMC
PART
NO*
SPORLAN MODEL**
TYPE S
SRE-1/2-C 4X5 ODF 5'
SRE-1/2-ZP 4X5 ODF 5'
SRE-1-1/2-C 4X5 ODF 5'
SRE-1-1/2-Z 4X5 ODF 5'
SRE-1-1/2-ZP 4X5 ODF 5'
SRE-1-C 4X5 ODF 5'
SRE-1-ZP 4X5 ODF 5'
SRE-2-L1 4X5 ODF 5'
SRE-4-Z 4X7 ODF 5'
SSE-1/4-C 3X4 ODF 5'
SSE-10-ZP 5X7 ODF 5'
SSE-10-ZP 7X9 ODF 5'
SSE-2-C 4X5 ODF 5'
SSE-2-ZP 4X5 ODF 5'
SSE-3-C 4X7 ODF 5'
SSE-3-L1 4X7 ODF 5'
SSE-3-ZP 4X7 ODF 5'
SSE-3-ZP40 4X7 ODF 5'
SSE-4-C 4X7 ODF 5'
SSE-4-ZP 4X7 ODF 5'
SSE-6-C 4X7 ODF 5'
SSE-6-C 5X7 ODF 5'
SSE-6-X 5X7 ODF 5'
SSE-6-Z 5X7 ODF 5'
SSE-6-ZP 5X7 ODF 5'
SSE-7-C 5X7 ODF 5'
SSE-7-ZP 5X7 ODF 5'
SVE-1/2-C 4X5 ODF 5'
SVE-10-C 5X7 ODF 5'
SVE-1-1/2-C 4X5 ODF 5'
SVE-1-1/2-L1 3X4 ODF 5'
SVE-1-1/2-Z 3X4 ODF 5'
SVE-1-1/2-ZP40 4X5 ODF 5'
SVE-15-C 7X11 ODF 5'
SVE-15-CP100 7X9 ODF 5'
SVE-1-C 4X5 ODF 5'
SVE-1-ZP40 4X5 ODF 5'
SVE-2-C 4X5 ODF 5'
SVE-2-L1 4X5 ODF 5'
SVE-2-ZP40 4X5 ODF 5'
SVE-3-C 4X5 ODF 5'
SVE-3-L1 4X5 ODF 5'
SVE-3-L2 4X5 ODF 5'
SVE-3-ZP40 4X5 ODF 5'
SVE-4-C 4X7 ODF 5'
SVE-4-L1 4X7 ODF 5'
SVE-4-X 4X7 ODF 5'
EMC-10-PC 3X4 ODF 5'
EMC-10-SC 3X4 ODF 5'
EMC-10-SZ 3X4 ODF 5'
EMC-10-VC 3X4 ODF 5'
EMC-10-VZ 3X4 ODF 5'
EMC-11-SZ 3X4 ODF 5'
EMC-20-PC 3X4 ODF 5'
EMC-20-SC 3X4 ODF 5'
EMC-20-VC 3X4 ODF 5'
EMC-21-PC 3X4 ODF 5'
EMC-21-SC 3X4 ODF 5'
EMC-21-VC 3X4 ODF 5'
EMCE-10-JC 3X4 ODF 5'
EMCE-10-PC 3X4 ODF 5'
EMCE-10-SC 3X4 ODF 5'
EMCE-10-SZ 3X4 ODF 5'
EMCE-10-VC 3X4 ODF 5'
EMCE-10-VZ 3X4 ODF 5'
EMCE-11-SZ 3X4 ODF 5'
EMCE-11-VZ 3X4 ODF 5'
EMCE-12-SC 3X4 ODF 5'
EMCE-12-SZ 3X4 ODF 5'
EMCE-12-VC 3X4 ODF 5'
EMCE-12-VZ 3X4 ODF 5'
EMCE-13-SZ 3X4 ODF 5'
EMCE-13-VZ 3X4 ODF 5'
EMCE-20-JC 3X4 ODF 5'
EMCE-20-PC 3X4 ODF 5'
EMCE-20-SC 3X4 ODF 5'
EMCE-20-VC 3X4 ODF 5'
EMCE-21-JC 3X4 ODF 5'
EMCE-21-PC 3X4 ODF 5'
EMCE-21-SC 3X4 ODF 5'
EMCE-21-VC 3X4 ODF 5'
EMCE-22-JC 3X4 ODF 5'
EMCE-22-PC 3X4 ODF 5'
EMCE-22-SC 3X4 ODF 5'
EMCE-22-VC 3X4 ODF 5'
EMCE-23-PC 3X4 ODF 5'
EMCE-23-SC 3X4 ODF 5'
EMCE-23-VC 3X4 ODF 5'
TYPE KT
KT-43-FC 5’(1.5M) ELEMENT
KT-43-FZ 5’(1.5M) ELEMENT
KT-43-FZP 5’(1.5M) ELEMENT
KT-43-PC 5’ ELEMENT
KT-43-RC 5’(1.5M) ELEMENT
KT-43-RZ 30"(.75M) ELEMENT
KT-43-RZP 5’(1.5M) ELEMENT
KT-43-VC 5’(1.5M) ELEMENT
KT-43-VZ 5’(1.5M) ELEMENT
KT-43-VZP 5’(1.5M) ELEMENT
KT-53-FC 5’ ELEMENT
KT-53-FZ 5’(1.5M) ELEMENT
KT-53-FZP 5’(1.5M) ELEMENT
KT-53-RC 5’ ELEMENT
KT-53-SZ 5’ ELEMENT
KT-53-SZP 5’ ELEMENT
KT-53-VC 5’ ELEMENT
KT-53-VZ 5’(1.5M) ELEMENT
KT-53-VZP 5’(1.5M) ELEMENT
KT-83-FC 5’ ELEMENT
KT-83-SC 5’ ELEMENT
KT-83-SZ 5’ ELEMENT
KT-83-SZP ELEMENT
KT-83-VC 5’ ELEMENT
KT-83-VZP, 5’ ELEMENT
KT-45-ZGA, 30" ELEMENT
IMPORTANT NOTES:
A. R-134a air conditioning and
commercial refrigeration
applications are using R-12 or
R-409A or R-401A elements.
B. R-404A commercial refrigeration
applications are using R-502 or
R-408A elements.
C. R-404A and R-507 low temperature
refrigeration applications are using
R-502 or R-402A or R-408A elements.
SVE-4-ZP40 4X7 ODF 5'
SVE-5-C 4X7 ODF 5'
SVE-8-C 5X7 ODF 5'
SVE-8-L1 5X7 ODF 5'
SVE-8-Z 5X7 ODF 5'
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service Center for PART NO & pricing.
635
SPORLAN
THERMOSTATIC EXPANSION VALVES
QUICK REFERENCE GUIDE — AIR CONDITIONING VALVES
VALVE TYPE
NOMINAL CAPACITY
RANGE (Tons)
R-22 R-134a
R-404A
&
R-507
CONNECTION
TYPES
VALVE DESCRIPTION AND APPLICATION
Compact and adjustable thermostatic expansion valve with an internal check valve to allow reverse flow on heat pump applications. Valve also can be used for refrigerant 410A applications.(2 Ton through 6 Ton) RC valve replaces RI valve.
2 thru 6 — — ODF Solder
2 thru 10 2 thru 6 2 thru 7 ODF Solder
Brass bar body, externally adjustable valve. Inlet has a permanent 12 mesh strainer. General purpose valve for air conditioning and refrigeration applications.
8 & 11 5 & 7 6 & 7-1/2
Extended ODF
Solder
Same physical size as the Type S valve except it features extended ODF connections and a balanced port construction.
15 thru 70 9 thru 40 9 thru 45 ODF Solder
Brass bar body, externally adjustable valve. Inlet has a permanent 12 mesh strainer. General purpose valve for air conditioning and refrigeration applications.
52thru10 35 thru 55
135 & 180 80 & 110
38 thru 70
—
ODF Solder or
FPT Flange
ODF Solder
Flange
Cast bronze body, externally adjustable valve with flange connections. Inlet has a 12 mesh strainer. This valve type features a dual port semi-balanced design. This valve type provides valve capacities greater than the
Type M, and is suitable for air conditioning and refrigeration applications. Flanges for the Type V are interchangeable with the Type M.
Cast bronze body, externally adjustable valve with flange connections. Inlet has a 12 mesh strainer. This valve type features a dual port semi-balanced design and it is primarily for large capacity chillers. This valve type provides the largest valve capacities available for flange connection TEVs.
* R-22 M Valves with GA & CP 100 Thermostatic chargers are also available.
636
THERMOSTATIC EXPANSION VALVES
Type-S
ELEMENT SIZE No. 83, Knife Edge Joint.
Standard Tubing Length - 5 Feet.
TYPE &
CAPACITY
REFRIGERANT
(Sporlan Code)
External
Equalizer Only
STANDARD
CONNECTIONS
(in. ODF Solder)
Inlet Outlet
22 (V)
SVE-2
SVE-3
SVE-4
SVE-5
SVE-8
SVE-10
GA or
CP100
1/2
5/8
5/8
7/8
Type-EBS
Balanced Port Construction ELEMENT SIZE No. 83,
Knife Edge Joint, Standard Tubing Length - 5 Feet
REFRIGERANT
(Sporlan Code)
TYPE &
CAPACITY
External
Equalizer
Only
STANDARD
CONNECTION
S
(in. ODF
Solder)
Inlet Outlet
22 (V)
EBSVE-8
EBSVE-11
GA or
CP100
5/8
7/8
Type-O
Balanced Port Construction ELEMENT SIZE No. 83 and 33,
Knife Edge Joint, Standard Tubing Length - 5 Feet
REFRIGERANT
(Sporlan
Code)
TYPE &
CAPACITY
STANDARD
CONNECTIONS
(in. ODF
Solder
Inlet Outlet
22 (V)
External
Equalizer
Only
OVE-15
OVE-20
OVE-30
OVE-40
OVE-55
OVE-70
3
3
8
3
GA or
CP100
7/8
1-1/8
1-1/8
1-3/8
SPORLAN
Type-RC
With internal check valve.
R-22 ELEMENT SIZE No. 43, Knife Edge Joint,
Standard Tubing Length - 30”
R-410A ELEMENT SIZE No. 45, Knife Edge Joint,
Standard Tubing Length – 30”
REFRIGERANT
(Sporlan Code)
TYPE &
CAPACITY
STANDARD
CONNECTIONS
Inches
ODF Solder
External
Equalizer
Only
Inlet Outlet
22 (V)
410A (Z)
RCVE-3
RCVE-4
2 RCVE-5
RCVE-6
GA
1/2
5/8
RCZE-2
RCZE-4
1/2
RCZE-5
RCZE-6
Only
1/2
5/8
Type-W
ELEMENT SIZE No. 63, Gasket Joint,
Standard Tubing Length - 5 Feet
Flange Ring Size — 1-3/4” OD x 1-1/2” ID.
REFRIGERANT
(Sporlan Code)
TYPE &
CAPACITY
External
22 (V)
Equalizer
Only
WVE-135
63
WVE-180
7
GA or
CP10
0
G only
Type-V
STANDARD
CONNECTIONS
Inches
Extended
ODF Solder
Inlet Outlet
1-5/8
ELEMENT SIZE No. 63, Gasket Joint,
Standard Tubing Length - 5 Feet
Flange Ring Size — 1-3/4” OD x 1-1/2” ID.
REFRIGERANT
(Sporlan Code)
TYPE &
CAPACITY
STANDARD
CONNECTIONS
Inches
Extended
ODF Solder
Inlet Outlet
22 (V)
External
Equalizer
Only
VVE-52
VVE-70
VVE-100
GA or
CP100
1-3/8 1-3/8
TEV REPLACEMENT ELEMENTS
KT-43-VGA 30”
Item Descriptions
KT-43-VCP100 30”
KT-33-VGA 60” KT-33-VCP100 60”
KT-53-VGA 60”
KT-83-VGA 60”
KT-63-VGA 10”
KT-53-VCP100 60”
KT-83-VCP100 60”
KT-63-VCP100 10”
2-1/8
637
SPORLAN
THERMOSTATIC EXPANSION VALVES
AIR CONDITIONING AND HEAT PUMP APPLICATIONS
VALVE TYPES NOMINAL CAPACITY
RC 2
RC 3
RC 4
RC 5
RC 6
EBS 8
EBS 11
O 15
O 20
O 30
O 40
O 55
O 70
S 2
S 3
S 4
S 5
S 8
S 10
S 15
V 52
V 70
V 100
W 135
W 180
REFRIGERANT
22 410A
RECOMMENDED THERMOSTATIC CHARGES
VCP100, VGA N, ZGA
EVAPORATOR TEMPERATURE (°F)
40° 40°
2.30
3.20
2.76
3.83
4.20
5.00
6.01
8.51
11.50
5.03
5.99
7.20
—
—
15.00
22.20
30.50
40.30
55.00
73.00
2.00
3.20
4.50
5.20
8.00
10.00
15.00
52.00
73.00
100.00
143.00
180.00
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
REFRIGERANT
LIQUID TEMPERATURE ENTERING TEV (°F)
60° 70° 80° 90° 100° 110° 120° 130° 140°
22
CORRECTION FACTOR, CF LIQUID TEMPERATURE
1.23 1.17 1.12 1.06 1.00 0.94 0.88 0.82 0.76
410A 1.32 1.24 1.16 1.08 1.00 0.92 0.83 0.73 0.62
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an evaporator temperature of 40° F.
PRESSURE DROP ACROSS TEV (PSI)
75 100 125 150 160
175 200 225 250 275
REFRIGERANT
CORRECTION FACTOR, CF PRESSURE DROP
40°F EVAPORATOR TEMPERATURE
22 0.87 1.00 1.12 1.22 — 1.32 1.41 1.50 1.58 1.66
410A 0.68 0.79 0.88 0.97 1.00 1.05 1.12 1.19 1.25 1.31
TEV CAPACITY = TEV RATING X CF LIQUID TEMPERATURE X CF PRESSURE DROP —
Example: Calculate the actual capacity of a nominal 2 ton, R-22, Type RC valve at 40° F evaporator, 80° F liquid temperature entering the TEV, and 75 psi pressure drop across the TEV:
TEV capacity = 2.30 (from rating chart) x 1.12 (CF liquid temperature) x 0.87 (CF pressure drop)
= 2.24 tons
638
THERMOSTATIC EXPANSION VALVE PART
NUMBERS
Type S Series Valves
PART NO
SVE-10-GA5/8X7/8ODF
SVE-15-GA7/8X1-1/8ODF
SVE-2-GA1/2/5/8ODF
SVE-3-GA1/2X5/8ODF
SVE-4-GA1/2X7/8ODF
SVE-5-GA1/2X7/8ODF
SVE-8-GA5/8X7/8ODF
SVE10CP1005/8X7/8ODF
SVE15CP1007/8X11/8OD
SVE2-CP1001/2X5/8OD
SVE3-CP1001/2X5/8OD
SVE4-CP1001/2X7/8OD
SVE5-CP1001/2X7/8OD
SVE8CP1005/8X7/8ODF
Type RC Series Valves
PART NO
RCVE-2-GA3/8X1/2ODF
RCVE-3-GA3/8X1/2ODF
RCVE-4-GA1/2X1/2ODF
RCVE-4-GA1/2X5/8ODF
RCVE-5-GA1/2X1/2ODF
RCVE-5-GA1/2X5/8ODF
RCVE-6-GA1/2X1/2ODF
RCVE-6-GA1/2X5/8ODF
RCZE-2-GA3/8X1/2ODF
RCZE-3-GA3/8X1/2ODF
RCZE-4-GA1/2X1/2ODF
RCZE-5-GA1/2X5/8ODF
RCZE-6-GA1/2X5/8ODF
Type EBS Series Valves
SPORLAN
DESCRIPTION
SVE-10-GA 5/8X7/8 ODF
SVE-15-CP100 7/8X1-1/8 ODF
SVE-2-GA 1/2X5/8 ODF
SVE-3-GA 1/2X5/8 ODF
SVE-4-GA 1/2X7/8 ODF
SVE-5-GA 1/2X7/8 ODF
SVE-8-GA 5/8X7/8 ODF
SVE-10-CP100 5/8X7/8 ODF
SVE-15-CP100 7/8X1-1/8 ODF
SVE-2-CP100 1/2X5/8 ODF
SVE-3-CP100 1/2X5/8 ODF
SVE-4-CP100 1/2X5/8 ODF
SVE-5-CP100 1/2X5/8 ODF
SVE-8-CP100 5/8X7/8 ODF
DESCRIPTION
RCVE-2-GA 3/8X1/2 ODF
RCVE-3-GA 3/8X1/2 ODF
RCVE-4-GA 1/2X1/2 ODF
RCVE-4-GA 1/2X5/8 ODF
RCVE-5-GA 1/2X1/2 ODF
RCVE-5-GA 1/2X5/8 ODF
RCVE-6-GA 1/2X1/2 ODF
RCVE-6-GA 1/2X5/8 ODF
RCZE-2-GA 3/8X1/2 ODF
RCZE-3-GA 3/8X1/2 ODF
RCZE-4-GA 1/2X1/2 ODF
RCZE-5-GA 1/2X5/8 ODF
RCZE-6-GA 1/2X5/8 ODF
Type O Series Valves
PART NO
OVE-20-GA7/8X7/8ODF
OVE15CP1007/8X11/8O
OVE15GA7/8X1-1/8ODF
OVE20CP1007/8X1-3/8OD
OVE20GA7/8X1-1/8ODF
OVE30CP1001-1/8X1-3/8O
OVE30GA1-1/8X1-3/8OD
OVE40CP10011/8X13/8O
OVE40CP10011/8X15/8O
OVE40GA1-1/8X1-3/8OD
OVE40GA1-1/8X1-5/8OD
OVE55CP10011/8X13/8O
OVE55CP10011/8X15/8O
OVE55GA1-1/8X1-3/8OD
OVE55GA1-1/8X1-5/8OD
OVE70CP10011/8X13/8O
OVE70CP10011/8X15/8O
OVE70GA1-1/8X1-3/8OD
OVE70GA1-1/8X1-5/8OD
Type V Series Valves
PART NO
VVE-100-GA13/8X13/8
VVE-52-GA13/8X138OD
VVE-70-GA13/8X13/8OD
VVE100CP10013/8X13/8
VVE52CP10013/8X13/8
VVE70CP10013/8X13/8O
Type W Series Valves
PART NO
WVE-135-GA15/8X21/8
WVE135CP10015/8X21/8
PART NO
EBSVE-11-GA5/8X7/8OD
EBSVE-8-CP1005/8X7/8
EBSVE-8-GA5/8X7/8ODF
EBSVE11CP1005/8X7/8O
DESCRIPTION
EBSVE-11-GA 5/8X7/8 ODF
EBSVE-8-C100 5/8X7/8 ODF
EBSVE-8-GA 5/8X7/8 ODF
EBSVE-11-CP100 5/8X7/8 ODF
DESCRIPTION
TXV, VALVE 7/8X7/8 ODF
OVE-15-CP100 7/8X1-1/8 ODF
OVE-15-GA 7/8X1-1/8 ODF
OVE-20-CP100 7/8X1-3/8 ODF
OVE-20-GA 7/8X1-1/8 ODF
OVE-30-CP100 1-1/8X1-3/8 ODF
OVE-30-GA 1-1/8X1-3/8 ODF
OVE-40-CP100 1-1/8X1-3/8 ODF
OVE-40-CP100 1-1/8X1-5/8 ODF
OVE-40-GA 1-1/8X1-3/8 ODF
OVE-40-GA 1-1/8X1-5/8 ODF
OVE-55-CP100 1-1/8X1-3/8 ODF
OVE-55-CP100 1-1/8X1-5/8 O
OVE-55-GA 1-1/8X1-3/8 ODF
OVE-55-GA 1-1/8X1-5/8 ODF
OVE-70-CP100 1-1/8X1-3/8 ODF
OVE-70-CP100 1-1/8X1-5/8 ODF
OVE-70-GA 1-1/8X1-3/8 ODF
OVE-70-GA 1-1/8X1-5/8 ODF
DESCRIPTION
VVE-100-GA 1-3/8X1-3/8 ODF
VVE-52-GA 1-3/8X1-3/8 ODF
VVE-70-GA 1-3/8X1-3/8 ODF
VVE-100-CP100 1-3/8X1-3/8 ODF
VVE-52-CP100 1-3/8X1-3/8 ODF
VVE-70-CP100 1-3/8X1-3/8 ODF
DESCRIPTION
WVE-135GA 1-5/8X2-1/8 ODF
WVE-135-CP100 1-5/8X2-1/8 ODF
639
SPORLAN
SOLENOID VALVES
REFRIGERANTS 22, 134a, 402A, 404A, 407C, 502, 507
SPECIFICATIONS
6 Proven Benefits of Sporlan Solenoid Valves:
• Molded coil for most sizes.
• Class “F” temperature rating – Coil types MKC-1, OMKC-1, MKC-2, and OMKC-2.
• Extremely rugged, simple design – few parts.
• “E” Series may be brazed without disassembly.
• Tight closing through use of synthetic seating material.
• Can be used on Refrigerants 22, 134a, 401A, 402A, 404A, 407C, 502 & 507 because of high MOPD ratings.
Sporlan Solenoid Valves are made in two general types, normally closed and normally open. The normally closed types may be further sub-divided into direct acting and pilot operated types.
The Sporlan “E” series solenoid valves feature extended solder type connections as standard. One important benefit to the user is that all valves in the “E” series can be installed without disassembly using either low or no silver content brazing alloy. The “E” series is interchangeable with the “B” series; solder type valves, providing the overall length can be accommodated.
All valves in the “E” series have the same capacities as the “B” series with the exception of the E42.
Its capacity is approximately 15% greater than the MA42.
All Sporlan solenoid valves are designed for liquid, suction and discharge gas applications.
Most Sporlan Solenoid Valves are listed by Underwriters’ Laboratories, Inc. –Guide No. Y10Z – File No.MH4576 and Canadian Standards Association –Guide 440-A-O, Class 3221, File 19953 and CE provisions of the LVD
73/23/EEC.
LIQUID CAPACITY SELECTION TABLE
PART NO TONS OF REFRIGERATION**
“E”
SERIES
VALVE
PRESSURE DROP – psi*
1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
1.3 1.9 2.1 0.8 1.2 1.5 1.8 2.0 0.9 1.3 1.6 1.9 2.1 0.6 0.9 1.1 1.2 1.4
2.3 3.3 3.6 1.5 2.1 2.6 3.0 3.4 1.6 2.3 2.8 3.3 3.7 1.1 1.5 1.9 2.1 2.4
4.0 5.7 6.4 2.7 3.8 4.6 5.3 5.9 2.9 4.1 4.9 5.7 6.4 1.9 2.7 3.3 3.8 4.2
6.6 9.3 10.4 4.4 6.2 7.5 8.7 9.7 4.7 6.6 8.1 9.3 10.4 3.1 4.4 5.3 6.2 6.9
9.1 6.4 9.1 11.1 12.8 14.4 4.2 6.0 7.3 8.5 9.4
12.9 9.1 12.9 15.8 18.2 20.4 6.0 8.5 10.4 12.0 13.4
104 104 127 147 165 48.5 68.5 83.9 96.9 108
PART NO
“E”
SERIES
VALVES
E3
E5
E6
E9
E10
E14
E19
E25
1
0.6
1.1
1.9
3.1
4.2
2
0.9
1.5
2.7
4.4
6.0
404A
3
1.1
1.9
3.3
5.4
7.3
4 5 1 2
TONS OF REFRIGERATION**
407C 502
PRESSURE DROP – psi*
3
1.2 1.4 0.8 1.2 1.5
2.1 2.4 1.5 2.1 2.6
3.8 4.2 2.6 3.7 4.5
6.2 6.9 4.3 6.1 7.4
4 5
1.7 1.9 0.6 0.8 1.0
3.0 3.4 1.0 1.5 1.8
5.2 5.8 1.9 2.6 3.2
8.6 9.6 3.0 4.3 5.2
8.5 9.5 5.9 8.3 10.2 11.8 13.2
1 2 3
4.2 5.9 7.2
4 5 1 2
507
3
1.2 1.4 0.6 0.8 1.0
2.1 2.4 1.0 1.5 1.8
3.7 4.1 1.9 2.6 3.2
6.0 6.8 3.0 4.3 5.2
8.3 9.3 4.2 5.9 7.2
4 5
1.2 1.4
2.1 2.4
3.7 4.1
6.0 6.7
8.3 9.3
6.0 8.5 10.4 12.0 13.4 8.4 11.8 14.5 16.7 18.7
5.9 8.4 10.2 11.8 13.2 5.9 8.3 10.2 11.8 13.2
9.2 13.1 16.0 18.5 20.7 12.8 18.2 22.3 25.8 28.8
9.0 12.8 15.7 18.2 20.3 9.0 12.8 15.7 18.1 20.3
15.7 22.3 27.4 31.6 35.4 21.9 31.0 38.0 44.0 49.2 15.5 21.9 26.8 31.0 34.7 15.4 21.8 26.8 30.9 34.6
E34
—
E42
—
22.0 31.1 38.1 44.0 49.2 30.5 43.2 53.0 61.2 68.4 21.5 30.5 37.4 43.2 48.3 21.5 30.4 37.3 43.1 48.2
40.8 55.2 65.8 74.6 82.2 56.4 76.3 91.1 103
48.6 68.8 84.2 97.2 109 67.6 95.6 117
72.8 98.5 118 133 147 101 136
163
135
184
114
151
203
39.5 53.4 63.7 72.2 79.5 39.8 53.8 64.2 72.8 80.2
47.7 67.4 82.5 95.3
70.4 95.3 114
107 47.6 67.3 82.4 95.1 106
129 142 71.0 96.1 115 130
*Do not use below 1 psi pressure drop, except Types E3 and A3 valves.
**Capacities are based on 40° F evaporator and 100° F liquid. Valve types whether Normally Closed or Normally Open have the same
capacities, i.e., B10 or OB10, E10 or OE10.
Solenoid valves for brine applications – consult Sporlan Valve Company, Washington, MO.
143
640
SPORLAN
SOLENOID VALVES
SPECIFICATIONS
REFRIGERANTS 22, 134a, 402A, 404A, 407C, 502, 507
PART NOE Series Extended Connections
Without Manual Lift Stem With Manual Lift Stem Normally Closed CONNECTIONS (in)
E3S120
E3S130
E5S120
E5S130
E6S130
E6S140
E9S240
E10S240
E10S250
E14S250
E19S250
E19S270
E25S270
E25S290
E34S290
E34S2110
E42S2130
E42S2170
—
—
—
—
ME6S130
ME6S140
ME9S240
ME10S240
ME10S250
ME14S250
ME19S250
ME19S270
ME25S270
ME25S290
ME34S290
ME34S2110
ME42S2130
ME42S2170
—
3/8 ODF Solder
1/4 ODF Solder
3/8 ODF Solder
3/8 ODF Solder
1/2 ODF Solder
1/2 ODF Solder
1/2 ODF Solder
5/8 ODF Solder
5/8 ODF Solder
5/8 ODF Solder
7/8 ODF Solder
7/8 ODF Solder
1-1/8 ODF Solder
1-1/8 ODF Solder
1-3/8 ODF Solder
1-5/8 ODF Solder
2-1/8 ODF Solder
SOLENOID PARTS KITS
Part No.
SOLENOID COILS
Coil Type and Voltage
PORT SIZE (in)
.101
.101
.150
.150
3/16
3/16
9/32
5/16
5/16
7/16
19/32
19/32
25/32
25/32
1
1
1-5/16
1-5/16
KS-B6/E6
KS-B9/E9
KS-B10/E10
KS-B19/E19
KS-B25/E25
KS-B34/E34
KS-B14/E14 KS-B42/E42
SOLENOID VALVES R410A
R-410A Valves with 4 different port sizes and ODF solder Connections are available from Sporlan. The smallest port
Valve uses a MKC-1 coil while the rest use MKC-2 coil.
Sporlan solenoid valves are available in many different
Voltage and cycle ratings. Standard coils are listed
In the specification table below.
MKC-1 and MKC-2 – 24 JAQ and CAQ
MKC-1 and MKC-2 – 120 JAM and CAM
MKC-1 and MKC-2 – 208-240 JAN and CAN
MKC-1 and MKC-2 – Dual JAU and CAU
SPECIFICATIONS
MOPD psi AC
300
300
300
300
300
300
300
300
300
300
300
300
300
300
300
300
300
300
VALVE CONNECTIONS PORT SIZE
SERIES Inches
ME6S130-HP 3/8
Inches
ODF 3/16 MKC-1
ME9S240-HP 1/2 9/32
7/16
ME19S270-HP 7/8 19/32
ME25S290-HP 1-1/8 25/32
MKC-2
24/50-60
120/50-60
208-240/50-60
220-240/50
120-208-240/50/60
1
1
10
15
641
WATTS
10
10
15
15
15
10
10
10
10
15
15
15
15
15
15
15
15
15
THREE-WAY HEAT RECLAIM VALVES
SPORLAN
Sporlan Heat Reclaim Valves are tight synthetic seating three way valves designed specifically to divert hot gas from the normal to auxiliary condenser.
OPERATION
“B” TYPE
Normal (Outdoor) Condenser – De-energized – With the
pilot valve de-energized, high side pressure is prevented from entering the cavity above the piston-seat assembly.
At the same time the upper pilot port is opened to suction pressure. The resulting pressure differential across the piston moves the piston-seat assembly to close the reclaim
(upper) main port. When the upper pilot port is open, the cavity above the piston is open to suction. Pump out of the reclaim condenser is controlled by the bleed rate through the piston. After the reclaim condenser has been pumped out, and the valve continues to operate in the normal condenser mode, all flow ceases, thus eliminating high to low side bleed and the resulting capacity loss.
“C” TYPE
Normal (Outdoor) Condenser – De-energized –
With the pilot valve de-energized, high side pressure is prevented from entering cavity above the pistonseat assembly. At the same time the upper pilot port is opened to suction pressure. The resulting pressure differential across the piston moves the piston-seat assembly to close the reclaim (upper) main port. The non bleed piston prevents high to low side bleed with the system operating in the normal condenser mode.
“B” AND “C” TYPE
Reclaim (Reheat) Condenser – Energized – When
the pilot valve is energized, high side pressure is permitted to flow thru the lower pilot port. At the same time the upper pilot port is closed to suction.
High side pressure on top of the piston moves the piston-seat assembly to close the normal condenser port and open the reclaim (upper) main port. With the upper pilot port closed there is no high to low side bleed loss with the system operating in the reclaim mode.
THREE-WAY HEAT RECLAIM SYSTEMS
• With Head Pressure Control
• With Split Condenser Control
• With Integral Check Valve
When employing heat reclaim on a refrigeration system, the addition of head pressure controls is important not only to maintain liquid pressure at the expansion valve inlet, but also to assure availability of quality hot gas at the reclaim heat exchanger. Split condenser controls are important to minimize the required refrigerant charge for wintertime operation. And, integral check valves are important to minimize installation costs
.
PART NO* Sporlan Model
10G711B 120/50-60 JAM
10G79B 120/50-60 JAM
12D11B LESS COIL
12D11C LESS COIL
12D13B LESS COIL
12D13B-SC LESS COIL
12D13C LESS COIL
16D17B LESS COIL
16D17B-SC LESS COIL
16D17C LESS COIL
8D7B 208-240/50-60 JAN
8D7B DUAL JAU
8D7C LESS COIL
8D9B DUAL JAU
8D9B LESS COIL
8D9B-CV 24/50-60 LAQ
8D9C LESS COIL
B5D5B DUAL JAU
NOTE: SC - split condenser; CV - check valve.
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service for P/N and Pricing.
642
SPORLAN
CATCH-ALL SEALED TYPE
The universal acceptance of the Catch-All Filter Drier is due to its unique molded porous core, consisting of a blend of highly effective desiccants. The quality features built into it assure years of service on any refrigeration system.
MOISTURE — The Catch-All Filter Drier removes moisture from the refrigerant by adsorbing and retaining it deep within the desiccant granules.
FOREIGN MATTER — The Catch-All Filter Drier will filter out scale, solder particles, carbon, sludge, dirt, or any other foreign matter with negligible pressure drop.
Fine particles that would go through an ordinary strainer are removed down to a minimum size in one pass filtration. The large filtering area of the Catch-All
Filter Drier core permits it to collect a large amount of dirt without plug up.
OIL SLUDGE AND VARNISH — Even the best refrigeration oils break down to produce varnish, sludge, and organic acids. Only the Catch-All Filter Drier is capable of removing these products of oil decomposition.
ACID —The Catch-All Filter Drier is unexcelled in acid removal ability. The hydrochloric, hydrofluoric, and various organic acids are adsorbed and held by the desiccant in a manner similar to the adsorption of moisture. Tests have demonstrated that the Catch-
All Filter Drier will remove over 10 times as much acid as the desiccant used in most driers. This ability, along with its excellent ability to clean up the oil, is responsible for the excellent field performance in cleaning up severely contaminated systems.SPECIAL APPLICATIONS — A special
“HH” core Catch-All Filter Drier is available to remove wax which frequently causes difficulty on low temperature Refrigerant 22 and 502 systems. For cap tube systems, use the C-032-CAP or CW-032-CAP
Catch-All which has fittings suitable for attaching to any size capillary tube.
Remember…It’s not how much moisture you remove from a refrigeration system that counts, it’s how little moisture is left
SEALED TYPE – Liquid Line and Suction Line
SPECIFICATIONS
LIQUID LINE TYPE
SAE Flare ODF Solder
SUCTION LINE
TYPE
ODF Solder
C-162
—
C-163
C-164
C-165
—
—
C-303
C-304
C-305
—
—
—
C-032 C-032-S
C-033 C-033-S
C-052
—
C-053
C-082
—
C-083
C-084
C-052-S
C-0525-S
C-053-S
C-082-S
C-0825-S
C-083-S
C-084-S
C-162-S
C-1625-S
C-163-S
C-164-S
C-165-S
—
C-167-S
C-303-S
C-304-S
C-305-S
C-306-S
C-307-S
C-309-S
—
—
—
—
—
—
C-084-S-T-HH
—
—
—
C-164-S-T-HH
C-165-S-T-HH
C-166-S-T-HH
C-167-S-T-HH
—
—
C-305-S-T-HH
C-306-S-T-HH
C-307-S-T-HH
C-309-S-T-HH
C-413
C-414
C-415
—
—
—
—
C-414-S
C-415-S
C-417-S
C-419-S
—
—
—
—
C-417-S-T-HH
C-419-S-T-HH
C-437-S-T-HH
C-439-S-T-HH
C-4311-S-T-HH
C-4313-S-T-HH
— C-607-S
C-609-S
C-607-S-T-HH
C-609-S-T-HH
COMPACT STYLE
C-144-S-TT-HH
C-145-S-TT-HH
C-146-S-TT-HH
C-147-S-TT-HH
C-149-S-TT-HH
CONNECTION
SIZE (in.)
1/4
5/16
3/8
1/2
5/8
3/4
7/8
3/8
1/2
5/8
3/4
7/8
1-1/8
3/8
1/2
5/8
7/8
1-1/8
7/8
1-1/8
1-3/8
1-5/8
7/8
1-1/8
1/4
3/8
1/4
5/16
3/8
1/4
5/16
3/8
1/2
1/2
5/8
3/4
7/8
1-1/8
VOLUME OF
DESICCANT
(cu in.)
3
60
14
9
5
30
16
41
48
OVERALL
LENGTH (in.)
SOLDER
SOCKET
DEPTH (in.) SAE Flare ODF
Solder
4.19 3.81 0.38
4.69 3.88 0.44
DIAMETER of BODY
(in.)
1.75
4.75
—
5.19
5.62
—
6.06
6.31
6.25
—
6.75
6.94
7.25
—
—
9.69
9.88
10.19
—
—
—
9.56
9.94
10.25
—
—
4.19
4.38
4.31
5.12
5.31
5.25
5.44
5.75
5.94
5.88
6.00
6.31
6.75
6.93
8.88
9.00
9.25
9.65
9.80
9.75
—
9.05
9.35
9.81
9.75
0.38
0.44
0.44
0.38
0.44
0.44
0.50
0.38
0.44
0.44
0.50
0.62
0.62
0.75
0.44
0.50
0.62
0.62
0.75
0.96
—
0.50
0.62
0.75
0.90
2.44
2.62
3.00
3.50
3.00
— 10.34
10.62
10.94
10.94
0.75
0.94
1.00
1.06
— 16.00
16.00
0.75
0.90
— 4.14
4.38
4.83
4.97
4.93
0.50
0.66
0.66
0.75
0.96
4.75
3.00
4.44
Listed by Underwriters Laboratories Inc. – Guide SMGT-File No. SA-1756A& B. Maximum Rated Pressure of 650 psi, except for the C-140 Series which has a maximum pressure of 450 psi.
643
CATCH-ALL REPLACEABLE CORE TYPE
SPORLAN
The rugged construction of the Replaceable Core Catch-All has proven itself in the field for
many years. The design features include:
1. The famous molded porous core for maximum 4. A complete line of fitting sizes
contaminant removal. The core cannot swell,
powder, or pack—assuring ease of installation
and removal;
2. The bolt and nut attachment of the end plate
provides simple and trouble free installation;
3. The internal construction gives a one piece
— all with copper fittings;
5. No plastic parts are used — all
internal parts are plated steel;
6. A corrosion resistant powder
paint protects the exterior of the
shell.
assembly and assures proper core alignment;
REPLACEABLE CORE TYPE
TYPE
C-485,C-485-G
C-485-T
C-487,C-487-G
C-487-T
C-489-T,C-489-G
C-4811-T,C-4811-G
C-4813-T,C-4813-G
C-967,C-967-G
C-967-T
C-969,C-969-G
C-969-T
C-9611-T,C-9611-G
C-9613-T,C-9613-G
C-1449,C-1449-G
C-1449-T
C-14411,C-14411-G
C-14411-T
C-14413-T,C-14413-G
C-19211,C-19211-G
C-19211-T
C-19213,C-19213-G
C-19213-T
C-30013,C-30013-G
C-30013-T
C-30017-T,C-30017-G
C-40017,C-40017-G
C-40017-T
C-40021-T,C-40021-G
C-40025-T,C-40025-G
C-40029-T,C-40029-G
C-40033-T,-C-40033-G
CONNECTIONS (in)
ODF Solder
5/8
5/8
7/8
7/8
1-1/8
1-3/8
1-5/8
7/8
1-1/8
1-3/8
1-3/8
1-5/8
1-3/8
1-3/8
7/8
1-1/8
1-1/8
1-3/8
1-5/8
1-1/8
1-5/8
1-5/8
1-5/8
1-5/8
2-1/8
2-1/8
2-1/8
2-5/8
3-1/8
3-5/8
4-1/8
3
3
4
4
3
3
2
2
2
3
2
2
NUMBER OF
CORES
1
1
1
1
1
1
1
2
4
4
4
4
4
3
3
3
4
4
4
CORE PART NO
OPTIONAL SECONDARY FILTER – ORDER SEPARATELY
Filter Part No. Description Quantity Required
FS-480
FS-960
FS-1440
Filter for C-480 Series Shell
FS-19200
1
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-48, RC-4864, or RC-4864-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
RCW-100, RC-10098, or RC-10098-HH
VOLUME OF
DESICCANT (cu in)
48
48
48
48
48
48
48
96
144
144
144
144
192
192
96
96
96
96
96
144
400
400
400
400
400
192
192
300
300
300
400
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
MOUNTING
BRACKETS
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-685
A-175-2
A-175-2
A-175-2
A-175-2
A-175-2
A-175-2
A-175-2
A-175-2
A-175-2
OVERALL
LENGTH (in)
9.15
9.15
9.30
9.30
9.50
9.60
9.60
14.84
20.58
20.68
20.68
20.68
26.22
26.22
14.84
15.04
15.04
15.14
15.14
20.58
26.22
26.22
26.22
27.94
28.06
28.06
34.56
34.57
34.44
34.81
35.12
644
SPORLAN
CATCH-ALL FILTER DRIERS
LIQUID LINE RATINGS AND SELECTION RECOMMENDATIONS
TYPE
C-032
C-032-CAP
C-032-S
C-032-F
SURFACE
FILTERING
AREA
9
Refrigerant
22
60 PPM
Refrigerant
134a
50PPM
RATINGS AT ARI STANDARD CONDITIONS
Water Capacity-Drops
Refrigerant
404A/507 50
PPM
Refrigerant
407C
50 PPM
Refrigerant
410A
50 PPM
Refrigerant Flow
Capacity**
(Tons at 1 psi ∆P)
75°F 125° F 75° F 125° F 75° F 125° F 75° F 125° F 75° F 125° F 22 134a 404A
507
SELECTION RECOMMENDATIONS (Tons)
Refrigeration
Commercial & Low
Temperature
&
134a
Equipment
502
& 507
Air Conditioning
Field Replacement or Field Built Up
12 &
134a
Systems
22, 407C &
410A
61 50 67 48 71 58 52 17 27 20
1.5
1.3 1.0 1.3 1.4
1/4 1/4 1/4 1/2 1/2
C-032-FM
C-033
C-033-S
3.5
3.2 2.3 3.2 3.4
3.8
3.5 2.6 3.5 3.7
C-052
C-052-S
C-052-F
C-052-FM
C-0525-S
15 146 119 158 114 169 138 123 40 63 48
2.1
1.9 1.4 1.9 2.0
3.4
3.1 2.3 3.1 3.3
1/3
4.1
3.8 2.7 3.8 4.0
4.7
4.3 3.1 4.3 4.5
1/3 1/3
3/4 thru
1
3/4 thru
2
C-053
C-053-S
C-082
C-082-S
C-0825-S
C-083
21 240 196 261 188 279 227 202 65 104 78
2.1
1.9 1.4 1.9 2.0
3.7
3.3 2.4 3.3 3.5
4.5
4.2 3.0 4.2 4.4
1/2
5.2
4.7 3.4 4.7 5.0 thru
8.7
7.9 5.9 8.0 8.5
1/2 thru
1-1/2
1/2 thru
1
3/4 thru
2
1 thru
2
C-083-S
C-084
C-084-S
9.6
8.8 6.4 8.8 9.4
C-162
C-162-S
C-1625-S
C-163
C-163-S
33 346 297 396 285 424 345 307 100 158 119
2.1
3.7
1.9 1.4 1.9 2.0
3.3 2.4 3.3 3.5
1
4.5
4.2 3.0 4.2 4.4
5.2
4.7 3.4 4.7 5.0
10.1 9.3 6.8 9.3 9.8 thru
2
1-1/2 thru
3
3/4 thru
2
1 thru
5
1-1/2 thru
5
C-164
C-164-S
11.0 10.1
7.3 10.1 10.7
C-165
C-165-S
13.8 12.6
9.2 12.7 13.4
15.9 14.5 10.6 14.6 15.5
C-303
C-303-S
C-304
C-304-S
53 696 567 756 545 809 658 586 189 302 227
4.6
5.3
4.2 3.0 4.2 4.4
4.7 3.4 4.7 5.0
10.1 9.3 6.8 9.3 9.8
3
11.0 10.1
7.3 10.1 10.7
14.9 13.6
9.9 13.7 14.5
16.9 15.5 11.3 15.5 16.4 thru
5
3 thru
5
2 thru
5
3 thru
7-1/2
4 thru
10
C-305
C-305-S
C-307-S
21.6 19.8 14.4 19.9 21.0
C-414
C-414-S
C-415
C-415-S
67 936 713 1017 733 1088 885 788 254 407 305
11.5 10.5
7.6 10.5 11.1
12.4 11.4
8.3 11.4 12.1
15.8 14.5 10.6 14.6 15.4
17.5 16.1 11.8 16.2 17.1
22.1 20.3 14.8 20.4 21.5
5 thru
10
24.3 22.3 16.3 22.4 23.7
C-417-S
C-419-S
C-607-S
C-609-S
106 1392 1134 1512 1090 1618 1316 1172 378 604
29.1 26.6 19.5 26.8 28.4
454 33.2 30.4 22.3 30.7 32.4
*The filtration area is equal to the core surface area plus the large internal surface available for depth filtration.
†20 drops = 1 gram = 1cc.
15
5 thru
12
15
5 thru
10
10
5 thru
12
15
7-1/2 thru
15
20
**Based on 86 F liquid line temperature and a refrigerant flow of 3.1 pounds per minute per ton of Refrigerant 134a; 2.9 pounds per minute per ton of
Refrigerant 22; 3.9 pounds per minute per ton for Refrigerant 404A; 2.9 pounds per minute per ton for Refrigerant 407C; 2.8 pounds per minute per ton for
Refrigerant 410A and 4.1 pounds per minute per ton for Refrigerant 507. Ratings in accordance to ARI Standard 710.
NOTES:
1. R-12 water capacity values are approximately 15 percent greater than R-134a. R-502 water capacities are similar to R-404A and R-507.
2. The variation in flow ratings of filter-driers having the same size core and shell is caused by the difference in connection sizes used.
645
SPORLAN
CATCH-ALL SUCTION LINE FILTER DRIER RECOMMENDATIONS
FOR CLEAN-UP AFTER BURNOUT AND NEW SYSTEMS
TYPE NUMBER
CONNECTIONS
(in.)
ODF Solder
Number of
Cores
C-084-S-T-HH 1/2
C-164-S-T-HH 1/2
C-165-S-T-HH 5/8
C-166-S-T-HH 3/4
C-167-S-T-HH 7/8
C-305-S-T-HH 5/8
C-306-S-T-HH 3/4
C-307-S-T-HH 7/8
C-309-S-T-HH 1-1/8
C-417-S-T-HH 7/8
C-419-S-T-HH 1-1/8
Driers
C-437-S-T-HH 7/8
C-439-S-T-HH 1-1/8
C-4311-S-T-HH 1-3/8
C-4313-S-T-HH 1-5/8
C-607-S-T-HH 7/8
C-609-S-T-HH 1-1/8
CORE
PART NO
Sealed
Type Filter
Driers
LENGTH
(in.)
SOLDER
SOCKET
DEPTH
(in.)
WIDTH
(in.)
3.00
3.00
4.75
1.00
SYSTEM CAPACITY IN HORSEPOWER
Refrigerant 22 & 407C
Permanent
Installation with Cores
Temporary
Installation
Cores for
Cleanup;
Filter
Elements after Cleanup
Refrigerant
12, 134a, 404A, 502 & 507
Permanent
Installation with Cores
Temporary
Installation
Cores for
Cleanup;
Filter
Elements after Cleanup
2
3
5
7-1/2
Select these types on basis of permanent installation
1/2
1
2
3
Select these types on basis of
4 permanent installation
10 5
C-144-S-TT-HH 1/2
C-145-S-TT-HH 5/8
C-146-S-TT-HH 3/4
0.75
0.96
4.44
5
2 1
3
3
2
C-147-S-TT-HH 7/8
5 3
C-149-S-TT-HH 1-1/8
C-30013-G 1-5/8
C-30017-G 2-1/8
C-40017-G 2-1/8
C-40021-G 2-5/8
4
C-40029-G 3-5/8
RC-10098-HH or
RC-10098
4.93 0.96
25
30
50
60
15
20
C-40033-G 4-1/8
*See page for RSF shells.
CATCH-ALL SUCTION LINE FILTER DRIER SELECTION INSTRUCTIONS
Selection of the proper Catch-All Suction Line Filter Drier will depend upon the intended usage. Either the “Permanent
Installation with Cores” or “Temporary Installation Cores for
Cleanup; Filter Elements after Cleanup” column may be used.
When the best possible system protection is desired, the
“Permanent with Cores” column should be used for selection.
These recommendations are made on the basis of a low pressure drop, and as a result the cores can be left in the shell for maximum drying and acid removal when the system returns to
expensive is to install cores temporarily for cleanup, and then remove these cores and install filter elements after cleanup.
Because of the larger system capacity, the pressure drop through the temporarily installed cores will be somewhat larger than normal, but still within the limits. After cleanup, the use of filter elements will assure a minimum pressure drop when the system is in normal operation. The low pressure drop through the filter elements assures maximum energy savings during normal operation. Cleanup of the system can be accomplished with either normal operation delivering its full rated capacity. the standard core (RC-10098) or the charcoal core
(RC-10098-HH).
An alternate selection that is satisfactory and less
SIGNIFICANCE OF THE PART NUMBER
The letters and numerals in the Catch-All part number each have a significance. The “C” indicates Catch-All, and “CW” indicates the High Water Capacity Catch-All. The
FIRST TWO
OR THREE DIGITS indicate cubic inches of desiccant. The
LAST ONE OR TWO DIGITS indicate fitting size in eighths. For sealed models, a “-S” following the last digit indicates solder fittings, and NO LETTER indicates a flare fitting. Replaceable core models (C-420 and larger) only have solder connections and the “-S” is omitted.
Examples: C-083 is 8 cu. in. and 3/8 in. flare, C-309-S is 30 cu. in. and 1-1/8 in. solder, C-19213 is 192 cu. in. and 1-5/8 in. solder.
Other suffix letters indicate special qualities. For example:
“-T” indicates a pressure tap consisting of a Schrader type
access valve on the inlet end of the Catch-All.
“-HH” indicates a charcoal style core for wax removal and
cleanup after a hermetic motor burnout.
25
30
646
SPORLAN
REPLACEABLE CORES AND PLEATED FILTER ELEMENTS
Cores for replaceable core type filter-driers are molded with the same desiccants that are used in the popular sealed filter-driers.
Cores are individually packed in metal cans, fully activated and hermetically sealed against moisture and dirt.
Filter elements are dried and packed in individual sealed metal cans. This method of packaging prevents the element from picking up moisture from the atmosphere
Each can contains a “triple gasket” consisting of a new end plate gasket, an end plate gasket for certain competitive filter-driers, and a core gasket where desired. See the specifications on Page * for the number of cores required for each type drier.
RC-4864 - Activated Core - Order as separate item
- Fits types C-480 thru C-19200 Series Shells. This is the standard core suitable for most installations in the liquid or suction line.
RCW-48 - High Water Capacity Core - Order as
separate item - Fits types C-480 thru C-19200
Series shell. Designed specially for use with
POE lubricants. This core should be used on
systems that have a ruptured water cooled condenser, or that have been exposed to the atmosphere, or for some reason have a high amount of moisture in the system.
RC-4864-HH - Activated Charcoal Core - Order as
separate item - Fits types C-480 thru C-19200
Series Shells. This core should be used for wax removal, and for clean-up of systems that have had a hermetic motor burnout.
RPE-48-BD - Filter Element - Order as separate
item - Fits types C-480 thru C-19200 Series
Shells and Replaceable Suction Filter (RSF)
Shells. This element should be used in RSF
shells installed in the suction line to obtain the lowest possible pressure drop. In cleaning up a system after a hermetic motor burnout, cores should be used first. After clean-up, the filter element should be installed.
RC-10098 - Activated Core - Order as a separate
item - Fits types C-30,000 and C-40,000 Series
Shells. This is the standard core suitable for liquid and suction line applications.
RCW-100 - High Water Capacity Core - Order as
separate item - Fits types C-30,000 and C-
40,000 Series Shells. Designed specially for
use with POE lubricants. This core should be
used on systems that have a ruptured water cooled condenser, or that have been exposed to the atmosphere, or for some reason have a high amount of moisture in the system.
RC-10098-HH - Activated Charcoal Core - Order
as separate item - Fits types C-30,000 and C-
40,000 Series Shells. This core should be used for wax removal, and for clean-up of systems that have had a hermetic motor burnout.
RPE-100 - Filter Element - Order as separate
item - Fits types C-30,000 and C-40,000 Series
Shells. This filter element should be used in the suction line to obtain the lowest possible pressure drop after cores were used for system clean-up.
HH STYLE CATCH-ALL FOR WAX REMOVAL
HH STYLE CATCH-ALL FOR WAX REMOVAL
U.S. PATENT NUMBER 3,407,617
Small amounts of wax are often a problem on low
temperature systems. Even well engineered systems
frequently contain minute quantities of wax which are
PART NO.
CONNECTIONS
(in.) sufficient to clog expansion valve screens or cause sticking of the valve. Sporlan has developed a special blend of desiccants including activated charcoal which removes small amounts of wax in the liquid line before this wax can cause trouble at the expansion valve.
These Catch-All Filter Driers have been very successful in correcting trouble jobs in the field.
By installing HH Style Catch-All Filter Driers in the liquid line of all low temperature systems these wax problems can be entirely prevented. In addition to their wax removal ability, these filter driers will remove all of the other harmful contaminants that the standard filter driers remove.
The following Catch-All Filter Driers are available with the HH core to meet the needs of low temperature systems. For dimensions, refer to the specifications
for standard filter driers or consult Bulletin 40-10.
C-052-HH 1/4 SAE Flare
C-082-HH 1/4 SAE Flare
C-083-HH 3/8 SAE Flare
C-162-HH 1/4 SAE Flare
C-163-HH 3/8 SAE Flare
C-163-S-HH 3/8 ODF Solder C-414-HH
C-164-HH 1/2 SAE Flare
C-164-S-HH 1/2 ODF Solder C-417-S-HH 7/8 ODF Solder
C-165-HH 5/8 SAE Flare
PART NO.
C-303-HH
C-304-HH
C-304-S-HH 1/2 ODF Solder
C-305-HH
C-305-S-HH 5/8 ODF Solder
C-415-HH
RC-4864-HH
C-165-S-HH 5/8 ODF Solder RC-10098-HH
CONNECTIONS
(in.)
3/8 SAE Flare
1/2 SAE Flare
5/8 SAE Flare
1/2 SAE Flare
5/8 SAE Flare
Replaceable Core
647
SPORLAN
REVERSIBLE HEAT PUMP FILTER-DRIER
DESIGN BENEFITS
• A short overall length for easy installation.
• Drier operates in either flow direction with low pressure drop.
• Proven metal check valves used in construction — no synthetic materials.
• The Sporlan dependable molded core used for maximum filtration ability. When the
flow direction reverses, dirt already collected remains in the filter-drier.
• A carefully engineered blend of desiccants for maximum water capacity and acid
removal ability. The HPC-160-HH Series also has the HH style core with activated
charcoal which offers maximum ability to remove oleoresin and other reactive
chemical constituents in the oil.
• Same rugged construction as used in the Catch-All.
SPECIFICATIONS -FOR NEW INSTALLATIONS AND HFC SYSTEM USE
Part No
Connection
Size Inches
Selection
Recommendations
Tons
Dimensions
Overall
Length
Inches
Diameter
Inches
Flow Capacity
Tons at 1 psi
∆P
R-22 R-410A
Water Capacity
Refrigerant
R-22
Drops at 60 ppm
R-410A
Drops at 80 ppm*
75°F 125°F 75°F 125°F
Liquid Capacity
Ounces (Wt.)
@100°F
R-22 R-410A
6.75
FOR CLEAN-UP AFTER BURNOUT
5.88
6.00
3.4
4.5
3.3
4.4
215 176 171 105 12.2 10.6
Water Capacity
Refrigerant 22
Drops at 60 ppm Part No
HPC-163-HH
Connection
Size
Inches
Selection
Recommendations
Tons
Dimensions
Overall
Length
Inches
Diameter
Inches
Flow Capacity
R-22 Tons at 1 psi ∆P
3/8 Flare 1 thru 5 7.78 3.00 3.7
75°F
93
125°F
81
Liquid Capacity
Ounces (Wt.)
R-22 @ 100°F
14.5
HPC-163-S-HH
HPC-164-HH
HPC-164-S-HH
HPC-165-HH
3/8 Solder
1/2 Flare
1/2 Solder
5/8 Flare
1 thru 5
1 thru 5
1 thru 5
1 thru 5
6.92
7.95
7.07
8.28
3.00
3.00
3.00
3.00
3.7
4.0
4.0
4.9
93
93
93
93
81
81
81
81
14.5
14.5
14.5
14.5
HPC-165-S-HH 5/8 Solder 1 thru 5 7.35 3.00 4.9 93 81 14.5
UL and ULc Listed - Guide-SMGT-File No. SA-1756A & B. Core volume is 10 cubic inches for HPC-100 Series and 14 cubic inches for the HPC-160-HH Series. Core surface filtering area is 18 sq. in. for the HPC-100 Series and 26 sq. in. for the HPC-160-HH Series.
HPC-100 Series are rated for 650 psig; HPC-160-HH have a 500 psig rating.
*As of this printing, ARI has not established an EPD for R-410A.
648
SPORLAN
SUCTION FILTER WITH THE EXCLUSIVE BI-DIRECTIOL FEATURE
DESIGN BENEFITS
• Protects the compressor from dirt
• A relief device opens if the filter plugs
• Suitable for use with all brazing alloys
• Maximum corrosion resistance
• Full flow design for low pressure drop
• Complete line of sizes
Sporlan offers an exclusive concept in Suction
Filter design — a filter which is Bi-directional.
When flow is in one direction, the bypass relief feature is active. If the pressure drop across the element becomes excessive the bypass relief will open slightly to maintain sufficient gas flow and assure proper cooling of the hermetic motor.
When the Suction Filter is installed with flow in the opposite direction, the bypass relief feature is inactive and will never open, regardless of the increase in pressure drop.
The “-T” in the part number indicates that these models are equipped with an access valve to permit pressure drop readings. The access valve will be operational provided the Suction Filters are installed with the bypass feature inactive.
SPECIFICATIONS
Types with bypass relief feature (Bi-directiol Flow)
PART NO
WITHOUT Access Valve WITH Access Valve CONNECTIONS (in)
--
--
--
--
--
--
SF-283-F
--
--
SF-285-T
SF-286-T
SF-287-T
SF-289-T
SF-489-T
SF-4811-T
SF-4813-T
3/8 SAE Flare
5/8 ODF Solder
3/4 ODF Solder
7/8 ODF Solder
1-1/8 ODF Solder
1-1/8 ODF Solder
1-3/8 ODF Solder
1-5/8 ODF Solder
Types without bypass relief feature (Single Flow Direction)
Dimensions
FILTER AREA Sq In Overall Length Inches SOCKET DEPTH Inches
28
28
28
28
28
48
48
48
8.78
8.34
8.79
8.93
9.51
12.42
13.10
13.44
--
0.62
0.69
0.75
0.91
0.91
0.97
1.09
SHELL DIAMETER
Inches
3.00
3.00
3.00
3.00
3.00
3.00
3.00
3.00
PART NO
WITHOUT Access Valve WITH Access Valve CONNECTIONS (in)
--
--
SF-114
SF-114-F
SF-115
SF-115-F
--
--
--
--
SF-6417-T
SF-6421-T
SELECTION RECOMMENDATION
PART NO
WITHOUT Access Valve
1/2 ODF Solder
1/2 ODF Flare
5/8 ODF Solder
5/8 ODF Flare
2-1/8 ODF Solder
2-5/8 ODF Solder
WITH Access Valve
Dimensions
FILTER AREA Sq In Overall Length Inches SOCKET DEPTH Inches SHELL DIAMETER
Inches
11
11
4.36
5.25
0.50
--
2.00
2.00
11
11
388
388
4.60
5.56
1094
1094
0.62
--
1.24
1.38
2.00
2.00
4.75
4.75
CONNECTIONS (in)
--
--
--
--
--
--
SF-114
SF-114-F
SF-115
SF-115-F
--
--
SF-283-F
--
--
--
--
--
--
SF-285-T
SF-286-T
SF-287-T
SF-289-T
SF-489-T
SF-4811-T
SF-4813-T
SF-6417-T
SF-6421-T
1/2 ODF
1/2 SAE
5/8 ODF
5/8 SAE
3/8 SAE
5/8 ODF
3/4 ODF
7/8 ODF
1-1/8 ODF
1-1/8 ODF
1-3/8 ODF
1-5/8 ODF
2-1/8 ODF
2-5/8 ODF
*Use R-502 horsepower recommendations for R-502A & B and R-508A.
Use R-12 horsepower recommendations for R-501A & B and R-509A.
Ratings are in accordance with ARI Standard 730.
NOMINAL SYSTEM HORSEPOWER* Refrigerant
12, 134a, 404A, 502, 507
1/2
1-1/2
1-1/2
3
1/2
1/2
1
1
5
7
20
30
5
5
22, 407C
5
7-1/2
1
4
2
2
1
1
7-1/2
10
12
15
55
60
649
SPORLAN
REPLACEMENT SUCTION FILTER
The Replaceable Suction Filter shell, used with RPE-48-BD pleated filter element, is designed to be installed in the suction line of new systems to remove resident contaminants.
DESIGN BENEFITS:
• Low pressure drop
• Can be used with desiccant cores for clean-up after burnout
• Various fitting sizes up to 3-1/8” line size
• Access valve supplied for pressure drop measurement or charging
HOW IT’S USED – Sporlan Replaceable Suction Filters are installed in the suction line of air
conditioning systems to remove contaminants that may be in the system at start-up. The
Replaceable Suction Filter has large fittings permitting the use of a small shell on a system with a large line size, resulting in considerable economy. The angle construction is suitable for flow in either direction, which results in easy installation even on compact racks. The
Replaceable Suction Filters should be used with cores for cleaning up a system after a hermetic motor burnout. Select the RC-4864, RC-4864-HH or RCW-48 replaceable cores.
After clean-up, install RPE-48-D elements in the shells.
SELECTION – The table below gives information for choosing the proper model for a given
system. The filter elements are supplied in hermetically sealed metal cans.
SELECTION RECOMMENDATIONS WITH FILTER ELEMENTS
PART NO
CONNECTIONS
Inches
ODF Solder
NOMINAL SYSTEM HORSEPOWER
12 & 134a
Refrigerant
22 & 407C 404A, 502 & 507
NO. OF
FILTER
ELEMENTS
RSF-487-T 7/8 7 10 10
RSF-489-T 1-1/8 8 15 12
RSF-4811-T 1-3/8 10 20 15
One
RPE-48-BD
RSF-4813-T 1-5/8 12 25 20
RSF-4817-T 2-1/8 20 35 25
RSF-4821-T 2-5/8 25 50 35
RSF-9617-T 2-1/8 20 40 30
RSF-9621-T 2-5/8 30 50 40
Two
RPE-48-BD
RSF-9625-T 3-1/8 40 80 55
¦
Remove the screen when RPE-48-BD elements are used.
UL and ULc Listed — Guide-SMGT-File No. SA-1756A & B.
ACID TEST KIT
PART NO
TA-1 One Time Acid Test Kit
NO. OF CORES
One
RC-4864 or
RC-4864-HH
Two
RC-4864 or RC-4864-HH
OVERALL
LENGTH
Inches
9.30
9.37
9.60
9.60
9.37
9.75
14.96
15.43
15.12
650
SPORLAN
MOISTURE AND LIQUID INDICATORS
See -All Moisture and Liquid Indicators offers these 8 outstanding benefits
1. The See•All Moisture and Liquid Indicator provides a true moisture indication for Refrigerants 12, 134a, 22, 404A, 407C, 410A,
502 and 507. The See All is also suitable for Refrigerants 401A & B,
402A & B, 408A and 409A. The dark green indicates dry and a bright yellow indicates wet. The one indicator avoids the confusion found in models with two elements. You cannot pick the wrong element when checking the moisture content of the system.
2. RELIABLE and ACCURATELY CALIBRATED COLOR CHANGE
POINTS. The See•All Moisture and Liquid Indicator is accurately calibrated in parts per million of moisture for each refrigerant. All moisture indicators change color on the basis of relative saturation of the refrigerant. Therefore, liquid line temperature must be considered if an accurate calibration is to be obtained. A color chart is part of the label, for easy comparison.
3. COLOR CHANGES ARE EASILY DISTINGUISHED and
REVERSIBLE. The indicator’s color differs so widely between WET and DRY conditions that there is no possibility of confusion between the two. Colors will reverse as often as moisture concentration in the system changes.
4. LARGE FULL VIEW SIGHT GLASS. The See•All Moisture and
Liquid Indicator has an extra large crystal clear sight glass for viewing the refrigerant. Bubbles indicate a shortage of refrigerant or a restriction in the liquid line.
5. INDICATOR PROTECTED from DISCOLORATION and DIRT.
The indicator is protected by a filter pad and screen. This prevents washing of the indicator by the refrigerant and protects it from system contamination and turbulence.
6. REPLACEABLE INDICATOR ELEMENT. The color indicator paper can be changed on the new fused glass models without removing the See•All from the line. Replacement is thru the bottom
(see SA-14SU below). Request the K-SA-4 kit.
7. DISASSEMBLY OF THE SMALLER SIZES NOT REQUIRED.The extended steel fittings on solder models in the smaller sizes make it unnecessary to disassemble for installation since steel conducts onl one eighth as much heat as copper.
8. A DOUBLE DUTY PLASTIC CAP is supplied to keep the glass free from dust, dirt, and grease. It also permits the service engineer to use his own discretion concerning instructions to his customers on observing the See•All Moisture and Liquid Indicator.
Specifications
CONNEC
-TION
SIZES
Inches
5/8
MALE FLARE
Part
No
Overall
Length
Inches
FEMALE & MALE
No
FLARE
Part
—
Overall
Length
Inches
MALE FLARE X
SWIVEL NUT
Part
No
—
Overall
Length
Inches
—
SWIVEL NUT X
SWIVEL NUT
Part
No
—
— SA-15U 4.44 SA-15UU
Overall
Length
Inches
FEMALE FLARE X
SWIVEL NUT
Part
No
Overall
Length
Inches
SWIVEL NUT X
ODF SOLDER
Part
No
Overall
Length
Inches
ODF SOLDER
Part
No
Overall
Length
Inches
— — — — — SA-12S
3.95 SA-13UU 3.19 SA-13SU 4.19 SA-13S
4.62
4.50 SA-14UU 3.75 SA-14SU 4.62 SA-14S
4.75 — — SA-15SU 4.89 SA-15S
4.87
Listed by Underwriters’ Laboratories, Inc. - Guide SEYW - File No. SA3182
Maximum Rated Pressure – 650 psi. Overall width is: 1.31 in. for 1/4 in. and 3/8 in. sizes, 1.58 in. for 1/2 in. and 5/8 in. sizes, and 1.38 in. for 7/8 in. and
1-1/8 in. sizes. Most solder connections can be used as male fittings as well as female fittings. The 1/4 in. ODF is 3/8 in. ODM, the 3/8 in. ODF is 1/2 in.
ODM, the 1/2 in. ODF is 5/8 in. ODM, and the 5/8 in. ODF is 3/4 in. ODM. Models with female flare and/or swivel nut connections are supplied with a copper gasket in the fitting.
Moisture Content PPM
SEE•ALL
SHOWS
LIQUID
LINE
TEMP
Green Dry
75° F
12
100° F 75° F
22
100° F 75° F
134a
REFRIGERANT
100° F 75° F
502
100° F
404A & 507
75° F 100° F
407C
75° F
410A
75° F
Below 5 Below 10 Below 30 Below 45 Below 50 Below 80 Below 10 Below 20 Below 15 Below 30 Below 120 Below 75
Chartreuse CAUTION
Yellow WET
5-15
Above
15
10-30
Above
30
30-90
Above
90
45-130
Above
130
50-200
Above
200
80-225
Above
225
10-45
Above
45
20-65
Above
65
15-90
Above
90
30-140
Above
140
120-280 75-150
Above
280
Above
150
NOTE: Change or add Catch-All Filter-Drier when paper turns from green to chartreuse.
651
DISCHARGE BYPASS VALVES
SPORLAN
The Sporlan line of discharge bypass valves are designed to provide an economical method of compressor capacity control in place of cylinder
Unloader or to handle unloading requirements below the last step of cylinder unloading. These modulating control valves automatically bypass the required amount of discharge gas to the low side to maintain the desired minimum evaporator pressure. The valves are applicable on any refrigeration or air conditioning system that operates during periods of low load, which can result in coil icing or short cycling. These valves respond to downstream pressure changes and open when the evaporator pressure falls below the valve setting. At normal loads and evaporator conditions, the valve remains closed and the system operates in a conventional manner.
The DR line of valves consists of three basic types of valves: the adjustable models, the adjustable remote bulb models, and the non-adjustable models.
The SHGB valves are adjustable and pilot operated with a solenoid stop feature that eliminates the need for a hot gas solenoid valve. They were developed for use on larger capacity systems.
APPLICATION — The discharge bypass valve is normally applied in a branch line off the discharge line. To allow system pump down control, a soleno valves. The bypassed hot gas can enter the low side at several locations; however, two of the possible locations are preferred because of superior ope or directly into the suction line. By using the side connection distributor method, the system TEV will act as a desuperheating valve to keep the compres by the compressor manufacturer. When the hot gas is bypassed directly into the suction line, an auxiliary desuperheating TEV may be required.
SELECTION and CAPACITY RATINGS —The capacities given in the table below are valve hot gas capacities and not the capacities of the system on which the valve is to be applied. To select a valve, first determine the compressor capacity at the minimum allowable evaporating temperature.
Then the discharge bypass valve must supply the difference between this compressor capacity and the minimum evaporator load at which the system is to be operated. The valve pressure setting will be that pressure at which the bypass valve must start to open.
Connections - (Standard Connections in BOLD type).
ADRS(E)-2 – 3/8 in., 1/2 in., 5/8 in. ODF Solder or
3/8 in., 1/2 in., 5/8 in. SAE Flare
ADRP(E)-3 – 1/2 in., 5/8 in. ODF Solder or
1/2 in., 5/8 in. SAE Flare
ADRHE-6 & DRHE-6 – 5/8 in., 7/8 in., 1-1/8 in. ODF
652
SPORLAN
DISCHARGE BYPASS VALVES
DISCHARGE BYPASS VALVE CAPACITIES — Tons
Capacities based on 6°F evaporator temperature change from closed to rated opening (does not apply to pilot operated models), discharge temperature 30°F above isentropic compression, 100°F condensing temperature, 0°F subcooling, 25°F superheat at the compressor and includes both the hot gas bypassed and liquid refrigerant for desuperheating, regardless of whether the liquid is fed through the system thermostatic expansion valve or auxiliary desuperheating thermostatic expansion valve.
REFRIGERANT
MINIMUM VALVE TYPE & ADJUSTMENT RANGE (psig)
ALLOWABLE
EVAPORATOR
ADRI-1-1/4
ADRIE-1-1/4
ADRS-2
ADRSE-2
ADRP-3
ADRPE-3
ADRHE-6
DRHE-6
(Adjustable “Remote Bulb” Model)*
TEMPERATURE 0/55 0/75 0/100 0/30 0/80 0/30 0/80 0/30 0/80 25/35 32/44 55/70 65/80
SHGB-8
SHGBE-8
SHGB-15
SHGBE-15
0/100 0/75
22
134a
401A
402A
404A
407C
502
507
40
26
0
–20
40
26
0
40
26
0
40
26
0
–20
40
26
0
–20
40
26
0
–20
40
26
0
–20
40
26
0
–20
— 0.58 0.53 — 3.51 — 5.99 — 9.16 —
0.44
0.63 0.60 0.49 3.90 3.66 7.38 6.61 13.9 10.9 —
0.59 0.50 0.44 3.75 3.65 7.45 6.64 14.1 11.0 —
0.40
0.41 0.39 0.32 2.60 2.44 4.95 4.42 9.36 7.26 8.31
—
—
—
—
6.9 — 15.9
— — 16.2
— — 16.2
—
—
— 10.9
— 10.9
58
62
66
69
41
43
0.38
0.45
—
0.47 0.45 0.37 2.97 2.79 5.66 5.04 10.7 8.26 —
— —
11.0 —
— 11.0
— 12.3
9.49 — — 1
46
52
52
0.44 0.36 0.32 2.83 2.74 5.62 5.01 10.8 8.32 — — — — 12.5 56
— — 0.54 — — — — — — — — — — 17.3 —
— 0.65 0.60 — 3.91 — 6.66 — 10.3 — — — — 17.7 63
0.66 — — — 17.9
0.69 0.63 0.52 4.22 4.04 8.11 7.33 15.3 12.2 — — — — 18.0
63
64
— — 0.55 — — — — — — — — — — 17.5 —
— 0.67 0.60 — 3.91 — 6.70 — 10.4 — — — 21.4 17.7 64
0.67
0.68 0.61 0.51 4.17 4.02 8.08 7.28 15.3 12.1
— 0.78 0.65 — 4.25 — 7.50 — 12.1 —
0.61
0.74 0.68 0.56 4.51 4.31 8.63 7.81 16.3 13.0 —
0.68 0.56 0.50 4.33 4.23 8.64 7.71 16.5 12.9 —
— — 0.46 — 3.14 — 5.28 — 7.85 —
— 0.56 0.49 — 3.19 — 5.51 — 8.55 —
0.55 0.57 0.46 3.58 3.28 6.64 5.90 12.5 9.62
—
—
—
—
— 22.9 — 18.6
19.3 —
—
—
—
—
—
—
— 17.9
—
— 18.7
—
—
17.9
18.9
19.1
— — 19.2 14.3
— — 16.6 14.5
— — — 14.7
65
65
74
75
76
77
—
55
59
0.55 0.59 0.41 3.43 3.30 6.68 6.00 12.6 9.91 — — — — 14.8 61
— — 0.53 — — — — — — — — — — 17.4 —
— 0.65 0.59 — 3.87 — 6.60 — 10.2 — — — — 17.7 64
— 0.71 0.57 — 3.96 — 7.09 — 11.5 —
0.69 0.62 0.52 4.17 4.00 8.02 7.25 15.2 12.0 —
— — — 17.8
— — — 17.9
64
65
PART NO DESCRIPTION PART NO DESCRIPTION
ADRS-20/30ODF
ADRS-20/305ODF
ADRSE-20/304ODF
ADRSE-20/305ODF
ADRS-20/804ODF
ADRS-20/805ODF
ADRSE-20/803ODF
ADRSE-20/804ODF
ADRSE-20/805ODF
ADRP-30/304ODF
ADRS-2 0/30 4 ODF
ADRS-2 0/30 5 ODF
ADRSE-20/304ODF
ADRSE-20/305ODF
ADRS-2 0/80 4 ODF
ADRS-2 0/80 5 ODF
ADRSE-20/803ODF
ADRSE-20/804ODF
ADRSE-20/805ODF
ADRP-3 0/30 4 ODF
ADRHE-60/805ODF
ADRHE-60/807ODF
ADRHE-60/809ODF
DRHE-6-55/70AR7X7
DRHE-6-55/70AR9X9
SHGBE-8-0/1009ODF
SHGBE-8-0/1007ODF
SHGB-8-0/107ODF
SHGB-8-0/1009ODF
SHGB-15-0/759ODF
ADRHE-6 0/80 5 ODF
ADRHE-6 0/80 7 ODF
ADRHE-6 0/80 9 ODF
DRHE-6-55/70AR 7 ODF
DRHE-6-55/70AR 9 ODF
SHGBE-8-0/100 9 ODF LESS COIL
SHGBE-8-0/100 7 ODF LESS COIL
SHGB-8-0/100 7 ODF LESS COIL
SHGB-8-0/100 9 ODF LESS COIL
SHGB-15-0/75 9 ODF LESS COIL
ADRP-30/305ODF
ADRPE-30/304ODF
ADRPE-30/305ODF
ADRP-30/804ODF
ADRP-30/805ODF
ADRPE-30/804ODF
ADRP-3 0/30 5 ODF
ADRPE-30/304ODF
ADRPE-30/305ODF
ADRP-3 0/80 4 ODF
ADRP-3 0/80 5 ODF
ADRPE-30/804ODF
SHGB-15-0/7511ODF
SHGBE-15-0/759ODF
SHGBE-15-0/7511 ODF
SHGB-15-0/75 11 ODF LESS COIL
SHGBE-15-0/75 9 ODF LESS COIL
SHGBE-15-0/75 11 ODF LESS COIL
ADRPE-30/805ODF
ADRHE-60/305ODF
ADRPE-30/805ODF
ADRHE-60/305ODF
653
SPORLAN
CRANKCASE PRESSURE REGULATING VALVES
Crankcase Pressure Regulating Valves are designed to prevent overloading of the compressor motor by limiting the crankcase pressure to a predetermined maximum value during and after a defrost cycle or a normal shutdown period. These valves automatically throttle the vapor flow from the evaporator until the compressor can handle the load.
Sporlan manufactures five adjustable models…
CRO-4, CRO-6, CROT-6, CRO-10 and CROT-10 … all models respond only to their outlet pressure and modulate to prevent the suction pressure at the compressor from rising above the valve setting.
Since these valves are adjustable, the setting may be altered to suit the specific system requirements.
SELECTION and CAPACITY RATINGS
The ratings for these valves vary depending on three items: design suction pressure after pull down, maximum allowable suction pressure recommended by the compressor or unit manufacturer (this is the valve setting), and pressure drop across the valve. The difference between the design suction pressure and the valve setting determines how much of the valve stroke is used. Therefore, the valve setting should be kept as high as possible without exceeding the recommendation of the compressor or unit manufacturer.
PRESSURE REGULATING VALVES
HEAD PRESSURE CONTROL VALVES
PART NO* SPORLAN MODEL
CRO-4-0/20 4X4 ODF LS
CROT-10 30/110 9 ODF WS
CROT-10 30/110 11 ODF WS
CROT-10 0/6011ODF WS
CROT-10 0/60 1-1/8"ODF
CROT-10 0/60 7 ODF WS
CROT-10 30/110 7 ODF WS
CROT-12-65/225 9 ODF
CROT-15-65/225 11 ODF
CROT-6 0/60 5 ODF WS
CROT-6 0/60 1/2" SAE
CROT-6 0/60 5/8" SAE
CROT-6 0/60 7 ODF WS
CROT-6 30/110 5 ODF WS
CROT-6 30/110 7 ODF WS
*( ) Please contact your local Carlyle Certified Refrigeration
Partner or RCD Customer Service for P/N and Pricing.
Sporlan Head Pressure Control for systems with air cooled condensers can be accomplished with several valve types or combinations.
The valve types are: LAC-4, OROA-5, LAC-5, LAC-10, ORI/ORD combination and the ORIT/CROT combination.
PART NO* SPORLAN MODEL
ORD-4-20 5/8 ODF
ORD-4-20 7/8 ODF
ORD-4-25 5/8 ODF
ORD-4-30 5/8 ODF
ORD-4-35 5/8 ODF
ORI-10 65/225 1-1/8"
ORI-10 65/225 1-3/8"
ORI-10 65/225H 7ODF WS
ORI-10 65/225H 11 ODF WS
ORI-6 65/225 5/8" WS
ORI-6 0/50 5 ODF WS
ORI-6 65/225 7/8" WS
ORI-6 65/225H 9ODF WS
ORIT-15-65/225 11 ODF
ORIT-20-65/225 13 ODF
The LAC, OROA, ORI and ORIT are designed for application in the liquid line and should not be applied in the discharge line for any reason. Compressor pulsations can greatly shorten the life of the valves. If any of the valves are applied in any manner other than described here, the Sporlan warranty is void.
PART NO* SPORLAN MODEL
OROA-5-100 5/8 ODF WS
OROA-5-100 7/8 ODF WS
OROA-5-150 7/8 ODF WS
OROA-5-180 5/8 ODF WS
OROA-5-180 7/8 ODF WS
OROA-5-220 5/8 ODF WS
IMPORTANT NOTES: WS - With Strainer
LS - Less Strainer
PART NO*
PART NO*
SPORLAN MODEL
LAC-10-100 11X7 ODF LS
LAC-10-100 11X9 ODF LS
LAC-4-100 1/2 ODF LS
LAC-4-180 3/8 0DF LS
LAC-4-190 1/2 ODF LS
LAC-4-210 1/2 ODF LS
LAC-4-240 1/2 ODF LS
LAC-5-100 1-1/8 ODF LS
LAC-5-210 5/8 ODF WS
LAC-5-75 1/2 ODF LS
SPORLAN MODEL
CROT-12-65/225 9 ODF
CROT-15-65/225 11ODF
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service for P/N and Pricing.
654
SPORLAN
DEFROST DIFFERENTIAL PRESSURE REGULATING VALVES
DDR-20 VALVE OPERATION
The DDR-20 is designed to create a differential pressure between its inlet (discharge) pressure and the receiver pressure.
A solenoid bypass feature is incorporated in the valve so that the valve can be made to go full open when there is no need for a differential to be created. Energizing the solenoid coil opens the valve fully.
LOCATION
The (O)LDR valve is located between the receiver and the liquid header. The DDR-20 is located in the discharge line before the condenser.
ADJUSTMENT RANGE AND
PRESSURE SETTINGS
All defrost differential valves are set by turning the adjusting stem located under the cap on the pilot differential valve.
The adjustment range is 5 to 50 psig.
The (O)LDR has a factory setting of 18 psid and the DDR-20 has a factory setting of 30 psid. Turning the stem clockwise increases the setting, counterclockwise decreases setting.
PART
NO*
SPORLAN MODEL
OLDR-15 11ODF LESS COIL
OLDR-15 9ODF LESS COIL
OLDR-20 13ODF LESS COIL
OLDR-20 17ODF LESS COIL
DDR-20 13 ODF LESS COIL
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service for P/N and Pricing.
EVAPORATOR PRESSURE REGULATING VALVES
The Sporlan line of evaporator pressure regulating (EPR) valves are designed to provide an accurate & economical means of balancing system capacity and load requirements during
“low” loads and/or while maintaining different evaporator conditions on multi-temperature evaporator systems. These valves control evaporator temperature by maintaining evaporator pressure. As the evaporator load increases the ORI valves will Open on Rise of
Inlet pressure above the valve’s setting to
provide more flow capacity to meet the evaporator load. When the evaporator load decreases the valves will modulate closed to maintain the pressure setting of the valve.
Sporlan offers a number of EPR valve types in various sizes, and with optional features to accommodate almost any industry requirement.
For more complete information on any of the
EPR valve types see your Sporlan Wholesaler or contact your Sporlan Sales Engineer.
APPLICATIONS
• Maintain minimum evaporator temperature to avoid frost on air coils and provide improved humidity control
• Evaporator temperature control for food merchandisers
(single and multiple evaporator systems)
• Evaporator temperature control on water chilling units
SPORLAN MODEL
ORI-6 0/50 5 ODF WS
ORIT-10 0/50 7 ODF WS
ORIT-10 0/50 11 ODF WS
ORIT-10 0/50 9 ODF WS
ORIT-10 30/100 7 ODF WS
ORIT-10 30/100 9 ODF WS
ORIT-10 30/100 11 ODF WS
ORIT-12 0/100 9 ODF
ORIT-15 0/100 11 ODF
ORIT-20 0/100 13 ODF
ORIT-6 0/50 5/8" SAE
ORIT-6 0/50 1/2" SAE
ORIT-6 0/50 5 ODF WS
ORIT-6 0/50 7 ODF WS
SPORLAN MODEL
SORIT-12 0/100 208-240VAC 9ODF
SORIT-12-0/100 LC 9ODF
SORIT-15-0/100 LC 11ODF
SORIT-20-0/100 LC 13ODF
SORIT-PI-211S-0/100 LC
SORIT-PI-25S-0/100 LESS COIL
SORIT-PI-25SE-0/100 LESS COIL
SORIT-PI-27S-0/100 LESS COIL
SORIT-PI-27SE-0/100 LESS COIL
SORIT-PI-29S-0/100 LESS COIL
SORIT-PI-29SE-0/100 LESS COIL
SORIT-PI-311S-0/100 LESS COIL
SORIT-PI-313S-0/100 LESS COIL
SORIT-PI-37S-0/100 LESS COIL
ORIT-6 30/100 5 ODF WS
ORIT-6 30/100 7 ODF WS
ORIT-PI-25-0/100
ORIT-PI-27-0/100
ORIT-PI-29-0/100
ORIT-PI-311-0/100
ORIT-PI-39-0/100
ORIT-PI-411-0/100
ORIT-PI-413-0/100
ORIT-PI-513-0/100
IMPORTANT NOTES: WS - With Strainer
SORIT-PI-39S-0/100 LESS COIL
SORIT-PI-411S-0/100 LESS COIL
SORIT-PI-413S-0/100 LESS COIL
SORIT-PI-417S-0/100 LESS COIL
SORIT-PI-49S-0/100 LESS COIL
SORIT-PI-511S-0/100 LESS COIL
SORIT-PI-513S-0/100 LESS COIL
SORIT-PI-517S-0/100 LESS COIL
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD
Customer Service for P/N and Pricing.
PART
NO*
PART
NO*
655
SPORLAN
ELECTRONIC TEMP CONTROL SYSTEMS/OIL FILTERS
ELECTRONIC TEMPERATURE CONTROL SYSTEMS
TYPE CDS-9 and CDS-16
PART NO* SPORLAN MODEL
CDS-16 11ODF 10'-S ST
CDS-16 11ODF 20'-S ST
CDS-9 7ODF 20'-H
CDS-9 9ODF 20'-S
*( ) Please contact your local Carlyle Certified Refrigeration
Partner or RCD Customer Service for P/N and Pricing.
SERIES OIL FILTER
DESIGN BENEFITS
• Virtually eliminates the need for oil changes due to
suspended particulate in circulation
• Unsurpassed filtering efficiency:
99% removal of 3 micron sized particles
98% removal of 2 micron sized particles
• Element utilizes a pleated design for maximum
surface area
• Unsurpassed filtration capacities ESIGN BENEFITS
The Sporlan Catch-All or SF-283-F Suction Filter has been used for many years as an oil filter in refrigeration rack systems with mineral or alkylbenzene as the lubricant of choice.
With the use of the new polyolester (POE) oils, system chemistry has changed. Unlike mineral & alkylbenzene oils, POE oil has solvent like tendencies. POE oil has the ability to suspend and recirculate small, solid contaminants left from system installation or retrofit.
Analysis of POE oil samples taken from actual systems have shown the oil to suspend and recirculate a high concentration of 2-20 micron sized particles, with the largest percentage between 2-10 microns. Although some particles are smaller than bearing tolerances, studies have shown bearing life can still be affected.
PART NO*
• High flow capacities with
low pressure drop
• Filter element utilizes an
O-ring seal
• Inert micro glass filter
material insures lubricant
compatibility
• Dimensions allow for easy
replacement of current filter
Bearing wear depends upon the size, hardness, and concentration of particles in circulation. To effectively remove these small particles, Sporlan developed a new type of oil filter.
The OF Series Oil Filters are designed to be 99% efficient in removing 3 micron sized particles and yet have sufficient flow capacity at a low pressure drop. The unsurpassed filtration ability of the oil filters will assure clean POE, mineral, or alkylbenzene oil is returned to the compressors. Clean oil insures proper operation of the oil level control and minimizes compressor wear.
The Sporlan OF Series Oil Filters were designed to virtually eliminate the need for oil changes resulting from suspended solid contaminants in circulation.
SPORLAN MODEL
OF-303 OIL FILTER
OF-303-T OIL FILTER
OF-303-BP OIL FILTER
ROF-413-T REPLACEABLE FILTER
OFE-1 OIL FILTER ELEMENT
*( ) Please contact your local Carlyle Certified Refrigeration Partner or
RCD Customer Service for P/N and Pricing.
656
SPORLAN
OIL LEVEL CONTROL SYSTEM
Sporlan’s Oil Level Control System Components were developed to offer the refrigeration industry an oil level control system of the highest quality. The heart of the system is the Oil Level Control which when matched with the Oil Reservoir and Oil Differential Check Valve maintains a minimum oil level in the compressor crankcase during all phases of system operation.
OIL RESERVOIR Type OR-1-1/2
The Sporlan Oil Reservoir (OR-1-1/2) is a holding vessel to contain the oil that is not within the crankcase, the oil separator, or in circulation. The OR-1-1/2 has an inlet and an outlet service valve so it may be isolated from the rest of the system, or the oil supply from the oil reservoir to the Oil Level Control can be eliminated for service. The OR-1-1/2 also contains two sight glasses so the maximum and minimum oil level can be observed. The sight glasses are placed on the shell symmetrically so 1/4 gallon of oil is contained between the lower sight glass and the bottom of the shell; 1 gallon is contained between the sight glasses; and 1/4 gallon is contained between the upper sight glass and the top of the shell. This allows the shell to be mounted vertically with either service valve on top. Depending on which end of the OR-1-1/2 Oil Reservoir is mounted to the top, the oil service valves will be pointing either right or left for piping convenience.
OIL DIFFERENTIAL CHECK VALVE
Types OCV-5, OCV-10, OCV-20
The Sporlan Oil Level Differential Check Valve (OCV) is installed on the 3/8 SAE fitting on top of the OR-1-1/2, and allows pressure to be relieved from the reservoir to the suction as required to maintain a pressure in the reservoir at a preset level above the suction pressure.
The pressure differential created by the OCV assures oil flow from the reservoir to the Oil Level Control providing there is adequate oil in the reservoir.
NOTE: OL-60CH replaces OL-1CH and OL-2CH;
OL-60FH replaces OL-1FH and OL-2FH models.
The OCV will only relieve pressure from the reservoir in excess of its fixed set point.
Systems with fluctuating suction pressure as a result of compressor unlades, staging or other suction line controls must be fitted with an OCV with a differential greater than the suction pressure fluctuation to assure oil flow from the
OR-1-1/2 through the oil level control to the compressor crankcase.
Sporlan offers OCV’s with a 5, 10, and 20 psi fixed differential setting. However, Sporlan recommends the use of an OCV-20 on all field built up applications.
OIL LEVEL CONTROLS
The purpose of the Sporlan Oil Level Control is to regulate the flow of oil to the compressor crankcase to maintain a minimum oil level as specified by the compressor manufacturer for any given application.
PART NO*
SPORLAN MODEL
OL-60CH OIL LEVEL CONTROL
OL-60FH OIL LEVEL CONTROL
OL-60XH OIL LEVEL CONTROL
OR-1-1/2 OIL RESERVOIR
OCV-10 CHECK VALVE
OCV-20 CHECK VALVE
OCV-30 CHECK VALVE
OCV-5 CHECK VALVE
S-OL OIL LEVEL SIGHT GLASS KIT
AOL-C ADAPTER
AOL-A COPELAND ADAPTOR
AOL-K-1 ADAPTOR KIT -OM-1
AOL-R-1 KIT
*( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD
Customer Service for P/N and Pricing.
TEMPERATURE RESPONSIVE MISCELLANEOUS VALVES, REPLACEMENT PARTS, PARTS
KITS, SOLENOID COILS, AND STRAINER
PART
NO*
SPORLAN MODEL
PART
NO*
SPORLAN MODEL
PART
NO*
SPORLAN MODEL
ADRHE-60/307 ODF
ADRHE-60/309 ODF
ADRIE-1-1/4-0/55 3X3 ODF ST
ADRIE-1-1/4-0/75 3X3 ODF ST
825-005 INLET STRAINER 5/8 ODF
825-007 INLET STRAINER 7/8 ODF
825-009 INLET STR 1-1/8 ODF
825-011 INLET STR 1-3/8 ODF
877-003 INLET STRAINER 3/8 ODF
877-004 INLET STRAINER 1/2 ODF
6034 Y-TYPE 1/2 FPT STRAINER
K-PI-E KIT
RK-SORIT-PI-2 0/100
RK-SORIT-PI-3 0/100
RK-SORIT-PI-4 0/100
KS-10G
KS-12DB
KS-12DC
KS-16DB
KS-ORI/CDA-15 INT PARTS KIT
KS-ORI/CDA-20 INT PARTS KIT
K-SORIT-PI KIT
K-Y1005-1 0/100 PILOT ASSY KIT
OMKC-2 120/50-60 JAM
OMKC-2 208-240/50-60 JAN
Y 1037-FV-1-1/2-190 3VX3 ODF 5’
Y 1037-FV-1-190 3VX3 ODF 30’
Y 1037-FV-2-190 3VX3 ODF 5’
Y1037-FV-1-190 3VXB 5 FT CAP
Y 1037-FV-3-190 3VX3 ODF 5’
Y 1037-FV-5-190 3VX3 ODF 5’
Y 1037-FV-1/2-190 3VX3 ODF 5’
Y 1037-FV-1/2-220 3VX3 ODF 5’
Y 1037-FV-1/2-230 3VX3 ODF 5’
Y 1037-FV-1/2-250 3VX3 ODF 5’
Y 1037-FV-1/3-190 3VX3 ODF 5’
Y 1037-FV-1-1/2-220 3VX3 ODF 5’
Y 1037-FV-1-1/2-230 3VX3 ODF 5’
Y 1037-FV-1-1/2-250 3VX3 ODF 5’
Y 1037-FV-1-220 3VX3 ODF 5’
Y 1037-FV-1-230 3VX3 ODF 5’
Y 1037-FV-1-250 3VX3 ODF 5’
* ( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service for P/N and Pricing.
657
SPORLAN
PART
NO*
SPORLAN MODEL
PART
NO*
SPORLAN MODEL
PART
NO*
SPORLAN MODEL
ADRHE-60/307 ODF
ADRHE-60/309 ODF
ADRIE-1-1/4-0/55 3X3 ODF ST
ADRIE-1-1/4-0/75 3X3 ODF ST
825-005 INLET STRAINER 5/8 ODF
825-007 INLET STRAINER 7/8 ODF
825-009 INLET STR 1-1/8 ODF
825-011 INLET STR 1-3/8 ODF
877-003 INLET STRAINER 3/8 ODF
K-PI-E KIT
RK-SORIT-PI-2 0/100
RK-SORIT-PI-3 0/100
RK-SORIT-PI-4 0/100
KS-12DB
KS-12DC
KS-16DB
KS-ORI/CDA-15 INT PARTS KIT
KS-ORI/CDA-20 INT PARTS KIT
K-SORIT-PI KIT
MKC-1 120/50-60 JAM
MKC-1 208-240/50-60 JAN
MKC-1 24/50-60 JAQ
MKC-1-DUAL/50-60 JAU
MKC-2 24/50-60 JAQ
MKC-2 120/50-60 JAM
MKC-2 208-240/50-60 JAN
MKC-2-DUAL/50-60 JAU
OMKC-2 120/50-60 JAM
OMKC-2 208-240/50-60 JAN
877-004 INLET STRAINER 1/2 ODF K-Y1005-1 0/100 PILOT ASSY KIT
6034 Y-TYPE 1/2 FPT STRAINER
* ( ) Please contact your local Carlyle Certified Refrigeration Partner or RCD Customer Service for P/N and Pricing.
658