Monessen Hearth DEB24NV Installation And Operating Instructions Manual

Add to My manuals
40 Pages

advertisement

Monessen Hearth DEB24NV Installation And Operating Instructions Manual | Manualzz

UNVENTED GAS LOG HEATER OR

VENTED DECORATIVE APPLIANCE

INSTALLATION AND OPERATING INSTRUCTIONS

MODELS: DEB20, DEB24, DEB30

Natural Gas or Propane/LPG

Control Type: Manual, Milli-Volt, Thermostat or Hi/Lo Remote Control

This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited by local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.

This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided.

Refer to page 8.

WARNINGS

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

– Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

– WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch; do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

– Installation and service must be performed by a qualified installer, service agency or the gas supplier.

READ AND SAVE THESE INSTRUCTIONS

CONTENTS

Important Safety Information ..................................3

Getting Started..........................................................5

Product Features and Specifications ....................6

Natural Gas .........................................................6

Propane/LP..........................................................6

Ignition Controls...................................................7

Pilot......................................................................7

Thermal Generator ..............................................7

General Installation Information ............................7

Codes ..................................................................7

Adequate Combustion and Ventilation Air ...........7

Fireplace and Hearth Dimensions .......................10

Placement in a Fireplace with a Restrictive Barrier

........................................................................... 11

Clearances and Height Requirements .................12

Floor Clearance .....................................................17

Fireplace Preparation ............................................18

Installing Vented Applications .............................19

Connecting the Gas ...............................................20

Checking Gas Pressure ........................................21

Manual Control ..................................................21

Milli-Volt/Thermostat Control .............................21

Hi/Lo Control......................................................21

Electrical Wiring (Milli-volt) ...................................22

Connecting Remote Receiver............................23

Installing Thermostat Sensor.............................23

Operation of Thermostat Sensor .......................25

Log Placement .......................................................26

Placing the Decorative Rock .............................27

Flame Appearance..................................................27

Milli-Volt/Thermostat Control .............................27

Manual Control ..................................................27

Hi/Lo Control......................................................27

Checking Burner Flames ......................................28

Operating Instructions...........................................29

For Your Safety Read Before Lighting ...............29

Manual Control Lighting Instructions ................30

Milli-Volt/Thermostat Control

Lighting Instructions...........................................31

Hi/Lo Control Lighting Instructions.....................32

Match Lighting Instructions ................................33

Cleaning Instructions.............................................33

Troubleshooting .....................................................34

Illustrated parts breakdown .................................34

Replacement Parts .................................................36

Burner Assembly ...............................................36

Logs...................................................................38

Warranty ....................................................Back page

2

44D0060 44D0060

3

2

44D0060

IMPORTANT SAFETY INFORMATION

INSTALLER

Please leave these instructions with the owner.

OWNER

Please retain these instructions for future reference.

IMPORTANT

Read these instructions carefully before installing or trying to operate this vent-free gas heater.

• Any change to this heater or its controls can be dangerous.

• Improper installation or use of the heater can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.

• Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns.

• Do not use a blower insert, heat exchanger insert or other accessory, not approved for use with this heater where applicable.

1. Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.

2. Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition.

3. Young children should be carefully supervised when they are in the same room with the appliance.

4. Do not place clothing or other flammable material on or near the appliance.

5. Any safety screen or guard removed for servicing an appliance, must be replaced prior to operating the heater.

6. Installation and repair should be done by a qualified service person.

7. To prevent malfunction and/or sooting, an unvented gas heater should be cleaned before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways be kept clean.

8. CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Have the heater serviced as it may not be operating properly.

9. The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas

Code, ANSI Z223.l/NFPA54.

10. This unit complies with ANSI Z21.11.2-2001 Unvented

Heaters and also complies with ANSI Z21.60-2000 Decorative Vented Appliances for Solid Fuel Burning Fireplaces. State and local codes may only allow operation of this appliance in a vented configuration. Check your state or local codes. For vented operation, see “Vented

Instructions

” in this manual.

11. Do not install the heaters in a bathroom or bedroom.

12. Correct installation of the ceramic fiber logs, proper location of the heater, and annual cleaning are necessary to avoid potential problems with sooting. Sooting, resulting from improper installation or operation, can settle on surfaces outside the fireplace. See log placement instructions for proper installation.

13. Avoid any drafts that alter burner flame patterns. Do not allow fans to blow directly into fireplace. Do not place a blower inside burn area of firebox. Ceiling fans may create drafts that alter burner flame patterns. Sooting and improper burning will occur.

14. Caution: Candles, incense, oil lamps, etc. produce combustion byproducts including soot. Vent-free appliances will not filter or clean soot produced by these types of products. In addition, the smoke and/or aromatics (scents) may be reburnt in the vent-free appliance which can produce odors. It is recommended to minimize the use of candles, incense, etc. while the vent-free appliance is in operation.

15. This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. See page 8.

Continued on page 4

44D0060

3

IMPORTANT SAFETY INFORMATION

Continued from page 3

16. Keep room area clear and free from combustible materials, gasoline and other flammable vapors and liquids.

17. Unvented gas heaters are a supplemental zone heater.

They are not intended to be the primary heating appliance.

18. Unvented gas heaters emit moisture into the living area.

In most homes of average construction, this does not pose a problem. In houses of extremely tight construction, additional mechanical ventilation is recommended.

19. During manufacturing, fabricating and shipping, various components of this appliance are treated with certain oils, films or bonding agents. These chemicals are not harmful but may produce annoying smoke and smells as they are burned off during the initial operation of the appliance; possibly causing headaches or eye or lung irritation. This is a normal and temporary occurrence.

The initial break-in operation should last two to three hours with the burner at the highest setting. Provide maximum ventilation by opening windows or doors to allow odors to dissipate. Any odors remaining after this initial break-in period will be slight and will disappear with continued use.

20. Input ratings are shown in BTU per hour and are for elevations up to 2,000 feet. For elevations above 2,000 feet, input ratings should be reduced 4 percent for each 1,000 feet above sea level. Refer to the National

Fuel Gas Code.

21. The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).

22. The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig

(3.5 kPa).

23. Do not use this room heater if any part has been under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.

24. This appliance must not be used with glass doors in the closed position. This can lead to pilot outages and severe sooting outside the fireplace.

25. Never burn solid fuels in a fireplace where a unvented room heater is installed.

26. Always have a fireplace screen in place when the appliance is in operation and, unless other provisions for combustion air are provided, the screen must have an opening(s) for induction of combustion air.

4

44D0060 44D0060

5

GETTING STARTED

MAKE SURE YOU HAVE RECEIVED ALL PARTS:

Check your packing list to verify that all listed parts have been received. You should have the following:

• Unvented gas log grate/burner assembly • Two (2) Plastic bags containing crushed volcanic rock

• Installation/operating instructions • Two (2) anchoring screws

• Ceramic Fiber logs

The milli-volt controlled version of this heater is the only style designed to be operated with optional devices for

ON/OFF functions. The following options may be used with the milli-volt controlled heater. These options are not packaged with the log set.

• Hand held Remote with receiver • Wall thermostat with 15' wire

• Wall switch with 15' wire • Hand held Thermostat Remote with receiver

• Thermostat sensor

The following options may be used with Hi/Lo control heater.

• Hand held Remote with receiver

• Handle the gas log burner assembly by the grate only. Do not pick the unit up by the burners.

• Gloves are recommended when handling ceramic fiber logs to prevent skin irritation from loose fibers. Logs are fragile — handle with care.

Carefully inspect the contents for shipping damage. If any parts are missing or damaged, immediately inform the dealer from whom you purchased the appliance. Do not attempt to install any part of the appliance unless you

have all parts in good condition.

WHAT YOU WILL NEED FOR INSTALLATION:

You should have the following items available before proceeding with installation:

• External regulator (for propane/LPG and 1/2 lb. natural gas systems only)

• Piping which complies with local codes • Sediment trap (recommended)

• Screwdriver • Tee joint.

• Pipe sealant approved for use with propane/LPG (Resistant to sulfur compounds)

• Drill with 5/32 bit • Pipe wrench or appropriate size crescent wrench set

• Manual shutoff valve

4

44D0060 44D0060

5

PRODUCT FEATURES

AND

SPECIFICATIONS

NATURAL GAS

NOTE: An external regulator is required to reduce supply pressure to a maximum of 10

1

/

2

" W.C. (11"

W.C. for HI/LO) on natural gas systems operating at higher pressure.

Manual Pressure Milli-Volt and T-Stat Pressure Hi/Lo Pressure

Regulator Pressure: Setting: 3.0" w.c. Regulator Pressure Setting: 3.5" w.c. Regulator Pressure Setting: 3.5" w.c.

Pilot Regulator: 3.5" w.c.

Gas Inlet Pressure: Max. 10

1

/

2

" w.c. Gas Inlet Pressure: 10

1

/

2

" w.c.

Min. 5" w.c. Min. 5" w.c.

Pilot Regulator: 3.5" w.c.

Gas Inlet Pressure: Max. 11" w.c.

Min. 6" w.c.

Gas Rate

Model Number Control Max BTU/Hr

DEB20NM MANUAL 28,000

DEB24NM MANUAL 38,000

DEB30NM MANUAL 38,000

DEB20NV MILLI-VOLT 28,000

DEB24NV MILLI-VOLT 38,000

DEB30NV MILLI-VOLT 38,000

DEB20NH HI/LO 28,000

DEB24NH HI/LO 38,000

DEB30NH HI/LO 38,000

DEB20NT THERMOSTAT 28,000

DEB24NT THERMOSTAT 38,000

DEB30NT THERMOSTAT 38,000

Min BTU/Hr

18,000

20,000

20,000

18,000

25,000

25,000

18,000

20,000

20,000

18,000

25,000

25,000

PROPANE/LPG

Note: An external regulator is required to reduce supply pressure to a maximum of 13" w.c.

Manual Pressure Milli-Volt and T-Stat Pressure Hi/Lo Pressure

Regulator Pressure Setting: 10" w.c. Regulator Pressure Setting: 10" w.c. Regulator Pressure Setting: 10" w.c.

Gas Inlet Pressure: Max. 13" w.c. Gas Inlet Pressure: Max. 13" w.c.

Min. 11" w.c. Min. 11" w.c.

Gas Inlet Pressure: Max. 13: w.c.

Min. 12" w.c.

Gas Rate

Model Number Control Max BTU/Hr Min BTU/Hr

DEB20PM MANUAL 28,000 18,000

DEB24PM MANUAL 38,000

DEB30PM MANUAL 38,000

DEB20PV MILLI-VOLT 28,000

DEB24 PV MILLI-VOLT 38,000

DEB30PV MILLI-VOLT 38,000

DEB20PH HI/LO 28,000

DEB24PH HI/LO 38,000

DEB30PH HI/LO 38,000

DEB20PT THERMOSTAT 28,000

DEB24PT THERMOSTAT 38,000

DEB30PT THERMOSTAT 38,000

20,000

20,000

20,000

30,000

30,000

21,000

22,000

22,000

20,000

30,000

30,000

6

44D0060 44D0060

7

PRODUCT FEATURES

AND

SPECIFICATIONS

IGNITION CONTROLS

Piezo ignitor allows ignition of the pilot without the use of matches or batteries.

Manual control has three (3) positions:

OFF - All gas to the gas logs is shut off at the valve.

IGN - Valve position to light/maintain a standing pilot.

HI/LOW - Variable position corresponding to desired flame height.

Hi/Lo remote control valve has five (5) positions:

OFF - All gas to the gas logs is shut off at the valve.

IGN - Position not used on this log set.

PILOT - Valve position to light/maintain a standing pilot.

ON - Valve position to turn ON.

HI/LOW - Variable position corresponding from pilot only to desired flame height.

Milli-Volt and T-Stat control has four (4) positions:

OFF - All gas to the gas logs is shut off at the valve.

IGN

ON

- Valve position to light/maintain a standing pilot.

- Valve position to turn ON/OFF log set with remote switch/thermostat.

LOW/HI - Variable position to control flame height (heat output).

PILOT/ODS

The gas log heater is fitted with a specially designed safety pilot (ODS assembly) which senses the amount of oxygen available in the room and shuts the gas log heater off if the oxygen level begins to drop below a satisfactory level. The pilot can only be relit when adequate fresh air is available.

THERMAL GENERATOR

The milli-volt/t-stat gas log pilot is fitted with a milli-volt (thermopile) generator to provide power for remote activation.

6

44D0060 44D0060

7

GENERAL INSTALLATION INFORMATION

CODES

Adhere to all local codes or, in their absence, the latest edition of THE NATIONAL FUEL GAS CODE ANSI Z223.1 or NFPA54 which can be obtained from…

American National Standards Institute, Inc.

1430 Broadway

New York, NY 10018 or

National Fire Protection Association, Inc.

Batterymarch Park

Quincy, MA 02269

ADEQUATE COMBUSTION AND VENTILATION AIR

This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.

The National Fuel Gas Code, (ANSI Z223.1/NFPA 54), defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 BTU per hour (4.8 m

3

per kw) of the aggregate input rating of all appliances installed in that space. An unconfined space is defined as a space whose volume is not less than 50 cubic feet per 1,000 BTU per hour (4.8 m

3

per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

UNUSUALLY TIGHT CONSTRUCTION IS DEFINED AS CONSTRUCTION WHERE…

a) walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of 1 perm

(6 x 10

11

kg per pa-sec-m

2

) or less with openings gasketed or sealed; b) weather striping has been added on openable windows and doors, and c) caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

8

44D0060 44D0060

9

8

44D0060

GENERAL INSTALLATION INFORMATION

Counter

Fireplace

Figure 1 - Example of a Large Room with 1/2 Wall Divider

The following formula can be used to determine the maximum heater rating per the definition of unconfined space:

BTU/Hr = (L

1

+ L

2

) Ft x (W) Ft x (H) Ft

50 x 1000

Consider two connecting rooms with an open area between, with the following dimensions:

L

1

= 15

1

/

2

Ft., L

2

= 12 Ft., W = 12 Ft., H = 8 Ft.

BTU/Hr = (15

1

/

2

+ 12) x (12) x (8)

50 x 1000 = 52800 BTU/Hr

If there were a door between the two rooms the calculation would be based only on the room with the heater.

BTU/Hr = (15

1

/

2

) x (12) x (8)

50 x 1000 = 29760 BTU/Hr

If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel

Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.

44D0060

9

FIREPLACE AND HEARTH DIMENSIONS

This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built fireplace or in a listed ventless firebox enclosure. It has been design certified for these installations.

Exception: DO NOT install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.

Use manufacturer's installation and clearance requirements as defined in their manual.

The DEB Series unvented room heater is approved for installation into the following unvented fireplaces:

GCUF Series Fireboxes 32, 36, or 42

The DEB Series unvented room heater may also be installed into a Ventless Firebox Enclosure for Gas Fired Decorative Type

Unvented Room Heaters per IAS Requirement No. 2-97 ANSI Z21.91-2001 (typically referred to as a "Universal Firebox"), as long as firebox hearth dimensions meet the minimum hearth dimensions shown below.

Model A B C D

DEB20 18" 13

1

/

4

" 27" 17"

DEB24 22

1

/

4

" 13

1

/

4

" 28

1

/

2

" 17"

DEB30 25

1

/

2

" 13

1

/

4

" 32

1

/

2

" 17"

Figure 2 - Hearth Minimum Dimension

10

44D0060 44D0060

11

10

44D0060

PLACEMENT IN A FIREPLACE WITH A RESTRICTIVE BARRIER

IMPORTANT INFORMATION FOR THE INSTALLATION OF THIS GAS LOG SET

The following are guidelines for placing a gas log set in a fireplace that has a restrictive barrier along the bottom front opening of the fireplace. Some examples of barriers are glass/screen door frames and sunken/recessed fireplaces.

Height of Restriction (X) Minimum Depth of Fireplace/Firebox

No restriction 13

1

/

4

"

0 to 1

1

/

2

" 16"

From 1

1

/

2

" to 3" 16"

Greater than 3" ANY BARRIER GREATER THAN THREE INCHES (3")

PLACED IN FRONT OF THE GAS LOG SET IS NOT

RECOMMENDED BY THE MANUFACTURER.

Glass door frames with adjustable louvers should have the louvers fully

open while the unit is in operation.

The log set should be placed against or as near as possible to the rear wall of the fireplace/firebox.

Height of restrictive barrier caused by glass door frames, recessed fireplaces, etc. from the

X

base or bottom surface of the unit. (Refer to Table).

Depth of fireplace/firebox.

(Refer toTable).

Figure 3 - Reference Drawing of a Natural Flame Log Set in an Enclosure

Barriers such as the bottom of a glass door frame placed in front of a gas log set can change the air flow characteristics of the fireplace which in turn can cause the unit to overheat and malfunction.

NOTE: Non combustible material such as refractory brick may be used to line the floor of the fireplace in order to raise the height of the gas log set in relation to a restrictive barrier. If the unit is raised, the minimum height dimension listed in the homeowner’s manual must not be exceeded.

NOTE: If the log set is equipped with a remote receiver, a restrictive barrier may reduce the battery life by increasing the ambient temperature inside the fireplace. Placement of the receiver outside of the fireplace will extend the battery life.

44D0060

11

CLEARANCES

AND

HEIGHT REQUIREMENTS

The dimensions shown in Figures 4 through 12 and defined in the fireplace manufacturer's instructions are minimum clearances to maintain when installing this heater. Left and right clearances are determined when facing the front of the heater.

When heater is installed into a ventless firebox, minimum clearances, as specified by the ventless firebox manufacturer, must be met.

Follow these instructions carefully to ensure safe installation. Failure to follow instructions exactly can create a fire hazard.

Sidewall and ceiling clearances: The sides of the fireplace opening must be at least 16" from any combustible wall.

The ceiling must be at least 42" from the top of the fireplace opening.

���

���

Figure 4 - Sidewall and Ceiling Clearances

12

44D0060 44D0060

13

CLEARANCES and HEIGHT REQUIREMENTS

Heat resistant material (minimum requirements) with no wooden mantel or other combustible projection:

To install the gas logs into a fireplace with no wooden mantel, shelf or other combustible projection above the fireplace opening, measure the heat resistant material height, per Figure 5, then see TABLE A.

Heat resistant materials such as slate and marble must be at least 1/2” thick. Sheet metal should not be installed

onto combustible material.

IMPORTANT: If you cannot meet these minimum clearances you must operate the heater with chimney flue damper open.

Refer to “Installing Vented Applications” found on page 18.

����

���������

��������

�������

����

��������

������ ��

��������� ��

�������

12

44D0060

Figure 5 - Measuring Heat Resistant Material

HEAT RESISTANT REQUIREMENTS FOR SAFE INSTALLATION

MATERIAL

MEASUREMENT DEB20 DEB24 and DEB30

12" or more Hood not required. Hood not required.

8" to less than 12" Hood not required. Extend heat resistent material to 12" or install hood. See Figure 5.

Less than 8" Extend heat resistant Extend heat resistant material to at

material to at least 8" least 8" and install hood. See Figure

and install hood. 5. OR, extend heat resistant mater-

See Figure 5. ial to a height of at least 12".

TABLE A - Heat Resistant Material Requirements with no Mantel or Combustible Projection

44D0060

13

CLEARANCES and HEIGHT REQUIREMENTS

Heat resistant material (minimum requirements) with wooden mantel or other combustible projection:

To install the heater with a wooden mantel, shelf or other combustible projection above, first measure the heat resistant material shown in Figure 6, then refer to Table B.

������ ��

��������� ��

�������

����

�� �� ���� ��

���� ���������

��������

Figure 6 - Measuring Heat Resistant Material for Mantel

HEAT RESISTANT REQUIREMENTS FOR SAFE INSTALLATION WITH WOODEN MANTEL,

MATERIAL SHELF OR OTHER COMBUSTIBLE PROJECTION

MEASUREMENT

DEB20 DEB24 and DEB30

12" or more Hood not required. Observe profiles (side Hood not required. Observe profile (side

elevations) shown in Figure 7, page 15. elevations) shown in Figure 9, page 16.

8" to less than 12" Install hood and observe profiles shown Install hood and observe profiles shown

in Figure 8, page 15; OR extend heat in Figure 7, page 15; OR extend heat

resistant material to at least 12" and observe resistant material to at least 12" and observe

profiles shown in Figure 7, page 15. profiles shown in Figure 9, page 16.

Less than 8" Extend heat resistant material to at least Extend heat resistant material to at least

8", install hood and observe profiles shown 8", install hood and observe profiles shown

in Figure 8, page 15; OR extend heat in Figure 7, page 15; OR extend heat

resistant material to at least 12" and observe resistant material to at least 12" and observe

profiles shown in Figure 8, page 15. profiles shown in Figure 9, page 16.

TABLE B - Heat Resistant Material Heights and Mantel Location

14

44D0060 44D0060

15

CLEARANCES

AND

HEIGHT REQUIRMENTS

����

���������

��������

���

��

��

�� ��� ��

� ��

� ���

������ ��

��������� ��

�������

Example: A mantel may project from the wall a maximum of 2

1

/

2

" at a

minimum of 14" above the opening, and a maximum of 6" at a

minimum of 20 1

/

2

" above the opening.

14

44D0060

����

���������

��������

Figure 7 - Minimum Mantel Clearance with No Hood - DEB20

���

���

��

��

�� ��

� ��

� ��

� ���

����

������ ��

��������� ��

�������

Example: A mantel may project from the wall a maximum of 2

1

/

2

" at a

minimum of 8" above the opening, and a maximum of 6" at a

minimum of 14 1

/

2

" above the opening.

Figure 8 - Minimum Mantel Clearance with Hood - All Models

44D0060

15

CLEARANCES

AND

HEIGHT REQUIRMENTS

��� �� ����

����

���������

��������

��� ���� ���

������ ��

��������� ��

�������

Example: The bottom of the mantel may project from the wall a maximum of 10" at a minimum of 28" above the

Figure 9 - Minimum Mantel Clearance with No Hood — DEB24 and DEB30

��

��

��

��

��

Figure 10 is an example of an unsafe mantel installation.

This mantel projects 4" at 8" above the opening, exceeding the maximum acceptable distance of 2

1

/

2

" The mantel also projects 7" at 14

1

/

2

" above the opening, exceeding the maximum acceptable distance of 6".

If your mantel profile is unsafe, you may either:

• Raise the mantel to an acceptable height

OR

• Remove the mantel

Figure 10 - Minimum Mantel Clearance with No Hood - DEB24 and DEB30

(Example of Unsafe Installation)

16

44D0060 44D0060

17

FLOOR CLEARANCE

The gas log heater must be installed at least 5" above any combustible flooring material, such as carpeting or tile, which is closer than 14" to the base of the fireplace. The minimum distance must be maintained from the top surface of carpeting, tile, etc. See Figure 11.

OR,

The gas log heater may be installed nearer to the floor if a minimum of 14" of noncombustible material such as slate or marble is installed between the base of the fireplace and the combustible flooring. See Figure 12.

������ ��

��������� ��

�������

�����������

��������

�� �������

Figure 11 - Minimum Clearance above Combustible Flooring

16

44D0060

���� ��������

��� ��� ��

���� ���� ��

������ ��

��������� ��

�������

��� �������

�����������

��������

Figure 12 - Minimum Clearance above Combustible Flooring with

Noncombustible Material Installed at Base of Fireplace

44D0060

17

FIREPLACE PREPARATION

BEFORE FULLY INSTALLING THE UNIT:

• Turn OFF the gas supply to the fireplace or firebox.

• Seal any fresh air vents and/or ash clean-out doors located on the floor or wall of the fireplace. If left unsealed, drafting may cause pilot outage or sooting. Use a heat resistant sealant. Do not seal the chimney flue damper.

Before installing in a solid fuel burning fireplace, The chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner.

INSTALLING VENTED APPLICATIONS

Manual, milli-volt and Hi/Lo controlled gas logs may be installed as a vented decorative log set in compliance with ANSI

Z21.60 and National Fuel Gas Code, Section 6.6. Since, the gas logs are operated with the damper open, non-combustible

material and minimum mantel requirements do not apply.

This appliance is for installation only in a solid fuel burning fireplace (masonry fireplace or manufactured fireplace) with a working flue and constructed of noncombustible material.

Exception: DO NOT install this appliance in a factory-built fireplace that includes instructions stating that it has not been tested or should not be used with unvented gas logs. This log set may be installed as a vented log set.

BEFORE INSTALLING THE APPLIANCE:

• Turn off gas supply to fireplace or firebox.

• Have the fireplace floor and chimney professionally cleaned to remove ashes, soot, creosote or other obstructions.

Have this cleaning performed annually after installation.

• Seal any fresh air vents or ash clean-out doors located on floor or wall of fireplace. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant.

Install and operate the appliance as directed in this manual.

DAMPER STOP INSTALLATION:

A damper stop must be provided with the unit. Contact your dealer to obtain one. The damper stop must be installed as shown in Figure 13 to prevent full closure of the fireplace damper blade and provide a minimum

29 square inch flue opening.

������ ����

������

Figure 13 - Damper Stop Installation.

(See WARNING at top of next page.)

18

44D0060 44D0060

19

18

44D0060

INSTALLING VENTED APPLICATIONS

The fireplace and gas logs function as a system. If the fireplace is spilling into the room

(check with a match or a smoke stick), reposition the damper clamp until a positive draft is obtained by opening the damper. If negative pressure in home prevents having a positive draft, contact your dealer for assistance.

PLACING AND SECURING APPLIANCE

You must secure the gas log heater to the fireplace floor. If not, the entire unit may move when you adjust the controls. Movement of unit may cause shifting of the gas logs which leads to sooting and improper burning. Grate movement could cause a gas leak.

Special care is required if you are installing the unit into a sunken fireplace.

You must raise the fireplace floor to allow access to gas log controls. This will insure adequate air flow and guard against sooting. Raise the fireplace floor using noncombustible materials, as described in “Placement in a Fireplace with Restrictive

Barrier” on page 11.

ASSEMBLY PROCEDURE:

1. Center the gas log unit in the fireplace or firebox. Make certain the front feet of the grate sit inside the front edge of the fireplace or firebox.

2. Anchor holes are located on the right and left sides of the unit. After centering the grate correctly, mark the hole positions on the fireplace/firebox floor. Drill two (2)

5

/

32

" diameter holes approximately 1

1

/

2

" deep.

3. Anchor the grate to the fireplace/firebox floor using the screws provided. See Figure 14.

Proper installation of the grate is essential to prevent any movement of the gas logs and controls during operation.

Screw

Screw

Anchor

Hole

Anchor

Hole

Figure 14 - Securing Heater to Floor of Fireplace/Firebox

44D0060

19

CONNECTING THE GAS

NOTICE: A qualified gas appliance installer must connect the heater to the gas supply. Consult all local codes.

Use new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, section 2.6.3, providing gas meets hydrogen sulfide limits, and where permitted by local codes. Gas piping system must be sized to provide minimum inlet pressure (Listed on Data Plate) at the maximum flow rate (BTU/Hr).

Undue pressure loss will occur if the pipe is too small.

A manual shutoff valve must be installed upstream of the appliance. Union tee and plugged

1

/

8

" NPT pressure tapping point should be installed upstream of the appliance. See Figure 15.

To Heater

Valve

Pipe Coupling

Pipe

Locations that the Pressure

Tapping Point May Be Installed

Stainless

Flexible Tube

Manual Shutoff

Valve

Gas Supply

Inlet

Figure 15 - Gas Connection

IMPORTANT: Hold heater valve firmly with a wrench to prevent movement when connecting to inlet pipe.

CHECK GAS TYPE: The gas supply must be the same as stated on the heater’s rating plate. If the gas supply is different, DO NOT INSTALL THE HEATER. Contact your dealer for the correct model.

Always use an external regulator for all propane/LPG heaters and high pressure one to two-pound systems

only, to reduce the supply tank pressure to a maximum of 13" w.c. This is in addition to the internal regulator in the heater valve.

20

44D0060 44D0060

21

20

44D0060

Connecting directly to an unregulated propane/LPG tank can cause an explosion.

CHECKING GAS PRESSURE

The heater gas inlet connection is a

3

/

8

" NPT at the valve. On all control type units, the inlet connection is on the right side of unit.

To connect from the opposite side, route the pipe around the back portion of the unit.

When tightening up the joint to the valve, hold the valve securely to prevent movement.

Test all gas joints from the gas meter to the heater valve for leaks using a gas analyzer or soap and water solution after completing connection. DO NOT USE AN OPEN FLAME.

Check the gas pressure with the appliance burning and the control set to HIGH.

MANUAL CONTROL (Figure 16)

The pressure regulator is preset and locked to dis-

courage tampering. If the pressure is not as specified, replace the regulator with the correct part from the parts list in this manual.

Remove

1

/

8

" NPT plug, located on side of regulator body. Install fitting and tubing to pressure gauge. After taking pressure reading, reinstall test plug. Check for gas leaks.

NPT Test Plug

Figure 16 - Pressure Test Point Location

Manual Control

Test Port “OUT”

MILLI-VOLT AND T-STAT CONTROL (Figure 17)

The valve regulator controls the burner pressure which should be checked at the pressure test point.

Turn captured screw counter clockwise two or thre turns and then place tubing to pressure gauge over test point

(Use test point “OUT” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.

Figure 17 - Pressure Test Point Location

Milli-Volt Control

HI/LO REMOTE CONTROL (Figure 18)

Turn captured screw counter clockwise two or three turns. (The port is labeled A) Place tubing to pressure gauge over test point. After taking pressure reading, be sure to turn captured screw clockwise firmly to reseal.

Do not over torque. Check for gas leaks.

NOTE: If outlet pressure checks low, check inlet pressure. See page 6 for correct pressure for your unit.

A

“OUT”

Test Port

Figure 18 - Pressure Test Point Location

Hi/Lo Control

44D0060

21

ELECTRICAL WIRING (MILLI-VOLT)

The milli-volt valve is a self-powered combination gas control THAT DOES NOT REQUIRE 110 VAC TO

OPERATE.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

ODS

Pilot

On/Off

Switch

ODS

Pilot

Wall

Switch

On/Off

Switch

TH = 3

TP = 1

TP/TH = 2

Milli-volt

Valve

Spade

Terminal

Switch

Figure 19 - Wiring Diagram

Optional Wall

Switch, Remote

Receiver or

Optional T-Stat

CONNECTING OPTIONAL WALL SWITCH OR THERMOSTAT

1. Use 18 awg, two-wire cable, 15 feet maximum length.

2. At one end of the cable, connect both wires to the wall switch or thermostat. At the other end, connect one wire to

TP/TH and one wire to TH, or connect the wall switch/thermostat to the two male (0.25") terminals on the left side of the unit. The color of the wires does not matter.

22

44D0060 44D0060

23

22

44D0060

ELECTRICAL WIRING (MILLI-VOLT)

CONNECTING REMOTE RECEIVER

THESE INSTRUCTIONS SUPERCEDE THE SECTION

ENTITLED “HEARTH MOUNT” IN THE MILLI-VOLT

HAND-HELD REMOTE INSTRUCTIONS SUPPLIED

WITH THE REMOTE.

1. Cut cable to length (approximately 12") for placement in the fireplace.

2. Strip back each wire.

1

/

4

" of the insulation from both ends of

3. Connect two .25 female connectors to the wires at one end of the cable.

4. Insert the opposite ends of the wires into the receiver wire terminals and tighten the screws.

5. Connect the connectors to the two .25" male connectors located on the right side when facing the unit (Figure 20).

Do not let the wire touch the grate or burners.

Remote

Receiver

Remote

Wire

Connectors

Figure 20 - Installing Remote Receiver

6. Stick velcro pads with self-adhesive backing to side of remote receiver and to the right side of the unit. See Figure 20.

7. Attach remote receiver with velcro pads. Control switch must face forward.

NOTE: Heat reduces battery life. You can protect the receiver and extend battery life by mounting the receiver in a wall or other location outside the fireplace.

INSTALLING T-STAT SENSOR (OPTION SOLD SEPARATELY)

1. Remove metal bracket and label from box.

2. Peel away the paper backing on the label. Line up holes in label with holes on the bracket. Right side of label should flush with right side of bracket. See Figure 21. Press label firmly and smoothly to bracket.

3. Using Phillips screwdriver, install t-stat sensor to bracket with two screws provided. See Figure 22. Make sure the thermo bulb wire is at the bottom of t-stat sensor.

4. Plug in wiring harnesses to back of t-stat sensor. See Figure 22.

Wiring

Harnesses

Bracket

T-Stat

Sensor

���

���

����

��

���

���

���

��

����

��

���

Line Up

Holes

���

����

���

���

����

���

Flush edge of label to right side of bracket

Screws

Thermo Bulb

Figure 21 - Applying Label to Bracket

Figure 22 - Installing T-Stat Sensors and Wiring Harnesses

44D0060

23

ELECTRICAL WIRING (MILLI-VOLT)

5. Route wiring harnesses through large hole on side of unit. Mount bracket to side of unit with screw provided. See Figure

23.

6. Attach wiring harness to either TP/TH and TH on control valve or to existing wiring harness with two (2) 0.250" male spade terminals for remote or t-stat option. See Figures 23 and 24.

7. Install knob to shaft of t-stat sensor. See Figure 23.

8. Place thermo bulb in front of the firebox for incoming air.

Wiring Harnesses

Screw

Knob

���

��

���

��

���

���

����

���

T-Stat

Sensor and

Bracket

Thermo Bulb

Figure 23 - Installing T-Stat Sensor to DEB Base with Screw Provided

TH

TP/TH

Wiring Harnesses

Figure 24 - Attaching Wiring Harnesses to Control Valve

24

44D0060 44D0060

25

24

44D0060

ELECTRICAL WIRING (MILLI-VOLT)

OPERATION OF THERMOSTAT SENSOR

1.Follow millivolt lighting instructions on lighting plate attached to unit or in homeowner’s manual.

2.With control knob in the “ON” position make sure the ON/OFF switch is in the “OFF” position. See Figure 25.

3.The unit is now being controlled by the thermostat sensor. The sensor will now cycle the burners on and off. You can adjust how often the unit cycles by turning the control knob on the sensor.

ON/OFF

Switch

���

���

����

��

���

Control

Knob

���

����

���

T-Stat

Sensor

Figure 25 - Control Knob in “ON” Position and ON/OFF Switch in “OFF” Position

CHECKING SYSTEM OPERATION

The milli-volt system and individual components may be checked with a milli-volt meter having a 0-1000 mV range. Conduct each check shown in chart below by connection meter test leads to terminals as indicated.

CONNECT

CHECK TO METER THERMOSTAT METER

TEST TEST LEADS TO CONTACTS READING

TERMINALS SHOULD BE

A COMPLETE 2 & 3 CLOSED MINIMUM

SYSTEM 175

B THERMOPILE 1 & 2 OPEN MINIMUM

OUTPUT 500

A. COMPLETE MILLI-VOLT SYSTEM CHECK

(“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should turn ON)

a. If the reading is more than 175 milli-volts and the automatic valve still does not come on, replace the control.

b. If the closed circuit reading (“A” reading) is less than 175 milli-volts, determine cause for low reading, proceed to

Section B below.

B. Thermopile Output Reading Check

(“B” Reading - Thermostat contacts OPEN - Main burner OFF)

1. Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot voltage, 500 milli-volts minimum. If the minimum milli-volt reading is not obtainable, replace pilot.

44D0060

25

LOG PLACEMENT

Before you begin — This unit is supplied with four or five ceramic fiber logs. Do not handle these logs with your bare hands. Always wear gloves to prevent skin irritation from ceramic fibers. After handling the logs, wash your hands gently with soap and water to remove any traces of fibers.

The positioning of the logs are critical to the safe and clean operation of this heater.

Sooting and other problems may result if the logs are not properly and firmly positioned in the appliance. Never add additional logs or embellishments such as pine cones, vermiculite or rock wool to the heater. Only use the logs supplied with the unit.

Failure to position the parts in accordance with diagrams below or to use only parts specifically approved for this heater may result in property damage or personal injury.

INSTALLING LOGS ON GRATE (See Figures 26 and 27 )

NOTE: Model DEB18 has 4 logs and Models DEB24 and DEB30 has 5 logs.

1. Install back log (#1) on two pins located near the back of base. Check log position and stability.

2. Install right center log (#2) on pins located near right front of base and center of base.

3. Install left center log (#3) on pin located near left front of base and on top of right center log (#2).

4. Install middle front log (#4) in front of center log. Make sure bottom of log is resting on the center of grate. Do not let log #4 contact the front burner.

Log

#4

Log #6

Log #6

Log #4

5. DEB 24 and DEB 30 only: Rest right end of left front log (#5) on log #3 and the top of left front log on log #1.

Log

#1

Log #5

(24 & 30 only)

Log #3

6. Place back end of top center log

(#5) on recessed area of back log

(#1). Cross log #6 over log #2 and rest right extension on grate. Log #6 should fit on pin on center log #3.

Log

#3

Log

#2

Back

Pins

Back

Pins

Left Front Pin

Left Front Pin

Log

#2

Log

#1

Right Front and

Center Pins

Figure 26 - Installing Logs to Grate (Model DEB20)

Right Front and

Center Pins

Figure 27 - Installing Logs to Grate

(Models DEB24 and DEB30)

26

44D0060 44D0060

27

26

44D0060

FLAME APPEARANCE

PLACING THE DECORATIVE ROCK

DO NOT sprinkle volcanic rock on the logs, around the pilot, or on or near burners. This may cause sooting. Place volcanic rock only on the floor of the fireplace.

During initial operation of the new heater, burning logs will give off a paper burning smell and orange flames will be present. Simply open the windows for a few hours to vent the odor.

Flames from the pilot, front and rear burner should be visually checked as soon as the heater is installed.

In addition, periodically check the flames visually during operation.

CHECKING THE PILOT FLAME

The pilot flame must always be present when the heater is in operation. It should just touch the top of the thermocouple tip for natural. See Figures 28 and 30 for correct pilot flame.

If the pilot flame does not touch the thermocouple, then the main burner cannot function reliably. See Figures 29 and 31 for incorrect shape of pilot flame.

MILLI-VOLT CONTROL AND THERMOSTAT CONTROL

Thermocouple for Natural

Thermocouple for Natural

Thermocouple for LP

Figure 28 - Correct Appearance of Pilot Flame

MANUAL CONTROL AND HI/LO CONTROL

Thermocouple for LP

Figure 29 - Incorrect Appearance of Pilot Flame

Thermocouple for Natural

Thermocouple for Natural

Thermocouple for LP

Thermocouple for LP

Figure 30 - Correct Appearance of Pilot Flame Figure 31 - Incorrect Appearance of Pilot Flame

44D0060

27

CHECKING THE BURNER FLAME

In normal operation at full rate after 15 minutes, the following flame appearances should be observed:

Glowing Embers

Figure 32 - Correct Appearance of Rear Flames

The left and right rear flames should be yellow and extend 1"-2" above the mid log top surfaces. The yellow flames should

not contact the logs. There should be glowing embers on the middle log. Note: The front flames and embers will be

an opaque orange color during the burn off time.

OPERATING INSTRUCTIONS

Avoid any drafts that alter burner flame patterns. Do not allow fans to blow directly into the fireplace. Do not place a blower inside the burn area of the firebox. Ceiling fans may create drafts that alter flame patterns. Sooting and improper burning will result.

During manufacturing, fabricating and shipping, various components of this appliance are treated with certain oils, films or bonding agents. These chemicals are not harmful, but may produce annoying smoke and smells as they are burned off during the initial operation of the appliance, possibly causing headaches or eye or lung irritation. This is

a normal and temporary occurrence.

The initial break-in operation should last two to three hours with the burner at the highest setting. Provide maximum ventilation by opening windows or doors to allow odors to dissipate. Any odors remaining after this initial break-in will be slight and will disappear with continued use.

This appliance must not be used with glass doors in the closed position. This can lead to pilot outages and severe sooting outside the fireplace. See Figure 3, page 11.

28

44D0060 44D0060

29

OPERATING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

If you do not follow these instruction exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance is equipped with a piezo ignition device which lights the pilot. If piezo is not working properly see “Match Lighting Instructions”, page 33.

B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

• Do not attempt to light any appliance.

• Do not touch any electric switch; do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part of it has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.

Piezo

Ignitor

28

44D0060

Switch

Control Knobs

Figure 33 - Location of Piezo Ignitor, Control Knobs and Switch on Milli-volt, Thermostat, Hi/Lo and Manual Units

44D0060

29

OPERATING INSTRUCTIONS

MANUAL CONTROL LIGHTING INSTRUCTIONS

1. STOP! Read the safety information.

2. Make sure the manual shutoff valve is fully open.

3. This heater is equipped with an ignition device (piezo) which automatically lights the pilot.

4. Refer to Figure 33, page 29 for the location of the piezo ignitor and control knob. Push in gas control knob slightly and turn control knob clockwise to the OFF position.

NOTE: Knob cannot be turned to OFF unless knob is pushed in slightly. Do not force.

5. Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas STOP!

Follow the instructions under “What To Do if You Smell Gas”, page 29. If you do not smell gas, go to the next step.

6. From OFF position, push in gas control knob slightly and turn counterclockwise to the IGN position. See Figure 34. Push in and hold control knob for 5 seconds.

NOTE: If you are running the heater for the first time, it will be necessary to press in the control knob for 30 seconds to allow air to bleed out of the gas piping.

7. With the control knob pushed in, push and release the piezo ignitor button to light the ODS pilot. The pilot is located on the left side of the heater, behind the middle log and on the back of the rear burner. If piezo ignitor does not light the pilot, refer to “Match Lighting Instructions”, page 33.

8. Hold the control knob in for an additional 10 seconds to prevent the ODS pilot from shutting off the gas while the thermocouple is warming up.

9. Release the control knob.

• If the knob does not pop out when released, stop and immediately call your service technician or gas supplier.

• If the ODS pilot will not stay lit after several tries, push and turn the gas control knob clockwise

to OFF and wait 15 seconds. Repeat steps 6 through 9.

10. Push in control knob and turn counterclockwise to the HIGH setting. At this location the control knob will pop out when positioned correctly. The knob can now be positioned at any position between HIGH and LOW. Refer to Figures 35 and 36.

Rotate

Rotate

Rotate

Push

Figure 34 - IGN Position

Push

Figure 35 - HIGH Position Figure 36 - LOW Position

Wait 30 seconds before readjusting the heater when the control knob has been turned down to a lower setting.

TO TURN OFF GAS TO HEATER

1. Turn control knob clockwise to OFF position to completely shut off the heater.

2. If applicable: Turn off all electric power to the heater.

30

44D0060 44D0060

31

30

44D0060

OPERATING INSTRUCTIONS

MILLI-VOLT

AND

THERMOSTAT

CONTROL LIGHTING INSTRUCTIONS

1. STOP! Read the safety information label.

2. Make sure the manual shutoff valve is fully open.

3. This gas log set is equipped with an ignition device (piezo) which automatically lights the pilot. If piezo ignitor does not light the pilot, refer to instructions for “Match Lighting Instructions”, page 33.

4. Turn gas control knob clockwise and turn ON/OFF switch to OFF position.

to the OFF position, set the thermostat to the lowest setting

5. Wait (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP!

Follow the instructions under “What To Do If You Smell Gas,” page 29.

6. From OFF position, turn the gas control knob counterclockwise to IGN position. Push in control knob for 5 seconds. NOTE: If you are running the heater for the first time, it may be

necessary to press in the control knob for 30 seconds or longer to allow air to bleed out of the gas piping.

7. With the control knob pushed in, push in and release the piezo ignitor button to light the pilot.

8. Continue pushing the control knob in for a further 10 seconds to prevent the flame detector from shutting off the gas while the probe is warming up. Release the control knob.

9. Turn gas control knob counterclockwise to the ON position.

10. After the pilot has been lit for one minute, the burners can be turned on. Turn the ON/OFF switch to

ON position or adjust thermostat to desired setting. NOTE: To use the thermostat function (if

installed) the control knob must be set to “ON” and ON/OFF switch must be in the “OFF” position.

11. If the gas logs will not operate, follow the instructions “To Turn Off Gas To Heater” below and call your service technician or gas supplier.

On/Off Switch

Hi/Lo Control

Ignitor Pilot Control

Piezo

Figure 37 - Pilot

Figure 38 - Control Cover Plate for Milli-Volt

TO TURN OFF GAS TO HEATER

1. Turn control knob clockwise to OFF position to completely shut off the heater.

2. If applicable: Turn ON/OFF switch to OFF position and/or set thermostat (if present) to lowest setting.

3. If applicable: Turn off all electric power to the heater.

44D0060

31

OPERATING INSTRUCTIONS

HI/LO REMOTE CONTROL LIGHTING INSTRUCTIONS

1. STOP! Read the safety information.

2. Make sure the manual shutoff valve is fully open.

3. This heater is equipped with an ignition device (piezo) which automatically lights the pilot.

4. See Figure 34 for the location of the piezo ignitor and control knob. Push in gas control knob slightly and turn control knob clockwise to the OFF position.

NOTE: Knob cannot be turned to OFF unless knob is pushed in slightly. Do not force.

5. Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas

STOP! Follow the instructions under “What to Do if You Smell Gas”, page 27. If you do not smell gas, go to the next step.

6. From OFF position, push in gas control knob slightly and turn counterclockwise to the pilot position. Push in and hold control knob for 5 seconds.

NOTE: If you are running the heater for the first time, it will be necessary to press in the control knob for 30 seconds to allow air to bleed out of the gas piping.

7. With the gas control knob pushed in, push and release the piezo ignitor button to light the ODS pilot. The pilot is located on the left side of the heater, behind the middle log and in front of the rear log. If piezo ignitor does not light the pilot, refer to “Match Lighting Instructions”, page 33.

8. Hold the gas control knob in for an additional 10 seconds to prevent the ODS pilot from shutting off the gas while the thermocouple is warming up.

9. Release the gas control knob.

• If the knob does not pop out when released, stop and immediately call your service technician or gas supplier.

• If the ODS pilot will not stay lit after several tries, push and turn the gas control knob clockwise

to OFF and wait 15 seconds. Repeat steps 6 through 9.

10. Turn gas control knob counterclockwise from pilot to ON.

11. Control flame with Hi/Lo control knob. See Figure 39.

12. The Hi/Lo control knob will control the height of the flame from pilot to high position.

13. Hi/Lo can also be controlled with optional remote.

Wait 30 seconds before readjusting the heater when the control knob has been turned down to a lower setting.

Gas Control

Knob

HI/LO Control

Knob

Piezo

Figure 39 - Control Cover Plate for Hi/Lo

TO TURN OFF GAS TO HEATER

1. Turn control knob clockwise to OFF position to completely shut off the heater.

2. If applicable: Turn off all electric power to the heater.

32

44D0060 44D0060

33

32

44D0060

OPERATING INSTRUCTIONS

AND

CLEANING AND SERVICING

MATCH LIGHTING INSTRUCTIONS

1. Remove any items necessary for easy access to the pilot (for example: logs, screens, etc.).

2. Follow appropriate lighting instructions found previously. Instead of pushing and releasing the piezo button, light a match and hold the flame to the end of the pilot and ignite the pilot.

3. After control knob has been released and pilot stays lit, reinstall any items that were removed for pilot access.

4. Call a qualified service technician for repair or replacement of the piezo ignitor.

CLEANING AND SERVICING

Annual inspection and cleaning by your dealer or qualified service technician is recommended to prevent malfunction and/or sooting.

Turn off heater and allow to cool before cleaning. Disconnect electrical power before cleaning or servicing.

Remove logs, handling carefully by holding gently at each end. Gloves are recommended to prevent skin irritation from ceramic fibers. If skin becomes irritated, wash gently with soap and water. Refer to manual for correct log placement.

PERIODIC CLEANING - Refer to parts diagram for location of items discussed below.

• Do not use cleaning fluid to clean logs or any part of heater.

• Brush logs with soft bristle brush or vacuum with brush attachment.

• Vacuum loose particles and dust from the front and rear burner, control and piezo covers and grate weldment.

• Inspect and clean burner air intake holes. Remove lint or particles with vacuum, brush, or pipe cleaners. Failure to keep air intake holes clean will result in sooting and poor combustion.

• External case should be dusted and wiped with a wet soapy cloth.

ANNUAL CLEANING/INSPECTION - Refer to parts diagram for location of items discussed below.

• Inspect and clean burner air intake holes. Remove lint or particles with vacuum, brush or pipe cleaners. Failure to keep air intake holes clean will result in sooting and poor combustion.

• Inspect and clean all burner ports.

• Inspect ODS pilot for operation and accumulation of lint at air intake holes.

• Verify flame pattern and log placement for proper operation.

• Verify smooth and responsive ignition of main burner and rear burner.

• Replace battery in remote control device.

44D0060

33

TROUBLESHOOTING

Turn appliance OFF and allow to cool before servicing. Only a qualified service person should service and repair the heater.

Note: All troubleshooting items are listed in order of operation.

OBSERVED PROBLEM

When ignitor button is pressed, there is no spark at ODS/pilot.

Appliance produces unwanted odors.

Appliance shuts off during use.

Gas odor even when control knob is in OFF position.

When ignitor button is pressed, there is spark at ODS pilot, but no ignition.

POSSIBLE CAUSE

REMEDY

1. Ignitor electrode positioned wrong.

2. Ignitor electrode is broken.

3. Ignitor electrode not connected to ignitor cable.

4. Ignitor cable pinched or wet. Keep ignitor cable dry.

5. Broken ignitor cable.

6. Bad piezo ignitor.

1 Replace ignitor.

2. Replace ignitor.

3. Reconnect ignitor cable.

4. Free ignitor cable if pinched by any metal or tubing.

5. Replace ignitor cable.

6. Replace piezo ignitor.

1. Appliance burning vapors from paint, hair spray, glues, etc.

2. Gas leak.

3. Initial burn off.

1. Ventilate room. Stop using odor causing products while heater is running.

2. Locate and correct all leaks.

3. Ventilate room and turn unit on high until odor is gone. Odor should be gone after 2 to 3 hours of continuous use.

1. Not enough fresh air is available for ODS/ pilot to operate.

2. Low line pressure.

3. ODS/pilot is partially clogged.

4. Defective Thermopile.

5. Restrictions in incoming air flow.

1. Open window and/or door for ventilation.

2. Contact local gas company.

3. Clean ODS/pilot.

4. Check wire connections. Check output should be 500 milli-volts across TH/TP and TP Terminals with ON/OFF switches off.

5. Check for bottom riser on glass door, sunken fireplace, excessive lava rock/ cinders densely packed against grate.

1. Gas leak.

2. Control valve defective.

1. Locate and correct all leaks.

2. Replace control valve.

1. Gas supply turned off or manual shutoff valve closed.

2. Control knob not in PILOT position.

3. Control knob not pressed in while in PILOT position.

4. Air in gas lines when installed.

5. ODS/pilot is clogged.

6. Gas regulator setting is not correct.

1. Turn on gas supply or open manual shutoff valve.

2. Turn control knob to PILOT position.

3. Press in control knob while in PILOT position.

4. Continue holding down control knob.

Repeat igniting operation until air is removed.

5. Replace ODS/pilot assembly or get it serviced.

6. Check incoming pressure. Replace gas regulator.

34

44D0060 44D0060

35

TROUBLESHOOTING

If the gas quality is bad, your pilot may not stay lit, the burners may produce soot and the heater may backfire when lit. If the gas quality or pressure is low, contact your local gas supplier immediately.

34

44D0060

OBSERVED PROBLEM

ODS/pilot lights, but flame goes out when control knob is released.

Burner does not light after ODS/ pilot is lit.

Burner backfires during combustion.

Slight smoke or odor during initial operation.

Logs appear to smoke after initial operation.

Heater produces a whistling noise when burner is lit.

No gas to pilot.

POSSIBLE CAUSE

REMEDY

1. Control knob not fully pressed in.

2. Control knob not pressed in long enough.

3. Manual shutoff valve not fully open.

4. Thermocouple connection loose at control valve.

5. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This problem could be caused by either low gas pressure, or a dirty or partially clogged ODS/pilot.

6. Thermocouple damaged.

7. Control valve damaged.

1. Press in control knob fully.

2. After ODS/pilot lights, keep control knob pressed in for 30 seconds.

3. Fully open manual shutoff valve.

4. Hand tighten thermocouple connection until snug, then tighten 1/4 turn more.

5. Contact local gas company.

6. Replace thermocouple.

7. Replace control valve.

1. Burner orifice is clogged.

2. Burner orifice diameter is too small.

3. Inlet gas pressure is too low.

1. Manifold pressure is too low.

2. Burner orifice is clogged.

1. Clean orifice.

2. Replace burner orifice.

3. Contact qualified service person.

1. Contact local gas company.

2. Clean burner or replace burner orifice.

1. Burner orifice is clogged or damaged.

2. Burner is damaged.

3. Gas regulator defective.

1. Vapors from paint or curing process of logs.

1. Clean burner or replace burner orifice.

2. Replace burner.

3. Replace gas regulator.

1. Problem will stop after a few hours of operation. Run the heater with the damper open if you have one, or open a window for the first few hours.

2. Log heater is intended to be smokeless.

Turn OFF heater and call qualified service person.

1. Turning control knob to HIGH position when burner is cold.

2. Air in gas line.

3. Dirty or partially clogged burner orifices.

1. Turn control knob to LOW position and let warm up for a minute.

2. Operate burner until air is removed from line. Have gas line checked by local gas company.

3. Clean burner or replace burner orifice.

1. LP-regulator shut down due to inlet pressure too high.

1. Verify LP tank regulator is installed and set at 11" to 13" w.c.

2. Replace regulator on heater.

44D0060

35

REPLACEMENT PARTS

BURNER ASSEMBLY

��

� ��������

��

� �����������

��� �������

��

��

� ������ �������

��

Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.

36

44D0060 44D0060

37

36

44D0060

REPLACEMENT PARTS LIST

REPLACEMENT PARTS ARE AVAILABLE THROUGH YOUR RETAILER.

BURNER ASSEMBLY

DEB20 DEB24/DEB30

Item Description Qty Natural Propane Natural Propane

Common Parts

1 Piezo Ignitor 1 14D0503 14D0503 14D0503 14D0503

2 Piezo Wire 1 00K0632 00K0632 00K0632 00K0632

3 Front Burner 1 44D0020K 44D0020K 44D0019K 44D0019K

4 Rear Burner 1 44D0035K 44D0036K 44D0081K 44D0082K

Manual Control

5 Control Valve 1 30D0201 30D0202 30D0201 30D0202

6 Control Valve Nut 1 00F0586 00F0586 00F0586 00F0586

7 Valve Regulator 1 24D0305 24D0306 24D0305 24D0306

8 Front Burner Injector 1 44D0200 44D0202 44D0204 44D0206

9 ODS Pilot Assembly 1 26D2529 14D0476 26D2529 14D0476

10 Control Knob 1 18D0603 18D0603 18D0603 18D0603

11 Rear burner Injector 1 44D0201 44D0203 44D0205 44D0207

Milli-Volt Control / Thermostat Control

5 Control Valve 1 14D0467 14D0468 14D0467 14D0468

8 Front Burner Injector 1 44D0208 44D0210 44D0212` 44D0214

9 ODS Pilot Assembly 1 14D0473 14D0477 14D0473 14D0477

10 Control Knob 2 18D0603 18D0603 18D0603 18D0603

11 Rear burner Injector 1 44D0209 44D0211 44D0213 44D0215

12 On/Off Switch 1 32D0232 32D0232 32D0232 32D0232

13 Thermostat Sensor 1 26D3314 26D3314 26D3314 26D3314

Hi/Lo Remote Control

5 Control Valve 1 14D0467 14D0468 14D0467 14D0468

8 Front Burner Injector 1 44D0208 44D0210 44D0212 44D0214

9 ODS Pilot Assembly 1 26D2529 14D0476 26D2529 14D0476

10 Control Knob Assembly 2 18D0603 18D0603 18D0603 18D0603

Control Knob Adapter 2 44D0221K 44D0221K 44D0221K 44D0221K

HI/LO control Knob Adapter 2 44D0220K 44D0220K 44D0220K 44D0220K

11 Rear burner Injector 1 44D0204 44D0211 44D0213 44D0215

Accessories

Flex Connector Flexcon 30 All Models

Wall Switch Kit MVWS Milli-volt only

Wall Thermostat Kit MVWTS Milli-volt only

Hand Held Remote RCM Milli-volt only

Hand Held Thermostat Remote RCT Milli-volt only

Remote Receiver Cover Ember RRCE All Models

Remote Receiver Cover Metal RRCM All Models

Thermostat Sensor Kit TS All Models

44D0060

37

REPLACEMENT PARTS LIST

REPLACEMENT PARTS ARE AVAILABLE THROUGH YOUR RETAILER.

LOGS

Item Description Qty DEB20 DEB24 DEB30

1 Back Log 1 44D1011K 44D1001K 44D1006K

2 Right Center Log 1 44D1022 44D1020 44D10224

3 Left Center Log 1 44D1023 44D1021 44D1025

4 Middle Front Log 1 44D1012K 44D1002K 44D1007K

5 Left Front Log 1 N/A 44D1003K 44D1008K

6 Top Log 1 44D1013K 44D1004K 44D1009K

� �������������

Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.

38

44D0060 44D0060

39

NOTES

38

44D0060 44D0060

39

MONESSEN HEARTH SYSTEMS

LIMITED LIFETIME WARRANTY POLICY

LIFETIME WARRANTY

The following components are warranted for life to the original owner, subject of proof of purchase: Firebox,

Combustion Chamber, Heat Exchanger, Grate, and Stainless Steel Burners.

FIVE YEAR WARRANTY

The following components are warranted for 5 years to the original owner, subject of proof of purchase: Vent Free

Ceramic Fiber Logs and Aluminized Burners.

BASIC WARRANTY

Monessen Hearth Systems (MHS) warrants the components and materials in your gas appliance to be free from manufacturing and material defects for a period of two years from date of installation. After installation, if any of the components manufactured by MHS in the appliance are found to be defective in materials or workmanship,

MHS will, at its option, replace or repair the defective components at no charge to the original owner. MHS will also pay for reasonable labor costs incurred in replacing or repairing such components for a period of two years from the date of installation. Any products presented for warranty repair must be accompanied by a dated proof of purchase.

This Limited Lifetime Warranty will be void if the appliance is not installed by a qualified installer in accordance with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance, and does not extend to (1) firebox/burner assembly damage by accident, neglect, misuse, abuse, alteration, negligence of others, including the installation thereof by unqualified installers, (2) the costs of removal, reinstallation or transportation of defective parts on the appliance, or (3) incidental or consequential damage. All service work must be performed by an authorized service representative.

This warranty is expressly in lieu of other warranties, express or implied, including the warranty of merchantability of fitness for purpose and of all other obligations or liabilities. Monessen Hearth Systems, Inc. does not assume for it any other obligations or liability in connection with the sale or use of the appliance. In states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damage, those limitations of exclusions may not apply to you. You may also have additional rights not covered in this Limited Lifetime Warranty.

MHS reserves the right to investigate any and all claims against the Limited Lifetime Warranty and decide upon method of settlement.

For information about this warranty, contact:

Technical Services

Monessen Hearth Systems

149 Cleveland Drive

Paris, Kentucky 40361

May 2003 P/N 44D0060 • Rev. 3