Aspirating Fire Detection
Protec
Cirrus Pro 100
Protec Fire Detection plc
• Cloud Chamber Detection Principle
• Up to 100 mtrs Sampling Pipe
• Programmable ‘Pre-Alarm’ warning
condition
• 3 Programmable ‘Fire’ warning conditions
• Local Buzzer
• Silence and Reset Buttons
• Vast Sensitivity Range
• Latching / non latching alarm contacts
• Airflow Monitoring
• ‘Fault Diagnostic’ feature
• Immune to dust, humidity & temperature
changes
A D D R ESS IN G
CLOUD CHAMBER FIRE DETECTOR
ALMOST UNLIMITED APPLICATIONS
The ‘sensitivity range’ is the key feature
that makes the Cirrus Pro Series Fire
Detector the worlds most versatile fire
detection device.
High Sensitivity Applications include:Computer Rooms, Clean Rooms, Control
Rooms, Data Centres, Valve Halls, Archive
Storage, Anechoic Chambers, EDP areas.
For over 20 years Cloud Chamber detectors
have been known as the most sensitive
fire detection device, able to detect at the
true incipient stage of a developing fire.
General Sensitivity Applications include:Historic Buildings, Museums, Hospitals,
Cathedrals, Theatres, Art Galleries, Clean
Warehouses, Atria, Indoor Stadiums.
The New Cirrus Pro Series Detectors
have a vast sensitivity range capable of
being even more sensitive than previous
versions. In addition the detector may
now be configured to be installed in
heavily contaminated environments, such
as polluted production and warehousing
facilities.
Harsh
Environment
Applications
include:- Cold Storage Facilities,
Specialist Production Facilities, Food
Industry Facilities, Paper Production
Facilities, Transportation Terminals, Flight
Simulators, Aircraft Hangers, Prisons,
Inaccessible Voids, Dirty Warehouses.
S A F E T Y
SYST E M S
W I T H
I NT E L L I G E N CE
Connections
Dimensions (mm)
Sampling Pipe
285
Input 1
Fire 1 Output
Input 2
Fire 2 Output
Input 3
Fire 3 Output
Input 4
Common Fault Output
125
Supply Fault
Pre-Alarm Output
24V
RS485
15
215
25mm
0V
285
15
125
4
9000 Series BC Charger
215
Aspirating Fire Detection
Technical Specification
240V AC Mains Supply
Technical Specification:
Pipe ID
19 to 25mm (preferred OD 25mm)
Supply Voltage
20 - 29VDC
Alarm Indications
Pre-alarm, Fire 1, Fire 2, Fire 3.
Power Consumption
7.2 watts quiescent
(24VDC 90% Fan Speed)
Other Indications
Supply Healthy, General Fault.
Current Consumption
350mA quiescent 50mA alarm
(24VDC 90% Fan Speed)
Dimensions
(W) 285mm, (H) 215mm (D) 144mm
Weight4kg (8.8lbs)
Operating Conditions
Detector Ambient
Tested to
Sampled Air
Humidity 0˚C to 38˚C (32˚F to 100˚F)
0˚C to 55˚C (32˚F to 131˚F)
-20˚C to 60˚C (-4˚F to 140˚F)
10 - 95%RH, non-condensing
IP RatingIP30
Cable Access
6 x 20mm knock outs
Cable Termination
Screw terminal blocks
(0.2 - 2.5mm2, 30 - 12AWG)
Sampling Network
Single inlet port with combined
sampling pipe length up to 100m
typically (325ft.) Maximum Transport
Time allowed up to 120 seconds.
Sensitivity Range
20,000 particles per cc to 3 million
particles per cc 10 programmable
sensitivity ranges.
Programmable Inputs
4 monitored inputs that may be configured
for Isolate, Reset, Disable, Fault, Gain Set,
Battery Fault and Mains Fault, Silence and
Reset button, Disable.
Programmable Output Relays 5 Relays rated 1A @ 30VDC
(Volt-free change over contacts)
Event Log
128 events stored on FIFO basis.
Data Retention
Approx 10 day historical graph.
Variable Sensitivity Settings 7 day programmable settings with 3 time
zones per day.
Airflow Monitoring
Adjustable ‘High Airflow’ and ‘Low Airflow’
fault monitoring.
Company Policy is one of continuous improvement, we reserve the right to change specification without prior notice