Chint 100kw Installation Manual

Add to my manuals
100 Pages

advertisement

Chint 100kw Installation Manual | Manualzz

CPS SC

Series Grid-tied PV Inverter

CPS SC100KT-O/US-480

Installation and Operation Manual

Version: 1.1

CHINT POWER SYSTEMS AMERICA CO., LTD.

Address: 700 International Parkway,

Suite 102 Richardson, Texas

Zip Code: 75081

Web: www.chintpower.com/na

Email: [email protected]

Service Hotline: 855-584-7168

SHANGHAI CHINT POWER SYSTEMS CO., LTD. All rights reserved.

Specifications and designs included in this manual are subject to change without notice.

CHINT POWER 2013/06-MKT PN: 9.0020.0041F0

Table of Contents

Before You Start… ................................................................................... 1

Chapter 1 IMPORTANT SAFETY INSTRUCTIONS ............................... 2

Chapter 2 Overview ............................................................................... 8

2.1 Inverter for grid-tied PV systems ................................................ 8

2.2 Product type description ............................................................. 8

2.3 Product features ......................................................................... 9

2.4 Inverter circuit structure .............................................................. 9

2.5 Appearance description .............................................................. 10

Chapter 3 Installation ............................................................................ 12

3.1 Basic requirements ..................................................................... 13

3.2 Checklist of installation tools ...................................................... 14

3.3 Mechanical installation ............................................................... 14

3.4 Electrical installation ................................................................... 20

3.4.1 DC connection .................................................................... 26

3.4.2 AC connection ..................................................................... 31

3.4.3 Ground connection ............................................................. 32

3.4.4 Communication connection ................................................. 33

3.4.5 Connection of dry contact ................................................... 36

3.4.6 Installation of bottom filter and baffles ................................. 37

Chapter 4 Initial On-grid Testing .......................................................... 38

4.1 Testing steps .............................................................................. 38

4.2 Testing procedure statement ...................................................... 39

4.2.1 Check the appearance of inverter ....................................... 39

4.2.2 Check AC connection ......................................................... 39

4.2.3 Check DC connection ......................................................... 40

4.2.4 Turn on AC circuit breaker .................................................. 41

4.2.5 System self-check and time set-up ..................................... 41

4.2.6 Set up AC operational parameters ...................................... 42

4.2.7 Set up DC operational parameters ..................................... 42

4.2.8 Set up MPPT operational parameters ................................ 43

4.2.9 Turn on DC circuit breaker .................................................. 43

4.2.10 Power train of self-check .................................................. 43

4.2.11 Start up inverter ................................................................ 46

Chapter 5 Operation ............................................................................. 47

5.1 Shut-down and Start-up ............................................................. 47

5.1.1 Shut-down .......................................................................... 47

5.1.2 Start-up ............................................................................... 50

5.2 Operation mode ......................................................................... 51

5.3 Troubleshooting ......................................................................... 54

Chapter 6 Human Machine Interface ................................................... 67

6.1 Description of LCD panel ........................................................... 67

6.2 Operation state .......................................................................... 70

6.3 Interface and menu functions ..................................................... 71

6.3.1 Interface types .................................................................... 71

6.3.2 Main operation interface ..................................................... 74

6.3.3 Operation information ......................................................... 75

6.3.4 Present fault ....................................................................... 76

6.3.5 History ................................................................................ 76

6.3.6 System setup ...................................................................... 78

6.3.7 Power Dispatch .................................................................. 80

6.3.8 System protection parameters setup .................................. 82

Chapter 7 Service and Maintenance.................................................... 86

7.1 Maintenance instruction of filter net ........................................... 86

7.1.1 Maintenance of filter net on the top .................................... 86

7.1.2 Maintenance of filter net at the bottom ............................... 88

7.2 Maintenance of fan tray assembly ......................................... 89

Chapter 8 Technical Data ..................................................................... 91

Chapter 9 Limited Warranty ................................................................. 96

Before You Start…

This manual contains important information regarding installation and safe operation of this unit. Be sure to read this manual carefully before using.

Thanks for choosing this Grid-tied PV Inverter (referred to in this manual as

“PV Inverter”, or simply “Inverter”)

. This Grid PV Inverter is a highly reliable product due to its innovative design and perfect quality control. Such an

Inverter is used in high demand, grid-tied PV systems.

If you encounter any problems during installation or operation of this unit, first check this manual before contacting your local dealer or supplier. Instructions inside this manual will help you solve most installation and operation difficulties.

Please keep this manual on hand for quick reference.

1

Chapter 1 IMPORTANT SAFETY INSTRUCTIONS

(SAVE THESE INSTRUCTIONS)

Please read this user manual carefully before undertaking the installation.

CPS reserves the right to refuse warranty claims for equipment damage if the user fails to install the equipment as per the instructions in this manual.

DANGER:

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING:

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION:

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

NOTICE:

NOTICE indicates a hazardous situation which, if not avoided, could result in equipment working abnormally or property loss.

INSTRUCTION:

INSTRUCTION indicates important supplementary information or provides skills or tips that can be used to help you solve a problem or

2

save you time.

Warnings and symbols in this document

Markings on the product

HIGH VOLTAGE:

The product works with high voltages. All work on the product must only be performed as described in this document.

HOT SURFACE:

The equipment is designed to meet international safety standards, but surfaces can become hot during operation. Do not touch the heat sink or peripheral surfaces during or shortly after operation.

EARTH GROUND:

This symbol marks the location of grounding terminal, which must be securely connected to the earth through the PE

(protective earthing) cable to ensure operational safety.

3

DANGER:

Please disconnect the inverter from AC grid and PV modules before opening the equipment. When the PV array is exposed to light, it supplies DC voltage to this equipment. Make sure hazardous high voltage and energy inside the equipment has been discharged.

Do not operate or maintain the inverter until at least 8 minutes after disconnecting all sources from DC and AC sides.

DANGER:

Make sure that equipment is grounded properly. If a ground fault is indicated, the grounding conductors are probably ungrounded and energized.

WARNING:

All the installation and wiring connections should be performed only by qualified technical personnel. Disconnect the inverter from PV modules and the Power Grid before maintaining and operating the equipment.

WARNING:

4

When the connected PV module is exposed to the sunlight, it generates DC voltage and charges the DC bus capacitors of the inverter. Electric charges are still stored in the capacitors even the input of the PV inverter is turned off. Therefore, equipment shall not be maintained until 60 minutes after all inputs are cut off or the

“De-energy” command is carried out successfully.

WARNING:

Shut down the inverter before maintaining the inverter. Disconnect the inverter from PV panels and the Power Grid and make sure there is no electric charge left in the inverter before the maintenance.

CAUTION:

Although designed to meet international safety standards, the

PV-Inverter can become hot during operation. Do not touch the heat sink or peripheral surfaces during or shortly after operation.

NOTICE:

This inverter is designed to connect AC power only to the public grid.

Do not connect the AC output of this equipment directly to any private AC power equipment.

5

NOTICE:

Please choose the type of inverter based on the way of DC grounding system! Change of PV grounding in the inverter is prohibited without permission. Please contact our after-sale service personnel if the change of grounding in the inverter is necessary.

NOTICE:

If the polarity of the DC cables is not correct, the inverter will be damaged.

NOTICE:

Do not install the inverter under direct sunlight to avoid conversion efficiency de-rating caused by excessively high temperature.

NOTICE:

To ensure operational safety, run the initial on-grid testing before operating on the inverter.

INSTRUCTION:

Steel conduits as the cable protector need to be prepared before installation.

6

INSTRUCTION:

If no voltage is detected, check whether the connection from DC source to the inverter is correct. Maybe the combiner boxes are not properly connected or there is a short circuit in the DC cables.

7

Chapter 2 Overview

2.1 Inverter for grid-tied PV systems

CPS SC100KT-O/US-480 inverter can be applied to various commercial rooftop systems and distributed power station systems. Normally, the system mainly consists of PV modules, DC power distribution equipments, PV inverter and AC power distribution equipments (Figure 2-1). The inverter converts the

DC energy from PV modules to the AC energy that is compatible with the public grid. The AC energy can be used directly by the local load, or it can be sold to your energy provider.

DC power

distribution equipments

AC power

distribution equipments

Bidirectional electric meter

AC Grid

Figure 2-1 Grid-tied PV system

2.2 Product type description

CPS SC100KT-O/US-480 is a PV inverter integrated with a low frequency isolation transformer for indoor and outdoor application. The suffix

“US” means that this model of inverter passes the UL and CSA certifications and is

8

specialized for the American market.

2.3 Product features

CPS SC100KT-O/US-480 inverter incorporates the advanced MPPT controlling technology and variable structure modulation strategy to minimize the energy loss.

The design with transformer has the benefit of connecting the inverter to the low-voltage grid more conveniently.

The enclosure of inverter conforms to the NEMA 3R (IP44) protection class, which enables the inverter to be used in the outdoor environment.

Besides, the smart DSP control, complete protection function and advanced thermal design guarantee the inverter with high reliability.

2.4 Inverter circuit structure

The basic schematic diagram of CPS SC100KT-O/US-480 inverter is shown in Figure 2-2. The output of PV modules first passes through DC circuit breaker. The inverter converts DC voltage to 3-phase AC voltage. The 3-phase

AC voltage will be removed of high frequency component by the sine wave filter, then stepped up and isolated by the low frequency transformer and go through AC contactor, AC EMI filter, circuit breaker, at last, be fed to the LV grid.

9

PV+

PV-

=

Inverter

3~

CPS SC100KT-O/US-480

I

PV

U

PV+

U PV-

PWM

SPU

GFDi

RS485

Ia

Ib

Ic

JCC

Ua

Ub

Uc

Figure 2-2 Schematic diagram

2.5 Appearance description

1

4

5

6

2

3

Figure 2-3 Appearance sketch of CPS SC100KT-O/US-480

10

L1

L2

L3

G

RS485+

RS485-

Description of main components (shown in Figure 2-3):

1. Roof Panel

2. Operation buttons and LCD display panel with protection cover

3. Emergency stop button

4. Door lock

5. AC circuit breaker

6. DC circuit breaker

11

Chapter 3 Installation

Below is the installation instruction of the inverter. Please read carefully and install the product step-by-step.

1. CPS SC100KT-O/US-480

Check and make sure that the following items are included in the package before installation, as shown in Table 3-1.

Table 3-1 Main items

Q’ty

Note Item

(1) CPS

SC100KT-O/US-480

Grid-tied PV inverter

1 Grid-tied PV inverter

(2) Accessory kit 1

Contains all necessary accessories

The (2) Accessory kit contains items listed below:

Item

User manual

Table 3-2 Accessories

Q’ty

1

Purpose

Installation and operation

12

Warranty service card

Bottom baffle

Bottom filter

M4 screw

3.1 Basic requirements

1

2

1

8 manual

For maintenance and repair

For air convection

For dust proof

For bottom baffles

NOTICE:

Do not install the inverter under direct sunlight to avoid conversion efficiency de-rating caused by excessively high temperature.

 Check and make sure that the ambient temperature of the installation environment is -25

C ~+60

C;

 Make sure that the public power grid voltage is 422~528Vac and the grid frequency is 57.0~60.5Hz;

 Permission of grid connection has been granted by the local electric power authority;

 Installation personnel must be qualified electricians or people who have received professional training;

13

 Sufficient convection space;

 Away from flammable and explosive substances;

3.2 Checklist of installation tools

The checklist of tools for installation of the product:

Table 3-3

No.

1

2

Name

Spline screwdriver

Phillips head screwdriver

Specification

T25

PH2

Function

For screws on the backboard

For M3 and M4 screws

3

4

Open end wrench

Open end wrench

5 Straight screwdriver

6 Sleeve

7 Torque wrench

0.55 inch

0.67 inch

0.12 inch

0.28 inch

132.74 lb-In.

For M8 screws

For M10 screws

For screws on dry contact

For M4 nuts

For M10 screws

3.3 Mechanical installation

(1) Dimensions

Dimensions of CPS SC100KT-O/US-480 inverter are shown in Figure 3-1.

14

47.24in.

34

.65

in.

Figure 3-1 Sketch of dimensions

There are 2 ways to install the foundation of inverter:

(1) The dimensions of foundation installation for the first way are shown in

Figure 3-2 (a).

Please pay attention to the direction of the 4 fixing plates at the bottom.

15

2.64in.

D=0.63in.

4.33in.

47.24in.

38.58in.

1.97in.

Fixing plate

13.31in.

Figure 3-2 (a) Sketch of foundation installation dimensions

Place the fixing plates inward, as shown in Figure 3-2 (b).

1.97in.

Conduit area

Fixing plate

Figure 3-2 (b) Inward direction to place fixing plates

16

(2) The dimensions of foundation installation for the second way are shown in Figure 3-3 (a).

Please pay attention to the direction of the 4 fixing plates at the bottom.

1.10in.

50.79in.

48.58in.

47.24in.

2.64in.

1.97in.

D=0.63in.

Conduit area

Fixing plate

13.31in.

Figure 3-3 (a) Sketch of foundation installation dimensions

Place the fixing plates outward (Figure 3-3 (b)).

1.97in.

17

Fixing plate

Figure 3-3 (b) Outward direction to place fixing plates

Requirements of inverter installation:

According to the installation dimensions shown in Figure 3-2 (a) and 3-3

(a), secure the inverter on the hard ground or channel steel chassis with M12 foundation bolts through the 8 holes with a diameter of 0.63 inch at the bottom of the equipment.

Front door: A 25.6-inch space should be reserved to ensure that the front door can be opened and closed freely.

Back: A 31.5-inch space should be reserved for maintenance.

The weight of the inverter is approximately 1984.2 pounds. Make sure that the mounting place can bear the weight. Two approaches are recommended to lift the machine, i.e. lifting with a crane or a forklift:

18

Lifting with a crane

Before lifting the machine, adjust the width of the forklift arm within

16.5~33.5 inches and insert the fork into the bottom of the machine from the back and lift it to the appropriate location for installation as shown in Figure

3-4.

Figure 3-4 Diagram of lifting with a crane

Lifting with a forklift:

Adjust the width of the forklift arm within 16.5~33.5 inches and insert the fork into the bottom of the machine from the back and lift it to the appropriate

19

location for installation as shown in Figure 3-5.

>16.54in.

<33.46in.

Figure 3-5 Diagram of lifting with a forklift

3.4 Electrical installation

Open the front door of the machine. Proceed as shown in Figure 3-6.

1、Turn the handle bar of DC circuit breaker anti-clockwise to horizontal

20

position.

2、Turn the handle bar of AC circuit breaker anti-clockwise to horizontal position.

3、Unlock the door with the key. Pull the lock handle 45 degree outward to open the front door.

1 3 2

Figure 3-6 Diagram of opening front door

4、After opening the front door, remove the transparent Plexiglas cover for wiring. There are two ways to connect the external cables to the inverter: wiring from the bottom and wiring from the left side.

(1) Wiring from the bottom:

There are also 2 ways to connect cables from the bottom of the inverter.

① Routing from rectangular conduit areas:

21

Remove the two bottom covers with a Phillips head screwdriver and connect cables to the inverter through the rectangular conduit areas, as shown in Figure 3-7.

DC bottom cover

AC bottom cover

Figure 3-7 Routing from rectangular conduit areas

② Routing from round holes on the two bottom covers:

(a) Remove the cover screws, put the screws aside, and then take off the two covers;

(b) Punch two holes on the DC bottom cover for DC conduits, as shown in Figure 3-8;

(c) Punch three holes on the AC bottom cover

—one for the communication conduit, one for the AC conduit and one for

22

grounding conduit, as shown in Figure 3-9;

For DC conduit

Figure 3-8 Holes on DC bottom cover

For communication conduit For AC conduit For grounding conduit

Figure 3-9 Holes on AC bottom cover

(d) Install steel connectors on the DC and AC bottom covers and check the seal of the cover;

(e) Connect the steel conduits to these connectors;

23

(f) Restore the two covers to the inverter and attach the screws;

(g) Put the cables through steel conduits to connect to the inverter, as shown in Figure 3-10.

Figure 3-10 Routing from round holes on the two bottom covers

(2) Wiring from the left side:

(a) Remove the screws on the left side cover with a Phillips head screwdriver, put the screws aside, and then take off the cover;

(b) Punch five holes on the left bottom cover for steel conduits, as shown in Figure 3-11;

24

For communica tion conduit

For DC conduit

For AC conduit

For

Grounding conduit

Figure 3-11 Holes on the left side cover

(c) Install steel connectors on the left side cover and check the seal of the cover, as shown in Figure 3-12;

DC

AC

Com.

Grounding

Figure 3-12 Installation of steel connectors

25

(d) Connect the steel conduits to these connectors;

(e) Restore the cover to the inverter and attach the screws;

(f) Put the cables through steel conduits to connect to the inverter, as shown in Figure 3-13;

Figure 3-13 Wiring from the left side

3.4.1 DC connection

(1) To ensure the optimal performance of the inverter, please read the following guidelines before DC connection:

(a) First, make sure that the maximum open circuit voltage of the PV modules is lower than 600Vdc under any conditions;

(b) Ensure that the polarity of DC input is correct, i.e. the positive pole of PV module is connected to the positive pole of the inverter

’s DC

26

input, and the negative pole of PV module is connected to the negative pole of the inverter

’s DC input;

(c) The Max. DC input current of the inverter is 350A, so 2AWG~

3/0AWG copper cables with an insulation rating of 194℉ are recommended for inverter’s DC input. The DC connection requirement is shown in Table 3-4:

Table 3-4

4 strings 3 strings 2 strings

Positive 2AWG(35mm²) 1/0AWG (50 mm²) 3/0AWG (95 mm²)

Negative 2AWG(35mm²) 1/0AWG (50 mm²) 3/0AWG (95 mm²)

(d) Reserve a hole of 11mm diameter on the copper bar. Select the following recommended bolts to tighten the cables, see Table 3-5:

Metric Bolt

American

Bolt

Type

M10

3/8

Table 3-5

Length

25mm

1’

Torque Value

24.6N-M (217.4Lb-In.)

24.6N-M (217.4Lb-In.)

INSTRUCTION:

The standard DC configuration is 4 strings. Other configurations are

27

also available by changing corresponding fuses.

The specification of fuses for DC input strings is shown in Table 3-6.

Table 3-6

String Fuse Rated Fuse Rated

Interrupting Rating

# Un(V) In(A)

2 1000 275 150kA

Note

Minimum set

3

4

1000

1000

185

140

150kA

150kA

Minimum set

Default set

The position of DC fuses is shown in Figure 3-14.

Fuse

Figure 3-14 Position of DC fuses

28

(2) Confirm that the input PV modules are of the same specifications and types before connection of DC input;

(3) Connect the DC cable s to the inverter’s copper bar terminals on DC side according to the Table 3-7. In Table 3-6, CPS SC100KT-O/US-480, this type of inverter means that the negative pole of DC input needs to be connected to the Return ground bar and CPS SC100KT-OPG/US-480, this type of inverter means that the positive pole of DC input needs to be connected to the Return ground bar.

Table 3-7

Type of Inverter

CPS SC100KT-O/US-480

Default way of grounding PV -

Negative grounding Return

PV+

Hot

CPS SC100KT-OPG/US-480 Positive grounding Hot Return

NOTICE:

Please choose the type of inverter based on the way of DC grounding system! Change of PV grounding in the inverter is prohibited without permission. Please contact our after-sale service personnel if the change of grounding in the inverter is necessary.

29

Return

PV

Return

PV+

Figure 3-15 DC connection of CPS SC100KT-O/US-480

Hot

PV

Hot

PV+

Figure 3-16 DC connection of CPS SC100KT-OPG/US-480

30

The two schematic diagrams of wire connection are shown in Figure 3-17.

Outside the inverter

PV+

Hot

PV-

Return

Inside the inverter

GFDI

+ =

~

Negative ground

Outside the inverter

Hot

PV-

PV+

Return

Inside the inverter

GFDI

+

=

~

Positive ground

(a) (b)

Figure 3-17 Schematic diagram on DC side

3.4.2 AC connection

Connect the AC output of PV inverter to the AC cabinet or the power grid:

(1) Use the recommended copper cables with an insulation rating of

194℉. The AC calbe requirement is shown in Table 3-8:

Table 3-8

L1 L2 L3

Wire diameter 2/0AWG (70mm

2

) 2/0AWG (70mm

2

) 2/0AWG (70mm

2

)

Select the following recommended bolts to tighten the cables in Table 3-9:

Metric Bolt

Type

M10

Table 3-9

Length

25mm

31

Torque Value

10N-M (88.5Lb-In.)

American

3/8

’ 1’

10N-M (88.5Lb-In.)

Bolt

(2) Connect the power grid A, B, C cables to the L1, L2, and L3 te rminals of the inverter, as shown in Figure 3-18:

AC output cables

L1 L2 L3

Figure 3-18 AC output connection

(3) Make sure that all cables are well connected on the L1, L2, and L3 terminals.

3.4.3 Ground connection

The ground copper bar is located at the bottom right corner of the inverter, as shown in Figure 3-19.

32

Gnd copper bar

Figure 3-19 Ground connection

Connect the Ground (PE) cable to the Gnd terminal of Gnd copper bar.

The Ground connection requirement is shown in Table 3-10.

Table 3-10

Item

Wire diameter

Nut

Torque value

Gnd (PE)

2AWG (35mm

2

)

M8

12.5N-M (113.5 Lb-In.)

3.4.4 Communication connection

RS485 communication connection:

The signal pinboard on the inverter has 2 RS485 communication ports, which are RS485-1 and RS485-2 for field connections, as shown in Figure

33

3-20.

Figure 3-20 Signal cable terminals for communication

(1) The communication of one single local inverter is to connect the

RS485 communication bus cable through the RS485-1 or RS485-2 port of the inverter directly. Shielded twisted pair (STP) cable should be used for RS485 communication with the maximum allowable length of 3280 feet. Wiring requirement of RS485-1/2 is shown in Table 3-10:

Table 3-11 RS485-1/2 wiring requirement

34

5

6

3

4

7

8

No.

1

2

Color

White orange

Orange

White green

Blue

White blue

Green

White brown

Brown

Function

485+

N.C.

485-

N.C.

N.C.

N.C.

N.C.

N.C.

The wires are labeled 1~8 from left to right, as shown in Figure 3-21:

Figure 3-21 Diagram of RS485-1/2 wiring

(2) For remote monitoring of more inverters, connect the RS485-2 port of one inverter to the RS485-1 port of another inverter and then connect to the

35

data logger through the RS485 communication bus cable. For more information about CPS monitoring solutions, please contact our after-sales service center.

3.4.5 Connection of dry contact

The connection of dry contact is shown in Figure 3-22. The two terminals are potential-free contacts for fault alarming of the inverter. The wiring requirement is shown in Table 3-11.

Figure 3-22 Diagram of Dry contact connection

Table 3-12

Function

Inverter fault alarm

Wire diameter Signal type

18AWG (0.810mm

2

)

Dry contact

(MAX 240VAC 2A)

36

3.4.6 Installation of bottom filter and baffles

After all wire connections are completed, insert the filter into the filter slot at the bottom of the inverter. Then install the front and back baffles with the eight M4 screws (in the accessory pack), as shown in Figure 3-23.

Baffle

Filter

Baffle

Figure 3-23 Diagram of bottom filter and baffles installation

37

Chapter 4 Initial On-grid Testing

To ensure operational safety, initial on-grid testing is required as per the instructions in this chapter before connecting the inverter to PV panels and grid power after the installation of CPS SC100KT-O/US-480.

4.1 Testing steps

Take the following steps for the initial on-grid test:

(1) Check the appearance of inverter

(2) Check AC connection

(3) Check DC connection

(4) Turn on AC circuit breaker

(5) System self-check and time setup

(6) Set up AC operational parameters

(7) Set up DC operational parameters

(8) Set up MPPT operational parameters

(9) Turn on DC circuit breaker

(10) Power train of self-check

(11) Start up inverter

38

INSTRUCTION:

Please refer to “5.3 Troubleshooting” or contact our after-sale service personnel if any problem is found during the testing.

4.2 Testing procedure statement

4.2.1 Check the appearance of inverter

(1) Check whether the inverter has any visible abnormalities. Make sure that the DC and AC circuit breakers are turned off. Open the front door of the inverter and ensure the electrical components and connections are normal.

(2) Check and make sure that all the cables are properly connected and free of defects.

(3) Correct and record any identified problems.

4.2.2 Check AC connection

(1) Check whether the power grid A, B, C, and PE cables are properly torqued on the appropriate L1, L2, L3 and Ground terminals.

(2) Before connecting the inverter to the power grid, measure the line to line voltage between terminals of AC cables. The voltage of L1-L2, L2-L3 and

L3-L1 should be within the range of 422-528Vac.

(3) If abnormal power grid voltage or no voltage is detected, please

39

reconfirm the power transmission from the power grid to the inverter. If there is nothing wrong with the power transmission, check whether the AC connection is correct.

(4) Correct and record any identified problems.

4.2.3 Check DC connection

(1) Check whether the PV cables are properly torqued on the appropriate

DC terminals.

(2) Put through the DC input from PV panels, combiner boxes or other DC distribution equipments and then measure the voltage between Hot and

Return bars.

INSTRUCTION:

If no voltage is detected, check whether the connection from DC source to the inverter is correct. Maybe the combiner boxes are not properly connected or there is a short circuit in the DC cables.

(3) Confirm whether the polarity of DC connection is correct.

NOTICE:

If the polarity of the DC cables is not correct, the inverter will be

40

damaged.

(4) Correct and record any identified problems.

4.2.4 Turn on AC circuit breaker

(1) Close the front door of the inverter.

(2) Turn on the AC circuit breaker. The auxiliary power supply of the inverter will be energized and the control circuit be activated.

(3) Check carefully whether there is any abnormality.

(4) Turn off the AC circuit breaker immediately if there is any abnormality.

Reconfirm whether the previous testing steps are correct. Stop testing if anything abnormal occurs.

4.2.5 System self-check and time set-up

(1) “Sys. Checking” will be indicated on the LCD when the AC circuit breaker is turned on.

(2) The inverter will stand by after the self-check of system (about 30 seconds) is completed. Meanwhile, fault indication interface will be shown on the LCD if any malfunction occurs. The specific fault indication and solution are available to be found in “5.3 Troubleshooting”.

Besides, since the DC circuit breaker is not turned on, the fault

41

“Warn0040” will be indicated on the LCD. Please ignore the fault and keep the

DC circuit breaker in OFF state. (Please don’t turn on the DC circuit breaker until it is allowed in the Chapter 4.2.9).

(3) Enter the “4 SysTime” menu and set up the present date and time according to “6.3.6 System setup”.

4.2.6 Set up AC operational parameters

Enter “1 SysPara” menu according to “6.3.7 System protection parameter setup”.

(1) Check the AC voltage, frequency protection value and time of protection actions.

(2) Change the parameters referring to the “Protection Parameters Table” in Chapter 6.3.7 if necessary.

(3) Record the changed parameters.

4.2.7 Set up DC operational parameters

(1) Check the PV startup voltage and startup time of the inverter.

(2) Change the parameters if necessary.

(3) Record the changed parameters.

42

4.2.8 Set up MPPT operational parameters

(1) Check the active derating and reactive compensation parameters of the inverter;

(2) Set the active power derating to 10%.

(3) Record the changed parameters.

4.2.9 Turn on DC circuit breaker

(1) Turn off the AC circuit breaker.

(2) Turn on the DC circuit breaker to provide the PV power supply to the

DC side of the inverter.

(3) Check carefully whether there is abnormality.

(4) Turn off the DC circuit breaker if there is any abnormality. Reconfirm whether the previous testing steps are correct. Stop testing if anything abnormal occurs.

4.2.10 Power train of self-check

(1) Confirm that the front door of the inverter is closed and locked.

(2) Turn on the AC circuit breaker.

(3) Wait for the inverter to stand by, the status of which will be indicated on the LCD.

43

(4

) Select “2 PowerTrain” on the LCD and press “ENT” according to “6.3.6

System setup”. Then self-check interface will be indicated on the LCD. (Figure

4-1)

After pressing “ENT”, the system begins self-checking. (Figure 4-2)

PowerTrain?

Figure 4-1 Self-check confirmation interface

PowerTrain..

Figure 4-2 System self-checking

(4)

If “Low PV Volt” is indicated on the LCD, as shown in Figure 4-3, check whether the DC connection is correct and whether the DC voltage is below

300V (subject to grid voltage).

44

Low PV Volt

Figure 4-3 Low Volt

(5) If “PowerTrainFualt” is indicated on the LCD, as shown in Figure 4-4, check whether the DC circuit breaker is turned on. Then check whether the inverter is in

“ON State” according to “6.3.6 System setup”. If the fault still occurs when the DC circuit breaker is turned on and the inverter is “ON State”, turn off the AC and DC circuit breakers immediately and then contact our after-sales service personnel.

PowerTrainFault

Figure 4-4 Self-check fails

(6) If the selfcheck is successful, “PowerTrain OK” will be indicated on the LCD, as shown in Figure 4-5. Press ESC to return to the main menu.

45

PowerTrain OK

Figure 4-5 Self-check OK

4.2.11 Start up inverter

(1) If the PV voltage reaches the startup voltage (subject to the grid voltage and 330V is the default minimum voltage.) and the grid voltage meets the requirement of grid connection, the inverter will be energized to start up after 7-15 minutes under stand-by mode. The largest output power is 10% of the rated power. (The active power derating was set to 10%.)

(2)If nothing abnormal happens, the active derating value can be gradually increased to 100%.

(3)Check all the operation information on the LCD.

(4)Turn off the AC and DC circuit breaker or press the “emergency stop button” if anything abnormal occurs.

46

Chapter 5 Operation

NOTICE:

To ensure operational safety, run the initial on-grid testing before operating on the inverter.

5.1 Shut-down and Start-up

5.1.1 Shut-down

Manual shut-down : Normally, manual shutdown is not necessary. But the inverter can be shut down manually for maintenance or user

’s needs.

(1) Move the cursor from the main operation interface to “4 Setting” according to “6.3.6 System setup”. Press ENTER and go to submenu “1

ON/OFF”. The inverter will be shut down and enter “OFF State” after moving the cursor to “OFF” and press ENTER.

(2) Press the “emergency stop button” on the panel to shut down the inverter in case of emergencies.

Then the fault alert “EmergencyStp” will be indicated on the LCD and the inverter will stop working. Once the

“emergency stop button” is restored, the fault alert will be eliminated and the inverter will restart working automatically.

Automatic shut-down: The inverter will be shut down automatically and

47

enter standby mode when the output voltage of PV panel is lower than the set point (300Vdc minimum), or AC power grid fails; or the ambient temperature exceeds the normal range.

The inverter will restart working automatically when the appropriate grid-connection condition is detected.

Manual Shut-down for maintenance: If service personnel need to maintain or repair the inverter, please follow the following steps.

(1) Shut down the inverter according to the manual shut-down steps. Turn off the DC circuit breaker and ensure that the AC circuit breaker is turned on.

(2) Referring to

“6.3.6 System setup”, move the cursor from the main operation interface to

“4 Setting”, press ENTER and go to submenu “6

OtherCmd”. Then move the cursor to “1 De-energy” and press ENTER, as shown in Figure 5-1. After pressing ENTER to confirm, the DC bus capacitor begins to discharge, as shown in Figure 5-2.

De-energy?

Figure 5-1 Inverter de-energy interface

48

De-energy..

Figure 5-2 De-energy ongoing

(3) When “De-energy” is successfully completed (Figure 5-3), press ESC to return to the main menu. Check the PV voltage on the LCD according to

“6.3.3 Operation information” or check the voltage of DC bus capacitor with a voltmeter. Don’t turn off the AC circuit breaker or perform maintenance to the inverter until the DC bus capacitor is discharged to safe voltage, as shown in

Figure 5-3.

De-energy OK

Figure 5-3 De-energy OK interface

(4) If “De-energy” fails, as shown on the LCD in Figure 5-4. It takes at least 60 minutes for the inverter to discharge automatically by turning off the

AC circuit breaker. The inverter should not be maintained until the voltmeter

49

shows that there is no electric charge left in the DC bus capacitor.

InverterErr

Figure 5-4 De-energy error interface

(5) If the DC circuit breaker is not turned off, LCD will remind the user to

“TurnOff DC Break”, as shown in Figure 5-5. Please turn off the DC circuit breaker and press “ENT” to continue discharging.

TurnOff DC Break

Figure 5-5 Turnoff DC circuit breaker

5.1.2 Start-up

Turn on the DC and AC circuit breakers.

Manual start-up: Manual start-up is required after a manual shut-down or a fault shut-down by the user.

Move the cursor from the main operation interface to

“4 Setting” according

50

to

“6.3.6 System setup”. Press ENTER and go to submenu “1 ON/OFF”. Then move the cursor to “ON” and press ENTER to start the inverter. Then the inverter will start up and operate normally if the start-up condition is met.

Otherwise, the inverter stands by.

Automatic start-up

: Confirm that the inverter is “ON State” at first. The inverter will start up automatically when the output voltage (Default value is

330V, which can be adjusted according to

“6.3.6 System setup”.) of PV panel meets the set point, AC power grid is normal, and the ambient temperature is within allowable operating range.

5.2 Operation mode

There are 4 operation modes. The following are corresponding indications for each mode.

(1) System check mode is shown in Figure 5-6:

System is in self check status when inverter is energized. The program will complete initialization during this process.

51

Sys.Checking

>>>>>>

Figure 5-6 System self check ongoing

(2) Standby mode, as shown in Figure 5-7:

After self check is completed, the inverter will turn into standby mode if the output voltage of PV panel, AC power grid or ambient temperature does not meet the startup conditions. But the inverter will continue to check whether the startup conditions are met in standby mode until it comes back to normal operation mode. If the warning SPICommErr occurs and the FAULT LED is blinking, the operation mode shown by LCD may not be correct even if LCD shows

“Standby”. Please refer to the solution of SPICommErr in 5-1

Troubleshooting Table on Page 49.

Standby

>>>>>>

Figure 5-7 Inverter system in standby

(3) Normal operation mode, as shown in Figure 5-8:

52

The inverter will turn from standby into normal operation mode when the startup conditions are met as long as the inverter is “ON State”. In this mode, the inverter converts DC generated by PV modules to AC and feeds the AC to the power grid. Under the normal operation mode, the inverter will maximize the DC output from PV panels in the manner of MPPT (Maximum Power Point

Tracking). Meanwhile, the inverter will check the power grid and PV output voltage constantly. Once anything abnormal occurs, the inverter will stop working and take self-protection.

Figure 5-8 Normal operation mode interface

(4) Fault mode, as shown in Figure 5-9:

The inverter will stop working, disconnect from the power grid and turn into fault mode when the inverter or power grid fails. Check the fault information on the LCD according to

“6.3.4 Present fault” and “6.3.5 History”.

To find the specific cause and solution, you can refer to Table 5-1 in

“5.3

Troubleshooting”.

53

GridV.OutLim

Figure 5-9 Fault indication interface

5.3 Troubleshooting

Before you contact our after-sales service center, you are able to find most faults and solutions in Table 5-1 for the troubleshooting. There are three kinds of fault alert statuses: Warn, Protect and Fault. When there is a “Warn”, the system only reminds customers of the problem while it doesn’t change the operation mode. When there is a “Protect”, the system will turn into fault mode and c ome back to normal when the “Protect” disappears. When there is a

“Fault”, the system will stop working and remain standby until resetting the system or repair the inverter to eliminate the fault.

Two ways of system reset are listed as follows:

1. Turn off the AC circuit breaker, wait for 5 seconds and turn on the AC circuit breaker again to recharge the system control unit. If the system check is passed, the inverter will turn into normal operation mode.

2. Run the “2 Restart” command to reboot the system according to “6.3.7

54

System protection parameter setup”.

The causes of fault can be identified based on the faults listed in Table 5-1.

Please contact our after-sales service if the fault still exists.

WARNING:

Shut down the inverter before maintaining the inverter. Disconnect the inverter from PV panels and the Power Grid and make sure there is no electric charge left in the inverter before the maintenance.

55

Table 5-1 Troubleshooting Table

Warn

Definition:

Communication inside inverter fails

Possible causes:

1. Communication circuits inside inverter are loose;

2. LCD software problem;

1. SPICommErr

3. Inverter software problem;

2. Warn0010

Recommended solutions:

1. Observe for 5 minutes and see whether the alarm will be eliminated automatically;

2. Turn off 3-phase working power supply and then reboot the system;

3. Contact our after-sales service center.

Definition:

Fan (invisible from outside) inside inverter is working abnormally

56

3. Warn0030

Possible causes:

1. Fan is blocked;

2. Power supply circuit of the fan has problem;

3. Fan state test circuit is loose;

4. Fan service life has expired;

5. Inverter software problem

Recommended solutions:

1. Observe for 5 minutes and see whether the alarm will be eliminated automatically;

2. Switch off 3-phase working power supply and then reboot the system;

3. Contact our after-sales service center.

Definition:

Eeprom error

Possible causes:

Internal storage error

Recommended solutions:

1. Observe for 5 minutes and see whether the

57

4. Warn0040

5. Warn0050 alarm will be eliminated automatically;

2. Contact our after-sales service center

Definition:

DC circuit breaker error

Possible causes:

1. PV positive pole and negative pole are connected reversely;

2. PV over-current;

3. DC breaker is damaged;

4. DC circuit breaker is turned off

Recommended solutions:

1. Observe for 5 minutes and see whether the alarm will be eliminated automatically;

2. Check DC breaker;

3. Check PV cable connection;

4. Check whether the sunlight is too strong or the configuration of PV panel is appropriate;

5. Contact our after-sales service center

Definition:

58

Temperature sensor error

Possible causes:

1. Temperature inside inverter exceeds normal range;

2. Temperature sensor has problem

Recommended solutions:

1. Observe for 5 minutes and see whether the alarm will be eliminated automatically;

2. Check whether the operation temperature is

﹣25℃~60℃;

3. Contact our after-sales service center

Definition:

Inside warning

Possible causes:

6.

Warn0010~0150

Inverter has inside problem

Recommended solutions:

1. Observe for 5 minutes and see whether the alarm will be eliminated automatically;

59

Protect 1. TempOver

2. Contact our after-sales service center

Definition:

Ambient temperature or temperature inside inverter is too high

Possible causes:

1. Ambient temperature outside the inverter is too high;

2. Radiation air inlet is blocked; Too much dust is on the filter net;

3. Radiation fan is blocked without rotation

Recommended solutions:

1. Confirm that external ambient temperature is within the specified range of operating temperature;

2. Check whether radiation air inlet is blocked and filter net has too much dust;

3. Whether radiation fan is blocked;

4. Observe for 30 minutes and see whether the alarm will be eliminated automatically;

60

5. Contact our after-sales service center

Definition:

Grid voltage exceeds the allowable range, or power grid is not detected

Possible causes:

1. Grid voltage is abnormal;

2. Power grid breaks down;

3. Cable connection between the inverter and the grid is disconnected;

2. GridV.OutLim 4. Inverter has an internal fault

Recommended solutions:

1. Observe for 10 minutes and see whether the alarm will be eliminated automatically;

2. Check whether the grid voltage is within the allowable range;

3. Check whether the cable connection to the grid is disconnected or abnormal;

4. Contact our after-sales service center

3. GridF.OutLim Definition:

61

Grid voltage frequency is abnormal, or grid is not detected

Possible causes:

1. Grid frequency is abnormal;

2. Power grid breaks down;

3. Cable connection between the inverter and the grid is disconnected;

4. Inverter has an internal fault

Recommended solutions:

1. Observe for 10 minutes and see whether the alarm will be eliminated automatically;

2. Check whether the grid frequency is within the allowable range;

3. Check whether the cable connection to the grid is disconnected or abnormal;

4. Contact our after-sales service center

4. PV.VoltOver

Definition:

PV voltage exceeds the allowable value

Possible causes:

62

5. PV.Reverse

1. PV over-voltage

2. Inverter has an internal fault

Recommended solutions:

1. Observe for 30 minutes and see whether the alarm will be eliminated automatically;

2. Check whether PV voltage exceeds the allowable range;

3. Disconnect from PV input, wait for 5 minutes and reconnect to PV input;

4. Contact our after-sales service center

Definition:

PV panel is connected reversely

Possible causes:

1. PV positive pole and negative pole are connected reversely;

2. Inverter has an internal fault

Recommended solutions:

1. Check whether positive pole and negative pole are connected reversely;

63

6. AC.ContErr

2. Contact our after-sales service center

Definition:

AC contactor is abnormal

Possible causes:

1. AC contactor is damaged;

2. Inverter has an internal fault

Recommended solutions:

Contact our after-sales service center

Definition:

Inverter is in the status of emergent stop

Possible causes:

1. Emergency stop button is pressed

7. EmergencyStp

2. Inverter has an internal fault

Recommended solutions:

1. Check whether emergency stop button is pressed. If so, restore the button;

2. Contact our after-sales service center if the problem still exists

64

Definition:

Grounding fault

Possible causes:

1. Ground connection inside inverter is abnormal

2. Inverter has an internal fault

8. GFDIErr

Recommended solutions:

1. Check whether the system has ground connection or grounding fault;

2. Check whether the LED on GFDI is lighted on. If so, replace with a new fuse;

3. Contact our after-sales service center

Definition:

Internal protection of inverter

9. Possible causes:

Protect0010~0620 Internal protection of inverter

Recommended solutions:

1. Observe for 10 minutes and see whether the

65

Fault alarm will be eliminated automatically;

2. Contact our after-sales service center

Definition:

Fault inside inverter

Possible causes:

Serious fault occurs inside inverter

Fault0010~0160

Recommended solutions:

1. The inverter can be restarted referring to

“6.3.7 System protection parameters setup” if it is confirmed that there is no other problem;

2. Contact our after-sales service center

66

Chapter 6 Human Machine Interface

6.1 Description of LCD panel

The CPS SC100KT-O/US-480 LCD panel is protected with a cover which can be opened by switching the cover lock to the right, as shown in Figure 6-1.

Figure 6-1 Switch the cover lock

67

The LCD panel consists of LCD screen, LED lights, buzzer and 6 keys, as shown in Figure 6-2.

Figure 6-2 LCD panel

Different LED statuses are described in Table 6-1 and key functions are listed in Table 6-2.

Table 6-1 LED Indication

LED

Sign

Description State Status

POWER

Work power supply indicator light

Light up

Energized (control panel starts to work)

68

Light off No working power supply

Light up

In grid connection and power generation state

RUN

Grid connection operation indicator light

Blink

Derated running state (light up 0.5s, light off 1.6s)

Light off

In other operation state or no working power supply

GRID

Grid state indicator light

Light up

Blink

Grid is normal

Grid abnormal (light up

0.5s, light off 1.6s)

Light off No working power supply

FAULT

Light up Fault occurs

Slow Alarm occurs (light up 0.5s, blink light off 2s)

Fault state indicator light

Quick blink

Light off

Protective action (light up

0.5s, light off 0.5s)

No fault or no working power supply

69

Table 6-2 Definitions of the keys

Key Description Definition of function

Escape

Enter

Back/end/mute

Confirm entering the menu

/Confirm set point

Up

Down

Left

6.2 Operation state

Right

Page up in selection menu

Page down in selection menu

-1 when setting parameters

+1 when setting parameters

Table 6-1 indicates the definitions of LED, i.e. indicates the information of the inverter’s operation state. It indicates that the system is energized and under DSP control when “POWER” lights up.

“RUN” will light up when the inverter detects that the grid connection conditions meet the requirements and power is fed to the grid. “RUN” will blink

70

if the grid is in derated running state during the period of feeding power to the grid.

“GRID” will light up when the grid is normal during the operation of the inverter. Otherwise, “GRID” will blink until the grid restores to normal.

“FAULT” will blink quickly as a fault (except grid abnormality) occurs.

“FAULT” will not light off until the fault is eliminated. The light will blink slowly when an alarm occurs. “FAULT” keeps lighting up when an internal fault occurs.

“FAULT” will not light up if both the inverter and grid are normal.

The buzzer will give alarms if a fault (power grid abnormality included) occurs.

6.3 Interface and menu functions

Users can perform the corresponding operations with the 6 function keys according to the indications of the LCD.

6.3.1 Interface types

(1) The LCD interface starts with the company logo once the system is energized, as shown in Figure 6-3.

71

Figure 6-3 LOGO interface

(2) Indication of inverter operation mode:

Sys.Checking

>>>>>>

Figure 6-4 Inverter system check ongoing

Standby

>>>>>>

Figure 6-5 Inverter system in standby mode

72

PV

420 V

48.7 A

=

~

06/07 12:09:01

479

19.8

VAC kW

78.5

kwh

Figure 6-6 Default display interface for normal operation

GridV.OutLim

Figure 6-7 Fault indication interface

LCD screen will display different mode interfaces based on the operation modes of the inverter. There are four operation modes: startup system check mode (as shown in Figure 6-4), stand-by mode (as shown in Figure 6-5), normal operation mode (as shown in Figure 6-6) and fault mode (as shown in

Figure 6-7).

The default indication interface mainly indicates PV voltage, PV current,

Grid voltage, instant power, daily generated power and time information under normal operation.

The present fault information will be indicated on the LCD screen when

73

the inverter is in fault mode.

6.3.2 Main operation interface

LCD screen displays “default indication interface” when the inverter is in operation mode. Press the ESC key in this interface to escape the default interface and enter the main operation interface. The main operation interface is shown in Figure 6-8.

1 OP.Info

2 Alarm

3 History

4 Setting

→5 Dispatch

Figure 6-8 Contents indicated on the main operation interface

The main operation interface of LCD screen has 5 menus, i.e. “1 OP. Info”,

“2 Alarm”, “3 History”, “4 Setting” and ”5 Dispatch”. The users may select options with PAGEUP and PAGEDOWN, and then press ENTER to confirm selection. The users can return to the default indication interface by pressing the ESC key.

74

6.3.3 Operation information

When the cursor moves to “1 OP. Info” in the main interface, press

ENTER to select the operation information as shown in Figure 6-9. Check the information by pressing PAGEUP and PAGEDOWN. Return to the previous menu and enter the main operation interface by pressing ESC.

1 OP.Info

Yield 23.5kWh

MPac 20.0kW

Pac 19.8kW

RunT 12 .1 h

Uab 480.0V

Ubc 478.9V

Uca 479.5V

Freq 60.0Hz

Ia 22.7A

Ib 22.7A

Ic 22.7A

Tmod 78.2C

Tamb 50 C

Upv 420.0V

Ipv 48.7A

Figure 6-9 Operation information indication

75

6.3.4 Present fault

As described before, when faults occur during the normal operation of the inverter, corresponding fault message will be indicated in “2 Alarm” menu besides the sound and light alarms. Move the cursor to “2 Alarm” and press

ENTER to check out the specific fault information, as shown in Figure 6-10.

2 Alarm

If not existed

No Alarm existed

SPICommErr

IntProtectA

Figure 6-10 Present fault information

6.3.5 History

Move the cursor to “3 History” in the main interface. Press ENTER to check the history information, as shown in Figure 6-11. There are 4 submenus in “3 History” : “1 HistErr”, “2 OP. Recd”, “3 Version” and “4 TotalTag”.

(1) UP to 100 pieces of latest fault messages can be recorded and found in “1 HistErr” menu.

(2) The latest 21 days’ operation history data is available to be found in “2

OP. Recd” menu. All variable names in the data comply with the content in “1

76

OP. Info” menu of the main interface. The users can select the “2 OP. Recd” menu and input the retraceable days (For example, the input number is 21. If the current date is December 15th, the LCD will indicate the operation information of 21 days before that date which is November 24th).

(3) Software version, hardware version and serial number of the product are listed in “3 Version” menu.

(4) Cumulative generated power since the first day the inverter began working is available to be found in “4 TotalTag” menu.

If not existed

NoError

3 History

1 HistErr

2 OP.Recd

3 Version

→4 TotalTag

Existed

1.St2010.12.15 20:50

SPICommErr

2.Ed2010.12.15 20:59

SPICommErr

Pls input date

←2→ ß—12/15

RunT 6.3 h

MPac 20.0KW

Yield 123.5KWh

MachVer

1.00

SerialNo

11010101010101

T- Yield (kWH)

152123.5

Figure 6-11 History menu and submenu

77

6.3.6 System setup

Move the cursor to “4 Setting” in the main interface. Press ENTER to set the current system parameters, as shown in Figure 6-12. There are 6 submenu s in “4 Setting” : “1 ON/OFF”, “2 Language”, “3 Buzzer”, “4 SysTime”,

“5 Commun” and “6 OtherCmd”.

(1) The inverter can be started and shut down with “1 ON/OFF” menu.

Move the cursor to “ON” and press ENTER, “ON State” will then be indicated at the bottom of LCD screen

; move the cursor to “OFF” and press ENTER, then “OFF State” will be indicated as well. The inverter will stand by instead of working normally if the startup conditions are not satisfied even “ON” is selected. The inverter will be shut down i mmediately if “OFF” is selected in any cases.

(2) Two languages, i.e. English and Chinese are available in “2 Language” menu.

(3) Key beep and fault beep can be set mute/unmute in “3 Buzzer” menu.

“Key beep” and “Alarm beep” can be shifted by pressing PAGEUP and

PAGEDOWN. Shift between “Enable” and “Disable” by pressing LEFT and

Right if the cursor is on the “Key beep”. Complete the setup by pressing

ENTER. Similarly, the fault beep can be set up as well.

78

(4) Set up the system date and time with “4 SysTime” menu. (These parameters are of critical importance and will be used in history information).

Select year, month, day, hour and minute by pressing PAGEUP and

PAGEDOWN, and set up the specific date and time by pressing LEFT and

RIGHT.

(5) Set the 485 communication parameters with “5 Commun.” menu.

(6)

In “6 OtherCmd” menu, run “1 De-energy” to discharge the electric charges of DC capacitor quickly; run “2 PowerTrain” to check the status of main system circuit for the initial on-grid testing.

79

4 Setting

1 ON/OFF

2 Language

3 Buzzer

→4 SysTime

5 Commun

6 OtherCmd

→ ON

OFF

ON State

中文

→ English

EnglishVer

KeyBeep

Enabled

AlarmBeep

→ Disabled

2009 / 12 / 15

21 :14

→ Address 2

BaudRate 3

1 2400 2 4800

3 9600 4 115200

→ 1 De-energy

2 PowerTrain

Figure 6-12 System setup menu and submenu

6.3.7 Power Dispatch

“ActivePower” and “PowerFactor” parameters can be set up through LCD

80

operations as well as remote control by software.

Local dispatch order: Service personnel can adjust the “ActivePower” and

“PowerFactor” parameters through LCD operations. For detailed setup steps, please refer to “6.3.8 System protection parameters setup”.

The current parameters of “ActivePower” and “PowerFactor” can be checked by the following steps.

Move the cu rsor to “5 Dispatch” in the main interface, as shown in Figure

6-13:

1 OP.Info

2 Alarm

3 History

4 Setting

→5 Dispatch

Figure 6-13 Contents indicated on the main operation interface

81

Press ENTER to the interface shown in Figure 6-14.

ActivePower(%)

100.0

PowerFactor

1.000

Figure 6-14 Parameters of power dispatch

Remote dispatch method: The “ActivePower” and “PowerFactor” parameters can be adjusted through remote monitoring software. For detailed information, please refer to the manual of our monitoring system products.

6.3.8 System protection parameters setup

By pressing PAGEDOWN and ENTER at the same time in the main interface and entering the password

(PAGEUP->PAGEDOWN->RIGHT->LEFT), the system parameter setup menu is accessed. This menu includes 4 submenus

: “1 SysPara”, “2 Restart”, “3

Recover” and “4 ClrErrRecd”, as shown in Figure 6-15.

(1)

“1 SysPara” menu: Set up the system protection parameters in “1

SysPara” menu. The specification of protection parameters is shown in Table

6-3.

82

Table 6-3 Protection Parameters Table

No.

Description of parameter

1

Grid voltage upper limit (V)

LCD indication

GridV.Max(V)

2

3

Trip time under

Max. voltage (S)

GridVmaxTripT(S)

Grid votage lower limit (V)

GridV.Min(V)

Setup range (lower limit, default & upper limit)

(527, 527, 575)

(0.16, 0.16, 1.00)

(240, 421, 421)

4

5

Trip time under

Max. voltage (S)

GridVminTripT(S)

Grid frequency lower limit (Hz)

GridF.Min(Hz)

(0.16, 0.16, 2.00)

(57.00, 59.30, 59.80)

6

Frequency trip time

(S)

7

8

Active power derating (%)

Reactive

GridFTripT(S)

PowerDerating

(%)

ReactiveComp

(0.16, 0.16, 300.00)

(10%, 100%, 100%)

(-0.900, 1.000, 0.900)

83

No.

Description of parameter

LCD indication

Setup range (lower limit, default & upper limit)

Compensation

9 PV start voltage (V) PVStartVol(V)

(300, 330, 600)

10 Time delay (Min) Tdelay(Min)

(0.1, 5.0, 5.0)

(2)

“2 Restart” menu: If the inverter stops working as a result of a severe fault inside the inverter. The user may perform a force restart by the options in

“2 Restart” menu. Note that this function is effective for the inverter to restore to normal operation only when the Fault0010~0160 in the troubleshooting table occurs. This function will not respond when the inverter is in normal operation mode and a “FaultOperated” alarm will be indicated on the LCD screen.

(3) “3 Recover” menu: The manufacturer’s parameter default value can be recovered when the inverter is not in operation mode. Otherwise, a

“FaultOperated” alarm will be indicated.

(4)

“4 ClrErrRecd” menu: History information of the faults can be cleared.

A confirmation is required to clear the records.

84

GridV.Max(V)

→ 527

GridVmaxTripT(S)

0.16

Pls Input Pwd

****

Pwd Error

Pls Input Again

****

Wrong Password

→1 SysPara

2 Restart

3 Recover

4 ClrErrRecd

GridV.Min(V)

→ 421

GridVminTripT(S)

0.16

GridF.Max(Hz)

→ 59.30

GridFTripT(S)

0.16

Are You Sure?

Initialization?

FaultOperated

Restarting..

Success

Success !

Failure

Failure!

Recovering..

Succes s

Success !

Failure

Failure!

ClearErrors?

Success !

FaultOperated

Figure 6-15 System parameter setup

85

Chapter 7 Service and Maintenance

The following regular maintenance steps should be carried out at regular intervals to ensure the inverter’s operation with optimal performance.

CAUTION:

Although designed to meet international safety standards, the

PV-Inverter can become hot during operation. Do not touch the heat sink or peripheral surfaces during or shortly after operation.

7.1 Maintenance instruction of filter net

7.1.1 Maintenance of filter net on the top

WARNING:

Shut down the inverter before maintaining the inverter. Disconnect the inverter from PV panels and the Power Grid and make sure there is no electric charge left in the inverter before the maintenance.

Disassemble the filter net on the top as follows:

(1) Remove the M3 screws in the middle of the filter net with a PH2 Phillips head screwdriver and take off the fixing plate.

86

(2) Push aside the two clips on both sides and disassemble the filter net.

(3) Clean the filter net and put it back or replace with a new one and then reinstall the fixing plate.

Fixing plate

Push aside the clips on both sides

Filter net

Figure 7-1 Disassembling filter net on the top

87

WARNING:

Shut down the inverter before maintaining the inverter. Disconnect the inverter from PV panels and the Power Grid and make sure there is no electric charge left in the inverter before the maintenance.

7.1.2 Maintenance of filter net at the bottom

(1) Remove the four M4 screws on the baffle at the bottom of inverter with a

T25 spline screwdriver and then take off the baffle.

(2) Pull out the filter net from the bottom of the inverter, as shown in Figure 7-2.

Figure 7-2 Pulling out filter net at the bottom

(4) Clean the filter net, put it back or replace with a new one and then reinstall

88

the baffle.

WARNING:

Shut down the inverter before maintaining the inverter. Disconnect the inverter from PV panels and the Power Grid and make sure there is no electric charge left in the inverter before the maintenance.

7.2 Maintenance of fan tray assembly

(1) Remove the eight M5 screws on the top of inverter with a T25 spline screwdriver and then take off the cover, as shown in Figure 7-3.

Figure 7-3 Disassembling of top cover

89

(2) Disconnect the buckle on the fan tray, remove the screws on the fan tray, unplug the power supply connector and then take off the fan tray assembly, as shown in Figure 7-4.

Figure 7-4 Disassembling of fan tray assembly

(3) Clean the fan tray assembly, put it back or replace with a new one and then reinstall the fan tray assembly and top cover.

90

Chapter 8 Technical Data

Model Name

DC Input

Max. PV Power

Nominal DC Input

Power

Max. DC Input

Voltage

Operating DC Input

Voltage Range

Start-up DC Input

Voltage / Power

Nominal DC Input

Voltage

Number of MPP

Trackers

CPS

SC100KT-O/US-480

CPS

SC100KT-OPG/US-480

135kW

105kW

600Vdc

300-600Vdc

330Vdc/700W

430Vdc

1

91

MPPT Voltage

Range

Max. Input Current

Number of DC Inputs and Fuses

Grounding

DC Disconnection

Type

AC Output

Rated AC Output

Power

Max. AC Output

Power

Rated Output Voltage

Output Voltage

Range

Grid Connection

Type

Negative

330-500Vdc

350A

4

Breaker

100kW

480Vac

422-528Vac

3

100kW

/ PE

Positive

92

Max AC Output

Current

Rated Output

Frequency

Output Frequency

Range

Power Factor

Current THD

AC Disconnection

Type

System

Topology

Max. Efficiency

CEC Efficiency

Stand-by / Night

Consumption

Environment

Protection Degree

93

Transformer

96.8%

96.0%

<50W / <40W

NEMA 3R

120A

60Hz

59.3-60.5Hz

>0.99

<3%

Breaker

Cooling

Operating

Temperature Range

Variable speed cooling fans

-4°F to +140°F / - 20°C to +60°C (derating from

+50°C / +122°F)

Operating Humidity

Operating Altitude

0-95%, non-condensing

6562ft / 2000m (derating from 4921.3ft / 1500m)

Display and Communication

Display LCD + LED

RS485 Communication

Mechanical Data

Dimensions (WxHxD)

Weight

47.2x72.8x34.6in / 1200x1850x880mm

1984lbs / 900kg

Safety

Safety and EMC UL1741:2010, CSA-C22.2 NO.107.1-01, FCC

PART15 Standard

Grid Standard IEEE1547:2003, IEEE1547.1:2005

*Note 1

: Exceeding the rated voltage shown in “Max. DC Input Voltage” may cause permanent damage to the equipment.

**Note 2:

“Allowable Grid Voltage” and “Rated Output Frequency” depend on the specific national grid standard.

94

***Note 3: When the ambient temperature exceeds 50℃ (122℉), the maximum output power will derate as 3% per ℃/1.8℉. When the ambient temperature reaches 60℃ (140℉), the maximum output power will be 70% of the rated output power. The inverter will stop working under self-protection when the ambient temperature is over 65℃ (149℉).

95

Chapter 9 Limited Warranty

The warranty policy of this product is specified in the contract; otherwise, the warranty period is 5 years.

For service, Chint Power Systems America will provide local support. For

Warranty terms, please refer to the CPS America standard warranty policy in place at time of purchase.

96

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement