BAPI Delta Humidity Datasheet

B14 Delta Style Room Units
Humidity & Combination Temp/Humidity Sensors
Features & Options
Rev. 08/27/13
*
l Low Profile Delta Style Enclosure
l Humidity Only or Temp./Humidity Combo
l Optional Display
l 2% and 3% RH Accuracies
l Optional Communications Jack
l User Adjustable Toggle Rate Between Temperature and Humidity
l Wide Selection of Temperature Sensing Elements
l Full-range Temperature Compensation of RH Signal
l Two Year Warranty
The Delta Style room units are available as Humidity Only sensors or
as Combination temperature and humidity sensors. The Delta Style
enclosure features an optional display with a user adjustable toggle
rate between humidity and temperature and can display in either °C
or °F.
The unit is available with the entire line of BAPI
temperature sensors. If a temperature transmitter and
humidity transmitter are desired, then see the “X-Combo”
Unit on pages B12-13 of this section.
For detailed specs on the individual Sensors
& Transmitters, turn to the “Sensors” section.
* All Passive Thermistors 10K Ω and smaller are CE compliant.
The
Delta Style Enclosures
with and without Display
BAPI-Guard
l Prevents Tampering
and Unauthorized
Adjustment
l Exceptional Airflow
l Available in Two Sizes
(See Accessories for more info.)
Specifications
Agency: RoHS and CE* (for transmitters
Power:10 to 35 VDC (0 to 5 VDC or 4 to 20 mA Outputs)
15 to 40 VDC (0 to 10 VDC Output)
and select thermistors)
12 to 24 VAC (0 to 5 VDC Output)
15 to 28 VAC (0 to 10 VDC Output)
Note: If AC power is used, it must be shielded from the signal wiring
Power Consumption:
22 mA max. DC (0 to 5 VDC or 4 to 20 mA Outputs)
6 mA max DC (0 to 10 VDC Output)
0.53 VA max. AC (0 to 5 VDC Output)
0.14 VA max. AC (0 to10 VDC Output)
Sensing Elements:
Temperature - Thermistor, RTD or Semiconductor
Humidity - Capacitive Type, ±2% or ±3% RH, 20 to 80%@25°C
RH Calb. Adjustment: ±5% POT
Wiring: 2 to 3 pair of 16 to 22 AWG**
Mounting: Standard 2”x4” J-box or drywall mount - screws provided
Environmental Operation Range:
**BAPI recommends that you do not
Temperature: 32 to 122 oF (0 to 50 oC)
run wiring for the room units in the
Humidity: 5 to 95%, non-condensing
same conduit as line voltage wiring
Material: ABS Plastic
or with wiring used to supply highly
inductive loads such as motors,
Material Rating: UL94 HB
generators and coils.
Building Automation Products, Inc. • 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel: +1-608-735-4800 • Fax: +1-608-735-4804 • Email: sales@bapihvac.com • Web: www.bapihvac.com
Delta Style Room Units B15
Humidity & Combination Temp/Humidity Sensors
Rev. 08/27/13
Ordering Information
Delta Style Room Unit, Humidity only or Temp./Humidity Combo
BA/
Optional Temp. Sensor Use the designator number, shown to the left in bold. Omit if ordering humidity only
##-
1.8K
2.2K
3K
3.25K
3.3K
10K-2
10K-3
10K-3[11K]
20K
47K
50K
100K
THERMISTORS
1.8K Ω @ 25 °C
2.2K Ω @ 25 °C
3K Ω @ 25 °C
3.25K Ω @ 25 °C (T30 type)
3.3K Ω @ 25 °C
10K Ω @ 25 °C
10K Ω @ 25 °C
5,238 Ω @ 25 °C
20K Ω @ 25 °C
47K Ω @ 25 °C
50K Ω @ 25 °C
100K Ω @ 25 °C
100
1K [375]
1K[NI]
1K
2K
334
592
RTDs
100 Ω Platinum @ 0 °C, .385 Ω/°C temp. coeff.
1K Ω Platinum @ 0 °C, 3.75 Ω/°C temp. coeff.
1K Ω Nickel @ 21°C, 5 Ω/°C temp. coeff.
1K Ω Platinum @ 0 °C, 3.85 Ω/°C temp. coeff.
2K Ω Silicon @ 20 °C, 8 Ω/°C temp. coeff.
SEMICONDUCTORS
LM334 Semiconductor
AD592 Semiconductor, 273 µA @ 0 °C
List
Price
Your
Order
Thermistors
$18 Each
$_______
RTD's
$25 Each
or
$35 for 1K[NI]
$_______
Semiconductors
$25 Each
$_______
$240
$240
$240
$240
$_______
$_______
$_______
$_______
$35
$_______
$7.50
$_______
$10
$10
$_______
$_______
Total =
$______
TEMPERATURE TRANSMITTERS
See X-Combo Unit on pages B12-13
Humidity Transmitter
Must select one
H200
±2% Humidity Transmitter with Interchangeable Output of 0 to 5 V or 4 to 20 mA*
±2% Humidity Transmitter with 0 to 10 V Output
H210
H300
±3% Humidity Transmitter with Interchangeable Output of 0 to 5 V or 4 to 20 mA*
H310
±3% Humidity Transmitter with 0 to 10 V Output
Delta Style Enclosure
Must select
-R
Delta Style Room Enclosure
Optional LCD Display
D
Omit if ordering a unit without display
LCD Display
Optional Test & Balance
Skip if not required
Three Position Switch - "Low" & "High" values vary, "Normal"
-TB
is live sensor value. Call for details.
EXAMPLE
BA/
10K-2
H200
-R
Example Part Number: BA/10K-2-H200-RD-35L
Optional Comm. Jack
Mounted in unit's base
-C35L 3.5 mm Phono Jack w/ Leads Attached
-C35LT 3.5 mm Phono Jack w/ Leads & Terminal Block
Optional Copla White Enclosure
(Warm White is Standard)
-CPW Copla White Enclosure Color
D
-C35L
Your Part Number:
*DC input voltage is required for current output.
See the "X-Combo" Unit on page B12-13 for more Temperature Transmitter & Humidity Transmitter combination options.
Call BAPI if you have questions about the above ordering grid or the configuration of the product you are ordering.
Building Automation Products, Inc. • 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel: +1-608-735-4800 • Fax: +1-608-735-4804 • Email: sales@bapihvac.com • Web: www.bapihvac.com