Avocent Data Sheet
Avocent Power Management 10/20 Series
Distribution Units (PM 10/20 PDUs)
Integrated Remote Power Management and Distribution for Use in
Branch and Remote Offices
Quick Facts
• Power control over remote IT assets from
anywhere on earth
• Seamless integration with other Avocent
appliances and with the DSView® 3
management software
• Proactive fault management and isolation
• Fault notifications via e-mail, SMS page
and SNMP traps
Benefits
• Restore practically any IT asset without
dispatching service personnel
Avocent PM 10 Horizontal PDU
Avocent PM PDUs enable remote power control and system management of IT assets in
branch and remote offices. When used in conjunction with Avocent ACS advanced console
servers, MergePoint Unity® KVM over IP and serial console switches or DSR® KVM over IP
switch appliances, the Avocent PM PDUs offer quick problem resolution through an integrated management interface. With one or more outlets positively associated with a particular
device, users may control power “in line” through a user-defined “hot key” or by using an
• Virtually eliminate power control errors
during crisis situations
• Improve administrative efficiency with
integrated control functions
• Proactively identify and manage problems
to improve mean time between failure
(MTBF)
set facilitates scripting.
• Reduce risk, reduce mean time to repair
(MTTR)
NEMA Models
• Conserve valuable IP addresses and
switch ports
intuitive Web browser-based graphical user interface (GUI). In addition, a special command
Avocent NEMA PM PDU models are equipped with 5-15R power outlets and fixed power
cables. These units are available in 15A, 20A and 30A capacities with optional twist-lock input
plugs. Each model includes two RS-232 ports: one for management and the second for daisychain expansion. Daisy chaining allows an operator to control up to 128 power outlets as a
single device. The NEMA models are designed to operate in 100-125 VAC environments.
IEC Models
Avocent IEC PM PDU models are equipped with IEC320-C13 power outlets and either
IEC320 modular inlets or fixed power cables. These units are available in 10A, 15A, 16A,
20A, 30A and 32A capacities. Each model includes two RS-232 ports: one for management
and the second for daisy-chain expansion. Daisy chaining allows an operator to control up to
128 power outlets as a single device. The IEC models are designed to operate in 100-240
VAC environments.
An LED display shows the real-time, true RMS current draw. Each PM PDU may be configured to sound an alarm during an overcurrent condition, and if it is connected to an Avocent
ACS console server, the PDU may also send notifications via e-mail messages, Short
Message Service (SMS) pager messages and SNMP traps.
[Avocent Data Sheet] PM 10/20 Power Distribution Units
Typical PM Appliance Configuration
w3
DSVinet Software
eme
Manag
4
Admin
3
1
2
1
2
2
2 2
2
MergePoint Unity
KVM and Serial over IP
Serial Console Appliance
e
h Offic
Branc
enter
Data C
e
h Offic
Branc
1
2
2
Avocent PM
PDUs
3
Avocent ACS
Advanced Console Server
4
DSR
KVM over IP
Appliance
Features
Connectivity
• RS-232 serial port for configuration and management
• Second RS-232 serial port for control-level daisy chaining (up to 128 outlets)
• Full RS-232 signal support allows dial-in access via modem
Administration
• Name assignment per PDU (up to 8 characters)
• Name assignment per outlet (up to 16 characters)
• Local authentication support (up to 8 users)
• Per-outlet access control lists
Management
• Independent control of power outlets (power on/off, cycle)
• Virtual lock per outlet (on or off states)
• Sequential power up with user-defined inter-outlet delays
• Global, true RMS current monitoring per PDU
• Two-digit 7-segment LED current display
• On/off status LED per outlet
• User-defined overcurrent threshold with alarm
• Built-in visual and audible alarms
• Built-in ambient temperature sensor
Form Factors
• Industry’s highest outlet density (up to 10 outlets per 1U)
• Horizontal (1U) and vertical (0U) models address a wide variety of applications
Form Factors
• Industry’s highest outlet density (up to 10 outlets per 1U)
• Horizontal (1U) and vertical (0U) models address a wide variety of applications
Integration Features*
• Integrated power management through console and KVM sessions
• CLI, menu and GUI interfaces
• Multi-outlet grouping for devices with redundant power supplies
• RADIUS, TACACS+, Kerberos, LDAP and Active Directory server-
based, authentication with local fallback
• Token-based strong authentication (RSA SecurID)
• Event logging via syslog
• Fault notification via e-mail, SMS page, SNMP trap
• SNMP integration with enterprise systems
* Features available when product is used in conjunction with Avocent ACS console
servers, DSR and MergePoint Unity switches or DSView 3 management software
(not included).
IEC Models’ Specifications
Inputs
Power
Interfaces
PM 10i-10A PDU
2 RJ-45 RS-232 serial ports (9,600 8-N-1)
100–240 VAC, 10 A, IEC 320-C14 inlet
10 or 20 IEC 320-C13 outlets
10 A max. branch circuit rating (10 A max. per IEC
Recommended Operating Temperature
320-C13 outlet)
50ºF to 104ºF (10ºC to 40ºC)
PM 10i-15A* PDU
100–240 VAC, 15 A, IEC 320-C14 inlet
15 A max. branch circuit rating (10 A max. per IEC
320-C13 outlet)
PM 10i-16A PDU
122ºF (50ºC)
Storage Temperature
Unterminated
–40ºF to 185ºF (–40ºC to 85ºC)
on fixed 8-foot power cord
Humidity
16 A max. branch circuit rating (10 A max. per IEC
5% to 95% non-condensing
320-C13 outlet)
Dimensions (W x D x H)
100–240 VAC, 20 A, IEC 320-C20 inlet
20 A max. branch circuit rating (10 A max. per IEC
320-C13 outlet)
PM 10i-L30A,* PM 20i-L30A* PDUs
100–240 VAC, 30 A, NEMA L6-30P twist-lock plug
30 A max. branch circuit rating (10 A max. per IEC
320-C13 outlet)
on fixed 8-foot power cord
Maximum Operating Temperature
100–240 VAC, 16 A, IEC 320-C20 inlet
PM 10i-20A,* PM 20i-20A* PDUs
NEMA L6-30P
IEC 309
on fixed 8-foot power cord
PM 10i-10A, -15A, -16A, -20A PDUs
17 x 8 x 1.75 in. (43.18 x 20.32 x 4.45 cm)
PM 10i-L30A, -32A, -32Au PDUs
17 x 12 x 1.75 in. (43.18 x 30.48 x 4.45 cm)
PM 20i-16A, -20A, -L30A, -32A, -32Au PDUs
IEC 320-C14
2 x 2.8 x 66 in. (5.08 x 7.11 x 167.64 cm
modular inlet
Weight
PM 10i PDU
PM 10i-32A, PM 20i-32A PDUs
11.1 lbs. (5.0 kg)
100–240 VAC, 32 A, IEC 309 plug
32 A max. branch circuit rating (10 A max. per IEC
320-C13 outlet)
PM 20i PDU
IEC 320-C20
modular inlet
14.1 lbs. (6.4 kg)
PM 10i-32Au, PM 20i-32Au PDUs
*Units are certified to 80% of max. current rating.
100–240 VAC, 32 A, unterminated cable
†International models.
OUTLETS
32 A max. branch circuit rating (10 A max. per IEC
320-C13 outlet)
PM 20i-16A PDU
100–240 VAC, 16 A, IEC 320-C20 inlet
16 A max. branch circuit rating (10 A max. per IEC
IEC 320-C13
320-C13 outlet)
modular
Ordering details for IEC PM PDU Appliances
part #
PDU
Description
Ordering details for cables and accessories
part #
atp3110
PM 10i-10A
10 outlets, 10 A max. branch, IEC 320-C14
ATP3115-001
PM 10i-15A
10 outlets, 15 A max. branch, IEC 320-C14
ATP3116
PM 10i-16A
10 outlets, 16 A max. branch, IEC 320-C20
ATP3120-001
PM 10i-20A
10 outlets, 20 A max. branch, IEC 320-C20
ATP3231-001
PM 10i-L30A
10 outlets, 30 A max. branch, NEMA L6-30P
CAB0089
ATP3230
PM 10i-32A
10 outlets, 32 A max. branch, IEC 309
CAB0191
ATP3232
PM 10i-32A
10 outlets, 32 A max. branch, unterminated
ATP2116
PM 20i-16A 20 outlets, 16 A max. branch, IEC 320-C20
ATP2120-001
PM 20i-20A
20 outlets, 20 A max. branch, IEC 320-C20
ATP3130-001
PM 20i-L30A
20 outlets, 30 A max. branch, NEMA L6-30P
CAB0194
ATP2132
PM 20i-32A
20 outlets, 32 A max. branch, IEC 309
CAB0195
ATP2131
PM 20i-32Au
20 outlets, 32 A max. branch, unterminated
For country-specific availability, please contact an Avocent sales representative.
CAB0055
CAB0087
CAB0088
CAB0192
CAB0193
CAB0197
CAB0198
Type
PM 10i PDU, 10 A power
cable
PM 10i PDU, 10 A power
cable
PM 10i PDU, 10 A power
cable
PM 10i PDU, 10 A power
cable
PM 10i PDU, 15 A power
cable
PM 10i PDU, PM 20i, 16 A
power cable
PM 10i PDU, PM 20i, 16 A
power cable
PM 10i PDU, PM 20i, 16 A
power cable
PM 10i PDU, PM 20i, 20 A
US power cable
PM 10i PDU, PM 20i, 20 A
US power cable
PM 10i PDU, PM 20i, 20 A
US power cable
Description
8 ft., IEC320-C13 to AS3112, AUS & NZ
8 ft., IEC320-C13 to CEE 7/7 Schuko,
8 ft., IEC320-C13 to BS1363, UK &
8 ft., IEC320-C13 to NEMA 5-15P, USA
8 ft., IEC320-C13 to NEMA 6-15P, USA
8 ft., IEC320-C19 to AS3112,
8 ft., IEC320-C19 to CEE 7/7
8 ft., IEC320-C19 to BS1363,
8 ft., IEC320-C19 to NEMA
8 ft., IEC320-C19 to NEMA
8 ft., IEC320-C19 to NEMA
[Avocent Data Sheet] PM 10/20 Power Distribution Units
NEMA Models’ Specifications
Power*
Recommended Operating Temperature
PM 10-15A PDU
50ºF to 104ºF (10ºC to 40ºC)
100–125 VAC, 15 A, NEMA 5-15P plug
Maximum Operating Temperature
15 A max. branch circuit rating
122ºF (50ºC)
15 A max. per NEMA 5-15R outlet
Inputs
Inputs
NEMA 5-15P
on fixed 12-foot power cord
Storage Temperature
PM 10-20A, PM20-20A PDUs
100–125 VAC, 20 A, NEMA 5-20P plug
20 A max. branch circuit rating
–40ºF to 185ºF (–40ºC to 85ºC)
Humidity
5% to 95% non-condensing
NEMA 5-20P
PM 10-L20A, PM20-L20A PDUs
Dimensions (W x D x H)
on fixed 12-foot power cord
100–125 VAC, 20 A, NEMA L5-20P twist-lock
PM 10-15A, -20A, -L20A PDUs
plug
17 x 8.25 x 1.75 in. (43.18 x 20.96 x 4.45 cm)
20 A max. branch circuit rating
PM 10-L30A PDUs
15 A max. per NEMA 5-15R outlet
17 x 8.5 x 1.75 in. (43.18 x 21.59 x 4.45 cm)
PM 10-L30A, PM20-L30A PDUs
PM 20-20A, -L20A, -L30A PDUs
15 A max. per NEMA 5-15R outlet
100–125 VAC, 30 A, NEMA L5-30P twist-lock
1.8 x 2.2 x 66 in. (4.57 x 5.56 x 167.64 cm)
plug
Weight
30 A max. branch circuit rating
PM 10 PDU
15 A max. per NEMA 5-15R outlet
8.8 lbs. (4.0 kg)
Interfaces
PM 20 PDU
2 RJ-45 RS-232 serial ports (9,600 8-N-1)
12.4 lbs. (5.6 kg)
10 or 20 NEMA 5-15R outlets
NEMA L5-20P
on fixed 12-foot power cord
NEMA L5-30P
on fixed 8-foot power cord
*Units are certified to 80% of max. current rating.
OUTLETS
Ordering details for NEMA PM Appliances
part #
PDU
Description
ATP3015-001
PM 10-15A
10 outlets, 15 A max. branch, NEMA 5-15P
ATP3020-001 PM 10-20A
10 outlets, 20 A max. branch, NEMA 5-20P
ATP3025-001
PM 10-L20A
10 outlets, 20 A max. branch, NEMA L5-20P
ATP3036-001 PM 10-L30A
10 outlets, 30 A max. branch, NEMA L5-30P
ATP2020-001 PM 20-20A
20 outlets, 20 A max. branch, NEMA 5-20P
ATP2025-001
PM 20-L20A
20 outlets, 20 A max. branch, NEMA L5-20P
ATP2035-001
PM 20-L30A
20 outlets, 30 A max. branch, NEMA L5-30P
Avocent, the Avocent logo, MergePoint Unity, DSR and DSView are registered trademarks of
Avocent Corporation or its affiliates in the US or other countries. All other marks are the property
of their respective owners. © 2010 Avocent Corporation. All rights reserved. 0610-PM10i20i-DS-EN