BATTERY ALARM

___________________________________________________________________
Battery Alarm
Remote panel adjustments
Dipswitch explanation:
A
12V
-0,1V
-0,2V
-0,2V
-0,5V
-1V
-2V
ON
Not used
1
2
3
4
5
6
7
8
24V
-0,1V
-0,2V
-0,2V
-0,5V
-1V
-2V
OFF
Not used
B
12V
ON
ON
Not used
HYSB +1,25V
HYSA +2,50V
Uhigh -2V
Uhigh -1V
ON
24V
ON
OFF
Not used
HYSB +2,50V
HYSA +5V
Uhigh -2V
Uhigh -1V
OFF
1.
Place A7, B2, B8 on the 12V or 24V setting. [ON=12V] [OFF=24V]
2.
B1 always ON
3.
With the Dipswitches A1 t/m A6 chose a higher or lower Ulow alarm.
4.
Place A1, A2, A3, A4, A5, A6 = ON, then Ulow = 9.5V or
Warning:
For the J1 connector on the PCB the contacts
(COM, N0 and NC) are as per diagram below!
J1
J2
Battery Alarm
A1, A2, A3, A4, A6 = ON, and A5 = OFF, then Ulow = 10.5V or
A1, A2, A3, A4, A5 = ON, and A6 = OFF, then Ulow = 11.5V.
5.
With the Dipswitches B6, B7 chose a higher or lower Uhigh alarm.
B6, B7 = ON. The Uhigh alarm is 15V. Change this with B6 and B7.
B6 = ON, and B7 = OFF, then Uhigh alarm is 16V
B6 = OFF, and B7 = ON, then Uhigh alarm is 16.5V
6.
B4, B5 = OFF. The hysteresis for Ulow alarm is now 1V for 12V and 24V Battery Alarm remote panel.
For another hysteresis; switch B4 and/or B5 to the ON position.
B4 gives a 1V+1.25V hysteresis for a 12V Battery Alarm and 2V+2.5V for a 24V Battery Alarm.
B5 gives a 1V+2.50V hysteresis for a 12V Battery Alarm and 2V+5V for a 24V Battery Alarm.