GDS 301
TECHNOLOGIES LTD
Single line sample unit
Specification Sheet
ref C553
• Continuous monitoring
• Flammable, oxygen or toxic gases
• Easily installed and maintained
• 2 alarm levels & relays
• 4~20mA analogue output
• Line blockage and pump fail monitor
• Delay to alarm option
Application
The GDS 301 system is designed to monitor gas levels in situations where the positioning of
conventional gas sensors may not be practical. This may be due to equipment security, cable routing,
access for detector head installation/maintenance, harsh environment or a cost effective means of
monitoring designated hazardous areas, typically - tunnels, marine applications, underground/high
level voids, process control, brewing, horticulture, livestock husbandry.
Operation
A gas sample is continuously extracted via a fixed sample line from the target area. The central unit
provides gas level readouts with two alarm trip points, providing a range of signal outputs for
annunciator or control functions.
A wide range of sensor devices are available to suit customer requirements which include infra red,
electrochemical, catalytic and other specialist sensors which offer a 4~20mA signal output.
Technical Data
ref C553
Measurements
•
Combustible Gas L.E.L %Vol, ppm
Toxic Gas - ppm, %Vol
Oxygen % Vol
Power supply
•
230/115vAC or 24vDC ± 15%
The two voltages may be used
simultaneously (standby batteries)
Frequency
50/60Hz
Alarm Settings
•
•
•
Alarm delay
•
T1 - 10 seconds, T2 - 30 seconds,
T1 + T2 - 10 minutes
Indicators
•
•
•
•
•
•
•
•
•
•
•
•
Power - Green L.E.D.
Alarms - Low/High - Red L.E.D.
Flow fail - Amber L.E.D.
Fault - Amber L.E.D.
System test alarm L.E.Dʼs flashing
Consumption
Outputs
Audible Alarm
•
Low, High gas and Fault
Permanent mute option
Reset Switch
•
•
Auto or Manual - pre set manual
•
•
•
•
•
•
•
•
•
•
•
•
Isolation of alarm relays during service
Test Switch
Inhibit
Protection
10 watts
Environmental
Digital setting (fully adjustable
between zero and full scale)
Cable Entry
Sample Tube
Exhaust port
Miscellaneous
Low alarm relay - S.P.C.O
High alarm relay - S.P.C.O
Fault alarm relay - S.P.C.O
Flow fail - S.P.C.O
Relays rated 5A/230vAC
ND or NE pre set normally de energised
Analogue 4-20mA/1-5v
24vDC - 100mA max
(Auxiliary equipment supply)
Used to check alarm indicators, sounder
and relay action
IP65
Ambient temperature -5 to 45˚C
Storage temperature +10 to 60˚C
Humidity range 0 - 90 RH
Rear, side, top, bottom
6mm OD 4mm ID
Max. length 100m
8mm OD
Dimensions 315mm W 265mm H 95mm D
Weight 3.8kg
Cable entry - bottom, sides, rear
Relay Select
Energised / De Energised
F1
Sounder
Mute
Sounder
ED
Hi
Lo
F
T2
T1
LL
O2
RES
Transformer
M
A
Sensor volts
adjust
DPM Span
Remote
Reset
N/O
F2
DC out
select
Field Terminals
Alarm
set push
switch
T1 – Alarm delay - 10 secs
T2 – Alarm delay - 30 secs
T1 & T2 Alarm delay - 10 minutes
LL – Low/Low alarm
O2 – Oxygen sensor
RES – Manual/Auto Reset
TP1 – OV
TP2 + 4~20mA output
mV=mA
TP3 –
TP4 + DPM span
0.5v=F.S.D
TP5 –
TP6 and TP1 sensor supply mV = mA
]
]
4-20mA
Zero Calibration
output adjust
Span
High
Low
Fault
Power
Reset
Test
Gas Alarm Sample Monitor 301 GDS
IN
OUT
Sample
C914