Power distribution system SVS14 1

Power distribution system SVS14
Description
The power distribution system SVS14-10 optimises DC 24 V distribution
on the field level in automated process control, industrial production
and chemical plants. The system holds an integral ammeter (display
25 A) for the total current and offers ten ways for electronic and
thermal-magnetic circuit breakers including group signalling. It allows
protection of transformers, actuators, solenoids, peripheral PLCs,
intelligent terminals etc. on the field level. Particularly for systems with
a great number of sensors/actuators the SVS14 power distribution
system enables a space-saving and cost-effective design of protection
control cabinets.
1
Any load circuit which might be disconnected due to overload or short
circuit generates a single signal which will be summarised in a group
signal directly on the power distribution system and which will be fed
back directly to control.
The SVS14 is a track-mountable system and accommodates 10 electronic
or thermal-magnetic circuit breakers. All terminals (entry line DC +24 V,
GND (-) for self-supply, load outputs L(+) and group signalling are
standard screw terminals.
Features
l
l
l
l
Technical data (Tamb = 25 °C, UB = DC 24 V)
Application
The SVS14 accommodates the following E-T-A types:
Electronic circuit breaker
ESS20-003..
Electronic circuit protector
ESX10-103..
Thermal-magnetic circuit breaker
2210-S211, 3600-P10,
3900-P10
SVS14-10-C22-A01
Systematic integration of power distribution, protection
and signalling functions
Power distribution and selective protection of DC 24 V loads
from a single source
Group signalling pre-wired
Integral Si contact (per way) for free slots, Si circuit can be closed.
Ordering information
Type
SVS14 Power distribution system for ESS20-003, ESX10-103
l Short circuit limited DC 24 V applications
l Max. 25 A cont. load
l Integral group signalling terminals S2 S1, DC 24 V / max. 0.5 A to be protected separately
l Integral Si contact (per way) for free slots, Si circuit can be closed
l Including 2 end pieces X 222 004 01
Version, max. number of circuit breakers
10 10 circuit breakers (F1...F10)
Population option, load output
C22 Fully populated with pcb screw terminals (double level)
(max. 4 mm2, without wire end ferrule)
Integral ammeter
A01 Ammeter 90° to rail (vertical mounting position)
(25 A / class 1.5 % / 48x48)
A02 Ammeter 0° to rail
(horizontal mounting position)
(25 A / class 1.5 % / 48x48)
Special version
Sxxx
SVS14 - 10 -C22 -A01
Ordering example
Modular power distribution system for current limited DC 24 V - applications. In the event of current supply rated higher than 25 A and with battery-buffered supplies please use a 25 A protection with medium delay trip curve (e.g. E-T-A type 4220-T, 2210-T).
Supply
Rated voltage: DC 24 V (18...32 V)
Total current: max. 25 A
DC 24 V (+) terminal block X21 2+/1+
DC 24 V (-) terminal block X21 2-/1-
Terminals:
4-pole screw terminals
cable cross section max. 16 mm2 (with and without wire end ferrule)
Gauge: Ammeter DIN 48, current rating 25 A (moving-iron instrument, 1.5 %)
F ways
Ten ways for circuit breaker, prepared for types
ESS20-003, ESX10-103, 2210-S211, 3600-P10, 3900-P10 SVS14-10 / 10-way / F1… F10 = terminal X1+/X1-…X10+/X10Load outputs per way (F1...F10)
Rated voltage: DC 24 V (18...32 V)
Current: max. 8 A per way1) Number: 1 protected load output L(+) (at way F1 on terminal X1+)
1 minus return load (at way F1 on terminal X1-)
Terminals:
2-pole double level terminal with screw terminal
cable cross section max. 4 mm2 (with and without wire end ferrule)
Signalling
Signal terminal X31 (S2, S1) for group signal
Rated voltage: DC 24 V (18...28 V)
Total current: max. 0.5 A (Caution: use external protection 0.5 A/fast)
S1 External supply possible + DC 24 V for signalling
S2 Signal output, group signal of ways F1…F10
Terminals: 2-pole double level terminal with screw terminal
cable cross section max. 4 mm2 (with and without wire end ferrule)
1) When mounted side-by-side and full population with circuit breakers type ESS20, ESX10,
2210, 3600 and 3900 with current rating 10 A, each device should carry only 80 % of its
rating.
Accessories: external jumper and end piece see page “Accessories“
2015/16
www.e-t-a.de
1 - 77
Power distribution system SVS14
Technical data (Tamb = 25 °C, UB = DC 24 V)
Termination
C22 Supply terminal X21:
screw terminals max. 16 mm2 - with and without wire end ferrule
0.5 - 16 mm2
- stripped length
10 mm
- screw terminals
M4
- tightening torque
1.2 - 1.5 Nm
Load outputs terminal X1… X10:
double level screw terminals - with and without wire end ferrule
- stripped length
- screw terminals
- tightening torque
max. 4 mm2
0.25 - 4 mm2
8 mm
M3
0.5 - 0.6 Nm
Signalling terminal X31:
screw terminals max. 2.5 mm2 - with and without wire end ferrule
0.25 – 2.5 mm2
- stripped length
7 mm
- screw terminals
M3
- tightening torque 0.5 - 0.6 Nm
General data
l
Mounting: DIN rail to EN 50022 - 35 x 7.5
l
Temperature range: 0...50 °C (without condensation)
l
Storage temperature: -20...55 °C (-4...+131 °F)
l
Housing material: Plastic
l
Protection class: Terminals IP20 DIN 40050
Pcb IP00 DIN 40050 (double coating)
l
Insulation voltage: DC 250 V (pcb)
l
Dimensions see drawings
(tolerances to DIN ISO 286 part 1 IT13)
l
Mass: SVS14-10-C22-xxx approx. 600 g
The power distribution system must be installed by qualified
personnel only.
l Only after expert installation may the device be connected to
a power supply.
l The device is only suitable for use in safety extra-low voltage
(DC 24 V).
l Connection to higher or not reliable disconnected voltages may
cause perilous conditions or damages.
l The max. total current of the SVS14 system must not be exceeded.
l In each load circuit the cable cross sections und the current rating
of the protective element have to adjusted to the rating of the
connected load.
l The technical data of the circuit breakers used have to be observed.
l According to the “Machinery Directive 2006/42/EG and
the norm EN 60204-1, Machine Safety” special precautions have
to be taken in machinery (e.g. use of a safety PLC) to prevent inadvertent start-up of machinery parts. In the event of a failure (short
circuit/overload) the load circuit will be disconnected by the circuit
breaker.
l After tripping of the circuit breaker and before reset the trip cause
(short circuit or overload) has to be remedied.
l The international standards (e.g. DIN VDE 0100 for Germany) have
to be observed with installation and selection of cables.
l
Schematic diagram SVS14-10
DC 24 V / Max. 0,5 A
F9
F10
F2
F1
Line (+)
Line (+)
Line (+)
GND (-)
GND (-)
GND (-)
GND (-)
SC
SC
SC
SC
SO
SO
SO
SO
LOAD (L+)
LOAD (L+)
LOAD (L+)
Si 2
Line (+)
LOAD (L+)
Si 1
S2
S1
Si 9
X31
Si 10
1
Reference notes
A
+
X10 -
DC 24 V / 8 A
+
X9 -
X2
DC 24 V / 8 A
+
DC 24 V / 8 A
X1
+
-
DC 24 V / 8 A
DC 24 V / 25 A
X21
1 - 78
212+
1+
www.e-t-a.de
2015/16
Power distribution system SVS14
Dimensions SVS14-10-C22-A01 (vertical mounting position)
64.5
2.54
1
If the power distribution system is not
completely fitted with circuit breakers the
open signal way can be closed with a switch.
DIN rail EN 50022-35x7.5
(not part of the product)
Terminals
current supply (++/--)
screw terminals
16 mm2
max. 25 A
2+
1-
Si
X2
X3
X4
F3
184
7.24
F5
F6
X6
6-
Load outputs
screw terminals
double level 4 mm2
max. 8 A
9.5
.374
X7
X10
S2 S1
GERMANY
Typ: SVS14-10C22-A01 A02
F10
S2 S1
F9
10-
F8
9+
10+
Depending on version
marking (X)
X9
9-
F7
8+
X8
8-
7+
6+
7-
5+
X5
5-
F4
4+
4-
3+
3-
2+
2-
F2
1+
1-
X1
+
F1
X21
-
2-
2-
DC24V/25A
1- 2+ 1+
1+
9.5
.374
108.2
4.26
104
4.09
Group signalling
screw terminals
2.5 mm2
max. 0.5 A
X31
End piece
X 222 004 01
2 pcs are enclosed
Mounting position SVS14-10-C22-A01 (vertical mounting position)
2015/16
www.e-t-a.de
1 - 79
Power distribution system SVS14
70
2.76 ESX10-…
Application example SVS14-10-C22-A01 fitted with ESX10-103
2+
1-
X21
X1
+
X2
X6
X7
X10
S2 S1
GERMANY
Typ: SVS14-10C22-A01 A02
F8
F10
S2 S1
F9
10-
10+
9+
9-
X9
F7
8+
8-
X8
7+
F6
7-
6+
6-
F5
5+
X5
5-
F4
4+
4-
X4
3+
F3
X3
3-
2+
2-
F2
1+
1-
F1
-
Si
2-
2-
1-
DC24V/25A
1+
2+ 1+
64.5
2.54
1
X31
Please order the required population option separately.
1 - 80
www.e-t-a.de
2015/16
Power distribution system SVS14
Dimensions SVS14-10-C22-A02 (horizontal mounting position)
10+
9+
8+
7+
6+
5+
4+
3+
2+
1+
210-
8-
7-
6-
5-
4-
3-
2-
1-
2+
1
1+
1-
64.5
2.54
S2 S1
9-
DIN rail EN 50022-35x7.5
(not supplied with the product)
108.2
4.26
184
7.24
If the power distribution system is not completely fitted with circuit breakers,
the signal way can be closed with a switch.
104
4.09
Si
F10
F9
F8
F7
F6
F5
F4
F3
F2
DC24V/25A
F1
2-
2+
1+
X21
X31
-
S2 S1
X10
End piece
X 222 004 01
2 pcs are enclosed
1-
+
GERMANY
Typ: SVS14-10C22-A01 A02
X9
X8
X7
Depending on version
marking (X)
Group signalling
screw terminals
2.5 mm2
max. 0.5 A
X6
X5
X4
X3
X2
X1
Load outputs
screw terminals
double level 4 mm2
max. 8 A
Terminals
current supply (--/++)
screw terminals
16 mm2
max. 25 A
Mounting position SVS14-10-C22-A02 (horizontal mounting position)
2015/16
www.e-t-a.de
1 - 81
Power distribution system SVS14
Application example empty ways
Accessories
If the power distribution system is not completely fitted with
circuit breakers, the open signal way (S2) to (S1) can be closed
with the integral Si switch (per way), Si-switch change over
to close.
In OK condition (i.e. all circuit breakers plugged in and operating)
the signal way (S2) to (S1) is closed.
top view
Germany
Signalbrücke
Signal loop
SB-S11-P1-01-1-1A
Si
70
2.76
2+
1-
DC24V/25A
Si = open
2-
Si = closed
60
2.36
xxxx
1+
Symbol:
Signalbrücke
Signal loop
www.e-t-a.com
AC 240 V / DC 65 V, 1 A
2
14
12.3
.484
X3
10.3
.406
1
X2
13
X1
+
F2
contact 13+14
bridged
blade terminals
DIN 46244-A 6.3-0.8
End piece
recommended to fix on the DIN rail
X 222 004 01
width 10 mm
S2 S1
GERMANY
Typ: SVS14-10C22-A01 A02
If the power distribution
system is not completely
fitted with circuit breakers,
the open Signal way can
be closed with switch Si.
F9
F8
X10
X9
F7
X8
F6
X7
X6
F5
X5
F4
X4
F3
Si switch = open,
with circuit
breaker fitted
F1
-
X21
F10
1
Jumper
SB-S11-P1-01-1-1A
(for empty ways F1...F10)
optional instead of using the slide Si on the SVS14
X31
Caution: When populating the empty ways, the Si switch
must be re-opened.
2 end pieces are supplied with the product.
This is a metric design and millimeter dimensions take precedence (mm )
inch
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors
and omissions excepted.