Modbus Master/Slave to IEC 60870-5-101
Slave Gateway
5102-MCM3-101S
The MCM-101S modules are the ideal solution for the many applications where Modbus connectivity can be used to integrate an IEC 101 master device into a system. The IEC60870-5-101 Slave gateway is a powerful module designed with Slave support, enabling easy connection to an IEC 101 master device. In combination with the Modbus device support, the module provides a very powerful interface to the many
Modbus devices which are in use in the industrial marketplace today. Applications for the module are found in most industries, especially Manufacturing, Oil
and Gas, Electrical Power and Food Processing.
How to Contact Us: Sales and Support
All ProSoft Technology® products are backed with unlimited technical support. Contact our worldwide
Technical Support team directly by phone or email:
Asia Pacific
+603.7724.2080, [email protected]
Languages spoken include: Chinese, Japanese, English
Europe – Middle East – Africa
+33 (0) 5.34.36.87.20, [email protected]
Languages spoken include: French, English
North America
+1.661.716.5100, [email protected]
Languages spoken include: English, Spanish
Latin America (Sales only)
+1.281.298.9109, [email protected]
Languages spoken include: Spanish, English
Brasil
+55-11.5084.5178, [email protected]
Languages spoken include: Portuguese, English
Modbus Master/Slave to
IEC 60870-5-101 Slave Gateway
5102-MCM3-101S
The ProLinx Modbus Master/Slave to IEC60870-5-101 Slave
Gateway creates a powerful connection between devices on a
Modbus network and an IEC 101 master device. This stand-alone
DIN-rail mounted protocol gateway provides one IEC 101 Slave configurable serial port and three Modbus Master or Slave configurable serial ports.
The Modbus protocol driver supports Master and Slave implementations of the protocol. All Modbus serial ports are individually configurable, providing a very powerful and flexible host or device interface solution.
The IEC 60870-5-101 Slave protocol driver supports Slave implementations of the protocol. The serial port is user-configurable, providing a very powerful and flexible host or device interface solution.
Modbus Master/Slave
The Modbus driver provides extensive support for both the Master and the Slave implementations of the protocol. The serial port(s) on the gateway can be individually configured to support the Modbus protocol (Master or Slave, RTU or ASCII, Baud rate, etc.).
General Parameters – Modbus Protocol
Communication parameters
Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 7 or 8 bits
Parity: None, Even, Odd
RTS Timing delays: 0 to 65535 ms
Error Checking
Floating Point
Function Codes
RTU mode (binary) with CRC-16
ASCII mode with LRC error checking
Floating point data movement supported, including configurable support for Enron implementation
1: Read Output Status
2: Read Input Status
3: Read Multiple Data Registers
4: Read Input Registers
5: Write Single Bit
6: Write Single Data Register
15: Write Multiple Bits
16: Write Multiple Data Register
Modbus Master
Command List
Polling of command list
Up to 100 command per master port, each fully configurable for function, slave address, register to/from addressing and word/bit count.
Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled.
Modbus Slave
Node address 1 to 247 – software selectable
IEC 60870-5-101 Slave
The 101S module acts as an input/output module between the
IEC 60870-5-101 and other protocols and networks, as well as several proprietary interfaces.
General specifications include:
• User-definable module memory usage
• Storage of IEC time used in module is available in the database
• Protocol implementation conforms to the IEC 60870-5-101 specification with fully configurable parameters
• Priority Queues
• Invalid Bit Monitoring
• Supports Balanced and Unbalanced Mode
• Supports CP24 and CP56 time formats for events
• Event generation configurable per point or data type
General Parameters
Communication parameters
Baud Rate: 110 to 19,200 baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd
RTS Timing Delays: 0 to 65535 ms
IEC 60870-5-101 Slave
Configurable Parameters Data link address length
Common Address of ASDU length
Inform. Object Address length
Select/Operate Timeout
Event Scan delay
Use Balanced Mode
Short Pulse Time
Long Pulse Time
Time DB Offset
General Specifications
The ProLinx Communication Modules provide connectivity for two or more dissimilar network types. The modules, encased in sturdy extruded aluminum, are stand-alone DIN-rail mounted protocol gateways, providing communication between many of the most widely used protocols in industrial automation today.
Hardware Specifications
Specification Description
Power Supply 24 VDC nominal
18 to 36 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade
Current Load 500 mA max@ 24 VDC
Operating Temperature –20 to 50°C (–4 to 122°F)
Storage Temperature
Relative Humidity
–40 to 85°C (–40 to 185°F)
5 to 95% (non-condensing)
Dimensions Standard: 5.20H x 2.07W x 4.52D in.
(13.2cmH x 5.25cmW x 11.48cmD)
Extended: 5.20H x 2.73W x 4.52D in.
(13.2cmH x 6.934cmW x 11.48cmD)
Specification Description
LED Indicators
Configuration Serial Port
Ethernet Port (Ethernet modules only)
Application Serial Ports
Serial Port Isolation
Shipped with Each Unit
Power and Module Status
Application Status
Serial Port Activity LED
Serial Activity and Error LED Status
DB-9M RS-232 only
No hardware handshaking
RJ45 Connector
Link and Activity LED indicators
RS-232/422/485
RS-232 handshaking configurable
RS-422/485 screw termination included
2500V RMS port signal isolation per UL
1577
3000V DC min. port to ground and port to logic power isolation
Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal
Adaptor (1 or 4, depending on ports)
ProSoft Configuration Builder
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files customized to meet your application needs. PCB is not only a powerful solution for new configuration files, but also allows you to import information from previously installed (known working) configurations to new projects.
Additional Products
ProSoft Technology offers a full complement of hardware and software solutions for a wide variety of industrial communication platforms.
Visit our web site at http://www.prosoft-technology.com for a complete list of products.
Ordering Information
To order this product, please use the following:
5102-MCM3-101S Modbus Master/Slave to IEC 60870-5-101
Slave Gateway
To place an order, please contact your local ProSoft Technology distributor. For a list of ProSoft distributors near you, go to http://www.prosoft-technology.com
Distributors:
Place your order by email or fax to:
North American / Latin American / Asia Pacific [email protected], fax to +1 661.716.5101
Europe [email protected], fax to +33 (0) 5.61.78.40.52
Copyright © ProSoft Technology, Inc. 2000 - 2007. All Rights Reserved.
May 03, 2007
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project