8 / 10 / 16 / 20 HP Systems

AIR COOLED SPLIT TYPE AIR CONDITIONERS
8 / 10HP
16 / 20HP
8 / 10 / 16 / 20 HP Systems
Simple and Effective Control
Interactive "A-Control" makes system management easier than ever. Features like connectivity
to building air conditioning systems, quick, precise selection of indoor unit functions and a selfdiagnostic system for indoor/outdoor units reflect Mitsubishi Electric's promise to provide optimum comfort and performance.
Compact, Functional System
Advanced component and system design design technologies have been introduced to produce
some of the smallest and lightest rooftop air conditioning systems in the market.
FEATURES
Highly Efficient operation
Labor Saving Installation
The EER (Energy Efficiency Ratio) on These models is
greatly improved by revised design specifications and
by being manufactured stringently to Mitsubishi Electric high quality standards.
Because of the single unit configuration, all refrigeration work can be omitted.
The unit operation can commence immediately after
connection to the power supply, drain piping, ducting
and control system.
Minimum Floor Space
The PRH series feature a compact design and has been
succeeded in reducing more floor space.
8/10HP
16/20HP
250
Confort Cooling and Heating
The PRH series are designed to provide effective cooling and heating comfort with wide range of outside
temperature condition.
250
840mm
1,932mm
450
450
2
2.21m
5.85m
2
Cooling
24
15
-5
43
Outdoor air temperature (∞CDB)
TYPICAL INSTALLATION EXANPLE
PRH
Indoor air temperature (∞CDB)
Indoor air temperature (∞CWB)
450
Heating
27
15
–12
18
Outdoor air temperature (∞CWB)
Enhanced System Control and Operation Ease
Flexible Function Setting from Remote Controllers
Remote Controllers can now be used for the selection and setting of functions such as fan speed, air outlets, vane setting etc. which were previously set from the indoor unit base board. Setting canges can also be made very easily at the
installation stage.
Room temperature display
Set temperature display
Operation lamp
Operation mode switch
Filter sign reset switch
Test run switch
Check switch
Ventilation mode setting switch
(Control linked operation with Lossnay)
Wired remote controller
(PL/PEHD/PEAD/PC/PS Series)
Full System Diagnosis
Building Management
System Compatibility
"A-Control" interactivity between indoor and outdoor
units enables the system's self-diagnostic function to
be used for examining the entire system; even abnormalities in the outdoor unit will be shown on the remote controller display. Improvements in display details make more accurate and timely responses for
maintenance and repair possible.
"A-Control" technology offers compatibility so that systems of the series can operate as part of the MELANS
building air conditioning management system. Once
connected by a special adapter (optional), the systems
respond to commands given from the MELANS control
center. Remote controller can also be used for general
system control.
Remote display alternately shows error code and corresponding
model number
LED
Error code
Error deflection
article
CLOCK
ERROR CODE
OA UNIT ADDRESS
Other Functions
•Non-polarized, dual-core remote control wiring
•Control of up to 16 units
•Use of 2 remote controllers per group
•Independent operation of each unit
•Built-in thermostat
M-NET (MELANS) connection
CHECK MODE
NOT AVAILABLE
Self diagnostic target unit address
Man machine
interface
(G-50A)
Alternate
display
Corresponding
model number
Power supply unit
PAC-SC50KUA
(optional)
City Multi Y
outdoor unit
CLOCK
ERROR CODE
OA UNIT ADDRESS
CHECK MODE
NOT AVAILABLE
Indoor unit
Local remote
controller
Adopter
Rooftop unit
Indoor unit
Local remote
controller
Indoor unit
SPECIFICATIONS
Specifications of air-source heat pump type packaged air conditioner
(Rooftop unit)
Model name
PRH-P8MYA
Mode
Capacity
PRH-P10MYA
PRH-P16MYA
PRH-P20MYA
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
kW
20.9
23.7
26.0
30.5
41.8
47.4
52.0
Heating
61.0
kcal/h
18,000
19,000
22,400
26,200
36,000
40,800
44,800
52,400
Btu/h
71,430
75,400
88,890
104,000
142,860
150,800
177,780
208,000
pending
pending
pending
R407C
Refrigerant
3N~380/400/415V 50Hz
Power source
ElectricalPower consumption
characteristics Operating current
kW
A
Remote controller temperature setting range
8.12
8.02
10.22
9.82
14.7
14.5
18.8
18.2
pending
pending
pending
pending
19 C to 30 C
17 C to 28 C
19 C to 30 C
17 C to 28 C
19 C to 30 C
17 C to 28 C
19 C to 30 C
17 C to 28 C
Convertible(Side flow<factory setting> or top flow)
Indoor-side air flow direction
Sirrocco fan ✕ 2
Indoor-side fan Type ✕ Quantity
Air flow rate
External static pressure
CMM
70
90
140
180
Pa
100
100
200
200
Three-phase induction motor
Motor type
Motor output
kW
1.1
1.5
Propeller fan ✕ 1
Outdoor-side fan Type ✕ Quantity
CMM
185 ✕ 2
Three-phase induction motor
kW
0.38
0.38 ✕ 2
Outdoor-side heat exchanger type
Cross fin
Compressor
Hermetic
Type
Motor output
kW
5.5
7.5
kW
0.05 (240V)
0.05 (240V) ✕ 2
mm
1,715✕ 2,000 ✕ 926
1,735✕ 2,000 ✕ 2,130
Field supplied
Air filter
R1
Drain pipe Thread
Noise level
dB(A)
Net weight
kg
Protection devices
7.5 ✕ 2
Polyester powder (MUNSELL 5Y8/1)
External finish
External dimension H ✕ W ✕ D
5.5 ✕ 2
FVC68D(ether oil)
Oil type
Crankcase heater
3.7
Propeller fan ✕ 2
185
Motor type
Motor output
2.2
Cross fin
Indoor-side heat exchanger type
Air flow rate
pending
59
60
62
63
407
412
pending
pending
High pressure switch , Low pressure switch , fuse
Over current relay(compressor , indoor-side fan motor)
inner thermal switch in outdoor-side fan motor
Note 1. Cooling and Hetaing capacity indicates the maximum value at operation under the following condition.
Cooling Indoor : 27 CDB/19 CWB Outdoor : 35 CDB
Heating Indoor : 20 CDB
Outdoor : 7 CDB/6 CWB
2. The operating noise measuring point is 1m from the bottom of unit (1m from the front of the unit) in an
anechoic room. (Noise level is A-scale value)
3. Refrigerant charge volumes are factory charged.
4. The range of working voltage is with in ±10% voltage of power supply.
5. Specification subject to change without notice.
EXTERNAL DIMENSIONS
• ModelsPRH-P8MYA/P10MYA
<Accessory>
• Conduit mounting plate
(Painted the same color as the unit body)
ø 27..................................................1pc.
ø 34..................................................1pc.
ø 40 and ø 27.................................1pc.
• Tapping screw 4✕12........................4pcs.
2000
1932
68
10
800
800
144
Note 1. It is possible to change to ø 27 or
ø 34 by selecting the conduit
mounting plate.
2. The hole size can be selected to
ø 27 or ø 34 or ø 40 by selecting
the conduit mounting plate.
3. These dimension of supply air and
return air duct flange are the same.
6-14✕20 holes
<For mounting
anchor bolt M8>
[Field supply]
Top view
10
Supply air
duct flange
Air outlet
Service panel
230
15 100 100 15
18- ø 3 Holes
86
15
Drain R1
23
46
36.5
135
840
880
910
961
748
5✕135Pitch= 675
15
46
36.5
Note 3
386
Supply
air
43
10
1569
1579
X
X
Air inlet
ø 25.4 Knockout hole
<Right side hole for
the controller wiring>
Knockout hole
Return air
duct flange
ø 27 hole
<Front side hole for
the controller wiring>
(Accessory plate)
50
121
585
Y
ø 25.4 Knockout hole
<Bottom side hole for
the controller wiring>
495
611
Note 1
ø 38.1 Knockout hole
<Bottom side hole for
the power supply wiring>
X-X
84
149
165
Y
155
60
Drain R1
6- ø 3.9 holes
(Both side)
Left side view
69
Fresh air
intake
(Both side)
105
95
60
43
84
60
185
350
185
270
250
130
Return
air
Air inlet
1715
995
7✕130Pitch= 910
28- ø 3 Holes
6
5
Y-Y
Front view
829
794
1399
Note 2
ø 40 hole
<Front side hole for
the power supply wiring>
(Accessory plate)
Service panel
65
ø 38.1 Knockout hole
<Right side hole for
the power supply wiring>
Right side view
EXTERNAL DIMENSIONS
• ModelsPRH-P16MYA/P20MYA
2000
1932
800
144
<Accessory>
• Conduit mounting plate
(Painted the same color as the unit body)
ø 27..................................................1pc.
ø 34..................................................1pc.
ø 40 and ø 27.................................1pc.
• Tapping screw 4✕12........................4pcs.
10
24-ø3 Holes
800
15
68
150
8✕150Pitch=1200
56
10
38-ø3 Holes
2200
2130
2170
Supply air cover
for top flow
150 150
Supply air
duct flange
Note
1. It is possible to change to ø 27 or
ø 34 by selecting the conduit
mounting plate.
2. The hole size can be selected to
ø 27 or ø 34 or ø 40 by selecting
the conduit mounting plate.
3. Dimension of supply air and return
air duct flange are shown below.
67
(434)
67
(1312)
10
56
150
13✕150Pitch=1950
44
10
(730)
23
Drain R1
Top view
6-14✕20 holes
<For mounting
anchor bolt M10>
[Field supply]
65
Return air
duct flange
15
65
(2038)
4✕150Pitch=600
150
44
Supply
air
Air
inlet
Drain
Fresh air
R1
intake
(Both side)
60
165
5
6
5
Y
155
X-X
585
50
1030
50
585
6
495
611
Note 1
ø38.1 Knockout hole
<Bottom side hole for
the pwoer supply wiring>
Y-Y
829
X
Service panel
794
1549
Front view
Y
ø25.4 Knockout hole
<Bottom side hole for
the controller wiring>
Knockout hole
60
X
Return air
duct flange
(Note 3)
6-ø3.9 holes ø27 hole
(Both side) <Front side hole for
the controller wiring>
(Accessory plate)
Left side view
Air
inlet
1661
1671
89
80
105
115
730
155 155
290
200
180
Air
inlet
Note 2
ø40 hole
<Front side hole for
the power supply wiring>
(Accessory plate)
104
Return
air
1735
46
Air outlet
Service panel
202
2038
121
46
Air outlet
Supply air
duct flange
(Note 3)
525
104
169
1312
434
293
65
ø25.4 Knockout hole
<Right side hole for
the controller wiring>
ø38.1 Knockout hole
<Right side hole for
the power supply wiring>
Right side view
NEXT GENERATION CONTROLLER G-50A
Up to 50 units of packaged air conditioners can freely be
monitored and operated!
Furthermore, it has enabled the Monitoring and Operation
Via a Web Browser on a Personal Computer connected to
it using a LAN or telephone line!
First in the industry
With Web Server
Functions!
• Simple and Flexible
This new generation controller is suitable for small to large systems
with simple to complex functions available.
• Web Browser
Enables monitoring and operation of air conditioning units using a
PC with Microsoft Internet Explorer.
• Remote Access
Allows users to remotely monitor and operate the air conditioning
units using a PC connected to a telephone line.
• Auto Alarm
In the case of any malfunction, necessary information will be sent to
a mobile phone and/or personal computer by e-mail.
• Easy to Upgrade
Various new functions will be introduced gradually and can easily
be down loaded into any existing G-50A.
Example: Energy Monitoring
Demand Control
Annual Schedule
Example of display icons (air conditioner icons)
Operation
In timer operation
Stop
Lossnay on
Occurrence of
abnormality
Under energy-saving
control
Operation/
Occurrence of a filter sign
System Structure
Remote monitoring via a
Web browser
Web browser
G-50
M-NET
Public telephone
line
Provider
Router
Ethernet
City Multi
G-50
Provider
Adopter
Rooftop unit