FCQ-D
4-way Blow Ceiling
Mounted Cassette
(950mm x 950mm)
Split
Sky Air
air conditioning systems
technical data
Split - Sky Air
ISO14001 assures an effective environmental
management system in order to help protect
human health and the environment from the potential
impact of our activities, products and services and to
assist in maintaining and improving the quality of
the environment
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.
Daikin units comply with the European
regulations that guarantee the safety of
the product.
Daikin Europe N.V. participates in the Eurovent Certification
Programme for Air Conditioners (AC), Liquid Chilling Packages
(LCP) and Fan Coil Units (FC); the certified data of certified
models are listed in the Eurovent Directory.
Zandvoordestraat 300
B - 8400 Ostend Belgium
www.daikineurope.com
EEDE05-1/3 • 05/2005
Prepared in Belgium by Goekint Graphics
Specifications are subject to change without prior notice.
• Indoor Units • R-410A • FCQ-D
TABLE OF CONTENTS
FCQ-D
1
2
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nominal capacity and power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3
4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensional drawing
.........................................................6
5
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8
Air flow pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• Split Sky Air • Indoor Units
1
• Indoor Units • R-410A • FCQ-D
r at o 0D i o 1- ld 4Q npC- R1
ISF
Features
20
1
•
Compact & stylish
•
•
Ideal for shops, restaurants or offices requiring maximum floor space for
furniture, decorations and fittings
The wired remote control provides you with a schedule timer, enabling
to program the air conditioning daily or weekly.
•
•
Fits flush into each ceiling
The optional remote ON/OFF enables you to start/stop the air
conditioning from a mobile phone via a telephone remote control (field
supply).
•
Extremely quiet in operation
•
•
Air can be discharged in any of 4 directions
The optional forced OFF enables you to switch off the unit
automatically. E.g. when a window is opened, the unit switches off.
•
Possibility to shut 1 or 2 flaps for easy installation in corners or to use 1
or 2 branches
•
•
Air flow distribution for ceiling heights up to 4.2m without loss of
capacity.
•
Daikin remote controls give you easy control at your fingertips.
The ’home leave’ operation button prevents large temperature
differences by continuously operating at a minimum (heating mode) or
maximum (cooling mode) preset level while you’re out or sleeping. It
also allows the indoor temperature to return quickly to your favourite
comfort level.
(2 steps)
2
(heat pump)
(optional)
(optional)
(twin
application
only)
• Split Sky Air • Indoor Units
(standard)
(optional)
• Indoor Units • R-410A • FCQ-D
2
Specifications
20
2
2-1 NOMINAL CAPACITY AND POWER INPUT
For indoor units only:
INDOOR UNITS
NOMINAL INPUT
FCQ71DV3B
FCQ100DV3B
FCQ125DV3B
FCQ140DV3B
Cooling
kW
-
-
-
-
Heating
kW
-
-
-
-
For combination indoor + outdoor units (air cooled):
INDOOR UNITS
FCQ71DV3B
FCQ100DV3B
FCQ125DV3B
FCQ140DV3B
OUTDOOR UNITS
RZQ71B8V3B
RZQ100B8V3B/B7W1B
RZQ125B7W1B
RZQ140B7W1B
Nominal capacity Cooling
nominal
kW
3.2~7.1~8.0
5.0~10.0~11.2
5.7~12.5~14.0
6.2~14.0~15.4
Heating
nominal
kW
3.5~8.0~9.0
5.1~11.2~12.8
6.0~14.0~16.2
6.2~16.0~18.0
Cooling
nominal
kW
1.98
2.44
3.54
4.56
Heating
nominal
kW
1.97
2.56
3.59
4.52
EER
3.59
4.10
3.53
-
COP
4.06
4.375
3.90
-
Nominal input
Energy label
Annual energy
consumption
Cooling
A
A
A
-
Heating
A
A
A
-
990
1,220
1,770
-
FCQ140DV3B
Cooling
kWh
2-2 TECHNICAL SPECIFICATIONS
Dimensions
Unit
FCQ71DV3B
FCQ100DV3B
FCQ125DV3B
Height
mm
246
288
288
288
Width
mm
840
840
840
840
Depth
Weight
Machine Weight
Heat Exchanger
Dimensions
mm
840
840
840
840
kg
24.0
28.0
28.0
28.0
2
2
2
2
Fin Pitch
mm
1.20
1.20
1.20
1.20
Face Area
m2
0.454
0.544
0.544
0.544
10
12
12
12
Nr of Rows
Nr of Stages
Tube type
Fin
Fan
Type
Air Flow Rate
Cooling
Heating
Fan
Motor
Hi-XSS (7)
Type
Cross fin coil (Multi louver fins and Hi-XSS tubes)
Turbo fan
High
m3/min
19.0
30.0
30.0
30.0
Low
m3/min
14.0
21.0
24.0
25.0
High
m3/min
19.0
30.0
30.0
30.0
Low
m3/min
14.0
21.0
24.0
25.0
QTS46F15M
QTS46E17M
QTS46E17M
QTS46E17M
30
120
120
120
Model
Output
(high)
Cooling
Sound Power
Sound Pressure
Heating
Sound Power
Sound Pressure
Refrigerant
Type
Piping
connections
Liquid (OD)
W
High
dBA
50.0
58.0
58.0
58.0
Low
dBA
44.0
48.0
51.0
53.0
High
dBA
34.0
43.0
43.0
43.0
Low
dBA
28.0
33.0
36.0
38.0
High
dBA
50.0
58.0
58.0
58.0
Low
dBA
44.0
48.0
51.0
53.0
High
dBA
34.0
43.0
43.0
43.0
Low
dBA
28.0
33.0
36.0
38.0
9.5
9.5
15.9
15.9
R-410A
Type
Flare connection
Diameter
(OD)
Gas
Drain
mm
9.5
9.5
Diameter
(OD)
mm
15.9
15.9
Diameter
(OD)
mm
Type
Flare connection
• Split Sky Air • Indoor Units
I.D. 25/O.D. 32
3
• Indoor Units • R-410A • FCQ-D
2-2 TECHNICAL SPECIFICATIONS
FCQ71DV3B
FCQ100DV3B
Decoration Panel Model
Colour
Dimensions
20
FCQ140DV3B
White
H
mm
45
45
45
45
W
mm
950
950
950
950
mm
950
950
950
950
kg
5.5
5.5
5.5
5.5
D
2
FCQ125DV3B
BYCP125DJW1
Weight
Air Filter
Resin net with mold resistance
___
Safety Devices
Low pressure switch
High pressure switch
Fuse
2-3 ELECTRICAL SPECIFICATIONS
Power Supply
FCQ71DV3B
FCQ100DV3B
FCQ125DV3B
FCQ140DV3B
Name
V3
V3
V3
V3
Phase
1
1
1
1
Frequency
Hz
50
50
50
50
Voltage
V
230
230
230
230
NOTES
4
1
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m,
level difference : 0m.
2
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m,
level difference : 0m.
3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4
In case of drain piping for the outdoor unit, a drain piping kit (option) is needed.
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-D
3
Options
20
Item
Model
FCQ71D
Decoration panel
Colorimetric method
KAFP556D80
KAFP556D160
High efficiency filter 90%
Colorimetric method
KAFP557D80
KAFP557D160
Replacement high effiency filter 65%
Colorimetric method
KAFP552H80
KAFP552H160
Replacement high effiency filter 90%
Colorimetric method
KAFP553H80
3
KAFP553H160
Filter chamber
KDDFP55D160
Long life filter
KAFJ551C160
Ultra long-life filter
KAFP55D160
Chamber type
KAFJ55K160H
Without T-shape and fan
KDDP55D160
With T-shape, without fan
KDDP55D16OK
Direct installation type
Branch duct chamber
KDDJ55X160
KDP55D80
Insulation kit for high humidity
Remote control
FCQ140D
KDBP55H160WA
High efficiency filter 65%
Replacement ultra long-life filter
Fresh air intake kit
FCQ125D
BYCP125DJW1
Panel spacer
Filter related
FCQ100D
KDP55D160
KDT-55D80
Infrared
KDT-55D160
BRC7E51W
Wired
BRC1D527
Central remote control
DCS302C51
Unified ON/OFF control
DCS301B51
Schedule timer
DST301B51
Adapter for wiring *1
KRP1B59
Wiring adapter for electrical appendices *1
KRP4A53
Installation box for adapter PCB
KRP1D98
*1 Installation box for adapter PCB (KRP1D98) is necessary
3D048828
• Split Sky Air • Indoor Units
5
• Indoor Units • R-410A • FCQ-D
4
Dimensional drawing
4-1
Dimensional drawing
20
4
FCQ71D
12-M4 Hole
860∼910 (Ceiling opening) (Note 4)
680 Suspension position
300 or less
Note 2
780 (Suspension position)
860∼890 (Ceiling opening) (Note 4)
Drain connection
side
Pipe connection side
Branch duct connection
B Arrow view
4-M4 Hole
12-M4 Hole
Branch duct connection
Adjustable(0∼550)
C Arrow view
12-M4 Hole
Outdoor air intake (direct connection)
D Arrow view
Branch duct
connection
12-M4 Hole
Required space
1500 mm or more *
1500 mm or more *
Decoration panel
BYCP125DJW1
White 10Y 9/0.5
Note:
1. Sticking location for manufacture’ s label
Manufacture’ s label for indoor unit: on the bell mouth inside suction
grille.
Manufacture’ s label for decoration panel: on the inner frame inside
suction grille.
2. In case of using an infrared remote control, this position will be a signal
receiver.
Refer to the drawing of infrared remote control in detail
3. When it may exceed 30°C and RH 80% in the ceiling or fresh air is
inducted into the ceiling, an additional insulation (Thickness 10mm or
more of glasswool or polyethylene form) is required.
4. Though the installation is acceptable up to maximum of 910mm
square ceiling opening, keep the clearance of 35mm or less between
the main unit and the ceiling opening so that the panel overlap
allowance can be ensured.
1
2
3
4
5
6
7
8
1500 mm or more *
For height installation
35 or less
(Note 4)
Branch duct connection
1500 or more
35 or less
(Required space)
Suspension bolt
From the floor side 2500 or more
1500 mm or more *
* When the discharge grill is closed, the required
space is 200mm or more
Liquid pipe connection J9.5 Flare connection
Gas pipe connectionJ15.9 Flare connection
Drain pipe connection VP25 (O.D. J 32)
Power supply connection / wiring / remote control connection
Air outlet
Air suction grille
Corner decoration cover
3D033593A
Drain hose (option) O.D. J32 (outlet)
FCQ100∼140D
Note 2
300 or less
12-M4 Hole
860∼910 (Ceiling opening) (Note 4)
680 Suspension position
780 (Suspension position)
Pipe connection side
860∼890 (Ceiling opening) (Note 4)
Drain connection
side
Branch duct connection
B Arrow view
4-M4 Hole
12-M4 Hole
Adjustable(0∼550)
Branch duct connection
12-M4 Hole
C Arrow view
Branch duct
connection
Outdoor air intake (direct connection)
D Arrow view
12-M4 Hole
Required space
1500 mm or more *
1500 mm or more *
(Required space)
35 or less
(Note 4)
Branch duct connection
Decoration panel
BYCP125DJW1
White 10Y 9/0.5
Note:
1. Sticking location for manufacture’ s label
Manufacture’ s label for indoor unit: on the bell mouth inside suction
grille.
Manufacture’ s label for decoration panel: on the inner frame inside
suction grille.
2. In case of using an infrared remote control, this position will be a signal
receiver.
Refer to the drawing of infrared remote control in detail
6
3. When it may exceed 30°C and RH 80% in the ceiling or fresh air is
inducted into the ceiling, an additional insulation (Thickness 10mm or
more of glasswool or polyethylene form) is required.
4. Though the installation is acceptable up to maximum of 910mm
square ceiling opening, keep the clearance of 35mm or less between
the main unit and the ceiling opening so that the panel overlap
allowance can be ensured.
• Split Sky Air • Indoor Units
1
2
3
4
5
6
7
8
From the floor side 2500 or more
For height installation
35 or less
Suspension bolt
1500 or more
1500 mm or more *
1500 mm or more *
* When the discharge grill is closed, the required
space is 200mm or more
Liquid pipe connection J9.5 Flare connection
Gas pipe connectionJ15.9 Flare connection
Drain pipe connection VP25 (O.D. J 32)
Power supply connection / wiring / remote control connection
Air outlet
Air suction grille
Corner decoration cover
3D048825
Drain hose (option) O.D. J32 (outlet)
• Indoor Units • R-410A • FCQ-D
5
Piping diagram
20
5
FCQ-D
Heat exchanger
Model
FCQ71-100-125-140DV3B
A
J9.52
B
J15.90
Field piping J A C1220T-O
To outdoor unit
Field piping J B C1220T-O
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
4D037995D
• Split Sky Air • Indoor Units
7
• Indoor Units • R-410A • FCQ-D
6
Wiring diagram
6-1
Wiring diagram
20
6
FCQ71-140D
Receiver / display unit
Notes
To outdoor unit
Note 5
Note 5
Note 2
Central remote
control
HO5VV-U4G2.5
Wired remote control
Simultaneous operation system
Indoor unit
(master)
Indoor unit
(slave)
To outdoor unit
1. In case using central remote control, connect it to the unit
in accordance with the attached installation manual.
2. Remote controller model varies according to the
combination system, confirm engineering data and
catalogs, etc. before connecting.
3. Confirm the method of setting the selector switch (SS1,
SS2) by installation manual and engeneering materials,
etc.
4. Ground the shield of the remote controller cord to the
indoor unit (in case of using shield wire). See technical
data and catalogues before connecting.
g Field wiring D Terminal
F
: Connector
h
: Wire clamp
b
: Protective earth (screw)
Colours
BLK: Black / WHT: White / RED: Red / YLW: Yellow
Switch box
(Indoor unit)
Remote control
A1P
A2P
A3P
HAP
KPR
M1F
M1P
M1S
R1T
R2T
6-2
Printed circuit board
(Power supply)
Printed circuit board
(Control)
Printed circuit board
(Humidity sensor unit)
Light emitting diode (service monitor green)
Magnetic relay (M1P)
Motor (indoor fan)
Motor (drain pump)
Motor (swing flap)
Thermistor (air)
Thermistor (coil)
S1L
Float switch
SS1
Selector switch (emergency)
X1M
Terminal strip (power)
X2M
Terminal strip (control)
PC
Power circuit
RC
Signal receiver circuit
TC
Signal transmission circuit
Z1C
Noise filter
Z2C
Noise filter
Wired remote control
R1T
Thermistor (air)
SS1
Selector switch (main/sub)
Receiver / display unit (attached to infrared remote control)
A4P,A5P Printed circuit board
BS1
Push button (on/off)
H1P
Light emitting diode (on-red)
H2P
Light emitting diode (timer-green)
H3P
Light emitting diode (filter sign-red)
H4P
Light emitting diode (defrost-orange)
SS1
Selector switch (main/sub)
SS2
Selector switch (wireless address set)
Connector for optional parts
X33A
Connector (adapter for wiring)
X35A
Connector (group control adapter)
3D048786
External connection diagram
V3, Model
Power supply
1∼50Hz
230V
W1, Model
Power supply
1∼50Hz
220V-240V
Main switch
Main switch
Fuse
Fuse
H05VV-U4G
NOTES
1
2
3
4
5
6
7
8
9
8
Line voltage wiring
Control circuit wiring
All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.
Use copper conductors only.
See wiring diagrams for details.
Install fuse and mainswitch for safety.
All field wiring and components must be provided by a licensed electrician.
The unit shall be grounded in compliance with the applicable local and national codes.
Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific
installation.
Never share a common power supply with other equipment.
• Split Sky Air • Indoor Units
4D048881
• Indoor Units • R-410A • FCQ-D
7
Sound data
7-1
Sound pressure spectrum
20
7
FCQ100D
High
Low
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
FCQ71D
approximate threshold
hearing for continuous
noise
4D049024
NOTES
1
2
3
Octave band center frequency (Hz)
4D049025
NOTES
Location of microphone
1
2
3
High
Low
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
Octave band sound pressure level
dB:(0dB = 0.0002 μ bar)
3
Location of microphone
FCQ140D
approximate threshold
hearing for continuous
noise
1
2
Octave band center frequency (Hz)
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
FCQ125D
NOTES
Low
approximate threshold
hearing for continuous
noise
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
4D049026
High
High
Low
approximate threshold
hearing for continuous
noise
4D049027
Octave band center frequency (Hz)
NOTES
Location of microphone
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
• Split Sky Air • Indoor Units
1
2
3
Octave band center frequency (Hz)
Location of microphone
Measurement was taken in an anechoic room.
Operation conditions:
Power source = 230V, 50Hz
Cooling = Return air temperature: 27°C DB, 19°C WB
Outdoor temperature: 35°C DB, 24°C WB
Heating = Return air temperature: 20°C DB, 15°C WB
Outdoor temperature: 7°C DB, 6°C WB
Microphone
4 direction discharge
Operation noise differs with operation and ambient conditions.
9
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ71D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
FCQ71D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049080
10
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ100D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
FCQ100D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049084
• Split Sky Air • Indoor Units
11
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ125D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
FCQ125D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049082
12
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ140D
Cooling - air velocity distribution
4-way discharge air flow direction: horizontal
FCQ140D
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D049086
• Split Sky Air • Indoor Units
13
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ71D
Heating - air velocity distribution
4-way discharge, air flow direction: down
FCQ71D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049081
14
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ100D
Heating - air velocity distribution
4-way discharge, air flow direction: down
FCQ100D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049085
• Split Sky Air • Indoor Units
15
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ125D
Heating - air velocity distribution
4-way discharge, air flow direction: down
FCQ125D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049083
16
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-D
8
Air flow pattern
20
8
FCQ140D
Heating - air velocity distribution
4-way discharge, air flow direction: down
FCQ140D
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D049087
• Split Sky Air • Indoor Units
17