Smart-UPS
APC Smart-UPS 2200VA RM 3U 120V/230V In
120V Out
APC Smart-UPS, 1600 Watts / 2200
VA,Input 120V, 230V / Output 120V, Interface
Port DB-9 RS-232, SmartSlot, Rack Height 3 U
Includes: CD with software, Country-specific
detachable power cord, Smart UPS signalling
RS-232 cable, User Manual
Standard Lead Time: Usually Ships within 4
Weeks
Smart-UPS Features & Benefits
Availability
Boost and Trim
Automatic Voltage
Regulation (AVR)
Intelligent Battery
Management
Power conditioning
Temperaturecompensated battery
charging
Automatic restart of
loads after UPS
shutdown
Automatic self-test
Gives higher application availability by correcting low and high voltage
conditions without using the battery.
Maximizes battery performance, life, and reliability through intelligent,
precision charging.
Protects connected loads from surges, spikes, lightning, and other power
disturbances.
Prolongs battery life by regulating the charge voltage according to battery
temperature.
Automatically starts up the connected equipment upon the return of utility
power.
Periodic battery self-test ensures early detection of a battery that needs to be
replaced.
Cold-start capable
Provides temporary battery power when the utility power is out.
Disconnected battery Warns when a battery is not available to provide backup power.
notification
Generator Compatible Ensures clean, uninterrupted power to protected equipment when generator
power is used.
Manageability
Network manageable Provides remote management of the UPS over the network.
SmartSlot
Customize UPS capabilities with management cards.
Audible Alarms
Actively let you know if the unit is on battery, if the battery is low or if there
is an overload condition.
LED status indicators Quickly understand unit and power status with visual indicators.
Serial Connectivity
Provides management of the UPS via a serial port.
USB Connectivity
Provides management of the UPS via a USB port (not available on all
models).
Disconnected battery Warns when a battery is not available to provide backup power.
notification
InfraStruXure
Enables centralized management via the APC InfraStruXure® Manager.
Manager Compatible
Serviceability
User-replaceable
batteries
Hot-swappable
batteries
Predictive failure
notification
Resettable circuit
Increases availability by allowing a trained user to perform upgrades and
replacements of the batteries reducing Mean Time to Repair (MTTR)
Ensures clean, uninterrupted power to protected equipment while batteries
are being replaced
Provides early-warning fault analysis ensuring proactive component
replacement.
Enables a quick recovery from overload events.
breakers
Adaptability
Adjustable voltagetransfer points
Adjustable voltage
sensitivity
Field-replaceable
power distribution
panel
Maximizes useful battery life by widening the input voltage window or
tightening the output voltage regulation.
Provides the ability to adapt the UPS for optimal performance in specific
power environments or generator applications.
Ensures compatibility with equipment that has different plug types.
Safety
Safety-agency
approved
Ensures the product has been tested and approved to work safely with the
connected service provider equipment and within the specified environment.
UL, FCC, CE, C-Tick approvals.
Output
Output Power Capacity
1600 Watts / 2200 VA
Max Configurable Power
1600 Watts / 2200 VA
Nominal Output Voltage
120V
Output Voltage Distortion
Less than 5% at full load
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
Crest Factor
up to 5 : 1
Waveform Type
Sine wave
Output Connections
(8) NEMA 5-15R
Input
Nominal Input Voltage
120V,230V
Input Frequency
50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
NEMA 5-20P
Schuko CEE 7 / EU1-16P
British BS1363A
Italian CEI 23-16
Cord Length
1.83 meters
Input voltage range for main
operations
--V
Input voltage adjustable range for --V
mains operation
Batteries & Runtime
Battery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time
3 hour(s)
Replacement Battery
RBC12
RBC™ Quantity
1
Typical Backup Time
at Half Load
24.5 minutes (800 Watts)
Typical Backup Time
at Full Load
6.8 minutes (1600 Watts)
Runtime Chart
Smart-UPS
Communications & Management
Interface Port(s)
DB-9 RS-232,SmartSlot
Available SmartSlot™ Interface
Quantity
1
Control panel
LED status display with load and battery bar-graphs and On Line : On Battery :
Replace Battery : and Overload Indicators
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO)
Optional
Surge Protection and Filtering
Surge energy rating
480 Joules
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping
response time : meets UL 1449
Physical
Maximum Height
132.00 mm
Maximum Width
483.00 mm
Maximum Depth
635.00 mm
Rack Height
3U
Net Weight
46.82 KG
Shipping Weight
55.92 KG
Shipping Height
254.00 mm
Shipping Width
622.00 mm
Shipping Depth
953.00 mm
Color
Beige
Environmental
Operating Environment
0 - 40 °C
Operating Relative Humidity
0%
Operating Elevation
0-3000 meters
Storage Temperature
-15 - 45 °C
Storage Relative Humidity
0%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from
surface of unit
47.00 dBA
Online Thermal Dissipation
275.00 BTU/hr
Protection Class
--
Conformance
Regulatory Approvals
CSA,FCC Part 15 Class A,UL 1778
Standard Warranty
2 years repair or replace,optional on-site warranties available,optional extended
warranties available
ROHS/WEEE Compliance
RoHS 7b Exemption
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full
load rating of the UPS.