EKEQ Technical Data (EEDEN15

Add to my manuals
17 Pages

advertisement

EKEQ Technical Data (EEDEN15 | Manualzz
Ventilation
Technical Data
Control box for air handling applications
EEDEN15-205
EKEQ
• Accessory • EKEQ
TABLE OF CONTENTS
EKEQ
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4
Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5
Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wiring Diagrams - Single Phase
8
• Ventilation • EKEQ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1
• Accessory • EKEQ
1
Wide range of units offers maximum application potential and flexible
control options
•
Both option kits are designed for indoor and outdoor installation and
can be wall mounted.
•
The system provides optimized air conditions such as fresh air and
humidity control etc. and can be used in small warehouses,
showrooms and offices.
•
•
Control box and expansion valve kit are required for each
combination plus an air handling unit
Wide offer in control possibilities: control x: room, suction or
discharge temperature can be controlled via DDC control (field
supplied); control y: control by fixed evaporating temperature; control
z: room or suction temperature control via Daikin remote control;
remote ON/OFF can be achieved by an optional adapter KRP4A51
t x o a b l y r l i o o st r s tn eQ n cE e oKc •AEVC
1
2
Features
• Ventilation • EKEQ
• Accessory • EKEQ
2
Specifications
2-1 Technical Specifications
EKEQDCB
Application
Pair
Outdoor unit
Dimensions
Height
Packing
Casing
mm
3
VRV
132
Width
mm
400
Depth
mm
200
Height
mm
215
Width
mm
495
Depth
mm
310
2
Unit
kg
3.6
3.9
3.6
Packed unit
kg
4.6
4.9
4.6
Material
Carton / EPS / Plastic
Colour
White grey
Material
Operation range
EKEQMCBA
Multi
ERQ
Unit
Packed unit
Weight
EKEQFCBA
Resin
Cooling
Min.
°CDB
-10
Max.
°CDB
40
On coil temperature Heating Min.
°CDB
-
Cooling Max.
°CDB
-
Standard Accessories : Stopper (closing up); Quantity : 0;
Standard Accessories : Wire to wire splice; Quantity : 6;
Standard Accessories : Thermistor (R2T/R3T); Quantity : 2;
Standard Accessories : Capacity setting adapter; Quantity : 7;
Standard Accessories : Insulation sheet; Quantity : 2;
Standard Accessories : Rubber sheet; Quantity : 2;
Standard Accessories : Installation and operation manual; Quantity : 1;
Standard Accessories : Screw nut; Quantity : 8;
Standard Accessories : Tie-wraps; Quantity : 6;
Standard Accessories : Thermistor (R1T); Quantity : 1;
2-2 Electrical Specifications
Power supply
EKEQDCB
Name
EKEQFCBA
Phase
1~
Frequency
Hz
50
Voltage
V
230
Min.
%
-10
Max.
%
10
Voltage range
EKEQMCBA
V3
• Ventilation • EKEQ
3
• Accessory • EKEQ
2
Specifications
2-2 Electrical Specifications
Wiring connections
EKEQDCB
For power supply
For connection with
indoor
For remote control
2
3
Remark
Earth wire included
Quantity
2
Remark
F1,F2
Quantity
Remark
P1,P2 (for service)
Y1~Y6
Thermistors liquid
pipe
Quantity
2
Remark
R1,R2
Thermistors gas
pipe
Quantity
2
Remark
R3,R4
ON/OFF
Error signal
Operation signal
Capacity steps
Fan on/off
Defrost signal
EKEQMCBA
2
P1,P2
For expansion valve Quantity
kit
Remark
Thermistor air
P1,P2
6
Quantity
2
-
2
Remark
R5,R6
-
R5,R6
Quantity
2
Remark
T1,T2
Quantity
-
2
-
Remark
-
C1,C2
-
Quantity
-
2
-
Remark
-
C3,C4
-
Quantity
-
2
-
Remark
-
C5,C6
-
Remark
C1,C2
C7,C8
Quantity
-
2
-
Remark
-
C9,C10
-
Quantity
Power supply intake
4
EKEQFCBA
Quantity
2
Bottom
• Ventilation • EKEQ
C1,C2
• Accessory • EKEQ
3
Options
3-1
Options
3
EKEQ
Nr.
Item
1
Remote control / Wired type
2
3
Wiring adapter for electrical appendices
Remote sensor
4
Valve kit
EKEQFCBA
BRC1D528 (*)
BRC1E52A(*)
BRC1E52B(*)
BRC2E52C(*)
BRC3E52C(*)
/
/
EKEXV50
EKEXV63
EKEXV80
EKEXV100
EKEXV125
EKEXV140
EKEXV200
EKEXV250
EKEXV400
EKEXV500
EKEQDCB
EKEQMCBA
BRC1D528
BRC1E52A
BRC1E52B
BRC2E52C
BRC3E52C
KRP4A516
KRCS01-1
EKEXV63
EKEXV80
EKEXV100
EKEXV125
EKEXV140
EKEXV200
EKEXV250
3
EKEXV50
EKEXV63
EKEXV80
EKEXV100
EKEXV125
EKEXV140
EKEXV200
EKEXV250
EKEXV400
EKEXV500
(*) Useful accessory tool for service and installation, but not required for operation
CAUTION
1. The control boxes can be connected to the following DIII-NET devices: iTouch Manager II and Modbus Interface DIII.
2. 2QO\XVHWKLVV\VWHPLQFRPELQDWLRQZLWKD¿HOGVXSSOLHGDLUKDQGOLQJXQLW
Do not connect this system to other indoor units.
3. Refer to the combination table for the application of the valve kits.
4D090226
• Ventilation • EKEQ
5
• Accessory • EKEQ
4
Control systems
4-1
Control Systems
In order to maximize installation flexibility,
4 types of control systems are offered
4
Control w: Off the shelf control of air temperature (discharge
temperature, suction temperature, room temperature) via any DDC
controller
Control x: Precize control of air temperature (discharge
temperature, suction temperature, room temperature) requiring a
preprogrammed DDC controller (for special applications)
Control y: Control of refrigerant (Te/Tc) temperature via
Daikin control (no DDC controller needed)
Control z: Control of air temperature (suction temperature,
room temperature) via Daikin control (no DDC controller
needed)
Possibility W (Td/Tr control):
Possibility X (Td/Tr control):
Air temperature control via DDC controller
Room temperature is controlled as a function of the air handling
unit suction or discharge air (customer selection). The DDC
controller is translating the temperature difference between set
point and air suction temperature (or air discharge temperature or
room temperature) into a proportional 0-10V signal
which is transferred to the Daikin control box (EKEQFCBA).
Precise air temperature control via DDC controller
Room temperature is controlled as a function of the air handling
unit suction or discharge air (customer selection). The DDC
controller is translating the temperature difference between set
point and air suction temperature (or air discharge temperature
or room temperature) into a reference voltage (0-10V) which is
transferred to the Daikin control box (EKEQFCBA). This reference
voltage will be used as the main input value for the compressor
This voltage controls the compressor frequency.
frequency control.
Ts
DDC
Ts
Td
Te
AHU
Daikin
control box:
EKEQFCBA
Tr
DDC
Room
Te
Td
AHU
Daikin
control box:
EKEQFCBA
Tr
Room
Possibility Y (Te/Tc control):
Possibility Z (Ts/Tr control):
By fixed evaporating /condensing temperature
A fixed target evaporating temperature of between 3°C and
8°C can be set by the customer. In this case, room temperature is
only indirectly controlled. The cooling load is determined from
the actual evaporating temperature (i.e. load to the heat
Control your AHU just like a VRV indoor unit with 100% fresh air
(BRC1D52 or BRC1E52A/B - optional)
Set point can be fixed via standard Daikin infrared remote control.
Remote ON/OFF can be achieved
by an optional adapter KRP4A51.
No external DDC controller should be connected. The cooling load is
exchanger). A Daikin infrared remote control (BRC1D52 or
BRC1E52A/B - optional) can be connected for error indication.
determined from the air suction temperature and set point on
the Daikin controller.
ON / OFF
KRP4A51
Daikin
control box:
EKEQFCBA
AHU
Te
Ts
Tr
Ts
Td
Daikin
control box:
EKEQDCB
EKEQMCB
Room
BRC1D52
BRC1E52A/B
Room
BRC1D52
BRC1E52A/B
Tr = Room temperature
AHU = Air Handling Unit
Te = Evaporating temperature
DDC = Digital Display Controller
EKEQFCBA
Possibility y
EKEQDCB
EKFQMCBA*
* EKEQMCB (for ’multi’ application)
6
Tr
Td = Air discharge temperature
Possibility w
Possibility z
Td
Ts = Air suction temperature
Option kit
Possibility x
Te
AHU
• Ventilation • EKEQ
Features
DDC controller is required
temperature control using air suction or air discharge temperature
DDC and Microtech controller is required
Precise Temperature control using air suction or air discharge temperature
Using fixed evaporating temperature, no set point can be set using remote control
Using Daikin infrared remote control BRCD or BRCEA/B
Temperature control using air suction temperature
• Accessory • EKEQ
5
Combination table
5-1
Combination Table
3
EKEQ
Outdoor unit
System A
System B
System B
ERQ100
1
ERQ125
-phase
ERQ140
ERQ125
3
ERQ200
-phase
ERQ250
VRV III
VRV IV
Control box
Expansion valve kit
Options
EKEQDCBV3 EKEQFCBAV3 EKEQMCBAV3 EKEXV50 EKEXV63 EKEXV80 EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250 EKEXV400 EKEXV500 EKDK04 KWC26B160 KWC26B280 KRC19-26A6
P
P
P
P
P
P
0
0
P
P
P
P
P
P
P
0
0
P
P
P
P
P
P
0
0
P
P
P
P
P
P
P
0
0
P
P
P
P
P
P
P
0
0
P
P
P
P
P
P
0
0
n1
n1
n1
n1
n1
n1
n1
n1
n1
n1
n1
See note 1
1 -> 3
n2
n2
n2
n2
n2
n2
n2
n2
n2
n2
n2
See note 1
5
P (pair application): combination depends on the capacity of the air handling unit
n1 (multi application: combination of air handling units and VRV DX indoor units): to determine the quantity, refer to 3D090229.
n2 (multi application: multiple air handling units, or the combination of air handling units and VRV DX indoor units): to determine the quantity, refer to 3D090229.
NOTES
1. See outdoor unit. The system can only be connected to the following DIII-NET devices: iTouch Manager II and Modbus Interface DIII.
2. Control box EKEQD can only be connected to an ERQ outdoor unit (pair application).
3. Control box EKEQFA can be connected to an ERQ outdoor unit in pair application.
Control box EKEQFA can be connected to some types of VRV IV outdoor unit (with a maximum of 3 boxes per outdoor unit).
Do not combine EKEQFA control boxes with VRV DX indoor units, RA indoor units, or Hydroboxes.
For details, refer to the combination table drawing of the outdoor unit.
4. The control box EKEQMA can only be connected to a VRV outdoor unit in multi application.
5. Depending on the type of air handling unit, an appropriate expansion valve kit EKEXV must be selected using following limitations: SH (superheat) = 5K and SC (subcool) = 3K
Cooling
Heating
Allowed heat exchanger capacity [kW]
minimum
maximum
50
5.0
6.2
63
6.3
7.8
80
7.9
9.9
100
10.0
12.3
125
12.4
15.4
140
15.5
17.6
200
17.7
24.6
250
24.7
30.8
400
35.4
49.5
500
49.6
61.6
Saturated evaporating temperature: 6°C
Air temperature: 27°C DB / 19°C WB
Allowed heat exchanger capacity [kW]
minimum
maximum
50
5.6
7.0
63
7.1
8.8
80
8.9
11.1
100
11.2
13.8
125
13.9
17.3
140
17.4
19.8
200
19.9
27.7
250
27.8
34.7
400
39.8
55.0
500
55.1
69.3
Saturated evaporating temperature: 46°C
Air temperature: 20°C DB
EKEXV class
EKEXV class
3D090631
• Ventilation • EKEQ
7
• Accessory • EKEQ
6
Dimensional drawings
6-1
Dimensional Drawings
EKEQDCB
600 or more
j
1 4 holes to fix control box
j
2 Control box lid
j
3 Screw nut for power supply cable
j
4 Screw nut for expansion valve cable
j
5 Screw nut for thermistor cable (liquid) R2T + (Air) R1T
j
6 Screw nut for thermistor cable (gas) R3T
j
7 Screw nut for communication cable to outdoor unit
j
8 Screw nut for fan cable
j
9 Screw nut for remote controller
j
10 Screw nut for connection cable to controller
6
Service space
(Note 2)
200 or more
Service space
(Note 2)
Notes:
1
2
Installation:
Make sure that the control box is installed horizontal, screw nuts position
downwards.
The option boxes (expansion valve and electrical control box) can be installed
inside and outside.
Do not install the option boxes in or on the outdoor unit.
Do not put the option boxes in direct sunlight. Direct sunlight will increase the
temperature inside the option boxes and may reduce its lifetime and influence its
operation.
Choose a flat and strong mounting surface.
Operation temperature of the control box is between -10°C And 40°C
Service space:
Keep the space in front of the boxes free for future maintenance.
3TW32144-1
EKEQFCB
j
1 4 holes to fix control box
j
2 Control box lid
j
3 Screw nut for power supply cable
j
4 Screw nut for expansion valve cable
j
5 Screw nut for thermistor cable (liquid) R2T + (gas) R3T
j
6 Screw nut for fan
j
7 Screw nut for connection cable to controller
j
8 Stopper (closing cup)
j
9 Screw nut for communication cable to outdoor unit
j
10 Screw nut for connection cable to controller
600 or more
Service space
(Note 2)
200 or more
Service space
(Note 2)
Notes:
1
2
Installation:
Make sure that the control box is installed horizontal, screw nuts position
downwards.
The option boxes (expansion valve and electrical control box) can be installed
inside and outside.
Do not install the option boxes in or on the outdoor unit.
Do not put the option boxes in direct sunlight. Direct sunlight will increase the
temperature inside the option boxes and may reduce its lifetime and influence its
operation.
Choose a flat and strong mounting surface.
Operation temperature of the control box is between -10°C And 40°C
Service space:
Keep the space in front of the boxes free for future maintenance.
3TW32134-1
8
• Ventilation • EKEQ
• Accessory • EKEQ
6
Dimensional drawings
6-1
Dimensional Drawings
3
(.(40&%
RUPRUH
6
VHUYLFH
VSDFH
QRWH
RUPRUH
VHUYLFH
VSDFH
QRWH
7:$
KROHVWR¿[WKHFRQWUROER[
&RQWUROER[OLG
6FUHZQXWIRUSRZHUVXSSO\FDEOH
6FUHZQXWIRUH[SDQVLRQYDOYHFDEOH
6FUHZQXWIRUWKHUPLVWRUFDEOHOLTXLG57DLU57
6FUHZQXWIRUWKHUPLVWRUFDOEHJDV57
6UHZQXWIRUFRPPXQLFDWLRQFDEOH
6UHZQXWIRUIDQFDEOH
6UHZQXWIRUUHPRWHFRQWURO
6FUHZQXWIRUFRQQHFWLRQFDEOHWRFRQWUROOHU
127(6
,QVWDOODWLRQ
0DNHVXUHWKDWWKHFRQWUROER[LVLQVWDOOHGKRUL]RQWDO6FUHZQXWVSRVLWLRQGRZQZDUGV
7KHRSWLRQER[HVH[SDQVLRQYDOYHDQGHOHFWULFDOFRQWUROER[FDQEHLQVWDOOHGLQVLGHDQGRXWVLGH
'RQRWLQVWDOOWKHRSWLRQER[HVLQRURQWKHRXWGRRUXQLW
'RQRWSXWWKHRSWLRQER[HVLQGLUHFWVXQOLJKW'LUHFWVXQOLJKWZLOOLQFUHDVHWKHWHPSHUDWXUHLQVLGHWKHRSWLRQER[HVDQGPD\
UHGXFHLWVOLIHWLPHDQGLQÀXHQFHLWVRSHUDWLRQ
&KRRVHDÀDWDQGVWURQJPRXQWLQJVXUIDFH
2SHUDWLRQWHPSHUDWXUHRIWKHFRQWUROER[LVEHWZHHQƒ&DQGƒ&
6HUYLFHVSDFH
.HHSWKHVSDFHLQIURQWRIWKHER[HVIUHHIRUIXWXUHPDLQWHQDQFH
• Ventilation • EKEQ
9
• Accessory • EKEQ
7
Wiring diagrams
7-1
Wiring Diagrams - Single Phase
EKEQDCB
7
A1P
A2P
F1U
F3U
HAP
K1R
K4R
Q1DI
R7
R1T
R2T
R3T
T1R
X1M
X3M
X1M-R1/R2
X1M-R3/R4
X1M-R5/R6
X1M-Y1∼6
X1M-C1/C2
X1M-P1/P2
X1M-F1/F2
X1M-T1/T2
Y1E
: Printed circuit board
: Printed circuit board (Option KRP4)
: Fuse (250V, F5A) (A1P)
: Field fuse
: Light emitting diode (service monitor green)
: Magnetic relay
: Magnetic relay (Fan) AC
: Earth leakage breaker
: Capacity adaptor
: Thermistor (Air)
: Thermistor (Liquid)
: Thermistor (Gas)
: Transformer (220V/21.8V)
: Terminal block
: Terminal block
: Thermistor Liquid
: Thermistor Gas
: Thermistor Air
: Expansion valve
: Output: Fan ON/OFF
: Communication remote controller
: Communication outdoor
: Input: ON/OFF
: Electronic expansion valve
1 Use copper conductors only.
2 BLK: Black / WHT: White / RED: Red / BLU: Blue /
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange /
PINK: Pink / YLW: Yellow
: Live
: Neutral
: Connector
: Wire clamp
: Protective earth (Screw)
Outdoor
: Seperate component
: Optional accessory
: Field wiring
Wired remote control
Position in switch box
2TW32146-1
EKEQFCB
A1P
A2P
A3P
F1U
F2U
F3U
HAP
K2R
K3R
K4R
K5R
K1R, KAR, KPR
Q1DI
R5
R6
R2T
R3T
T1R
X1M
X2M
X3M
Y1E
X1M-R1/R2
X1M-R3/R4
X1M-Y1∼6
X2M-P1/P2
X2M-C1/C2
X2M-C3/C4
X2M-C5/C6
X1M-C7/C8
X1M-C9/C10
X2M-F1/F2
X2M-T1/T2
Only for 0-10V input
: Printed circuit board
: Printed circuit board (for voltage conversion)
: Printed circuit board (Power supply)
: Fuse (250V, F5A) (A1P)
: Fuse (250V, T1A) (A3P)
: Field fuse
: Light emitting diode (service monitor green)
: Magnetic relay (error status) AC
: Magnetic relay (Operation / Compressor ON/OFF) AC
: Magnetic relay (Fan) AC
: Magnetic relay (Defrost signal) DC
: Magnetic relay
: Earth leakage breaker
: Resistance (DC 120 OHM)
: Capacity adaptor
: Thermistor (Liquid)
: Thermistor (Gas)
: Transformer (220V/21.8V)
: Terminal block
: Terminal block
: Terminal block
: Electronic expansion valve
: Thermistor Liquid
: Thermistor Gas
: Expansion valve
: Communication remote controller
: Output: error status
: Output: Operation / Compressor ON/OFF
: Input: 0-10V DC capacity control
: Output: Fan ON/OFF
: Output: Defrost signal
: Communication outdoor
: Input: ON/OFF
1 Use copper conductors only.
2 BLK: Black / WHT: White / RED: Red / BLU: Blue /
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange /
PINK: Pink / YLW: Yellow
: Live
: Neutral
: Connector
: Wire clamp
: Protective earth (Screw)
Outdoor
: Seperate component
: Optional accessory
: Field wiring
Wired remote control
Position in switch box
2TW32136-1
10
• Ventilation • EKEQ
• Accessory • EKEQ
7
Wiring diagrams
7-1
Wiring Diagrams - Single Phase
3
EKEQMCB
A1P
A2P
F1U
F3U
HAP
K1R
K4R
Q1DI
R7
R1T
R2T
R3T
T1R
X1M
X3M
X1M-R1/R2
X1M-R3/R4
X1M-R5/R6
X1M-Y1∼6
X1M-C1/C2
X1M-P1/P2
X1M-F1/F2
X1M-T1/T2
Y1E
: Printed circuit board
: Printed circuit board (Option KRP4)
: Fuse (250V, F5A) (A1P)
: Field fuse
: Light emitting diode (service monitor green)
: Magnetic relay
: Magnetic relay (Fan) AC
: Earth leakage breaker
: Capacity adaptor
: Thermistor (Air)
: Thermistor (Liquid)
: Thermistor (Gas)
: Transformer (220V/21.8V)
: Terminal block
: Terminal block
: Thermistor Liquid
: Thermistor Gas
: Thermistor Air
: Expansion valve
: Output: Fan ON/OFF
: Communication remote controller
: Communication outdoor
: Input: ON/OFF
: Electronic expansion valve
7
1 Use copper conductors only.
2 BLK: Black / WHT: White / RED: Red / BLU: Blue /
BRN: Brown / GRY: Grey / GRN: Green / ORG: Orange /
PINK: Pink / YLW: Yellow
: Live
: Neutral
: Connector
: Wire clamp
: Protective earth (Screw)
Outdoor
: Seperate component
: Optional accessory
: Field wiring
Wired remote control
Position in switch box
2TW32156-1
• Ventilation • EKEQ
11
• Accessory • EKEQ
8
External connection diagrams
8-1
External Connection Diagrams
EKEQDCB
Valve kit
Air handling unit
Power supply
Outdoor unit
Main switch
Field supplied air handling
unit
Electronic expansion
valve
8
Filter
Filter
Switch
Max.
Fuse
L1 (Min. 5m)
(Max. 50m)
Max.
Expansion valve
connector
L (Max. 20m)
Transmission line
L (Max. 100m)
Switch
Fuse
Air handling unit controller
L2 (Max. 5m)
1
2
3
4
5
Thermistor lines (3x)
Power line
L (Standard 2.5m)
(Max. 20m)
6
7
Fan switch
Digital output
Control box
8
9
10
11
All wiring, components and materials to be produced on the site must
comply with the applicable local and national codes.
Use copper conductors only.
For more details, see wiring diagram.
Install a circuit breaker for safety.
All field wiring and components must be provided by a licensed
electrician.
Unit shall be grounded in compliance with the applicable local and
national codes
Wiring shown are general points-of-connection guides only and are not
intended for or to include all details for a specific installation.
Be sure to install the switch and the fuse to the power line of each
equipment.
Install the main switch that can interrupt all power sources in an integrated
manner because this system consists of the equipment utilizing the
multiple power sources.
For detailed control box side connection, see control box manual and
wiring diagram.
For detailed pipe connections and limitations, see manuals.
Remote controller
Wiring
Refrigerant
piping
3TW32149-1
EKEQFCB
Outdoor unit
Main switch
Air handling unit
Valve kit
Power supply
Electronic expansion
valve
Filter
Field supplied air handling
unit
Filter
Max.
Switch
L2 (Max. 5m)
Fuse
Max.
L1 (Min. 5m)
(Max. 50m)
Transmission line
L (Max. 100m)
Switch
Fuse
Expansion valve
connector
L (Max. 20m)
Power line
1
2
3
4
5
Fan switch
Digital output
6
Control box
Thermistor lines
7
L (Standard 2.5m)
(Max. 20m)
8
9
L (Depend on digital controller)
10
11
Field supplied digital
controller
All wiring, components and materials to be produced on the site must
comply with the applicable local and national codes.
Use copper conductors only.
For more details, see wiring diagram.
Install a circuit breaker for safety.
All field wiring and components must be provided by a licensed
electrician.
The unit shall be grounded in compliance with the applicable local and
national codes.
Wiring shown are general points-of-connection guides only and are not
intended for or to include all details for a specific installation.
Be sure to install the switch and the fuse to the power line of each
equipment.
Install the main switch that can interrupt all power sources in an integrated
manner because this system consists of the equipment utilizing the
multiple power sources.
For detailed control box side connection, see control box manual and
wiring diagram.
For detailed pipe connections and limitations, see manuals.
Wiring
Refrigerant piping
Digital controller
12
• Ventilation • EKEQ
3TW32139-1
• Accessory • EKEQ
8
External connection diagrams
8-1
External Connection Diagrams
3
EKEQMCB
Valve kit
Air handling unit
Power supply
Electronic expansion
valve
Field supplied air
handling unit
Main switch
Filter
8
Filter
Max.
(Max. 5m)
Switch
Fuse
Air handling unit controller
Liquid pipe
Gas pipe
Expansion valve Connector
L (Max. 20m)
Switch
Transmission
Fuse
Thermistor lines (3x)
L (Standard 2.5m)
(Max. 20m)
Fan switch
Digital output
Power supply
Control box
Remote controller
Notes:
1
2
3
4
5
6
7
8
9
Indoor unit
10
Remote controller
11
12
Indoor unit
All wiring, components and materials to be produced on the site must comply
with the applicable local and national codes.
Use copper conductors only.
For more details, see wiring diagram.
Install a circuit breaker for safety.
All field wiring and components must be provided by a licensed electrician.
The unit shall be grounded in compliance with the applicable local and
national codes.
Wiring shown are general points-of-connection guides only and are not
intended for or to include all details for a specific installation.
Be sure to install the switch and the fuse to the power line of each equipment.
Install the main switch that can interrupt all power sources in an integrated
manner because this system consists of the equipment utilizing the multiple
power sources.
For detailed control box side connection, see control box manual and wiring
diagram.
For detailed pipe connections and limitations, see manuals.
Connection appliance can be standard indoor unit or free choice of air
handling unit.
Remote controller
Wiring
Refrigerant piping
3TW32159-1
• Ventilation • EKEQ
13
The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.
BARCODE
Daikin products are distributed by:
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
EEDEN15-205 • 11/14 • Copyright Daikin
The present publication supersedes EEDEN14-205
These products are not within the scope of
the Eurovent certification program

advertisement