Aero Series Commercial Energy Saver Multi Flue Oil–Powered

Aero Series Commercial Energy Saver
Multi Flue Oil–Powered Models
CF-38 / CF-80 / CF-100
The Multi Flue Oil-Powered Models feature:
■ Automatic Controls—Single aquastat (shipped with burner) with
mechanical control monitors tank temperature through upper and lower
ports. Provides more uniform result for controls. (CF-80 and CF-100).
Electronic control aquastat on CF-38 with built-in high limit.
■ Factory installed Hydrojet® 2™ Sediment Reduction System—Cold water
inlet sediment reducing device helps prevent sediment build up in the tank.
■ Vitraglas® Lining—Bradford White tanks are lined with an exclusively
engineered enamel formula that provides superior tank protection from the
highly corrosive effects of hot water. This formula (Vitraglas®) is fused to the
steel surface by firing at a temperature of over 1600° F.
■ Non-CFC Foam Insulation—Covers the sides and top of tank, reducing
the amount of heat loss. This results in less energy consumption, improved
operation efficiencies and jacket rigidity.
■ Magnesium Anode Rods—Employed to provide an extra measure of
corrosion prevention for longer life.
■ Water Connections—Factory installed dielectric waterway fittings extend
water heater life and eases installation.
■ Hand Hole Cleanout—Allows inspection of tank interior and facilitates
removal of water heater's principal deterrent to long life—accumulated lime
and sediment deposits.
■ T&P Relief Valve—Installed.
■ Brass Drain Valve—Durable tamper proof design.
■ ASME Code Construction—Available on 80 and 100 gallon (303 and 379
liters) models, not available on 38 (144 liter) gallon models.
■ Carlin Burners—All burners are 120V, 1-stage with multiple firing rates.
Beckett and Riello are optional burners, but not available through Bradford
White.
■ New Carlin Burners are Compatible with Biofuel—Up to B5 (5% Biofuel)
can be used with water heater, provided the Biofuel meets ASTM D6751.
Photo is of
CF-80-3
3-Year Limited Tank Warranties / 1-Year Limited Warranty on Component Parts.
For more information on warranty, please visit www.bradfordwhite.com
For products installed in USA, Canada and Puerto Rico. Some states do not allow limitations on warranties. See complete
copy of the warranty included with the heater.
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 5,954,492; 5,761,379; 5,943,984; 5,081,696; 5,988,117; 6,142,216; 5,199,385; 5,574,822; 5,372,185; 5,485,879; 5,277,171;
(B1)5,341,770; 5,660,165; 5,596,952; 5,682,666; 4,904,428; 5,023,031; 5,000,893; 4,669,448; 4,829,983; 4,808,356; 5,115,767; 5,092,519; 5,052,346; 4,416,222; 4,628,184; 4,861,968; 4,672,919; Re. 34,534;
7,270,087 B2. OTHER U.S. AND FOREIGN PATENT APPLICATIONS PENDING. CURRENT CANADIAN PATENTS: 1,272,914; 1,280,043; 1,289,832; 2,045,862; 2,112,515; 2,108,186; 2,107,012; 2,092,105; 2,409,271.
Vitraglas® and Hydrojet® are registered trademarks of Bradford White® Corporation.
611-B-0612-A
Commercial Energy Saver Multi Flue Oil–Powered Models
CF-38 / CF-80 / CF-100
B
B
B
C
C
C
K
K
K
A
A
D, G, M
H
J
D, G, M
J
A, J
D
G L
F
L
F
L
N
N
E
E
E
CF-38
CF-80
CF-100
Energy Saver Models
Meet or exceed ASHRAE 90.1b (current standard) C.E.C. Listed
80% Recovery Efficiency
Oil
Model
Number
CF-38-3
CF-80-3
CF-100-3
Model
Number
CF-38-3
CF-80-3
CF-100-3
A
Floor to
Flue Conn.
B
Jacket
Dia.
C
Vent
Size
D
E
F
H
G
Floor to
Floor to Front / Rear Front / Rear Floor to
T&P
C/L Burner Cold Water
Hot Water Top Water
Conn.
Opening
Conn.
Conn.
Conn.
J
L
M
N
Std.
K
ASME
Floor to Depth** Floor to Floor to Floor to Shipping Shipping
Heater
Aquastat Aquastat Drain Weight * Weight *
Top
Avg Bulb Valve
in.
in.
in.
in.
in.
in.
in.
in.
in.
in.
in.
in.
in.
in.
lbs.
503/8
723/4
731/4
281/4
301/4
301/4
8
8
8
403/4
623/8
623/8
123/8
125/8
113/8
26
341/4
295/8
411/2
623/8
623/8
723/4
503/8
721/4
721/4
3513/16
435/8
393/8
35
433/8
367/8
623/8
623/8
213/4
277/8
295/8
428
850
760
875
798
A
Floor to
Flue Conn.
B
Jacket
Dia.
C
Vent
Size
D
Floor to
T&P
Conn.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
kg.
kg.
1280
1848
1861
718
768
768
203
203
203
1035
1584
1584
314
321
289
660
870
752
1054
1584
1584
1848
1280
1835
1835
910
1108
1000
889
1102
937
1584
1584
552
708
752
194
386
345
397
362
Aquastat
and Avg.
Bulb
Tapping
Relief
Valve
Opening
Drain
Valve
Opening
mm.
mm.
mm.
19
19
19
25
25
25
19
19
19
E
F
H
G
Floor to Front / Rear Front / Rear Floor to
C/L Burner Cold Water
Hot Water Top Water
Opening
Conn.
Conn.
Conn.
J
L
M
N
Std.
K
ASME
Floor to Depth** Floor to Floor to Floor to Shipping Shipping
Heater
Aquastat Aquastat Drain Weight * Weight *
Top
Avg Bulb Valve
* Weight does not include burner and controls.
** Depth includes burner dimensions.
Model
Number
CF-38-3
CF-80-3
CF-100-3
F
N
Water
Connections
Size
Front / Rear / Top
Aquastat
and Avg.
Bulb
Tapping
Relief
Valve
Opening
Drain
Valve
Opening
in.
in.
in.
in.
in.
in.
11/2
11/2
11/2
11/2
-
-
3/4
1
1
1
3 /4
3/4
3/4
3/4
3/4
Model
Number
Water
Connections
Size
Front / Rear / Top
mm. mm. mm.
CF-38-3
CF-80-3
CF-100-3
38
38
38
30
-
-
Specifications for Commercial Multi Flue Water Heaters
CF-38
CF-80
CF-100
Tank Capacity Gallons
Number of Flues
Firing Rate Range GPH
38
11
1.75 to 2.50
80
20
3.50 to 5.00
100
12
2.50 to 3.00
Model Number
Firing Rate GPH
Btu/hr Input
Recovery Rate – 100°F Rise
– 90°F Rise
CF-38-350-3
2.50
350,000
334
371
CF-80-700-3(A)
5.00
700,000
665
740
CF-100-420-3(A)
3.00
420,000
410
456
Model Number
Firing Rate GPH
Btu/hr Input
Recovery Rate – 100°F Rise
– 90°F Rise
CF-38-315-3
2.25
315,000
304
338
CF-80-630-3(A)
4.50
630,000
608
676
CF-100-350-3(A)
2.50
350,000
355
395
Model Number
Firing Rate GPH
Btu/hr Input
Recovery Rate – 100°F Rise
– 90°F Rise
CF-38-280-3
2.00
280,000
273
304
CF-80-560-3(A)
4.00
560,000
543
604
–
–
–
–
–
Model Number
Firing Rate GPH
Btu/hr Input
Recovery Rate – 100°F Rise
– 90°F Rise
CF-38-245-3
1.75
245,000
240
267
CF-80-490-3(A)
3.50
490,000
483
537
–
–
–
–
–
Installed
180°F
8"
3
Installed
180°F
8"
4
Included
180°F
8"
4
Front
11⁄2" Male NPT
Rear – 11⁄2"
1
1 ⁄2" Female NPT Capped
Front
11⁄2"
N/A
N/A
Front & Top
11⁄2" & 11⁄2"
N/A
N/A
Included
Included
Included
428
503⁄8"
281⁄4"
TriWall Carton
850
721⁄4"
875
301⁄4"
Wood Crate
768
721⁄4"
798
301⁄4"
Wood Crate
T&P Valve
Maximum Operating Temperature
Flue Collar Size
Number of Anodes
Water Connection Location
Water Connection Type
Auxiliary Connections Location
Auxiliary Connections Type
Hand Hole Clean Out
Water
Water
Water
Water
Water
Heater
Heater
Heater
Heater
Heater
Shipping Weight – lbs.
Height
Shipping Weight (ASME)– lbs.
Diameter
Packaging
(A) ASME Construction available for CF-80 and CF-100 only.
For ASME construction add "A" to the model number as displayed (Ex. CF-80-490-3A).
These models meet or exceed the Thermal Efficiency and Standby Loss Requirements of ASHRAE 90.1b (current edition).
All models are design certified for up to 180°F. (82°C) application as an Automatic Storage Heater, and an Automatic Circulating Tank
Heater.
As an Automatic Storage Heater, all models are complete self-contained water heating systems. It needs no separate storage tank, pump,
wiring or elaborate piping network. When equipped with a mixing valve, it will supply 180°F (82°C) sanitizing and 140°F (60°C) general
purpose hot water simultaneously. (Maximum temperature for CF-38 is 160°F). These models can be used either as a single unit or in
multiples connected in parallel.
Sample Specification
The water heater shall be a Bradford White model _______ with a rated storage capacity of not less than _______ gallons, a minimum input
of
_______ BTUH/KW, a firing rate of _______ GPH/LPH, and a minimum recovery of _______ GPH/LPH at 100°F (56°C). temperature rise. It
shall be design certified for 180°F (82°C). application, either with or without a separate storage tank. The tank shall be lined with Vitraglas®
vitreous enamel and shall have a bolted hand hole cleanout. The tank shall have multiple extruded magnesium anode rods installed in
separate head couplings. This water heater shall be equipped with cold water inlet, Hydrojet® Sediment Reduction System, an ASME rated
T&P relief valve and a flame retention high speed oil burner (120V/60Hz. or 220V/50 Hz. AC required). The entire installation shall be made
in compliance with state and local codes and ordinances.
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
Ambler, PA
For U.S. and Canada field service, contact your professional installer or local Bradford White sales representative.
Sales 800-523-2931 ● Fax 215-641-1670 / Technical Support 800-334-3393 ● Fax 269-795-1089 ● Warranty 800-531-2111 ● Fax 269-795-1089
International: Telephone 215-641-9400 ● Telefax 215-641-9750 / www.bradfordwhite.com
Sales / Technical Support 866-690-0961 / 905-238-0100 ● Fax 905-238-0105 / www.bradfordwhite.com
©2012, Bradford White Corporation. All rights reserved.
611-B-0612-A
Printed in U.S.A.