ACCESS CONTROL
AS-626M-200
AS-626S-200
AS-634-200
PRODUCT SPECIFICATION
Models AS-626M-200, AS-626S-200, AS-634-200
MOUNTING INSTRUCTIONS
Drill mounting holes using template provided
Connect keypad using wiring detail on reverse of unit
For 12VDC inductive loads such as electric strikes and electromagnetic locks, the enclosed 12VDC varister must be
Connected in parallel with the load, at the load terminals and not in the keypad.
Ensure power supply is of correct rating, taking into account the current requirements of the locking items and accessories.
Do not insert security plugs into fixing holes until all installation and testing has been completed.
WIRING DESCRIPTION
BROWN
BLUE
BLACK
RED
YELLOW
+ 12V - 24V AC/DC Power Supply
= Ground
= Common
= N.O C.O. Form C ; Contact 2 Amp. Dry contact for Door Strike
= N.C.
WHITE / ORANGE = REMOTE OPENING DOOR ( DRY CONTACT ONLY !)
ACTIVATION
LED signaling explanation
GREEN LED:
RED LED:
Door Strike activated
Normal Operation : 3 sec. ON = Wrong Code Entry
Slow flashing = Wrong code entry 3 times
Programming Mode:
Fast flashing = Programming different
Slow flashing = programming stand-by
Very Fast flashing = Erasing All user codes
TESTING THE UNIT
Enter the master code [1 2 3 4 #]
The Door Relay changes its contacts for 5 sec.
The Green LED will light up for 5 sec. Repeat this step 2,3 times.
If the master code is wrongly typed in, the Red LED lights up for 3 sec. re-enter the Code as soon as the
LED goes OFF.
IMPORTANT:
CHANGE THE FACTORY SET MASTER CODE WHEN YOU PROGRAM YOUR UNIT FOR USE. THERE IS NO WAY
TO RECOVER THE NEW MASTER CODE IF IT IS LOST OR FORGOTTEN. THE UNIT CAN BE RESET TO FACTORY
PRESETS AND CUSTOMISED AGAIN.