Air Conditioners
Technical Data
I n t ro d u c t i o n
EEDEN14-200
Air Conditioners
Technical Data
I n t ro d u c t i o n
EEDEN14-200
• Introduction
TABLE OF CONTENTS
I Introduction
1
Indoor unit range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Ventilation range
3
Biddle air curtain range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4
Hydrobox range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5
Network solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6
Possible outdoor units using R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
................................................... 4
Outdoor unit range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
VRV Heat Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
VRV Heat Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Replacement VRV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
VRV-WIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Indoor unit capacity index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Biddle air curtains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ventilation units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hydroboxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
• VRV Systems • Introduction
12
13
14
14
15
1
• Introduction
1
Indoor unit range
VRV air conditioning brings summer freshness and winter warmth to offices, hotels, department stores and many other commercial premises. It
enhances the indoor environment and creates a basis for increased business prosperity and whatever the air conditioning requirement, a Daikin indoor
unit will provide the answer.
Capacity
I
Type
FLOOR STANDING CEILING SUSPENDED
WALL
MOUNTED
CONCEALED CEILING
CEILING MOUNTED CASSETTE
1
Model
Product
name
Round flow cassette
autocleaning function3
Presence & floor sensor3
FXFQ-A
Fully flat cassette
Presence & floor sensor3
FXZQ-A
2-way blow
ceiling mounted cassette
FXCQ-A
Ceiling mounted
corner cassette
FXKQ-MA
Small concealed ceiling unit
FXDQ-M9
Slim concealed ceiling unit
FXDQ-A
Concealed ceiling unit
with inverter driven fan
FXSQ-P
Concealed ceiling unit
with inverter driven fan
FXMQ-P7
Large concealed
ceiling unit
FXMQ-MA4
Wall mounted unit
FXAQ-P
Ceiling suspended unit
FXHQ-A
4-way blow ceiling
suspended unit
FXUQ-MA
Floor standing unit
FXLQ-P
Concealed
floor standing unit
FXNQ-P
Cooling capacity (kW)1
Heating capacity (kW)2
15
20
25
32
40
50
63
71
80
100 125 140 200 250
1.7
2.2
2.8
3.6
4.5
5.6
7.1
1.9
2.5
3.2
4.0
5.0
6.3
8.0
8.0
9.0
11.2
14.0
16.0
22.4
28.0
9.0
10.0
12.5
16.0
18.0
25.0
31.5
NOTES
2
1
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB,
equivalent refrigerant piping: 5m, level difference: 0m.
2
Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB,
equivalent refrigerant piping: 5m, level difference: 0m
3
Optional
4
Not connectable to VRV III-S
• VRV Systems • Introduction
• Introduction
1
Indoor unit range
3
Connectable
outdoor unit
Model
Product
name
CEILING MOUNTED
CASSETTE
Round flow cassette
(incl. autoclean function1)
FCQG-F

Fully flat cassette
FFQ-C

CONCEALED CEILING
Capacity
Small concealed ceiling unit
FDBQ-B

Slim concealed ceiling unit
FDXS-F(9)

Concealed ceiling unit
with inverter driven fan
FBQ-C

Daikin Emura
Wall mounted unit
FTXG-LW/LS


Wall mounted unit
CTXS-K
FTXS-K


Wall mounted unit
FTXS-G


Ceiling suspended unit
FHQ-C
Nexura floor standing unit
FVXG-K


Floor standing unit
FVXS-F


Flexi type unit
FLXS-B(9)


FLOOR STANDING
CEILING
SUSPENDED
WALL MOUNTED
Type
15
20
25
35
42
50
60
71
RYYQ-T
RXYQ-T
RXYSQ-P8V1
RXYSQ-P8Y1
I
1

NOTES
1
Decoration panel BYCQ140CG + BRC 1E51A needed
2
To connect RA indoor units a BP box is required
• VRV Systems • Introduction
3
• Introduction
2
Ventilation range
Humidification: optimise the balance between
indoor and outdoor humidity
Ventilation: provision of fresh air
I
Pre conditioning: cooling or heating of incoming fresh air to maintain a
consistent temperature for maximum comfort
2
Air flow rate (m3/h)
Type
HEAT
RECLAIM
VENTILATION
Product
name
Model
VAM-FA/FB
1 Ventilation
VKM-GB
1 Ventilation
3 Pre conditioning
VKM-GBM
1 Ventilation
2 Humidification
3 Pre conditioning
OUTDOOR AIR
PROCESSING UNIT1
FXMQ-MF
1 Ventilation
3 Pre conditioning
VRV AIR
HANDLING
APPLICATIONS2
EKEXV-kit
1 Ventilation
3 Pre conditioning
0
200
400
600
800 1,000 1,500 2,000 4,000 6,000 8,000
NOTES
4
1
Not connectable to VRVIII-S (RXYSQ-P8V1, RXYSQ-P8Y1)
2
Air flow rate is a calculated indication only, based on the following values: heating capacity EKEXV-kit * 200m³/h
3
For more information on Daikin air handling units refer to your local dealer
• VRV Systems • Introduction
• Introduction
3
Biddle air curtain range
Type
BIDDLE AIR CURTAIN FREE HANGING
CYV S/M/L-DK-F
BIDDLE AIR CURTAIN CASSETTE
CYV S/M/L-DK-C
BIDDLE AIR CURTAIN RECESSED
CYV S/M/L-DK-R
4
I
3
Door height (m)
3.0m
3
3
Product name
2.3m
2.5m
2.4m
2.75m
2.3m
2.15m
2.5m
2.0m
2
Biddle air curtain range for VRV
1
Favourable
Normal
ex: covered shopping mall or ex: little direct wind, no
revolving door entrance
opposite open doors, building
with ground floor only
4
Unfavourable
ex: location at a corner or
square, multiple floors
and / or open stairwell
Installation condition
Hydrobox range
Capacity
Product name
leaving water
temperature range
LOW TEMPERATURE HYDROBOX 1
HXY-A
5°C - 45°C
HIGH TEMPERATURE HYDROBOX 2
HXHD-A
25°C - 80°C
Type
80
125
NOTES
1
Only connectable to RYYQ-T / RXYQ-T
2
Only connectable to REYAQ-P
Network solutions
User friendliness
Max. Indoors groups
Scheduling presets (programs)
ACNSS connection
air conditioning network service system
Free cooling changeover
Sliding t° avoids overcooling via sensor
0°⌬ Between cooling & heating
Other control functions
Pre cooling / heating
Http option
Web acces & control
Ppd
Visualisation
Graphical report
Options
Control via GSM
Daily/monthly/yearly reports
Touch screen
Malfunction code
Indication filter replacement
Basic monitoring functions:
ON/OFF status, operation mode, set point temp.
Monitoring
Fire emergency stop control
Weekly schedule control
Automatic changeover
Basic control functions:
ON/OFF, temp. Setting, air flow settings
Control
Password security
5
+
4
8
+++
64
100
+++
512
DTA113B51
+
INTELLIGENT
TOUCH
CONTROLLER
++
INTELLIGENT
TOUCH MANAGER
+++
DMS-IF1
N/A
N/A
64
BACNET2
N/A
N/A
4x64
NOTES
1
Interface for Lonworks networks
2
Interface for BACnet networks
• VRV Systems • Introduction
5
• Introduction
6
Possible outdoor units using R-410A
6-1
Outdoor unit range
: component is connectable
x : component is not connectable
Not all components are connectable
at the same time to one outdoor unit.
Refer to the engineering databook for
more information.
I
6
Capacity (HP)
RXYQ-T
Heat pump without
continuous heating
*1
*1
*1
Control
systems
Air
curtain
Hydrobox
connection
 x   
    

 x   
RXYSQ-P8V1 (Single phase)
RXYSQ-P8Y1 (Three phase)
   x 

x x   
RTSYQ-PA
Heat pump
optimised for heating
 x   

x x   
RXYCQ-A
 x   x
x
x x   
REYQ-P8/P9
Small footprint combination
 x   

x x   
REYHQ-P
High COP combination
 x   

x x   
REYAQ-P
for connection with
heating only hydrobox
 x   

x    
RWEYQ-T
 x   

 x   
 x   

x x   
Low temperature hydrobox for VRV
High temperature hydrobox for VRV
Individual control (such as BRC)
Centralised control (such as DCS3*/DST)
Network solutions (such as DCS6*/DAM/DMS)
*1
Biddle Air curtain for VRV (CYV)
*1
VRV type indoor units (such as FXSQ)
Residential type indoor units (such as Daikin Emura)
Heat Reclaim ventilation (such as VAM)
Fresh air indoor units (such as FXMQ-MF)
AHU connection kit (such as EKEXV)
*1

HEATRECOVERY
HEAT
RECOVERY
HEAT PUMP
WATER
COOLED
RYYQ-T
Heat pump with
continuous heating
    
AIR COOLED
HEAT PUMP
4 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
Ventilation
Product name
Indoor
unit
System Type
22
Capacity (HP)
System Type
Product name
4 5 8 10 12 13 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
REPLACEMENT VRV
HEAT RECOVERY HEAT PUMP
AIR COOLED
Capacity class
140
280
360
460
500
540
*1
*1
*1
RXYQQ-T
VRVIV - Q - H/P
-Q
RQCEQ-P
VRVIII-Q - H/R
Single unit
Multi combination
NOTES
*1 Not a standard combination (free combination)
6
• VRV Systems • Introduction
636
712
744
816
848
• Introduction
6
Possible outdoor units using R-410A
6-2
VRV Heat Pump
3
6 - 2 - 1 Small footprint combination
VRV IV heat pump
Possible combination1
N° of outdoor units
N° of compressors
N° of connectable indoor
units
Minimum capacity index
Maximum capacity index
I
6
RYYQ8T / RXYQ8T
RYYQ8T / RXYQ8T
1
1
max 172
100
260
RYYQ10T / RXYQ10T
RYYQ10T / RXYQ10T
1
1
max 212
125
325
RYYQ12T / RXYQ12T
RYYQ12T / RXYQ12T
1
1
max 262
150
390
RYYQ14T / RXYQ14T
RYYQ14T / RXYQ14T
1
2
max 302
175
455
RYYQ16T / RXYQ16T
RYYQ16T / RXYQ16T
1
2
max 342
200
520
RYYQ18T / RXYQ18T
RYYQ18T / RXYQ18T
1
2
max 392
225
585
RYYQ20T / RXYQ20T
RYYQ20T / RXYQ20T
2
2
max 43 2
250
650
RYYQ22T / RXYQ22T
RYMQ10T + RYMQ12T /
RXYQ10T + RXYQ12T
2
2
2
max 47
275
715
RYYQ24T / RXYQ24T
RYMQ8T + RYMQ16T /
RXYQ8T + RXYQ16T
2
3
max 522
300
780
RYYQ26T / RXYQ26T
RYMQ12T + RYMQ14T /
RXYQ12T + RXYQ14T
2
3
max 562
325
845
RYYQ28T / RXYQ28T
RYMQ12T + RYMQ16T /
RXYQ12T + RXYQ16T
2
3
max 60 2
350
910
RYYQ30T / RXYQ30T
RYMQ12T + RYMQ18T /
RXYQ12T + RXYQ18T
2
3
max 64 2
375
975
RYYQ32T / RXYQ32T
RYMQ16T + RYMQ16T /
RXYQ16T + RXYQ16T
2
4
max 64 2
400
1,040
RYYQ34T / RXYQ34T
RYMQ16T + RYMQ18T /
RXYQ16T + RXYQ18T
2
4
max 64 2
425
1,105
RYYQ36T / RXYQ36T
RYMQ16T + RYMQ20T /
RXYQ16T + RXYQ20T
2
4
max 64 2
450
1,170
RYYQ38T / RXYQ38T
RYMQ8T + RYMQ10T + RYMQ20T /
RXYQ8T + RXYQ10T + RXYQ20T
3
4
max 64 2
475
1,235
RYYQ40T / RXYQ40T
RYMQ10T + RYMQ12T + RYMQ18T /
RXYQ10T + RXYQ12T + RXYQ18T
3
4
max 64 2
500
1,300
RYYQ42T / RXYQ42T
RYMQ10T + RYMQ16T + RYMQ16T /
RXYQ10T + RXYQ16T + RXYQ16T
3
5
max 64 2
525
1,365
RYYQ44T / RXYQ44T
RYMQ12T + RYMQ16T + RYMQ16T /
RXYQ12T + RXYQ16T + RXYQ16T
3
5
max 64 2
550
1,430
RYYQ46T / RXYQ46T
RYMQ14T + RYMQ16T + RYMQ16T /
RXYQ14T + RXYQ16T + RXYQ16T
3
6
max 64 2
575
1,495
RYYQ48T / RXYQ48T
RYMQ16T + RYMQ16T + RYMQ16T /
RXYQ16T + RXYQ16T + RXYQ16T
3
6
max 64 2
600
1,560
RYYQ50T / RXYQ50T
RYMQ16T + RYMQ16T + RYMQ18T /
RXYQ16T + RXYQ16T + RXYQ18T
3
6
max 64 2
625
1,625
RYYQ52T / RXYQ52T
RYMQ16T + RYMQ18T + RYMQ18T /
RXYQ16T + RXYQ18T + RXYQ18T
3
6
max 64 2
650
1,690
RYYQ54T / RXYQ54T
RYMQ18T + RYMQ18T + RYMQ18T /
RXYQ18T + RXYQ18T + RXYQ18T
3
6
max 64 2
675
1,755
NOTES
1
VRV IV offers free combinations, the above combination is only one of the possibilities.
2
Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio
restriction for the system (50% <= CR <= 130%)
6 - 2 - 2 VRVIII-C Heat pump optimized for heating
VRVIII heat pump
Fixed combinations
N° of outdoors
N° of compressors
N° of connectable indoor
units
Minimum capacity index
Maximum capacity index
RTSYQ10PA
RTSQ10PA + BTSQ20P
1 + function unit
2+1
21
125
325
RTSYQ14PA
RTSQ14PA + BTSQ20P
1 + function unit
3+1
30
175
455
RTSYQ16PA
RTSQ16PA + BTSQ20P
1 + function unit
3+1
34
200
520
RTSYQ20PA
RTSQ8PA + RTSQ12PA + BTSQ20P
2 + function unit
3+1
43
250
650
• VRV Systems • Introduction
7
• Introduction
I
6
6
Possible outdoor units using R-410A
6-2
VRV Heat Pump
6 - 2 - 3 VRVIII-S
N° of connectable indoor
units
VRVIII-S
N° of outdoors
N° of compressors
RXYSQ4P8V1/RXYSQ4P8Y1
1
1
8
50
130
RXYSQ5P8V1/RXYSQ5P8Y1
1
1
10
62.5
162.5
RXYSQ6P8V1/RXYSQ6P8Y1
1
1
13
75
195
VRV Classic
N° of outdoor units
N° of compressors
N° of connectable indoor
units
Minimum capacity index
Maximum capacity index
Minimum capacity index
Maximum capacity index
6 - 2 - 4 VRV Classic
8
RXYCQ8A
1
1
16
100
240
RXYCQ10A
1
1
20
125
300
RXYCQ12A
1
2
24
150
360
RXYCQ14A
1
2
28
175
420
RXYCQ16A
1
3
32
200
480
RXYCQ18A
1
3
36
225
540
RXYCQ20A
1
3
40
250
600
• VRV Systems • Introduction
• Introduction
6
Possible outdoor units using R-410A
6-3
VRV Heat Recovery
3
6 - 3 - 1 Small footprint combination
I
VRVIII heat reovery
Fixed combinations
N° of outdoors
N° of compressors
N° of connectable indoor
units
Minimum capacity index
Maximum capacity index
REYQ8P9
REYQ8P9
1
2
17
100
260
REYQ10P8
REYQ10P8
1
2
21
125
325
REYQ12P9
REYQ12P9
1
2
26
150
390
REYQ14P8
REYQ14P8
1
2
30
175
455
REYQ16P8
REYQ16P8
1
2
34
200
520
REYQ18P9
REMQ8P9 + REMQ10P8
2
3
39
225
585
REYQ20P9
REMQ8P9 + REMQ12P8
2
3
43
250
650
REYQ22P8
REMQ10P 8+ REMQ12P8
2
4
47
275
715
REYQ24P8
REMQ12P8 + REMQ12P8
2
4
52
300
780
REYQ26P8
REMQ10P8 + REMQ16P8
2
5
56
325
845
REYQ28P8
REMQ12P8 + REMQ16P8
2
5
60
350
910
REYQ30P8
REMQ14P8 + REMQ16P8
2
6
64
375
975
REYQ32P8
REMQ16P8 + REMQ16P8
2
6
64
400
1,040
REYQ34P9
REMQ8P9 + REMQ10P8 + REMQ16P8
3
6
64
425
1,105
REYQ36P9
REMQ8P9 + REMQ12P8 + REMQ16P8
3
6
64
450
1,170
REYQ38P8
REMQ10P8 + REMQ12P8 + REMQ16P8
3
7
64
475
1,235
REYQ40P8
REMQ12P8 + REMQ12P8 + REMQ16P8
3
8
64
500
1,300
REYQ42P8
REMQ10P8 + REMQ16P8 + REMQ16P8
3
8
64
525
1,365
REYQ44P8
REMQ12P8 + REMQ16P8 + REMQ16P8
3
8
64
550
1,430
REYQ46P8
REMQ14P8 + REMQ16P8 + REMQ16P8
3
8
64
575
1,495
REYQ48P8
REMQ16P8 + REMQ16P8 + REMQ16P8
3
9
64
600
1,560
6
6 - 3 - 2 High COP combination
VRVIII heat reovery
Fixed combinations
N° of outdoors
N° of compressors
N° of connectable indoor
units
Minimum capacity index
Maximum capacity index
REYHQ16P
REMQ8P9 + REMQ8P9
2
2
34
200
520
REYHQ20P
REMQ8P9 + REMHQ12P8
2
3
43
225
585
REYHQ22P
REMQ10P8 + REMHQ12P8
2
4
47
250
650
REYHQ24P
REMQ12P8 + REMHQ12P8
2
4
52
275
715
6 - 3 - 3 With connection to heating only hydrobox
VRVIII heat reovery
N° of outdoors
N° of compressors
N° of connectable indoor units
Minimum capacity index
Maximum capacity index
REYAQ10P
1
2
21
125
325
REYAQ12P
1
2
26
150
390
REYAQ14P
1
2
30
175
455
REYAQ16P
1
2
34
200
520
• VRV Systems • Introduction
9
• Introduction
6
Possible outdoor units using R-410A
6-4
Replacement VRV
HP
Cooling
capacity
kW
Heating
capacity
kW
N° of
outdoors
N° of
compressors
N° of
connectable
indor units
130%
120%
110%
100%
90%
80%
70%
60%
50%
RQEQ140P + RQEQ140P
10
28.0
32.0
2
2
21
364
336
308
280
252
224
196
168
140
RQCEQ360P
RQEQ180P + RQEQ180P
13
36.0
40.0
2
2
28
468
432
396
360
324
288
252
216
180
RQCEQ460P
RQEQ140P + RQEQ140P + RQEQ180P
16
45.0
52.0
3
3
34
598
552
506
460
414
368
322
276
230
RQCEQ500P
RQEQ140P + RQEQ180P + RQEQ180P
18
50.0
56.0
3
3
39
650
600
550
500
450
400
350
300
250
RQCEQ540P
RQEQ180P + RQEQ180P + RQEQ180P
20
54.0
60.0
3
3
43
702
648
594
540
486
400
378
324
270
RQCEQ636P
RQEQ212P + RQEQ212P + RQEQ212P
22
63.6
67.2
3
3
47
827
763
699
636
572
508
445
381
318
RQCEQ712P
RQEQ140P + RQEQ180P + RQEQ180P + RQEQ212P
24
71.2
78.4
4
4
52
926
854
783
712
640
569
498
427
356
RQCEQ744P
RQEQ140P + RQEQ180P + RQEQ212P + RQEQ212P
26
74.4
80.8
4
4
56
967
892
818
744
669
595
520
446
372
RQCEQ816P
RQEQ180P + RQEQ212P + RQEQ212P + RQEQ212P
28
81.6
87.2
4
4
60
1,061
979
897
816
734
652
571
489
408
RQCEQ848P
RQEQ212P + RQEQ212P + RQEQ212P + RQEQ212P
30
84.8
89.6
4
4
64
1,102
1,017
932
848
763
678
593
508
424
Heating
capacity
kW
N° of
outdoors
N° of compressors
HP
Cooling
capacity
kW
I
Replacement VRV Heat recovery
Fixed combinations
RQCEQ280P
6
Replacement
VRV
- Heat pump
Fixed combinations
RQYQ140P
RQYQ140P
5
14.0
16.0
1
RXYQQ8T
RXYQQ8T
8
22.4
25
RXYQQ10T
RXYQQ10T
10
28
RXYQQ12T
RXYQQ12T
12
RXYQQ14T
RXYQQ14T
RXYQQ16T
130%
120%
110%
100%
90%
80%
70%
60%
50%
1
10
162.5
150
137.5
125
112.5
100
87.5
75
62.5
1
1
641
260
240
220
200
180
160
140
120
100
31.5
1
1
641
325
300
275
250
225
200
175
150
125
33.5
37.5
1
1
641
390
360
330
300
270
240
210
180
150
14
40
45
1
2
641
455
420
385
350
315
280
245
210
175
RXYQQ16T
16
45
50
1
2
641
520
480
440
400
360
320
280
240
200
RXYQQ18T
RXYQQ18T
18
50
56
1
2
641
585
540
495
450
405
360
315
270
225
RXYQQ20T
RXYQQ20T
20
56
63
1
2
641
650
600
550
500
450
400
350
300
250
RXYQQ22T
RXYQQ10T + RXYQQ12T
22
61.5
69
2
2
641
715
660
605
550
495
440
385
330
275
RXYQQ24T
RXYQQ8T+RXYQQ16T
24
67.4
75
2
3
641
780
720
660
600
540
480
420
360
300
RXYQQ26T
RXYQQ12T+RXYQQ14T
26
73.5
82.5
2
3
641
845
780
715
650
585
520
455
390
325
RXYQQ28T
RXYQQ12T+RXYQQ16T
28
78.5
87.5
2
3
641
910
840
770
700
630
560
490
420
350
3
64
1
975
900
825
750
675
600
525
450
375
4
64
1
1,040
960
880
800
720
640
560
480
400
4
641
1,105
1,020
935
850
765
680
595
510
425
1
RXYQQ32T
RXYQQ34T
RXYQQ12T+RXYQQ18T
RXYQQ16T+RXYQQ16T
RXYQQ16T+RXYQQ18T
Capacity range
30
32
34
83.5
90
95
93.5
100
106
2
2
2
Indoor unit combination ratio
RXYQQ36T
RXYQQ16T+RXYQQ20T
36
101
113
2
4
64
1,170
1,080
990
900
810
720
630
540
450
RXYQQ38T
RXYQQ8T+RXYQQ10T+RXYQQ20T
38
106
120
3
4
641
1,235
1,140
1,045
950
855
760
665
570
475
4
641
1,300
1,200
1,100
1,000
900
800
700
600
500
5
1
1,365
1,260
1,155
1,050
945
840
735
630
525
RXYQQ40T
RXYQQ42T
10
Indoor unit combination ratio
N° of
connectable
indoor units
RXYQQ30T
1
Capacity range
RXYQQ10T+RXYQQ12T+RXYQQ18T
RXYQQ10T+RXYQQ16T+RXYQQ16T
40
42
112
118
125
132
3
3
64
Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
• VRV Systems • Introduction
• Introduction
6
Possible outdoor units using R-410A
6-5
VRV-WIII
3
6 - 5 - 1 Unified standard and geothermal series
Fixed combinations
N° of outdoors
N° of compressors
N° of connectable
indoor units
Minimum capacity
index
Maximum capacity
index
RWEYQ8T
1
1
17
100
260
RWEYQ10T
RWEYQ10T
1
1
21
125
325
RWEYQ16T
RWEYQ8T + RWEYQ8T
2
2
34
200
520
RWEYQ18T
RWEYQ8T + RWEYQ10T
2
2
36
225
585
RWEYQ20T
RWEYQ10T + RWEYQ10T
2
2
36
250
650
RWEYQ24T
RWEYQ8T + RWEYQ8T + RWEYQ8T
3
3
36
300
780
RWEYQ26T
RWEYQ8T + RWEYQ8T + RWEYQ10T
3
3
36
325
845
RWEYQ28T
RWEYQ8T + RWEYQ10T + RWEYQ10T
3
3
36
350
910
RWEYQ30T
RWEYQ10T + RWEYQ10T + RWEYQ10T
3
3
36
375
975
VRV IV W-series
heat pump
VRV IV W-series
heat recovery
RWEYQ8T
6-6
I
6
Indoor unit capacity index
Model
15
20
25
32
40
50
63
71
80
100
125
200
250
Capacity index
15
20
25
31.25
40
50
62.5
71
80
100
125
200
250
• VRV Systems • Introduction
11
• Introduction
I
7
Nomenclature
7-1
Indoor units
F
X
F
Q
40
A
7
VE
B
Special series for Europe (CE approved)*
Power supply symbol
V1: 1~, 220-240V, 50Hz
V3: 1~, 230V, 50Hz
VE: 1~, 220-240V, 50Hz
M/P/A:Indicates major design category
7/8/9: Indicates DENV production
Capacity Indication
Conversion to horsepower:
15: 0.6HP
20: 0.8HP
25: 1HP
32: 1.25HP
40: 1.6HP
50: 2.0HP
63: 2.5HP
80: 3.2HP
100: 4HP
125: 5HP
200: 8HP
250: 10HP
Indicates the use of R-410A
Model name
F:
Roundflow ceiling mounted cassette
Z:
4-way blow ceiling mounted cassette (600x600mm)
C:
2-way blow ceiling mounted cassette
K:
Ceiling mounted corner cassette
S:
Concealed ceiling unit
D:
Concealed ceiling unit (small)
M: Concealed ceiling unit (large)
H:
Ceiling suspended unit
A:
Wall mounted unit
L:
Floor standing unit
LM: Concealed floor standing unit
X:
inverter
F:
indoor unit
* B is not mandatory for indoor units
12
• VRV Systems • Introduction
• Introduction
7
Nomenclature
7-2
Biddle air curtains
CY
V
S
150
DK
80
F
S
3
C
C = controller standard; N = no controller
Color. B = White (RAL6010), S: Grey (RAL 9006)
I
7
Installation type: F = Freehanging, C = Cassette, R = Recessed
Capacity class (kW)
Daikin direct expansion
Door width (cm)
Range. S = Small, M = Medium, L = Large
V = connectable to VRV; Q = connectable to ERQ
Biddle air curtain
• VRV Systems • Introduction
13
• Introduction
I
7
Nomenclature
7-3
Ventilation units
V
A
M
500
F
B
VE
Ventilation
7
Air
Mounted type
Air flow rate (m3/h)
Major design category
Design category for EC application
Power supply
VE: Single Phase 50 Hz 220-240V,
60 Hz 200V
V
K
M
50
GB
M
V1
Ventilation
Outdoor Air Treatment Type
Mounted type
Nominal Air flow rate 50 : 500 m3/h, 80 : 750 m3/h, 100 : 950 m3/h
Major design category
Moisture (M : With Humidifier Elements, nothing : without Humidifier Elements)
Power supply
V1: Single Phase 50 Hz 220-240V,
7-4
H
X
Hydroboxes
H
D
125
A
7
V1
B
Hydrobox
Inverter
H = heating only; Y = heat pump (reversible)
D = incl. domestic hot water; nothing = no domestic hot water possible
Capacity indication Conversion to horsepower: 125: 5HP
Major design category
7/8/9: Indicates DENV production
Power supply
V1: Single Phase 50 Hz 220-240V,
Special series for europe (CE approved)*
*B is not mandatory for indoor units
14
• VRV Systems • Introduction
• Introduction
7
Nomenclature
7-5
Outdoor units
RX
Y
S
Q
5
P8
3
V1
B
Special series for Europe (CE approved)
Power supply symbol:
V1 : 1N~, 220-240V, 50Hz
V3: 1N~, 230V, 50Hz
W1: 3N~, 400V, 50Hz
Y1: 3N~, 380-415V, 50Hz
P, P7, T, A: indicates major design category (internal company symbol)
5: 5HP
8: 8HP
10: 10HP
12:12HP
14:14HP
16:16HP
I
7
etc.
Indicates the use of R-410A
S: small capacity
A: connectable to hydroboxes
C: 2nd layer VRV (VRV classic)
Q: replacement series
Y: heat pump
RE: indicates that this is a HEAT RECOVERY outdoor unit
RX: indicates that this is a HEAT PUMP outdoor unit
RY: indicates that this is a HEAT PUMP CONTINUOUS HEATING outdoor unit
RQ: indicates that this is a R-22 REPLACEMENT outdoor unit
RT: indicates that this is a LOW AMBIENT outdoor unit
RWE: Indicates that this is a WATER COOLED outdoor unit (heat recovery and heat pump)
• VRV Systems • Introduction
15
Daikin products are distributed by:
The present publication is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
compiled the content of this publication to the best of its knowledge. No express
or implied warranty is given for the completeness, accuracy, reliability or fitness
for particular purpose of its content and the products and services presented
therein. Specifications are subject to change without prior notice. Daikin Europe
N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest
sense, arising from or related to the use and/or interpretation of this publication.
All content is copyrighted by Daikin Europe N.V..
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
EEDEN14-200_1 • CD • 10/13 • Copyright Daikin
The present publication supersedes EEDEN13-200
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern
for the environment is set in the EMAS and ISO 14001 systems.
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende
VRV products are not within the scope of the
Eurovent certification programme.