Whirlpool Indirect-Fired Water Heater Specifications

Add to my manuals
35 Pages

advertisement

Whirlpool Indirect-Fired Water Heater Specifications | Manualzz

SuperStor Ultra

Indirect Fired

Water Heaters

INSTALLATION

START-UP

MAINTENANCE

PARTS

For Residential and Commercial Use

This manual must only be used by a qualified installer/service technician. Read all instructions in this manual before installing. Perform steps in the given order. Failure to comply could result in substantial property damage, severe personal injury, or death.

NOTICE: HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors in literature.

The surfaces of these products contacted by consumable water contain less than 0.25% lead by weight, as required by the Safe

Drinking Water Act, Section 1417.

NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.

120 Braley Rd. P.O. Box 429 East Freetown, MA 02717-0429 www.htproducts.com

LP-83 Rev. 8.14.14

2

The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important product information.

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.

FOREWORD

This manual is intended to be used in conjunction with other literature provided with the SuperStor Ultra Indirect Fired Water Heater.

This includes all related control information. It is important that this manual, all other documents included with this system, and additional publications including the Code for the Installation of Heat Producing Appliances (latest version), be reviewed in their entirety before beginning any work.

Installation should be made in accordance with the regulations of the local code authorities and utility companies which pertain to this type of water heating equipment.

FOR THE INSTALLER

This water heater must be installed by qualified and licensed personnel. The installer should be guided by the instructions furnished with the water heater, and with local codes and utility company requirements.

INSTALLATIONS MUST COMPLY WITH:

Local, state, provincial, and national codes, laws, regulations and ordinances.

TABLE OF CONTENTS

PART 1 – GENERAL SAFETY INFORMATION .......................................................................................................................... 3

A. PRECAUTIONS .......................................................................................................................................................................... 3

B. WHEN SERVICING THE WATER HEATING SYSTEM .............................................................................................................. 4

C. HEATER WATER ....................................................................................................................................................................... 4

D. FREEZE PROTECTION ............................................................................................................................................................. 4

E. CHEMICAL VAPOR CORROSION ............................................................................................................................................. 4

F. WATER TEMPERATURE ADJUSTMENT .................................................................................................................................. 5

PART 2

– PREPARE THE WATER HEATER ............................................................................................................................. 5

A. REDUCED BOILER INPUT SIZING GUIDE ............................................................................................................................... 8

B. PERFORMANCE AND SIZING GUIDELINES ............................................................................................................................ 9

C. LOCATING THE WATER HEATER ............................................................................................................................................ 9

D. WATER CHEMISTRY REQUIREMENTS ................................................................................................................................. 10

LP-83 Rev. 8.14.14

3

PART 3 – PIPING ...................................................................................................................................................................... 11

A. PLUMBING ............................................................................................................................................................................... 11

B. BOILER CONNECTIONS ......................................................................................................................................................... 11

C. DOMESTIC PIPING INLET ....................................................................................................................................................... 11

D. TEMPERATURE AND PRESSURE RELIEF VALVE................................................................................................................ 11

E. SCALDING ................................................................................................................................................................................ 12

F. POTABLE EXPANSION TANK ................................................................................................................................................. 13

G. PRESSURE DROP SIZING FOR CIRCULATOR ..................................................................................................................... 13

H. PIPING ...................................................................................................................................................................................... 14

PART 4

– HEATER CONTROL AND WIRING .......................................................................................................................... 23

A. CONTROL ................................................................................................................................................................................ 23

B. WIRING ..................................................................................................................................................................................... 23

C. WIRING DIAGRAMS ................................................................................................................................................................ 24

PART 5

– START-UP AND OPERATION.................................................................................................................................. 31

PART 6 – MAINTENANCE AND TROUBLESHOOTING .......................................................................................................... 33

HTP CUSTOMER INSTALLATION RECORD FORM...................................................................................................................... 35

PART 1 – GENERAL SAFETY INFORMATION

A. PRECAUTIONS

This water heater is approved for indoor installations only, and it not intended for use as a pool heater. Clearance to combustible materials: 0” top, bottom, sides and back. Heater must have room for service: 24” front and 6” sides are minimum recommended service clearances. (A combustible door or removable panel is acceptable front clearance.) This water heater has been approved for closet installation, and installation on combustible flooring. Install the water heater in a location where temperature and pressure relief valve discharge or a leak will not result in damage to the surrounding area. If such a location is not available, install an auxiliary catch pan.

INSTALLER

Read all instructions in this manual before installing. Perform steps in the order given.

USER This manual is for use only by a qualified heating installer/service technician. Have this heater serviced/inspected by a qualified service technician annually.

FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE

PERSONAL INJURY, OR DEATH.

NOTE: If the heater is exposed to the following, do not operate until all corrective steps have been made by a qualified serviceman:

1. FIRE

2. DAMAGE

3. WATER

Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.

High heat sources (sources generating heat 100 o

F / 37 o

C or greater, such as stove pipes, space heaters, etc.) may damage plastic components of the water heater as well as plastic vent pipe materials. Such damages ARE NOT covered by warranty. It is recommended to keep a minimum clearance of 8” from high heat sources. Observe heat source manufacturer instructions, as well as local, state, provincial, and national codes, laws, regulations and ordinances when installing this water heater and related components near high heat sources.

LP-83 Rev. 8.14.14

NOTE: OBTAIN ALL APPLICABLE PERMITS AND OBEY ALL LOCAL CODES.

NOTE: Install all system components and piping in such a manner that does not reduce the performance of any fire rated assembly.

DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN UNDERWATER. Immediately call a qualified service technician.

4

Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.

B. WHEN SERVICING THE WATER HEATING SYSTEM

To avoid electric shock, disconnect electrical supply before performing maintenance.

To avoid severe burns, allow water heater and associated equipment to cool before servicing.

C. HEATER WATER

Do not use petroleum-based cleaning or sealing compounds in a water heating system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.

 Do not use “homemade cures” or “heater patent medicines”. Damage to heater, substantial property damage, and/or serious personal injury may result.

NOTICE FOR SINGLE-WALL HEAT EXCHANGER MODELS

Per the Uniform Plumbing Code:

Single-wall heat exchangers are permitted if they satisfy all of the following requirements:

1. The heat transfer medium is potable water or contains only substances which are recognized as safe by the U.S. Food and

Drug Administration (FDA).

2. The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of the potable water system (steam systems must comply with this statement).

3. The equipment is permanently labeled to indicate that only additives recognized as safe by the FDA shall be used as the heat transfer medium.

Other heat exchanger designs may be permitted where approved by the Administrative Authority.

D. FREEZE PROTECTION

NOTE: Consider piping and installation when determining heater location. Place water heater as close to the boiler as possible, in a location not prone to freezing.

Failure of the water heater due to freeze related damage IS NOT covered by warranty.

In water heaters with single wall heat exchangers, the heat transfer fluid must be water or nontoxic food grade glycol, FDA rated

“generally recognized as safe” (GRAS) and having a toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial

Products, 5 th

edition. Ensure the system is permanently labeled to indicate any additives used in the heat transfer fluid.

NEVER use any toxic chemical, including automotive, standard glycol antifreeze, or ethylene glycol made for hydronic (non-potable) systems. These chemicals can attack gaskets and seals in water systems, are poisonous if consumed, and can cause injury or death.

E. CHEMICAL VAPOR CORROSION

NOTE: DAMAGE TO THE WATER HEATER OR RELATED COMPONENTS CAUSED BY EXPOSURE TO CORROSIVE VAPORS

IS NOT COVERED BY WARRANTY. The limited warranty is voided when failure of water tank is due to a corrosive atmosphere. (Refer to the limited warranty for complete terms and conditions).

LP-83 Rev. 8.14.14

5

PRODUCTS TO AVOID

Spray cans containing fluorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric or Muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, laundry detergents, and cleaning solvents

Adhesives used to fasten building products

Table 1 – Chemical Contaminants

F. WATER TEMPERATURE ADJUSTMENT

If the water heater is going to have a set temperature above 120 o

F, you must use an

ASSE 1017 rated mixing valve to avoid severe burns or death from scalding temperature.

AREAS LIKELY TO HAVE CONTAMINANTS

Dry cleaning/laundry areas and establishments

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

Auto body shops

Plastic manufacturing plants

Furniture refinishing areas and establishments

New building construction

Remodeling areas

Garages and workshops

Households with small children, disabled, or elderly persons may require a

120 o

F or lower temperature setting to prevent severe personal injury or death due to scalding.

APPROXIMATE TIME / TEMPERATURE RELATIONSHIPS IN SCALDS

120 o

F More than 5 minutes

125 o

F

130 o

135 o

F

F

1 ½ to 2 minutes

About 30 seconds

About 10 seconds

140 o

F

145 o

F

150 o

155 o

F

F

Less than 5 seconds

Less than 3 seconds

About 1 ½ seconds

About 1 second

Table 2

PART 2 – PREPARE THE WATER HEATER

UNCRATING HEATER

– Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.

COLD WEATHER HANDLING – If the heater has been stored in a very cold location (BELOW 0 o

F) before installation, handle with care until the plastic components come to room temperature.

Remove all sides of the shipping crate to allow the heater to be moved into its installation location.

LP-83 Rev. 8.14.14

6

Figure 1

– Dimensions

LP-83 Rev. 8.14.14

7

Figure 2 - Specifications

CONTINUOUS FLOW PERFORMANCE CALCULATION

FIRST HOUR RATING – (.75 X TANK CAPACITY) = CONTINUOUS FLOW

EXAMPLE: SSU-45C = 314

– (.75 X 45) = 280.25

LP-83 Rev. 8.14.14

8

A. REDUCED BOILER INPUT SIZING GUIDE

NOTE: IT IS NOT RECOMMENDED TO REDUCE BOILER INPUT WHEN USING DOUBLE WALL TANKS.

MODEL

GROSS OUT

BTU/HR

199,000

GROSS OUT

BTU/HR

220,000

GROSS OUT

BTU/HR

240,000

GROSS OUT

BTU/HR

260,000

GROSS OUT

BTU/HR

280,000

GROSS OUT

BTU/HR

300,000

SSU-60

SSU-80

A

B

A

B

A

370

266

489

359

457

370

266

503

370

470

370

266

503

370

543

-

-

503

-

627

-

-

503

370

645

SSU-119 B 335 345 399 460 474

Table 3

– DESCRIBES COLD START FIRST HOUR RATINGS (A and B) AND BOILER SIZE

-

-

503

370

645

474

GROSS OUT

BTU/HR

320,000

-

-

-

-

645

474

PRODUCT LINE CONSISTS OF VARIOUS MODELS AVAILABLE IN DIFFERENT SIZES

CALL THE FACTORY FOR PRODUCT AND WARRANTY INFORMATION

“DW” (double wall heat exchanger) models are available in the 45, 60, 80, and 119 US gallon sizes.

“C” commercial models for dual systems or commercial applications; use one coil for wood boiler, the other for oil boiler; adaptable to solar systems as well; good for hotels, motels, and apartments. Models are available in the 45, 60, 80, and 119 US gallon sizes.

DETERMINE AMOUNT OF DOMESTIC HOT WATER NEEDED. THEN USE THE CHART BELOW TO OPTIMIZE SUPERSTOR

ULTRA AND BOILER SIZING.

NOTE: FIRST DRAW AT 140 o

F at 90 o

F ΔT. (FOR PERFORMANCE AT 115 o

F, MULTIPLY BY 1.56 FOR MINUTES OF WATER DRAW.)

LINE A GALLONS - LOW MASS BOILERS THAT TAKE LESS THAN 90 SECONDS TO HEAT TO TEMPERATURE

LINE B GALLONS - HIGH MASS BOILERS THAT TAKE GREATER THAN 90 SECONDS TO HEAT TO TEMPERATURE

MODEL 2 GPM 2.5 GPM 3 GPM 3.5 GPM 4 GPM 4.5 GPM 5 GPM

SSU-20

SSU-30

SSU-30LB

SSU-45

SSU-45C

SSU-60

B

A

B

A

A

B

A

B

A

B

A

B

A

9.5

8.5

16.0

14.0

18.0

17.0

23.0

18.0

45.0

8.0

7.5

13.0

12.0

14.0

12.0

18.0

15.0

24.0

7.0

6.5

10.0

9.0

12.0

10.0

14.0

13.0

26.0

5.5

5.0

7.5

7.0

9.0

8.0

11.0

10.0

29.0

18.0

4.5

4.0

6.0

5.5

6.5

6.0

8.5

7.5

20.0

16.0

36.0

29.0

4.0

3.5

5.5

5.0

6.0

5.5

7.5

7.5

17.0

13.0

30.0

19.0

46.0

3.5

3.0

5.0

4.5

5.5

5.0

7.0

6.5

14.0

10.0

22.0

12.0

29.0

SSU-60C B ∽ ∽ ∽ ∽ ∽ 30.0 21.0

SSU-80

SSU-80C

A

B

A

B

∽ A

SSU-119

SSU-119C

B

A

B

Table 4 - NOTE: THIS INFORMATION IS BASED ON BOILER SIZE CONFORMING TO THE MINIMUM BTU/H REQUIRED TO

ACHIEVE FIRST HOUR RATINGS, OBTAINABLE FROM CHART ABOVE. - Indicates infinity (continuous duty).

LP-83 Rev. 8.14.14

9

B. PERFORMANCE AND SIZING GUIDELINES

NOTE: TABLE 5 DESCRIBES MINIMUM BTU/H REQUIRED TO ACHIEVE THE LISTED FIRST HOUR RATING.

MODEL GROSS BOILER OUTPUT

140 o

F

90 o

F ΔT

127

77 o o

F

F ΔT

SSU-20

SSU-30

84,000 121 140

SSU-30LB

SSU-45

SSU-45C

SSU-60

SSU-60C

SSU-80

SSU-80C

102,000

113,000

141,000

215,000

174,000

245,000

212,000

154

169

212

314

266

354

330

180

198

248

367

311

414

386

SSU-119

SSU-119C

Table 5

331,000

269,999

425,000

490

423

637

573

495

745

115 o

F

65 o

F ΔT

168

212

234

292

414

370

467

440

647

564

841

C. LOCATING THE WATER HEATER

This water heater is certified for indoor use only. DO NOT INSTALL OUTDOORS. Outdoor installations ARE NOT covered by warranty.

Choose a location for the water heater as centralized to the piping system as possible. Also, locate the water heater and domestic water piping where it will not be exposed to freezing temperatures. All piping should be insulated. Additionally, place the water heater so that the drain, controls, and inlets/outlets are easily accessible.

Locate the water heater where any leakage from the relief valve, related piping, tank, or connections will not result in damage to surrounding areas or lower floors of the building. The water heater should be located near a floor drain, or installed in a drain pan. HTP will NOT be held liable for leakage damages.

NOTE: To save on heating costs and improve energy efficiency, keep the distance between the boiler and water heater to a minimum to reduce heat loss from excess piping and keep friction loss to a minimum. Ensure all piping between the boiler and water heater is properly insulated to minimize heat loss.

The water heater may be located some distance from the boiler provided the circulator meets flow requirements through the coil. The greater the distance from the water heater to the boiler, the longer the response will be to a call for domestic hot water.

This water heater must be installed vertical on a level surface.

Ensure water heater location can support the entire filled weight of the tank. Failure to properly support the tank could result in property damage, serious personal injury, or death.

Figure 3 – Recommended Service Clearances

LP-83 Rev. 8.14.14

10

NOTE: If you do not provide the minimum clearances shown in Figure 3, it might not be possible to service the heater without removing it from the space.

This water heater must not be located near flammable liquids such as gasoline, butane, liquefied propane, adhesives, solvents, paint thinners, etc., as the controls of this water heater could ignite these vapors and cause an explosion, resulting in property damage, severe personal injury, or death.

D. WATER CHEMISTRY REQUIREMENTS

Chemical imbalance of the water supply may affect efficiency and cause severe damage to the water heater and associated equipment.

HTP recommends having water quality professionally analyzed to determine whether it is necessary to install a water softener. It is important that the water chemistry on both the domestic hot water and central heating sides are checked before installing the water heater, as water quality will affect the reliability of the system. Failure of a water heater due to lime scale build-up, low pH, or other chemical imbalance IS NOT covered by the warranty.

Operating temperatures above 135 o

F will further accelerate the build-up of lime scale and may shorten the service life of the water heater. Failure of the water heater due to lime scale build-up on the heating surface, low pH, or other chemical imbalance IS NOT covered by the warranty.

Outlined below are water quality parameters which need to be met in order for the system to operate efficiently for many years.

Water Hardness

Water hardness is mainly due to the presence of calcium and magnesium salts dissolved in water. The concentration of these salts is expressed in mg/L, ppm, or grains per gallon as a measure of relative water hardness. Grains per gallon is the common reference measurement used in the U.S. water heater industry. Hardness expressed as mg/L or ppm may be divided by 17.1 to convert to grains per gallon. Water may be classified as very soft, slightly hard, moderately hard, or hard based on its hardness number. The minerals in the water precipitate out as the water is heated and cause accelerated lime scale accumulation on a heat transfer surface. This lime o scale build-up may result in premature failure of the water heater. Operating temperatures above 135 F will further accelerate the buildup of lime scale and may shorten the service life of the water heater.

Water that is classified as hard and very hard must be softened to avoid water heater failure.

CLASSIFICATION

Soft

Slightly Hard

Moderately Hard

Hard

Very Hard

MG/L OR PPM

0 – 17.1

17.1

– 60

60 – 120

120

– 180

180 and over

GRAINS/GAL

0 - 1

1

– 3.5

3.5 – 7.0

7.0

– 10.5

10.5 and over

If the hardness of the water exceeds the maximum level of 7 grains per gallon, water should be softened to a hardness level no lower than 5 grains per gallon. Water softened as low as 0 to 1 grain per gallon may be under-saturated with respect to calcium carbonate, resulting in water that is aggressive and corrosive. pH of Water pH is a measure of relative acidity, neutrality or alkalinity. Dissolved minerals and gases affect water pH. The pH scale ranges from 0 to

14. Water with a pH of 7 is considered neutral. Water with a pH lower than 7 is considered acidic. Water pH higher than 7 is considered alkaline. A neutral pH (around 7) is desirable for most potable water applications. Corrosion damage and tank failures resulting

from water pH levels of lower than 6 or higher than 8 ARE NOT covered by the warranty. The ideal pH range for water used in a water heater is 7.2 to 7.8.

Total Dissolved Solids

Total Dissolved Solids (TDS) is a measurement of all minerals and solids dissolved in a water sample. The concentration of total dissolved solids is usually expressed in parts per million (ppm).

Water with a high TDS concentration will greatly accelerate lime and scale formation in the hot water system. Most high TDS concentrations precipitate out of the water when heated. This can generate a scale accumulation that will greatly reduce the service life of a water heater.

The manufacturer of the water heater has no control over water quality, especially TDS levels in your system. Total dissolved solids in excess of 2,000 ppm will accelerate lime and scale formation on the element or heat exchanger. Water heater failure due to total

LP-83 Rev. 8.14.14

11 dissolved solids in excess of 2,000 ppm is a non-warrantable condition. Failure of a water heater due to lime scale build up IS NOT

covered by the warranty.

Hardness: 7 grains

Chloride levels: 100 ppm

pH levels: 6-8

TDS: 2000 ppm

Sodium: 20 mGL

PART 3 – PIPING

A. PLUMBING

It is mandatory that all plumbing be done in accordance with federal, local, and state plumbing codes and practices. Failure to properly install the water heater WILL VOID the warranty. It is also necessary to use both thread tape and pipe dope on all mechanical plumbing connections.

When filling the water heater, open a hot water tap to release air in the tank and piping. Failure to do so could lead to improper water heater operation.

B. BOILER CONNECTIONS

Use two wrenches when tightening water piping at heater. Use one wrench to prevent the heater return or supply line from turning.

Failure to prevent piping connections from turning could cause damage to heater components.

Use a 1” nominal minimum pipe size when piping with zone valves or circulators.

On the water heater, the boiler supply connects to the outlet of the circulator. The circulator inlet is to be connected to the hot outlet side of the boiler. Be sure that the arrow on the circulator is facing the correct flow direction. (See pressure drop sizing for circulator, this manual.) On the tank, the boiler return is to be connected to the return side of the boiler. The return(s) from heating loop(s) should have a flow check or swing check valve installed before the return pipe from the tank.

In a steam boiler, the tank supply must be connected to the boiler well below the minimum water level. A strainer and drain valve should be installed at the boiler for periodic draining of scale and sludge. Banging and steam bound traps will occur if the boiler water supplied to the heat exchanger has steam or is slightly above the low water cut off.

NOTE: It is possible to use live steam in the heat exchanger of the SuperStor Ultra 80 and 119 residential and commercial models

ONLY. Using any other Superstor Ultra model in live steam applications will result in product failure and VOID the warranty.

Never use dielectric fittings or galvanized steel fittings on any domestic water connections. Use only copper or brass fittings. Failure to follow this caution will result in premature heater failure. Such failure is NOT covered by warranty.

C. DOMESTIC PIPING INLET

Use both thread tape and pipe dope to connect an NPT brass tee. On the run, install a brass drain valve. In the branch, install an NPT male X ¾” (minimum) pipe adapter. A shut off valve between the city water supply and tank inlet is recommended for ease of service.

It may be recommended to use a back flow preventer

– check local codes. If a back flow preventer or a no return valve is used, a thermal expansion tank must be installed on the cold water supply between the tank and valve. If the tank is replacing a tankless coil in the boiler, disconnect coil plumbing and use the cold inlet pipe and hot water outlet pipes for the water heater.

D. TEMPERATURE AND PRESSURE RELIEF VALVE

On SSU-80 and SSU-119 residential and all commercial models, a ¾” temperature and pressure (T&P) port and relief valve are provided. On all other models, an appropriate T&P valve must be supplied and installed as described in Figure 4.

Use both thread tape and pipe dope to install an NPT brass T&P relief valve for hot water storage tanks, as required by local codes, but not less than valves certified as meeting the requirements for relief valves for hot water heaters (ANSI Z21.22 and CAN1-4.4) by a nationally recognized lab that maintains periodic inspection of production listed equipment. Make sure the relief valve is sized to the

BTU/Hour capacity and storage capacity of the water heater. The T&P relief valve must be plumbed down so discharge can exit at least

LP-83 Rev. 8.14.14

12

6” above the structural floor. The relief line cannot be in contact with any live electrical parts. If the relief valve constantly weeps, install an expansion tank, and see expansion tank manufacturer’s instructions for suggestions.

Do not thread a cap or plug into the relief valve under any circumstances! Explosion and property damage, serious injury, or death may result.

To avoid water damage or scalding due to relief valve operation:

Discharge line must be connected to relief valve outlet and run to a safe place of disposal. Terminate the discharge line in a manner that will prevent possibility of severe burns or property damage should the relief valve discharge.

Discharge line must be as short as possible and the same size as the valve discharge connection throughout its entire length.

Discharge lin e must pitch downward from the valve and terminate at least 6” above the floor drain, making discharge clearly visible.

The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375

Do not pipe discharge to any location where freezing could occur. o

F or greater.

No valve may be installed between the relief valve and heater or in the discharge line. Do not plug or place any obstruction in the discharge line.

Test the operation of the relief valve after filling and pressurizing the system by lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, immediately replace with a new properly rated relief valve.

Test T&P valve at least once annually to ensure the waterway is clear

. If valve does not operate, turn the heater “off” and call

a plumber immediately.

Take care whenever operating relief valve to avoid scalding injury or property damage.

FAILURE TO COMPLY WITH THE ABOVE GUIDELINES COULD RESULT IN FAILURE OF RELIEF VALVE OPERATION,

RESULTING IN POSSIBILITY OF SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR DEATH.

RE-INSPECTION OF T&P RELIEF VALVES: T&P valves should be inspected AT LEAST ONCE EVERY THREE YEARS, and

replaced, if necessary, by a licensed plumbing contractor or qualified service technician, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally.

Certain naturally occurring conditions may corrode the valve and its components over time, rendering the valve inoperative. Such conditions can only be detected if the valve and its components are physically removed and inspected. Do not attempt to conduct an

inspection on your own. Contact your plumbing contractor for a re-inspection to assure continued safety.

FAILURE TO RE-INSPECT THIS VALVE AS DIRECTED COULD RESULT IN UNSAFE TEMPERATURE AND/OR PRESSURE

BUILDUP WHICH CAN RESULT IN SEVERE PROPERTY DAMAGE, SERIOUS PERSONAL INJURY, OR DEATH.

E. SCALDING

An ASSE 1017 or ASSE 1070 temperature limiting or mixing valve is recommended in installations servicing disabled or elderly persons, or children. Mixing valves do not eliminate the risk of scalding.

To avoid scalding:

Set the water heater set point temperature as low as possible.

Feel water before bathing or showering.

If thermostatic valves are required, use devices specifically designed for such purpose. Install these devices in accordance with instructions provided by the manufacturer.

Failure to install a temperature limiting or mixing valve and follow these instructions could result in property damage, or severe personal injury or death due to scalds.

This water heater can deliver scalding water. Be careful whenever using hot water to avoid scalding injury.

Certain appliances, such as dishwashers and automatic clothes washers may require increased water temperature. By setting the thermostat on this heater to obtain the increased water temperature required by these appliances, you may create the potential for scald injury.

To protect against injury, you should install a mixing valve in the water system. This valve will reduce point of

APPROXIMATE TIME / TEMPERATURE RELATIONSHIPS IN SCALDS

120 o

F More than 5 minutes

Table 6

125 o

130 o

F

F

135 o

F

140 o

F

145 o

150 o

F

F

155 o

F

1 ½ to 2 minutes

About 30 seconds

About 10 seconds

Less than 5 seconds

Less than 3 seconds

About 1 ½ seconds

About 1 second

LP-83 Rev. 8.14.14

13 discharge temperature by mixing cold and hot water in branch supply lines. Such valves are available from your local plumbing supplier.

Table 6 details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the

safest water temperature for your applications.

F. POTABLE EXPANSION TANK

A potable hot water expansion tank may be required to offset heated water expansion. If there is a back flow preventer or any other type of no return or check valve on the system, a thermal expansion tank is mandatory. The expansion tank must be sized for the entire water volume of the hot water system. A weeping relief valve indicates the need for an expansion tank. See Typical Expansion Tank installation, Fig. 4, for more details.

G. PRESSURE DROP SIZING FOR CIRCULATOR

The boiler circulator flow rate must meet the requirements found in Figure 1 or the published ratings cannot be achieved. The flow chart below represents the pipe run, water heater, and heat exchanger ONLY and does not include any flow checks, zone valves, or friction loss through the boiler. That resistance must be added to the value found in the chart below.

PIPE SIZE

PRESSURE DROP FOR PIPE

LENGTH OF 1” COPPER, SIX 90 o

20’ 30’ 40’

ELBOWS, AND ONE TEE

50’ 60’

6 GPM

7 GPM

10 GPM

12 GPM

14 GPM

14 GPM

8.63

11.3

10.25

11.3

8.93

11.77

11.1

13.2

9.23

12.24

11.95

14.1

9.53

12.7

12.8

15

9.8

13.1

13.66

16

19.8

19.8

PIPE SIZE

20 GPM

22 GPM

24 GPM

28 GPM

15.3 16.4 17.5 18.6

15.3 16.4 17.5

PRESSURE DROP FOR PIPE LENGTH OF 1 ¼” COPPER, TEN 90 o

18.6

ELBOWS, AND TWO TEES

20’ 30’ 40’ 50’

10.9

14

16.2

20.4

11.7

15

17.5

22

12.6

16

18.8

23.6

13.4

17

20.1

25.2

60’

14.3

18

21.5

26.8

Table 7

LP-83 Rev. 8.14.14

14

H. PIPING

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In

Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

Figure 4 - Typical Mixing Valve Installation

LP-83 Rev. 8.14.14

15

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248

CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See

Part 3, Section E for more information.

Figure 5 – Typical Expansion Tank Application

LP-83 Rev. 8.14.14

16

Figure 6 – Zoning with Zone Valves

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

LP-83 Rev. 8.14.14

17

Figure 7 – Zoning with Circulators

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

LP-83 Rev. 8.14.14

18

Figure 8 – Typical Installation with Storage Tank

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

LP-83 Rev. 8.14.14

19

Figure 9

– Typical Installation with High Efficiency Boiler

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

LP-83 Rev. 8.14.14

Figure 10

– Typical Dual Purpose Application w/ Wood Boiler

20

Figure 11

– Typical Dual Purpose Application

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In

Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

7. On multiple source applications, use a Honeywell L4081-A-1148, which has (2) limit settings. This allows the wood stove to operate on the tank high setting, and the tank low limit setting for conventional boiler back-up.

LP-83 Rev. 8.14.14

Figure 12

– Dual Purpose Application with Wood Stove

21

Figure 13 – Dual Purpose Application with Solar Panel

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In

Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

7. On multiple source applications, use a Honeywell L4081-A-1148, which has (2) limit settings. This allows the wood stove to operate on the tank high setting, and the tank low limit setting for conventional boiler back-up.

LP-83 Rev. 8.14.14

22

Figure 14

– Typical Steam Boiler -

NOTE: On Typical Steam Boiler applications, the SSU indirect heat exchanger supply and return connections must be below the water line from the boiler connection. The internal flow check or spring check must be used to avoid thermal siphoning from the connected boiler. A basket strainer should also be used to avoid sludge and sediment getting into the pump or heat exchanger.

Figure 15 – Live Steam Installation -

NOTE: Live Steam Installations are allowed with 80 and 119 gallon SSU/SSU-C models ONLY.

LP-83 Rev. 8.14.14

23

Figure 16 – Typical Multiple Tank Installation

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.

2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet.

3. All circulators should have an integral flow check.

4. Drains and check valve between unit and storage tank will assist in purging air from system.

5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In

Massachusetts, you must install a vacuum relief valve per 248 CMR.

6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

7. All piping in parallel used for large dumps of hot water, high usage, short duration.

8. Massachusetts requires a limit of (4) tanks per mechanical room. Consult with your local inspector.

PART 4 – HEATER CONTROL AND WIRING

A. CONTROL

Install control element into well and tighten in place with screws on control body. Thermal conductive paste is recommended. Once the control is operational, it is very important to make sure the control is maintaining the desired operating temperature.

B. WIRING

Wiring is to be done in accordance with all applicable local and state codes. Turn off all power related to the boiler starting and wiring procedures. It is recommended that a disconnect switch be installed between the boiler control and water heater.

LP-83 Rev. 8.14.14

24

When wiring the water heater and controls, be sure to label all wires for ease of future maintenance. Wiring errors can cause improper and dangerous operation.

C. WIRING DIAGRAMS

Figure 17

– Wiring with Circulators

Figure 18

– Wiring with Zone Valves

LP-83 Rev. 8.14.14

25

ZONING WITH CIRCULATORS – 4845 RELAY

Figure 19 – Zoning with Circulators – 4845 Relay

ZONING WITH CIRCULATORS USING R8182D AND DPST – NO RELAY REQUIRED

Figure 20

– Zoning With Circulators Using R8182D and DPST – No Relay Required

LP-83 Rev. 8.14.14

ZONING WITH CIRCULATORS USING L8124 A, C, AND R845A RELAY

26

Figure 21

– Zoning with Circulators Using L8124 A, C, and R845A Relay

ZONING WITH CIRCULATORS USING L8124 E, F, AND DPST CONTROL – NO RELAY REQUIRED

Figure 22 – Zoning with Circulators Using L8124 E, F, and DPST Control – No Relay Required

LP-83 Rev. 8.14.14

ZONING WITH CIRCULATORS – R182D AND R845A RELAY

27

Figure 23 – Zoning with Circulators – R182D and R845A Relay

CONTROL WITH BUILT-IN DPST SWITCH – NO RELAY REQUIRED

Figure 24 – Control with Built-In DPST Switch – No Relay Required

LP-83 Rev. 8.14.14

ZONING WITH CIRCULATORS USING L8124 A, C, AND R845A RELAY

28

Figure 25 – Zoning with Circulators Using L8124 A, C, and R845A Relay

ZONING WITH CIRCULATORS USING L8124 A, C, AND DPST – NO RELAY REQUIRED

Figure 26 – Zoning with Circulators Using L8124 A, C, and DPST – No Relay Required

LP-83 Rev. 8.14.14

USING L8148A OR L8152A COLD START BOILER CONTROL WITH CIRCULATORS

29

Figure 27 – Using L8148A or L8152A Cold Start Boiler Control with Circulators

PRIORITY ZONE WITH CIRCULATORS

Figure 28

– Priority Zone with Circulators

LP-83 Rev. 8.14.14

USING L8148A OR L8152A COLD START BOILER CONTROL WITH ZONE VALVES

30

Figure 29 – Using L8148A or L8152A Cold Start Boiler Control with Zone Valves

PRIORITY ZONE WITH ZONE VALVES

Figure 30 – Priority Zone with Zone Valves

LP-83 Rev. 8.14.14

31

PART 5 – START-UP AND OPERATION

1. Fill the water heater by opening the cold water shut-off valve. Purge air from the system by opening a hot water outlet at a fixture in a kitchen or bathroom. When water flows freely from the outlet, the system is purged.

2. Check the system for leaks.

Fix any leaks before continuing the installation. Any leaks can result in serious property damage and personal injury.

3. After ensuring there are no leaks within the system, flush the system to clear any soldering residue. Many soldering fluxes contain Zinc Chloride, which can corrode stainless steel.

Draw at least three times the volume of the water heater to properly flush the system.

4. Initiate a call for hot water. Ensure each zone valve or circulator operates only when its thermostat calls for heat. Purge each zone of air to ensure proper operation.

5. Set the water heater to the desired temperature. Boiler high limit should be set at least

20 o

F higher than the heater temperature. Set the low limit of the boiler control at the minimum setting – this will call the burner on only to satisfy the tank control.

We recommend a water heater temperature setting of 120 o

F. However, a lower temperature setting may be required to comply with local and state codes for normal operation. The differential should be set at 10 o

to 15 o

F. You may prefer a setting of either higher or lower water temperature. A mixing valve in conjunction with a high temperature setting may be used for high demand applications (spas, hot tubs, whirlpools).

6. When the system is completely flushed, purged of air, and the temperature is set, turn on the boiler. Observe operation. Ensure the boiler shuts down after the indirect water heater set point is satisfied.

If draining of the heater is necessary, open the temperature and pressure valve or a hot water tap to prevent vacuum buildup in the tank and piping.

Risk of scald injury increases as you increase water temperature.

LP-83 Rev. 8.14.14

32

Figure 31

–Parts

MODEL

SSU-20

SSU-30

SSU-30LB

SSU-45

SSU-60

SSU-80

SSU-119

SSU-45C

SSU-60C

SSU-80C

SSU-119C

SSU-45DW

SSU-60DW

SSU-80DW

SSU-119DW

Table 8 – Replacement Parts

#1 – T&P RELIEF VALVE

TP1500 (Not Included)

TP1500 (Not Included)

TP1500 (Not Included)

TP1500 (Not Included)

TP1500 (Not Included)

TP1400 (Included)

TP1400 (Included)

TP1400 (Included)

TP1400 (Included)

TP1400 (Included)

TP1400 (Included)

TP1500 (Not Included)

TP1500 (Not Included)

TP1500 (Not Included)

TP1500 (Not Included)

#2 – CONTROL WELL

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

PMW-3SENP-1

LP-83 Rev. 8.14.14

33

PART 6 – MAINTENANCE AND TROUBLESHOOTING

Periodic maintenance should be performed by a qualified service technician to assure that all the equipment is operating safely and efficiently. The owner should make necessary arrangements with a qualified heating contractor for periodic maintenance of the heater.

Installer must also inform the owner that the lack of proper care and maintenance of the heater may result in a hazardous condition.

INSPECTION ACTIVITIES

PIPING

Near heater piping Check heater and system piping for any sign of leakage; make sure pipes are properly supported.

SYSTEM

Visual

Functional

Temperatures

Do a full visual inspection of all system components. Ensure all components (including boilers, water treatment systems, mixing valves, circulators, etc.) are operating properly and have been maintained.

Test all functions of the system. Perform any maintenance required by local codes. Verify system pressure is in the safe operating range.

Check control for temperature accuracy.

*In installed in system - verify safe settings on Mixing Valve.

ELECTRICAL

Smoke and CO detector

Circuit Breakers

Connections Check wire connections. Make sure they are tight.

RELIEF AND DRAIN VALVE

Relief Valve

Drain Valve

Lift and release the relief valve on the water heater. Make certain that the valve operates properly by allowing several gallons to flush through the discharge line. Replace if valve is blocked or does not operate properly.

NOTE: DISCHARGED WATER MAY PRESENT A SCALD

RISK. TAKE CAUTION WHEN OPERATING RELIEF

VALVE.

Open the drain valve and drain a few quarts of water from the bottom of the tank to flush any hard water deposits. Replace if valve is blocked or does not operate properly.

NOTE: DRAINED WATER MAY PRESENT A SCALD RISK.

TAKE CAUTION WHEN OPERATING DRAIN VALVE.

FINAL INSPECTION

Check for combustible materials

*Verify devices are installed and working properly. Change batteries if necessary.

Check to see that the circuit breaker is clearly labeled.

Exercise circuit breaker.

Check list

Check area around heater for combustible materials, such as gasoline or paint thinner. If combustible materials are found, move away from the heater to a safe location.

Verify that you have completed entire check list. WARNING:

FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY

OR DEATH

Homeowner Review what you have done with the homeowner.

INITIAL AND DATE AFTER INSPECTION/SERVICE. CONTINUE INSPECTIONS ON

ANNUALLY BEYOND THE FOURTH YEAR.

1 st

YEAR

DATE LAST COMPLETED

2 nd

YEAR 3 rd

YEAR 4 th

YEAR*

Table 9 - *If applicable to system.

LP-83 Rev. 8.14.14

PROBLEM

Zone valve not opening

Circulator not operating

Tank control set too low

Boiler control set too low

Wiring incorrect

Tank control failure

Zone valve failure

Circulator failure

Air trap in loop

TROUBLESHOOTING

NO HOT WATER

POSSIBLE SOLUTION

Open manually to replace.

Check or replace

Raise tank temperature* (SEE NOTE BELOW)

Raise boiler temperature

Recheck wiring

Replace control

Replace valve

Replace circulator

Purge air

NOT ENOUGH HOT WATER

POSSIBLE SOLUTION

1” full bore replace zone valve

Reverse circulator

PROBLEM

Zone valve restriction

Circulator arrow reversed

Tank temperature too low

Boiler temperature too low

Boiler sized too small

Tank sized too small

Demand flow rate too high

Air trap in loop

Raise tank temperature* (SEE NOTE BELOW)

Raise boiler temperature

Check sizing chart

Check sizing chart

Install mixing valve, raise tank temperature*

Purge to remove air

Install flow regulator

Heat and tank come on together

Not enough space heat

Slow recovery

Recheck wiring or set indirect as priority over central heating.

Draw tank down and lower thermostat. Recheck.

Boiler sized too small. Consult chart.

Circulator head capacity too low

T & P VALVE DISCHARGES

POSSIBLE SOLUTION

Lower temperature on tank

PROBLEM

Tank temperature too high

Water expands when heated

Water pressure too high

Install expansion tank

Install pressure reducing valve

PROBLEM

HOT TUBS, SPAS, MULTIPLE SHOWERS, HIGH DEMAND

POSSIBLE SOLUTION

Pressure too low

Recovery of tank slow

Check line pressure for restriction

Slow startup boiler. See chart.

Boiler sized too small. See chart.

Check flow rate and compare to chart

Not enough hot water Demand too great. Check flow rates and compare to chart. Install mixing valve and/or flow restricting valve and raise tank and boiler temperature*.

Table 10 - *See scald warning below.

34

When raising tank temperature, the risk of scald injury increases. To avoid scald injury, use a water tempering or mixing valve and extreme caution when using hot water. Consult codes for conformance.

LP-83 Rev. 8.14.14

35

HTP CUSTOMER INSTALLATION RECORD FORM

The following form should be completed by the installer for you to keep as a record of the installation in case of a warranty claim. After reading the important notes at the bottom of the page, please also sign this document.

Customer’s Name:

Installation Address:

Date of Installation:

Installer’s Code/Name:

Product Serial Number(s):

Comments:

Installer’s Phone Number:

Signed by Installer:

Signed by Customer:

IMPORTANT:

Customer: Please only sign after the installer has reviewed the installation, safety, proper operation, and maintenance of the system. In the case that the system has any problems, please call the installer. If you are unable to make contact, please contact your HTP Sales Representative.

Distributor/Dealer: Please insert contact details.

LP-83 Rev. 8.14.14